Differences in ANSI-IEEE and IEC Short Circuit Calculations and Their Implications
Short Description
This manual compares the short circuit calculation between ANSI and IEC...
Description
Institute of Integrated Electrical Engineers of the Philippines, Inc. 41 Monte Monte de Piedad Piedad St., Cubao, Cubao, Quezon Quezon City
A Technical Report on
Differences in ANSI/IEEE and IEC Short Circuit Calculations and Their Implications
______________________________ ____________________________________________ ___________________________ _______________________ __________
Prepar Prepared ed by: Institut Institutee of Integr Integrate atedd Electr Electrica icall
Differences in ANSI/IEEE and IEC Short Circuit Calculations and Their Implications
Differences in ANSI/IEEE and IEC Short Circuit Calculations and Their Implications
Disclaimer It is not the intention of this paper to endorse over another the compared short-circuit calculations and standards. All discussions discussions in this report are are based on the featured featured system one line line diagram only. only. The same parameters parameters were considered for the American National Standards Standards Institute/Institut Institute/Institutee of Electri Electrical cal and Electro Electronic nicss Enginee Engineers rs (ANSI/ (ANSI/IEE IEEE) E) and the Internat Internationa ionall Electro-t Electro-tech echnic nical al Commission Commission (IEC) (IEC) calculations calculations for result comparison. comparison. The values of these parameters, parameters, however, may vary from every project in terms of available utility short circuit levels, power system configuration, wiring method and all applicable factors to consider. IIEE and this Committee will not be responsible for any disputes that may arise out of referencing from this paper.
Preface This technical report focuses on two of the most widely used short circuit calculation methods and standards/guidelines namely: American National Standards Institute/Institute of Electrical and Electronics Engineers (ANSI/C37/IEEE std 551) and the International Electrotechnical Commission (IEC 60909). To fully understand the analytical techniques of short circuit current analysis in industrial and commercial power system using both methods, a representative network model was exemplified and a comprehensive comparison between the two calculation methods was presented. For expediency, a short circuit calculating software was employed and the results were presented and evaluated at the end of the analysis. This technical report provides information and inculcates awareness to electrical practitioners in the country on the difference in the procedure of short circuit calculations and its implication between the standards cited. It is not intended to show the detailed short circuit current calculation for both methods. The reader is still recommended to consult technical books for reference on a complete and accurate calculation procedure. This paper starts off with a brief introduction on the current scenario in the Philippines and the importance of short circuit calculation in Chapter I and expounds on its basic principle in Chapter II. The equivalent short circuit schematic diagram is also available for analysis in simple calculation. Chapter III discusses the asymmetry current application focusing on the importance of determining the total available short circuit current in the design of electrical equipment such as circuit breakers, switches, transformers and fuses that are subjected to fault current. Chapter IV shows the different components in determining the short circuit calculation based on the two standard/guidelines, the ANSI/IEEE and the IEC. This is followed by Chapter V
Participants The following are the working group members of the Institute of Integrated Electrical Engineers of the Philippines, Inc. (IIEE) under the Standards Committee: Chairman: Gem J. Tan
Fuji-Haya Audit Inspection and Maintenance Corporation Members: Arjun G. Ansay
Jesus C. Santos
Arturo M. Zabala
Marites R. Pangilinan
Edwin V. Pangilinan
Roderick T. Khu
Frumencio T. Tan
Samson D. Paden
Technological University of the Philippines – Manila AC-DC-KV and Associates Total Power Box Solution, Inc. Safety Consultant
JC Santos and Associates LJ Industrial Fabrication, Inc. Airnergy and Renewables, Inc. Department of Trade and IndustryBureau of Product Standards
Genesis A. Ramos
Department of Energy
Vincent E. Jimenez
Delta Power Engineering and Consulting Gideon S. Tan
Yu Eng Kao Electrical Supply and Hardware, Inc.
Wilson T. Yu
Standards Committee Member Jaime S. Jimenez
Meralco
Advisers: Arthur A. Lopez
Table of Contents Chapter
Title
Page
I.
Introduction
1
II.
Basic Short-Circuit Discussion Figure 1 : Current Model for Asymmetry Figure 2 : Maximum Peak Asymmetrical Short Circuit Current
1 1 2
III.
Asymmetry Current Application
2
IV.
Short-Circuit Current Calculation Standard/Guideline
3
V.
