TECHNICAL DATA SHEET
Nozzles
NOZZLE DK 6 – 04 – 04 – A57°C A57°C (- T)
01.01.2007 Version 1 Page 1 of 1
Description This nozzle is used for automatic systems (wet pipe, dry pipe and pre-action). It requires no additional detection system (except pre – action system). In stand-by mode, the water is blocked by a piston inside the nozzle. As result of heat, the glass bulb bursts and the piston is pushed downwards by a spring. This opens the water way and water is discharged. Optional protective Teflon caps prevent passing contamination inside the nozzle.
General Properties
K – Factor Factor :
1,200
Flow r ate (at 100 100 bar):
12,00 l/min
Glass bulb:
Fast Response 57°C
Material Material nozzle body and cage:
Stainless steel
Material Material mic ro – nozzles:
Stainless steel with brass swirling device
Material Material micro – filter:
Stainless steel with copper seal
Material Material O – ring:
NBR*
Material Material piston :
Brass
Material spring:
Stainless Steel
Material Material protecti ve cap:
Teflon
Weight:
0,200 kg
* O – ring is recommended to be changed every 10 years
Part Part Number Descrip Descrip tion
Part Part Number
DK 6 – 04 – A57°C
33000918
DK 6 – 04 – A57°C – T
33000792
FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification. © FOGTEC Brandschutz Brandschutz GmbH & Co. KG ● Schanzenstr. Schanzenstr. 19A ● 51063 Köln Köln ● Germany
[email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 +49-(0)-221 96 22 30
J
TECHNICAL DATA SHEET
Nozzles
NOZZLE DK 5 – 11 – O (- T)
01.01.2007 Version 1 Page 1 of 1
Description This nozzle is used for deluge systems. It requires a system with manual, electric or pneumatic activation. activation. As soon as the system is activated, water mist is discharged. Optional protective Teflon caps prevent passing contamination inside the nozzle.
General Properties
K – Factor Factor :
0,290
Flow r ate (at 100 100 bar):
2,90 l/min
Material Material nozzle body:
Stainless steel
Material Material mic ro – nozzles:
Stainless steel with brass swirling device
Material Material micro – filter:
Stainless steel with copper seal
Material Material O – ring:
NBR*
Material Material protecti ve cap:
Teflon
Weight:
0,200 kg
* O – ring is recommended to be changed every 10 years
Part Part Number Descrip Descrip tion
Part Part Number
DK 5 – 11 – O
33000080
DK 5 – 11 – O – T
33000081
FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification. © FOGTEC Brandschutz Brandschutz GmbH & Co. KG ● Schanzenstr. Schanzenstr. 19A ● 51063 Köln Köln ● Germany
[email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 +49-(0)-221 96 22 30
Sockets
TECHNICAL DATA SHEET
INDUSTRIAL SOCKET OT L12
01.01.2007 Version 1 Page 1 of 1
Description Socket is to be used only with FOGTEC nozzles. Socket has one pipe connection in addition to nozzle inlet. Cutting ring and nut are included to socket assembly.
General Properties
Material (socket and nut s):
Stainless steel
Material (cutting rin g):
Stainless steel
Pipe tolerances:
12mm (ø12x1,0 DIN2391)
Max pr essure:
200 bar
Weight:
0,160 kg
Part Number Descrip tion Industrial Socket OT L12
Part Number 33100003
FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification. © FOGTEC Brandsch utz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany
[email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30
Sockets
TECHNICAL DATA SHEET
T-SOCKET OT L12
01.01.2007 Version 1 Page 1 of 1
Description Socket is to be used only with FOGTEC nozzles. Socket has two pipe connections in addition to nozzle inlet. Cutting rings and nuts are included to socket assembly.
