SEC-EOA

380/115kV

Contract No.

SITE TEST REPORT 380kV CURRENT TRANSFORMER

30733178/00

CT Ref

CT.810.B1

Phase

A

Core

Ratio

Date: 28!og/W Sheet #

l 'D1.3

(C1,C2,C3,C4)

1

Sr.No.

2

09921191

4

3

09921194

3000-2500-2000 3000-2500-2000 1500-1250-1 OOOJ 1< 1500-1250-1000 750/1A 750/1A

09921197 3000-2500-2000 ·1500-1250-1000 750/1A

09921200 3000-2500-2000 1500-1250-1000 750/1A

Class

TPS

TPS

TPS

0.2

Type

BSD-675A

BSD-675A

BSD-675A

BSD-705A

Rct

3.10

3.10

3.10

-

-

-

-

50VA

Vkp

3700V

3700V

3700V

-

Imag

75mA

75mA

75mA

CB A810 BF PROTECTION

AL FADHILI L1NE-2 SET-1 PROTN

AL FADHILI L1NE-2 SET-2 PROTN

Burden

Application

SI.No. 1 2 ~-

ABU HADRIY AH BSP

3 4 5 6 7 8

AL FADHILI L1NE-2 METERING

Checks to be performed Criteria of acceptance Inspect for physical damage/defects. No damage Check for Name plate correctness. As per approved drg. Check for Tightness of all bolted connections. Satisfactory Check for correct polarity markings. As per approved drg. Check for all groundings are securely As per approved drg. connected. Check secondary wiring is correctly color 2. Add coded and size of wire is as specified .l1ex b MI' :) S per approve rg Check proper lugs have been used on termination. Check CT location physically and secondary terminal labelinQ has been done correctlv .

Satisfactory

Result OK OK OK OK N/A OK OK

As per approved

drg

OK

BeE1i103 GO

Core 2 - Ground

>103 GO

Core 3 - Ground

>103 GO

Core 4 - Ground

>103 GO

Core to Core: .Applied· Between

TESTED BY: NAME SIGNATURE:

Measured Value

Core 1 - Core 2

>103 GO

Core 1 - Core 3

>103 GO

Core 1 - Core 4

>103 GO

Core 2 - Core 3

>103 GO

Core 2 - Core 4

>103 GO

Core 3 - Core 4

>103 GO

NCC.WITNESSED : V.Sivakumar

NAME

BY: SEC-CSD

REVIEWED BY: TOSHIBA

: Ashraf Farouk

NAME

SIGNATURE:/1

/'/

~

t'/I

: Ben

SIGNATURE:

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952,

SEC·EOA Contract No.

380/115kV

SITE TEST REPORT 380kV CURRENT TRANSFORMER

30733178/00

Tap

CT Ref

CT.810.B1.C1

CT.810.B1.C2

CT.810.B1.C3

CT.810.B1.C4

Ratio

Sheet #

3 01.3

Knee Point Current (mA)

Ratio Error

Polarity

Winding Resistance (Q)

Voltage (V)

(%)

51-55

3000/1A

4.120

6072

17.05

-0.009

51-54

2500/1A

3.519

5055

20.59

-0.013

52-55

2000/1A

2.625

4170

27.36

-0.019

52-54

1500/1A

2.018

3088

35.26

-0.035

53-55

1250/1A

1.576

2553

41.65

-0.048

51-52

1000/1A

1.504

2089

56.30

-0.074

53-54

750/1A

0.972

1542

72.05

-0.122

51-55

3000/1A

4.114

6167

22.64

-0.007

51-54

2500/1A

3.514

5117

26.76

-0.013

52-55

2000/1A

2.613

4072

32.80

-0.020

52-54

1500/1A

2.011

3145

48.63

-0.034

53-55

1250/1A

1.577

2602

56.89

-0.048

51-52

1000/1A

1.505

2053

68.04

-0.075

53-54

750/1A

0.974

1568

97.36

-0.128

51-55

3000/1A

4.113

6695

21.62

-0.010

51-54

2500/1A

3.509

5547

25.21

-0.016

52-55

2000/1A

2.609

4414

31.20

-0.025

52-54

1500/1A

2.005

3286

41.37

-0.044

53-55

1250/1A

1.570

2735

49.03

-0.060

51-52

1000/1A

1.508

2210

60.89

-0.093

53-54

750/1A

0.965

1635

80.32

-0.153

51-55

3000/1A

8.298

149.7

3.40

0.025

51-54

2500/1A

6.777

126.5

4.30

0.031

52-55

2000/1A

5.726

100.6

5.24

0.068

52-54

1500/1A

4.208

76.49

7.43

0.066

53-55

1250/1A

3.680

63.24

8.63

0.077

51-52

1000/1A

2.575

50.34

10.57

-0.101

53-54

750/1A

2.160

37.80

14.31

0.127

*" CT-~:Ce¥ TESTED BY:

Date: 28/0g1UJ

ABU HADRIY AH BSP

T,eg~

le.porl=-

OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK

~. REVIEWED BY: TOSHIBA

NCC

NAME

NAME

SIGNATURE:

SIGNATURE'

: Ashraf Farouk

/"..-l

c /"'

NAME SIGNATURE:

Test Device:

CT-Analyzer

Serial Number: Software Version: Hardware Version: DatelTime: File Name: Status Info:

FF377Z 3.53 (09-09-0116:29) 01/00/07/05/00/11 2010-08-28,10:09:25AM A:\ABU BSP\A810\CT810.B1.C1.PH-A.S1-S5.xml Test successful

SEC-EOA

Company: Country: Station: Feeder: Phase: IEC-ID: Manufacturer: Type:

KSA ABUHADRIYAH-BSP A810 A Toshiba BSD-675A

Serial Number: Core Number: Tap: Optional 1: Primary Current I-pn: Secondary Current I-sn: Applied Standard: Core Type:

09921191 CT 801.B1.C1 S1-S5 3000.00A 1.000A 60044-6 ProtectionCT

Class: TPS Frequency: 60Hz Nominal Burden: 30.000VAcos q>: 1.000 Operating Burden: 30.000VAcos q>: 1.000 Rct: 4.120n Delta compensation: Ratio 1 Class Multiplying Factor: 1.000 Kssc: 178 K: 1.00 Tp: O.OOOOs V-al: 6072V I-al: 0.017056A E1: le1:

3036V 0.009606A

v~·

Parameter Class ...s-t V-aI I-al le1 K*Kssc Rct Ts Kr

Auto Manual OK ? OK ? OK ? OK ? OK ? OK ? OK ? nla ? nla ?

Status Info: Test successful I-DC test: 1.OOOA Results: R-meas.: 3.4550 I-DC: V-DC:

1.064A 3.677V

Temperature Compensation for Copper: T-meas.: 25.0°C T-ref.: 75.0°C R-ref.: 4.1200

Status Info: Test successful Overload: no Used Standard: 60044-6 Results: Knee Points: Standard V 6428V IEC 60044-1 IEC 60044-6 6056V ANSI 30 6267V ANSI 45 4955V Kr:

I 15.51mA 17.01mA 14.78mA 11.13mA

76%

Lm: 1200.0H Ls:

nla

V-al: I-al: E1: le1:

6071.55V 17.06mA 3035.78V 9.61mA

v: ~.

Results with nominal Burden: Burden: 30.000VA cas q>: 1.000 Kssc:

177.94

Ts:

35.175

Results with operating Burden: Burden: 30.000VA cas q>: 1.000 Kssc:

177.94

Ts:

35.175

2000 1000

200 100

If A I

10

Measured Data

L

VCorerms ICTpeak 8206V

11.00A

2.8H

8140V

6.757A

4.5H

8087V

4.151A

7.3H

8033V

2.550A

11.8H

1.566A 7889V 962.0mA

30.8H

7967V

19.1H

7803V 590.9mA 7710V 363.0mA 7602V 223.1mA

127.8H

7466V 137.1mA 7295V 84.21mA

204.3H 325.0H

7091V 51.69mA

514.6H

6831V 31.79mA

806.1 H

49.5H 79.7H

6703V 26.64mA 944.0H 6546V 22.42mA 1095.2H 6344V 19.09mA 1246.2H 6070V 17.05mA 1335.8H 5690V 16.13mA 1323.6H 5178V 14.91mA 1303.0H 4507V 13.31mA 1270.5H 3672V 11.25mA 1223.9H 2820V 9.034mA 1171.0H 2061V 6.930mA 1115.7H 1535V 5.392mA 1067.7H 1184V 4.324mA 1027.1 H 935.1V 3.538mA 991.6H 739.2V 2.896mA 957.4H 577.0V 2.357mA 441.2V 1.893mA 330.8V 240.7V 171.2V 125.4V

