REPUBLIC OF THE PHILIPPINES

OFFICE OF THE BUILDING OFFICIAL GENERAL NOTES:

B

A

ALL ELECTRICAL WORKS HEREIN SHALL BE DONE IN ACCORDANCE WITH THE PROVISION OF THE LATEST APPROVE EDITION OF THE PHILIPPINE ELECTRICAL CODE, THE LAWS AND ORDINANCES OF THE LOCAL CODE ENFORCING AUTHORITIES AND REQUIREMENTS OF THE LOCAL POWER AND TELEPHONE COMPANY. 1. SERVICE POWER SHALL BE 230V, SINGLE PHASE, 2-WIRES WITH GROUND, 60Hz SYSTEM.

A

B

C

D

C

D

E

E District/City/Municipality

WCO

t

PARENT'S BEDROOM

1

CO

WH

1

3. SMALLEST BRANCH CIRCUIT WIRE SHALL BE 3.5mm² THHN FOR LIGHTING AND POWER SYSTEM, UNLESS OTHERWISE STATED IN THE PLAN, IN RACEWAY 15mm TRADE SIZE CONDUIT, WIRE SHALL BE INSULATED FOR 600 VOLTS.

T&B-1

WCO

2

CO

CO

HALLWAY CO

CO

LP-7

KITCHEN

LP-18 CO

6. ALL FLUORESCENT LAMP SHALL BE PRE-HEAT TYPE, WITH HIGH POWER FACTOR BALLAST, CAPACITOR AND SPRING LOADED LAMP HOLDERS.

CO

Sb Sg

3

S3Wg

CO

m

7. ALL LIGHT-CONTROLLED SWITCHES SHALL BE RATED 15 AMPS, 220 VOLTS AC ONLY, SWITCHES SHALL BE INSTALLED FOR WITH HORIZONTAL MOTION.

m

LIVING AREA

LIVING AREA

KITCHEN

LP-2

Srs Spq

p

k

DINNING AREA

u

PORCH

Skl

LP-1

S3Wmn

LP-4

DINNING AREA

b

g

CO CO

c

Sa

2

CO

CO

HANNAH'S BEDROOM

S3e

HANNAH'S BEDROOM

CO

RA

3

5. WHENEVER NECESSARY PULLBOX OF PROPER SIZE AND DIMENSION SHALL BE PROVIDED ALTHOUGH NOT INDICATED IN THE PLAN. ALL JUNCTION BOXES SHALL BE PROVIDED WITH METAL PLATE COVER.

CO

CO

S3e

a

CO

4. ALL BRANCH CIRCUIT HOMERUN SHALL BE INSTALLED AS INDICATED IN THE PLAN. EXPOSED CIRCUIT RUN SHALL BE PARALLEL TO OR PERPENDICULAR WITH THE BUILDING LINE AND SUPPORTED BY CONDUIT CLAMPS EVERY 1.5 METERS. DIAGONAL CONDUIT RUN SHALL NOT BE ACCEPTED.

Sc

e

PARENT'S BEDROOM

W.I.C.

CO

LP-11

W.I.C.

T&B-1

CO

CO

CO

CO

WCO

2. WIRINR METHOD SHALL BE DONE IN PVC CONDUIT FOR LIGHTING, POWER, TELEPHONE AND AUXILIARY SYSTEM UNLESS OTHERWISE INDICATED IN THE PLAN.

r

PORCH

g

q

LP-5 LP-6

4 LP-13

BEDROOM 1

CO

CO

BEDROOM 1

LP-12

5

LP-3

S3Wg

HALLWAY

6

a. LIGHT-CONTROLLED SWITCHES ---------- 1.40 M. ABOVE FLOOR FINISH AT CENTER b. DUPLEX CONVENIENCE OUTLET ---------- 0.30 M. ABOVE FLOOR FINISH AT CENTER c. TELEPHONE OUTLET --------------------------- 0.30 M. ABOVE FLOOR FINISH AT CENTER d. PANELBOARDS ----------------------------------- 1.40 M. ABOVE FLOOR FINISH AT CENTER UNLESS OTHERWISE INDICATED BY THE FIELD CONDITIONS.