Calculation Comparison Table 1 : Comparison Matrix of ANSI/IEEE and IEC
3 4
VI.
Comparison of Device Duty Rating and Short-Circuit Duty Table 2 : ANSI/IEEE Parameter Table 3 : IEC Parameter Table 4 : ANSI/IEEE vs. IEC Parameter
5 5 5 5
VII.
Sample Calculation using ANSI/IEEE and IEC Figure 3 : Single Line Diagram of the Sample Network Figure 4 : Single Line Diagram to consider IEC SC Result Figure 5 : Single Line Diagram to consider ANSI SC Result Figure 6 : Impedance Diagram for ANSI/IEEE SC Method
6 6 7 16 23
I.
Introduction
In the emerging world market place, Electrical Engineers should be familiar with the basic differences between the American National Standards Institute (ANSI) and the International Electro-technical Commission (IEC) with regards to short circuit current calculation procedures. Both the ANSI and the IEC Standards developed these procedures to provide rating for electrical equipment. These two standards are currently being applied by the electrical practitioners in the Philippines and it is important to determine the differences between these standards so that a more logical evaluation and breaker rating selection can be appropriated. IEC procedure requires significantly more detailed modeling of the power system short circuit contribution than ANSI. A short circuit calculation is an important task undertaken by a professional in power systems planning and operation. Circuit breaker and switchgear selection, protection settings and coordination require a comprehensive, detailed and accurate short-circuit calculation. The report focuses on the guidelines found in the following shortcircuit standards: the North American ANSI/IEEE standard and its European counterpart, IEC.
II.
Basic Short Circuit Discussion
To come up with a precise short circuit calculation requires a very complex computation. What is important is that whatever the short circuit calculation method used, it should be compared with the assigned (tested) fault current rating of the protective devices. The final equivalent short circuit schematic diagram is shown below. R
L
i(t)
~
2 Esin(ωt + Ø)
The asymmetrical fault current decay time is longer when X/R ratio is greater at the fault point. For specific X/R ratio, the angle of the applied voltage at the time of short-circuits initiation determines the degree of fault current asymmetry that will exist for that X/R ratio. The maximum asymmetrical short-circuit current occurs at the fault inception when the voltage sine wave is at zero point and not necessarily at the highest dc component.
Figure 2: Maximum Peak Asymmetrical Short Circuit Current
IV.
Short Circuit Calculation Standard / Guideline
ANSI C37/IEEE Std. 551
The ANSI/IEEE method calls for determining the momentary network fault impedance which makes it possible to calculate the close and latch rating of the breaker. It also calls for identifying the interrupting network fault impedance which makes it possible to calculate the interrupting duty of the breaker. The interrupting network fault impedance value differs from the momentary network in that the impedance increases from the sub-transient to transient level. The IEEE standard permits the exclusion of 3 phase induction motors below 50 hp and all single phase motors. Hence no reactance adjustment is required for these sizes of motors. For detailed calculation requirements please refer to the applicable standards. IEC60909
The IEC method calls for the adjusted network impedance in calculating the symmetrical three phase fault (I” k ) at a voltage higher than the nominal rating by a factor (c). The result is further manipulated to calculate peak current i p which is then compared to the breaker’s making capacity (I cm). Also, further manipulation of the calculated three-phase fault current I”k will result to the interrupting rating requirement that is compared to the selected breaker’s interrupting capacity (I b). For detailed calculation requirements please refer to the applicable standards.
V.
Calculation Comparison
Table 1 presents a brief comparison of the ANSI/IEEE and IEC with regards to short circuit current calculation method and multiplying factors.
Table 1: Comparison of ANSI/IEEE and IEC ANSI/IEEE Standard Calculation Method
IEC
North America 1. Voltage Source is equivalent to the pre-fault voltage at the location
Europe Predominant 1. Pre-fault voltage is automatically adjusted by a factor ( c ) 2. Machines are represented by their internal impedances 2. Machines are represented by 3. Line capacitance of transmission their internal impedances lines and static loads are considered for unbalanced ground faults 3. Line capacitance and static following a Shunt Admittance Model loads are neglected 4. System impedances are assumed balanced 3-phase 4. Bolted Fault is assumed hence 5. Uses symmetrical components for arc resistance is neglected unbalanced fault calculations 6. (I”k ) Initial RMS Symmetrical SCC 5. System impedances are calculates through adjusted assumed balanced 3-phase impedance network of synchronous machine Zk 6. Uses symmetrical components 7. (i p) Peak Short circuit current = for unbalanced fault calculations k1*sqrt 2* I”k where k is determined by Method A, B or C 7. Momentary calculates through 8. (I b) Symmetrical Short-Circuit sub-transient impedance Breaking Current = I” k for near network at half cycle generator faults and = u*I” k for synch
VI.