General Properties
Material (socket and nut s):
Stainless steel
Material (cutting rin g):
Stainless steel
Pipe tolerances:
12mm (ø12x1,0 DIN2391)
Max pr essure:
200 bar
Weight:
0,340 kg
Part Number Descrip tion T-Socket OT L12
Part Number 33100030
FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification. © FOGTEC Brandsch utz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany
[email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30
TECHNICAL DATA SHEET
Wall Cabinets
W ALL C ABINET B WITH FOGGUN 2
01.01.2007 Version 1 Page 1 of 1
Description The FOGGUN wall cabinet system is designed for manual fire fighting. It can be either stand-alone or be part of a FOGTEC fixed installation with automatic or open nozzles. The FOGGUN wall cabinet system includes the wall cabinet and the FOGGUN 2 fire fighting gun. The FOGGUN 2 has two different spray pattern settings which can be chosen. The first setting creates a very effective fine droplet water mist, so even fluid or dust fires normally can be put out without splashing. The fine mist can be used in conjunction with a centrally located jet that creates a coarse mist. The central jet is used to achieve greater reach or to enable the use of mist on deep seated fires by using higher momentum of the droplets. The FOGGUN also produces lateral jets which protect the fire fighter from radiated heat.
General Properties
Material of box: Colour: Fire fighting gun:
Hose: Connection t o the system:
Carbon steel and corrosion resistant painting Red (RAL3000) FOGGUN 2: - Flow 25l/min @ 100 bar - Maximum pressure 120 bar - 12 side nozzles and 1 center nozzle DN12, 35 or 70 meters, stainless steel fittings Stainless steel fitting for pipe L15 (DIN2391)
Part Number Descrip tion
Hose Length
Part Number
Wall Cabinet B with FOGGUN 2
30 m
34000051
Wall Cabinet B with FOGGUN 2
50 m
34000052
FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification. © FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany
[email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30
J
Section Valves
TECHNICAL DATA SHEET
SECTION V ALVE – SOLENOID G 1“ (DN25)
01.01.2007 Version 1 Page 1 of 1
Description The section valve is meant to be used with deluge system and open nozzles. The pressure range of valve is designed for pump systems. The section valve is a 2/2 – way solenoid valve that is controlled by an external fire detection system. They can be installed in different locations or they can be centralized in a valve station with a separate supply pipe to each section, or decentralized at each distribution point from the main high pressure supply pipe to the individual sections. The test connection is used for air/water bleeding and testing the function of the solenoid section valve.
General Properties
Materials (contact to water):
Stainless Steel
Connections:
BSP - ISO 1719-1
Valve operation :
Normally Closed
Maximum operating pressure:
150 bar
Solenoids:
24V(1,9A), 110V(0,42A), 230V(0,2A)
Part Number Descrip tion
Part Number
SECTION VALVE - SOLENOID G1”(150bar) – 24V
35000074
SECTION VALVE - SOLENOID G1”(150bar) – 110V
35000095
SECTION VALVE - SOLENOID G1”(150bar) – 230V
35000025
FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification. © FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany
[email protected]
●
www.fogtec.com
● Tel.: +49-(0)-221
96 22 30
J
TECHNICAL DATA SHEET
Section Valves
SECTION V ALVE – OH G 1“ (DN25)
01.10.2008 Version 1 Page 1 of 1
Description Valve is meant for automatic systems where the main pipes are wet until automatic nozzles. The section valve is especially design for Ordinary Hazard Group 1 applications. The section valve groups nozzles to separate zones. The section valve has several functions which are following: A. B. C. D. E.
Detection of activated zone and giving an alarm signal Closing section manually Test connection for regular operation tests without activating nozzle Check valve function allowing drainage of main pipes without draining section piping Pressure gauge for visual pressure level check
The section valve can be equipped on request with limit switch to control the portion of manual closing valve. The section valve will be delivered without fittings.
General Properties
Materials (contact to w ater):
Stainless Steel / Brass
Connections:
ISO 1719-1
Maximum operating pressure:
140 bar
Pressure loss:
3.5bar @ 150l/min
Flow switch:
Max 200V, 1A, 20VA
Pressure gauge:
0-250bar
Part Number Descrip tion
Part Number
SECTION V ALVE – OH G1 (140bar) Standard
35000255
SECTION V ALVE – OH G1 (140bar) with limit switch
on request
FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification. © FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany
[email protected]
●
www.fogtec.com
● Tel.: +49-(0)-221
96 22 30
J
Section Valves
TECHNICAL DATA SHEET
SECTION V ALVE – PNEUMATIC G 1“ (DN25)
01.01.2007 Version 1 Page 1 of 1
Description This valve is meant for deluge systems where the main pipes are wet until section valves. Section piping is dry and only open nozzles are used. The valve combines following parts. A. Manual service valve, B. Testing connection and C. pneumatic driven main valve.
