Edwards Fire Alarm Equipment

May 29, 2016 | Author: Бахтияр Юмачиков | Category: N/A
Share Embed Donate


Short Description

Fire Alarm...

Description

89024-0010T Issue 1

drawing on the best Job Name 400 City Hall Square Prop Number 38-209-3016-000 Customer Rorison Industrial Electric P.O. Number: E050-5365 August 25, 2010

Life Safety Systems Intelligent Initiating Devices

Overview People detect danger by relating many observations to one another and comparing them to familiar patterns. The simultaneous use of multiple senses allow humans to filter out situations which are not dangerous. The ability to detect danger depends largely on intelligence and knowledge from past experience. GE Security 4D detectors provide both. The SIGA-IPHS Intelligent 4D Multisensor Detector gathers analog information from each of its three fire sensing elements (ionization, photoelectric, and heat) and converts it into digital signals. The detector’s on-board microprocessor measures and analyzes these signals separately with respect to a fourth element - Time. We call this technology 4D. It compares the information to historical readings, time patterns and several known fire characteristics to make an alarm decision. Digital filters remove signal patterns that are not typical of fires. Unwanted alarms are virtually eliminated.

Standard Features • Integrates three sensing technologies Processes and analyzes information from each sensor (ion/photo/heat) separately using dynamic filters then applies a sophisticated algorithm for optimum detection accuracy. • Non-volatile memory Permanently stores serial number, type of device, and job number. Automatically updates historic information including hours of operation, last maintenance date, number of alarms and troubles, time of last alarm1 and analog signal patterns for each sensing element just before last alarm.

• Automatic device mapping Each detector transmits wiring information regarding its location with respect to other devices on the circuit. Detectors installed in the wrong location during cleaning are automatically reported to the loop controller. • Electronic addressing Permanently stores programmable address; there are no switches or dials to set. Addresses are downloaded from a PC, or the SIGA-PRO Signature Program/Service Tool. • Environmental compensation Each sensing element self-compensates for changes in the detector’s installed environment to maintain the sensitivity setting and prevent unwanted alarms. The detector reports when it cannot compensate any further. • Integral microprocessor — Intelligent detector All decisions are made at the detector allowing lower communication speed while substantially improving control panel response time. Less sensitive to line noise and loop wiring properties; twisted or shielded wire is not required. • Wide 0.67 — 3.70%/ft. sensitivity range window Program the detector to operate at any one of five sensitivity settings within the window. • Pre-alarm Detector stores one of 20 pre-alarm sensitivity values to alert local personnel prior to the sensor reaching a full evacuation sensitivity. Sensitivity values can be set in 5% increments.1 Note: Some features described here may not be supported by all control systems. Check your control panel’s Installation and Operation Guide for details.

Intelligent 4D Multisensor Detector SIGA-IPHS

MEA

S

CHINA

Application Notes Available

Data Sheet 85001-0245 Issue 7 Not to be used for installation purposes. Page  of 6

• Identification of dirty or defective detector Self-diagnostic and sensitivity check provides a dirty detector signal. • Automatic day/night sensitivity adjustment Makes detector more sensitive during inactive nighttime periods. • Stand-alone operation The detector makes decisions and inputs an alarm even if the loop controller fails. The detector reverts to an intelligent “conventional” detector when polling interrogation stops. • Stable design Sensitivity remains stable with air velocity up to 500 ft/min (2.53m/sec) making it suitable for direct insertion in low velocity duct applications. • Designed for high ambient temperature operation Install in ambient temperatures up to 100° F (38° C). • Twin status LEDs Flashing GREEN shows normal; flashing RED shows alarm state; steady RED and steady GREEN show alarm state in stand alone mode, visible from any direction. • Standard, relay, fault isolator, and audible mounting bases Four mounting bases provide clamp terminals, allow room side wiring and include an optional tamper-resist feature. • Designed to ISO 9001 standards Manufactured to strict international quality standards for highest reliability.

Signature Series Overview The microprocessor in each detector provides four additional benefits - Self-diagnostics and History Log, Automatic Device Mapping, Stand-alone Operation and Fast, Stable Communication. Self-diagnostics and History Log - Each Signature Series detector constantly runs self-checks to provide important maintenance information. The results of the self-check are automatically updated and permanently stored in the detector’s non-volatile memory. This information is accessible for review any time at the control panel, PC, or by using the SIGA-PRO Signature Program/Service Tool. Automatic Device Mapping - The loop controller learns where each device’s serial number address is installed relative to other devices on the circuit. This mapping feature provides supervision of each device’s installed location to prevent a detector from being reinstalled (after cleaning etc.) in a different location from where it was originally. The history log for the detector remains relevant and intact regardless of its new location. The Signature Series Data Entry Program also uses the mapping feature. With interactive menus and graphic support, the wired circuits between each device can be examined. Layout or “as-built” drawing information showing wire branches (T-taps), device types and their address are stored on disk for printing hard copy. This takes the mystery out of the installation. The preparation of as-built drawings is fast and efficient. Stand-alone Operation - A decentralized alarm decision by the detector is guaranteed. On-board intelligence permits the detector to operate in stand-alone mode. If loop controller CPU communications fail for more than four seconds, all devices on that circuit go

into stand-alone mode. The circuit acts like a conventional alarm receiving circuit. Each detector on the circuit continues to collect and analyze information from its surroundings. The detector alarms if the preset smoke obscuration level is reached or ambient temperature increases by 65oF (35oC). If the detector is mounted to a relay base, the relay operates. Similarly, if it is mounted to an audible base, the on-board horn sounds. Fast Stable Communication - On-board intelligence means less information needs to be sent between the detector and the loop controller. Other than regular supervisory polling response, the detector only needs to communicate with the loop controller when it has something new to report. This provides very fast control panel response time and allows a lower baud rate (speed) to be used for communication on the circuit. Environmental Compensation - Detection sensitivity for the SIGAIPHS is virtually independent of its installed environment and its physical condition. Environmental compensation means each sensing element adapts to long-term changes caused by dirt, humidity, temperature, aging etc. It even compensates for small amounts of normal ambient smoke. Approximately six times every hour, the detector adjusts and updates the sensitivity (% obscuration) and ambient temperature baselines for each sensing element. Signature Series environmental compenstion is so reliable that it meets NFPA72 field sensitivity testing requirements — without the need for external meters. Sensitivity Range - The SIGA-IPHS has a sensitivity range or window of 0.67 - 3.70% obscuration per foot. The installer selects the detector’s ALARM sensitivity level. Five settings ranging from the least sensitive at 3.5% obscuration/ft to the most sensitive at 1.0% obscuration/ft are available. Pre-Alarm - Pre-alarm warnings may alert local staff to a possible fire condition allowing them to investigate before entering into a full alarm condition which requires building evacuation. The 4D multisensor’s wide sensitivity range permits the use of early warning pre-alarm values. The pre-alarm value can be set by the user in 5% increments, allowing up to 20 pre-alarm settings. Automatic Day/Night Sensitivity Selection - Signature Series detectors may be programmed for different sensitivities during day and night periods. This allows the detector to be more sensitive during unoccupied periods when lower ambient background conditions are expected. Stability - The 4D detector’s sensitivity remains stable in wind velocities up to 500 ft/min (2.53 m/sec). Ambient temperature has very little affect on the detector. The detector may be installed in rooms with ambient temperatures up to 100oF (38oC). Status LEDs - Twin LEDs are visible from any direction. A flashing GREEN LED shows normal system polling from the loop controller. A flashing RED LED means the detector is in alarm state. Both LEDs on steady shows alarm state - stand-alone mode. Normal GREEN LED activity is not distracting to building occupants, but can be quickly spotted by a maintenance technician. Electronic Addressing - The loop controller electronically addresses each detector, saving valuable time during system commissioning. Setting complicated switches or dials is not required. Each detector has its own unique serial number stored in its on-board memory. The loop controller identifies each device on the circuit and assigns a “soft” address to that device’s serial number. If desired, detectors can be addressed using the SIGA-PRO Signature Program/Service Tool.

Data Sheet 85001-0245 Issue 7 Not to be used for installation purposes. Page  of 6

Application With intelligent 4D multisensor detectors, unwanted alarms go down to nearly zero and the detection of all types of fire increases to nearly 100%. The European standard DIN EN 54 part 9 describes six standard test fires used to rate the sensitivity of heat, ionization, and photoelectric smoke detectors. No single sensing element is equally suitable for all test fires.

Test Fire Open Wood Wood Pyrolysis Smouldering Cotton Poly Urethane Foam n-Heptane Liquid Fire without Smoke

SIGA-IS Ion optimum suitable very suitable very suitable optimum unsuitable

SIGA-PS Photo unsuitable optimum optimum very suitable very suitable unsuitable

Depending on the type of fire expected in a protected space, the designer usually chooses from three types of sensor technology. Ionization sensors respond well to fast, flaming fires. Photoelectric sensors respond well to smoldering fires, and heat sensors are used as backup or in environmentally poor atmospheres for smoke detection. Agency requirements demand that ionization sensors respond to smoldering fires and that photoelectric sensors respond to flaming fires. This makes single element sensors more prone to false alarms and slow to respond to fires that are difficult for them

The table below shows that the 4D detector is suited for all applications. Normal detector spacing guidelines should be followed. SIGA-IPHS detectors are compatible only with GE Security’s Signature Loop Controller.

SIGA-HRS and SIGAHFS Rate-of-Rise/ Fixed Temp. optimum unsuitable unsuitable suitable very suitable optimum

SIGA-PHS Photo Heat 3D very suitable optimum optimum very suitable optimum very suitable

SIGA-IPHS Ion/Photo/Heat 4D optimum optimum optimum optimum optimum very suitable

to detect. Only when ALL three fire sensing elements — Ionization, Photoelectric and Heat — are suitably combined into one detector can ALL types of fires be effectively detected while virtually eliminating false alarms. When 4D multisensor detectors are installed, a fire alarm system does not have to be altered when the application or the type of “expected” fire changes. The guesswork is removed. The SIGA-IPHS 4D detector is suited for all fire detection applications.

Installation

Data Sheet 85001-0245 Issue 7 Not to be used for installation purposes. Page  of 6

Typical Wiring The detector mounting bases accept #18 AWG (0.75mm2), #16 AWG (1.0mm2), #14 AWG (1.5mm2), and #12 AWG (2.5mm2) wire sizes. Note: Sizes #16 AWG (1.0mm2) and #18 AWG (0.75mm2) are preferred for ease of installation. See Signature Loop Controller catalog sheet for detailed wiring requirement specifications. Standard Detector Base, SIGA-SB, SIGA-SB4

Relay Detector Base, SIGA-RB, SIGA-RB4 Term Description 1 Normally-Open 2 DATA IN/OUT (+) 3 Common 4 DATA IN (-) 5 Not Used 6 Normally-Closed 7 DATA OUT (-)

Term Description 1 Not Used 2 DATA IN/OUT (+) 3 Not Used 4 DATA IN (-) 4 Remote LED (-) 5 Remote LED (+) 6 Not Used 7 DATA OUT (-)

Isolator Detector Base, SIGA-IB, SIGA-IB4 Isolator Detector Base, SIGA-IB, SIGA-IB4 Term Description 1 Not Used 2 DATA IN/OUT (+) 3 DATA IN (-) 4 Not Used 5 Not Used 6 DATA OUT (-) 7 Not Used

Audible Detector Base, SIGA-AB4G

Volume setting

PROPER METHOD FOR T-TAPS

Default = Temporal pattern Cut for steady tone SIG+

SIG-

DATA- DATA- DATA+ OUT IN IN/OUT

To configure output volume or tone, cut the circuit board as shown.

Data in From Signature controller or previous device +

NO

Tone setting

Default = High volume Cut for low volume

24 Vdc in From power supply or + previous base

YES

CONTACT RATING 1.0 Amp @ 30 VDC (Pilot Duty)

-

24 Vdc out

+ To next base or EOL relay -

Data out

+ To next Signature device

NO

TO T-TAPPED DEVICE

TO NEXT DEVICE

FROM PREVIOUS DEVICE TERMINAL STRIP JUNCTION BOX

Data Sheet 85001-0245 Issue 7 Not to be used for installation purposes. Page  of 6

Warnings and Cautions

Testing & Maintenance

This detector will not operate without electrical power. As fires frequently cause power interruption, we suggest you discuss further safeguards with your fire protection specialist.

Each detector automatically identifies when it is dirty or defective and causes a “dirty detector” message. The detector’s sensitivity measurement can also be transmitted to the loop controller. A sensitivity report can be printed to satisfy NFPA sensitivity measurements which must be conducted at the end of the first year and every two years thereafter.

This detector will NOT sense fires that start in areas where smoke or heat cannot reach the detector. Smoke or heat from fires in walls, roofs, or on the opposite side of closed doors may not reach the detector to alarm it. The heat sensor in this device only provides a source of information to supplement the information provided by the ionization and photoelectric smoke sensors. The heat sensor by itself does NOT protect life against fire and smoke.

The user friendly maintenance program shows the current state of each detector and other pertinent messages. Single detectors may be turned off temporarily, from the control panel. Availability of maintenance features is dependent on the fire alarm system used. Scheduled maintenance (Regular or Selected) for proper detector operation should be planned to meet the requirements of the Authority Having Jurisdiction (AHJ). Refer to current NFPA 72 and ULC CAN/ULC 536 standards.

Accessories All detector mounting bases have wiring terminals that are accessible from the “room-side” after mounting the base to the electrical box. The bases mount to North American 1-gang boxes and to 3½ inch or 4 inch octagon boxes, 1½ inches (38 mm) deep. They also mount to European BESA and 1-gang boxes with 60.3 mm fixing centers. The SIGA-SB4, SIGA-RB4, and SIGA-IB4 mount to North American 4 inch sq. electrical boxes in addition to the above boxes. They include the SIGA-TS4 Trim Skirt which is used to cover the “mounting ears” on the base. The SIGA-AB4G mounts to a 4” sqare box only.

to other audible bases on the same 24 Vdc circuit. Relay and Audible Bases operate as follows: - at system power-up or reset, the relay is de-energized. - when a detector is installed in the base with the power on, the relay energizes for four seconds, then de-energizes. - when a detector is removed from a base with the power on, the relay is de-energized. - when the detector enters the alarm state, the relay is energized. Isolator Base SIGA-IB, SIGA-IB4 - This base includes a built-in line fault isolator for use on Class A circuits. A detector must be installed for it to operate. The isolator base does not support the SIGA-LED Remote LED.

SIGA-AB4G Audible Base

SIGA-SB Standard Base

SIGA-IB Isolator Base

SIGA-RB Relay Base

SIGA-LED Remote LED

Standard Base SIGA-SB, SIGA-SB4 - This is the basic mounting base for GE Security Signature Series detectors. The SIGA-LED Remote LED is supported by the Standard Base. Relay Base SIGA-RB, SIGA-RB4 - This base includes a relay. Normally open or closed operation is selected during installation. The dry contact is rated for 1 amp (pilot duty) @ 30 Vdc. The relay’s position is supervised to avoid accidentally jarring it out of position. The SIGA-RB can be operated as a control relay if programmed to do so at the control panel (EST3 V. 2 only). The relay base does not support the SIGA-LED Remote LED. Audible Base SIGA-AB4G - This base is designed for use where localized or group alarm signaling is required. When the detector senses an alarm condition, the audible base emits a local alarm signal. The optional SIGA-CRR Polarity Reversal Relay can be used for sounding

The isolator operates as follows: - a short on the line causes all isolators to open within 23 msec - at 10 msec intervals, beginning on one side of the Class A circuit nearest the loop controller, the isolators close to provide the next isolator down the line with power - when the isolator next to the short closes, it reopens within 10 msec. The process repeats beginning on the other side of the loop controller. Remote LED SIGA-LED - The remote LED connects to the SIGA-SB or SIGA-SB4 Standard Base only. It features a North American size 1-gang plastic faceplate with a white finish and red alarm LED. SIGA-TS4 Trim Skirt - Supplied with 4 inch bases, it can also be ordered separately to use with the other bases to help hide surface imperfections not covered by the smaller bases. Use black model (SIGA-TSB) with SIGA-IPHSB.