Comparison of Device Duty Rating and Short-Circuit Duty
The tables below show the different parameters used in evaluating a protective device in terms of calculated short circuit duty of the ANSI/IEEE and IEC Standards. Table 2:
ANSI/IEEE Parameter
DEVICE TYPE
HV BUS BRACING LV BUS BRACING HVCB LVCB Table 3:
LVCB Fuse
Asymm. KA rms Symm. KA rms Symm. KA rms Asymm. KA rms C and L Capability KA rms C and L Capability KA Crest Interrupting KA Rated Interrupting KA
Asymm. KA rms Symm. KA rms Symm. KA rms Asymm. KA rms Asymm. KA rms Asymm. KA Crest Adjusted KA Adjusted KA
IEC Parameter
DEVICE TYPE
MVCB
DEVICE CAPABILITY
CALCULATED SHORTCIRCUIT DUTY (Momentary Duty)
DEVICE CAPABILITY
CALCULATED SHORT-CIRCUIT DUTY (Momentary Duty)
Making AC Breaking Making Breaking
i p I b ,symm i p I b ,symm
Breaking
I b ,symm
VII. Sample Calculation using ANSI/IEEE and IEC Description of Sample network
The sample network consists of two power transformers connected to a 13.2 KV bus. One of the transformers feeds a bus at a nominal voltage of 240 V, while the other transformer feeds a bus at a nominal voltage of 2.3 KV. The data of the transformer and other equipment and their principal characteristics are presented in Fig. 3. For the purpose of presenting a discussion on fault calculation, points Bl and B2 are selected to have experienced a 3 phase bolted fault.
A. IEC SHORT CIRCUIT RESULT
Figure 4: Single Line Diagram to consider IEC SC Result
7
ETAP
Project: Location: Contract: Engineer: Filename: sample
Page: 1 Date: 10-19-2010 SN: FUJIHAYAPH Revision: Base Config.: Normal
6.0.0C
Study Case: SC
Electrical Transient Analyzer Program Short-Circuit Analysis IEC 60909 Standard 3-Phase Fault Currents
Maximum Short-Circuit Current
Number of Buses:
Number of
Swing 1
V-Control 0
Load 7
XFMR2 2
XFMR3 0
Reactor 0
Synchronous
Total 8
Line/Cable Impedance 0 0
Power Synchronous Induction
Lumped
Tie PD 5
Total 7
Adjustments
Tolerance Transformer Impedance: Reactor Impedance: Overload Heater Resistance: Transmission Line Length: Cable Length: Temperature Correction Transformer Resistance: Cable Resistance:
Apply Adjustment Yes Yes No No No
Individual /Global Individual Individual
Apply Adjustment Yes Yes
Individual /Global Global Global
Percent
Degree C 20 20
Bus Input Data Bus
ID B1 B2 Bus4 Bus5 Bus6 Bus7 Bus8 UB
Type Load Load Load Load Load Load Load SWNG
Initial Voltage
Nom. kV 0.240 2.300 0.240 2.300 2.300 2.300 2.300 13.200
Base kV 0.240 2.300 0.240 2.300 2.300 2.300 2.300 13.200
8 Buses Total All voltages reported by ETAP are in % of bus Nominal kV. Base kV values of buses are calculated and used internally by ETAP
Sub-sys 1 1 1 1 1 1 1 1
%Mag. 100.00 100.00 100.00 100.00 100.00 100.00 100.00 100.00
Ang. 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Power Grid Input Data % Impedance 100 MVA Base
Power Grid
Connected Bus
Rating
ID
ID
MVAsc
kV
R
X"
R/X
U1
UB
720.000
13.200
0.00014
13.88889
0.00
Total Connected Power Grids ( = 1 ): 720.000 MVA
Induction Machine Input Data Induction Machine
Connected Bus
ID
Type
Qty
M2
Motor
1
M3
Motor
M4
% Impedance (Motor Base)
Rating
ID
mFact.
