CUMINS PS0500 Service manual.pdf
Short Description
Download CUMINS PS0500 Service manual.pdf...
Description
Service Manual Power Start 0500
Genset Models: X1.3, S and B series
1
Foreword Schedule of Abbreviations AC ACB ACH ATS AVR
Alternating Current Air Circuit Breaker Anti-Condensation Heaters Automatic Transfer Switch Automatic Voltage Regulator
BHP BMS BST
Brake Horsepower Building Management System Busbar Sensing Transformer
CB CCA CHP COP CT
Circuit Breaker Cold Cranking Amps Combined Heat and Power Continuous Power Rating Current Transformer
dB(A) DC DIP
Unit of noise level Direct Current Dual In-line Package
DMC DMSU
Digital Master Control Demand Load Standby Unit
EMCU EMF EPU
Engine Monitoring and Control Unit Electromotive Force Engine Protection Unit
FSS
First Start Sensor
GCP Genset GKWT
Generator Control Panel Generator set Global Kilowatt Transducer
HMI HV
Human/Machine Interface High Voltage
MCB MCCB MF MFSS MR
Miniature Circuit Breaker Moulded Case Circuit Breaker Mains Failed Master First Start Sensor Mains Returned
MST MSU MV
Mains Sensing Transformer Mains Sensing Unit Medium Voltage
NEC
Neutral Earthing Contact
PC PF PFC PLC PMG PRP PSU
PowerCommand® Power Factor Power Factor Controller Programmable Logic Controller Permanent Magnet Generator Prime Power Rating Power Supply Unit Potential Transformer / Current Transformer
PT/CT
2
QCC
Quadrature Current Control
RFI
Radio Frequency Interference
RMS RPM RTD
Root Mean Square Revolutions Per Minute Resistance Temperature Detector
V VAC VCB VDC VF VT
Volts Volts, Alternating Current Vacuum Circuit Breaker Volts, Direct Current Volt-free Voltage Transformer
IC I/O
Integrated Circuit Input / Output
kVA kVAR kW kWh
Apparent Power Reactive Power Active / Real Power Unit of electrical energy or work
LED LTP LTA
Light-Emitting Diode Limited Time Power Rating Low Temperature Aftercooling
LV
3
Low Voltage
INDEX Sr.
Contents
1.
Preliminary and safety………………………………..………… 1.1 Warning, Caution and Note styles used In this manual 1.2 General information 1.3 General plant safety code
5
2.
Control System…………………………………………..……….
6
2.1 2.2 2.3 2.4 2.5 2.6 2.7 3.
Control System Description Operating modes Display Module Configuration Mode Sequence of operation Stopping Connector Details
Status Indicators…………………………………..……………… 3.1 3.2
4.
Page no.
20
Fault/Status codes Fault code list
Troubleshooting………………………………………..…………... 22 4.1 4.2 4.3 4.4
Introduction Control unit Troubleshooting procedure for fault codes Fault Finding
5.
InPower connectivity……………………………..………………… 26
6.
Calibration Procedure…..…………………...…………………….. 27
7.
Wiring Diagrams…..…………………...…………………………... 33
4
1. Preliminary and safety 1.1 Warning, Caution and Note styles used in this manual The following safety styles found throughout this manual indicate potentially hazardous conditions to the operator, service personnel or the equipment. WARNING: WARNS OF A HAZARD THAT MAY RESULT IN SEVERE PERSONAL INJURY OR DEATH. Caution
Warns of a hazard or an unsafe practice that can result in product or property damage.
Note:
A short piece of text giving information that augments the current text.
1.2 General Information This manual should form part of the documentation package supplied by Cummins Power Generation Limited with specific generator sets. In the event that this manual has been supplied in isolation please refer to other Cummins Power Generation Limited literature, in particular the Health and Safety Manual (0908-0110-00). Note:
It is in the Operator’s interest to read and understand all Health and Safety information together with all Warnings and Cautions contained within the documentation relevant to the generator set, its operation and daily maintenance.
1.3 Generator Plant Safety Code Before operating the generator set, read the manuals and become familiar with them and the equipment. Safe and efficient operation can be achieved only if the equipment is properly operated and maintained. Many accidents are caused by failure to follow fundamental rules and precautions. WARNING: IMPROPER OPERATION AND MAINTENANCE CAN LEAD TO SEVERE PERSONAL INJURY OR LOSS OF LIFE AND PROPERTY BY FIRE, ELECTROCUTION, MECHANICAL BREAKDOWN OR EXHAUST GAS ASPHYXIATION. READ AND FOLLOW ALL SAFETY PRECAUTIONS, WARNINGS AND CAUTIONS THROUGHOUT THIS MANUAL AND THE HEALTH AND SAFETY MANUAL 0908-0110-00.
