Diseño Reservorio Circular 10 m3

March 18, 2017 | Author: CRISTHIANDG | Category: N/A
Share Embed Donate


Short Description

Download Diseño Reservorio Circular 10 m3...

Description

Diseño de Reservorio Circular 10.00 M3

RESERVORIO DE

RESUMEN DE DISEÑO DEL RESERVORIO CILÍNDRICO

VOL.=

ALTURA NETA DEL TANQUE (AGUA ÚTIL)

=

1.471

m.

ESP. LOSA DE TECHO

=

ALTURA TOTAL SIN LOSA TECHO

=

1.821

m.

ESP. LOSA DE FONDO

=

ALTURA TOTAL RESERVORIO

=

1.921

m.

CIMIENTO ANCHO

=

DIÁMETRO INTERIOR

=

2.942

m.

CIMIENTO ALTURA

=

ESPESOR DE PARED TANQUE

=

0.120

m.

VOLADIZO DE PROTECCIÓN

ÁREA DE ACERO HORIZ.EN PARED Fe

3/8

ÁREA DE ACERO VERT.EN PARED Fe

3/8

As = TECHO DEL TANQUE Fe

3/8

As = EN CIMIENTO DEL TANQUE

3/8

Ast CIMIENTO(Contracción y Temp.) =

3/8

As = LOSA DE FONDO

3/8

01 @.05 + SE UTILIZARÁ SE UTILIZARÁ SE UTILIZARÁ SE UTILIZARÁ SE UTILIZARÁ

6 1 1 1 1 1

Fe Fe Fe Fe Fe

@ @ @ @ @ @

DISEÑO DE RESERVORIO CILÍNDRICO

=

10.00

M3.

0.100 0.120 0.300 0.277 20.000 0.18

m. m. m. m. m.

+REST @ m. AMBOS SENTIDOS m. m. AMBOS SENTIDOS

0.18 0.33 0.20 0.12 0.25 0.33 V=

m.

10.00

M3.

10.00

M3.

LOS ELEMENTOS ESTRUCTURALES QUE CONFORMAN EL RESERVORIO SON: - PARED LATERAL DEL TANQUE - TECHO DEL TANQUE - LOSA DE FONDO Y CIMIENTOS ( SOLADOS) - CERCO PERIMÉTRICO DE PROTECCIÓN.

A) DIMENSIONES DEL TANQUE.CAPACIDAD DEL TANQUE =

V=

RELACION DIÁMETRO ALTURA =

H = 0.50*D

DIÁMETRO DEL TANQUE =

D=

2.94

ALTURA NETA DEL TANQUE (AGUA ÚTIL)=

H=

1.47

M.

10.00

M3.

COMPROBACIÓN DE SU CAPACIDAD =

Vn = PI/4*D^2*H

0.35

BORDE LIBRE O CAM. DE AIRE MAS ALTURA LOSA DE FONDO A LA SALIDA DE AGUA =

M.

M. dato

LAS DIMENSIONES FINALES DEL TANQUE SERÁN : DIÁMETRO INTERIOR =

Di =

2.94

M.

ALTURA TOTAL ( SIN LOSA TECHO) =

Ht =

1.82

M.

LA FUERZA DE TENSIÓN PARA CADA ANILLO (INF)=

T=

3,183.10

KG.

LA FUERZA DE TENSIÓN PARA CADA ANILLO(SUP) =

T=

795.77

KG.

f't =

13.82

Kg/cm2. dato

1.57

CM.