Se Sm m

d m

T&B-2

u CO

13. MOUNTING HEIGHT NOT SHOWN ON SCHEDULE ARE AS FOLLOWS:

BEDROOM 2

BEDROOM 3

a

Sd Su

BEDROOM 3

CO

CO

CO

12. ALL RECEPTACLE OUTLET SHALL BE PROPERLY GROUNDED TO THE BOX BY MEANS OF GROUNDING LUGS.

p

Sa

WH

11. ALL BOXES SHELL BE MADE OF CODE GAUGE STEEL WITH ZINC CHROMATE PROTECTION.

LP

CO

CO

l

S3Wmn

4

HALLWAY LP-9

WCO

5

CO CO CO CO

CO

LP-6

CO

10. ALL MATERIALS TO BE USED SHALL BE NEW AND APPROVED TYPE FOR THE LOCATION AND PURPOSES.

PB

CO

9. ALL METALLIC CONDUIT, CABINET, BOXES AND EQUIPMENT SHALL BE PROPERLY GROUNDED AND BONDED.

CO

n

Stuv

WCO

CO

n

LP-8

CO

8. ALL PANELBOARD SHALL BE PROVIDED WITH SOLID GROUNDING BUS WITH TERMINALS.

BEDROOM 2

6

CO

v

s

WCO

14. THE ELECTRICAL CONTRACTOR SHALL SECURE ALL WIRING PERMITS AND ALL FEES REQUIRED FOR THE WORK AND SHALL FURNISH THE OWNER THROUGH THE ENGINEERS FINAL CERTIFICATES OF ELECTRICAL INSPECTION AND APPROVAL FROM PROPER GOVERNMENT AUTHORITIES FOR COMPLETE WORK.

1 CONVENIENCE OUTLET LAYOUT A-2 E-1

2 LIGHTING LAYOUT

1 : 100

A-2 E-1

15. THE ELECTRICAL CONTRACTOR SHALL REFER TO ARCHITECTURAL DRAWING FOR THE EXACT LOCATION AND MOUNTING HEIGHT OF ALL VISIBLE WIRING DEVICES, FIXTURES AND THE LIKES.

A

B

C

D

1 : 100

E

16. ALL ELECTRICAL WORKS HEREIN SHALL BE DONE UNDER THE DIRECT AND IMMEDIATE SUPERVISION OF A DULY QUALIFIED LICENSED ELECTRICAL ENGINEER OR MATER ELECTRICIAN. ALL MOUNTING HEIGHTS ARE SUBJECT TO THE APPROVAL OF THE ARCHITECT/OWNER.

1 TEL

T&B-1

W.I.C.

CA

PARENT'S BEDROOM

2

HANNAH'S BEDROOM

CTB

TEL

CA

LEGEND:

TTB

3

CTB

ELECTRICAL FIXTURES LEGEND

RCP LEGEND

CO

PL

CONVENIENCE OUTLET

PINLIGHT WCO

KITCHEN

WEATHERPROOF OUTLET ONE-GANG SNAP SWITCH

Sa

DINNING AREA

RA

LIVING AREA

RANGE OUTLET

PORCH

REF

Sabc

REFRIGERATOR OUTLET

CTB

TEL

CTB

TELEPHONE OUTLET

THREE-GANG SNAP SWITCH

CTB

4

CA

CABLE TV OUTLET

TWO-WAY SNAP SWITCH

LIGHT AND POWER PANEL TTB

POWER LINE

CTB

5

TELEPHONE TERMINAL BOIX

TTB CTB

BEDROOM 1

CA

BEDROOM 3

TEL

CATV TERMINAL BOX

BEDROOM 2 LIGHTING WIRE LINE

T&B-2 TEL

6

CIRCUIT BREAKER

CTB

CA

GROUNDINGS ENTRANCE

3 AUXILIARY LAYOUT A-2 E-1

SEAL

ENGR. PASCUAL P. FERRER PROFESSIONAL ELECTRICAL ENGINEER ENGINEER

ADDRESS

PRC No.:

2757

PTR No.:

1598261

Date:

JAN. 02, 2014

Place:

PAKIL, LAGUNA

REPUBLIC ACT 9266 SEC. 33 THESE DRAWINGS AND SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS, DULY SIGNED, STAMPED OR SEALED AS INSTRUMENT OF SERVICE, ARE INTELLECTUAL PROPERTY AND DOCUMENTS OF THE ARCHITECT, WETHER THE OBJECT FROM WHICH THEY ARE MADE EXECUTED OR NOT, IT SHALL BE UNLAWFUL FOR ANY PERSONS TO DUPLICATE OR TO MAKE COPIES OF SAID DOCUMENTS FOR USE IN THE REPETITION OF AND FOR OTHER PROJECTS OR BUILDING, EXECUTED PARTLY OR IN WHOLE WITHOUT THE WRITTEN CONSENT OF ARCHITECT OR AUTHOR OF SAID DOCUMENTS

1 : 100

PROJECT & LOCATION:

OWNER:

SHEET CONTENTS:

PROPOSED:

FABILA RESIDENCE LOT 152, LO-ONG, CONCEPCION, ILOILO PROVINCE

MS. HANNAH MAE C. FABILA

SHEET NO.:

LIGHTING, CONV. OUTLET, & AUXILIARY LAYOUT, GENERAL NOTES, & LEGEND

DRAWN:

CHECKED:

DATE:

02/05/14

E-1 PROJ. NO.:

0011

FOR BUILDING PERMIT

SW

TEL CA

TO TELEPHONE SERVICE ENTRANCE

CA LP

TO CATV SERVICE ENTRANCE

TTC

02/05/14

TWO-GANG SNAP SWITCH

Sab

L1

REPUBLIC OF THE PHILIPPINES

L2

OFFICE OF THE BUILDING OFFICIAL

LOAD SCHEDULE AND COMPUTATION MAIN:

PANEL: LP MOUNTING: FLUSH MOUNTED LOCATION: KITCHEN

100AT, 2P, 230V, 60HZ. CKT. BREAKER IN NEMA 1 ENCLOSE 2 - 30mm² THHN & 1 - 8.0mm² TW GND. WIRE IN 1 - 25mm DIA. RSC / 32mm DIA. PVC PIPE

USE:

2P, 100AT 2P,15AT

CRK. BREAKER CKT. NO

DESCRIPTION

VOLT

VA

AMP P

AT

AF

SIZE OF CONDUCTOR

SIZE OF CONDUIT

1

LIGHTING OUTLETS (HANNA'S/T&B/PARENT'S

230

250

1.09

2

15

50

2 - 3.5 mm² THHN & 1 - 2.0 mm² TW GND

20mm Ø PVC

2

LIGHTING OUTLETS (LIVING/DINING/PORCH

230

400

1.74

2

15

50

2 - 3.5 mm² THHN & 1 - 2.0 mm² TW GND

20mm Ø PVC

3

LIGHTING OUTLETS (GUEST/BEDROOM 1&2/T&B)

230

250

1.09

2

15

50

2 - 3.5 mm² THHN & 1 - 2.0 mm² TW GND

20mm Ø PVC

4

LIGHTING OUTLETS (KITCHEN/LAUNDRY/UTILITY)

230

350

1.52

2

15

50

2 - 3.5 mm² THHN & 1 - 2.0 mm² TW GND

20mm Ø PVC

5

CONVENIENCE OUTLETS (KITCHEN)

230

540

2.35

2

20

50

2 - 3.5 mm² THHN & 1 - 3.5 mm² TW GND

20mm Ø PVC

6

CONVENIENCE OUTLETS (KITCHEN)

230

720

3.13

2

20

50

2 - 3.5 mm² THHN & 1 - 3.5 mm² TW GND

20mm Ø PVC

7

CONVENIENCE OUTLETS (HANNA'S/T&B/PARENTS)

230

2160

9.39

2

20

50

2 - 3.5 mm² THHN & 1 - 3.5 mm² TW GND

20mm Ø PVC

8

CONVENIENCE OUTLETS (LIVING/DINING)

230

2160

9.39

2

20

50

2 - 3.5 mm² THHN & 1 - 3.5 mm² TW GND

20mm Ø PVC

9

CONVENIENCE OUTLETS (BEDROOM 2/T&B)

230

1080

4.70

2

20

50

2 - 3.5 mm² THHN & 1 - 3.5 mm² TW GND

20mm Ø PVC

10

CONVENIENCE OUTLETS (BEDROOM 1/GUEST)

230

1440

6.26

2

20

50

2 - 3.5 mm² THHN & 1 - 3.5 mm² TW GND

20mm Ø PVC

11

WATER HEATER 1 (T&B)

230

3000

13.04

2

30

50

2 - 3.5 mm² THHN & 1 - 3.5 mm² TW GND

20mm Ø PVC

12

WATER HEATER 2 (BEDROOM 2)

230

3000

13.04

2

30

50

2 - 5.5 mm² THHN & 1 - 5.5 mm² TW GND

20mm Ø PVC

13

ACU 0.75 HP (BEDROOM 1)

230

720

3.13

2

20

50

2 - 5.5 mm² THHN & 1 - 5.5 mm² TW GND

20mm Ø PVC

14

ACU 0.75 HP (BEDROOM 2)

230

720

3.13

2

20

50

2 - 3.5 mm² THHN & 1 - 3.5 mm² TW GND

20mm Ø PVC

15

ACU 0.75 1 HPHP (HANNA'S (GUESTROOM) ROOM)

230

720

3.13

2

20

50

2 - 3.5 mm² THHN & 1 - 3.5 mm² TW GND

20mm Ø PVC

16

ACU 0.75 HP (PARENT'S ROOM)

230

720

3.13

2

20

50

2 - 3.5 mm² THHN & 1 - 3.5 mm² TW GND

20mm Ø PVC

17

ACU 1 HP (HANNA'S ROOM)

230

950

4.13

2

20

50

2 - 3.5 mm² THHN & 1 -3.5 mm² TW GND

20mm Ø PVC

18

ELECTRIC RANGE (KITCHEN)