HP/kW
kVA
kV
Amp
PF
R
X"
R/X"
MW/PP
Bus5
500.00
440.28
2.300
110.52
90.82
2.96
15.41
0.19
0.19
1
Bus6
500.00
440.28
2.300
110.52
90.82
2.96
15.41
0.19
0.19
Motor
1
Bus7
500.00
440.28
2.300
110.52
90.82
2.96
15.41
0.19
0.19
M5
Motor
1
Bus8
500.00
440.28
2.300
110.52
90.82
2.96
15.41
0.19
0.19
M1
Motor
1
Bus4
125.00
110.12
0.240
264.91
91.51
4.62
16.01
0.29
0.05
Total Connected Induction Machines ( = 5 ): 1871.3 kVA
Lumped Load Input Data Lumped Load
Motor Loads
Lumped Load
Connected Bus
Rating
ID
ID
kVA
kV
Amp
L1
B1
1000.0
0.240
2405.63
Total Connected Lumped Loads ( = 1 ): 1000.0 kVA
% Load
% Impedance Machine Base
Loading
Fact.
% PF
MTR
STAT
kW
kvar
R
X"
R/X"
MW/PP
5.00
60
40
510.0
316.1
.46
15.37
0.42
0.51
SHORT - CIRCUIT REPORT
3-Phase fault at bus: Nomimal kV Voltage c Factor Peak Value Steady State
B1
= = = =
0.240 1.10 181.348 68.754
(Maximum If) kA Method A kA rms
Contribution
Voltage and Initial Symmetrical Current (rms)
From Bus
To Bus Total
%V From Bus 0.00
ID
ID
B1 UB L1 M1 Bus4
B1 B1 Bus4 B1
96.12 100.00 100.00 0.00
kA
kA
X/R
kA
Real
Imaginary
Ratio
Magnitude
13.406
-78.631
5.9
79.766
9.232 3.690 0.485 0.485
-68.170 -8.782 -1.680 -1.680
7.4 2.4 3.5 3.5
68.792 9.526 1.748 1.748
Breaking and DC Fault Current (kA) Based on Total Bus Fault Current
TD (S)
Ib sym
Ib asym
Idc
0.01 0.02 0.03 0.04 0.05 0.06 0.07 0 08
78.916 78.315 77.529 76.761 76.017 75.656 75.301 74 952
101.347 86.941 80.547 77.794 76.406 75.79 75.347 74 968
63.588 37.756 21.843 12.637 7.704 4.504 2.633 1 539
3-Phase fault at bus: Nomimal kV Voltage c Factor Peak Value Steady State
B2
= = = =
2.300 1.10 51.136 17.417
(Maximum If) kA Method A kA rms
Contribution
Voltage and Initial Symmetrical Current (rms)
From Bus ID B2
To Bus ID Total
%V From Bus 0.00
kA Real 1.882
kA Imaginary -20.420
X/R Ratio 10.9
kA Magnitude 20.506
UB
B2
90.44
1.297
-17.377
13.4
17.425
M5
Bus8
100.00
0.146
-0.761
5.2
0.775
M4
Bus7
100.00
0.146
-0.761
5.2
0.775
M3 M2
Bus6 Bus5
100.00 100.00
0.146 0.146
-0.761 -0.761
5.2 5.2
0.775 0.775
Bus5
B2
0.00
0.146
-0.761
5.2
0.775
Bus6
B2
0.00
0.146
-0.761
5.2
0.775
Bus7
B2
0.00
0.146
-0.761
5.2
0.775
Bus8
B2
0.00
0.146
-0.761
5.2
0.775
Breaking and DC Fault Current (kA)
Based on Total Bus Fault Current TD (S)
Ib sym
Ib asym
Idc
0.01
20.014
28.877
20.816
0.02
19.722
25.04
15.429
0.03
19.441
22.464
11.254
3-Phase fault at bus:
Bus4
Nomimal kV
= 0.240
Voltage c Factor
= 1.10
(Maximum If)
Peak Value
= 181.348
kA Method A
Steady State
= 68.754
kA rms
Contribution
Voltage and Initial Symmetrical Current (rms)
From Bus ID
To Bus ID
%V From Bus
kA Real
kA Imaginary
X/R Ratio
kA Magnitude
Bus4
Total
0.00
13.406
-78.631
5.9
79.766
M1
Bus4
100.00
0.485
-1.680
3.5
1.748
UB
B1
96.12
9.232
-68.170
7.4
68.792
L1
B1
100.00
3.690
-8.782
2.4