B) DISEÑO DE LA PARED DEL TANQUE.DIVIDIMOS LA ALTURA DEL TANQUE EN DOS PARTES : EL EMPUJE MÁXIMO DEL AGUA =

P = .5*W*H^2

210.00

EMPLEANDO UN ESFUERZO DE TRACCIÓN DEL CTO. = EL ESPESOR DEL TANQUE SERÁ =

Kg/cm2. e = T/(H/2*fct)

CONSIDERAMOS UN ESPESOR DE =

e=

12.00

CM. dato

C) CALCULO DE LA ARMADURA (As=).ESFUERZO DE TRABAJO DEL ACERO =

fs = 0.45 * fy

AREA DE ACERO ANILLO INFERIOR = ESPACIAMIENTO DE ACERO =

fs =

ESPACIAMIENTO DE ACERO =

0.71

Asi = 01 FIERRO DE

CM2.

3/8

@

3/8

0.71

Ass = 01 Fe. DE

3/8

@

DE fy = 4200 KG/CM2.

CM.

18.00

CM.

0.42

CM2.

124.03

CM.

18.00

CM.

18.00

CM.

0.0018

ÁREA DE ACERO VERTICAL =

Asv =

3/8

0.71

CM. dato

18.00 Ass = DIAMETRO =

CUANTÍA DE DISEÑO = USANDO FIERRO DE:

1.68 31.01

CHEQUEO DE ESPACIAMIENTO MÁXIMO =

POR LO TANTO ACERO ANILLO SUPERIOR: REFUERZO VERTICAL.-

KG/CM2.

Asi =

3/8

DIAM.

CHEQUEO DE ESPACIAMIENTO MÁXIMO =

ACERO ANILLO INFERIOR: ÁREA DE ACERO ANILLO SUPERIOR =

1,890.00

Asv =

2.16

1 @

33

CM2. CM. dato

* TANTO EL REFUERZO HORIZONTAL COMO EL VERTICAL SE CONTINUARÁN HASTA EL EXTREMO SUPERIOR DEL TANQUE.

D) CHEQUEO DEL ESPESOR ( e=).RESISTENCIA DEL CONCRETO f'c =

f'c =

210

KG/CM2.

Ac =

136.08

CM2.

e=

12.00

CM.

POR SER ELEMENTO SOMETIDO A TRACCIÓN AXIAL: SUPERFICIE DE CONCRETO = ESPESOR DE LA PARED DEL TANQUE =

E) DISEÑO DEL TECHO DEL TANQUE 20.00

LOSA MACIZA ARMADA EN DOS SENTIDOS; TENDRÁ UN VOLADIZO DE PROTECCIÓN DE LA PARED =:

CM.

PREDIMENSIONAMIENTO (h); NO DEBE SER INFERIOR A:

h1 =

7.21

CM.

NO DEBE SER INFERIOR A:

h2 =

7.88

CM.

PERO EN NINGÚN CASO SUPERIOR A:

h3 =

8.97

CM.

8.43

CM.

ENTONCES EL ESPESOR SERÁ = REDONDEANDO EL ESPESOR MÁS FAVORABLE :

METRADO DE CARGAS(U).-

h=

h=

10.00

CM. dato

CARGA MUERTA =CM =

CM =

PP + PT =

CV =

CARGA VIVA = CV = CARGA ÚLTIMA : U = I=

8,333

DEFLEXIÓN MAXIMA PERMISIBLE =

Ùmáx

DE DONDE

KG/M2. dato

824.87

KG/M2

+M =

297.49

KG-M.

Ùmáx =

0.44

CM.

Ùmáxad =

1.63

CM.

Ùmáxad =====>

<

KG/M2.

U=

MOMENTO ACTUANTE +M = CHEQUEO DEL ESPESOR e = POR DEFLEXIÓN

302.26

400.00

OK

CÁLCULO DEL CORTANTE =

V=

1,395.40

KG.

CANTO EFECTIVO 01 =

CUNT.MAX=

0.02

d1 =

2.47

CM.

CANTO EFECTIVO 02 =

RECUB d' =

4.50

d2 =

5.50

CM.

d=

5.50

CM.

vu =

2.87

KG/CM2.

vc =

7.68

KG/CM2.

