DRS_setting Calculation Reference 1
Short Description
Download DRS_setting Calculation Reference 1...
Description
SETTING CALCULATION NUMERICAL PROTECTION SYSTEM
2 X 50 MW MALANA-II HYDRO ELECTRIC PROJECT
CLIENT :
ABIR INFRASTRUCTURE PVT. LTD.
MALANA-II HYDRO ELECTRIC PROJECT
Rev.
Modification
Date
Check
Date
Drawn:
DD.MM.YYYY
SS
Checked:
DD.MM.YYYY
SS
Approved:
DD.MM.YYYY
SKV
Appd PROJECT NO: C. 290
PLANT: 2 X 50 MW MALANA-II HYDRO ELECTRIC PROJECT
= FU
PLN
= LO CUSTOMER No:
SETTINGCALCULATION NUMERICAL PROTECTION SYSTEM
Internal Drawing Number:
Rev.
2 783001
0
Page 1 of 29
THIS DOCUMENT IS THE PROPERTY OF VA TECH HYDRO AND MUST NEITHER BE COPEID NOR USED IN ANY OTHER WAY WIHTOUT THE WRITTEN CONSENT OF VA TECH HYDRO NEITHER IT IS TO BE HANDED OVER, NOR IN OTHER WAY COMMUNICATED TO A THIRD PARTY. INFRINGMENT WILL LEAD TO PROSECUTION
SETTING CALCULATION NUMERICAL PROTECTION SYSTEM
2 X 50 MW MALANA-II HYDRO ELECTRIC PROJECT
SETTING CALCULATION FOR DIGITAL PROTECTION SYSTEM
Table of Contents
1.
GENERAL ............................................................................................................................3
2.
TECHNICAL DATA ..............................................................................................................4
3.
GENERATOR, TRANSFORMER AND UNIT AUXILIARY TRANSFORMER PROTECTION ...6 A) B) C) D) E) F) G) H) I) J) K) L) M) N) O) P) Q) R) S)
4.
GENERATOR DIFFERENTIAL PROTECTION 87G .............................................................. 6 GENERATOR UNDEREXCITATION PROTECTION 40G....................................................... 7 GENERATOR NEGATIVE PHASE SEQUENCE PROTECTION 46G ........................................ 8 GENERATOR OVERVOLTAGE PROTECTION 59................................................................ 9 GENERATOR UNDERVOLTAGE PROTECTION 27G ......................................................... 10 GENERATOR OVER/UNDERFREQUENCY PROTECTION 81O/U ........................................ 10 GENERATOR STATOR EARTH FAULT PROTECTION 64G1 .............................................. 11 GENERATOR STATOR EARTH FAULT PROTECTION 64G2 .............................................. 11 ROTOR EARTH FAULT PROTECTION 64R ..................................................................... 12 GENERATOR REVERSE POWER PROTECTION 32G ........................................................ 13 VOLTAGE SUPERVISION FUNCTION 60G, 60M AND 60A ............................................... 13 GENERATOR UNDERIMPEDANCE PROTECTION 21G ..................................................... 14 DEAD MACHINE 27/51V .............................................................................................. 15 UNIT DIFFERENTIAL PROTECTION 87GT ..................................................................... 16 RESTRICTED EARTH FAULT PROTECTION 64REF ......................................................... 17 RESTRICTED EARTH FAULT PROTECTION 64REF- DISCRETE RELAY ............................. 19 OVERFLUXING PROTECTION 99G ................................................................................ 21 UAT DIFFERENTIAL PROTECTION 87UAT..................................................................... 21 UAT OVERCURRENT PROTECTION 50U/51U................................................................. 22 DISTANCE PROTECTION .................................................................................................23
MALANA-II HEP
Page 2 of 29
SETTING CALCULATION NUMERICAL PROTECTION SYSTEM
2 X 50 MW MALANA-II HYDRO ELECTRIC PROJECT
1.GENERAL This document provides information about the various protective schemes for the unit transformer protection, generator protection and UAT. The document lists the particular protective functions as how they overlap and complement each other for back-up and outlines the philosophy about the selection of the protection setting values. Please note that the generator and transformer characteristics and capability curves and data are contained in separate documents. Also the documentation with detailed descriptions of the various protection systems are provided in separate relay documents. Note: The calculated relay settings are based on different data sheets available during the workout (e.g. generator data sheet, CB data, and single line diagram) of the document. In case of any equipment modification or change of various electrical characteristics this document has to be revised. Therefore all the settings have to be checked and revised during the commissioning on site. Generally the calculation of the settings is done according to our best knowledge and conscience. So we can’t accept any responsibility for errors included in the document. Further we are not liable for any incident or damage resulting from the content of this setting calculation. Some protection settings (e.g. frequency, voltage) have to be checked and approved also from the power distribution owner.