Data Sheet 85001-0245 Issue 7 Not to be used for installation purposes. Page  of 6

U.S. T 888-378-2329 F 866-503-3996 Canada T 519 376 2430 F 519 376 7258 Asia T 852 2907 8108 F 852 2142 5063 Australia T 61 3 9259 4700 F 61 3 9259 4799 Europe T 32 2 725 11 20 F 32 2 721 86 13 Latin America T 305 593 4301 F 305 593 4300 www.gesecurity.com © 2006 General Electric Company All Rights Reserved

Signature Series is a Trademark of GE Security.

Specifications Agency Listings Ion Sensor Photo Sensor Heat Sensor Storage and Operating Environment

Sensitivity Range User Selected Alarm Sensitivity Settings Pre-alarm Sensitivity Operating Voltage Operating Current Construction & Finish Compatible Mounting Bases LED Operation

Compatibility Address Requirements UL Listed Spacing

UL, ULC, CSFM, MEA (unipolar) 0.135µC Americium 241 Light Scattering Principle Alarms at 65ºF (35ºC) above ambient Air Velocity Range: 0 to 500 ft/min (0 to 2.53 m/s) Operating Temperature: 32ºF to 100ºF (0ºC to 38ºC) Storage Temperature: -4ºF to 140ºF (-20ºCto 60ºC) Humidity: 0 to 93% RH, Non-condensing Altitude: 6,000 ft. (1828m) above sea level maximum ULI/ULC - 0.67% to 3.70% obscuration/foot Most Sensitive: 1.0%/ft. More Sensitive: 2.0%/ft. Normal: 2.5%/ft. Less Sensitive: 3.0%/ft Least Sensitive: 3.5%/ft. 5% increments, allowing up to 20 pre-alarm settings 15.2 to 19.95 Vdc (19 Vdc nominal) Quiescent: 45µA @ 19 V Alarm: 45µA @ 19 V Emergency Stand-alone Alarm Mode: 18mA Pulse Current: 100µA (100 msec) High-Impact Engineering Polymer - White or Black SIGA-SB Standard Base, SIGA-RB Relay Base, SIGA-IB Isolator Base, SIGAAB4, AB4G Audible Bases On-board Green LED - Flashes when polled On-board Red LED - Flashes when in alarm Both LEDs - Glow steady when in alarm (stand-alone) Compatible Remote Red LED (model SIGA-LED) Flashes when in alarm Use With Signature Loop Controller Uses one Device Address 30 ft.

Ordering Information Catalog Number SIGA-IPHS SIGA-IPHSB Accessories SIGA-SB SIGA-SB4 SIGA-RB SIGA-RB4 SIGA-IB SIGA-IB4 SIGA-LED SIGA-AB4G SIGA-TS4 SIGA-TSB SIGA-TS

Description

Ship Wt. lbs (kg)

Intelligent 4D Multisensor Detector - UL/ULC Listed Intelligent 4D Multisensor Detector (Black) - UL/ULC Listed

Detector Mounting Base 4 inch Detector Mounting Base c/w SIGA-TS4 Trim Skirt Detector Mounting Base w/Relay 4 inch Detector Mounting Base w/Relay c/w SIGA-TS4 Trim Skirt Detector Mounting Base w/Fault Isolator 4 inch Detector Mounting Base w/Fault Isolator c/w SIGA-TS4 Trim Skirt Remote Alarm LED Audible (Sounder) Base Trim Skirt (supplied with 4 inch bases) Trim Skirt - Black (use with black detector) Trim Skirt - (optional for non-4” bases)

0.5 (.23)

0.2 (.09)

0.2 (.09) 0.3 (0.15) 0.1 (.04)

Data Sheet 85001-0245 Issue 7 Not to be used for installation purposes. Page  of 6

Life Safety Systems Intelligent Input/Output

Overview

Standard Features

The SIGA-CT1 Single Input Module and SIGA-CT2/SIGA-MCT2 Dual Input Modules are intelligent analog addressable devices used to connect one or two Class B normally-open Alarm, Supervisory, or Monitor type dry contact Initiating Device Circuits (IDC).

• Multiple applications Including Alarm, Alarm with delayed latching (retard) for waterflow applications, Supervisory, and Monitor. The installer selects one of four “personality codes” to be downloaded to the module through the loop controller.

The actual function of these modules is determined by the “personality code” selected by the installer. This code is downloaded to the module from the Signature loop controller during system configuration. The input modules gather analog information from the initiating devices connected to them and convert it into digital signals. The module’s on-board microprocessor analyzes the signal and decides whether or not to input an alarm. The SIGA-CT1 and SIGA-CT2 mount to standard North American 1-gang electrical boxes, making them ideal for locations where only one module is required. Separate I/O and data loop connections are made to each module. The SIGA-MCT2 is part of the UIO family of plug-in Signature Series modules. It functions identically to the SIGA-CT2, but takes advantage of the modular flexibility and easy installation that characterizes all UIO modules. Two- and six-module UIO motherboards are available. All wiring connections are made to terminal blocks on the motherboard. UIO assemblies may be mounted in GE Security enclosures.

• Plug-in (UIO) or standard 1-gang mount UIO versions allow quick installation where multiple modules are required. The 1-gang mount version is ideal for remote locations that require a single module. • Automatic device mapping Signature modules transmit information to the loop controller regarding their circuit locations with respect to other Signature devices on the wire loop. • Electronic addressing Programmable addresses are downloaded from the loop controller, a PC, or the SIGA-PRO Signature Program/Service Tool. There are no switches or dials to set. • Non-volatile memory Permanently stores serial number, type of device, and job number. • Stand-alone operation The module makes decisions and inputs an alarm from initiating devices connected to it even if the loop controller’s polling interrogation stops. (Function availability dependent upon control panel.) • Ground fault detection by address Detects ground faults right down to the device level.

Input Modules

SIGA-CT1, SIGA-CT2 & SIGA-MCT2

SIGA-CT1/2

SIGA-MCT2

MEA

S

CHINA

Application Notes Available

Data Sheet 85001-0241 Issue 6 Not to be used for installation purposes. Page  of 4

Signature Series Overview

UIO Motherboard 6-32 Self-tapping screws

The Signature Series intelligent analog-addressable system from GE Security is an entire family of multi-sensor detectors and mounting bases, multiple-function input and output modules, network and non-network control panels, and user-friendly maintenance and service tools. Analog information from equipment connected to Signature devices is gathered and converted into digital signals. An onboard microprocessor in each Signature device measures and analyzes the signal and decides whether or not to input an alarm. The microprocessor in each Signature device provides four additional benefits – Self-diagnostics and History Log, Automatic Device Mapping, Stand-alone Operation and Fast, Stable Communication. Self-diagnostics and History Log – Each Signature Series device constantly runs self-checks to provide important maintenance information. The results of the self-check are automatically updated and permanently stored in its non-volatile memory. This information is accessible for review any time at the control panel, PC, or using the SIGA-PRO Signature Program/Service Tool. Automatic Device Mapping –The Signature Data Controller (SDC) learns where each device’s serial number address is installed relative to other devices on the circuit. The SDC keeps a map of all Signature Series devices connected to it. The Signature Series Data Entry Program also uses the mapping feature. With interactive menus and graphic support, the wired circuits between each device can be examined. Layout or “as-built” drawing information showing branch wiring (T-taps), device types and their address are stored on disk for printing hard copy.

Installation SIGA-CT1 and SIGA-CT2: modules mount to North American 2½ inch(64 mm) deep 1-gang boxes and 1½ inch (38 mm) deep 4 inch square boxes with 1-gang covers and SIGA-MP mounting plates. The terminals are suited for #12 to #18 AWG (2.5 mm2 to 0.75 mm2) wire size. Compatible electrical box

Wall plate, white (1-gang)

M ALAR FIRE ULE MOD

SIGA-MCT2: mount the UIO motherboard inside a suitable GE Security enclosure with screws and washers provided. Plug the SIGAMCT2 into any available position on the motherboard and secure the module to the motherboard with the captive screws. Wiring connections are made to the terminals on the motherboard (see wiring diagram). UIO motherboard terminals are suited for #12 to #18 AWG (2.5 mm2 to 0.75 mm2) wire size.

Plug-in (UIO) Module

Captive screws

#6 Flat washers Cabinet or electrical enclosure

Electronic Addressing - The loop controller electronically addresses each module, saving valuable time during system commissioning. Setting complicated switches or dials is not required. Each module has its own unique serial number stored in its on-board memory. The loop controller identifies each device on the loop and assigns a “soft” address to each serial number. If desired, the modules can be addressed using the SIGA-PRO Signature Program/Service Tool. GE Security recommends that this module be installed according to latest recognized edition of national and local fire alarm codes.

Application The duty performed by the SIGA-CT1 and SIGA-CT2/MCT2 is determined by their sub-type code or “Personality Code”. The code is selected by the installer depending upon the desired application and is downloaded from the loop controller. One personality code can be assigned to the SIGA-CT1. Two personality codes can be assigned to the SIGA-CT2/MCT2. Codes 1, 2, 3 and 4 can be mixed on SIGA-CT2/MCT2 modules only. For example, personality code 1 can be assigned to the first address (circuit A) and code 4 can be assigned to the second address (circuit B). NORMALLY-OPEN ALARM - LATCHING (Personality Code 1) - Assign to one or both circuits. Configures either circuit A or B or both for Class B normally open dry contact initiating devices such as Pull Stations, Heat Detectors, etc. An ALARM signal is sent to the loop controller when the input contact is closed. The alarm condition is latched at the module. NORMALLY-OPEN ALARM - DELAYED LATCHING (Personality Code 2) - Assign to one or both circuits. Configures either circuit A or B or both for Class B normally-open dry contact initiating devices such as Waterflow Alarm Switches. An ALARM signal is sent to the loop controller when the input contact is closed for approximately 16 seconds. The alarm condition is latched at the module. NORMALLY-OPEN ACTIVE - NON-LATCHING (Personality Code 3) Assign to one or both circuits. Configures either circuit A or B or both for Class B normally-open dry contact monitoring input such as from Fans, Dampers, Doors, etc. An ACTIVE signal is sent to the loop controller when the input contact is closed. The active condition is not latched at the module. NORMALLY-OPEN ACTIVE - LATCHING (Personality Code 4) - Assign to one or both circuits. Configures either circuit A or B or both for Class B normally open dry contact monitoring input such as from Supervisory and Tamper Switches. An ACTIVE signal is sent to the loop controller when the input contact is closed. The active condition is latched at the module.

Data Sheet 85001-0241 Issue 6 Not to be used for installation purposes. Page  of 4

Typical Wiring Modules will accept #18 AWG (0.75mm2), #16 (1.0mm2), and #14AWG (1.50mm2), and #12 AWG (2.50mm2) wire sizes. Note: Sizes #16 AWG (1.0mm2) and #18 AWG (0.75mm2) are preferred for ease of installation. See Signature Loop Controller catalog sheet for detailed wiring requirement specifications. Initiating (Slave) Device Circuit Wire Specifications Maximum Allowable Wire Resistance

50 ohms (25 ohms per wire) per Circuit

Maximum Allowable Wire Capacitance

0.1µF per Circuit Maximum Distance to EOLR

Wire Size

For Design Reference:

#18 AWG (0.75 mm²) #16 AWG (1.00 mm²)

4,000 ft (1,219 m)

#14 AWG (1.50 mm²) #12 AWG (1.50 mm²)

SIGA-CT2

SIGA-CT1

Typical NO Initiating Device

NOTES 1 Maximum 25 Ohm resistance per wire.

UL/ULC Listed 47K EOL

Input 2

UL/ULC Listed 47K EOL

Input 1

2 Maximum #12 AWG (2.5 mm² ) wire; Minimum #18 AWG (0.75 mm2).

1

2

4

3 Refer to Signature controller installation sheet for wiring specifications. 4 Maximum 10 Vdc @ 350 µA

This module will not operate without electrical power. As fires frequently cause power interruption, we suggest you discuss further safeguards with your local fire protection specialist.

Compatibility

Data Out

Green LED (Normal) Red LED (Active)

EDWARDS SYSTEMS TECHNOLOGY

4 3 2 1

TB7

TB14

473387351

Signature Data Circuit

Warnings & Cautions

4 3 2 1

Data In

CAT NO.

7 These modules will not support 2-wire smoke detectors.

SIGA-UIO(R) series motherboard

3

SIGA-MCT2

6 All wiring is supervised and power-limited.

SIGA-MCT2

1 23 4

5 The SIGA-UIO6R and the SIGA-UIO2R do not come with TB14.

5 No connections required for SIGA-MCT2 Other modules may require connections.

4 3 2 1

TB15 1 2 3 4

No connections or jumper settings required for SIGA-MCT2.

SIGA-MCT2

The Signature Series modules are compatible only with GE Security’s Signature Loop Controller.

Data Sheet 85001-0241 Issue 6 Not to be used for installation purposes. Page  of 4

U.S. T 888-378-2329 F 866-503-3996 Canada T 519 376 2430 F 519 376 7258 Asia T 852 2907 8108 F 852 2142 5063

Specifications Catalog Number Type Code

48 (factory set) Four sub-types (personality codes) are available

49 (factory set) Four sub-types (personality codes) are available

Address Requirements

Uses One Module Address

Uses Two Module Addresses

Operating Current

Europe T 32 2 725 11 20 F 32 2 721 86 13

Construction

www.gesecurity.com © 2006 General Electric Company All Rights Reserved

SIGA-CT2 SIGA-MCT2 Dual Input Module

Single Input Module

Australia T 61 3 9259 4700 F 61 3 9259 4799

Latin America T 305 593 4301 F 305 593 4300

SIGA-CT1

Description

Operating Voltage

High Impact Engineering Polymer

Mounting

Storage and Operating Environment LED Operation Compatibility

Standby = 396µA; Activated = 680µA Standby = 250µA; Activated = 400µA 15.2 to 19.95 Vdc (19 Vdc nominal) UIO2R/6R/6 MotherNorth American 2½ inch (64 mm) deep one-gang board boxes and 1½ inch (38 mm) deep 4 inch square boxes with one-gang covers and SIGA-MP mounting plates Operating Temperature: 32°F to 120°F (0°C to 49°C) Storage Temperature: -4°F to 140°F (-20°C to 60°C); Humidity: 0 to 93% RH On-board Green LED - Flashes when polled; On-board Red LED - Flashes when in alarm/active Both LEDs - Glow steady when in alarm (stand-alone) Use with Signature Loop Controller UL, ULC, MEA, CSFM

Agency Listings Signature Series is a Trademark of GE Security.