9.526
B1
Bus4
0.00
12.921
-76.952
6.0
78.029
Breaking and DC Fault Current (kA)
Based on Total Bus Fault Current TD (S)
Ib sym
Ib asym
Idc
0.01
78.916
101.347
63.588
0.02
78.315
86.941
37.756
0.03
77.529
80.547
21.843
0.04
76.761
77.794
12.637
0.05
76.017
76.406
7.704
3-Phase fault at bus:
UB
Nomimal kV
= 13.200
Voltage c Factor
= 1.10
(Maximum If)
Peak Value
= 90.256
kA Method A
Steady State
= 31.492
kA rms
Contribution
Voltage and Initial Symmetrical Current (rms)
From Bus ID
To Bus ID
%V From Bus
kA Real
kA Imaginary
X/R Ratio
kA Magnitude
UB
Total
0.00
0.142
-32.117
226.5
32.117
B1
UB
13.64
0.060
-0.167
2.8
0.178
B2
UB
13.86
0.081
-0.458
5.7
0.465
U1
UB
100.00
0.000
-31.492
99999.0
31.492
Breaking and DC Fault Current (kA)
Based on Total Bus Fault Current TD (S)
Ib sym
0.01
32.048
55.226
44.977
0.02
32.004
55.166
44.934
0.03
31.959
54.943
44.692
0.04
31.915
54.723
44.452
0.05
31.874
54.998
44.82
Ib asym
Idc
Short Circuit Summary Report
3-Phase FaultCurrent Bus ID B1
Device Capacity (kA)
Device kV
ID
Type
Making Peak
Ib sym
Ib asym
Short-Circuit Current (kA) Idc
I"k
ip
79.766
181.348
Ib sym
Ib asym
Idc
Ik
0.240
1
Bus
0.240
CB2
CB
220.000
100.000
102.111
79.766
181.348
77.920
83.044
28.718
0.240
CB6
CB
176.000
80.000
80.426
79.766
181.348*
77.219
77.219
17.549
B2
2.300
2
Bus
20.506
51.136
17.417
Bus4
0.240
us4
Bus
79.766
181.348
68.754
0.240
CB6
CB
79.766
181.348*
13.200
B
Bus
32.117
90.256
UB
176.000
80.000
80.426
68.754
77.219
79.188
17.549 31.492
ip is calculated using method A Ib does not include decay of non-terminal faulted induction motors Ik is the maximum steady state fault current Idc is based on X/R from Method C and Ib as specified above LV CB duty determined based on ultimate rating. Total through current is used for device duty. *Indicates a device with calculated duty exceeding the device capability. # Indicates a device with calculated duty exceeding the device marginal limit ( 95 % times device capability)
Short Circuit Summary Report
3-Phase Short-Circuit
B. ANSI SHORT CIRCUIT RESULT
FIGURE 5:
Single Line Diagram to consider ANSI SC Result
16
Project: ANSI Calc Total Bus Fault Peak Current Location: Contract: Engineer: Filename: sample
ETAP
Page: 1 Date: 10-19-2010 SN: FUJIHAYAPH Revision: Ansi Breaker Config.: Normal
6.0.0C
Study Case: SC
Electrical Transient Analyzer Short-Circuit Analysis ANSI Standard 3-Phase Fault Currents
Number of Buses:
Number of
Swing 1
V-Control 0
Load 7
XFMR2 2
XFMR3 0
Reactor 0
Total 8
Line/Cable Impedance Tie PD 0 0 5
Synchronous Power Synchronous Induction Lumped
Total 7
Adjustments Tolerance Transformer Impedance: Reactor Impedance: Overload Heater Resistance: Transmission Line Length: Cable Length: Temperature Correction Transformer Resistance: Cable Resistance:
Apply Adjustment Yes Yes No No No
Individual /Global Individual Individual
Apply Adjustment Yes Yes
Individual /Global Global Global
Percent
Degree C 20 20
Bus Input Data Bus
ID B1 B2 Bus4 Bus5 Bus6 Bus7 Bus8 UB
Type Load Load Load Load Load Load Load SWNG
Initial Voltage
Nom. kV 0.240 2.300 0.240 2.300 2.300 2.300 2.300 13.200
Base kV 0.240 2.300 0.240 2.300 2.300 2.300 2.300 13.200
8 Buses Total All voltages reported by ETAP are in % of bus Nominal kV.
Sub-sys 1 1 1 1 1 1 1 1
%Mag. 100.00 100.00 100.00 100.00 100.00 100.00 100.00 100.00
Ang. 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Branch Connections CKT/Branch
Connected Bus ID
% Impedance, Pos. Seq., 100 MVAb
ID
Type
From Bus
To Bus
R
X
Z
Y
T1
2W XFMR
UB
B1
53.48
379.58
383.33
T2
2W XFMR
UB
B2
11.74
142.52
143.00
CB6
Tie Breaker
B1
Bus4
CB7
Tie Breaker
B2
Bus5
CB8
Tie Breaker
B2
Bus6
CB9
Tie Breaker
B2
Bus7
CB10
Tie Breaker
B2
Bus8
Power Grid Input Data % Impedance 100 MVA Base
Power Grid
Connected Bus
Rating
ID
ID
MVASC
kV
X/R
R
X
U1
UB
720.000
13.200
99999
0.00014
13.88889
Total Connected Power Grids ( = 1 ): 720.000 MVA
Induction Machine Input Data Induction Machine
Connected Bus
Rating
X/R Ratio
% Impedance (Motor Base)
SHORT - CIRCUIT REPORT
3-Phase fault at bus:
B1
Prefault voltage = 0.240 =
=
100.00% of nominal bus kV ( 0.240 kV ) 100.00% of base ( 0.240 kV )
Contribution
1/2 Cycle
From Bus
To Bus
ID
ID
B1
%V
kA
kA
Imag.
kA Symm.
Real
Imaginary
/Real
Magnitude
Total
From Bus 0.00
10.893
-67.489
6.2
68.362
UB
B1
96.57
8.165
-60.047
7.4
60.600
L1
B1
100.00
2.577
-6.134
2.4
6.653
M1
Bus4
100.00
0.150
-1.307
8.7
1.316
*Bus4
B1
0.00
0.150
-1.307
8.7
1316
NACD Ratio = 1.00 # Indicates a fault current contribution from a three-winding transformer * Indicates a fault current through a tie circuit breaker If faulted bus is involved in loops formed by protection devices, the short-circuit contribution through these PDs will not be reported
NACD Ratio = 1.00 # Indicates a fault current contribution from a three-winding transformer * Indicates a fault current through a tie circuit breaker If faulted bus is involved in loops formed by protection devices, the short-circuit contribution through these PDs will not be reported
3-Phase fault at bus:
B4
Prefault voltage = 0.240
= =
100.00% of nominal bus kV ( 0.240 kV ) 100.00% of base ( 0.240 kV )
Contribution
1/2 Cycle
From Bus ID Bus4
To Bus ID Total
%V From Bus 0.00
kA Real 10.893
kA Imaginary -67.489
Imag. /Real 6.2
kA Symm. Magnitude 68.362
M1 UB L1
Bus4 B1 B1
100.00 96.57 100.00
0.150 8.165 2.577
-1.307 -60.047 -6.134
8.7 7.4 2.4
1.316 60.6 6.653
*B1
Bus4
0.00
10.743
-66.181
6.2
67.048
NACD Ratio = 1.00 # Indicates a fault current contribution from a three-winding transformer * Indicates a fault current through a tie circuit breaker If faulted bus is involved in loops formed by protection devices, the short-circuit contribution through these PDs will not be reported
3-Phase fault at bus:
UB
Prefault voltage = 13.200
=
100.00% of nominal bus kV ( 13.200 kV ) 100.00% of base ( 13.200 kV )
Momentary Duty Summary Report
3-Phase Fault Currents: (Prefault Voltage = 100% of the Bus Nominal Voltage
Bus
Device
Momentary Duty
Device Capability
ID
kV
ID
Type
Symm. kA rms
X/R Ratio
M.F.