MALANA-II HEP
Page 3 of 29
SETTING CALCULATION NUMERICAL PROTECTION SYSTEM
2 X 50 MW MALANA-II HYDRO ELECTRIC PROJECT
2. TECHNICAL DATA Generator: GENERATOR OUTPUT= RATED VOLTAGE= POWER FACTOR RATED CURRENT RATED FREQUENCY SYNCRONOUS REACTANCE TRANSIENT REACTANCE (STAURATED) NEGETIVE PHASE SEQUENCE WITHSTAND UNBALANCED LOAD FIELD CURRENT STATOR LEAKAGE REACTANCE SYNCRONOUS REACTANCE QUARD AXIS
Sn Un p.f. In fn Xd Xd' I2 (I2/IN)²xt If xs Xq
55560.00 11 0.9 2915.9 50 93.30% 26% 8% 20 875 0.0952 0.602
kVA kV
Un Sn Uk
11/132 63.9 12.5 % YNd11
kV MVA
Un Sn
11000/415 500 Dyn11
V KVA
Un Sn
11000/364 630 Dy5
V KVA
R1 X1 R0 X0 L L1 L2
0.14 0.387 0.272 1.233 70 30 30
A Hz
sec Adc PU PU
Step up transformer RATED VOLTAGE RATED OUTPUTS SHORT CIRCUIT VOLTAGE VECTOR GROUP Auxiliary Transformer : RATED VOLTAGE RATED OUTPUTS VECTOR GROUP Excitation Transformer : RATED VOLTAGE RATED OUTPUTS VECTOR GROUP Line Parameters: POSITIVE SEQUENCE RESISTANCE POSITIVE SEQUENCE REACTANCE ZERO SEQUENCE RESISTANCE ZERO SEQUENCE RESISTANCE LINE LENGTH LENGTH OF NEXT SHORTEST LINE LENGTH OF NEXT LONGEST LINE
MALANA-II HEP
OHMS/KM OHMS/KM OHMS/KM OHMS/KM KM KM KM
Page 4 of 29
SETTING CALCULATION NUMERICAL PROTECTION SYSTEM Current Transformer GENERATOR TRANSFORMER HV SIDE GENERATOR TRANSFORMER NEUTRAL GENERATOR NEUTRAL GENERATOR TERMINAL AUX TRANSFORMER HV SIDE (OVERALL DIFF) GENERATOR TRANSFORMER HV SIDE (DIFF) AUX TRANSFORMER HV SIDE (OVERCURRENT PROT) Voltage transformer PROTECTION CORE AVR CORE NEUTRAL TRANSFORMER METERING CORE LINE PT
MALANA-II HEP
2 X 50 MW MALANA-II HYDRO ELECTRIC PROJECT
Primary 400A 400A 4000A 4000A 4000A 600A
Secondary 1A 1A 5A 5A 5A 1A
100A
1A
Primary 11000V 11000V 11000V 11000V 110000V
Secondary 110V 110V 110V 110V 110V
Page 5 of 29
SETTING CALCULATION NUMERICAL PROTECTION SYSTEM
2 X 50 MW MALANA-II HYDRO ELECTRIC PROJECT
3.GENERATOR, TRANSFORMER AND UNIT AUXILIARY TRANSFORMER PROTECTION
A) GENERATOR DIFFERENTIAL PROTECTION 87G This function protects the generator system from the neutral CTs to the generator terminal CTs. When function operates, the unit will be shut down immediately. The differential setting value is calculated as follows:
Igp
Sn 55560kVA 2916.14 A Generator primary current Un 3 11kV 3
Now with a CT ratio = 4000/5 A the generator secondary current is calculated
Igs
Igp 2916.14A 5 A 3.65 A Generator secondary current CTratio 4000 A
The differential current setting is chosen to be 20% of the relay current rating, i.e.
I 87 s 0.20 5 A 1A This is in turn the equivalent to the generator rated current.
I %
I 87 s 1A 100 100 27.4% Igs 3.65 A
The bias slope is set to
bias 40%
Setting Name of parameter Operate Value Bias
MALANA-II HEP
Range 1A 40%
Page 6 of 29
SETTING CALCULATION NUMERICAL PROTECTION SYSTEM
2 X 50 MW MALANA-II HYDRO ELECTRIC PROJECT
B) GENERATOR UNDEREXCITATION PROTECTION 40G The under excitation MHO protection is used to detect failures in the excitation system of synchronous generators and to prevent damage to the equipment and power swings in the system. The given direct reactances are Synchronous reactance Transient reactance (saturated)
xd xd´
93.3% 26%
A compensation factor F must be determined according to the equation below, in order to adjust the reactances to the CT and VT ratios:
F
VG CTratio Ir 11000V 4000 A 110V 5A 1.5 IG VTratio Vr 2916.14 A 5 A 11000V 100V
where Ir … Vr …
rated current of the relay rated voltage of the relay (100V internally)
So the adapted reactances are
xd F xd 1.5 0.933 pU 1.399 pU xd ' F xd ' 1.5 0.255 pU 0.382 pU The relay function setting is calculated as follows.
Diameter xd 1.40 pU Center
xd ' xd 0.382 pU 1.4 pU 0.891 pU 2 2 2 2
The relay will be set to the next possible set point: Diameter: 1.4 pU Center: 0.89 pU The Time Delay Stage 1 is set to 5 sec. The parameters Operate Value St. 2, Rotor Cur. Comp., Rotor Cur. Offset has no relevance. Stage 2 is using the following logical function: Underexcitation Stage 1 Pickup Undervoltage 27/40 Pickup
&
Time Delay Stage 2
Trip
The Time Delay Stage 2 is set to 1 sec. The Operate Value of the Function "27/50" is set to 50V.