General Properties
Materials:
Stainless Steel
Connections:
BSP - ISO 1719-1
Valve operation:
Normally Closed
Maximum operating pressure:
120 bar
Ai r s up pl y: Power supply:
6 bar 24 V, DC
Part Number Descrip tion
Part Number
SECTION V ALVE – PNEUMATIC G 1” (120bar)
35000098
Fogtec Brandschut z GmbH & Co. KG Schanzenstr. 19 A D–51063 Köln (Cologne) Tel: +49-221-96223-0 Fax: +49-221-96223-30
[email protected] www.fogtec.com FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification. The document is protected under copyright law. All rights with regard to the contents are reserved. These documents are to be treated confidentially. They may not be copied and third parties may not be allowed access to them without written consent. They are to be returned to us on request. These documents may not be translated, microfilmed nor stored or further processed in electronic systems without written consent. In the case of contravention of our rights legal action will be taken. Any rights to claim compensation are reserved
J
Section Valves
TECHNICAL DATA SHEET
SECTION V ALVE – PRE- ACTION G 1“ (DN25)
01.01.2007 Version 1 Page 1 of 1
Description This valve is to be used in water mist systems with automatic nozzles and wet pipe work until the section valve, where the pipework after section valve shall be under pressurized air in stand-by situation. The valve combines following parts. A. Manual service valve, B. Two pressure gauges, C. Pressure sensor, D. Testing connection and E. Pneumatic driven main valve.
General Properties
Materials:
Stainless Steel
Connections:
BSP - ISO 1719-1
Valve operation:
Normally Closed
Maximum operating pressure:
120 bar
Ai r s up pl y:
6 bar
Power supply:
24 V, DC
Part Number Descrip tion
Part Number
SECTION V ALVE – PRE-ACTION G1” (120bar)
35000104
FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification. © FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany
[email protected]
●
www.fogtec.com
● Tel.: +49-(0)-221
96 22 30
TECHNICAL DATA SHEET
Cylinder systems
01.01.2007
80-LITRE M ASTER MODULE ELECTRIC RELEASE/DRY PIPE SYSTEM
Version 1 Page 1 of 1
Description The activation is triggered by an electric signal. The nitrogen cylinder valve is a solenoid operated valve with manual override for safety reasons in case of electric failure. After activation the nitrogen is released to the slave module which will pressurize the pipe work and the nozzles starts the extinguishing. A pressure switch in the water manifold of the slave module gives a message of activated system.
General Properties
Nitrogen cy linder :
1 x 80 litre (pressure 200 bar at 20°C)
Release method:
Solenoid valve (electric signal or manual override) 31100380, 31100381, 31100382, 31100383,
Compatible Slave Modules:
31100384, 31100385 Connections: Slave port
Stainless steel fitting for pipe L12 (DIN2391)
N 2 filling port
W21,8x1/14” (DIN477)
Electric components: Solenoid
24V (10W) available also in 230V on request
Pressure switch
230V (max. 6A), set value 30bar
Part Number Descrip tion
Part Number
Dry Pipe Master Cylinder Module 1 x 80l N2, Electric release
31100311
FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification. © FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany
[email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30
TECHNICAL DATA SHEET
Cylinder systems
80-LITRE SLAVE MODULE 6 X 80L DRY PIPE SYSTEM
01.01.2007 Version 1 Page 1 of 1
Description The activation is triggered by pressure increase caused by activation of the master cylinder. After activation the nitrogen is released to the water cylinder which will pressurize the pipe work and the nozzles starts the extinguishing. A pressure switch in the water manifold gives a message of activated system. This module shall only used in combination with dry pipe system master modules.