Asymm kA rms
Asymm. kA Crest
B1
0.240
B1
Bus
68.362
6.9
1.342
91.741
157.859
B2
2.300
B2
Bus
17.840
13.1
1.496
26.68
45.067
Bus4
0.240
Bus4
Bus
68.362
6.9
1.342
91.741
157.859
UB
13.200
UB
Bus
31.901
999.9
1.728
55.139
90.088
Symm kA rms
Method : IEEE - X/R is calculated from separate R and X networks. Protective device duty is calculated based on total fault current * Indicates a device with momentary duty exceeding the d evice capability
Interrupting Duty Summary Report
3-Phase Fault Currents: (Prefault Voltage = 100% of the Bus Nominal Voltage
Bus
Device
Interrupting Duty
Device Capability
Asymm. kA rms
Asymm kA Crest
C. ANSI/IEEE Short Circuit Method (for Manual Calculation)
Impedance Diagram Development @ 100 MVA base
XU R T2
R T1 XT1 R M1 XM1
where:
B2
B1
XT2 R M3
R M2
R L XL
XM3
XM2
R M4 XM4
R M5 XM5
MOTOR (MVA) = HP(0.746) (Eff)(pf)(100) 500(0.746) M2 = (1000)(0.9325)(0.9082) M2 = 0.440 MVA
Figure 6: Impedance Diagram
j
1.
XU
2.
R T1
3.
X T1
4.
R T2
5
X
100
j 0.13889 720 100 0.575 cos tan 7.1 0.53463 1.5 100 0.575 sin tan 7.1 j 3.79587 1.5 100 0.0715 cos tan 12.14 0.11739 5 100 0 0715 sin tan 12 14 j1 42157
Solving for ½ cycle 3 phase fault at
Z T B1
Z
T2
B1
Z M2 Z M3 Z M4 Z M5 Z U Z T1 Z M1 Z L
0.56271 j3.44496 3.49062 80.72
I T3 B
1
100 x 10
6
68.9 kA
3 240 3.49062
Solving for ½ cycle, 3phase fault at
B2
Z M2 Z M3 Z M4 Z M5
Z T B2
Z
M1
Z L Z T1 Z U Z T2
0.10787 j1.40240 1.40655 85.6
I T3 B
2
100 x 10 6 3 2300 1.40655
17.85 kA
IEC Short Circuit Calculation
1. XUK 2. R T1K K
j0.13889 0.534630.965 0.51592 0.965 asper60909IECformula C
Solving for 3 phase fault at Z TK B1
B1
, I"K
Z T2K Z M2K Z M3 K Z M4K Z M5K Z UK Z T1K Z M1K Z L
0.54641 j3.22821 3.27412 80.39
I"K B
1
100 x 10 6 1.1 3 240 3.27412
Solving for 3 phase fault at Z TK B 2
I"K B
, I"K
Z M2K Z M3K Z M4K Z M5K
0.10307
1.32948 85.6
2
B2
80 kA
j1.32547
100 x 10 6 1.1 3 2300 1.32948
Z M1K Z LK Z T1K
Z UK Z T2K
17.85 kA
* It is therefore the basic inclusion of factors Cm and k that increases the calculated short-circuit of IEC method when being compared to the result of the ANSI method.
VIII.
Protective Devices Selection and evaluation
X/R Ratio for Breaker Evaluation
The fault point X/R ratio is a critical factor in the calculation of short circuit current when evaluating breakers. The X/R ratio determines the amount of dc component in the short circuit current and in the application to the circuit breaker withstands and interrupting time duties. ANSI/IEEE C37.010-1999 recommends a separate R and jX network reduction to determine the fault point X/R ratio while IEC 61909 allows several methods to provide a conservative X/R ratio. The peak current calculation that yields a very close approximation to the exact peak current and is conservative for most values of circuit X/R ratios greater than 0.81. The non-conservative errors for circuit X/R ratio around 10 are negligible. Please refer to equation below: X / R Half cycle I ac peak 1 e or
ANSI / IEEE
X / R 2 I ac rms 1 e
3 X / R Half cycle I ac peak 1.02 0.98 e or
IEC 60909 3 X / R 2 I ac rms 1.02 0.98 e
Based on NEMA AB1/UL489, the circuit breakers interrupting capacity, lagging power factor should be in accordance with Table 6. Table 6: Circuit Breakers Interrupting Capacity
MCCB and ICB Power Circuit Breaker (Unfuse) Power Circuit Breaker (Fuse)
IX.