918.3H 874.5H

1.512mA

821.0H

1.179mA

765.8H 704.7H

911.3~A

720.2~A 102.8V 619.9~A 84.51V 534.7~ 68.78V 457.8~A

653.2H 622.2H

56.95V 397.1~A 45.70V 339.2~A

538.0H 505.4H

38.06V 297.7~ 36.91V 212.8~A 20.31V 163.1~A

479.7H

11.18V 115.3~A 6.153V 97.3~A 3.387V 88.3~ 81.6~A 1.864V

369.4H

aboutblank

592.9H 563.6H

650.6H 467.0H 232.6H 136.4H 82.0H

V. ~.

II

1.ooovl 71.6J.1A1 49.0HII

aboutblank

\f. ~

...

Error:

10%

K-Value at nominal Burden:

155.0756

K-Value at operating Burden: 155.0756

o

ZlOhm

o

1000

K-Value Impedance

50.0000 45.0000 40.0000 35.0000 30.0000 25.0000 20.0000 15.0000 12.0000 10.0000 9.0000 8.0000 7.0000 6.0000 5.0000 4.0000 3.0000 2.0000 1.0000

158.69140 176.75780 198.73050 227.53910 265.62500 318.35940 397.94920 529.29690 660.15630 791.01560 876.95310 984.37500 1000.00000 1000.00000 1000.00000 1000.00000 1000.00000 1000.00000 1000.00000

v.~·

Results with operating Burden: Used Burden: Used I-p: Ratio: Deviation: &-c: N: &-t: Phase: Polarity:

Burden

30.000VA cos q>:1.000 3000.00A 3000.0: 0.9999 -0.009% 0.012% 2999.89 -0.004% 0.27min OK

Current ratio error in % at % of rated current

VAl cos q> 1.0 5.0 10 20 50 100 120 200 30.00 / 1.000 -0.012 -0.038 -0.028 -0.019 -0.012 -0.009 ! -0.007 ! -0.005 15.00 / 1.000 -0.001 -0.021 -0.019 -0.013 -0.007 -0.005 -0.004 ! -0.002 7.50/1.000 0.000 -0.004 -0.012 -0.009 -0.005 -0.003 -0.002 -0.001 3.75/1.000 0.002 0.000 -0.005 -0.006 -0.003 -0.001 -0.001 0.000 Burden

Phase displacement in minutes at % of rated current

VAl cos q> 1.0 5.0 10 20 50 100 120 200 30.00 / 1.000 10.37 3.69 1.89 0.97 0.44 0.27 ! 0.51 ! 0.44 15.00 / 1.000 6.18 3.38 1.87 0.95 0.40 0.23 0.20 ! 0.29 7.50/1.000 3.94 3.05 1.75 0.94 0.38 0.20 0.18 0.12 3.75/1.000 2.80 2.31 1.63 0.91 0.38 0.20 0.17 0.11 NOTE: Measurements with 'I' have reduced accuracy. Accuracy only guaranteed on non gapped cores.

v. __

.

Test Device: Serial Number: Software Version: Hardware Version: DateITlme: File Name: Status Info:

CT-Analyzer FF377Z 3.53 (09-09-0116:29) 01/00/07/05/00/11 2010-08-28,10:13:24AM A:\ABU BSP\A810\CT810.B1.C1.PH-A.S1-S4.xml Test successful

Company: Country: Station: Feeder: Phase: IEC-ID: Manufacturer: Type: Serial Number: Core Number: Tap: Optional 1: Primary Current I-pn: Secondary Current I-sn: Applied Standard: Core Type: Class: Frequency: Nominal Burden: Operating Burden: Rct: Delta compensation:

SEC-EOA KSA

ABUHADRIYAH-BSP A810 A

Toshiba BSD-675A 09921191 CT 801.B1.C1 S1-S4 2500.00A 1.000A 60044-6 ProtectionCT TPS 60Hz 30.000VAcos 30.00 / 1.000 15.00 / 1.000 7.50/1.000 3.75/1.000

Phase displacement

50 100 120 200

1.0 5.0 10 20

31.70 8.11 4.38 2.68 1.62 1.24 ! 1.68 ! 1.51 20.57 7.52 4.07 2.23 1.20 0.84 0.77 ! 0.68 12.46 6.77 3.84 2.06 0.98 0.63 0.57 0.44 7.97 6.03 3.48 1.97 0.87 0.51

NOTE: Measurements cores.

aboutblank

in minutes at % of rated current

0.46

0.34

with '!' have reduced accuracy. Accuracy only guaranteed on non gapped

V, ~

.

