Supplementary Specification to GIS 30-851 Specification for Fire and Gas Detection Rev B02
Revision History History Amendment Date
Revision Number
Amender Initials
Amendment
30-JAN-2015 30-JAN-2015
B01 B01
MGK MGK
No Comments from client. Reformatted to new template. template.
21-NOV-2014
A01
DM
No Comments from IDC
11-NOV-2014
01
DM
First Issue
All previous issues are ar e hereby superseded and are to b be e destroyed. NOTES: Revisions after Rev. A01 are denoted as follows: By a vertical line in the right-hand margin adjacent to the revised text. OR By a triangle symbol for graphics, the revision number being denoted within the symbol positioned adjacent to the revision.
Related Documents and References Document Number
Document Name
GPO-EN-SPE-30851 Rev
GIS 30-851 Specification for Fire and Gas Detection
Supplementary Specification to GIS 30-851 Specification for Fire and Gas Detection Rev B02
1.
Introduction This document is a supplement to the BP GIS 30-851 Specification for Fire and Gas Detection Rev B02 dated 12th of September 2014. The purpose of this document is to identify specific requirements for modifications, deletions and additions to the GIS 30-851 applicable to the West Nile Delta Onshore Gas Development
Project. Where a paragraph in the parent document is required to be amended, modified or deleted, it will be identified in this document. The clauses in Section 2 Supplementary Data outline the specific project requirements to be added, modified or deleted. Paragraphs that are not revised or mentioned in this document remain applicable. Following table describes the intent of the instructions used in this supplement: Instruction
Description
Add
This supplement’ supplement’s s clause to be add added ed to existing GIS GIS’s ’s clause/section.
Modify
This supplement’s clause to substitute existing GIS’s clause/section.
Supplementary Specification to GIS 30-851 Specification for Fire and Gas Detection Rev B02
LED
Light Emitting Diode
LFL
Lower Flammable Limit
MAC
Manual Alarm Callpoint
NEMA
National Electrical Manufacturers Association
NFPA
National Fire Protection Association
NPT
National Pipe Thread
PVC
PolyVinyl Chloride
SS
Stainless Steel
UEL
Upper Explosive Limit
UFL
Upper Flammable Limit
6
General Technical Requirements
6.1 General
Modify 6.1.f. 2. Addressable, using a recognised industry protocol for Fire Detection. Modify 6.1.i. Protocols supported shall be indicated in the instrument data sheets. Delete 6.1.l. 2. NEMA 4X in conformance to NEMA 250 for outdoor use. 6.1.l. 4. NEMA 1 in conformance to NEMA 250 for indoor use.
6.2 Hazardous Area Classification Delete 6.2.a. 4. FM, UL or CSA certification or other NRTL certified device subject to approval by Company responsible engineer. Modify 6.2.b. In order to prevent electrical apparatus, including electronic Fire and Gas Detector instrumentation, from becoming a source of ignition in (potential) gas or dust atmospheres, protective measures shall be taken, based on the hazardous area classification of the particular area in which the electrical apparatus are being installed. For the electrical apparatus with protection type certified for use in explosive atmospheres the appropriate safety documentation shall be provided. All field detectors shall be certified for use in Zone 1, Gas Group IIB, and Temperature Class T3 hazardous area in compliance with the requirements of ATEX directive 94/9/EC. The detector shall bear the relevant hazardous area compliance mark and certificate number for the purposes of traceability. Wherever possible, all field detectors shall be certified explosion proof (Ex d). The hazardous area requirements shall be specified on the detector datasheet.
6.3 Marking Add 6.3.d. In addition to 6.3 a, and b, each field mounted detector shall be identified by a traffolyte nameplate supplied by the Instrument Installation Contractor, giving the tag number and service. This nameplate shall be engraved with minimum of 13mm letters with red / white / red (white lettering on a red background) for Fire & Gas duties, and be fixed to an adjacent permanent structure or purpose made brackets.