Page: 2 The Main Protection is a distance protection scheme using a D60 UR relay. The D30 consists of five phase and ground distance zones of protection (either mho or quadrilateral characteristics). In addition to the Main protection, the D30 also provides Powerswing Blocking, Directional Earth fault protection, Overvoltage protection, Fault Recording and VT supervision. Local End
Remote End End A CT
End B CT
F1
UR Relay - D60
CT Ratio: Ratio Used: VT Prim Voltage: VT Sec Voltage: VT Ratio: Relay Rating: Element Used: Ranges available
150/1 150 132 110 1200 1.0
/1 (kV) (V) :1
F5
F1
F5
FP2
FP1
Phase to Phase voltage Phase to Phase voltage
Amp(s)
DISTANCE Min - All Zones Reach - Max 0.02 500.00 Min - Relay Char Ang - Max 30 90
Step Size 0.01
Setting Criteria: Distance protection shall be set as follows: Zone 1 i) Reach at the line angle of 80% of the protected line (ii) Time delay - 0 seconds Zone 2 i) Reach at the line angle of 120% of the protected line ii) Time delay of 0.5 seconds. Zone 3 i) Reach at the line angle of 170% of the protected line ii) Time delay of 1.0 seconds.
1
values shown in secondary ohms values shown in Degrees
Page: 3 ZONE 1: Phase Settings: The relay characteristic angle should be set to match the characteristic angle of the protected line: +ve sequence RCA = 67 Degrees Setting = PHASE DISTANCE Z1 RCA zero sequence RCA = 67 Degrees Setting = GROUND DISTANCE Z1 RCA Direction of Zone = Forward Setting = PHASE DISTANCE Z1 Direction Shape of zone = Mho Setting = PHASE DISTANCE Z1 Shape Required zone 1 reach = Time Delay on zone 1 =
0.0188 0.000
Ω sec seconds
= 0.8 * Z Setting = PHASE DISTANCE Z1 Delay
The Phase Distance Z1 Comp Limit setting can be used to shape the operating characteristic of the zone: Comp Limit = 90 Degrees Setting = PHASE DISTANCE Z1 Comp Limit The directional supervising function RCA and Comp Limit should be to the same as the distance element settings: 67 Degrees Setting = PHASE DISTANCE Z1 DIR RCA 90 Degrees Setting = PHASE DISTANCE Z1 DIR Comp Limit
The supervision function provides current supervision of the distance elements to avoid maloperation under fuse fail conditions. It is set above load if possible, but below 95% of the current for a fault at the limit of Zone 1. If the Fuse Fail function is arranged to block the distance function, then the setting shall be at minimum. Min Fault at 132 = 13.1 MVA = 763.624 Zone 1 Reach = 0.0188 Fault at limit of zone 1 = 763.643 = 57 A = 0.382 pu
Choose setting in range: 0 < Supervision < 0.382 Choose = 0.050 pu Ground Settings: Direction of Zone = Shape of zone = Z0/Z1 Magnitude = Z0/Z1 Angle = Ground distance reach = Comp Limit = Directional RCA = Directional RCA Comp Limit = Blinder = Reach *( Tan(RCA) 1/Sq.rt(3))/Tan(RCA
Setting = PHASE DISTANCE Z1 Supervision
Forward Setting = GROUND DISTANCE Z1 Direction Quad Setting = GROUND DISTANCE Z1 Shape 3.99 Setting = GROUND DISTANCE Z1 Z0/Z1 Mag 9 Degrees Setting = GROUND DISTANCE Z1 Z0/Z1 Ang 0.02 Ω sec Setting = GROUND DISTANCE Z1 Reach 90 Degrees Setting = GROUND DISTANCE Z1 Comp Limit 67 Degrees Setting = GROUND DISTANCE Z1 DIR RCA 90 Degrees Setting = GROUND DISTANCE Z1 DIR Comp Limit 0.01 Ω sec Setting = GROUND DISTANCE Z1 Quad Right Bld 67 Degrees Setting = GROUND DISTANCE Z1 Quad Right Bld RCA 0.01 Ω sec Setting = GROUND DISTANCE Z1 Quad Left Bld 67 Degrees Setting = GROUND DISTANCE Z1 Quad Left Bld RCA 0.050 pu Setting = GROUND DISTANCE Z1 Supervision Time Delay on zone 1 = 0.000 seconds Setting = GROUND DISTANCE Z1 Delay Note: Z0/Z1 Magnitude and Angle are used for zero sequence compensation of the ground fault element
ZONE 2:
Page: 4