Test Device: Serial Number: Software Version: Hardware Version: DatelTime: File Name: Status Info:

CT-Analyzer FF377Z 3.53 (09-09-0116:29) 01/00/07/05/00/11 2010-08-28,10:22:51AM A:\ABU BSP\A810\CT810.B1.C1.PH-A.S3-S5.xml Test successful

Company: Country: Station: Feeder: Phase: IEC-ID: Manufacturer: Type: Serial Number: Core Number: Tap: Optional 1: Primary Current I-pn: Secondary Current I-sn: Applied Standard: Core Type: Class: Frequency: Nominal Burden: Operating Burden: Rct: Delta compensation: Class MUltiplying Factor: Kssc: K: Tp: V-al: I-al: E1: le1:

SEC-EOA KSA

ABUHADRIYAH-BSP A810 A Toshiba BSD-675A 09921191 CT 801.B1.C1 S3-S5 1250.00A 1.000A 60044-6 ProtectionCT TPS 60Hz 30.000VAcos cp: 1.000 30.000VAcos cp: 1.000 1.5760 Ratio 1 1.000 80.9 1.00 O.OOOOs 2553V 0.041656A 1277V 0.023000A

Parameter Class ...g-t V-al I-al le1 K*Kssc Rct Ts Kr

Auto Manual OK ? ? OK ? OK ? OK OK ? ? OK ? OK n/a ? n/a ?

Status Info: Test successful I-DC test:

1.000A

Results: R-meas.: 1.322.0 I-DC: V-DC:

1.069A 1.412V

Temperature Compensation for Copper: T-meas.: 25.0°C T-ref.: 75.0°C R-ref.: 1.576.0

Status Info: Test successful Overload: no Used Standard: 60044-6 Results: Knee Points: Standard V I IEC 60044·1 2673V 37.03mA IEC 60044-6 2516V 40.84mA ANSI 30 2599V 35.12mA ANSI 45 2061V 26.44mA Kr: 79% Lm: 208.4H Ls: 18.6mH V-al: 2553.49V I-al: 41.66mA

about:blank

V ~.

E1:

1276.74V

le1: 23.00mA Results with nominal Burden: Burden: 30.000VA cos Kssc:

80.87

Ts:

6.599s

lj):

1.000

Results with operating Burden: Burden: 30.000VA cos Kssc:

80.87

Ts:

6.599s

lj):

2000 1000

\f~.

1.000

Measured Data VCorerms ICTpeak

L

3376V

13.00A 974.3mH

3359V

8.349A

1.5H

3338V 3312V

5.362A 3.444A

2.3H 3.6H

3283V

2.212A

5.6H

3251V

1.421A

8.6H

3216V 912.4mA 3176V 586.0mA 3127V 376.4mA

20.3H

3066V 241.8mA 2993V 155.4mA

13.2H 31.2H 47.6H 72.3H

2906V 99.35mA 2785V 64.04mA 2724V 54.94mA 2650V 47.48mA

186.0H 209.4H

2553V 41.65mA

230.0H

109.7H 163.1 H

2428V 38.98mA

233.6H

2263V 36.75mA

231.0H

2051V 33.90mA 1787V 30.31mA

221.1 H

227.0H

1466V 25.78mA

213.3H

1051V 19.58mA 733.7V 14.54mA

201.3H

532.6V 11.15mA

179.2H

398.3V 8.766mA

170.5H

189.3H

298.0V 6.891mA

162.2H

218.6V 5.360mA

153.0H

156.0V 4.095mA 117.4V 3.265mA 93.44V 2.723mA

134.9H 128.7H

142.9H

74.58V 2.276mA 59.44V 1.903mA

122.9H

47.33V 1.590mA

111.6H

117.2H

37.91V 1.343mA

105.9H 37.58V 1.127mA 125.1H 20.65V 728.5J.LA 106.3H 11.35V 482.4I!A 88.2H 351.2J.LA 6.234V 66.6H 3.424V 277.6I!A 46.3H 1.881V 239.31!A 1.000V 214.5J.LA

aboutblank

29.5H 17.4H

V~·

Error:

10%

K-Value at nominal Burden:

107.2045

K-Value at operating Burden: 107.2045

o

ZlOhm I

o

1000

K-Value Impedance

50.0000 45.0000 40.0000 35.0000 30.0000 25.0000 20.0000 15.0000 12.0000 10.0000 9.0000 8.0000 7.0000 6.0000 5.0000 4.0000 3.0000 2.0000 1.0000

65.42970 72.75390 81.90920 93.62790 109.13090 130.85940 163.33010 217.04100 270.50780 323.24220 358.39850 402.34380 458.98440 533.20310 636.71880 791.01560 1000.00000 1000.00000 1000.00000

about blank

\I.~.

Results with operating Burden: Used Burden: 30.000VA cos q>: 1.000

Phase:

1250.00A 1250.0 : 0.9995 -0.048% 0.068% 1249.97 -0.002% 1.66min

Polarity:

OK

Used I-p: Ratio: Deviation: E-C:

N: E-t:

Burden

VAl cos q> 30.00 /1.000 15.00 /1.000 7.50/1.000 3.75/1.000 Burden

VAl cos q> 30.00 /1.000 15.00 /1.000 7.50/1.000 3.75/1.000

about:blank

Current ratio error in % at % of rated current

1.0

5.0

10

20

50

-0.226 -0.036 -0.017 -0.008

-0.151 -0.105 -0.064 -0.028

-0.106 -0.076 -0.055 -0.037

-0.078 -0.053 -0.039 -0.029

-0.057 -0.036 -0.024 -0.017

Phase displacement

9.88 9.14 8.25 7.10

V~

5.54 4.96 4.62 4.28

3.42 2.79 2.50 2.36

120

200

-0.048 ! -0.042 ! -0.038 -0.028 -0.027 -0.024 -0.018 -0.017 -0.014 -0.012 -0.011 -0.009

in minutes at % of rated current

1.0 5.0 10 20 37.72 28.90 16.87 10.46

100

50 100 120 200 2.15 1.55 1.23 1.08

.

1.66 1.10 0.81 0.65

! 2.22 1.02 0.73 0.57

! 2.07 0.86 0.58 0.43

Test Device: Serial Number: Software Version: Hardware Version: DateITime: File Name:

CT-Analyzer FF377Z 3.53 (09-09-0116:29) 01/00/07/05/00/11 2010-08-28,10:25:11AM A:\ABU BSP\A810\CT810.B1.C1.PH-A.S1-S2.xml

Status Info:

Test successful

SEC-EOA Company: KSA Country: ABUHADRIYAH-BSP Station: A810 Feeder: A Phase: IEC-ID: Toshiba Manufacturer: BSD-675A Type: 09921191 Serial Number: CT 801.B1.C1 Core Number: S1-S2 Tap: Optional 1: Primary Current I-pn: 1000.00A Secondary Current I-sn: 1.000A Applied Standard: 60044-6 Core Type: ProtectionCT Class: TPS Frequency: 60Hz Nominal Burden: 30.000VAcos q>: 1.000 Operating Burden: 30.000VAcos q>: 1.000 Rct: 1.5040 Delta compensation: Ratio 1 Class Multiplying Factor: 1.000 Kssc: 66.3 K: 1.00 Tp: O.OOOOs V-al: 2089V I-al: 0.056300A E1: 1044V le1: 0.028985A

v.~·

Parameter Auto Manual Class

OK

...E-t

OK

V-a I

OK

I-al

OK

le1

OK

K*Kssc

OK

Rct

OK

Ts

n/a

Kr

n/a

? ? ? ? ? ? ? ? ?

