April 11, 2017 | Author: SamirdeOliveira | Category: N/A
Download CIMPLICITY HMI FIELD SERVICE HANDBOOK-Rev-2.pdf...
GE Industrial Control Systems Turbine Control Systems Salem, Virginia
HMI FIELD SERVICE HANDBOOK (For Mark V & CIMPLICITY HMI 3.22)
SK-HMI-C322 Release 2.0, December 1, 1999
© 1999 General Electric Company, USA All rights reserved Printed in the United States of America
2
Table of Contents 1.0 DOCUMENT PURPOSE ..............................................................................................................................................6 1.1 1.2 1.3
SALEM ANSWER CENTER & POWER ANSWER CENTER............................................................................................6 CIMPLICITY REGISTRATION .................................................................................................................................6 CCS SUPPORT NUMBERS.........................................................................................................................................6
2.0 HANDBOOK FEEDBACK ..........................................................................................................................................7 3.0 HMI INSTALLATION .................................................................................................................................................8 3.1 INSTALLATION INFORMATION .......................................................................................................................................8 3.2 HMI INSTALLATION & CHECKLIST ...............................................................................................................................9 4.0 OVERVIEW................................................................................................................................................................12 4.1 DIRECTORY STRUCTURE ............................................................................................................................................. 13 5.0 POWER UP SEQUENCE FOR HMI.........................................................................................................................15 5.1 OVERVIEW ................................................................................................................................................................. 15 5.2 DETAILED POWER UP INSTRUCTIONS ........................................................................................................................... 16 6.0 WINDOWS NT ...........................................................................................................................................................16 6.1 USER ADMINISTRATION/ PASSWORDS .......................................................................................................................... 16 6.2 WINDOWS NT VERSION & SERVICE PACK ................................................................................................................... 17 6.3 PERFORMANCE MONITOR............................................................................................................................................ 18 6.4 WINDOWS NT TASK MANAGER................................................................................................................................... 19 7.0 CIMPLICITY HMI.....................................................................................................................................................22 7.1 PROJECT CONFIGURATION .......................................................................................................................................... 22 7.2 PROJECT CONFIGURATION CABINET ............................................................................................................................ 23 7.3 CIMPLICITY VERSION ............................................................................................................................................. 23 7.4 RUN CIMPLICITY PROJECT ...................................................................................................................................... 23 7.5 CIMPLICITY REGISTRATION .................................................................................................................................... 23 7.6 DESKTOP SHORTCUT FOR UNIT CONTROL SCREEN ....................................................................................................... 24 7.6 CIMPLICITY POINT CONTROL PANEL........................................................................................................................ 24 7.7 CIMPLICITY PROJECT BACKUP................................................................................................................................. 24 8.0 NETWORK CONFIGURATION...............................................................................................................................24 8.1 UPDATE DRAWING TO SHOW IP ADDRESSES AND COMPUTER NAMES .............................................................................. 25 8.2 VERIFY CABLE CONNECTIONS ..................................................................................................................................... 25 8.3 NETWORK ADAPTER: VERIFY SETUP (ETHERNET CARD ADAPTER DRIVERS, I/O ADDRESS, INTERRUPT, ETC.) ............... 25 8.4 WINDOWS NT ............................................................................................................................................................ 29 8.5 TCP/IP ...................................................................................................................................................................... 31 8.6 HOST FILE ENTRIES .................................................................................................................................................... 34 8.7 STAGELINK ................................................................................................................................................................ 34 8.8 TROUBLESHOOTING .................................................................................................................................................... 35 9.0 TURBINE CONTROL INTERFACE ........................................................................................................................37 9.1 TCI CONFIGURATION FILES ........................................................................................................................................ 37 9.2 TCI CONFIGURATION SETTINGS ................................................................................................................................ 37 9.3 MARKV TIME SYNCHRONIZATION ............................................................................................................................. 39 9.4 HMI UNIT-SPECIFIC DIRECTORY................................................................................................................................. 39 9.5 REBUILD START MENU ............................................................................................................................................... 39 9.6 NET START/STOP ........................................................................................................................................................ 40 9.0 HMI TROUBLE SHOOTING GUIDE ......................................................................................................................40 10.1 TCI TROUBLESHOOTING TOOLS ................................................................................................................................ 41 10.2 ARCWHO .................................................................................................................................................................. 41 3