MALANA-II HEP
Page 7 of 29
SETTING CALCULATION NUMERICAL PROTECTION SYSTEM
2 X 50 MW MALANA-II HYDRO ELECTRIC PROJECT
C) GENERATOR NEGATIVE PHASE SEQUENCE PROTECTION 46G
The calculation of the setting values is done according to e.g. following generator data: Rated power SG =55560 KVA Rated voltage VG = 11 kV Negative phase sequence current withstand 8% Therefore the generator primary current is
Igp
Sg 55560kVA 2916.14 A Vgp 3 11kV 3
and by using a current transformer with a CT ratio of 12000A/1A the corresponding secondary current is
Igs
Igp 2916.14A 5 A 3.64 A CTratio 4000 A
So the CT ratio compensation is
CT ratio comp
I gs IN
3.64 A 0.73 5A
A further data for the generator (manufacturer data) is the inverse time characteristic i2t, which is for example i2t=20s Note: This characteristic is only valid for high current values i, as shown below (calculation tripping time). So the time constant is selected to be
20 s 3125s 0.082
52min
The tripping time can be calculated exactly
i2 ttrip ln 2 2 2 i i 2 2e In case of a failure with n.p.s=45%, i2 results to 5xi2e, and the tripping time is
MALANA-II HEP
Page 8 of 29
SETTING CALCULATION NUMERICAL PROTECTION SYSTEM
ttrip ln
2 X 50 MW MALANA-II HYDRO ELECTRIC PROJECT
25 0.0408 127.5s 24
Compared with the manufacturer data
ttrip
3.5s 20 s 98.7 s 2 i2 0.452
The values for the "neg.ph.sequ.alarm" and "neg.ph.sequ.trip" are selected as a percentage of the load limit. The load limit is reached after approximately 4 time constants when running constant admissible unbalance current. Typical values are (depends on the customer wishes): neg.ph.sequ.alarm=80% neg.ph.sequ.trip=100% D) GENERATOR OVERVOLTAGE PROTECTION 59 The overvoltage function protects the generator and the transformer against electrical field stresses. The function is provided with 2 stages whereby stage 1 has a lower voltage setting and a larger time delay to cater for voltage regulator response time in case of full load rejections and stage 2 is provided with a higher voltage setting above loss of load conditions and minimum time delay. The calculation of the setting value for Stage 1 is as follows The setting is chosen to be 110% of the generator rated voltage, therefore
Vs
Vgp 11000V 110V 110% 1.10 121.0V VTratio 11000V
and the time delay is set to t = 2.0 s Stage 2 is selected to be 125% of the generator rated voltage, therefore
Vs
Vgp 11000V 110V 125% 1.25 137.5V VTratio 11000V
and the time delay is set to t = 0.0 s Setting: Name of parameter Operate Value Stage 1 Operate Value Stage 2 Time Delay Stage 1 Time Delay Stage 2 Type
MALANA-II HEP
Range 121.0 137.5 2 0 1 Over Voltage
Unit V V Sec Sec
Page 9 of 29
SETTING CALCULATION NUMERICAL PROTECTION SYSTEM
2 X 50 MW MALANA-II HYDRO ELECTRIC PROJECT
E) GENERATOR UNDERVOLTAGE PROTECTION 27G The function is enabled during the generator set being connected to the power system and is disabled (blocked) by the 220kV CB open position. It is a 1-stage function. The function settings are selected as follows.
V 27 70% Vns 0.70 110V 77V Time delay trip t 27 2.5s Setting: Name of parameter Operate Value Time Delay Type
Range 77 2,5 2 Under Voltage
Unit [V] [Sec] -
F) GENERATOR OVER/UNDERFREQUENCY PROTECTION 81O/U The protective function has 4 Stages providing separate adjustable over- and under-frequency alarm and trip facilities. In addition to the mechanical overspeed and excitation system underspeed detection it provides backup protection for such conditions. All stages will initiate an alarm and trip the unit. The function settings are selected as follows. Stage 1 overfrequency Stage 2 overfrequency Stage 3 underfrequency Stage 4 underfrequency
f 81.1 52.0 Hz f 81.2 52.5 Hz f 81.3 48.5 Hz f 81.4 47.0 Hz
time delay t 81.1 0.5s
Trip
time delay t 81.2 0.0 s
Trip
time delay t 81.3 20.0 s time delay
t 81.4 0.0 s
Trip Trip
The frequency settings need to be reviewed by the grid regulator. Setting: Name of parameter Min. Volt. Setting Max. Volt. Setting Operate Value St. 1 Time Delay St. 1 Type St. 1 Operate Value St. 2 Time Delay St. 2 Type St. 2 Operate Value St. 3 Time Delay St. 3 Type St. 3 Operate Value St. 4 Time Delay St. 4 Type St. 4 MALANA-II HEP
Range 60 – 100 100 – 140 52 0.5 Overdetection 52.5 0.00 Overdetection 48.5 20 Underdetection 47 0.00 Underdetection
Unit [V] [V] [Hz] [s] [Hz] [s] [Hz] [s] [Hz] [s]
Page 10 of 29
SETTING CALCULATION NUMERICAL PROTECTION SYSTEM
2 X 50 MW MALANA-II HYDRO ELECTRIC PROJECT
G) GENERATOR STATOR EARTH FAULT PROTECTION 64G1 The function should serve as an earth fault function for the complete 11kV-system and for the generator up to 90% of its winding. With an earth fault in the 11kV-system (respectively on the terminals of the generator) we receive the following voltage in the generator neutral:
VN sec
VGen 1 11kV 1 63.5V 3 transf ratio 3 11kV / 110V
For a protection range of 90% we are able to calculate the setting value:
100% prot.range 100% 95% VN sec Vset 63.5V 3.18V 100% 100% Selected value (according to setting range of the protection relay): 3.2V. Time delay 1.0s Setting: Name of parameter Operate Value Time Delay Type
Range 3.2 1.0 Over detection
Unit V Sec -
H) GENERATOR STATOR EARTH FAULT PROTECTION 64G2 For simplification an evenly distribution of the 3rd harmonic over neutral and terminals for the generator in healthy condition is assumed (see figure below).