Ordering Information Catalog Number SIGA-CT1 SIGA-CT2 SIGA-MCT2

Description Single Input Module — UL/ULC Listed Dual Input Module — UL/ULC Listed Dual Input Plug-in (UIO) Module — UL, ULC Listed

Related Equipment 27193-11 Surface Mount Box - Red, 1-gang 27193-16 Surface Mount Box - White, 1-gang SIGA-UIO2R Universal Input-Output Module Board w/Riser Inputs — Two Module Positions SIGA-UIO6R Universal Input-Output Module Board w/Riser Inputs — Six Module Positions SIGA-UIO6 Universal Input-Output Module Board — Six Module Positions MFC-A Multifunction Fire Cabinet — Red, supports Signature Module Mounting Plates SIGA-MP1 Signature Module Mounting Plate, 1 footprint SIGA-MP2 Signature Module Mounting Plate, 1/2 footprint SIGA-MP2L Signature Module Mounting Plate, 1/2 extended footprint

Ship Wt. lbs (kg) 0.4 (0.15) 0.4 (0.15) 0.1 (0.05)

1.0 (0.6) 1.0 (0.6) 0.32 (0.15) 0.62 (0.28) 0.56 (0.25) 7.0 (3.1) 1.5 (0.70) 0.5 (0.23) 1.02 (0.46)

Data Sheet 85001-0241 Issue 6 Not to be used for installation purposes. Page  of 4

GE Security

EST Fire & Life Safety Intelligent Input/Output

Overview

Standard Features

The Control Relay Module and the Polarity Reversal Relay Module are part of the Signature Series system. They are intelligent analog addressable devices available in either plug-in (UIO) versions, or standard 1-gang mount versions.

• Provides one no/nc contact (SIGA-CR/MCR) Form “C” dry relay contact can be used to control external appliances such as door closers, fans, dampers etc.

The SIGA-CR/MCR Control Relay Module provides a Form “C” dry relay contact to control external appliances such as door closers, fans, dampers etc. This device does not provide supervision of the state of the relay contact. Instead, the on-board microprocessor ensures that the relay is in the proper ON/OFF state. Upon command from the loop controller, the SIGA-CR/MCR relay activates the normally open or normally-closed contact. The SIGA-CRR/MCRR Polarity Reversal Relay Module provides a Form “C” dry relay contact to power and activate a series of SIGAAB4G Audible Sounder Bases. Upon command from the Signature loop controller, the SIGA-CRR reverses the polarity of its 24 Vdc output, thus activating all Sounder Bases on the data loop. Standard-mount versions (SIGA-CR and SIGA-CRR) are installed to standard North American 1-gang electrical boxes, making them ideal for locations where only one module is required. Separate I/O and data loop connections are made to each module. Plug-in uIO versions (SIGA-MCR and SIGA-MCRR) are part of the UIO family of plug-in Signature Series modules. They function identically to the standard mount versions, but take advantage of the modular flexibility and easy installation that characterizes all UIO modules. Two- and six-module UIO motherboards are available. All wiring connections are made to terminal blocks on the motherboard. UIO assemblies may be mounted in GE Security enclosures.

• Allows group operation of sounder bases The SIGA-CRR/MCRR reverses the polarity of its 24 Vdc output, thus activating all Sounder Bases on the data loop. • Plug-in (uIO) or standard 1-gang mount UIO versions allow quick installation where multiple modules are required. The 1-gang mount version is ideal for remote locations that require a single module. • Automatic device mapping Signature modules transmit information to the loop controller regarding their circuit locations with respect to other Signature devices on the wire loop. • Electronic addressing Programmable addresses are downloaded from the loop controller, a PC, or the SIGA-PRO Signature Program/Service Tool; there are no switches or dials to set. • Intelligent device with microprocessor All decisions are made at the module to allow lower communication speed with substantially improved control panel response time and less sensitivity to line noise and loop wiring properties; twisted or shielded wire is not required. • Ground fault detection by address Detects ground faults right down to the device level.

Control Relay Modules

SIGA-CR, SIGA-MCR, SIGA-CRR, SIGA-MCRR

MEA

SIGA-CR

SIGA-MCR

Data Sheet 85001-0239 Issue 7.2 Not to be used for installation purposes. Page 1 of 6

Installation

Application

SIGA-CR and SIGA-CRR: modules mount to North American 2½ inch (64 mm) deep 1-gang boxes and 1½ inch (38 mm) deep 4 inch square boxes with 1-gang covers and SIGA-MP mounting plates. The terminals are suited for #12 to #18 AWG (2.5 mm2 to 0.75 mm2) wire size.

The operation of Signature Series control relays is determined by their sub-type code or “Personality Code.”

Compatible electrical box

Wall plate, white (1-gang)

Personality Code 8: CONTROL RELAY (SIGA-CR/MCR) - Dry Contact Output. This setting configures the module to provide one Form “C” DRY RELAY CONTACT to control Door Closers, Fans, Dampers, etc. Contact rating is 2.0 amp @ 24 Vdc; 0.5 amp @ 120 Vac (or 220 Vac for non-UL applications). Personality Code 8 is assigned at the factory. No user configuration is required. Personality Code 8: Polarity Reversal Relay Module (SIGACRR/MCRR). This setting configures the module to reverse the polarity of its 24 Vdc output. Contact rating is 2.0 amp @ 24 Vdc (pilot duty). Personality Code 8 is assigned at the factory. No user configuration is required.

Compatibility The Signature Series modules are compatible only with GE Security’s Signature Loop Controller.

M ALAR FIRE DULE MO

Warnings & Cautions SIGA-MCR and SIGA-MCRR: mount the UIO motherboard inside a suitable GE Security enclosure with screws and washers provided. Plug the module into any available position on the motherboard and secure the module to the motherboard with the captive screws. Wiring connections are made to the terminals on the motherboard (see wiring diagram). UIO motherboard terminals are suited for #12 to #18 AWG (2.5 mm2 to 0.75 mm2) wire size. UIO Motherboard 6-32 Self-tapping screws

Plug-in (UIO) Module

This module will not operate without electrical power. As fires frequently cause power interruption, we suggest you discuss further safeguards with your local fire protection specialist.

Testing & Maintenance The module’s automatic self-diagnosis identifies when it is defective and causes a trouble message. The user-friendly maintenance program shows the current state of each module and other pertinent messages. Single modules may be turned off (deactivated) temporarily, from the control panel. Availability of maintenance features is dependent on the fire alarm system used. Scheduled maintenance (Regular or Selected) for proper system operation should be planned to meet the requirements of the Authority Having Jurisdiction (AHJ). Refer to current NFPA 72 and ULC CAN/ULC 536 standards.

Captive screws

#6 Flat washers Cabinet or electrical enclosure

Electronic Addressing - The loop controller electronically addresses each module, saving valuable time during system commissioning. Setting complicated switches or dials is not required. Each module has its own unique serial number stored in its on-board memory. The loop controller identifies each device on the loop and assigns a “soft” address to each serial number. If desired, the modules can be addressed using the SIGA-PRO Signature Program/Service Tool. GE Security recommends that this module be installed according to latest recognized edition of national and local fire alarm codes.

Data Sheet 85001-0239 Issue 7.2 Not to be used for installation purposes. Page  of 6

Typical Wiring Modules will accept #18 AWG (0.75mm2), #16 (1.0mm2), #14 AWG (1.50mm2) and #12 AWG (2.5mm2) wire sizes. Note: Sizes #16 AWG (1.0mm2) and #18 AWG (0.75mm2) are preferred for ease of installation. See Signature Loop Controller catalog sheet for detailed wiring requirement specifications.

Notes

1 Refer to Signature Loop Controller Installation Sheet for wiring specifications. 2 NFPA 72 requires that the SIGA-CR/SIGA-MCR be installed in the same room as the device it is controlling. This requirement may not apply in all markets. Check with your local AHJ for details. 3 The SIGA-UIO6R and the SIGA-UIO2R do not come with TB14.

SIGA-CR Control Relay

Normally Open

Common

4 The SIGA-UIO6 does not come with TB8 through TB13. 5 Supervised and power-limited.

Normally Closed

6 If the source is nonpower-limited, maintain a space of 1/4 inch from power-limited wiring or use FPL, FPLP, FPLR, or an equivalent in accordance with the National Electrical Code. 2

7) Maximum #12 AWG (2.5mm2) wire. Min. #18 (0.75mm2).

1 23 4

1



Data In 4 3 2 1

TB7

TB14

MCR

CAT NO.

Data Out

473387358

4 3 2 1

Green LED (Normal) Red LED (Active)

3

No connections required for MCR. Other modules may require connections. 4 3 2 1

TB15 1 23 4 4

No connections required for MCR. Other modules may require connections.

SIGA-MCR Control Relay

Data Sheet 85001-0239 Issue 7.2 Not to be used for installation purposes. Page  of 6

Typical Wiring

Modules will accept #18 AWG (0.75mm2), #16 (1.0mm2), #14 AWG (1.50mm2) and #12 AWG (2.50mm2) wire sizes. Note: Sizes #16 AWG (1.0mm2) and #18 AWG (0.75mm2) are preferred for ease of installation. See Signature Loop Controller catalog sheet for detailed wiring requirement specifications. AB4G Audible Base

AB4G Audible Base

AB4G Audible Base 6254A-003 EOL Relay

+

Listed 24 VDC Nominal Power Supply

-

1

2

1

2

2

1

3

3

CR

2

2

2

CRR

CT1

SIGA-CRR

3

3

SIGA-MCRR

1 2

10

3

6254A-003 EOL Relay required for supevision

5

6

7

9

Audible Bases

4

Polarity reverses when activated.

8

Power In Power Out

11

SIGA-MCRR Schematic

SIG +

SIGA-CRR Schematic

Optional CR for disabling/disconnecting sounder base

DATA (+) IN/OUT

SIGA-CRR Schematic

3

DATA (-) IN

3

DATA (-) OUT

-

SIG -

+

DATA

Signature Controller

For General Fire Alarm Operation 4

3 2 1

or 1 23 4

1 23 4 MCRR

7

1

UIO(R) series motherboard 4 3 2 1

Data Out 4 3 2 1

Green LED (Normal) Red LED (Active) Optional MCRR or MCR for disabling/disconnecting an audible base.

473387359

TB7 Data In

CAT NO.

TB14

MCRR

Signature Data Circuit

473387360

7 Supervised and power-limited. 8 If the source is nonpower-limited, maintain a space of 1/4 inch from power-limited wiring or use FPL, FPLP, FPLR, or an equivalent in accordance with the National Electrical Code. 9 Maximum #12 AWG (2.5 mm² ) wire; Minimum #18 AWG (0.75 mm² ). 10 End-of-Line Relay must monitor and report power supply trouble to control panel. 11 Class B Data wiring may be “T-tapped.”

7

CT1

For normal operation

UL/ULC Listed 24 Vdc power supply

3 One Pair of Wires (Signature Data). 4 Single Wire (24 Vdc power). 5 The SIGA-UIO6R and the SIGA-UIO2R do not come with TB14. 6 The SIGA-UIO6 does not come with TB8 through TB13.

8

8

CAT NO.

1 Refer to the Signature controller installation sheet for wiring. 2 One Pair of Wires (24 Vdc power).

7

Signature Data Out Data Circuit

MCRR

Notes

4 3 2 1

TB15 1 23 4

1 23 4

6

6

5

No connections required for MCRR. Other modules may require connections.

Green LED (Normal) Red LED (Active)

No connections required for MCRR. Other modules may require connections.

No connections required for MCRR. Other modules may require connections.

Data Sheet 85001-0239 Issue 7.2 Not to be used for installation purposes. Page  of 6

Specifications Catalog Number

SIGA-CR

SIGA-MCR

Description

Control Relay

Type Code

Personality Code 8 (Factory Set)

Address Requirements

SIGA-MCRR

Polarity Reversal Relay Personality Code 8 (Factory Set) Uses 1 Module Address

Operating Current

Standby = 100µA Activated = 100µA

Operating Voltage

15.2 to 19.95 Vdc (19 Vdc nominal)

Relay Type and Rating Mounting

SIGA-CRR

Form “C” 24 VDC = 2 amps (pilot duty) 120 Vac = 0.5 amps 220 Vac (non-UL) = 0.5 amps North American 2½ inch (64 mm) deep 1-gang boxes and 1½ inch (38 mm) deep 4 inch square boxes with 1-gang covers and SIGA-MP mounting plates

Plugs into UIO2R, UIO6R or UIO6 Motherboards

Construction & Finish

North American 2½ inch (64 mm) deep 1-gang boxes and 1½ inch (38 mm) deep 4 inch square boxes with 1-gang covers and SIGA-MP mounting plates

Plugs into UIO2R, UIO6R or UIO6 Motherboards

High Impact Engineering Polymer

Storage and Operating Environment

Operating Temperature: 32°F to 120°F (0°C to 49°C) Storage Temperature: -4°F to 140°F (-20°C to 60°C) Humidity: 0 to 93% RH

LED Operation

On-board Green LED - Flashes when polled On-board Red LED - Flashes when in alarm/active

Compatibility

Use With: Signature Loop Controller

Agency Listings

UL, ULC, CSFM, MEA

Ordering Information Catalog Number

Description

Ship Weight - lbs (kg)

SIGA-CR

Control Relay Module (Standard Mount)

0.4 (0.15)

SIGA-MCR

Control Relay Module (UIO Mount)

0.18 (0.08)

SIGA-CRR

Polarity Reversal Relay Module (Standard Mount)

0.4 (0.15)

SIGA-MCRR

Polarity Reversal Relay Module (UIO Mount)

0.18 (0.08)

Related Equipment 27193-11

Surface Mount Box - Red, 1-gang

1 (0.6)

27193-16

Surface Mount Box - White, 1-gang

SIGA-UIO2R

Universal Input-Output Module Board w/Riser Inputs - Two Module Positions

0.32 (0.15)

SIGA-UIO6R

Universal Input-Output Module Board w/Riser Inputs - Six Module Positions

0.62 (0.28)

SIGA-UIO6

Universal Input-Output Module Board - Six Module Positions

0.56 (0.25)

SIGA-AB4G

Audible (Sounder) Detector Base

0.3 (0.15)

1 (0.6)

Accessories MFC-A

Multifunction Fire Cabinet - Red, supports Signature Module Mounting Plates

7.0 (3.1)

SIGA-MB4

Transponder Mounting Bracket (allows for mounting two 1-gang modules in a 2-gang box)

0.4 (0.15)

SIGA-MP1

Signature Module Mounting Plate, 1 footprint

1.5 (0.70)

SIGA-MP2

Signature Module Mounting Plate, 1/2 footprint

0.5 (0.23)

SIGA-MP2L

Signature Module Mounting Plate, 1/2 extended footprint

1.02 (0.46)

Data Sheet 85001-0239 Issue 7.2 Not to be used for installation purposes. Page  of 6

GE Security U.S. T 888-378-2329 F 866-503-3996 Canada T 519 376 2430 F 519 376 7258 Asia T 852 2907 8108 F 852 2142 5063 Australia T 61 3 9259 4700 F 61 3 9259 4799 Europe T 32 2 725 11 20 F 32 2 721 86 13 Latin America T 305 593 4301 F 305 593 4300 www.gesecurity.com/est © 2006 General Electric Company All Rights Reserved

Signature Series is a Trademark of GE Security.