kA I ≤ 10 10 < I ≤ 20 20 < I All All
lagging pf 0.45 – 0.5 0.25 – 0.30 0.15 – 0.20 0.15 0.20
X/R 1.98 – 1.73 3.87 – 3.17 6.59 – 4.90 6.59 4.90
Findings and Results
From the result of ETAP Total Bus Fault Short Circuit Study, the following results were found: Table 7: IEC Short Circuit Calculation
Bus ID Device B1
CB2
Device Capacity (kA) Making I b sym I b asym Peak 176
80
80.426
Short Circuit Calculation Result (kA) I" b
i p
I b sym
I b asym
79.8
181.348*
77.219
79.188
Note: Method A, Total Bus Fault
From the data in Table 7, the calculated short circuit current level of 79.8kA (I” k ) is within the circuit breaker capacity of 80 kA (I b sym), however, other parameters such as peak short circuit current ( i p) is 181.348 kA exceeded the circuit breaker rating equivalent to 176 kA (making peak) only. Therefore, the selected IEC rated
MF
1 e 1 e
R X C R X T
1 e 1e
1 6.9 C 1 4.9 T
1.07
Where:
R X T
R X C
MF
X.
- Break test R/X ratio - Calculated R/X ratio at the point fault - Multiplying factor
Conclusion and Recommendation
From the above short circuit calculation examples, IEC method shows a higher value of short circuit current as compared to ANSI/IEEE calculation method. This is due to the differences in the consideration as mentioned above. Both methods are being used and internationally acceptable. In any electrical system, it is important to know the short circuit level of each of the protective equipment. However, we should not forget to verify the X/R ratio of the faulted bus against the circuit breaker test power factor or X/R ratio based on their product standard (e.g. UL/NEMA/ANSI or IEC). The example above
XI. References 1 IEEE Std 551-2006, IEEE Recommended Practice for Calculating Short-Circuit currents in Industrial and Commercial Power System. 2 IEEE Papers, Simplifying IEEE/ANSI and IEC Fault Point X/R Ratio for Breaker Evaluation by Ketut Dartawan and Conrad St. Pierre 3 IEC 60497-1:2009, Low-voltage switchgear and control gear - Part 1: General rules 4 IEC 60497-2:2009, Low-voltage switchgear and control gear - Part 2: Circuit-breakers 5 ANSI C37.5-1989, Calculation of Fault Currents for Application of Power Circuit Breakers Rated on a Total Current Basis 6 UL 489-1986, Molded Case Circuit Breaker and Circuit Breakers Enclosure 7 IEC 60909-0, Corrigendum 1 - Short-circuit currents in three-phase A.C. systems - Part 0: Calculation of currents 8 Electrical Transient Analyzer Program (ETAP) Software version 6.0
Appendix Courtesy of ABB Phil., Inc.
proM Compact
Technical features
S 200
of MCBs S 200 series
Series
S 200
S 200 M
Characteristics
B,C,D
B,C,D
Rated current
[A]
Breaking capacity
[kA]
Reference standard IEC 23-3/EN 60898 IEC/EN 60947 - 2 Alternating current
Nr. Poles lcs lcu
1, 1P + N 2,3,4 2,3,4
lcs
1, 1P + N
S 200 P B,C,D
B,C,D
S 280 B,C,D
B,C
K,Z
K,Z
K,Z
K,Z
0.5 ≤ ln ≤ 63
0.5 ≤ ln ≤ 63
0.2 ≤ ln ≤ 25
32 ≤ ln ≤ 40
50 ≤ ln ≤ 63
80≤ LN ≤ 100
6
10
25
15
15
6
133 230 230 400 500 690
20 10 20 10
25➇ 15➇ 25➇ 15➇
40 25 40 25
25 15 25 15
25 15 25 15
15 6 10 6
133
15
18.7 ➇
20
18.7
18.7
15
Ue [V] 230 / 400
30
K,Z
(continued …)
2,3,4 2,3,4
7.5 15 ➀ 7.5
11.2 ➇ 18.7 ➇ 11.2 ➇
12.5 20 12.5
11.2 18.7 11.2
7.5 18.7 7.5
6 10 6
20 10
10
15
10
10
10
20 10
10
15
10
10
10
24 60 125 250
20 10
10
15
10
10
10
48 125 250 500 600 800 375
20 10
10
15
10
10
10
230 230 400 500 690
IEC/EN 60497 - 2 Direct current T= lR≤ 5ms for all series except S280 UC and S800S-UC where T = lR
View more...
Comments