5
2. Control System 2.1 Control System Description The control system is used to start and stop the generator set, and provides full generator set monitoring capability and protection in a stand-alone situation (non paralleling) from the display screen. It monitors the engine for temperature, oil pressure, battery voltage, estop and genset hours, and provides voltage and current metering. In the event of a fault the unit will indicate the fault type and automatically shut down the generator set on critical faults. All indicators, control buttons and the display screen are on the face of the display module as illustrated in Figure 1. There are two fault level signals generated by the control system as follows: •
Warning: - signals an imminent or non-critical fault for the engine. The control provides an indication only for this condition.
•
Shutdown: - signals a potentially critical fault for the engine. The control will immediately take the engine OFF-load and automatically shut it down.
The standard control system operates on 12 VDC battery power. The auxiliary equipment operates on LV AC power. The history data is stored in non-volatile memory and will not be deleted due to loss of battery power.
Figure 1
KEY 1. 2.
Typical Control System Panel
Display Module Emergency Stop Button
NOTE: Normally E-stop placement on canopy is totally under OEM scope.
6
2.2 Operating Modes The PowerStart 0500 control is operated by the Manual / Start / Stop / Auto buttons on the display module face.
2.2.1 OFF Mode Note: Some published control service literature may refer to this mode as the STOP mode. When in the OFF mode, the control does not allow the generator set to start. Refer to Section 4.2.7 – Auto and Manual Run Modes – to re-start the generator set. If the generator set is running, in either Manual Run or Auto mode, and the Stop button is pressed, a normal shutdown sequence will be initiated. In OFF Mode the red LED above the Stop button will be lit.
2.2.2 Manual Run Mode When in Manual Run mode, the generator set starts and continues to run until the control is put into the OFF mode. Pressing the Stop button initiates a normal shutdown sequence that does not include a time delay stop. While in the Manual Run mode, any remote start signal is ignored.
2.2.3 Auto Mode When in Auto mode, the control allows the generator set to be started at any time, with a remote signal only. When a remote start signal is received, the generator set starts after a time delay start is completed (default delay is zero seconds). When a remote start signal is removed, the control performs a normal shutdown sequence which includes a time delay stop (default delay is zero seconds). If the generator set is running in Auto mode and the Stop button is pressed, the control immediately stops the generator set and the control transitions to the OFF mode.
2.2.4 Sleep Mode The PowerStart 0500 control enters a low power (Sleep) mode of operation where the current drawn is less than 60 milliamps (DC) at normal battery voltage levels. Sleep mode is automatically enabled, and the display module will turn itself OFF after five minutes of keypad inactivity when in OFF mode. When in Auto mode, the Sleep mode is enabled only when the trim “Wake in Auto Enabled” is enabled. If the trim is disabled (which is the default value), the Sleep mode will never be enabled when in Auto mode. It awakes from the sleep mode if the reset button is pressed or if there is a Tool wakeup input or a Remote Start signal is received or an E-stop signal is received both in Stop as well as Auto mode.
7
The control will not enter the Sleep mode if there are any active, unacknowledged, shutdown faults or if the control is in the Manual Run mode.
2.2.5 Battle Short Mode The purpose of Battle Short Mode is to satisfy local code requirements, where necessary. Battle Short mode is a generator set mode of operation that prevents the generator set from being shutdown by all but a few, select, critical shutdown faults. Caution:
All shutdown faults, including those overridden by Battle Short, must be acted upon immediately to ensure the safety and well being of the operator and the generator set.
WARNING: USE OF THE BATTLE SHORT MODE FEATURE CAN CAUSE A FIRE OR ELECTRICAL HAZARD, RESULTING IN SEVERE PERSONAL INJURY OR DEATH AND/OR PROPERTY AND EQUIPMENT DAMAGE. OPERATION OF THE SET MUST BE SUPERVISED DURING BATTLE SHORT OPERATION. This feature must only be used during supervised, temporary operation of the generator set. The faults that are overridden when in Battle Short mode can affect generator set performance, or can cause permanent engine, alternator or connected equipment damage. Only trained and experienced service personnel should enable this feature. When shipped from the factory, this feature is disabled. Caution:
If this mode of operation is selected, the protection of load devices will be disabled. Cummins Power Generation Limited will not be responsible for any claim resulting from the use of this mode.
Note:
The Battle Short feature must be enabled or disabled using the PC Service tool.