Signature Series Overview The Signature Series intelligent analog-addressable system from GE Security is an entire family of multi-sensor detectors and mounting bases, multiple-function input and output modules, network and non-network control panels, and user-friendly maintenance and service tools. Analog information from equipment connected to Signature devices is gathered and converted into digital signals. An onboard microprocessor in each Signature device measures and analyzes the signal and decides whether or not to input an alarm. The microprocessor in each Signature device provides four additional benefits – Self-diagnostics and History Log, Automatic Device Mapping, Stand-alone Operation and Fast, Stable Communication. Self-diagnostics and History Log – Each Signature Series device constantly runs selfchecks to provide important maintenance information. The results of the self-check are automatically updated and permanently stored in its non-volatile memory. This information is accessible for review any time at the control panel, PC, or using the SIGA-PRO Signature Program/Service Tool. The information stored in device memory includes: • Device serial number, address, and type • Time and date of last alarm • Most recent trouble code logged by the detector — 32 possible trouble codes may be used to diagnose faults. Automatic Device Mapping –The Signature Data Controller (SDC) learns where each device’s serial number address is installed relative to other devices on the circuit. The SDC keeps a map of all Signature Series devices connected to it. The Signature Series Data Entry Program also uses the mapping feature. With interactive menus and graphic support, the wired circuits between each device can be examined. Layout or “as-built” drawing information showing branch wiring (T-taps), device types and their address are stored on disk for printing hard copy. This takes the mystery out of the installation. The preparation of as-built drawings is fast and efficient. Device mapping allows the Signature Data Controller to discover: • Unexpected additional device addresses • Missing device addresses • Changes to the wiring in the circuit. Most Signature modules use a personality code selected by the installer to determine their actual function. Personality codes are downloaded from the SDC during system configuration and are indicated during device mapping. Standalone Operation – A decentralized alarm decision by the device is guaranteed. Onboard intelligence permits the device to operate in stan­dalone (degrade) mode. If Signature loop controller CPU communications fail for more than four seconds, all devices on that circuit go into standalone mode. The circuit acts like a conventional alarm receiving circuit. Each Signature device on the circuit continues to collect and analyze information from its slave devices. When connected to a panel utilizing standalone op­eration, modules with their “personality” set as alarm devices (IDC) will alarm should their slave alarm-initiating device activate.

Data Sheet 85001-0239 Issue 7.2 Not to be used for installation purposes. Page  of 6

Life Safety Systems Fire Suppression

Overview

Standard Features

The SIGA-REL is an analog addressable module that communicates directly with the fire alarm panel Signature loop controller. The SIGA-REL controls sprinkler, pre-action and deluge systems, and may also be used to release extinguishing agents such as CO2, Halon, or foam. The module is easily configured in the field and offers a wide range of options that ensure dependable service, while preventing the unnecessary release of extinguishing agent.

• Ideal for sprinkler, pre-action and deluge systems Suitable a wide range of sprinkler applications and extinguishing agents such as CO2 and Halon.

In addition to being an intelligent network component, the SIGA-REL interfaces with a number of conventional devices. These provide manual actuation of abort, release, and service disconnect functions. Together with the SIGA-REL, they comprise a complete fire suppression package. There is no need for a separate releasing panel because the SIGA-REL takes full advantage of the existing control panel communications infrastructure. This ensures low-cost installations with all the benefits of Signature Series analog initiation and control. Seven on-board circuits provide added flexibility. Each SIGA-REL hosts: • Two supervised Class B release circuits • Two supervised Class B pre-release NACs • One supervised Class B manual release input circuit (latching) • One supervised Class B abort circuit for normally-open abort switch (non-latching) • One first alarm output relay (Form C contact) The SIGA-REL also includes a series of built-in timers that determine the duration of abort routines and release sequences. These timers are easily configured in the field and provide a highly flexible range of options.

• Built-in timers Selectable durations for abort, manual, and automatic delays. • Four abort modes Field-configurable abort routines determine how the timers operate when the abort function is initiated. • Supervised circuitry you can rely on Two Class B release circuits and two pre-release circuits provided. • Manual operation keeps ultimate control in plain view The SIGA-REL features a manual release input circuit as well as a manual abort input circuit. • Fully automated response leaves nothing to chance This module’s Form C relay is ideal for room preparation routines. • Unprecedented compatibility The SIGA-REL is compatible with any solenoid that is both ULlisted and FM-approved. • Automatic device mapping simplifies installation Signature modules transmit directly to the loop controller their circuit locations with respect to other Signature devices on the wire loop.

Releasing Module SIGA-REL

Patented

Data Sheet 85001-0531 Issue 4 Not to be used for installation purposes. Page  of 8

Application Understanding fire suppression Fire suppression today is an important part of a growing number of life safety installations. With an ever-increasing reliance on mission-critical computer systems and record high capital investment in high-tech production facilities, businesses large and small are looking for a means of protecting their investments and ensuring a fire won’t cripple their operations. While fire detection remains the first line of defense against the risks of fire to people, building owners are looking to fire suppression as a means of protecting their property and assets. But it’s a well known fact that fire suppression is a double-edged sword: water can snuff out a mission-critical computer system as easily as it can a fire. Alternatives to water, including carbon dioxide and other extinguishing agents can endanger lives, while the release of even the most inert extinguishing agents can disrupt operations and cost millions of dollars in down-time and lost production.

Understanding the SIGA-REL The SIGA-REL Releasing Module is a network component that provides control for fire suppression routines. It fulfils much the same purpose as a standalone releasing panel, but supports Signature Series detectors as an integral part of the suppression system. The SIGA-REL is easy to set up and accepts programming via the control panel’s SDU Rules Editor. The diagram below represents typical application of the SIGA-REL. The explanations that follow summarize each element of the module. Fire alarm control panel Signature loop controller

Signature Series smoke detectors M

Signature Series modules Horn circuit Strobe circuit

M

SD A MR

Service Disconnect Station Manual Abort Station Manual Release Station First Alarm Output Relay

M

Releasing Module

A

SD

RELA-EOL

Release Circuit 1

SD

RELA-EOL

Release Circuit 2

MR

Release Circuits. The SIGA-REL includes two supervised release circuits, each of which provides fire suppression control to different areas of a protected space. The releasing circuits actuate solenoids on the suppression agent tanks according to pre-defined release routines. These solenoids release the agent into the protected area. Both circuits operate together.

A primary goal of any fire suppression system is to prevent the release of extinguishing agent unless it is absolutely necessary. There is no margin for error. But no matter what measures are taken to prevent the unwanted release of extinguishing agent, the fact remains that no suppression system is any better than the detectors it relies on for input. The foundation of an effective suppression system, therefore, rests firmly on the quality and reliability of its smoke detectors. Signature Series detectors form an integral part of the suppression system built around the SIGA-REL releasing module. These detectors provide unsurpassed reliability and immunity from false alarms. The SIGA-REL is engineered to the same exacting standards of quality and performance. With a robust set of features designed to eliminate any unwanted release of extinguishing agent, the SIGA-REL provides all the benefits of a dedicated releasing panel without the extra expense, and equally important, all the proven advantages of the Signature Series family of products.

First Alarm Relay. This on-board relay provides a Form C contact that activates at the first alarm input or manual release. The relay is typically used for room preparation such as controlling fans and dampers in advance of the release of suppression agent. Pre-release. Pre-release circuits are used to provide power to notification appliances located within the protected are. Two supervised pre-release circuits are provided: one (steady) for visual notification appliances, and one (pulsed) for audible notification appliances. The pre-release circuits activate with the start of the automatic delay timer. Manual Release. The manual release circuit is used to activate the suppression system by means of a connected normallyopen release station. This initiates the manual release sequence according to a pre-defined routine. The manual release circuit is supervised and latching. Input from this circuit is processed at the module – communication with the control panel is not necessary. Abort. The abort circuit is used to prevent the release of agent into the protected area after the release sequence has begun, but before the automatic delay timer expires. A connected normallyopen release station provides manual control over this circuit. The abort circuit is supervised and non-latching. Service Disconnect. The service disconnect switch is used to temporarily disable the fire suppression system. There is no dedicated circuit for this switch. Instead, it is installed on both release circuits between the SIGA-REL and the RELA-EOL end-ofline relay. Opening the Service Disconnect Switch allows the fire alarm system to be tested without activating the fire suppression system. The operation of this switch causes a trouble signal at the control panel. Data. The Signature data circuit provides an input and an output to the data loop that communicates with the Signature loop controller at the control panel. The SIGA-REL resides on the same data loop as the Signature Series detectors that initiate the automatic release sequence. This close association offers the most reliable performance and ensures compliance with prevailing life safety codes. Power. The SIGA-REL requires 24 Vdc (power limited). See the specification table for details. Data Sheet 85001-0531 Issue 4 Not to be used for installation purposes. Page  of 8

Operation The SIGA-REL has several built-in safeguards to prevent the unwanted release of extinguishing agent. All release sequences are subject to configurable delay timers that provide the opportunity for an occupant of the area to manually abort the release sequence. If no abort signal is received before the delay timer expires, the suppression agent is released.

Note: Misapplication of the SIGA-REL can have serious consequences. Descriptions provided here are for information only, are subject to change, and should not be used as a guide to field installation of equipment. Always consult the SIGA-REL installation manual when setting up or configuring this component.

The SIGA-REL includes three delay timers: one for manual release sequences (up to 30 seconds); one for automatic release sequences (up to 50 seconds); and one for abort sequences (10 seconds). Normal State

Automatic Release Sequence

In its normal operating state the SIGA-REL supervises both of its release circuits and both of its pre-release NAC circuits for faults. Should a short or open occur on any of these circuits, a Trouble condition is reported to the control panel.

The automatic release sequence requires an AND group (cross zone) or a matrix group (counting zone). AND groups and matrix groups require fire alarm signals from designated Signature Series devices. These logic groups are programmable through a laptop computer and the System Definition Utility (SDU).

A trouble condition on any of these circuits may prevent the operation of that circuit, but it won’t inhibit the operation of any other fault-free circuit. Manual Release Sequence The operation of a manual release station initiates the manual release sequence. The diagram below outlines the manual release sequence. Time Line (see details below)



 



The diagram below outlines the automatic release sequence. Time Line (see details below)

 

 



First alarm relay Automatic delay timer

First alarm relay

Pre-release circuits

Manual delay timer

Release circuits

Pre-release circuits

First alarm

Release circuits

Manual release activated

Note: EST2 systems do not support matrix groups. See Programming the SIGA-REL for AND group rules. To create AND groups and matrix groups, see the System Programming Manual and the SDU Online Help for your system.

Selectable manual delay time (0 to 30 seconds)

Agent release System reset (manually at the control panel)

Note: A manual release sequence cannot be aborted. Manual Release Time Line  An active manual release station disables automatic operation and the abort function and simultaneously activates the:   Manual delay timer   Pre-release circuit   Pre-release strobe circuit (steady On)   Pre-release horn circuit (60 pulses per minute)  Ten seconds before the expiration of the manual delay timer, the pre-release horn changes from 60 pulses per minute to steady On.  The manual delay timer expires and the release circuits activate.  A manual reset at the fire alarm control panel deactivates the release solenoids and the Releasing Module returns to the normal state.

Active signal from AND group (e.g.: Second alarm)

Selectable automatic delay time (10 to 50 seconds)

Agent release System reset

Automatic Release Time Line  A detector signals the first alarm. This event simultaneously activates the:   First alarm relay   Pre-release strobe circuit (steady On)   Pre-release horn circuit (15 pulses per minute)  A detector in the protected area signals a second alarm and meets the AND group conditions.* The automatic delay timer then starts its countdown and the pre-release horn circuit changes to 60 pulses per minute. * AND group and matrix group conditions depend on programming.  10 seconds before the automatic delay timer expires, the pre-release (horn) circuit changes to steady On.  The automatic delay timer expires and the release circuits activate.   A manual reset at the fire alarm control panel deactivates the release solenoids and the Releasing Module returns to the normal state.

Data Sheet 85001-0531 Issue 4 Not to be used for installation purposes. Page  of 8

Abort Sequences The SIGA-REL provides four abort modes. Aborts do not terminate the release of fire suppression agents. They merely offer a limited extension of the automatic timer delay period. Abort Mode 1 (factory default) If the abort is initiated before the automatic time delay expires, it will prevent the releasing action. The automatic delay timer will continue to run while the abort is active. When the abort switch is restored, the release will occur with the expiration of the automatic delay timer or the abort delay timer, whichever occurs last. Abort Mode 2 If the abort is initiated before the automatic time delay expires, it will prevent the releasing action. The automatic delay timer will stop running. When the abort switch is restored, the automatic delay timer will continue from the stop point and the release will occur with the expiration of the timer.

Abort Mode 3 Industrial Risk Insurers (IRI) Mode: To be recognized as valid, the abort must be active when the second alarm is received. When the abort switch is restored, the release will occur with the expiration of the abort delay timer (set for 10 sec). Abort Mode 4 International applications: If the abort is initiated before the automatic time delay expires, it will prevent the releasing action. The automatic delay timer will stop running. When the abort switch is restored, the automatic delay timer will reset and commence time from t = 0. The release will occur with the expiration of the timer setting minus 10 seconds.

Compatibility Sprinkler systems The SIGA-REL works with two types of sprinkler systems: deluge and pre-action. The primary difference between both systems is the type of sprinkler head (or nozzle) that terminates the pipes. Table1-1 outlines the Factory Mutual Research Corporation (FMRC) requirements for deluge and pre-action systems. FM approval requirements for deluge and pre-action sprinkler systems Standby operation

90 hours

Alarm operation

10 minutes

NFPA style

Class A (Style D or E) or Class A (Style 2, 5, 6, or 7)

FMRC documentation

FMRC Approval Guide (Volume 1)

The following fire detection systems meet FRMC requirements for pre-action systems: • Hydraulic rate-of-rise • Pneumatic rate-of-rise • Electric Automatic fire extinguishing systems Automatic fire extinguishing systems automatically detect and extinguish fires. They require no manual input because detectors automatically activate releasing solenoids or sprinkler valves. The table below provides a list of the fire suppression agents and the applicable NFPA documents. Fire suppression agents and NFPA documentation Agent

NFPA documentation

Low-expansion foam

NFPA 11

Deluge sprinkler systems In Deluge sprinkler systems, open-valve sprinkler heads terminate pipes connected to a water supply controlled by a single valve. When the system detects a fire it automatically opens the valve to allow the waterflow through all of the sprinkler heads. Deluge sprinklers are useful for applications that require the simultaneous discharge of water through every sprinkler.

Medium- and high-expansion foam

NFPA 11A

CO2

NFPA 12

Sprinklers

NFPA 13

Water spray

NFPA 15

Foam-water

NFPA 16

The following fire detection systems meet FRMC requirements for deluge systems: • Wet pilot sprinkler line • Dry pilot sprinkler line • Hydraulic rate-of-rise • Pneumatic rate-of-rise • Electric

Dry chemicals

NFPA 17

Pre-action sprinkler systems In Pre-action sprinkler systems, closed-valve sprinkler heads terminate pipes connected directly to a water supply. The water supply is usually in the same area as the sprinklers and the pipes are supervised for air pressure. Pre-action sprinklers are useful where it is important to prevent the accidental discharge of water.