10.3 STAGE LINK COMMUNICATION (ARCNET) ............................................................................................................... 42 10.4 CARD_ID .................................................................................................................................................................. 42 10.5 CHECKCRC ............................................................................................................................................................... 43 10.6 CONSTSET & CONSTDSP ........................................................................................................................................... 43 10.7 CONSTCHK ........................................................................................................................................................... 44 10.8 LOGIC FORCING DISPLAY .......................................................................................................................................... 44 10.9 DEMAND DISPLAY .................................................................................................................................................... 44 11.0 CIMPLICITY HMI TROUBLESHOOTING ..........................................................................................................46 11.1 PROCESS CONTROL ................................................................................................................................................... 46 11.2 CIMPLICITY OPTIONS............................................................................................................................................ 46 11.3 CIMPLICITY HMI LOG FILES ................................................................................................................................. 47 12.0 CIMPLICITY HMI...................................................................................................................................................50 12.1 SIGNAL MANAGER .................................................................................................................................................... 50 12.2 ADDING A POINT TO THE CIMPLICITY DATABASE.................................................................................................... 51 12.3 ALARMS ................................................................................................................................................................... 51 12.4 DATABASE POINTS.................................................................................................................................................... 55 12.5 CIMPLICITY VIRTUAL POINTS................................................................................................................................ 55 12.6 SCREEN EDITING FUNDAMENTALS ............................................................................................................................. 56 12.7 AUTO LOGON FOR WINDOWS NT & CIMPLICITY HMI ........................................................................................... 62 12.8 TCI VIEWER SETUP .................................................................................................................................................. 63 12.9 MULTI-UNIT SETUP .................................................................................................................................................. 64 13.0 HARD DRIVE RESTORATION PROCEDURE .....................................................................................................67 13.1 PC CONFIGURATION ................................................................................................................................................. 67 13.2 REFORMAT PC HARD DRIVE, INSTALL NT, CIMPLICITY, TCI & CIMBRIDGE ......................................................... 67 13.3 RESTORE NETWORK CONFIGURATION ........................................................................................................................ 68 13.4 CIMPLICITY INSTALLATION ................................................................................................................................... 68 13.5 SOFTWARE VERIFICATION ......................................................................................................................................... 68 14.0 PRINTERS ................................................................................................................................................................69 14.1 ALARM PRINTER & EPA PRINTER ............................................................................................................................. 69 14.2 PRINTER SETUP ON HMI AND HISTORIAN CONNECTED OVER ETHERNET ...................................................................... 70 14.3 PRINTER SETUP ON HMI AND HISTORIAN CONNECTED OVER PARALLEL PORT CONNECTION......................................... 71 15.0 CREATING THE IO_TEST SCREENS ..................................................................................................................72 16.0 MODBUS CONFIGURATION WITH HMI............................................................................................................73 16.1 FILE CONFIG.DAT (ONLY THE LINES NEEDED FOR MODBUS ARE SHOWN) ..................................................................... 73 16.2 FILE IO_PORTS.DAT (ONLY THE LINES NEEDED ARE SHOWN)....................................................................................... 73 16.3 PROCEDURE ............................................................................................................................................................. 73 16.4 MODCOMM CONFIGURATION ................................................................................................................................. 74 16.5 TROUBLESHOOTING .................................................................................................................................................. 74 17.0 REMOTE ACCESS SERVER ..................................................................................................................................75 17.1 TO CONFIGURE REMOTE ACCESS (RAS) .................................................................................................................... 75 17.2 CONFIGURE ADMINISTRATOR PRIVILEGES.................................................................................................................. 78 17.3 TO MANUALLY START RAS USING WINDOWS ............................................................................................................. 80 18.0 MANUALS AND SERVICE PACKS .......................................................................................................................82 18.1 CIMPLICITY HMI MANUALS ................................................................................................................................. 82 18.2 CIMPLICIY SERVICE PACKS .................................................................................................................................... 82 18.3 MARK V HMI APPLICATION MANUAL ....................................................................................................................... 82 18.4 CIMPLICITY UPGRADES ......................................................................................................................................... 82 19.0 LIST OF DOCUMENTATION ................................................................................................................................83
4
20.0 PROBLEM REPORT ...............................................................................................................................................84 21.0 HMI INSTALLATION & CHECKLIST ................................................................................................................85 22.0 SITE INSTALLATION INFORMATION ...............................................................................................................88 23.0 CCS WARRANTY FORM .......................................................................................................................................89
5
1.0 Document Purpose This condensed handbook is intended as a guide to answering common questions encountered during HMI installation in the field. Detailed documentation is provided on the product CD, which comes with the installation hardware. A list of the documentation provided on the CD is included at the end of manual. An electronic copy of the complete CIMPLICITY HMI manuals in PDF format can be accessed online with indexing and search capabilities. The manuals are also provided on the CIMPLICITY installation CD. You will find this invaluable when editing CIMPLICITY screens. If the information you require is not found in the handbook an additional source is the electronic HMI FAQ which resides on the product CD. This document is also intended to assure a standardized unified product that is serviceable.