This distribution of the 3rd harmonic over neutral and terminal side is taken for the evaluation of earth faults close to the generator neutral. The 3rd harmonic is measured in the generator neutral with a single-phase voltage transformer and on the generator leads with a voltage transformer in open delta MALANA-II HEP
Page 11 of 29
SETTING CALCULATION NUMERICAL PROTECTION SYSTEM
2 X 50 MW MALANA-II HYDRO ELECTRIC PROJECT
connection. In case of an earth fault, the 3rd harmonic in the neutral is shorted whereby the value on the generator terminals is increased by the same value (see figure below).
The following requirement is assumed: the relay with the measurement of the 3rd harmonic shall protect the 15% of the stator coil close to the neutral point. The other 85% are protected by a normal overvoltage relay with the measurement of the fundamental frequency. The correct settings will be determined on site during earth fault tests. For this purpose different measurements of the 3rd harmonic in the generator neutral and on the generator leads have to be done in dependence of different generator loads for the healthy condition and for an earth fault. The 3rd harmonics are processed via the following formula:
3rd .Harm.gen.terminal volt. ratio 3rd .Harm.gen.neutral volt. measured values There should be a difference between the measured values for the healthy condition and for the case of an earth fault. Setting: Settings will be determined on site during earth fault tests.
I) ROTOR EARTH FAULT PROTECTION 64R This protection function comprises an auxiliary supply, which is connected between the earth and one side of the field circuit. A direct voltage appears at the output, which is indirectly proportional to the rotor insulation value and corresponds to the resistance. If this measured resistance is smaller than the setting value, the required trip sequences for a unit shutdown are carried out. The setting of the rotor earth fault protection is selected to Stage 1: R 50 k MALANA-II HEP
with a time delay t delay 10 s Page 12 of 29
SETTING CALCULATION NUMERICAL PROTECTION SYSTEM
2 X 50 MW MALANA-II HYDRO ELECTRIC PROJECT
Stage 1 will initiate an Alarm only. Stage 2: R 1500
with a time delay
t delay 1s
Stage 2 will initiate a trip. Setting: Name of parameter Operate Value, Stage1 Time Delay, Stage1 Operate Value, Stage2 Time Delay, Stage2
Setting 50 10 1.5 1
Unit [kΩ] [s] [kΩ] [s]
J) GENERATOR REVERSE POWER PROTECTION 32G When operating on reverse power this protective function will perform a unit shut down. The setting is selected due to our experience, i.e. -5.0% of the generator rating power. The relay function setting is calculated as follows. The relay primary power is
P relp 3 Vp ICTp cos 3 11.00kV 300 A 1 5715.77 kW The required -5.0% primary reverse power setting of the machine rating is
Pp 32 5.0% 3 Vp Ig cos 0.05 3 11.00kV 262.4 A 0.9 225kW The required relay setting is Pp32/Prelp = -225/5715.77 = -3.94% The time delay is set to t 32 5.0 s Setting: Name of parameter Operate Value Time Delay Power Direction Phase Rotation
Setting
Unit
-3.94 5 Direction 1 Right
[% PN] [s] -
K) VOLTAGE SUPERVISION FUNCTION 60G, 60M AND 60A The setting for the negative phase sequence voltage for unbalanced secondary phase to phase voltages is selected to Operate Value U=50.0 V
MALANA-II HEP
with a time delay t=5s
Page 13 of 29
SETTING CALCULATION NUMERICAL PROTECTION SYSTEM
2 X 50 MW MALANA-II HYDRO ELECTRIC PROJECT
The second condition of the function is the setting for the negative phase sequence current. A high negative phase sequence current indicates e.g. a failure in the network and the protection function is blocked. Normally an unbalanced voltage causes only a small n.p.s. current. So the setting is chosen to be Operate Value I=0.2 A The selection parameter declares the setting for the phase rotation. Setting: Name of parameter Operate Value I Operate Value U Time Delay Phase Rotation
Range 0.2 50 5 2 (Right)
Unit A V [s] -
L) GENERATOR UNDERIMPEDANCE PROTECTION 21G This protection function consists of two stages, whereby the first stage is a so called impedance protection relay with a current interlock and the second stage is a backup protection, which is designed as overcurrent protection relay. Therefore the generator current is
Igp
Sg Vgp 3
262.4 A Generator primary current
The current and voltage transformer are designed according to the related voltage and rated current of the generator. For this purpose the VT ratio is selected to be 11000V/110V and the CT ratio of the current transformer at the neutral is selected to be 10000/1A The HV and LV transformer currents are:
Ihvp
ILvp
St Vhvp 3 St VLvp 3
57.73 A
HV transformer primary current
577.35 A
LV transformer primary current
The primary short circuit impedance of the transformer is obtained by
Zp
V
2
TS
St
MALANA-II HEP
11k V 2 7.50 uk 0.835 100 11MVA 100 Page 14 of 29
SETTING CALCULATION NUMERICAL PROTECTION SYSTEM
2 X 50 MW MALANA-II HYDRO ELECTRIC PROJECT
Therefore the secondary transformer impedance is calculated
Zs
CTratio 300 110 Zp 0.825 0.495 VTratio 5 11000
In order not to overreach on external system faults an impedance of approximately 50% to 70% of the transformer is selected with a corresponding setting of
Z 21G 50% Zs 0.5 1.73 0.247
With time delay t 21G 0.2 s
The impedance current interlock setting, i.e. the overcurrent stage is a starting element for the under impedance stage, is set to 120% of the generator rated current and calculated as follows
Is 1.2 ILV
1 5 1.2 577.35 11.55 A CT ratio 300
The time delay setting for stage 2 depends on the time grading of the remaining network. Setting: Name of parameter Operate Value Time Delay Imp. Time Delay Curr. Current Interlock
Range
Unit
0.25 0.2 Depends on time grading of remaining n/w 11.55
[Ohm] [s] [s] A
M) DEAD MACHINE 27/51V The overcurrent setting will be coordinated with all the other overcurrent functions (generator, transformer ...).