The table below outlines the FMRC requirements for automatic fire extinguishing systems. FM approval requirements for automatic fire extinguishing systems Standby operation

24 hours

Alarm operation

10 minutes

NFPA style

B or D

FMRC documentation

FMRC Approval Guide (Volume 1)

Warning! Improper applications of fire suppression agents can lead to property damage, injury, or loss of life. Consult the applicable NFPA documents and the authority having jurisdiction (AHJ) for more information. Data Sheet 85001-0531 Issue 4 Not to be used for installation purposes. Page  of 8

Compatible panels and devices Panels. The SIGAREL is compatible with EST2 and EST3 fire alarm control panels. You may install the SIGA-REL in any of the following enclosures: • 2-WB(X) series • 2-CAB series • 3-CAB series • RACCR series • MFC-A Note: Maintain a 1-inch (25.4 mm) minimum clearance all around the SIGA-REL. The clearance space must also comply with the National Electrical Code.

Power supplies. The SIGA-REL is compatible with the following power supplies: • 2-PPS(-220) • 2-PPS/6A(-220) • SIGA-APS(-220) • 3-BPS/M • 3-PPS/M • BPS6*, BPS10*

Wiring Abort circuit

Manual [5] release circuit

[3]

[5] First alarm output [9]

[8]

1 2 3 4 TB3

Signature Data Circuit In

+ _

Out

+ _

TB1

TB4 1 _ 2 3_ 4 + +

Service Disconnect Switch

Release circuit 1

RELA-EOL

1 2 3 4

[6]

1 2 3 4

[6]

RELA-EOL

[5]

1 2 3 4

[6]

RELA-EOL

Abort mode and time delay settings are configured by means of dip switches on the module.

1 2 3 4

[6] [5]

Mounting

Notes Four RELA-EOLs per circuit, max.

[2]

Class B, 24 Vdc output

[3]

Class B, normally-open manual release station

[4]

Class B, normally-open abort station

[5]

Listed 47 k EOL resistor

[6]

Nonpolarized valve. The releasing solenoid valve wiring is not supervised for wire-to-wire shorts. Run the connection to the valve in conduit within 20 feet of the RELA-EOL Solenoid Polarizing Relay.

[7]

Polarity of circuit shown in supervisory state. On alarm, polarity reverses.

[8]

Supervised and power-limited.

[9]

Power-limited when connected to a powerlimited source. If nonpower-limited, maintain 1/4 inch (6.4 mm) separation. Otherwise, use FPL, FPLR, or FPLP in accordance with the National Electric Code (NEC). Destroy power-limited markings.

1 2 3 4

10

Installations, which include other wiring, require FPL, FPLR, FPLP, or equivalent NEC-approved wiring for all power-limited wiring.

LED Operation

MFC-A

Releasing Module #6-32 self-tapping screws

Abort time delay (seconds) Delay SW8 The length of time that the deluge is 0 0 DEFAULT 10 inhibited when the abort function is 1 restored (i.e.: cancelled). DEFAULT Denotes default settings.

24 Vdc out

[1]

RELA-EOL

The length of time that the deluge is inhibited when the releasing function is initiated by the control panel (i.e.: after receiving an alarm).

+

24 Vdc in

Release circuit 2

RELA-EOL

Switch Settings

Automatic time delay (seconds) Delay SW5 SW6 SW7 10 0 0 0 20 0 0 1 30 0 1 0 40 0 1 1 DEFAULT 50 1 0 0

+ _

Pre-release Circuit 1 (audible) (pulsed 15/60/Steady) [8] [5] [2]

Service Disconnect Switch

[6]

Manual time delay (seconds) Delay SW3 SW4 The length of time that the 0 0 0 DEFAULT 10 deluge is inhibited when the 0 1 releasing function is manually 20 1 0 initiated. 30 1 1

[8]

Pre-release Circuit 2 (visual) (steady) [8] [5] [2]

[1] [2] [7] [8]

Listing agencies. Listing agencies include: • Factory Mutual Research Corporation (FMRC) • Underwriters Laboratories, Inc. (UL) • Underwriters Laboratories Canada (ULC)

Routines that determine how the abort function interacts with the timers.

_

TB5 1_ 2 3_ 4 + +

[1] [2] [7] [8]

Service disconnect stations. The SIGA-REL is only compatible with service disconnect stations that are normally-closed (minimum 2.0 Amps). Service disconnect stations must be listed with the appropriate agencies in your area. See Listing agencies.

Abort mode Mode SW1 SW2 DEFAULT 1 0 0 2 0 1 3 1 0 4 1 1

1 2 3 TB2

TB6

Releasing Module

Solenoid polarizing relays. Use the RELA-EOL with the SIGA-REL. For more information, see the RELAEOL installation sheet. Abort stations. The SIGA-REL is only compatible with normally-open, momentary-action abort stations. Abort stations must be listed with the appropriate agencies in your area. See Listing agencies.

4 3 2 1

4 3 2 1

[8]

*Not compatible with FMRC sprinkler applications that require 90 hours of standby.

Releasing solenoid valves. Releasing solenoid valves must be listed with the appropriate agencies in your area. See Listing agencies.

[4]

#6 Flat Washers

LED Color Pattern Function DS1 Red Flashing Data (alarm conditions)* DS2 Green Flashing Data (normal conditions)* DS3 Red Steady Alarm DS4 Green Steady Power DS5 Yellow Steady Abort DS6 Yellow Steady Trouble DS7 Red Steady Release Active *Note: During a loss of communications, the Releasing Module will go into a standby condition, which will cause DS1 and DS2 to change to a steady pattern during an alarm condition.

Data Sheet 85001-0531 Issue 4 Not to be used for installation purposes. Page  of 8

Accessories Abort Station

Typical application of SIGA-REL accessories (computer room)

Signature Series smoke detectors

Horn

Abort Station

Fire alarm control panel

Agent release nozzle

Signature loop controller

Strobe

Release Station

Release circuit 1

Releasing Module (mounted in MFC-A cabinet)

Service Disconnect

RELA-EOL

Service Disconnect

RELA-EOL

The abort station is a normally-open, non-latching device. It is used to prevent the release of agent into the protected area after the release sequence has begun.

Release circuit 2 2

Extinguishing agent storage cylinder

1

Service Disconnect Switch

Raised floor

Agent release nozzle

Signature Series smoke detectors

Slab

Manual Release Station

From releasing panel, module, or device To next device or end of line resistor Second circuit may be connected or left open

The service disconnect switch is used to temporarily disable the fire suppression system. One switch is installed on each of the two release circuits between the SIGA-REL and the RELA-EOL end-of-line relay. Opening the Service Disconnect Switch allows the fire alarm system to be tested without activating the fire suppression system. The operation of this switch causes a trouble signal at the control panel. End-of-Line Relay

Release Station (rear view)

The manual release station is a normally-open, dry contact signal initiating device. The 276A-REL is a single-action station that requires the user to pull the release handle to initiate the release of a fire suppression agent. The 278A-REL (shown) is a double-action station that requires the user to raise the upper door, then pull the release handle to initiate the release.

(-) (+)



4

(-)

3

(+)

2

(-)

1

(+)

To nonpolarized solenoid valve

End-of-line resistor or next relay From releasing panel or module

Polarity shown for release active.

End-of-Line Relay (rear view)

The End-of-Line Relay facilitates the connection of a non-polarized releasing solenoid to a supervised, polarized releasing circuit. One relay is required per release solenoid. Module Enclosure The MFC-A cabinet is UL-listed for use with Signature modules. Shown here with plug-in style I/O modules, the MFC-A also meets UL requirements for spacing and clearance around the SIGA-REL Releasing Module. The cabinet features red epoxy finish with white “FIRE” markings.

Data Sheet 85001-0531 Issue 4 Not to be used for installation purposes. Page  of 8

Specifications Power riser

Release circuits

Pre-release alarm circuits

Manual release input circuit

Abort circuit

Line Resistance

Input voltage Supervisory current Riser input current Alarm Output rating Valves per circuit Max. supervisory current Nominal supervisory current Supervisory voltage End of line device Output rating Max. supervisory current Nominal supervisory current Supervisory voltage End of line device Max. supervisory current Nominal supervisory current Supervisory voltage End of line device Circuit type Circuit capacitance Max. supervisory current Nominal supervisory current Supervisory voltage End of line device Circuit type Circuit capacitance

First alarm output relay Signature Data line

Environmental condiitions

Contact rating Operating voltage Supervisory current Alarm current Operating temperature Storage temperature Humidity

Wiring Terminals Type Code Addressing Requirements Agency Listings Compatible Solenoids

24 Vdc (power limited) 25 mA, max. 4 amps maximum 170 mA min.; 4 A max. 2 A @ 24 Vdc (for each circuit) 4 valves, max. 0.4 mA (short circuit) 0.18 mA 26 Vdc, max. (open circuit) 47k Ohm EOL 2 A @ 24 Vdc (for each circuit) 0.4 mA (short circuit) 0.18 mA 26 Vdc, max. (open circuit) 47k Ohm resistor 0.4 mA (short circuit) 0.18 mA 26 Vdc, max. (open circuit) 47k Ohm resistor Class B N.O. latching 0.1 µF, max 0.4 mA (short circuit) 0.18 mA 26 Vdc, max. (open circuit) 47k Ohm resistor Class B N.O. non- latching 0.1 µF, max 3 A @ 24 Vdc (0.6 power factor) Form C 5.2 to 19.95 Vdc 1000 µA 1000 µA 32° F to 120° F (0° C to 49° C) -4° F to 140° F (-20° C to 60° C) 0 to 93% Non-condensing

Suitable for #18 to #12 AWG (2.5 mm² to .75 mm²)

Power riser Total Distance from SIGA-REL to power supply riser current #12 AWG 2.5 mm² #14 AWG 1.5 mm² (Amps) 4.0 29 ft 8.84 m 20 ft 6.10 m 3.5 34 ft 10.36 m 23 ft 7.01 m 3.0 39 ft 11.89 m 27 ft 8.23 m 2.5 47 ft 14.33 m 32 ft 9.75 m 2.0 59 ft 17.98 m 40 ft 12.19 m 1.5 78 ft 23.77 m 53 ft 16.15 m 1.0 118 ft 35.97 m 80 ft 24.38 m

Wire resistance (Ohms per wire) 0.050 0.057 0.067 0.080 0.100 0.133 0.200

Pre-release and release circuits (per circuit) Total Distance from SIGA-REL to power supply riser current #12 AWG 2.5 mm² #14 AWG 1.5 mm² (Amps) 2.00 176 ft 53.64 m 120 ft 36.58 m 1.75 202 ft 61.57 m 137 ft 41.76 m 1.50 235 ft 71.63 m 160 ft 48.77 m 1.25 282 ft 85.95 m 192 ft 58.52 m 1.0 353 ft 107.59 m 240 ft 73.15 m 0.50 706 ft 215.19 m 480 ft 146.30 m

Wire resistance (Ohms per wire) 0.300 0.343 0.400 0.480 0.600 1.200

Ordering Information Model

Description

SIGA-REL

Analog addressable releasing module Manual releasing station (single-action). English markings, black text on yellow polycarbonate body. Manual releasing station (double-action). English markings, black text on yellow polycarbonate body. Manual Abort Station. English markings, black text on yellow polycarbonate body. Service Disconnect Switch. English markings, white text on blue polycarbonate body. Polarized end-of-line relay. English markings on stainless steel cover. UL listed cabinet for mounting releasing modules, red with white “FIRE”. HWD: 8” x 14” x 3½” (203mm x 356mm x 89mm)

276A-REL

278A-REL

Factory Set Uses six module addresses UL, ULC, and FM Must be both UL/ULC-listed and FM-approved

RELA-ABT RELA-SRV RELA-EOL

Note: Output circuits are power-limited when the riser circuit is power-limited.

MFC-A

Ship Wt. lb (kg) 0.52 (0.23) 1.0 (0.45)

1.0 (0.45) 1.0 (0.45) 1.0 (0.45) 0.2 (0.1)

7.0 (3.1)

Data Sheet 85001-0531 Issue 4 Not to be used for installation purposes. Page  of 8

U.S. T 888-378-2329 F 866-503-3996 Canada T 519 376 2430 F 519 376 7258 Asia T 852 2907 8108 F 852 2142 5063 Australia T 61 3 9259 4700 F 61 3 9259 4799 Europe T 32 2 725 11 20 F 32 2 721 86 13 Latin America T 305 593 4301 F 305 593 4300 www.gesecurity.com © 2006 General Electric Company All Rights Reserved

Signature Series is a Trademark of GE Security.

Data Sheet 85001-0531 Issue 4 Not to be used for installation purposes. Page  of 8

GE Security

Overview The SIGA-270 and SIGA-278 series Manual Pull Stations are part of GE Security’s Signature Series system. The SIGA-270 Fire Alarm Manual Pull Stations feature our very familiar teardrop shape. They are made from die-cast zinc and finished with red epoxy powder-coat paint complemented by aluminum colored stripes and markings. With positive pull-lever operation, one pull on the station handle breaks the glass rod and turns in a positive alarm, ensuring protection plus fool-proof operation. Presignal models (SIGA-270P) are equipped with a general alarm (GA) keyswitch for applications where two stage operation is required. The up-front highly visible glass rod discourages tampering, but is not required for proper operation. GE Security’s double action single stage SIGA-278 station is a contemporary style manual station made from durable red colored lexan. To initiate an alarm, first lift the upper door marked “LIFT THEN PULL HANDLE”, then pull the alarm handle.

Standard Features

EST Fire & Life Safety Intelligent Initiating Devices

• Break glass operation An up-front visible glass rod on the SIGA-270 discourages tampering. • Intelligent device with integral microprocessor All decisions are made at the station allowing lower communication speed while substantially improving control panel response time. Less sensitive to line noise and loop wiring properties; twisted or shielded wire is not required. • ADA Compliant Meets ADA requirements for manual pull stations. • Electronic Addressing with Non-volatile memory Permanently stores programmable address, serial number, type of device, and job number. Automatically updates historic information including hours of operation, last maintenance date, number of alarms and troubles, and time and date of last alarm. • Automatic device mapping Each station transmits wiring information to the loop controller regarding its location with respect to other devices on the circuit.

Note: Some features described here may not be supported by all control systems. Check your control panel’s Installation and Operation Guide for details.

• Stand-alone operation The station inputs an alarm even if the loop controller’s polling interrogation stops.

• Traditional familiar appearance SIGA-270 models feature our familiar teardrop design with simple positive pull action and sturdy die-cast metal body.

• Diagnostic LEDs Status LEDs; flashing GREEN shows normal polling; flashing RED shows alarm state.

• One stage (GA), two stage (pre-signal), and double action models SIGA-270 models are available for one or two stage alarm systems. The single stage double action SIGA-278 features a rugged Lexan housing with keyed reset mechanism.

• Designed for high ambient temperature operation Install in ambient temperatures up to 120 °F (49 °C).

Manual Pull Stations SIGA-270, SIGA-270P, SIGA-278

MEA

SIGA-270 SERIES

Patented

SIGA-278 Data Sheet 85001-0279 Issue 8 Not to be used for installation purposes. Page 1 of 4

Application

Typical Wiring

The operating characteristics of the fire alarm stations are determined by their sub-type code or “Personality Code”. NORMALLYOPEN ALARM - LATCHING (Pesonality Code 1) is assigned by the factory; no user configuration is required. The device is configured for Class B IDC operation. An ALARM signal is sent to the loop controller when the station’s pull lever is operated. The alarm condition is latched at the station.