General Properties
Water cylind er:
4 x 80 litre
Nitrogen cylinder:
1 x 80 litre (pressure 200 bar at 20°C)
Release method:
Activated by Dry Pipe System Master Module
Compatible Master Modul es:
31100311, 31100316
Connections: Water port
Stainless steel fitting for pipe L12 (DIN2391)
N 2 filling port
W21,8x1/14” (DIN477)
Part Number Descrip tion
Part Number
Dry Pipe Slave Cylinder Module 4 x 80l H20 + 1 x 80l N2
31100382
FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification. © FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany
[email protected]
●
www.fogtec.com
● Tel.: +49-(0)-221
96 22 30
TECHNICAL DATA SHEET
Pump systems
PUMP UNIT 2X120 L/MIN A UTOMATIC
00.00.2007 Version 1 Page 1 of 2
Description This 2x120 l/min pump unit is designed to be used in automatic systems. The pump unit is built modular and with reduced number of components. The jockey pump is meant to keep the pre-pressure of approx. 20bar in wet pipes. The high-pressure pump type used is a triplex plunger high-pressure pump with the maximum flow rate of 120l/min at maximum pressure of 120bar. Both pumps in the pump unit assembly have individual electric motors, couplings and safety valves. Other main components are connected to the suction and high-pressure manifolds that are shown in the dimension drawing.
Dimensions and main components
Jockey pump unit Frame Suction manifold Electric motor Housing and coupling High-pressure pump High-pressure manifold
Specifications Materials (contact to water):
Stainless Steel / Brass
Suction connection:
DN80 DN32 120 bar 2x120 l/min
Discharge connection: Maximum operating pressure: Maximum f low rate:
FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification. © FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany
[email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30
TECHNICAL DATA SHEET
Pump systems
PUMP UNIT 2X120 L/MIN A UTOMATIC Safety valve:
One per pump
Strainer / filt er:
One per pump 2x30kW (400V, 50Hz) 1060kg
Electric motor: Weight:
00.00.2007 Version 1 Page 2 of 2
Part n umbers and arrangement The pump unit is available in two versions. The standard version has all pipe connections to the right side of the pump unit. The mirrored version has all pipe connections to the left side. 2x120 l/min Aut omati c, Standard (30100835)
2x120 l/min Aut omati c, Mirro red (30100857)
Descript ion
Version
Part number
2 x 120l/min Automatic
Standard
30100835
2 x 120l/min Automatic
Mirrored
30100857
Compatibility Pump unit can be connected to the following tank, suction line / filling units and return line.(See technical data sheets of tank units in order to see the different layout possibilities with different tank and pump unit combinations) 2x120 l/min Aut omati c, Standard (30100835): Tank unit / Suction line
500L, DN80 1000L, DN80 3000L, DN80 4000L (On request)
Part Number
Return line (optional) Compressor (optional)
Standard 30000729 Standard 30000735 Standard 30000745
DN50 30000716 DN50 30000716 DN50 30000716
-
-
All suitable All suitable All suitable -
2x120 l/min Automatic, Mirrored (30100857): Tank unit / Suction line
500L, DN80 1000L, DN80 3000L, DN80 4000L (On request)
Part Number
Return line (optional) Compressor (optional)
Mirrored 30000732 Mirrored 30000740 Mirrored 30000750
DN50 30000716 DN50 30000716 DN50 30000716
-
-
All suitable All suitable All suitable -
FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification. © FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany
[email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30
TECHNICAL DATA SHEET
Pump systems
PUMP UNIT 2X120 L/MIN DELUGE
13.04.2007 Version 1 Page 1 of 2
Description This 2x120 l/min pump unit is designed to be used in deluge systems. The pump unit is built modular and with reduced number of components. The pump type used is a triplex plunger high-pressure pump with the maximum flow rate of 120l/min at maximum pressure of 120bar. Both pumps in the pump unit assembly have individual electric motors, couplings and safety valves. Other main components are connected to the suction and high-pressure manifolds that are shown in the dimension drawing.
