DATA SHEET of Transformers -100-300-500-1000 kVA

May 5, 2019 | Author: engnajeeb75 | Category: Transformer, Power Engineering, Electric Power, Electromagnetism, Electricity
Share Embed Donate


Short Description

Download DATA SHEET of Transformers -100-300-500-1000 kVA...

Description

SCHEDULE TECHNICAL PARTICULARS: 100 KVA KVA (11-15/0,415 KV) Ref No.

Description

Unit

Data

POLE MOUNTED DISTRIBUTION TRANSFORMER

1 2 3 4 5 6 7 8 9 10

Applicable Standards Manufacture and Country of manufacture Manufacture’s Type Number Rated Power output Number of phases Rated frequency Rated Primary voltage / Current Rated Secondary voltage / Current Vector group Off - load tapping of primary winding

11

Ambient temperature

12

Temperature rise in Winding Top oil Core Applied test voltage, 1min, 50 Hz Primary winding Secondary winding Impulse test voltage, full wave, primary winding

13

14 15 16 17 18 19

20

21

22

23

No-load losses Load losses Impedance voltage No- load current Terminal bolts Material Diameter, primary side Diameter, secondary side Material of windings High voltage Low voltage Mass Total mass Mass of oil Untanked mas Termination Primary side Secondary side ALTITUDE ABOVE SEA LEVEL

Signature:____________________ Date: ____________________

IEC 60076 EREN TRAFO TURKEY ONAN kVA 100

°C

3 50 11 - 15 0,415 Dyn 11 11 * (-/+)2,5%*3 15 * (-/+)2,5%*3 50

°C °C °C

55 50 50

kV kV kV kW kW % %

28 3 75 at 11 kV 95 at 15 kV 300 1800 4 1

mm mm

copper 12 12

Hz kV/A kV/A %

COPPER COPPER

kg kg kg

720 190 340 Open bushing Open bushing

M

2300

SCHEDULE TECHNICAL PARTICULARS: 300 KVA (11-15/0,415 KV) Ref No.

Description

Unit

Data

POLE MOUNTED DISTRIBUTION TRANSFORMER

1 2 3 4 5 6 7 8 9 10

Applicable Standards Manufacture and Country of manufacture Manufacture’s Type Number Rated Power output Number of phases Rated frequency Rated Primary voltage / Current Rated Secondary voltage / Current Vector group Off - load tapping of primary winding

11

Ambient temperature

12

Temperature rise in Winding Top oil Core Applied test voltage, 1min, 50 Hz Primary winding Secondary winding Impulse test voltage, full wave, primary winding

13

14 15 16 17 18 19

20

21

22

23

No-load losses Load losses Impedance voltage No- load current Terminal bolts Material Diameter, primary side Diameter, secondary side Material of windings High voltage Low voltage Mass Total mass Mass of oil Untanked mas Termination Primary side Secondary side ALTITUDE ABOVE SEA LEVEL

Signature:____________________ Date: ____________________

IEC 60076 EREN TRAFO TURKEY ONAN kVA 300

°C

3 50 11 - 15 0,415 Dyn 11 11 * (-/+)2,5%*3 15 * (-/+)2,5%*3 50

°C °C °C

55 50 50

kV kV kV kW kW % %

28 3 75 at 11 kV 95 at 15 kV 700 3550 4 1

mm mm

copper 12 20

Hz kV/A kV/A %

COPPER COPPER

kg kg kg

1170 300 650 Open bushing Open bushing

M

2300

SCHEDULE TECHNICAL PARTICULARS: Ref No.

500 kVA (11-15/0,415 kV)

Description

Unit

Data

GROUND MOUNTED DISTRIBUTION TRANSFORMER (ONAN)

1 2 3 4 5 6 7 8 9 10

Applicable Standards Manufacture and Country of manufacture Manufacture’s Type Number Rated Power output Number of phases Rated frequency Rated Primary voltage / Current Rated Secondary voltage / Current Vector group Off - load tapping of primary winding

11

Ambient temperature

12

Temperature rise in Winding Top oil Core Applied test voltage, 1min, 50 Hz Primary winding Secondary winding Impulse test voltage, full wave, primary winding

13

14 15 16 17 18 19

20

21

22

23

No-load losses Load losses Impedance voltage No- load current Terminal bolts Material Diameter, primary side Diameter, secondary side Material of windings High voltage Low voltage Mass Total mass Mass of oil Untanked mass Termination Primary side Secondary side ALTITUDE ABOVE SEA LEVEL

Signature:____________________ Date: ____________________

IEC 60076 EREN TRAFO TURKEY ONAN kVA 500

°C

3 50 11 - 15 0,415 Dyn 11 11 * (-/+)2,5%*3 15 * (-/+)2,5%*3 50

°C °C °C

55 50 50

kV kV kV kW kW % %

28 3 75 at 11 kV 95 at 15 kV 1100 5500 4,5 1

mm mm

COPPER 12 30-Bus Duct

Hz kV/A kV/A %

COPPER COPPER

kg kg kg

1770 450 970 CABLE BOX CABLE BOX

M

2300

SCHEDULE TECHNICAL PARTICULARS: 1000 kVA (11-15/0,415 kV) Ref No.

Description

Unit

Data

GROUND MOUNTED DISTRIBUTION TRANSFORMER (ONAN)

1 2 3 4 5 6 7 8 9 10

Applicable Standards Manufacture and Country of manufacture Manufacture’s Type Number Rated Power output Number of phases Rated frequency Rated Primary voltage / Current Rated Secondary voltage / Current Vector group Off - load tapping of primary winding

11

Ambient temperature

12

Temperature rise in Winding Top oil Core Applied test voltage, 1min, 50 Hz Primary winding Secondary winding Impulse test voltage, full wave, primary winding

13

14 15 16 17 18 19

20

21

22 23

No-load losses Load losses Impedance voltage No- load current Terminal bolts Material Diameter, primary side Diameter, secondary side Material of windings High voltage Low voltage Mass Total mass Mass of oil Untanked mass Termination Primary side Secondary side ALTITUDE ABOVE SEA LEVEL

Signature:____________________ Date: ____________________

IEC 60076 EREN TRAFO TURKEY ONAN kVA 1000

°C

3 50 11 - 15 0,415 Dyn 11 11 * (-/+)2,5%*3 15 * (-/+)2,5%*3 50

°C °C °C

55 50 50

kV kV kV kW kW % %

28 3 75 at 11 kV 95 at 15 kV 1700 10500 6,2 1

mm mm

12 42-Bus Duct

Hz kV/A kV/A %

COPPER COPPER

kg kg kg

2950 740 1500 CABLE BOX CABLE BOX

M

2300