When Battle Short mode is enabled (Default is Disabled), the Warning status indicator lights, and code 1131 – Battle Short Active – is displayed. When Battle Short mode is enabled and an overridden shutdown fault occurs, the shutdown lamp remains lit even though the set continues to run. Fault code 1416 – Fail to Shutdown – is displayed. If the OK button is pressed to acknowledge the fault, the fault pop up is cleared from the display but remains in one of the scrolling screens displaying the fault code and its description to indicate that it is an active fault as long as Battle Short mode is enabled. Battle Short is suspended and a shutdown occurs immediately if any of the following critical shutdown faults occur: •
Speed Signal Lost (Loss of Speed Sense)
Fault code 121
•
Overspeed
Fault code 234
•
Local Emergency Stop
Fault code 1433
•
Excitation Fault (Loss of Voltage Sense)
Fault code 2335
•
Fault code 1123 – Shutdown After Battle Short – is then displayed.
8
2.3 Display Module - Front Panel Figure 2 shows the features of the front panel. It includes four LED indicators, the graphical display, and six buttons used to navigate through the menus and adjust parameters.
KEY 1. 2. 3. 4. 5. 6.
LED Indicator – Genset Running LED Indicator – Remote Start LED Indicator – Shutdown LED Indicator – Warning Manual Mode Button Start Button
7. 8. 9. 10. 11.
Auto Mode Button Reset Button Stop Button OK Button Alpha numeric LCD Display
2.3.1 Alpha numeric LCD Display The 2 line 16 Character, Backlit LCD display is used to indicate various generator set parameters in several frames. The frames scroll sequentially and display for 2 seconds. The scrolling can be stopped and parameters on a particular frame can be monitored for longer by pressing the OK button (See Figure 2). Pressing the OK button again causes the frames to start scrolling again. The display is also used to present the setup menus in the configuration mode. L1N=000 L2N=000 L3N=000 HZ=00.0
2 SEC
CURRENT FLT=212 CLNT TEMPOOR WRN
2 SEC
2 SEC
L12=000 L23=000 L13=000 HZ=00.0
E STOP=INACTIVE CUST IN=INACTIVE
2 SEC
2 SEC
I1=00.0 KVA=00.0 I2=00.0 I3=00.0
BATT VOLTS=11.7 GENSET HRS=00000
9
2 SEC
2 SEC
KVA1 KVA2 KVA3 00.0 00.0 00.0
2 SEC
Figure 1
OIL PRESS=003PSI CLNT TEMP=342F
Scrolling display messages
2.3.2 LED Indicators PS0500 includes four LED indicators, the graphical display and six buttons used to navigate through the menus and adjust parameters.
Genset Running This green LED is lit when the generator set is running at or near rated speed and voltage.
Shutdown This red lamp is lit when the control detects a Shutdown condition. The generator set cannot be started when this lamp is on. After the condition has been corrected, the lamp can be reset by pressing the Stop button. Note:When Battle Short mode has been enabled and an overridden shutdown fault occurs, the Shutdown lamp will be lit even though the generator set will continu to run.
Warning This yellow lamp is lit whenever the control detects a Warning condition. This lamp is automatically shut OFF when the Warning condition no longer exists.
Remote Start This green lamp indicates the control is receiving a remote run signal.
2.3.3 Control Panel Buttons Manual Press this button to put the control in Manual mode from OFF mode. If the Start button is not pressed within ten seconds of the pressing of the Manual Button, the control automatically returns to OFF mode The green LED above this button lights when the control is in Manual mode. Auto Press this button to put the control in Auto mode from OFF mode. The green LED above this button lights when the control is in Auto mode. In Auto mode, the generator set starts and runs when a remote start signal is received. It is also used to exit from configuration mode.
10
Stop Press this button to switch to the OFF mode from both Manual as well as Auto modes. The Red LED above this button lights when the control is in OFF mode. Start In Manual mode, press this button to initiate a Manual Start sequence. In Auto mode, this button has no effect. Reset This button wakes the control from Power Down Sleep Mode. The control enters configuration mode when Reset button and Stop button are pressed together. To enter in configuration mode it is necessary that the control is in Stop mode. WARNING: ADJUSTING THE SETTINGS IN CONFIGURATION MODE MUST ONLY BE DONE BY TECHNICALLY TRAINED AND EXPERIENCED SERVICE PERSONNEL. THE FREQUENCY SETTINGS MUST ONLY BE ADJUSTED TO CORRESPOND TO THE PARAMETERS OF THE INSTALLED INPUT POWER SUPPLY. SAVING SETTINGS THAT DO NOT CORRESPOND TO THE POWER SUPPLY CAN CAUSE SEVERE PERSONAL INJURY AND EQUIPMENT OR PROPERTY DAMAGE. OK This button is used to acknowledge the fault pop ups. It is also used to Pause / Resume the scrolling of the parameter frames. It is used to select the menu items and the parameters in the selected menu in the configuration mode. The selected parameter will be preceded by an * asterisk and will get saved when the configuration mode will be exited using Auto button. Note: Manual, Auto, OK and Reset buttons are used for navigation in the configuration mode.