230

2680

11.65

2

30

50

2 - 5.5 mm² THHN & 1 - 5.5 mm² TW GND

20mm Ø PVC

19

CONVENIENCE OUTLETS (LAUNDRY AREA/UTILITY)

230

360

1.56

2

20

50

2 - 3.5 mm² THHN & 1 - 3.5 mm² TW GND

20mm Ø PVC

20

SPARE

230

2

15

50

------------

20mm Ø PVC

21

SPARE

230

2

20

50

------------

20mm Ø PVC

22

SPARE

230

2

30

50

------------

20mm Ø PVC

LIGHTING OUTLETS (HANNA'S/T&B/PARENT'S

1 2P,15AT

LIGHTING OUTLETS (GUEST/BEDROOM 1&2/T&B)

TOTAL

22220

CONVENIENCE OUTLETS (HANNA'S/T&B/PARENTS)

CONVENIENCE OUTLETS (BEDROOM 2/T&B)

WATER HEATER 1 (T&B)

ACU 0.75 HP (BEDROOM 1)

ACU 0.75 HP (GUEST ROOM)

ACU 1 HP (HANNA'S ROOM)

8

CONVENIENCE OUTLETS (LIVING/DINING)

10

CONVENIENCE OUTLETS (BEDROOM 1/GUEST)

12

WATER HEATER 2 (BEDROOM 2)

14

ACU 0.75 HP (BEDROOM 2)

16

ACU 0.75 HP (PARENT'S ROOM)

18

ELECTRIC RANGE (KITCHEN)

20

SPARE

22

SPARE

2P,30AT

17 2P,20AT

CONVENIENCE OUTLETS (KITCHEN)

2P,20AT

15 2P,20AT

6

2P,20AT

13 2P,20AT

LIGHTING OUTLETS (KITCHEN/LAUNDRY/UTILITY)

2P,30AT

11 2P,20AT

4

2P,20AT

9 2P,30AT

LIGHTING OUTLETS (LIVING/DINING/PORCH

2P,20AT

7 2P,20AT

2

2P,20AT

5 2P,20AT

District/City/Municipality

2P,15AT

3 2P,20AT

CONVENIENCE OUTLETS (KITCHEN)

2P,15AT

2P,15AT

96.61

CONVENIENCE OUTLETS (LAUNDRY AREA/UTILITY)

LP = (96.61 A x 0.80 DF) + (1.5 x 4.13 A) = 83.84 A (USE 100ATAFCB)

19 2P,20AT

ILp= (96.61A x 0.80DF) +1.5 x4.13A = 83.84A Use 100AT100AFCB

SPARE

2P,30AT

21

POWER SERVICE ENTRANCE 1 DIA. 2 WIRE + GROUND, 230 VAC, 60 HZ

2 - 30 MM THHN COPPER & 1 - 8.0 MM TW COPPER IN 1 - 25 MM DIA. PVC

PANEL LP (KITCHEN)

1 PANEL DETAIL (LP) E-2

02/05/14

KILOWATT - HOUR METER

1700 (VERIFY)

M

NTS

2 - 30 MM THHN COPPER & 1 - 8.0 MM TW COPPER IN 1 - 32 MM DIA. PVC

2 POWER SINGLE LINE DIAGRAM E-2

NTS

SEAL

ENGR. PASCUAL P. FERRER PROFESSIONAL ELECTRICAL ENGINEER ENGINEER

ADDRESS

PRC No.:

2757

PTR No.:

1598261

Date:

JAN. 02, 2014

Place:

PAKIL, LAGUNA

REPUBLIC ACT 9266 SEC. 33 THESE DRAWINGS AND SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS, DULY SIGNED, STAMPED OR SEALED AS INSTRUMENT OF SERVICE, ARE INTELLECTUAL PROPERTY AND DOCUMENTS OF THE ARCHITECT, WETHER THE OBJECT FROM WHICH THEY ARE MADE EXECUTED OR NOT, IT SHALL BE UNLAWFUL FOR ANY PERSONS TO DUPLICATE OR TO MAKE COPIES OF SAID DOCUMENTS FOR USE IN THE REPETITION OF AND FOR OTHER PROJECTS OR BUILDING, EXECUTED PARTLY OR IN WHOLE WITHOUT THE WRITTEN CONSENT OF ARCHITECT OR AUTHOR OF SAID DOCUMENTS

PROJECT & LOCATION:

OWNER:

SHEET CONTENTS:

PROPOSED:

FABILA RESIDENCE LOT 152, LO-ONG, CONCEPCION, ILOILO PROVINCE

MS. HANNAH MAE C. FABILA

SHEET NO.:

SCHEDULE OF LOAD, SIGLE LINE DIAGRAM, & PANEL DETAIL

DRAWN:

CHECKED:

DATE:

02/05/14

E-2 PROJ. NO.:

0011

FOR BUILDING PERMIT