Column Shear Design
Short Description
wew...
Description
NSCP 2010 Specification and Equation No.
Angel Lazaro & Associates International Consulting Engineers and Architects 160 Panay Ave., cor EDSA, Diliman, Quezon City, 1103 Phil Tel # : 924-1911 924-1879 Fax #: 924-1865 924-1931 (632) 924-1887
Project Title : Location :
Design of Rockery Slope Protection Palali, Sta. Lucia, Ilocos Sur, Region 1
Client : Address :
Department of Public Work and Highways (DPWH)
Cal'c by : Date : Checked by: Date : Rev : Date :
A.H.Sinconiegue Feb. 4 , 2013 B.S.Buenconsejo
Design Refference: NSCP Volume 1, Fourth Edition 2010 Design of Reinforce Concrete, 2ND Edition by Jack C. McCormac Reinforced Concrete Mechanics and Design ( 4th Edition SI Units) by James McGregor I. Design Inputs :
409.4.2.3
Axial Demand, Nu = Shear Demand, Vu = Shear Capacity Reduction Factor, ɸ =
127.13 KN 137.53 KN 0.75
II. Material Properties Compressive Concrete Strength, fc' = Steel Yeild Strenght Main Bar, fy = Steel Yeild Strenght Tie Bar, fLT = Modulus Elasticity of steel, Es =
21.00 413.00 276.00 200000.00
Mpa Mpa Mpa Mpa
650.00 650.00 602.00 40.00 16.00 12.00 1.00
mm mm mm mm mm mm
III. Design Assumption
411.8.4.3
Column Width, b = Column Depth, h = Effective depth, d = Concrete cover, cc = Main Bar diameter, Ø = Lateral Tie diameter , ØLT = Modification factor, λ = IV. Design Vertical Tie Spacing,S Ultimate Design Factored Shear Force, Vu =
137.53 KN
Calculation for Nominal Shear Strength provided by concrete, Vc 411.4.1.2
Vc = 0.17 ( 1 + Nu/14*Ag )*λ*sqrt(fc')*b*d/1000
311.39 KN
Check if Lateral Ties is needed, Vu > 0.5ФVc 411.6.6.1
0.5*Ф*Vc =
116.77 KN
Shear Reinforcement Needed
Note: If shear reinf. Not needed adopt spacing from Section.407.11.5.1. Calcualtion below N/A. Calculation for Nominal Shear Force, Vn 411.2.1
Vn = Vu/Ф
183.37 KN
Calculation for shear strength provided by lateral ties, Vs 411.2.1
Vs = Vn - Vc
-128.02 KN
Check if shear strength provided by lateral ties, Vs exceeds 0.33*sqrt(fc')*b*d/1000 411.6.5.3
0.33*sqrt(fc')*b*d/1000 =
591.74 KN
max. spacing d/2
Calculation for maximum spacing, Smax 411.6.5.1
Smax=d/2
301.00 mm
Check if shear strength provided by lateral ties, Vs exceeds 0.66*sqrt(fc')*b*d/1000 411.6.7.9
0.66*sqrt(fc')*b*d/1000 =
1183.49 KN
Section is Appropriate
Calculation for area for lateral tie reinforcement, Av 411.6.7.3
Av = 2*π*(ØLT)2/4
2 226.19 mm
Calculation for theoretical spacing, S 411.6.7.2
S= Av*fLT*d/Vs
-293.58 mm
250 mm
274.42 mm
250 mm
Calculation for maximum spacing to provide minimum area of shear reinforcement, S 411.7.5.2
S = Av*fLT/(0.35*b) Vertical spacing shall not exceed the following :
407.11.5.1 407.11.5.1 407.11.5.1
16*Ø = 48*ØLT = least dimension =
256.00 mm 576.00 mm 650.00 mm
smallest value =
256.00 mm
Adopt actual spacing, Sact =
250.00 mm
Note: these should be used over one-fourth of the column length of each end. V. Design Summary Therefore since lat. Ties is not needed adopt spacing, Sact = Provide : Ø12mm lat tie, spaced 1 @ 50mm rest @ 200mm O.C.
250.00 mm
say
200
mm