Cooling Load calculations
Short Description
Cooling Load calculations for a enclosed space...
Description
Cooling Load
Contents • • • • •
Principle of cooling load Why cooling load & heat gains are different Design conditions Understand CLTD/CLF method An example
Cooling Load • It is the thermal energy that must be removed from the space in order to maintain the desired comfort conditions • HVAC systems are used to maintain thermal conditions in comfort range
Purpose of Load Estimate • • • •
Load profile over a day Peak load (basis for equipment sizing) Operation Energy analysis HVAC Construction cost
Principles of cooling Load Estimate • Enclosure heat transfer characteristics – Conduction – Convection – radiation
• Design conditions – Outdoor & indoor
• Heat Gains – Internal – External or Solar
• Thermal capacity
Space Characteristics • • • • • •
orientation Size and shape Construction material Windows, doors, openings Surrounding conditions Ceiling
Space Characteristics • • • •
Occupants (activity, number, duration) Appliances (power, usage) Air leakage (infiltration or exfiltration) Lighting (W/m2)
Indoor Design Conditions Basic design parameters • Air temperature – Typically 22-26 C
• Air velocity – 0.25 m/s
• Relative humidity – 30-70 %
• See ASHRAE 55 – 2004 Comfort Zone
Indoor Design Conditions • Indoor air quality – Air contaminants – Air cleaning
• Acoustic requirements • Pressurization requirements
Outdoor Design Conditions • Weather data required for load calculation – Temperature & humidity – Wind speed, sky clearness , ground reflectance etc
• Design outdoor conditions data can be found in ASHRAE Fundamentals Handbook
Outdoor Design Conditions • ASHRAE Fundamentals 2001 – Design severity based on 0.4%, 1%, & 2% level annually (8760h) – For example at 1% level, the value is exceeded in 0.01x8760h = 87.6 h in a year
Outdoor Design For Cooling Criteria: 0.4% DB and MWB Station
Cooling DB/MWB
Miri Malaysia
0.4%
1%
2%
DB (˚C ) MWB ( ˚C )
DB
MWB
DB
MWB
32.2
31.8
26.3
31.4
26.2
26.3
Source: ASHRAE Fundamentals 2001
Terminology • Space- a volume without partition or a group of rooms
• Room- an enclosed space • Zone- a space having similar operating characteristics
Heat Gain • Space Heat gain – The instantaneous rate at which heat enters into , out of, or generated within a space. The components are: Heat gains Convective Radiant (%) • Sensible gain • Latent gain
(%) Solar radiation with internal shading
42
58
Fluorescent lights
50
50
People
67
33
External wall
40
60
Heat Gain
Cooling Load • Space Cooling load – The rate at which heat must be removed from a space to maintain air temperature and humidity at the design values
• Cooling load differs from the heat gain due to – delay effect of conversion of radiation energy to heat – Thermal storage lag
Heat Gain = Cooling Load
Heat Gain = Cooling Load Thermal storage and Construction Type
Time of the Day: Solar Radiation
Time-delay Effect: Lighting
Extraction Rate • Space Heat extraction rate – The actual heat removal rate by the cooling equipment from the space – The heat extraction rate is equal to cooling load when the space conditions are constant which is rarely true.
Heat Balance The principal terms of heat Gains/Losses are indicated below .
(Source: ASHRAE Handbook Fundamentals 2005)
Coil Load • Cooling coil load – The rate at which energy is removed at the cooling coil – Sum of: • • • •
Space cooling load (sensible + latent) Supply system heat gain (fan + supply air duct) Return system heat gain (return air duct) Load due to outdoor ventilation rates (or ventilation load)
External Loads 1. Heat gains from Walls and roofs – sensible
2. Solar gains through fenestrations – Sensible
3. Outdoor air – Sensible & latent
Internal Loads 1. People – Sensible & latent
2. Lights – sensible
3. Appliances – Sensible & latent
Total Cooling Load
Cooling Load Components • Space cooling load – Sizing of supply air flow rate, ducts, terminals and diffusers – It is a component of coil load – Bypassed infiltration is a space cooling load
• Cooling coil load – Sizing of cooling coil and refrigeration system – Ventilation load is a coil load
Refrigeration Load • The capacity of the refrigeration system to produce the required coil load.
