Compact NS400 to 630 circuit breakers, types N, H and L, 3-pole and 4-pole, may be equipped with any of the STR23SE, STR23SV, STR53UE and STR53SV electronic trip units.
Protection of distribution systems STR trip units for Compact NS400 to 630
60
40
6 1 1 5 0 1 B D
250
400
500
600
STR23SE / STR53UE STR23SE 0SN STR23SE / STR53UE
STR23SV / STR53SV? ?
The and of STR53SV trip units offerSTR53UE a wider range settings and the STR53UE offers a number of optional protection, measurement and communications functions.
Standard protection with selectivity
Protection of systems with an overloaded neutral Protection of systems U > 525 V
Protection of systems supplied by generators. Protection of long cables
Selection of the trip unit depends on the type of distribution system protected and the operational voltage of the circuit breaker. Protection for all types of circuits, from 60 to 630 A, is possible with only five tripunit catalogue numbers, whatever the circuit-breaker operational voltage: b U y 525 V: STR23SE, STR23SE OSN or STR53UE b U > 525 V: STR23SV or STR53SV. Trip units do not have a predefined rating. The tripping threshold depends on the circuit breaker rating and the LT (long time) current setting. For example, for an STR23SE trip unit set to the maximum value, the tripping threshold is: v 250 A, when installed on a Compact NS400 250 A v 630 A, when installed on a Compact NS630.
STR23SE (U y 525 V) and STR23SV (U > 525 V) electronic trip units 6
1
7
3
t
1 5 7 3 0 1 B D
1
STR 23 SE
4 9 0 4 2 E
2
Io .8
.9
.7
3
.93 .95 .98
.8 x In
+
.88
Isd
.85
.5
4
.9 1
.63
90 %Ir 105
alarm
Ir
1
5
6
4
7
3
8
2
x Io
10 x Ir
Ir
-
Isd
5 test
0
1
long-time threshold (overload protection) Ir long-time tripping delay short-time pick-up (short-circuit protection) Isd short-time tripping delay instantaneous pick-up (short-circuit protection) Ii test connector percent load indication
2 3 4 5 6 7
Ir
Isd
li
I
Protection The protection functions may be set using the adjustment dials. Overload protection Long-time protection with an adjustable threshold and fixed tripping delay: b Io base setting (6-position dial from 0.5 to 1) b Ir fine adjustment (8-position dial from 0.8 to 1). Short-circuit protection Short-time and instantaneous protection: b short-time protection with an adjustable pick-up and fixed tripping delay b instantaneous protection with fixed pick-up. Protection of the fourth pole On four-pole circuit breakers, neutral protection is set using a three-position switch to 4P 3d (neutral unprotected), 4P 3d + N/2 (neutral protection at 0.5 In) or 4P 4d (neutral protection at In). Protection of an overloaded neutral (OSN): For 4-pole circuit breakers, special protection of systems with high 3rd order harmonic contents. In position 4P 4d, the switch sets the neutral protection threshold to 1.6 x Ir.
Indications A LED on the front indicates the percent load: b ON - load is > 90 % of Ir setting b flashing
- load is > 105 % of Ir setting.
Test A mini test kit or a portable test kit may be connected to the test connector on the front to check circuit-breaker operation after installing the trip unit or accessories.