Phase Settings: The relay characteristic angle should be set to match the characteristic angle of the protected line: +ve sequence RCA = 67 Degrees Setting = PHASE DISTANCE Z2 RCA zero sequence RCA = 67 Degrees Setting = GROUND DISTANCE Z2 RCA Direction of Zone = Forward Setting = PHASE DISTANCE Z2 Direction Shape of zone = Mho Setting = PHASE DISTANCE Z2 Shape Required zone 2 reach = Time Delay on zone 2 =
0.0283 0.500
Ω sec seconds
= 1.2 * Z Setting = PHASE DISTANCE Z2 Delay
The Phase Distance Z2 Comp Limit setting can be used to shape the operating characteristic of the zone: Comp Limit = 90 Degrees Setting = PHASE DISTANCE Z2 Comp Limit The directional supervising function RCA and Comp Limit should be to the same as the distance element settings: 67 Degrees Setting = PHASE DISTANCE Z2 DIR RCA 90 Degrees Setting = PHASE DISTANCE Z2 DIR Comp Limit
The supervision function provides current supervision of the distance elements to avoid maloperation under fuse fail conditions. It is set above load if possible, but below 95% of the current for a fault at the limit of Zone 1. If the Fuse Fail function is arranged to block the distance function, then the setting shall be at minimum. Min Fault 13.1 MVA = 0.399 Zone 1 Reach = 3.7052 Fault at limit of zone 1 = 4.104 = 3517 A = 3.517 pu
Choose setting in range: 0 < Supervision < 3.517 Choose = 0.050 pu Ground Settings: Direction of Zone = Shape of zone = Z0/Z1 Magnitude = Z0/Z1 Angle = Ground distance reach = Comp Limit = Directional RCA = Directional RCA Comp Limit =
Setting = PHASE DISTANCE Z2 Supervision
Forward Setting = GROUND DISTANCE Z2 Direction Quad Setting = GROUND DISTANCE Z2 Shape 3.99 Setting = GROUND DISTANCE Z2 Z0/Z2 Mag 9 Degrees Setting = GROUND DISTANCE Z2 Z0/Z2 Ang 0.03 Ω sec Setting = GROUND DISTANCE Z2 Reach 90 Degrees Setting = GROUND DISTANCE Z2 Comp Limit 67 Degrees Setting = GROUND DISTANCE Z2 DIR RCA 90 Degrees Setting = GROUND DISTANCE Z2 DIR Comp Limit 0.01 Ω sec Setting = GROUND DISTANCE Z2 Quad Right Bld 67 Degrees Setting = GROUND DISTANCE Z2 Quad Right Bld RCA 0.01 Ω sec Setting = GROUND DISTANCE Z2 Quad Left Bld 67 Degrees Setting = GROUND DISTANCE Z2 Quad Left Bld RCA 0.050 pu Setting = GROUND DISTANCE Z2 Supervision Time Delay on zone 2 = 0.500 seconds Setting = GROUND DISTANCE Z2 Delay Note: Z0/Z1 Magnitude and Angle are used for zero sequence compensation of the ground fault element
ZONE 3:
Page: 5
Phase Settings: The relay characteristic angle should be set to match the characteristic angle of the protected line: +ve sequence RCA = 67 Degrees Setting = PHASE DISTANCE Z3 RCA zero sequence RCA = 67 Degrees Setting = GROUND DISTANCE Z3 RCA Direction of Zone = Forward Setting = PHASE DISTANCE Z3 Direction Shape of zone = Mho Setting = PHASE DISTANCE Z3 Shape Required zone 3 reach = 0.0400 Time Delay on zone 3 = 1.000
Ω sec seconds
= 1.7 * Z Setting = PHASE DISTANCE Z3 Delay
The Phase Distance Z3 Comp Limit setting can be used to shape the operating characteristic of the zone: Comp Limit = 90 Degrees Setting = PHASE DISTANCE Z3 Comp Limit The directional supervising function RCA and Comp Limit should be to the same as the distance element settings: 67 Degrees Setting = PHASE DISTANCE Z3 DIR RCA 90 Degrees Setting = PHASE DISTANCE Z3 DIR Comp Limit The load blinder shall be set with the same RCA as above and the maximum allowable resistive reach: The supervision function provides current supervision of the distance elements to avoid maloperation under fuse fail conditions. It is set above load if possible, but below 95% of the current for a fault at the limit of Zone 1. If the Fuse Fail function is arranged to block the distance function, then the setting shall be at minimum. Min Fault at 13.1 MVA = 0.399 Zone 1 Reach = 3.7052 Fault at limit of zone 1 = 4.104 = 3517 A = 23.440 pu