Profiles of Offshore Systems Cooling Loads Components
% Load LQ (L)
%Load LQ (U)
%Load CCR
%Load SG/MCC
Solar Transmission
3
4
7
4
Occupants
3
3
3
0
Lights
5
5
8
4
Equipment
10
1
29
21
Outdoor air bypassed 7
8
5
6
Outdoor air not bypassed
72
79
48
64
Total
100
100
100
100
Heat Load Components
Outdoor air & Electrical Equipment loads (77-85% ) People: 3% Lighting: 4-8% Solar Transmission: 3-7% Infiltration : 5-8%
Calculation Methods 1. Rule of thumb method – Least accurate – eg 100 btu/ft2 for a space
2. Static analysis (Room temperature is constant) – CLTD/CLF method
3. Dynamic analysis – Computer modeling
CLTD/CLF Method • Cooling load is made up of – Radiation and conduction heat gain – Convection heat gain
• Convective gain is instantaneous – No delay – Heat gain equals cooling load
• Conductive and radiation heat gains are not instantaneous – Thermal delay – Heat gain is not equal to cooling load – Use CLTD & CLF factors
CLTD/CLF Method (ASHRAE 1989) Cooling load due to solar & internal heat gains • Glazing (sensible only) – Radiation & conduction – Convection (instantaneous)
• Opaque surface ( wall, floor, roof) load (sensible only) – Conduction – Convection (instantaneous)
• Internal loads (sensible & latent) – Radiation & conduction – Convection (instantaneous)
Cooling Load Temperature Difference CLTD Compare Q transmission = UA (T o – T i ) Q transmission = UA (CLTD) • CLTD is theoretical temperature difference defined for each wall/roof to give the same heat load for exposed surfaces to account for the combined effects of radiation, conductive storage, etc – It is affected by orientation, time , latitude, etc – Data published by ASHRAE
Cooling Load Factor (CLF) • This factor applies to radiation heat gain • If radiation is constant, cooling load = radiative gain • If radiation heat is periodical, than Q t = Q daily max (CLF) CLF accounts for the delay before radiative gains becomes a cooling load
Glazing glass
• Q = A (SC) (SHGF) (CLF) A= glass area SC= shading coefficient SHGF= solar heat gain factor, tabulated by ASHRAE CLF= cooling load factor, tabulated by ASHRAE
• Q = U x A x CLTD U= surface U-factor A= surface area CLTD= cooling load temperature difference
Solar ray
transmitted
reflected absorbed
Opaque Surfaces • Q 2 = UA (CLTD) U= surface U-factor A= surface area CLTD= cooling load temperature difference
• Tabulated or chart values for CLTD can be referred • Offshore enclosure – Light weight – Metal frame with insulation – Group G wall with U-value about 0.5-1.0 W/m2 K
CLTD for Sunlit Wall Group G
Source: ASHRAE Fundamental
Opaque Surface Calculations • Use Table for wall CLTD • Use Table for roof CLTD – Select wall/roof type – Look up uncorrected CLTD – Correct CLTD CLTD c=(CLTD+LM)+ (25.5-t r) + (t m-29.4)
• LM= latitude /month correction (Table ) • T r = indoor temperature (22C) • T m= average temperature on the design day = (35+22)/2 = 28.5 C Eg. If CLTD=40 C, LM=-1.7 (west face) CLTD c= (40-1.7) + (25.5-22)+ (28.5-29.4) = 40.9 C
Types of Internal Load • Internal loads are – People – Lights – Equipment or appliances
• Consist of convective and radiant components – Light (mostly radiant) – Electrical heat (radiant and convective) – People (most convective)
• Time-delay effect due to thermal storage
Internal Load- Lighting •Heat gain (lighting) = 1.2 x total wattage x CLF Or based on light power density ranging from 10-25 W/m2 (average density, say=20 W/m2) •Where light is continuously on, CLF=1
Area Office Corridor Sleeping CCR MCC/SG Kitchen Recreation
Light Power Density W/m2 25 10 10 25 25 25 20
Internal Loads- People • Q people-s = No x sensible heat gain/p x CLF • Q people-L = No x latent heat gain/p
Internal Load – Equipment Heat • Cooling of electrical equipment in MCC/SG is an important function of HVAC system offshore. The components include: • • • • • • • • •
Transformers Motors Medium/high voltage switchgears Cables & trays Motor starters Inverters Battery chargers Circuit breakers Unit panel board etc
• Heat dissipation from these equipments are mainly based data published by the manufacturers
Typical Outdoor & Indoor Design Conditions Used Here Conditions
Dry-bulb temperature (C)
