Diesel Generator Sizing Voltage Dip Calculations Worksheet
Load summary
Largest Motor Connected to DG Data
Here you just add your load connected to DG bus. Make sure the load is in kVA, if it's in kW then divide it by system power factor. Make sure to also include largest motor kW in this.
Rated power Power factor Efficiency Full load current Starting current Starting power factor Rated voltage
Load kVA
1665
Total power consumption
kVA 2081.25 kVA @ 0.85 power factor
Starting capacity
Power consumption of all other loads
1424.262 kVA
tan θ2
1.252918
0.897192 51.40534 degree
A B C D
1210.623 210.2362 750.2766 1029.943
Minimum DG size
θ2
450 0.89 0.962 632 2 0.2 480
A times
632.187
V
1051.181 kVA Angels Section θ1 0.554811 31.78833 degree sin θ1 cos θ1 θ
2277.723 kVA
kW
θ2
0.526783 0.85
1.369438 78.46304 degree sin θ cos θ
0.979796 0.2
0.897192 51.40534 degree sin θ2 cos θ2
0.781579 0.623807
data to be entered by user calculated data
Page 1 of 3
11/16/2012
Diesel Generator Sizing Voltage Dip Calculations Worksheet
Generator terminal voltage Transit reactance X'd
480 0.25
initial pu current final pu current a b
0.26125 0.171958
Vg
0.905503 pu
Vdip
0.094497
V pu
0.625301 pu 0.95 pu
Voltage dip at DG bus formula:
(use 1.0 pu)
Calculations of motor per units currents or
9.449717 %
the above reading is the voltage dip at the main bus connected to the DG, which also will affect all other connected loads. 10% voltage dip due to starting of the largest motor while all other loads connected, is acceptable reading. Next step, should be to calculate the voltage drop at motor terminal during motor starting. And this reading should not exceed 20% of system rated voltage. Refer to worksheet #3 for the final step in the calculations.
Page 2 of 3
for full pu current you can always use 1.0 pu current, assuming that the system runs at full load at its rated kW. the initial pu current is the total load connected to the DG without including the largest motor. Initial power Initial current
1424.262 kVA 1713.121 A
Total power Total current
2277.723 kVA 2739.675 A
Initial pu Current
0.625301 pu
11/16/2012
Diesel Generator Sizing Voltage Dip Calculations Worksheet
Cable voltage drop at largest motor terminal: Cable length Cable resistance Cable Rreactance Vd
180 0.0495 0.045
m Ω/km Ω/km
0.044339 pu
Cable resistance data must be entered manually from manufacturer's catalogue. Cable reactance data must be entered manually from manufacturer's catalogue. or
4.433915 %
Vd is the voltage drop on the cable caused by motor starting current.
Total Voltage Drop at Largest Motor Starting
13.88363206
%
and this value should be at all times kept less than 20%, otherwise re-do the calculations again. Maybe try different cable size (larger cable, or double run per phase).
This worksheet is brought to you by Rajab. (http://thepiratebay.se/user/rajabmm/)
Thank you for interesting in our services. We are a non-profit group that run this website to share documents. We need your help to maintenance this website.