I 27 / 51V 1.10 A The typical operating range of a generator lies between 90% and 110% of the rated voltage. For generators with an isolated starpoint or with an earthed starpoint via a resistor the generator voltage drops to values of about 30% caused of a phase to phase fault. For this case the parameter "Voltage Limit" has to be chosen in that way, that the generator voltage is below the setting of this parameter. The operating value of the current setting will then be reduced to the "K-Factor". The setting is chosen to be 60% of the generator nominal voltage; this is for the secondary side:
V 27 / 51V
60% 110 66.0V 100%
MALANA-II HEP
Page 15 of 29
SETTING CALCULATION NUMERICAL PROTECTION SYSTEM
2 X 50 MW MALANA-II HYDRO ELECTRIC PROJECT
The k-factor is chosen to be 20% (to make sure that the current exceeds the setting value).
K 0. 2 Setting: Name of parameter Operate Value Voltage Limit K-Factor Time Delay
Range 1.1 66 0.2 4
Unit [A] [V] [s]
N) UNIT DIFFERENTIAL PROTECTION 87GT The unit differential protection is protecting the system from the transformer 220kV CTs up to the 11kV generator neutral and Auxiliary Transformer busbar CTs. When operating the unit is tripped and will be shut down immediately.
Ihvp
Ihvs
St Vhvp 3
11000kVA 110kV 3
57.74 A
HV transformer primary current
Ihvp 57.74 A 1.0 A 0.96 A CTratio 60 A
HV transformer secondary current
With a differential current setting of 0.20xIn the setting as a percentage of the transformer rated current can be calculated
%Ihvs
Is 0.20 A 100 20.8% Ihvs 0.96 A
By choosing a differential current setting of 0.20A secondary the primary setting is calculated as follows.
Ihvp CT ratio Ihvs
500 A 0.15 A 75 A 1.0 A
High set over current = 5.0 x IN =4.8 To cater for the different CT ratios on the transformer HV and LV side the CT ratio compensation factor system2/system1 and systm3/system1 is calculated according to following formulas whereby system 1 refers to the 220kV HV winding, system 2 to the generator leg and system 3 to the aux transformer LV winding.
CTratio comp 2 1
CTsystem 2 CTsystem1 tr.ratio
system1 system2
300 / 1A 0.5 110kV 60 / 1A 11kV
5 MALANA-II HEP
Page 16 of 29
SETTING CALCULATION NUMERICAL PROTECTION SYSTEM
CTratio comp3 1
CTsystem3 CTsystem1 tr.ratio
system1 system3
2 X 50 MW MALANA-II HYDRO ELECTRIC PROJECT
300 / 1A 0.05 110kV 60 / 1A 11kV
Setting: Name of parameter Operate Value High Set OC CT Ratio Comp. 2-1 CT Ratio Comp. 3-1 2nd Harmonic 5th Harmonic Bias Vector Group 1-2 Vector Group 1-3 Zero Sequ. Syst.1 Zero Sequ. Syst.2 Zero Sequ. Syst.3
Range 20% 4,8A 0.5 0.05 20 (to be verified during commissioning) 15 (to be verified during commissioning) 50 1 11 On Off Off
Unit % % % -
O) RESTRICTED EARTH FAULT PROTECTION 64REF The grid transformer restricted earth fault protection 64REF is protecting the system from the transformer 220kV CTs up to the grid transformer neutral to cater for faults near the neutral point (grid transformer). High impedance scheme and high speed tripping is provided. When operating the function trips the generator unit. CT data for the 220kV transformer feeder switchgear CT’s. CT ratio 600/1,0 A CT secondary current In = 1,0 A Estimated CT knee point voltage Vk > 300 V Estimated CT secondary resistance Rct = 5 Estimated single lead resistance to relay Rl = 0.3 CT data for the 220kV transformer neutral CT CT ratio 600/1,0 A CT secondary current In = 1,0 A Estimated CT knee point voltage Vk > 300 V Estimated CT secondary resistance Rct = 5 Estimated single lead resistance to relay Rl = 0.3 The CT requirements for the High impedance transformer restricted earth fault protective function, is according to the following formula. Vk > 2IF ( Rct + 2 Rl + Rext )
MALANA-II HEP
Page 17 of 29
SETTING CALCULATION NUMERICAL PROTECTION SYSTEM
2 X 50 MW MALANA-II HYDRO ELECTRIC PROJECT
Whereby IF is the maximum secondary three phase through fault current considering a short circuit failure. The secondary fault current IF at the 220kV level is calculated as follows (British EATS 48-3 standard).