% RH
Moisture content, kg/kg
Outdoor air
35
70
0.025
Indoor air
22
55
0.009
Difference
13
0.016
ASHRAE fundamental Handbook published data, at 0.4%, 1% and 2% design level. At 0.4% design level, Miri has only 35h (out of 8760 h a year) at 32.2 DB & 26.3 WB or higher
Infiltration Air is Cooling Load • Load due to Ventilation air into the space Sensible load, (W) = mass flow rate x specific heat x (∆T) = 1.23 x l/s x (To – T i) or (1.08 x cfm x ∆T) Where To = Outside temperature, C Ti = indoor air temperature, C
Ventilation Cooling Load Ventilation latent load, (W) = mass flow rate x latent heat of vaporization x (humidity difference) = 3010 x l/s x (∆ẁ) or (4840 x cfm x ∆ẁ)
Where ∆ẁ = Inside-outside humidity ratio difference of air ( kg/kg)
Total Cooling Load • This is also call the Grand total load • Sum of – Space heat gain – System heat gain
Room Total Load
– load due to outdoor air supplied through the air handling unit • Air bypassed the coil • Air not bypassed the coil
System Heat Gain • These are sometimes external to the air conditioned space • HVAC equipment also contributes to heat gain – Fan heat gain – Duct heat gain
Bypass Factor Bypass factor is an important coil characteristic on moisture removal performance . It’s value depends on: • Number of rows/fins per inch • Velocity of air
Bypass Factor of the coil • When air streams across the cooling, portion of air may not come into contact with the coil surface • BPF = un-contacted air flow total flow BPF is normally selected at 0.1 for offshore cooling and dehumidification.
Typical Coil Bypass Factor 14 fins/inch
Row Deep Face velocity=
2.5 m/s
3 m/s
2 m/s 1
0.52
0.56
0.59
2
0.274
0.31
0.35
4
0.076
0.10
0.12
6
0.022
0.03
0.04
Source: Refrigeration and Air Conditioning by CP Arora
Effect of Bypass Factor on Ventilation Load • Coil load due to outdoor air SH= (OASH)(1-BPF) LH= (OALH)(1-BPF)
• Effective room load ERSH=RSH+(OASH)(BPF) ERLH=RLH + (OALH)(BPF)
Cooling Load Classroom Exercise • Estimate the cooling load of a portal cabin shown here: • Assuming that – Outdoor condition is 35C, 70% RH – Indoor condition is 22C , 55 % RH – U-factor=0.5 W/m2 K – Occupied by 2 persons – Electrical equipment heat is 3 kW – 100l/s leakage due to pressurization
N
4x4 Platform x 3 h Lower Deck
Cooling Load Calculations Items
Procedures
Transmission- sensible Wall- West side Wall- East side Wall – North Wall- South Roof Floor Total (T1)
Q = UA (CLTD)
Internal load- sensible People Equipment Light Total (T2) Safety Factor (5% of T1+ T2) Fan heat & supply Duct Gain (7 % of T1+T2) RSH (Total of the above)
Coil Load Calculations Items Room Latent Heat (RLH) People
Room Total Heat RSH + RLH
Procedures
Cooling Load Calculations Items
Procedures
Design conditions
Outdoor 35C, 70% RH Indoor 22C, 55 RH
Ventilation- sensible Bypass air (0.1 bypass factor) Sensible heat of bypass air
Ventilation - Latent Latent heat of bypass air
10% x outdoor air
Cooling Load Calculations Items
Procedures
Design conditions
Outdoor 35C, 70% RH Indoor 22C, 55 RH
ERSH RSH Sensible heat of air bypass Effective Room Sensible Heat ERLH People Latent heat of air bypass Effective Room Latent Heat Effective Room Total Heat (ERTH) ERSH+ESLH
Coil Load Calculation Items
Procedures
Design conditions
Outdoor 35C, 70% RH Indoor 22C, 55 RH
Coil Load – Sensible Effective Room Sensible Heat SH of Outdoor air not bypassed Total (Coil Sensible heat) Coil Load – Latent Effective Room Latent Heat LH of Outdoor air not bypassed Total (Coil latent heat) Total coil load (GTH)
Sensible Heat Factor (SHF) SHF RSHF ESHF GSHF
Sensible Heat Factor (SHF) • Ratio of sensible to total heat – SHF = Sensible heat/ total heat
= SH/ (SH + LH) A low value of SHF indicates a high latent heat load, which is common in humid climate. • In the above example, – Calculate the SHF of the room (RSHF) – Calculate the effective room sensible heat factor (ESHF) – Calculate the SHF of the coil (GSHF)
Selection of Air Conditioning Apparatus • The necessary data required are: – GTH ( Grand total heat load) – Dehumidified air quantity – Apparatus dew point
These determine the size of the apparatus and refrigerant temperature.
View more...
Comments