2.3.4 Default Settings The control panel can display SAE or Metric units of measurement and should be set during the initial setup of the generator set. Qualified service personnel are required to change the default setting. Contact your authorised distributor.
2.3.5 Fault Messages A Fault message is an indicator of a Warning or Shutdown condition that is also announced with a lamp indicator. Fault messages include the fault code number and a short description. The below table provides a list of fault codes, fault types, messages displayed, and descriptions of the faults.
11
2.3.6 Fault Acknowledgement Shutdown Faults are reset after a shutdown fault is cleared when engine comes to a standstill and all start commands are removed. In Manual mode, the start command is removed when the Stop button, on the front panel, is pressed. In Auto Mode, the start command is removed when the Remote Start signal is removed. Faults are removed from the display when they are cleared. Note: Faults are re-announced if they are detected again after being acknowledged.
2.3.7 Display Module - Auto and Manual Run Modes Auto, Manual Run and OFF modes can be selected as follows:
Selecting Auto Mode To switch to Auto mode, a) Ensure that it is safe to do so before proceeding to change the mode. b) Press the Stop button to ensure that the control is in the OFF mode. c) Press the Auto button while in the OFF mode. The green LED above this button is lit when the control is in Auto mode. To disable Auto mode, press the Stop button. The generator set is now ready to receive a remote start signal that will initiate the Auto run mode. WARNING:
SHOULD A REMOTE START SIGNAL BE RECEIVED, THE GENERATOR SET WILL START AUTOMATICALLY. ENSURE THERE IS NO DANGER TO PERSONNEL OR EQUIPMENT SHOULD THE GENERATOR SET START WITHOUT WARNING.
WARNING:
MANUAL RUN MODE CANNOT BE SELECTED FROM AUTO MODE. THE CONTROL HAS TO BE IN STOP MODE BEFORE CHANGING THE MODE. SWITCHING TO STOP MODE WILL RESULT IN THE GENERATOR SET SHUTTING DOWN.
Selecting Manual Run Mode To switch to Manual Run mode, a) Ensure that it is safe to do so before proceeding to change the mode. b) Press the Stop button to ensure that the control is in the OFF mode
12
c) Press the Manual button on the front panel while in the OFF mode. The green LED above this button is lit when the control is in Manual mode. To disable Manual Run mode, press the Stop button. Note:
Auto mode cannot be selected whilst in Manual Run mode. The control has to be in OFF mode before changing the mode. Switching to OFF mode will result in the generator set shutting down.
Selecting OFF Mode To switch to OFF mode. a) Ensure that it is safe to do so before proceeding to stop the set b) Press the Stop button on the front panel. The red LED above the Stop button is lit when the control is in the OFF mode
2.4 Configuration Mode WARNING:
ADJUSTING THE SETTINGS IN CONFIGURATION MODE MUST ONLY BE DONE BY TECHNICALLY TRAINED AND EXPERIENCED SERVICE PERSONNEL. THE FREQUENCY SETTINGS MUST ONLY BE ADJUSTED TO CORRESPOND TO THE PARAMETERS OF THE INSTALLED INPUT POWER SUPPLY. SAVING SETTINGS THAT DO NOT CORRESPOND TO THE POWER SUPPLY CAN CAUSE SEVERE PERSONAL INJURY AND EQUIPMENT OR PROPERTY DAMAGE.
Configuration mode is used to adjust the parameters of the generator set and must only be done by technically trained and experienced service personnel.6 membrane keys are used to step through the different menu options and to adjust parameters.
13
Reset
Entering into the Config Mode…
Ok
Press For 5 Sec
No Navigation is needed
SW PART 3267727 SW VER 1.12
As seen from the above figure, on pressing RESET and OK button on PS0500 for 5 seconds, controller enters into configuration mode. Before displaying the menu, software part no. and version are displayed. One needs to understand key to operate.
Keys
Properties Will go to the next value Will go to the previous value
Will go down It shows the default value. When selected for a
*
*
Particular value, comes which Indicates that value has been set
In Configuration mode the PowerStart 0500 control has the following menus: •
Alt Setup: Select alternator set-up parameters (Single / Three phase, 50 / 60 Hz operation, Star / Delta, Voltage etc.)
•
Units: Select SAE or Metric units of measure for Coolant Temperature and Oil Pressure
•
Oil Pr Input: Select the oil pressure sensor type.
•
Customer I/O: Configure the response to Customer Input and use of the Customer Output
•
Flt History: Displays the last five faults.
