TUTORIAL SCOPE 1. FUNDAMENTALS 2. CHARACTERISTICS 3. POLARIZATION 4. ZONES SETTING CRITERIA 5. MHO VS QUADRILATERAL 6. SWITCH ON TO FAULT 7. POWER SWING BLOCKING/TRIPPING 20 December 2010
Protection Courses
2
TUTORIAL SCOPE 8. LOAD ENCROACHMENT 9. LOSS OF POTENTIAL 10. UNIT PROTECTION 11. PERMISSIVE UNDER REACH 12. PERMISSIVE OVER REACH 13. CARRIER BLOCKING 14. CURRENT REVERSAL 20ZONE December 15. 1 2010 EXTENSIONProtection Courses
3
TUTORIAL SCOPE 16. WEAK IN-FEED 17. SERIES COMPENSATION 18. MUTUAL COMPENSATION 19. AUTO RECLOSER 20. STUB PROTECTION 21. CCVT TRANSIENT 22. DIRECTIONAL EARTH FAULT 20 December 2010
Protection Courses
4
MHO
MHO CHARACTERISTICS 20 December 2010
Protection Courses
5
MHO CHARACTERISTICS
20 December 2010
Protection Courses
6
Quadrilateral
QUADRILATERAL CHARACTERISTICS 20 December 2010
Protection Courses
7
OFFSET MHO CHARACTERISTICS
20 December 2010
Protection Courses
8
20 December 2010
Protection Courses
9
POLARIZATION METHODS SELF POLARIZATION Terminal faults will not cover CROSS POLARIZATION Use other healthy phase voltages Terminal three phase fault will not cover MEMORY POLARIZATION Covers all type of faults 20 December 2010
Protection Courses
10
VRB VB VBY
VR VY VYR
POLARIZATION METHODS
20 December 2010
Protection Courses
11
ZONES SETTING CRITERIA S/Stn 1
S/Stn 2
Relay A
Time
Zone 3R
Relay B
Zone 2
Relay C
Zone 2
Zone 1
Relay D
Zone 3F
Zone 3R Zone 1
Zone 3R
Zone 3
20 December 2010
S/Stn 3
Zone 2
Protection Courses
Zone 2
Zone 1
Zone 1
Zone 3R
12
ZONES SETTING CRITERIA
X A
B
C
Zone 4 Zone 1 Zone 2
Zone 3
R
20 December 2010
Protection Courses
13
SWITCH ON TO FAULT
SWITCH ON TO FAULT. Failure to remove Earth Clamps after CB Maintenance Practically Zero Impedance in fault path. Fault Point is at the Origin - Boundary condition for Zones 1 & 2 For a 3-Phase fault, cross-polarising will have no effect
SOTF Fault Point
20 December 2010
Protection Courses
14
SOTF ALGORITHMS AC SOTF - Used where VT is on LINE SIDE of the CB IF Current and Voltage have been Dead for 10 Secs AND the Current Rises ABOVE 30% of Nominal AND Voltage remains BELOW 20% of Nominal THEN Remove the Time Delay from Zone 3 AND Allow tripping on Overcurrent only FOR 200ms DC SOTF - Used where VT is on BUSBAR SIDE of the CB When Circuit Breaker Manual Close Handle is Operated Remove the Time Delay from Zone 3 FOR 400ms (Longer delay allows for CB Closing time) 20 December 2010
Protection Courses
15
Power Swing Outer boundary If the System Impedance Remains in the Power Swing Detection Zone for longer than the PSD Transit Time (Nominally 50 ms) POWER SWING ALARM will Operate
Power Swing Inner Zone 3
boundary
Zone 2
Power swing locus
Zone 1
Transit time
POWER SWING DETECTION & BLOCKING
20 December 2010
Protection Courses
16
POWER SWING DETECTION & BLOCKING
20 December 2010
Protection Courses
17
LOAD ENCROACHMENT
20 December 2010
Protection Courses
18
LOSS OF POTENTIAL
20 December 2010
Protection Courses
19
Operation of Zone 1 sends signal to remote end
Instantaneous trip if Zone 1 Operation Zone 2 + Signal from Remote end
S/Stn 1
SIGNALLING CHANNEL REQUIRED BETWEEN ENDS
PERMISSIVE UNDER REACH
Relay A
S/Stn 2
Relay B
Signalling Channel Zone 2 Carrier Aided Trip
Time
Relay C
Zone 2 Time Delayed Trip
Distance
Zone 1 (No Operation)
Zone 1
Zone 2
Distance
ALLOWS INSTANTANEOUS TRIPPING OVER 100% OF THE LINE LENGTH 20 December 2010
Protection Courses
20
Instantaneous Operation of Zone 2 sends signal to remote end
Instantaneous trip if Zone 1 Operation Zone 2 + Signal from Remote end
SIGNALLING CHANNEL REQUIRED BETWEEN ENDS
PERMISSIVE OVER REACH S/Stn 1
Relay A
S/Stn 2
Relay B
Signalling Channel Zone 2 Carrier Aided Trip
Time
Relay C
Zone 2 Time Delayed Trip
Distance
Zone 1 (No Operation)
Zone 2
Zone 2 Instantaneous Zone 1 Distance
ALLOWS INSTANTANEOUS TRIPPING OVER 100% OF THE LINE LENGTH 20 December 2010
Protection Courses
21
BLOCKING SCHEME
Operation of Zone 4 sends blocking signal to remote end
Instantaneous trip if Zone 1 Operation Zone 2 + No blocking Signal from Remote end WITHIN the Permissive Trip Time