IF 16
ST 175000kVA 16 12.24 A 3 220kV 600 / 1.0 A 3 V CTratio Vk = 300 V > 2 x 12.24A (5 + 2 x 0.3 ) = 137.16 V Vk = 300 V > 2 x 12.24A (5 + 2 x 0.3 ) = 137.16 V
220kV lead CTs 220kV neutral CT
Therefore the selected restricted earth fault protection voltage setting is chosen to be greater than the minimum stability voltage IFx( Rct + 2 Rl + Rext )=68.58V Vs=69V and the resulting external stabilising resistor for a relay setting IS = 0.15A (33% rated current) is
RST
0.1 relayVA 69 0.15 455 IS IS 0.15
VS
The minimum CT kneepoint voltage should be greater than twice the relay voltage setting 220kV:
Vk = 300V > 2 x VS = 138V
Check, whether a voltage limiting device is required:
V p 2 2 VK V f VK 3000V VK=300V
V f I F RCT 2 Rl RST R R 12.24 5 2 0.3 455 5637V Thus, V p 3579V Due to ensure a safety margin a voltage limiting resistor is connected into the circuit. Continuous power rating of the setting resistor:
Pcon I S RST 0.15 455 10.2W 2
2
with a short time rating:
Pshort
V fs
2
RST
MALANA-II HEP
3 V K RST I F RST
1 4
2
1.3 159W for 0.5 sec onds
Page 18 of 29
SETTING CALCULATION NUMERICAL PROTECTION SYSTEM
2 X 50 MW MALANA-II HYDRO ELECTRIC PROJECT
Thermal rating of the non-linear resistor:
P
4 4 I F VK 12.24 A 300V 4677.94W 3.15
Isetting
V 69 0.15 A RST 455
Settings: Name of parameter Operate Value Drop Off Delay
Range 42.5 % 0.5
Unit s
P) RESTRICTED EARTH FAULT PROTECTION 64REF- DISCRETE RELAY The grid transformer restricted earth fault protection 64REF is protecting the system from the transformer 220kV CTs up to the grid transformer neutral to cater for faults near the neutral point (grid transformer). High impedance scheme and high speed tripping is provided. When operating the function trips the generator unit. CT data for the 220kV transformer feeder switchgear CT’s. CT ratio 600/1,0 A CT secondary current In = 1,0 A Estimated CT knee point voltage Vk > 300 V Estimated CT secondary resistance Rct = 5 Estimated single lead resistance to relay Rl = 0.3 CT data for the 220kV transformer neutral CT CT ratio 600/1,0 A CT secondary current In = 1,0 A Estimated CT knee point voltage Vk > 300 V Estimated CT secondary resistance Rct = 5 Estimated single lead resistance to relay Rl = 0.3 The CT requirements for the High impedance transformer restricted earth fault protective function, is according to the following formula. Vk > 2IF ( Rct + 2 Rl + Rext ) Whereby IF is the maximum secondary three phase through fault current considering a short circuit failure. The secondary fault current IF at the 220kV level is calculated as follows (British EATS 48-3 standard).
IF 16 MALANA-II HEP
ST 175000kVA 16 12.24 A 3 V CTratio 3 220kV 600 / 1.0 A Page 19 of 29
SETTING CALCULATION NUMERICAL PROTECTION SYSTEM
220kV lead CTs 220kV neutral CT
2 X 50 MW MALANA-II HYDRO ELECTRIC PROJECT
Vk = 300 V > 2 x 12.24A (5 + 2 x 0.3 ) = 137.16 V Vk = 300 V > 2 x 12.24A (5 + 2 x 0.3 ) = 137.16 V
Therefore the selected restricted earth fault protection voltage setting is chosen to be greater than the minimum stability voltage IFx( Rct + 2 Rl + Rext )=68.58V Vs=69V and the resulting external stabilising resistor for a relay setting IS = 0.15A (33% rated current) is
RST
0.1 relayVA 69 0.15 162.22 IS IS 0.15
VS
The minimum CT kneepoint voltage should be greater than twice the relay voltage setting 220kV:
Vk = 300V > 2 x VS = 138V
Check, whether a voltage limiting device is required:
V p 2 2 VK V f VK 3000V VK=300V
V f I F RCT 2 Rl RST RR 12.24 5 2 0.3 162.22 2055.28 Thus, V p 2052.48V Due to ensure a safety margin a voltage limiting resistor is connected into the circuit. Continuous power rating of the setting resistor:
Pcon I S RST 0.15 162.22 3.65W 2
2
with a short time rating:
Pshort
V fs
2
RST
3 VK RST I F RST
1.3 1 4
2
2412.82W for 0.5 sec onds
Thermal rating of the non-linear resistor:
P
4 4 I F VK 12.24 A 300V 4677.94W 3.15
MALANA-II HEP
Page 20 of 29
SETTING CALCULATION NUMERICAL PROTECTION SYSTEM
Isetting
2 X 50 MW MALANA-II HYDRO ELECTRIC PROJECT
V 69 0.42 A RST 162.22
Settings: Name of parameter Operate Value Drop Off Delay
Range 42.5 % 0.5
Unit s
Q) OVERFLUXING PROTECTION 99G The degree of saturation (overfluxing) is calculated according to following formula.
S
V fN VN f
Whereby V and VN are the actual voltage and rated voltage and f and fN the actual frequency and rated frequency respectively. The operating value of stage 1 is set to the maximum continuous overfluxing withstand of the generator, which must be specified by the manufacturer of the generator, i.e. to 105% voltage at rated frequency and the other stage is set to increasing higher levels. Stage 1 alarm Stage 2 trip
S1A=1.05 time delay t=10.0s S2T=1.10 time delay t=1.0s
Setting: Name of parameter Operate Value St. 1 Time Delay St. 1 Operate Value St. 2 Time Delay St. 2 Nominal Frequency Nominal Voltage
Setting 1.05 10.00 1.10 1.00 50.0 110
Unit [p.U.] [s] [p.U.] [s] [Hz] [V]
R) UAT DIFFERENTIAL PROTECTION 87UAT This function protects the UAT system from the HV side CTs to the LV side CTs and operates for phase to phase and three phase faults. The differential setting value is calculated as follows:
IAT-HVp
SAT 500kVA 26.24 A Vnp 3 11kV 3
UAT (HV) primary current
Now with a CT ratio = 30/5 A the generator secondary current is calculated
IAT-HVs
IAT-HVp 26.24 A 5 A 4.37 A CTratio 30 A
MALANA-II HEP
UAT (HV) secondary current Page 21 of 29
SETTING CALCULATION NUMERICAL PROTECTION SYSTEM
IAT-LVp
SAT 500kVA 695.60 A Vnp 3 415V 3
2 X 50 MW MALANA-II HYDRO ELECTRIC PROJECT
UAT (LV) primary current
and with a CT ratio of 800/5A the corresponding secondary current is
IAT-LVs
IAT-LVp 695.60 A 1A 0.87 A CTratio 800 A
UAT (LV) secondary current
The differential current setting is chosen to be 20% of the relay current rating, i.e.