1.1 SALEM Answer Center & Power Answer Center In an effort to support the various Field Engineering groups, Salem is implementing a "One-Number" service support line: 1-800-533-5885 Toll Free 540-378-3280 (D.C. *244-3280) (With no access to the 800 #) FAX: 540-378-3234 (D.C. *244-3234) Please use this number to contact Salem personnel regarding technical requests and inquiries, parts orders and status, etc. for Turbine related products (MK I/ II/ III/ IV/ V/ VI panel, EX2000, LCI, , HMI, GCP, etc.). All Salem personnel have been asked to direct inquiries to this number. Calling the support line: When calling the service support line, the voice attendant menu will list the available options. Select the appropriate option to connect with a Customer Service Coordinator. The coordinator will obtain initial information to direct your call appropriately and will provide you with a case reference number. Be sure to use this number in all communications with Salem. 24 x 7 support: This is a 24 x 7 support line that you may call at any time, day or night, from anywhere in the world. Depending on the urgency of the situation, the appropriate personnel will be contacted, generally responding within an hour. If the issue does not constitute an emergency, the specifics of your call will be passed to the next available Product Service Engineer for call back the next business day. Global Installation and Field Services (PGS): If you have not been issued a PAC (Power Answer Center) case, please call 1-888-443-7747 to obtain one before calling the Salem support line. If a PAC case has been opened, please give the case number to the Customer Service Coordinator when calling. ES/Customers and Other non-PGS personnel: Please use the case number assigned by the Customer Service Coordinator when referencing your inquiry.
1.2 CIMPLICITY Registration The telephone numbers in Albany are 518-464-4642
1.3 CCS Support Numbers. If you require CCS support, use the procedure described in the warranty sheet provided in section 19.0. The CCS support number is (540) 382-4234 ex 161, The contact at GE Drives is RAJ SEN (540) 387-7742 6
2.0 Handbook Feedback To continue providing improvements, striving toward our Six-Sigma goal, it is imperative to receive feedback from those who use this handbook. Please take the time to answer the following questions and return any additional information you think is necessary to improve the handbook. Please be precise as to the section and content of the document where problems were found. Use additional sheets if more space is needed to answer the survey. Return survey by email to Mark Phelps/Brad Lewis at:
[email protected] or Brad Lewis at:
[email protected] 1.
Where was the handbook lacking? a.
Clarity
b.
Graphics
c.
Amount of information
d.
Other
2.
Was the handbook applicable to your installation?
3.
Please provide a network topology map of your installation if the one provided with the documentation was not sufficient.
4.
Other feedback you feel is relevant.
5.
In your best estimation, how did this handbook influence the time spent on HMI start-up? How did it influence the time spent on entire HMI installation?
7
3.0 HMI Installation A copy of the tables below is included at the end of the manual for your use. 3.1 Installation Information 3.1.1 Usernames and Passwords
Include all HMI Servers, HMI Viewers, Historians Computer Name
Username
User Password
3.1.2 Unit Configuration Provide a Network Topology of the Installation. Complete the project configuration below and E-Mail it back to Salem.
Unit 1
Unit 2
Unit 3
Unit 4
Unit 5
Unit 6
Unit 7
Unit 8
1. PROJECT NAME 2. Computer Workgroup 3. IP Address 4. ARCNET Address 5. TCI Version 6. CIMBridge Version 7. CIMPLICITY Version & Build 8. Microsoft NT Version 9. Ethernet Adapter Driver 10. Ethernet Node Address 11. Ethernet I/O Address 12. Ethernet media Type
8
3.2 HMI Installation & Checklist The computers are shipped with Windows NT, CIMPLICITY, CIMBridge and TCI pre-installed. The following configuration items need to be completed in the order specified for as a pre-requisite to system start up. The individual items should be checked off when completed and the information documented for future reference. Detailed information on how to obtain or implement the information is provided on the reference pages identified. A copy of the table below is included at the end of the manual for your use.