Status Info: Test successful I-DC test:

1.000A

Results: R-meas.: 1.2610 I-DC:

1.068A

V-DC:

1.347V

Temperature

Compensation

for Copper:

T-meas.: 25.0°C T-ref.:

75.0°C

R-ref.:

1.5040

Status Info:

Test successful

Overload:

no

Used Standard: 60044-6 Results: Knee Points:

V

Standard

I

IEC 60044-1 2137V 45.88mA IEC 60044-6 2005V 49.93mA ANSI 30 2074V 43.32mA ANSI 45 Kr:

1640V 32.54mA

79%

Lm: 136.0H Ls:

23.3mH

V-al: 2088.55V I-al: 56.30mA

E1:

1044.27V

le1: 28.98mA Results with nominal Burden: Burden: 30.000VA co5 : 1.000 0.97270 Ratio 1 1.000 40.0 1.00 O.OOOOs 1542V 0.072058A 771.2V 0.038292A

Parameter Class ...E-t V-aI I-al le1 K*Kssc Rct Ts Kr

Auto Manual OK ? OK ? OK ? ? OK OK ? OK ? OK ? n/a ? n/a ?

Status Info: Test successful I-DC test: 1.000A Results: R-meas.: 815.6mQ I-DC: V-DC:

1.068A 0.871V

Temperature Compensation for Copper: T-meas.: 25.0°C T-ref.: 75.0°C R-ref.: 972.7mQ

Status Info: Test successful Overload: no Used Standard: 60044-6 Results: Knee Points: Standard IEC 60044-1 IEC 60044-6 ANSI 30 ANSI 45

V I 1607V 61.87mA 1499V 67.19mA 1553V 57.83mA 1219V 43.13mA

Kr:

81%

Lm: Ls: V-al: I-al:

75.2H 17.1mH 1542.32V 72.06mA

v:~.

E1:

771.16V

le1: 38.29mA Results with nominal Burden: Burden: 30.000VA Kssc:

49.80

Ts:

2.429s

CDS

q>: 1.000

Results with operating Burden: Burden: 30.000VA Kssc:

49.80

Ts:

2.429s

CDS

q>: 1.000

VN 2000

\f.~.

Measured Data VCorerms ICTpeak

L

2010V

11.00A 685.4mH

1997V

7.396A

1982V

4.973A

1.5H

1966V

3.344A

2.2H

1948V

2.248A 1.512A

4.8H

1929V

1.0H

3.3H

1908V 1.016A 1882V 683.5mA 1851V 459.6mA

7.0H 10.3H

1813V 309.1mA 1769V 208.0mA

22.0H

1714V 140.0mA 1634V 93.42mA

45.9H

1593V 81.67mA 1542V 72.05mA

73.2H

1478V 64.97mA 1397V 61.94mA 1295V 58.16mA

15.1H 31.9H 65.6H 80.3H 85.4H 84.6H

1168V 53.48mA

83.5H 81.9H

1013V 47.71mA

79.6H

738.9V 36.99mA 488.2V 26.45mA

74.9H

331.7V 19.35mA 233.2V 14.53mA

64.3H 60.2H

163.9V 10.90mA 119.4V 8.421mA

56.4H

93.57V 6.904mA 73.29V 5.659mA 57.22V 4.627mA 44.59V 3.785mA

69.2H

53.2H 50.8H 48.6H 46.4H 44.2H

36.98V 2.897mA

47.9H

20.35V 1.828mA

41.8H

11.20V 1.178mA 6.163V 800.11lA 3.390V 579.51lA 1.865V 462.5/lA 1.000V 399.61lA

35.7H 28.9H 21.9H 15.1H 9.4H

v~.

Error:

10%

64.6366 K-Value at operating Burden: 64.6366

K-Value at nominal Burden:

o

ZlOhm I

o

1000

K-Value Impedance

50.0000 45.0000 40.0000 35.0000 30.0000 25.0000 20.0000 15.0000 12.0000 10.0000 9.0000 8.0000 7.0000 6.0000 5.0000 4.0000 3.0000 2.0000 1.0000

38.94040 43.27390 48.70610 55.66410 64.81930 77.75880 96.92380 128.66210 160.15630 191.40630 212.40240 238.28130 271.48440 314.94140 375.97660 465.82030 613.28130 900.39060 1000.00000

v,~·

Results with operating Burden: Used Burden: Used I-p: Ratio: Deviation: e-C: N: e-t: Phase: Polarity:

Burden VAl cos
View more...