The fire alarm station’s terminal block accepts #18 AWG (0.75mm2) to #12 AWG (2.5mm2) wire sizes. See Signature Loop Controller catalog sheet for detailed wiring requirement specifications. Wiring Notes 1 Refer to Signature Loop Controller manual for maximum wire distance.

2. All wiring is power limited and supervised.

Compatibility Signature Series manual stations are compatible only with GE Security’s Signature Loop Controller.

Warnings & Cautions This device will not operate without electrical power. As fires frequently cause power interruption, we suggest you discuss further safeguards with your local fire protection specialist.

Testing & Maintenance To test (or reset) the station simply open the station and operate the exposed switch. The SIGA-270 series are opened with a tool; the SIGA-278 requires the key which is supplied with that station. The station’s automatic self-diagnosis identifies when it is defective and causes a trouble message. The user-friendly maintenance program shows the current state of each Signature series device and other pertinent messages. Single devices may be deactivated temporarily, from the control panel. Availability of maintenance features is dependent on the fire alarm system used.

Figure 4. Single Stage Systems

Scheduled maintenance (Regular or Selected) for proper system operation should be planned to meet the requirements of the Authority Having Jurisdiction (AHJ). Refer to current NFPA 72 and ULC CAN/ULC 536 standards.

Figure 5. Two Stage Systems

Data Sheet 85001-0279 Issue 8 Not to be used for installation purposes. Page  of 4

Installation Single-stage Signature Series fire alarm manual pull stations mount to North American 2½ inch (64 mm) deep 1-gang boxes. Two stage presignal (270P) models require 1½ inch (38 mm) deep 4-inch square boxes with 1-gang, ½-inch raised covers. Openings must be angular. Rounded openings are not acceptable. Recommended box: Steel City Model 52-C-13; in Canada, use Iberville Model CI-52-C-49-1/2. All models include terminals are suited for #12 to #18 AWG (2.5 mm2 to 0.75 mm2) wire size. GE Security recommends that these fire alarm stations be installed according to latest recognized edition of national and local fire alarm codes. Electronic Addressing: The loop controller electronically addresses each manual station, saving valuable time during system commissioning. Setting complicated switches or dials is not required. Each station has its own unique serial number stored in its on-board memory. The loop controller identifies each device on the loop and assigns a “soft” address to each serial number. If desired, the stations can be addressed using the SIGA-PRO Signature Program/Service Tool.

Figure 1. SIGA-278 installation

Figure 2. SIGA-270, SIGC-270F, SIGC-270B installation

Cover Release Screw Comp atible Electrical Box with ½-inch raised covers

Back Plate Toggle Switch

AL ORM

N

LIFT

Glass Rod Release Lever

Do not use boxes with rounded openings.

Figure 3. SIGA-270P, SIGC-270PB installation

Data Sheet 85001-0279 Issue 8 Not to be used for installation purposes. Page  of 4

GE Security Specifications

U.S. T 888-378-2329 F 866-503-3996

Catalog Number

Canada T 519 376 2430 F 519 376 7258

Description Addressing Requirements

Asia T 852 2907 8108 F 852 2142 5063

Operating Current

Australia T 61 3 9259 4700 F 61 3 9259 4799

SIGA-270, SIGC-270F, SIGC-270B

SIGA-270P, SIGC-270PB

Single Action - One Stage

Single Action -Two Stage (Presignal)

SIGA-278 Double Action - One Stage

Uses 1 Module Address

Uses 2 Module Addresses

Uses 1 Module Address

Standby = 250µA Activated = 400µA

Standby = 396µA Activated = 680µA

Standby = 250µA Activated = 400µA

Diecast Zinc - Red Epoxy with aluminum markings Factory Set

Construction & Finish Type Code

Europe T 32 2 725 11 20 F 32 2 721 86 13

15.2 to 19.95 Vdc (19 Vdc nominal)

Operating Voltage Storage and Operating Environment

Latin America T 305 593 4301 F 305 593 4300

LED Operation

www.gesecurity.com/est

Compatibility

© 2007 General Electric Company All Rights Reserved

Agency Listings

Signature Series is a Trademark of GE Security.

Lexan - Red with white markings

Operating Temperature: 32ºF to 120ºF (0ºC to 49ºC) Storage Temperature: -4ºF to 140ºF (-20ºC to 60ºC) Humidity: 0 to 93% RH On-board Green LED - Flashes when polled On-board Red LED - Flashes w hen in alarm Both LEDs - Glow steady when in alarm (stand-alone) Use With: Signature Loop Controller UL, ULC (note 1), MEA, CSFM

Note: SIGC-270F, SIGC-270B and SIGC-270PB are ULC listed only. Suffix “F” indicates French markings. Suffix “B” indicates English/French biling ual markings.

Ordering Information Catalog Number SIGA-270 SIGC-270F SIGC-270B SIGA-270P SIGC-270PB SIGA-278 Accessories 32997 276-K2 276-K1 27165 270-GLR 276-GLR 276B-RSB

Description One Stage Fire Alarm Station, English Markings - UL/ULC Listed One Stage Fire Alarm Station, French Markings - ULC Listed One Stage Fire Alarm Station, French/English Markings - ULC Listed Two Stage (Presignal) Fire Alarm Station, English Markings - UL/ULC Listed Two Stage (Presignal) Fire Alarm Station, French/English Markings - ULC Listed Double Action (One Stage) Fire Alarm Station, English Markings - UL/ULC Listed

GA Key w/Tag - for pre-signal station (CANADA ONLY) GA Key - for pre-signal station (USA ONLY) Station Reset Key, Supplied with all Key Reset Stations 12 Glass Rods - for SIGA-270 series (CANADA ONLY) 20 Glass Rods - for SIGA-270 series (USA ONLY) 20 Glass Rods - for SIGA-278 series Surface Mount Box, Red - for SIGA pull stations

Ship Wt. lbs (kg)

1 (0.5)

0.1 (.05)

1 (0.6)

imagination at work Data Sheet 85001-0279 Issue 8 Not to be used for installation purposes. Page  of 4

GE Security

EST Life Safety & Communications Strobes, Horns, Bells & Chimes

Overview

• Unique low-profile design – The most compact UL-1971/ULC-S526 listed strobe available – Ultra-slim – protrudes less than one inch – Attractive appearance – No visible mounting screws

The Genesis line of fire alarm and mass notification/emergency communications (MNEC) signals are among the smallest, most compact audible-visible life safety signaling devices in the world. About the size of a deck of playing cards, these devices are designed to blend with any decor. Thanks to patented breakthrough technology, GE Security Genesis strobes do not require bulky specular reflectors and lenses. Instead, an exclusive cavity design conditions light to produce a highly controlled distribution pattern. Significant development efforts employing this new technology have given rise to a new benchmark in strobe performance – FullLight technology.

• Four field-configurable options in one device – Select 15, 30, 75, or 110 cd strobe output – Select high (default) or low dB horn output – Select temporal (default) or steady horn output – Select public mode flash rate (default) or private mode temporal flash • Fixed 15/75 cd model available

FullLight strobe technology produces a smooth light distribution pattern without the spikes and voids characteristic of specular reflectors. This ensures the entire coverage area receives consistent illumination from the strobe flash. As a result, Genesis strobes with FullLight technology go well beyond the UL-1971 and ULC-S526 light distribution requirements.

• MNEC models available

Genesis strobes and horn-strobes offer 15 to 110 candela output, which is selectable with a conveniently-located switch on the side of the device. Models are also available that offer fixed 15/75 cd output. The candela output setting remains clearly visible even after final installation, yet it stays locked in place to prevent unauthorized tampering.

• Unparalleled performance – Industry’s most even light distribution – Meets tough synchronizing standards for strobes – Single microprocessor controls both horn and strobe – Low current draw minimizes system overhead – Independent horn control over a single pair of wires – Highly regulated in-rush current – Multiple frequency tone improves sound penetration – Industry’s first temporal strobe output

Genesis MNEC appliances offer emergency signaling with clear or amber lenses and with optional ALERT housing labels. They are ideal for applications that require differentiation between fire alarm and mass notification alerts.

• Easy to install – Fits standard 1-gang electrical boxes – no trim plate needed – Optional trim plate accommodates oversized openings – Pre-assembled with captive hardware – #12 AWG terminals – ideal for long runs or existing wiring

Standard Features

Field Configurable Horns and Strobes Genesis Series

Pending

MNEC appliances available with clear or amber lenses.

Data Sheet 85001-0573 Issue 10 Not to be used for installation purposes. Page 1 of 6

Application

Installation

Genesis strobes are UL 1971-listed for use indoors as wall-mounted public-mode notification appliances for the hearing impaired. Prevailing codes require strobes to be used where ambient noise conditions exceed 105 dBA (87dBA in Canada), where occupants use hearing protection, and in areas of public accommodation as defined in the Americans with Disabilities Act (see application notes – USA).

Genesis horns and strobes mount to any standard one-gang surface or flush electrical box. Matching optional trim plates are used to cover oversized openings and can accommodate one-gang, two-gang, four-inch square, or octagonal boxes, and European 100 mm square. All Genesis signals come pre-assembled with captive mounting screws for easy installation. Two tabs at the top of the signal unlock the cover to reveal the mounting hardware. The shallow depth of Genesis devices leaves ample room behind the signal for extra wiring. Once installed with the cover in place, no mounting screws are visible.

Combination horn-strobe signals must be installed in accordance with guidelines established for strobe devices. Consult with your Authority Having Jurisdiction for details. All Genesis strobes exceed UL synchronization requirements (within 10 milliseconds over a two-hour period) when used with a synchronization source. Synchronization is important in order to avoid epileptic sensitivity. NOTE: The flash intensity of some visible signals may not be adequate to alert or waken occupants in the protected area. Research indicates that the intensity of strobe needed to awaken 90% of sleeping persons is approximately 100 cd. GE Security recommends that strobes in sleeping rooms be rated at at least 110 cd. WARNING: These devices will not operate without electrical power. As fires frequently cause power interruptions, further safeguards such as backup power supplies may be required.

Horns Genesis horn output reaches as high as 99 dB and features a unique multiple frequency tone that results in excellent sound penetration and an unmistakable warning of danger. Horns may be configured for either coded or non-coded signal circuits. They can also be set for low dB output with a jumper cut that reduces horn output by about 5 dB. Horn-only models may be ceiling-mounted or wall-mounted. The suggested sound pressure level for each signaling zone used with alert or alarm signals is at least 15 dB above the average ambient sound level, or 5 dB above the maximum sound level having a duration of at least 60 seconds, whichever is greater, measured 5 feet (1.5 m) above the floor. The average ambient sound level is, A-weighted sound pressure measured over a 24-hour period. Doubling the distance from the signal to the ear will theoretically result in a 6 dB reduction of the received sound pressure level. The actual effect depends on the acoustic properties of materials in the space. A 3 dBA difference represents a barely noticeable change in volume. MNEC Applications Genesis MNEC appliances bring the same high-performance fire alarm features and unobtrusive design to mass notification applications. Available with amber lenses and optional ALERT housing labels, they are ideal for applications that require differentiation between fire alarm and mass notification alerts.

Field Configuration

Genesis Horn/Strobe with optional trim plate

Temporal horn and horn-strobe models are factory set to sound in a three-pulse temporal pattern. Units may be configured for use with coded systems by cutting a jumper on the circuit board. This results in a steady output that can be turned on and off (coded) as the system applies and removes power to the signal circuit. A Genesis Signal Master is required when horn-strobe models are configured for coded systems. Non-temporal, horn-only models sound a steady tone. Genesis clear strobes and horn-strobes are shipped from the factory ready for use as UL 1971 compliant signals for public mode operation. These signals may be configured for temporal flash by cutting a jumper on the circuit board. This battery-saving feature is intended for private mode signaling only. Genesis clear strobes and horn-strobes may be set for 15, 30, 75, or 110 candela output. The output setting is changed by simply opening the device and sliding the switch to the desired setting. The device does not have to be removed to change the output setting. The setting remains visible through a small window on the side of the device after the cover is closed. Horns and horn-strobes are factory set for high dB output. Low dB output may be selected by cutting a jumper on the circuit board. This reduces the output by about 5 dB.

Wiring Field wiring terminals accommodate #18 to #12 AWG (0.75 mm² to 2.5 mm²) wiring. Horns, strobes, and combination horn-strobes are interconnected with a single pair of wires as shown below.

+ + Polarity shown in alarm condition

+

H

H

-

-

To next device or end of line device

Note: Strobes must have continuous voltage.

Data Sheet 85001-0573 Issue 10 Not to be used for installation purposes. Page 2 of 6

Current Draw Strobes, Horn-Strobes

Horns

Multi-cd Wall Strobes (G1-VM) 15 cd* 30 cd* 15/75 cd** RMS RMS RMS 16 Vdc 103 141 152 16 Vfwr 125 179 224 *G1-VM multi-cd; **G1F-V1575 fixed 15/75 cd UL Rating

Typical Current 16 Vdc 20 Vdc 24 Vdc 33 Vdc 16 Vfwr 20 Vfwr 24 Vfwr 33 Vfwr

15 cd RMS 85 71 59 46 119 103 94 87

30 cd RMS 127 98 82 64 169 143 129 112

15/75 RMS 150 123 104 84 223 189 169 148

75 cd* RMS 255 346

110 cd* RMS 311 392

75 cd RMS 245 188 152 112 332 253 218 179

110 cd RMS 285 240 191 137 376 331 262 205

Wall Temporal Horn-strobes – High dB Setting UL Rating 16 Vdc 16 Vfwr Typical Current 16 Vdc 20 Vdc 24 Vdc 33 Vdc 16 Vfwr 20 Vfwr 24 Vfwr 33 Vfwr

15 cd* RMS 129 176

30 cd* RMS 167 230

15 cd RMS 102 88 81 74 144 141 136 125

15/75 cd** RMS 172 269

75 cd* RMS 281 397

30 cd RMS 135 109 94 72 182 162 152 144

110 cd* RMS 337 443

*G1-HDVM multi-cd **G1F-HDV1575 fixed 15/75 cd

16 Vdc 16 Vfwr Typical Current 16 Vdc 20 Vdc 24 Vdc 33 Vdc 16 Vfwr 20 Vfwr 24 Vfwr 33 Vfwr

15 cd* RMS 122 162

30 cd* RMS 160 216

15 cd RMS 96 79 68 56 128 118 113 112

15/75 cd** RMS 146 231

75 cd* RMS 274 383

15/75 RMS 160 137 122 106 247 220 203 196

30 cd RMS 130 104 88 71 180 157 144 137

110 cd* RMS 330 429

UL Rating 16 Vdc 24 Vdc 33 Vdc 16 Vfwr 24 Vfwr 33 Vfwr

High dB (RMS) 26 36 41 51 69 76

Low dB (RMS) 19 27 33 37 52 70

Typical Current

High dB RMS 22 24 27 32 34 40 45 52

Low dB RMS 17 19 22 26 30 34 38 47

16 Vdc 20 Vdc 24 Vdc 33 Vdc 16 Vfwr 20 Vfwr 24 Vfwr 33 Vfwr

Wall or Ceiling Mounted Horns (G1-P) UL Designation

75 cd RMS 246 193 161 124 352 274 235 201

110 cd RMS 309 248 203 154 393 362 282 232

Regulated 24 Vdc 24 fwr

Max. Current, RMS 13 mA 11 mA

Voltage Range 16 - 33 Vdc 16 - 33 Vfwr

Typical Current 24 Vdc 24 Vdc 31 Vdc 20 Vfwr 24 Vfwr

RMS 10 11 12 9 10

Notes and Comments 1. Current values are shown in mA. 2. UL Nameplate Rating can vary from Typical Current due to measurement methods and instruments used.