SIGNALLING CHANNEL REQUIRED BETWEEN ENDS
S/Stn 1
Relay A
S/Stn 2
Relay B
Signalling Channel
Relay C
Zone 2 Carrier Aided Trip
Time
Distance
Zone 1 (No Operation)
Zone 1
Zone 2
Zone 4 - Blocking
Distance
ALLOWS INSTANTANEOUS TRIPPING OVER 100% OF THE LINE LENGTH 20 December 2010
Protection Courses
22
Operation of Zone 4 sends blocking signal to remote end
Instantaneous trip if Zone 1 Operation Zone 2 + NO BLOCKING SIGNAL from Remote End WITHIN the Permissive Trip Time
S/Stn 1
SIGNALLING CHANNEL REQUIRED BETWEEN ENDS
BLOCKING SCHEME
Relay A
S/Stn 2
Relay B
Signalling Channel
Relay C
Zone 2 Carrier Aided Trip
Time
Distance
Zone 1 (No Operation)
Zone 1
Zone 2
Distance
Zone 4 - Blocking (No Operation)
ALLOWS INSTANTANEOUS TRIPPING OVER 100% OF THE LINE LENGTH 20 December 2010
Protection Courses
23
CURRENT REVERSAL
20 December 2010
Protection Courses
24
CURRENT REVERSAL
20 December 2010
Protection Courses
25
CURRENT REVERSAL
20 December 2010
Protection Courses
26
No Signalling used between ends Used with Auto-Recloser only Results in More Breaker Operations
Gives improved fault clearance time for fault @ this position
S/Stn 1
Relay A
S/Stn 2
Relay B
Will trip CB @ 'A' for fault @ this position
Relay C
S/Stn 3
Relay C
Time
Trip
Zone 1 Ext Distance
Reclose
Zone 1
Zone 2
Zone 3F Distance
ZONE 1 EXTENSION SCHEME 20 December 2010
Protection Courses
27
WEAK IN FEED LOGIC
20 December 2010
Protection Courses
28
SERIES COMPENSATION • Used to increase load capacity • Improve power system stability • Improve load division on parallel paths • Reduce transmission losses
20 December 2010
Protection Courses
29
• Voltage reversal
SERIES COMPENSATION
20 December 2010
Protection Courses
30
Ia Double Circuit Line
ZMO
Fault
Ib
•
•
•
COUPLING BETWEEN LONG LINES CAN HAVE A SIGNIFICANT EFFECT ON DISTANCE PROTECTION MEASUREMENT ONLY AFFECTS ZERO SEQUENCE COMPONENT (PPS AND NPS COMPONENTS ARE BALANCED AND THEREFORE SUM TO ZERO)
IF RELAY NOT COMPENSATED FOR EARTH RETURN AND MUTUAL EFFECTS Z1 WILL BE OVER‐ ESTIMATED AND THE RELAY WILL UNDER‐REACH
MUTUAL COMPENSATION 1 20 December 2010
Protection Courses
31
MUTUAL COMPENSATION 2
• •
•
When one of the lines is out of service and earthed at both ends Energise a Status Input SWITCH TO ALTERNATE SETTINGS group
ALTERNATE SETTING GROUP uses – Increased Earth Fault Compensation Factor to take account of the Zero Sequence Mutual Coupling due to the parallel line
20 December 2010
Protection Courses
32
CCVT TRANSIENT
20 December 2010
Protection Courses
33
CCVT TRANSIENT
Distance element may over reach CCVT Trans. Reduce the fundamental component of the fault voltage results in decrease in the calculated impedance High capacitance reduced transient effect Passive Ferro-resonance reduced transient effect
20 December 2010
Protection Courses
34
CCVT TRANSIENT 20 December 2010
Protection Courses
35
•
Unrestricted Characteristic – Operates for any fault current above setting in selected direction
X •
Detects high impedance earth faults – Operate quantity - residual current – Polarising quantity - residual voltage
Line Angle
R
DIRECTIONAL EARTH FAULT 1 20 December 2010
Protection Courses
36
DUAL DIRECTIONAL EARTH FAULT X •
TWO Unrestricted Characteristics
• • •
Common Line Angle Setting Different Operating Current Settings Forward DEF – Operates on Current above FWD setting in FORWARD direction Reverse DEF – Operates on Current above REV setting in REVERSE direction
•
20 December 2010
Protection Courses
Forward DEF
Line Angle
R
Reverse DEF
37
DIRECTIONAL EARTH FAULT 2 • •
Discrimination using DTL or IDMTL Time Grading (DEF Direct Trip) • OR High Speed operation using a Signalling Channel (DEF POR)
Operation of both DEF elements allows instantaneous tripping
• • •
If no Signalling Channel is available OR Signalling Channel fails
•
RELAY CAN OPERATE AS BACK-UP TIME GRADED OVER CURRENT 20 December 2010
Thank you for interesting in our services. We are a non-profit group that run this website to share documents. We need your help to maintenance this website.