CÁLCULO DEL CANTO EFECTIVO =

CHEQUEO POR CORTE.CORTANTE ACTUANTE NOMINAL =

Vu =

1,343.23

CORTANTE CRITICO ( vc ) =

vc

CONSIDERANDO QUE

CALCULO DEL ÁREA DE ACERO (As =)

>

fy =

vu

--------->

4,200

CÁLCULO DE a EL MÁS REAL = CÁLCULO DEL ÁREA DE ACERO =

OK

1.48

0.35

0.35

a=

0.35

CM.

0.35

As1 =

1.48

CM2.

Asm =

1.83

CM2.

As =

1.83

CM2.

Smáx =

20

CHEQUEO DEL ÁREA DE ACERO MÍNIMO EN TRACCIÓN = ÁREA DE ACERO EN AMBOS SENTIDOS =

3/8

USANDO FIERRO DE :

0.71

ENTONCES SE UTILIZARÁ 1 Fe.

39

3/8

Y

CM. dato

20 CM. EN AMBOS SENTIDOS

F) DISEÑO DEL CIMIENTO CORRIDO DE LA PARED DEL TANQUE : 0.30

TENDRÁ FORMA DE ANILLO CONCÉNTRICO EN LA BASE DEL TANQUE, UNA VEREDA DE PROTECCIÓN DE =

M. dato

METRADO DE CARGAS.CARGA MUERTA =

3.78

30.30

0.95

CM =

1,028.03

KG/ML.

CV =

378.20

KG/ML.

Cu=U =

2,082.18

KG/ML.

CARGA VIVA = CARGA TOTAL =

CÁLCULO DEL ANCHO NECESARIO DE CIMIENTO CORRIDO.-

σt =

CONSIDERANDO UN ESFUERZO DEL TERRENO SUPUESTO DE (RESISTENCIA DEL TERRENO ) = ANCHO DEL CIMIENTO = ANCHO MÍNIMO DE CIMIENTO =

0.30 =====>

PERALTE DEL CIMIENTO - DISEÑO POR FLEXIÓN , CALC.MOM =

0.47

EL PERALTE MÍNIMO SERA =

si m =

DISEÑO POR CORTE =

Vup =

0.69

3/8

KG/CM2. dato 0.23

b=

0.30

M. M.

M'u =

4,324.53

KG-CM2.

9.00

h mín =

3.71

CM.

12.32

h=

17.71

CM.

he =

28

CM.

As =

5.90

CM2.

Ast =

0.96

CM2.

PERALTE ADOPTADO PARA EL CIMIENTO SERÁ =

CÁLCULO DEL ÁREA DE ACERO As =

1.03

b=

0.71

dato

CALCULAMOS EL ÁREA DE ACERO CON LA CUANTÍA MÍNIMA 14/fy = As = 01 Fe.

3/8

@

12

CM.

Ast = 01 Fe.

3/8

@

25

CM.

G) DISEÑO DE LA LOSA DE FONDO: LA LOSA IRÁ APOYADA SOBRE UN SOLADO DE DOSIFICACIÓN CEMENTO - HORMIGÓN 1:12, Y TENDRÁ UNA PENDIENTE DE 1 % HACIA EL TUBO DE DESAGÜE. EL ESPESOR IGUAL A LA PARED DEL TANQUE = ÁREA DE ACERO MÍNIMO =

12.00

CM.

Asmín =

2.16

CM2.

USANDO UN FIERRO DE

3/8

Smín =

32.87

CM.

EL ESP. MÁXIMO USANDO FIERRO DE

3/8

Smáx =

36.00

CM.

As = UN FIERRO DE

3/8

S=

32.87

CM.

@

SOLADO DE CONCRETO 1:12 SEGÚN EL TIPO DE SUELO =

ESPESOR

ANCHO DE VEREDA DE PROTECCIÓN = VOLADIZO DEL TECHO DEL TANQUE =

FIN DEL DISEÑO RESERVORIO DE

10.00

10.00 0.30 0.20 M3

CM.

dato

M.

dato

M.