•
Load Defaults: Resets to the default values.
14
•
Lamp/LED Test: Tests all the LED’s on the PS0500 display module.
2.5 Sequence of Operation The generator set is run automatically using a Remote Start signal, or Manually using the generator set control panel buttons. LEDs are provided on the display module front panel to indicate the operating run mode of the generator set. The PowerStart 0500 control initiates a starter cranking signal and will perform an automatically sequenced manual start, under a complete engine protection system combined with full monitoring capability. If a fault is sensed at Start-up, the engine is locked out and will not start. The choice of Auto or Manual run mode is decided by authorised personnel during the generator set initial setup.
2.5.1 Starting Before attempting to start the generator set, the operator should read through this entire manual, together with the Health and Safety manual and the specific engine manual provided as part of the documentation pack supplied with the generator set. It is essential that the operator be completely familiar with the generator set and the PowerStart 0500 control. The following sub-sections cover the systems used to start and stop the generator set. Before starting the generator set, make sure that exhaust and fuel fittings are tight and properly positioned, and that proper maintenance and pre-start checks have been performed. The generator set can be configured for a number of starting cycles (one to seven) with set times for crank and rest periods for all starting modes (manual/remote). The default setting is for three start cycles, composed of fifteen seconds of cranking and 5 seconds of rest.
2.5.2 Starting at Display Panel (Manual Run Mode) To start the generator set in the Manual Run mode, press the Start button within 10 seconds of pressing the Manual button. Follow the instructions in Section 4.2.9 (Selecting Manual Run Mode). Note: Any Remote Start/Stop signal is ignored whilst in Manual Run Mode. The PowerStart 0500 control will initiate a starter cranking signal and will perform an automatically sequenced manual start, under a complete engine protection system combined with full monitoring capability. This will activate the engine control system and the starting procedure. The starter will begin cranking, and after a few seconds the engine will start and the starter will disconnect. In the Manual Run mode the control will not complete the Time Delay to Start or Time Delay to Stop. The Remote Start red LED, and the Manual Run, green LED will be lit. If the engine does not start, the starter will disengage after a specified period of time and the control will indicate a Fail to Start Shutdown.
15
Wait a minimum of two minutes for the starter motor to cool and then repeat the starting procedure. If the engine does not run after a second attempt, refer troubleshooting guidelines.
2.5.3 Starting from Remote Location (Auto Mode) To start the generator set in the Auto Run mode, press the Auto button from the menu bar of the display module front panel. Follow the instructions in Section 4.2.8 (Selecting Auto Mode). The Auto, green LED will be lit. Only on receipt of a remote start signal, and after a Time Delay to Start, will the PowerStart 0500 control initiate the starting sequence as above. The Remote Start LED will be lit.
2.6 Stopping 2.6.1 Stopping at Display Panel (Manual Mode) The module will not respond to any Remote Stop signal whilst in Manual Run Mode. When in Manual run mode, pressing the Stop button will initiate a normal (Manual) shutdown sequence. In the Manual Run mode the control will not complete the Time Delay to Stop. Note: Remove load and run set for five minutes to reduce engine heat before pressing the OFF button.
2.6.2 Stopping from Remote Location (Auto Mode) In Auto mode, the control allows the generator set to be started with a Remote Start Signal only. If the control receives a Remote Stop signal, the generator set will complete its normal shutdown sequence which includes a Time Delay Stop (Default is zero seconds). If the generator set is running in Auto mode and the Stop button is pressed, the control immediately stops the generator set without completing the Time Delay to Stop and the control transitions to the OFF mode.
2.6.3 Emergency Stop (Code 1434) The Emergency Stop Button is situated on the front of the Control Panel. This is a mechanically latched switch that will unconditionally stop the engine when pressed, bypassing any time delay to stop. Push this button in for Emergency Shutdown of the engine. Note : If the engine is not running, pushing the button in will prevent the starting of the engine, regardless of the start signal source (Manual or Auto - remote). When the Stop Button is pressed the display panel will indicate the Shutdown condition by illuminating the red Shutdown status LED graphical LCD display:
16
and displaying the following message on the
If a Stop Button is activated the following message will be displayed; Fault: 1434 EMERGENCY SH To reset: a)
Press the OK button on the Display Module to acknowledge the fault.
b)
Press the Stop button and pull, or twist and pull, the button out to reset the fault condition
c)
Press the Auto or Manual Run Button, as previously determined.