I 87 s 0.20 5 A 1.00 A This is in turn the equivalent to the generator rated current.
I %
Is IAT-HVs
100
1.0 A 100 38.16% 2.62 A
High set overcurrent = 5.0 x IN =13.1 The bias slope is set to
CTratio comp
bias 40% CTsystem 2
system1 CTsystem1 tr.ratio system2
800 1.00 11kV 30 / 1A 0.415kV
Setting: Name of parameter Operate Value High Set OC CT Ratio Comp. 2-1 2nd Harmonic 5th Harmonic Bias Vector Group 1-2 Zero Sequ. Syst.1 Zero Sequ. Syst.2
Range 38.16% 13.1 1.00 20 (to be verified during commissioning) 15 (to be verified during commissioning) 40 11 Off Off
Unit % % % -
S) UAT OVERCURRENT PROTECTION 50U/51U This function protects the auxiliary transformer against substantial overloading and heavy internal and external HV side short circuits and will trip the generator unit when operating. For the overcurrent protection stage 1 an inverse time characteristic is chosen to cater for field forcing conditions and the current setting is selected to be 1.0x the transformer rated current. The overcurrent protection stage 2 setting is chosen to be about 5 x In with a small time delay MALANA-II HEP
Page 22 of 29
SETTING CALCULATION NUMERICAL PROTECTION SYSTEM
2 X 50 MW MALANA-II HYDRO ELECTRIC PROJECT
The protective function settings are obtained
IATp
SAT 500kVA 26.24 A auxiliary transformer primary current Vnp 3 11kV 3
and with a CT ratio of 50/5A the corresponding secondary current is
IATs
IATp 26.24 A 5 A 2.62 A CTratio 50 A
auxiliary transformer secondary current
Hence the current setting for Stage 1 is selected to be 120% of the rated current
I 51 IATs 1.2 2.62 A 1.2 3.15 A With a Time Multiplier setting TMS 0.5
normally inverse time characteristic
The Stage 2 current setting is selected to be approximately 5 x In and is obtained
I 50 I 51 5.0 3.15 A 5.0 15.75 A The time delay of Stage 2 is chosen to be t 50 0.1s
Setting: Name of parameter Operating Val. St.1 TMS St.1 Curve Operating Val. St.2 Time delay St.2
Range 3.15 0.5 normal inverse 15.75 0.1
Unit A A Sec
4. Distance Protection Line Parameters: POSITIVE SEQUENCE RESISTANCE POSITIVE SEQUENCE REACTANCE ZERO SEQUENCE RESISTANCE ZERO SEQUENCE RESISTANCE LINE LENGTH LENGTH OF NEXT SHORTEST LINE LENGTH OF NEXT LONGEST LINE ARC RESISTANCE PH-PH ARC RESISTANCE PH-EARTH
R1 X1 R0 X0 L1 L2 L3 Arc ph-ph Arc ph-e
0.0659 0.3836 0.272 1.233 70 30 30 0 20
OHMS/KM OHMS/KM OHMS/KM OHMS/KM KM KM KM OHMS OHMS
Primary Values per Km: MALANA-II HEP
Page 23 of 29
SETTING CALCULATION NUMERICAL PROTECTION SYSTEM
2 X 50 MW MALANA-II HYDRO ELECTRIC PROJECT
R1=0.0659 X1=0.3836 R0=0.272 X0=1.233
Z1 R1 2 X 12 0.3892 LineAngle( Ph Ph), 1 Tan 1
X1 80.2517 R1
Z 0 R0 2 X 0 2 1.2626
LineAngle( Ph E ), 0 Tan 1
X0 77.5598 R0
Values Protected Line: Primary Value: R1pL1=0.0659*70=4.6130 X1pL1=0.3836*70=26.8508 R0pL1=0.2720*70=19.0400 X0pL1=1.2330*70=86.3100 Secondary Value:
CTratio 0.06 PTratio R1sL1=4.6130*0.06=0.2767 X1sL1=26.8508*0.06=1.6110 R0sL1=19.0400*0.06=1.1424 X0sL1=86.3100*0.06=5.1786
Earth Impedance (residual) Compensation: Resistance Ratio:
RG 1 R 0 1 1.04248 RL 3 R1
Reactance Ratio:
XG 1 X 0 1 0.7381 XL 3 X 1
Earth Compensation Factor, Ko: MALANA-II HEP
1 Z K 0 0 1 3 Z1
Page 24 of 29
SETTING CALCULATION NUMERICAL PROTECTION SYSTEM
2 X 50 MW MALANA-II HYDRO ELECTRIC PROJECT
K 0 0.7469 0.0508i