Choose setting in range: 0 < Supervision < 23.44 Choose = 0.050 pu Ground Settings: Direction of Zone = Shape of zone = Z0/Z1 Magnitude = Z0/Z1 Angle = Ground distance reach = Comp Limit = Directional RCA = Directional RCA Comp Limit = Blinder = sqrt(3)*Reach *( Tan(RCA) -
Setting = PHASE DISTANCE Z3 Supervision
Forward Setting = GROUND DISTANCE Z3 Direction Quad Setting = GROUND DISTANCE Z3 Shape 3.99 Setting = GROUND DISTANCE Z3 Z0/Z1 Mag 9.0000 Degrees Setting = GROUND DISTANCE Z3 Z0/Z1 Ang 0.04 Ω sec Setting = GROUND DISTANCE Z3 Reach 90 Degrees Setting = GROUND DISTANCE Z3 Comp Limit 67 Degrees Setting = GROUND DISTANCE Z3 DIR RCA 90 Degrees Setting = GROUND DISTANCE Z3 DIR Comp Limit 0.02 Ω sec Setting = GROUND DISTANCE Z3 Quad Right Bld 67 Degrees Setting = GROUND DISTANCE Z3 Quad Right Bld RCA 0.00 Ω sec Setting = GROUND DISTANCE Z3 Quad Left Bld 67 Degrees Setting = GROUND DISTANCE Z3 Quad Left Bld RCA 0.050 pu Setting = GROUND DISTANCE Z3 Supervision Time Delay on zone 3 = 1.000 seconds Setting = GROUND DISTANCE Z3 Delay Note: Z0/Z1 Magnitude and Angle are used for zero sequence compensation of the ground fault element
Power Swing Blocking: The Power Swing Blocking function is required, therefore apply the following settings: Is Power Swing Block Required:
Blinder = Reach *( Tan(RCA) 1/Sq.rt(3))/Tan(RCA)
Yes Enabled Quad Two step 0.05 0.04 0.04 87 0.01 0.01 0.04 0.008 0.03 0.006 0.1 0.05 ON
Switch On To Fault Min Fault at 132 = Z fault = 3Io fault = Required current setting = = =
9.2 3272.817 207.5 159.6 1.064 1.064
MVA %
Undervoltage setting = LEO Pickup Delay = SOTF time = = High Speed AR Bypass =
0.850 0.000 0.200 0.200 Enabled
pu s s s
A prim pu pu
Less infeed from 0.45 = (3 * Z1s) + (2 * Z1ohl) + (Z0ohl) = 3 * Io
Setting = Phase IOC Line Pickup Setting = UV Pickup Setting = Line End Open Pickup Delay Setting = Line End Open Reset Delay Setting = OV Pickup Delay Setting = Autoreclose Coordination Bypass
Directional Earth Fault Element Used: Range available RCA
NEUTRAL EARTHFAULT DIR. OVERCURRENT I Pickup Min I Pickup Max Step Size 0.000 30.000 0.001 values shown pu (of Relay Rating) -90 Deg 90 Deg 1 Deg
Required current setting = = RCA
437.386 2.916 -15
A prim pu Degrees
MVA/(Sqrt(3) X KV)
VT Fuse Failure function:
Page: 7
This is designed to detect the loss of either 1, 2 or all 3 phase voltages. To detect the loss of 1 or 2 phases, the relay looks for a significant level of -ve sequence voltage, to detect loss of 3 phases, the relay looks for +ve sequence current and insignificant +ve sequence voltage. The fuse fail alarm is inhibited for a fault condition. As the settings for the voltage/current pickups are inbuilt to the relay, the only selectable setting for this function is to enable or disable it. Function Enabled Setting = VT Fuse Failure Function The associated time delay is set using TIMER 9 VT Fail Alarm Timer = 3
seconds
Setting = TIMER 9 Pickup Delay
The VT fuse fail can be used to block the operation of the Main Protection: Is VT Fuse Fail to block MP: Yes Normal setting is "Yes" Enabled (Block ON) Setting = LATCH 3 Function Phase Overvoltage Element Used
Flexi element 1,2 & 3 Enabled Enabled FxE 1 FxE 2 Vag RMS Vbg RMS SIGNED SIGNED LEVEL LEVEL OVER OVER 1.150 pu 1.150 pu 3.00% 3.00%
Element Used: PHASE OV1 Measured Quantity = Phase to Ground Required Under volts setting = 1.200 pu Characteristic = Definite Time Time Delay = 0.00 Minimum voltage = 0.300
Stage1 for Alarm Enabled FxE 3 Vcg RMS SIGNED LEVEL OVER 1.150 pu 3.00%
Thank you for interesting in our services. We are a non-profit group that run this website to share documents. We need your help to maintenance this website.