2.7 CONNECTOR DETAILS 2.7.1 Description TB15 – Tool Connector Arrow at Pin 1
J12 – CT connector Arrow at Pin 1
J12 –Pin 4
J16 – Engine connector arrow at Pin 1
J22 – Voltage connector Arrow at Pin 1
J16 –Pin 7
TB2 – Customer TB Arrow at Pin 1
17
Following are the description for all the terminals on PS0500
2.7.2 Engine Connector The engine connector (J16) is a 12 pin connector-plug (12 MINI M-N-L). The PCB outline drawing shows where the connector is located as above .Each signal is described as below – Connector Pin J16-1 J16-2 J16-3 J16-4 J16-5 J16-6 J16-7 J16-8 J16-9 J16-10 J16-11 J16-12
Signal Name Coolant temperature sensor Battery charging alternator (WL) Starter Relay Driver (Low Side) Fuel shutoff relay Driver (Low Side) BATChassis GND NC NC Oil Pressure Sensor Starter Disconnect Input Sensor Common BAT +
2.7.3 CT Connector The CT connector is a 6- pin MATE-N-LOCK connector. Connector details are as follows – Connector pin J12-1 J12-2 J12-3 J12-4 J12-5 J12-6
Signal CT1_input CT2_input CT3_input CT1_COM CT2_COM CT3_COM
2.7.4 Voltage Connector The voltage connection is via a 4 pin header with alternate spaces between the pins. Connector pin J22-1 J22-2 J22-3 J22-4
Signal Gen_V1 Gen_V2 Gen_V3 Gen_N
18
2.7.5 Customer Connection TB - 2 The customer connection TB2 is a 6 pin terminal block. The terminal pins details are as shown belowTerminal pins TB2-1 TB2-2 TB2-3 TB2-4 TB2-5 TB2-6
Signal Remote start Switch Input Glow Plug Output Relay Driver (Low Side) Customer Output Relay Driver (Low Side) Customer input E-stop NC
Returns for all the above connections are required to be connected externally. All the inputs are active GND. Remote E-Stop switch should have two independent potential free contacts. One NC contact for cutting out the Battery supply to the Fuel Solenoid and another NC contact to connect controller’s E-Stop input to GND to indicate to the control when the E-Stop is pushed in active state.
Battery Positive is not provided on the Customer terminal block (TB2). External provision needs to be made in the harness to provide the B+ signal for convenience of wiring up external relays and may be used as relay supply (high side) for FSO, Starter, Customer Output and Glow plug Relays via a 1 Amp Fuse.
2.7.6 PC Tool Connector The PC tool connector is a dedicated 5 pin connector header block. Terminal pins TB15-1 TB15-2 TB15-3 TB15-4 TB15-5
Signal GND NC RS485_DATA_A RS485_DATA_B TOOL_WAKEUP
19
3. Status Indicators
Display Panel
Genset Running This green LED is lit when the generator set is running at or near rated speed and voltage.
Shutdown This red lamp is lit when the control detects a Shutdown condition. The generator set cannot be started when this lamp is on. After the condition has been corrected, the lamp can be reset by pressing the OFF button. Note:
When Battle Short mode has been enabled and an overridden shutdown fault occurs, the Shutdown lamp will be lit even though the generator set will continue to run.
Warning This yellow lamp is lit whenever the control detects a Warning condition. This lamp is automatically shut OFF when the Warning condition no longer exists.
Remote Start This green lamp indicates the control is receiving a remote run signal.
20
3.1 Fault Code list CTG
CODE
LAMP
DESCRIPTION
C
141
Warning
Indicates the oil pressure sensor output is out of range (OOR), low.
B
143**
Warning
C
144
Warning
C
146**
Warning
D
151**
Shutdown
D
359
Shutdown
A
415**
Shutdown
D
441**
Warning
D
442**
Warning
B
1123*
Shutdown
D
1131*
Warning
E
1312
Configurable
Indicates the engine oil pressure is approaching an unacceptable level. Indicates the coolant temperature sensor output is out of range (OOR), low. Indicates that the engine is operating near cooling system capacity. Increase in load or higher ambient temperature may cause High Coolant Temp (code 151) shutdown. Indicates that the engine coolant temperature is above normal and has reached the Shutdown trip point. The system has failed to start after a set number of crank attempts. This indicates a possible fuel system or air induction problem (engine cranks but fails to start). Indicates the engine oil pressure has dropped below normal and has reached the shutdown trip point. Indicates battery voltage supply to the control is approaching a low level at which unpredictable operation can occur. Indicates battery voltage supply to the control is approaching a high level at which damage to the control can occur. A shutdown fault occurred while the Battle Short mode was enabled. Indicates that the control is in Battle Short mode – used to bypass several fault shutdowns for generator set operation during emergencies. The nature of the fault is an optional customer selection.