ABS ( K 0 ) 0.7469 2 0.0508 2 0.7486 0.0508 ARG ( K 0 ) tan 1 3.89 0.7469 Next Shortest Line: Primary Value: R1pL2=0.0659*30= 1.9770 X1pL2=0.3836*30= 11.5075 R0pL2=0.2720*30= 8.1600 X0pL2=1.2330*30= 36.99 Secondary Values: R1sL2=1.9770*0.06=0.1186 X1sL2=11.5075*0.06=0.6904 R0sL2=8.1600*0.06=0.4896 X0sL2=36.9900*0.06=2.2194 Next Longest Line: Primary Value: R1pL3=0.0659*30= 1.9770 X1pL3=0.3836*30= 11.5075 R0pL3=0.2720*30= 8.1600 X0pL3=1.2330*30= 36.99
Secondary Values: R1sL3=1.9770*0.06=0.1186 X1sL3=11.5075*0.06=0.6904 R0sL3=8.1600*0.06=0.4896 X0sL3=36.9900*0.06=2.2194
KPCL Setting Philosophy: Zone1 :
80% of Protected Line
Zone2 :
100% of protected line + 50% of next shortest line
MALANA-II HEP
Page 25 of 29
SETTING CALCULATION NUMERICAL PROTECTION SYSTEM
Zone3 :
100% + 100% of next longest line
Zone4 :
Normally 15% to 20% of Zone 1
2 X 50 MW MALANA-II HYDRO ELECTRIC PROJECT
Zone 1 Calculation: Phase to Phase Faults:
Primary Values
R1Z 1 p ( R1 pL1 * 0.8) arcph ph 3.69 X 1Z1 p ( X 1 pL1 * 0.8) 21.481 Secondary Values
R1Z1s R1Z1 p * 0.06 0.221 X 1Z1s X 1Z1 p * 0.06 1.289 Phase to Earth Faults:
Primary Values
R 0 Z1 p ( R 0 pL1 * 0.8) arcph e 35.232 X 0 Z 1 p ( X 0 pL1 * 0.8) 69.048 Secondary Values
R 0Z1s R 0Z1 p * 0.06 2.114 X 0 Z 1s X 0 Z1 p * 0.06 4.143
Zone 2 Calculation: Phase to Phase Faults:
Primary Values
R1Z 2 p ( R1 pL1) ( R1 pL 2 * 0.5) arcph ph 5.602 X 1Z 2 p ( X 1 pL1) ( X 1 pL 2 * 0.5) 32.605 Secondary Values
R1Z 2 s R1Z 2 p * 0.06 0.336 X 1Z 2 s X 1Z 2 p * 0.06 1.956 MALANA-II HEP
Page 26 of 29
SETTING CALCULATION NUMERICAL PROTECTION SYSTEM
2 X 50 MW MALANA-II HYDRO ELECTRIC PROJECT
Phase to Earth Faults:
Primary Values
R0 Z 2 p ( R0 pL1) ( R0 pL 2 * 0.5) arcph e 43.120 X 0 Z 2 p ( X 0 pL1) ( X 0 pL 2 * 0.5) 104.805 Secondary Values
R0Z 2s R0Z 2 p * 0.06 2.587 X 0 Z 2 s X 0 Z 2 p * 0.06 6.288 Zone 3 Calculation: Phase to Phase Faults: Primary Values
R1Z 3 p ( R1 pL1) ( R1 pL3) arcph ph 6.590 X 1Z 3 p ( X 1 pL1) ( X 1 pL3) 38.358 Secondary Values
R1Z 3s R1Z 3 p * 0.06 0.395 X 1Z 3s X 1Z 3 p * 0.06 2.301 Phase to Earth Faults:
Primary Values
R 0 Z 3 p ( R0 pL1) ( R0 pL3) arcph e 47.200 X 0 Z 3 p ( X 0 pL1) ( X 0 pL3) 123.300 Secondary Values
R0 Z 3s R0 Z 3 p * 0.06 2.832 X 0 Z 3s X 0 Z 3 p * 0.06 7.398 Reverse Zone 4 Calculation: Phase to Phase Faults: Primary Values MALANA-II HEP
Page 27 of 29
SETTING CALCULATION NUMERICAL PROTECTION SYSTEM
2 X 50 MW MALANA-II HYDRO ELECTRIC PROJECT
R1Z 4 p ( R1 pL1 * 0.2) arcph ph 0.923 X 1Z 4 p ( X 1 pL1 * 0.2) 5.370 Secondary Values
R1Z 4 s R1Z 4 p * 0.06 0.055 X 1Z 4 s X 1Z 4 p * 0.06 0.322 Phase to Earth Faults:
Primary Values
R0 Z 4 p ( R0 pL1 * 0.2) arcph e 23.808 X 0 Z 4 p ( X 0 pL1 * 0.2) 17.262 Secondary Values
R0Z 4s R0Z 4 p * 0.06 1.428 X 0 Z 4 s X 0 Z 4 p * 0.06 1.036
Settings: Name of parameter Line Angle Earth fault Compensation Factors Zone 1 (Forward) Zone 2 (Forward) MALANA-II HEP
ph-ph ph-e ph-ph
ph-ph ph-e Re/Rl Xe/Xl R X R X R X
Set Value 80.2517 77.5598
Unit Degrees
1.042489 0.738143 0.221 1.289 2.114 4.143 0.336 1.956
Ohms Ohms Page 28 of 29
SETTING CALCULATION NUMERICAL PROTECTION SYSTEM R X R X R X R X R X
ph-e Zone 3 (Forward) Zone 4 (Reverse)
ph-ph ph-e ph-ph
Operation time
MALANA-II HEP
ph-e Zone Zone Zone Zone
1 2 3 4
2.587 6.288 0.395 2.301 2.832 7.398 0.055 0.322 1.428 1.036 0 0.4 0.8 1.2
2 X 50 MW MALANA-II HYDRO ELECTRIC PROJECT
Ohms
Ohms
secs
Page 29 of 29
View more...
Comments