Dimensions and main components
Frame Suction manifold Electric motor Housing and coupling High-pressure pump High-pressure manifold
Specifications Materials (contact to water):
Stainless Steel / Brass
Suction connection:
DN80
Discharge connection:
DN32
Maximum operating pressure:
120 bar
Maximum f low rate:
2x120 l/min
Safety valve:
One per pump
Strainer / filt er:
One per pump
Electric motor:
30kW (400V, 50Hz)
Weight:
1060kg
FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification. © FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany
[email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30
TECHNICAL DATA SHEET
Pump systems
13.04.2007 Version 1
PUMP UNIT 2X120 L/MIN DELUGE
Page 2 of 2
Part n umbers and arrangement The pump unit is available in two versions. The standard version has all pipe connections to the right side of the pump unit. The mirrored version has all pipe connections to the left side.
2x120 l/min Deluge, Standard (30100856)
2x120 l/min Deluge, Mirro red (30100858)
Descript ion
Version
Part number
2 x 120l/min Deluge
Standard
30100856
2 x 120l/min Deluge
Mirrored
30100858
Compatibility Pump unit can be connected to the following tank, suction line / filling units and return line. (See technical data sheets of tank units in order to see the different layout possibilities with different tank and pump unit combinations) 2x120 l/min Deluge, Standard (30100856): Tank unit / Suction line 500L, DN80 1000L, DN80 3000L, DN80 4000L (On request)
Pump unit
Return line (optional)
Compressor (optional)
Standard 30000729 Standard 30000735 Standard 30000745
DN50 30000716 DN50 30000716 DN50 30000716
-
-
-
Pump unit
Return line (optional)
Compressor (optional)
Mirrored 30000732 Mirrored 30000740 Mirrored 30000750
DN50 30000716 DN50 30000716 DN50 30000716
-
-
All suitable All suitable All suitable
2x120 l/min Delug e, Mirro red (30100858): Tank unit / Suction line 500L, DN80 1000L, DN80 3000L, DN80 4000L (On request)
All suitable All suitable All suitable -
FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification. © FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany
[email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30
TECHNICAL DATA SHEET
Pump systems
COMPRESSOR
17.04.2007 Version 1 Page 1 of 2
Description The compressor produces compressed air that is needed in pre-action and dry pipe systems for filling the pipes or using pneumatic operated valves in deluge systems. The compressor for all systems is the same, but there are two different mounting versions. The compressor with wall mounting kit can be used with all pump units. The compressor with pump unit mounting kit is available only with 2 and 3 x 120 l/min pump systems.
Types and Dimensions
COMPRESSOR WITH WALL MOUNTING KIT
COMPRESSOR WITH PUMP MOUNTING KIT
Part numbers and Compatibility Part number
Type
Compatibility
30100855
Standard compressor with wall mounting kit
All pump units
Standard compressor with pump mounting kit
2x120l/min Deluge (30100856, 30100858) 2x120l/min Automatic (30100835, 30100857) 3x120l/min Deluge (30100860, 30100862) 3x120l/min Automatic (30100859, 30100861)
30100834
FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification. © FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany
[email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30
TECHNICAL DATA SHEET
Pump systems
COMPRESSOR
17.04.2007 Version 1 Page 2 of 2
Specifications Pressure connection: Capacity: Maximum pressure Volume of tank: Power requirement:
¼“ connection, equipped with quick coupling for DN6 hose 150l/min @ 6bar 10bar 24 litres 1.2kW (400V, 50Hz)
FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification. © FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany
[email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30
TECHNICAL DATA SHEET
Tank Unit
00.00.2007 Version 1
1000 L ITRE T ANK UNIT
Page 1 of 4
Description The 1000 litre tank unit can be used with all standard pump units. The tank unit can work as total volume storage or as break tank where water is supplied from a tank to the pumps. The tank is simultaneously filled with fresh water from an external water supply in brake tank arrangement. The main water supply must assure the minimum flow rate of the pump system within a pressure range of 1,5 to 6 bar to tank filling. Tanks should be placed generally close to the pump unit, but the tank pump orientation can be changed to different layouts. The standard tank is made of black polyethylene*. The tank frame is galvanized carbon steel. The filling unit and suction line assemblies are part of the tank unit, but depended on the used pump configuration. The available suction line and filling unit assemblies are available in different sizes. The return line assembly can optionally be installed. The tank overflow is used to protect the tank against overfilling. The tank overflow should always be connected to water drain. A level measurement is mounted to the side wall of the tank. This level measurement optically indicates the water level in the tank. It also includes switches, giving opening signals via the PLC control to the tank filling valve as well as a minimum alarm if the water level in the tank reaches the lowest level.