B
1416*
Warning
D
1434
Shutdown
D
1435**
Warning
D
1442**
Warning
A
1446**
Shutdown
A
1447**
Shutdown
A
1448**
Shutdown
A
1449**
Shutdown
A
2335
Shutdown
A
2677
Shutdown
Indicates that a shutdown fault is active, but is being bypassed by Battle Short. Indicates a Remote Emergency Stop has been activated. Indicates that the engine coolant temperature is below the adjusted setpoint. This may indicate that the coolant heater is not operating or is not circulating coolant. Indicates that the generator set battery voltage is below battery thresholds during cranking. Indicates that one or more measured AC output voltages have exceeded the threshold for longer than a specified time limit. The threshold and time limits are 130% of nominal for zero seconds or 110% of nominal for ten seconds. Indicates that the measured AC output voltage is below the threshold for longer than a specified time limit. The threshold and time limits are 85% of nominal for ten seconds. Indicates that the alternator frequency is 6 Hertz under the nominal frequency. Indicates that the alternator frequency is 6 Hertz above the nominal frequency. Indicates that a loss of voltage or frequency sensing from the generator has occurred. The generator set continues to run after receiving a stop command from the controller.
21
4. Troubleshooting 4.1 Introduction Fault codes information together with Warning and Shutdown information is provided in this section to assist in locating and identifying the possible causes of faults in the generator set system. Refer also to the Operator’s engine specific manual supplied as part of the generator set documentation pack. This latter manual will contain further information regarding the running and care of the generator set and also specific equipment instructions that may differ from the standard generator set.
4.2 Control Unit The generator set control system continuously monitors engine sensors for abnormal conditions, such as low oil pressure and high coolant temperature. If any of these conditions occur, the control will light a yellow Warning lamp or a red Shutdown lamp and will display a message on the graphical display panel. In the event of an engine shutdown fault (red Shutdown LED), the control will stop the engine immediately. This section lists the Warning and Shutdown Fault Codes/Messages and suggests possible causes of the fault.
4.3 Troubleshooting Procedures for Fault Code 4.2
CODE:
143
LAMP: MESSAGE:
Warning PRE-LOW OIL PRESSURE
CODE:
146
LAMP: MESSAGE:
Warning PRE-HIGH COOL TEMP
CODE:
151
Indicates engine oil pressure has dropped below the warning trip point. If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow the fault code 415 procedure.
Indicates engine is operating near cooling system capacity. Increase in load or higher ambient temperature may cause High Coolant Temp (151) shutdown. Review fault code 151 correction list for other possible causes.
Indicates engine has overheated (coolant temperature has risen above the shutdown trip point). Allow engine to cool down completely before proceeding with the following checks: a) Look for possible coolant leakage points and repair if necessary. Check coolant level and replenish if low b) Check for obstructions to cooling airflow and correct as necessary c) Check fan belt and repair or tighten if necessary
22
LAMP:
Shutdown
d) Check blower fan and circulation pumps on remote radiator installations
MESSAGE:
HIGH COOLANT TEMP
e) Reset control and restart after locating and correcting problem.
CODE:
359
Indicates possible fuel system or air induction problem. (Engine cranks but fails to start). Allow engine to cool down completely before proceeding with the following checks:
LAMP:
Shutdown
f) Check for empty fuel tank, fuel leaks, or blocked fuel lines and correct as required g) Check for dirty fuel filter and replace if necessary h) Check for dirty or blocked air filter and replace if necessary
MESSAGE:
Fail to Start
i) Reset control and restart after correcting the problem.
CODE:
415
Indicates engine oil pressure has dropped below the shutdown trip point. Allow engine to cool down completely before proceeding with the following checks: j) Check the oil level, lines and filters
LAMP:
Shutdown
k) If the oil system is OK but the oil level is low, replenish
MESSAGE:
LOW OIL PRESSURE
l) Reset control and restart after locating and correcting problem.
CODE:
441
Indicates battery voltage supply to the control is approaching a low level at which unpredictable operation will occur. If engine can be stopped allow engine to cool down completely before proceeding: m) Poor battery cable connections. Clean the battery cable terminals and tighten all connections n) Check battery charge voltage float level if applicable (raise float level) o) Discharged or defective battery
LAMP:
Warning
Check the battery charger fuse
MESSAGE:
LOW BAT VOLTAGE
Recharge or replace the battery.
CODE:
442
Indicates battery voltage supply to the control is approaching a high level at which damage to the control can occur. If engine can be stopped allow engine to cool down completely before proceeding:
LAMP:
Warning
p) Poor battery cable connections. Clean the battery cable terminals and tighten all connections
MESSAGE:
HIGH BAT VOLTAGE
q) Check battery charge float level if applicable (lower float level).