Wall Temporal Horn-strobes – Low dB Setting UL Rating

Wall or Ceiling Mounted Temporal Horns (G1-HD)

3. GE Security recommends using the Typical Current for system design including NAC and Power Supply loading.

*G1-HDVM multi-cd **G1F-HDV1575 fixed 15/75 cd

15/75 RMS 158 133 119 100 241 213 195 182

75 cd RMS 243 189 156 118 344 266 230 197

110 cd RMS 302 241 197 146 389 343 279 226

4. Use the Vdc RMS current ratings for filtered power supply and battery AH calculations. Use the Vfwr RMS current ratings for unfiltered power supply calculations. 5. Fuses, circuit breakers and other overcurrent protection devices are typically rated for current in RMS values. Most of these devices operate based upon the heating affect of the current flowing through the device. The RMS current (not the mean current) determines the heating affect and therefore, the trip and hold threshold for those devices.

Data Sheet 85001-0573 Issue 10 Not to be used for installation purposes. Page 3 of 6

dBA output

Average Sound Output (dBA) (High dB setting, anechoic, 24V, measured at 10ft)

Temporal Horns, Horn-strobes (G1-HD, G1-HDVM series) UL464

High dB Setting

Temporal

Steady

16 Vdc 24 Vdc 33 Vdc

81.4 84.4 86.3

85.5 88.6 90.4 UL464

Low dB Setting

Temporal

Steady

16 Vdc 24 Vdc 33 Vdc

76.0 79.4 82.1

80.1 83.5 86.5

Average Temporal/ Steady 91.4 94.5 96.9

Peak Temporal/ Steady 94.2 97.6 99.5

Average Temporal/ Steady 86.3 89.8 92.5

Peak Temporal/ Steady 89.2 92.5 95.3

-90°

120 110 100 90

80

70

60

50

40

30

20

10

dBA 0 10

20

30

40

50

60

70

80

90 100 110 120

90°

75°

-75°

60°

-60°

45°

-45°

30°

-30° -15°

15°



Light output - (effective cd) Percent of UL rating versus angle

Steady Tone Horns (G1-P series) 16 Vdc 16 Vfwr

UL464 77 dBA, min 77 dBA, min

Average 85 dBA 85 dBA

Notes

Peak 91 dBA 91 dBA

120 110 100 90

80

70

60

50

40

30

Per Cent of UL Rating 20 10 0 10 20

30

40

50

60

70

80

90 100 110 120

90°

75°

-75°

1. All values shown are dBA measured at 10 feet (3.01m). 2. UL464 values measured in reverberant room.

60°

-60°

3. Average and Peak values are measured in anechoic chamber. 45°

-45°

30°

-30° -15°



15°

Specifications Housing Lens Mounting (indoor only) Wire connections Operating environment Agency listings/approvals Dimensions (HxWxD)

Operating voltage

Strobe output rating

Strobe flash rate

Synchronization Sources

Horn pulse rate Temporal audible pattern

Red or white textured UV stabilized, color impregnated engineered plastic. Exceeds 94V-0 UL flammability rating. Optical grade polycarbonate (clear) Strobes and horn-strobes are for wall-mount installation only. Horn-only models may be ceiling- or wall-mounted. Flush mount: 2½ inch (64 mm) deep one-gang box Surface mount: Model 27193 surface mount box, wiremold box, or equivalent surface-mount box With optional trim plate: One-gang, two-gang, four-inch square, octagonal, or European single-gang box Screw terminals: single input for both horn and strobe. #18 to #12 AWG (0.75 mm² to 2.5 mm²) wire size Indoor only: 32-120°F (0-49°C) ambient temperature. 93% relative humidity UL 1971, UL 1638, UL 464, ULC S525, ULC S526, CSFM, CE, FCC, MEA. (All models comply with ADA Code of Federal Regulation Chapter 28 Part 36 Final Rule.) Signal: 4-1/2” x 2-3/4” x 13/16” (113 mm x 68 mm x 21 mm) Trimplate: 5” (127 mm); Height – 5-7/8” (149 mm); Depth – ½” (13 mm) G1-HD series temporal-tone horns: non-coded, filtered 16-33 Vdc or unfiltered 16-33 Vdc FWR (or coded when horn set to steady tone) G1-HDVM series temporal-tone horn-strobes: non-coded, filtered 16-33 Vdc or unfiltered 16-33 Vdc FWR (or coded (audible NAC only) when used with optional G1M Genesis Signal Master) G1-VM series strobes: non-coded, filtered 16 - 33 Vdc or unfiltered 16-33 Vdc FWR G1-P series steady-tone horns: coded or non-coded, filtered 20-31 Vdc or unfiltered 20-27 Vfwr UL 1971, UL 1638, ULC S526: selectable 15 cd, 30 cd, 75 cd, or 110 cd output UL 1971: 15 cd (fixed 15/75 cd models) UL 1638, ULCS526: 75 cd (fixed 15/75 cd models) G1-VM strobes and G1-HDVM series temporal-tone horn-strobes: one flash per second synchronized with optional G1M Genesis Signal Master indefinitely within 10 milliseconds (or self-synchronized within 200 milliseconds over thirty minutes on a common circuit without G1M Genesis Signal Master) Temporal setting (private mode only): synchronized to temporal output of horns on same circuit SIGA-CC1S, SIGA-MCC1S, SIGA-CC2A, SIGA-MCC2A, G1M-RM BPS6A, BPS10A, APS6A, APS10A, iO64, iO500, Fireshield Plus 3, 5 and 10 zone. Add G1M for G1-CVM &G1-HDVM devices only. G1-HD temporal-tone horns and G1-HDVM series temporal-tone horn-strobes: temporal rate synchronized with optional G1M Genesis Signal Master indefinitely within 10 milliseconds (or self-synchronized within 200 milliseconds over thirty minutes on a common circuit without G1M Genesis Signal Master) G1-P steady-tone horns: continuous, steady tone only ½ sec ON, ½ sec OFF, ½ sec ON, ½ sec OFF, ½ sec ON, 1½ sec OFF, then repeat cycle Data Sheet 85001-0573 Issue 10 Not to be used for installation purposes. Page 4 of 6

Fire appliances available with white or red housings.

MNEC appliances available with clear or amber lenses.

Ordering Information Model

Housing

Marking

Lens

Strobe

Horn

Ship Wt. lbs (kg)

Fire Alarm Appliances (c/w running man icon screen printed on housing) G1-VM White None Clear Selectable 15, 30, 75, or 110 cd Strobe only G1F-HD White FIRE Clear Horn only Selectable high/low dB G1F-HDV1575 White FIRE Clear 15/75 cd¹ Temporal hi/lo dB-24V G1F-HDVM White None Clear Selectable 15, 30, 75, or 110 cd Selectable high/low dB G1F-P White FIRE Clear Steady Horn (not compatible with Genesis Signal Master) G1F-V1575 White FIRE Clear 15/75 cd¹ Strobe only G1F-VM White FIRE Clear Selectable 15, 30, 75, or 110 cd Strobe only G1-HD White None Clear Horn only Selectable high/low dB G1-HDVM White None Clear Selectable 15, 30, 75, or 110 cd Selectable high/low dB G1-P White None Clear Steady Horn (not compatible with Genesis Signal Master) G1RF-HD Red FIRE Clear Horn only Selectable high/low dB G1RF-HDV1575 Red FIRE Clear 15/75 cd¹ Temporal hi/lo dB-24V G1RF-HDVM Red None Clear Selectable 15, 30, 75, or 110 cd Selectable high/low dB G1RF-P Red FIRE Clear Steady Horn (not compatible with Genesis Signal Master) G1RF-V1575 Red FIRE Clear 15/75 cd¹ Strobe only G1RF-VM Red FIRE Clear Selectable 15, 30, 75, or 110 cd Strobe only G1R-HD Red None Clear Horn only Selectable high/low dB G1R-HDVM Red None Clear Selectable 15, 30, 75, or 110 cd Selectable high/low dB G1R-P Red None Clear Steady Horn (not compatible with Genesis Signal Master) G1R-VM Red None Clear Selectable 15, 30, 75, or 110 cd Strobe only

0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25

(0.11) (0.11) (0.11) (0.11) (0.11) (0.11) (0.11) (0.11) (0.11) (0.11) (0.11) (0.11) (0.11) (0.11) (0.11) (0.11) (0.11) (0.11) (0.11) (0.11)

MNEC Appliances (no running man icon on housing) G1WA-HDVMA White ALERT Amber G1WA-HDVMC White ALERT Clear G1WA-VMA White ALERT Amber G1WA-VMC White ALERT Clear G1WN-HDVMC White None Clear G1WN-VMA White None Amber G1WN-VMC White None Clear

Selectable A, B, C or D Selectable 15, 30, 75, or 110 cd Selectable A, B, C or D Selectable 15, 30, 75, or 110 cd Selectable 15, 30, 75, or 110 cd Selectable A, B, C or D Selectable 15, 30, 75, or 110 cd

0.25 0.25 0.25 0.25 0.25 0.25 0.25

(0.11) (0.11) (0.11) (0.11) (0.11) (0.11) (0.11)

Lens Kits G1LK-A G1LK-B G1LK-G G1LK-R

G1 Field replaceable lens kit, amber G1 Field replaceable lens kit, blue G1 Field replaceable lens kit, green G1 Field replaceable lens kit, red

N/A N/A N/A N/A

N/A N/A N/A N/A

Trim Plates G1T G1RT G1T-FIRE G1RT-FIRE G1WT-ALERT

White Red White Red White

None None FIRE FIRE ALERT

Surface Boxes 27193-16 27193-11

White Red

N/A N/A

Amber Blue Green Red

Selectable high/low dB Selectable high/low dB Strobe only Strobe only Selectable high/low dB Strobe only Strobe only

Genesis Trim Plate (for two-gang or 4” square boxes) Genesis Trim Plate (for two-gang or 4” square boxes) Genesis Trim Plate (for two-gang or 4” square boxes) Genesis Trim Plate (for two-gang or 4” square boxes) Genesis Trim Plate (for two-gang or 4” square boxes)

One-gang surface mount box One-gang surface mount box

0.15 (0.7) 0.15 (0.7) 0.15 (0.7) 0.15 (0.7) 0.15 (0.7)

1 (0.4) 1 (0.4)

¹ These 15/75 cd models provide fixed output and are not multi-candela devices. The 15 cd output component complies with UL1971, while the 75 cd output component complies with UL 1638.

Data Sheet 85001-0573 Issue 10 Not to be used for installation purposes. Page 5 of 6

GE Security U.S. T 888-378-2329 F 866-503-3996 Canada T 519 376 2430 F 519 376 7258 Asia T 852 2907 8108 F 852 2142 5063 Australia T +61 3 9239 1200 F +61 3 9239 1299 Europe T 32 2 725 11 20 F 32 2 721 86 13 Latin America T 305 593 4301 F 305 593 4300 www.gesecurity.com/est © 2009 General Electric Company All Rights Reserved. Genesis Series is a trademark of GE Security.

Data Sheet 85001-0573 Issue 10 Not to be used for installation purposes. Page 6 of 6

Life Safety Systems Notification Appliances

Overview

Standard Features

GE Security 439D Series Vibrating Bells are specially designed for Fire Alarm applications. The gongs are made from select alloy steel chosen to give the loud, resonant tones necessary in fire alarm and life safety systems. Two sizes of gongs are available to help overcome different ambient noise levels.

• Mounts to 1-gang opening

GE Security 439D Bells are the “under-dome” type and use heavy duty mechanisms. The bell’s die-cast aluminum base and gong are finished with a durable “Fire Red” baking enamel.

• Low current draw

All 439D Bells are supplied with a universal mounting plate that fits any standard North-American 1-gang electrical box opening. This same plate also allows the bell to mount on any standard NorthAmerican 3-1/2 or 4 inch octagon box, or 4 inch square electrical box. Both the 6 and 10 inch (150 and 250mm) size bells utilize the same mounting plate and can therefore be easily interchanged.

• Weatherproof mounting option

• Plug-in design • Heavy duty mechanism • Loud resonant tones • 6" and 10" (150 and 250mm) size • “Fire Red” Finish

Field wiring connections are made to a ‘quick-connect’ plug with colour-coded leads. The bell just plugs-in and is fastened to the bell’s mounting plate. For weatherproof applications, GE Security offers the catalogue number 449 optional Surface Weatherproof Backbox. (Refer to literature sheet #85001-0309.) Yard hoods and protective grilles for protecting the bell from the elements are also available.

Vibrating Bells - 24 Vdc 439D Series

439D-10AWC

439D-6AWC

Data Sheet 85001-0123 Issue 1 Not to be used for installation purposes. Page  of 4

Installation GE Security 439D series Fire Alarm Bells are high quality signalling appliances. GE Security recommends that they always be installed in accordance with the latest recognized edition of local fire alarm codes.

Typical Wiring

Data Sheet 85001-0123 Issue 1 Not to be used for installation purposes. Page  of 4

Specifications Catalogue Number Gong Size — Diameter dBA Level at 10’ (3.05m) Type of Operation Operating Voltage Range Operating Current Finish Approvals and Listings Ambient Operating Environment

439D-6AWC 439D-10AWC 6” (150mm) 10” (250mm) 92 94 Vibrating 20 to 24Vdc 85 mA “Fire Red” Baking Enamel ULC — S525, FM — 3151-3152 (Indoor Only) Temperature: -40°C to 66°C, Relative Humidity: 93%

Ordering Information Catalogue No. 439D-6AWC 439D-10AWC

Description 6” (150mm) Fire Alarm Bell , Red Finish 10” (250mm) Fire Alarm Bell, Red Finish

Ship Wt. (kg) 1.0 1.5

Accessories 449 512-1 512-10 512-2 512-3 513-1 513-10 513-2 513-3

Weatherproof Backbox c/w Gasket and Grey Finish — for Surface Mounting 439D Series Bell Wallbox — for flush mounting 439D-6AWC into wall Ceiling Box — for flush mounting 439D-6AWC into ceiling Grille c/w Prime Paint Coat for 512 Series Backbox Grille c/w Brushed Stainless Steel Finish — for 512 Series Backbox Wallbox — for flush mounting 439D-10AWC into wall Ceiling Box — for flush mounting 439D-10AWC into ceiling Grille c/w Prime Paint Coat for 513 Series Backbox Grille c/w brushed Stainless Steel Finish — for 513 Series Backbox

0.3 2.5 3.5 1.0 1.0 4.5 6.0 1.5 1.5

Data Sheet 85001-0123 Issue 1 Not to be used for installation purposes. Page  of 4

U.S. T 888-378-2329 F 866-503-3996 Canada T 519 376 2430 F 519 376 7258 Asia T 852 2907 8108 F 852 2142 5063 Australia T 61 3 9259 4700 F 61 3 9259 4799 Europe T 32 2 725 11 20 F 32 2 721 86 13 Latin America T 305 593 4301 F 305 593 4300 www.gesecurity.com © 2006 General Electric Company All Rights Reserved

Data Sheet 85001-0123 Issue 1 Not to be used for installation purposes. Page  of 4

GE Security

EST Life Safety & Communications Power Supplies

Overview

Standard Features

The Booster Power Supply (BPS) is a UL 864, 9th Edition listed power supply. It is a 24 Vdc filtered-regulated, and supervised unit that can easily be configured to provide additional notification appliance circuits (NACs) or auxiliary power for Mass Notification/Emergency Communication (MNEC), as well as life safety, security, and access control applications.