Dimensions and main components**
Main filter Frame Overflow Return line Suction connection Filling valve
* 1000 litre stainless steel tank unit is also available on request, please contact FOGTEC Fire Protection. ** Notice! Dimensions might change slightly depending on chosen filling unit and suction line assembly FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification. © FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany
[email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30
TECHNICAL DATA SHEET
Tank Unit
00.00.2007 Version 1
1000 L ITRE T ANK UNIT
Page 2 of 4
Specifications Tank material:
Polyethylene (black)
Suction lin e size:
DN40, DN50, DN80, DN100 and DN125
Filling unit assemblies:
DN25, DN40 and DN50
Overflow connection:
DN80
Return l ine assembly (option al):
DN25 and DN50
Filtration rate (water):
100µm (abs.)
Filtration r ate (air):
10 µm (abs.)
Versions Pump unit is available in two versions, standard and mirrored. The standard version has always all pipe connections to the left side of the tank unit, which means that it can be connected to standard pump unit versions. The mirrored version means connections to the right side and only mirrored pump units. The main dimensions of standard and mirrored pump units are exactly same.
1000 Lit re Tank Unit Standard
1000 Lit re Tank Unit Mirro red
FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification. © FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany
[email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30
TECHNICAL DATA SHEET
Tank Unit
00.00.2007 Version 1
1000 L ITRE T ANK UNIT
Page 3 of 4
Possible layout arrangements The connections between tank unit and pump units are flexible, which enables changing of the layout easily. The following drawing shows approximate areas where tank unit can be positioned. The drawing shows standard pump and tank units, but this can be mirrored with mirrored pump and tank units.
Possible tank unit installation area with standard supply components
There is minimum distance between tank and pump unit that varies depending on the pump unit configuration. The normal minimum distance is 1.5 metre. This can be reduced to 0.7 metre if the pump unit configurations of 1-2 times 50l/min pumps or 1 time 120l/min pump units are used.
Part n umbers and compatibility The part numbers of different pump unit configurations are shown in the following table. The tank unit includes always the suction line and filling unit assembly. These have to be dimensioned according to pump unit configuration. All compatibilities between different pump units and 1000 litre tank unit are explained in the table. The return line assembly is an optional selection with the different part number. Notice! 1x50l/min and 1x120l/min standard pump units can be used with both tank designs.
FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification. © FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany
[email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30
You're Reading a Preview Unlock full access with a free trial.
Download With Free Trial
TECHNICAL DATA SHEET
Pump systems
CONTROL C ABINETS FOR 120L /MIN PUMP UNITS
16.04.2007 Version 1 Page 1 of 2
Description The control cabinet controls and monitors all electrical components in the pump system according the FOGTEC software that is installed to the PLC. Control cabinet controls both tank unit and pump unit. The electrical connections to tank unit are standard independent which tank unit is used, but they differ depending on the pump concept. All pump units will have a different control cabinet depending on the number of pumps and used system type (deluge/automatic). Control cabinets are available with two possible mounting possibilities depending on the size. Smaller systems with 1 to 2 pumps use cabinets with wall mounting. Larger pump systems are built to self standing cabinets. Notice! Control cabinets have different sizes depending on mounting method and number of controlled pumps.
All control cabinets have several self-diagnostic functions and failures are detected automatically. Control cabinets have different programs for service runs. Pumps can also be manually operated and tested with push buttons on the door of control cabinet.
Specifications Power supply:
400V 50Hz (L1,L2,L3,PEN-4 wires)
Power requir ement:
1x120 l/min = 30kW (main fuses 80A) 2x120 l/min = 60kW (main fuses 125A) 3x120 l/min = 90kW (main fuses 200A) 4x120 l/min = 120kW (main fuses 250A)
IP class:
54
Potential free contacts :
A. Common failure B. System running C. Start signal (only deluge systems) RAL7035
Colour:
Part num bers, Compatibi lity and Dimensions
FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification. © FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany
[email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30