CODE:
1131
Indicates that the control is in Battle Short mode – used to bypass several fault shutdowns therefore allowing generator set operation during emergencies.
LAMP:
Warning
23
MESSAGE:
BATTLE SHORT ACTIVE
CODE:
1311, 1312, 1317, 1318
The nature of the fault is an optional customer selection. Example inputs: Low Fuel Day Tank, Water In Fuel, Ground Fault, etc. Each of the fault functions can be programmed (using InPower service tool or access to Setup menu), as follows: r) Event , Warning or Shutdown level if Function Select = Fault Input
LAMP:
Configurable
s) Change display name using up to 32 characters
MESSAGE:
CONFIGURABLE INPUT 1, 2, 3, 4
CODE:
1416
LAMP:
Warning
MESSAGE:
FAIL TO SHUTDOWN
CODE:
1433/1434
The generator set continues to run after receiving a shutdown command from the controller. The Battle Short feature is enabled – this is used to bypass several critical fault shutdowns therefore allowing generator set operation during emergencies.
Indicates local or remote Emergency Stop. Emergency Stop shutdown status can be reset only at the local control panel. After locating and correcting problem, reset the local/remote Emergency Stop button as follows: t) De-activate (disable) emergency stop button u) Press the O (OFF) button v) Select the desired operating mode (manual or remote).
CODE:
1435
Indicates engine coolant heater is not operating or is not circulating coolant. If engine can be stopped allow engine to cool down completely before proceeding with the following checks: w) The coolant heater not connected to power supply. Check for blown fuse or disconnected heater cable and correct as required x) Look for possible coolant leaks and repair as required Check for low coolant level and replenish if required.
LAMP:
Warning
Set is not operating. Warning occurs when engine coolant temperature is 21oC (70oF) or lower.
MESSAGE:
LOW COOLANT TEMP
NOTE: In applications where the ambient temperature falls below 4oC (40oF), Low Coolant Temp may be indicated even though the coolant heaters are operating.
CODE:
1442
Indicates that during cranking, the battery voltage is at, or below, the weak battery warning trip point for a time greater than, or equal to, the weak battery set time.
24
LAMP:
Warning
MESSAGE:
WEAK BATTERY
See code 441 for corrective action
CODE:
1448
Indicates that the generator set frequency has dropped below 90% of nominal for approximately ten seconds. Allow engine to cool down completely before proceeding with the following checks: y) Check the fuel supply z) Check the air intake supply, the load and correct any overload.
4.4 FAULT FINDING Should a fault condition occur during operation follow the procedures in the following tables to locate and correct the problem. For any symptom not listed, contact an authorised service centre for assistance. Before starting any fault finding, ensure that the following basic checks are carried out: •
All switches and controls are in their correct positions
•
The fuel oil level is correct
•
The lubricating oil level is correct
•
The coolant level is correct
•
The radiator matrix is free from obstruction
•
The battery charge condition is satisfactory and the connections are secure
•
The generator set electrics and alternator connections are secure
•
The panel connections are secure
•
The protection circuits have been reset
•
Blown fuses have been replaced
•
Tripped contactors or circuit breakers have been reset
25
5. Inpower Connectivity 1. PS0500 can be connected with inpower using the communication cable (Part no. 0338-4590) and RS485-232 convertor (Part no. 0324-0021). 2. Configure the site of PS0500 in Inpower before moving ahead. 3. Connect one end of the cable to TB15 connector of PS0500 4. Connect the other end of cable to RS 485-232 convertor. 5. Connect the RS232 side of the convertor towards laptop 6. Open Inpower and connect the PS0500 with the created site.
LAPTOP
26
RS 485-232 convertor P/N 03240021
P/N of cable 0338-4590
6. Calibration Procedure NOTE: PS0500 is calibrated from factory. You are not advised to do the calibration for the new part. Only the required CT ratio has to be selected as per the engine model. Please confirm with AO/ZO before performing calibration. 1. Got to Device -> Initial Calibration
27
2. The select calibration window will appear. Select 0326-7727 and click next.
3. History window will appear. The latest calibration should be 1.14 or above. Click NEXT
28
4. Save and Restore parameter window will appear. Click NEXT after this.
5. Click the feature number as A029W892 and click FINISH.
29
6. Window of Calibration will pop up. Click YES to continue calibration.
7. Window of Device Explorer will pop up and click yes for continuing the calibration.
30
8. Progress window will appear. Don’t click anything and allow the calibration to happen.
10. A window of EROOR might pop up. Click OK and continue.
31
11. Once the calibration is completed, the window for successful calibration will pop up. Click OK to finish the calibration.
32
7. Wiring Diagram
33
View more...
Comments