• Allows for reliable filtered and regulated power to be installed where needed

The BPS contains the circuitry to monitor and charge internal or external batteries. Its steel enclosure has room for up to two 10 ampere-hour batteries. For access control-only applications, the BPS can support batteries totaling up to 65 ampere-hours in an external enclosure. The BPS has four Class B (convertible to two Class A) NACs. These can be activated in one or two groups from the BPS’s unique dual input circuits. The BPS is available in 6.5 or 10 ampere models. Each output circuit has a capacity of three amperes; total current draw cannot exceed the unit’s rating. The BPS meets current UL requirements and is listed under the following standards: Standard (CCN) UL864 9th ed.ition (UOXX) UL636 (ANET, UEHX7) UL609 (AOTX, AOTX7) UL294 (ALVY, UEHX7) UL365 (APAW, APAW7) UL1076 (APOU, APOU7) UL1610 (AMCX) ULC-S527 (UOXXC) ULC-S303 (AOTX7) ULC-S304 (AMCX7) C22.2 No. 205

Description Fire Alarm Systems Holdup Alarm Units and Systems Local Burglar Alarm Units and Systems Access Control Systems Police Station Connected Burglar Alarm Units and Systems Proprietary Burglar Alarm System Units Central Station Alarm Unit Control Units, Fire Alarm (Canada) Local Burglar Alarm Units and Systems (Canada) Central and Monitoring Station Burglar Alarm Units (Canada) Signaling Equipment (Canada)

• Cost effective system expansion • Provides for Genesis and Enhanced Integrity notification appliance synchronization • Supports coded output operation • Self-restoring overcurrent protection • Multiple signal rates • Can be cascaded or controlled independently • Easy field configuration • On-board diagnostic LEDs identify wiring or internal faults • Standard GE Security keyed lockable steel cabinet with removable door • 110 and 230 Vac models available • Accommodates 18 to 12 AWG wire sizes • Optional tamper switch • Dual battery charging rates

Remote Booster Power Supplies BPS6A, BPS10A

Data Sheet 85005-0125 Issue 3 Not to be used for installation purposes. Page 1 of 4

Application

Dimensions

The BPS provides additional power and circuits for notification appliances and other 24 Vdc loads. It is listed for indoor dry locations and can easily be installed where needed.

D5

Fault conditions are indicated on the on-board diagnostic LEDs, opening the BPS input sense circuit and the trouble relay (if programmed). While this provides indication to the host system, the BPS can still be activated upon command. A separate AC Fail contact is available on the BPS circuit board, which can be programmed for trouble or AC Fail. There are seven on-board diagnostic LEDs: one for each NAC fault, one for battery fault, one for ground fault, and one for AC power.

BPS NACs can be configured for a 3-3-3 temporal or continuous output. California temporal rate outputs are also available on certain models. This makes the BPS ideal for applications requiring signaling rates that are not available from the main system. In addition to the internally generated signal rates, the BPS can also be configured to follow the coded signal rate of the main system NACs. This allows for the seamless expansion of existing NACs.

D2

D3

Side View

D4

Front View

D1

D6

Side View

The unique dual-input activation circuits of the BPS can be activated by any voltage from 6 to 45 VDC (filtered-regulated) or 11 to 33 Vdc (full-wave rectified, unfiltered). The first input circuit can be configured to activate 1-4 of the four possible outputs. The second input circuit can be configured to control circuits 3 and 4. When outputs are configured for auxiliary operation, these circuits can be configured to stay on or automatically deactivate 30 seconds after AC power is lost. This feature makes these circuits ideal for door holder applications. The BPS also has a separate 200 mA 24 Vdc output that can be used to power internal activation modules.

Top View

All knockouts for 3/4 in conduit (1.9 cm)

D1

D2

D3

D4

D5

D6

17.0 in (43.2 cm)

3.5 in (8.9 cm)

13.0 in (33.0 cm)

6.5 in (16.5 cm)

3.375 in (8.6 cm)

12.0 in (30.4 cm)

Wire routing

The BPS enclosure has mounting brackets for up to three Signature modules to the right of the circuit board.

Engineering Specification Supply, where needed, GE Security BPS Series Booster Power Supplies (BPS) that are interconnected to and supervised by the main system. The BPS shall function as a stand-alone auxiliary power supply with its own fully-supervised battery compliment. The BPS battery compliment shall be sized to match the requirements of the main system. The BPS shall be capable of supervising and charging batteries having the capacity of 24 ampere-hours for Mass Notification/Emergency Communication (MNEC), life safety and security applications, and the capacity of 65 ampere-hours for access control applications. The BPS shall provide a minimum of four independent, fully supervised Class B circuits that can be field configurable for notification appliance circuits or auxiliary 24 Vdc power circuits. BPS NACs shall be convertible to a minimum of two Class A NACs. Each BPS output circuit shall be rated at 3 amperes at 24 Vdc. Each output circuit shall be provided with automatically restoring overcurrent protection. The BPS shall be operable from the main system NAC and/or GE Security Signature Series control modules. BPS NACs shall be configurable for continuous, 3-3-3 temporal or optionally, California rate. Fault conditions on the BPS shall not impede operation of main system NAC. The BPS shall be provided with ground fault detection circuitry and a separate AC fail relay.

Notes 1. Maintain 1/4-inch (6 mm) spacing between power-limited and nonpower-limited wiring or use type FPL, FPLR, or FPLP cable per NEC. [2] Power-limited and supervised when not configured as auxiliary power. Non-supervised when configured as auxiliary power. [3] Source must be power-limited. Source determines supervision. 4. When using larger batteries, make sure to position the battery terminals towards the door.

Data Sheet 85005-0125 Issue 3 Not to be used for installation purposes. Page 2 of 4

Typical Wiring To next signaling device, booster, or EOL resistor

NAC Circuit NAC Circuit

Single or castcaded booster anywhere on a notification appliance circuit

Fire Alarm Control Panel

Sense 2 Input

Sense 1 Input

Existing NAC end-of-line resistors are not required to be installed at the booster’s terminals. This allows multiple boosters to be driven from a single NAC circuit without the need for special configurations.

NAC output #1 NAC output #2 NAC output #3 NAC output #4

Booster Power Supply

Configuring the Booster for AC Power Fail delay operation* Notification appliance circuit (NAC)

10 9

EOL 47 kÙ

CC1(S) module [1][3] 8765

+

TB2 CT1 module [4]

Data in from previous + + device or Signature controller

4 321

+ +

Data in from previous device or Signature controller Data out to next device

+ +

IN Sense 1 COM OUT IN Sense 2 COM OUT NO Trouble COM NC

EOL 47 K

+

+

UL listed EOL 15 KW

+

+ +

200 mA AUX Continuous

Notification appliance circuit (NAC)

+

UL listed EOL 15 kÙ

UL listed EOL 15 KW

+

+ +

Notification appliance circuit (NAC)

+ TB5

IN Sense 1 COM OUT IN Sense 2 COM OUT NO Trouble COM NC

Notification appliance circuit (NAC)

TB1

NAC1/ AUX1 NAC2/ AUX2 NAC3/ AUX3 NAC4/ AUX4

UL listed EOL 15 kÙ

TB5

+

TB1

NAC1/ AUX1 NAC2/ AUX2 NAC3/ AUX3 NAC4/ AUX4 200 mA AUX Continuous

Multiple CC1(S) modules using the BPS’s sense inputs

EOL 47 K

+

+

10 9

CC1(S) module

TB2

Data out to next device

10 9

8765

+ +

CC1(S) module

4 321

[1]

4 321

8765

[1]

+ +

[3]

*The Booster supports AC Power fail delay of three hours via its trouble contact when dip switch SW2-6 is on. All other troubles are reported to supervising module or panel without delay via Sense inputs.

Security and access BPS 24 V

12 V Security device

24DC12

EOL monitoring device

Security device

+

+

+

+

TB1

NAC1/ AUX1 NAC2/ AUX2 NAC3/ AUX3 NAC4/ AUX4

Control panel

+ [1] Disable the BPS’s ground fault jumper (JP3)

BPS [1] Card reader controller

+

Card reader controller

+

+

Card reader controller

+

To next device or end

Data Sheet 85005-0125 Issue 3 Not to be used for installation purposes. Page 3 of 4

GE Security U.S. T 888-378-2329 F 866-503-3996 Canada T 519 376 2430 F 519 376 7258 Asia T 852 2907 8108 F 852 2142 5063 Australia T +61 3 9239 1200 F +61 3 9239 1299 Europe T 32 2 725 11 20 F 32 2 721 86 13 Latin America T 305 593 4301 F 305 593 4300 www.gesecurity.com/est © 2009 General Electric Company All Rights Reserved

Specifications Model

6.5 amp Booster 120VAC or 220-240VAC 50/60Hz 390 watts

Notification Appliance Circuit Ratings

3.0A max. per circuit @ 24Vdc 3.0A max. per circuit @ 24Vdc nominal 10A max total all NACs nominal 6.5A max total all NACs 2 Amps @ 30Vdc

Trouble Relay Auxiliary Outputs Input Current (from an existing NAC)

Four configurable outputs replace NACs 1, 2, 3 or 4. as auxiliary outputs and 200 mA dedicated auxiliary. (See note 2.) 3mA @ 12Vdc, 6mA @ 24Vdc 70mA

Booster Internal Supervisory Current

Accomodates three two-gang modules.

Signature Mounting Space Maximum Battery Size

10 Amp Hours (2 of 12V10A) in cabinet up to 24 Amp hours with external battery cabinet for fire and security applications; up to 65 Amp hours for access control applications in external battery box.

Terminal Wire Gauge Relative Humidity Temperature Rating NAC Wiring Styles

32° to 120°F (0° to 49°C) Class A or Class B

Ground Fault Detection Agency Listings 1. 2.

18-12 AWG 0 to 93% non condensing @ 32°C

Output Signal Rates Signature Series is a Trademark of GE Security.

10 amp Booster 120VAC or 220-240VAC 50/60Hz 580 watts

AC Line Voltage

Continuous, California rate, 3-3-3 temporal, or follow installed panel’s NAC. (See note 1.) Enable or Disable via jumper UL, ULC, CSFM

Model BPS*CAA provides selection for California rate, in place of temporal. Maximum of 8 Amps can be used for auxiliary output.

Ordering Information Catalog Number BPS6A BPS6AC BPS6A/230 BPS6CAA BPS10A BPS10AC BPS10A/230 BPS10CAA

Description 6.5 Amp Booster Power Supply 6.5 Amp Booster Power Supply (ULC) 6.5 Amp Booster Power Supply (220V) 6.5 Amp Booster Power Supply with California rate 10 Amp Booster Power Supply 10 Amp Booster Power Supply (ULC) 10 Amp Booster Power Supply (220V) 10 Amp Booster Power Supply with California rate

Related Equipment 12V6A5 7.2 Amp Hour Battery, two required 12V10A 10 Amp Hour Battery, two required 3-TAMP Tamper switch BC-1 Battery Cabinet (up to 2 - 40 Amp Hour Batteries) BC-2 Battery Cabinet (up to 2 - 17 Amp Hour Batteries) 12V17A 18 Amp Hour Battery, two required (see note 1) 12V24A 24 Amp Hour Battery, two required (see note 1) 12V40A 40 Amp Hour Battery, two required (see notes 1, 2) 12V50A 50 Amp Hour Battery, two required (see notes 1, 2) 12V65A 65 Amp Hour Battery, two required (see notes 1, 2) 1. 2.

Shipping Wt. lb (kg) 13 ( 5.9) 13 ( 5.9) 13 ( 5.9) 13 ( 5.9) 13 ( 5.9) 13 ( 5.9) 13 ( 5.9) 13 ( 5.9)

3.4 (1.6) 9.5 (4.3) 58 (26.4) 19 (8.6) 13 ( 5.9) 20 (9.07) 32 (14.5) 40 (18.14) 49 (22.2)

Requires installation of separate battery cabinet. BPS supports batteries greater than 24 Amp hours for access control applications only.

Data Sheet 85005-0125 Issue 3 Not to be used for installation purposes. Page 4 of 4

Life Safety Systems Accessories

Overview

Application

Rechargeable sealed lead-acid batteries are ideal for use as a secondary (standby) power source as defined by NFPA 72. Their low maintenance and high energy density make them ideal for fire alarm signaling applications.

When multiple power supplies are provided, each power supply’s battery requirements should be calculated individually. Consult the specific system manual to determine battery capacity requirements.

Standard Features • Rechargeable • Non-spillable • Non-hazardous

Safety Information Due to a battery’s low internal resistance and high power density, high levels of short circuit current can develop across battery terminals. Put on protective eye covering and remove all jewelry before working on batteries. Do not rest tools or cables on the battery, and only use insulated tools. Follow all manufacturers installation instructions and diagrams when installing or maintaining batteries.

• Low maintenance • High energy density

Sealed Lead-Acid Batteries

Data Sheet 85010-0127 Issue 3 Not to be used for installation purposes. Page  of 2

U.S. T 888-378-2329 F 866-503-3996 Canada T 519 376 2430 F 519 376 7258 Asia T 852 2907 8108 F 852 2142 5063 Australia T 61 3 9259 4700 F 61 3 9259 4799 Europe T 32 2 725 11 20 F 32 2 721 86 13 Latin America T 305 593 4301 F 305 593 4300 www.gesecurity.com © 2006 General Electric Company All Rights Reserved

Specifications Case Material Regulatory Information Operating Environment

ABS Thermoplastic DOT Class 60, Batteries, non-hazardous, non-spillable 32° F to 120° F (0° C to 49° C) 0 to 93% RH, Non-condensing

Ordering Information Catalog Number 12V1A2 12V4A 12V6A5 6V8A 6V10A 12V10A 12V17A 12V24A 12V40A 12V50A 12V65A

Description 1.2 Ah Sealed Lead Acid Battery - 12 Vdc 4.5 Ah Sealed Lead Acid Battery - 12 Vdc 7.2 Ah Sealed Lead Acid Battery - 12 Vdc 8 Ah Sealed Lead Acid Battery - 6 Vdc 12 Ah Sealed Lead Acid Battery - 6 Vdc 11 Ah Sealed Lead Acid Battery - 12 Vdc 18 Ah Sealed Lead Acid Battery - 12 Vdc 26 Ah Sealed Lead Acid Battery - 12 Vdc 40 Ah Sealed Lead Acid Battery - 12 Vdc 50 Ah Sealed Lead Acid Battery - 12 Vdc 65 Ah Sealed Lead Acid Battery - 12 Vdc

Shipping Weight, lb (kg) 1.25 (0.57) 5 (2.27) 6 (2.72) 4 (1.81) 5 (2.27) 10 (4.45) 13 (5.90) 20 (9.07) 32 (14.51) 40 (18.14) 49 (22.23)

Data Sheet 85010-0127 Issue 3 Not to be used for installation purposes. Page  of 2

View more...

Comments

Copyright ©2017 KUPDF Inc.
SUPPORT KUPDF