Table 3.1: Installation Checklist Complete
Installation Checklist 1 2 3
4
5
Connect system per A108 Configuration Topology drawing provided by Salem Power up System Install CIMPLICITY project using CD provided with Installation Manual a) Match computer name with project directory e.g. SVR1 and open directory. b) Run Setup.exe to install CIMPLICITY project. This is a self-extracting file. Check NT Usernames & Passwords. • From the Start menu select Settings/Control Panel/Network. On the Identification tab, look at the Computer Name and Workgroup entries. • All of the HMI computers are delivered with the name HMI1. Each computer must have a unique name. Names should be descriptive to the function, such as SVR1(server), VWR1(viewer), REM1, etc. On a multi-unit system names such as SVR1, SVR2, may be appropriate. • NT users (Administrator, Operator, Supervisor… ) and CIMPLICITY Users must have the same user names and same passwords, exactly. (You should verify that NT Users are Administrator, oper or maint) • To configure NT users/passwords , while logged on as Administrator Select Programs | Administrative tools | User Manager • Computer Passwords Computer Password HMI Servers Administrator gepgc oper maint maint Historian Administrator gepgc (or Administrator) User gepgc (or Administrator) Operator gepgc (or Administrator) Check CIMPLICITY Project configuration by confirming the following: a) Check CIMPLICITY Version • From Configuration Cabinet Select Help | About CfgCab b) Check CIMPLICITY Configuration • Select Project | Project Settings from the menu bar of Project Configuration Cabinet • CIMPLICITY HMI should be configured with the following project properties Project Name: Appropriate name
Reference p15
p16
p22
Ex: SVR1, VWR1 Sub Directory: Must be Cimproj (Check using Windows Explorer) Path: C:\SITE ( Check in TCI : see section 9) Options: None c)
Check CIMPLICITY Protocol should be MARK V+ Communication 9
d) Check CIMPLICITY Registration • Select Start | Programs | CIMPLICITY | HMI | Registration e) Create Desktop Shortcut • From c:\Site\Cimprog\Screens directory, right click on Unit_Control.cim and select Create Shortcut. Move shortcut to desktop. • If you use autologin, add /waitforproject SVR1(project name) to the shortcut. 6
Check Network Configuration a) IP Address All computers come with I/P Address 192.168.1.20 Select Start | Settings | Control | Network | Protocols | TCP/IP i. Leave one computer with this address. ii. Change the second computer to I/P Address 192.168.1.21 iii. Change the third computer to I/P Address 192.168.1.22 iv. Index each subsequent computer I/P Address by a value of 1. v. Subnet Mask should be 255.255.255.0 vi. Select DNS Entry (not normally used) b) Cable Connections i. Check if correct cable is being used ii. Network Adapter Verify driver by selecting Start | Settings | Control | Network | Adapters . Select Adapter Tab and verify adapter to be 3COM Etherlink XL Adapter or equivalent iii. Media Type Select Properties Tab under Network Adapter. Use Auto select unless there is no doubt of media type. c) Host Files Use Wordpad to edit the file C:\winNT\system32\drivers\etc\Hosts. Create entries for each of the computers in the system, according to the names and IP addresses assigned. An example of a Host File is shown below. The host file should be provided by the requisition engineer. Identical copies of this file should be on each computer. 192.168.1.20 192.168.1.21 192.168.1.22 192.168.1.23
7
8
9
SVR1 SVR2 VWR1 VWR2
p62 p24
#Local server #Remote server #Local viewer for gas turbine unit Tn #Local viewer for steam turbine unit S1
Check TCI Version • Select Start | Programs | Turbine Control Maintenance | HMI Configurtion | View TCI Version • The Version.dat file in G:\Data gives the version of TCI Site Installation Check the overall system configuration by checking the Config.dat file for the following: a) Options supplied ____________ b) Number of Units ____________ c) Unit Names ____________ d) Unit ARCNET addresses ____________ TCI Settings Check TCI Settings by selecting Start | Settings | Control Panel | TCI and the appropriate tab (1) Autologin Select Enabled
p14
p37
p37
10
(2) Site c:\site\SVR1 Default Scale (3) TimeSync Time Acquistion Card
10
Select Select
English or Metric Low Resolution
(4) ARCNET Network Type Select Stagelink or CSF Base IO Address Select Default 0x2B0 (hex) Base Memory Address Select Default 0xD0000 (hex) Interrupt Number 15 (Normally 15 unless there is more than 1 Arcnet Card) Arcnet Link Address ( set at “1F” when shipped ) TCI (Turbine Control Interface) Running Correctly a) Reboot Computer b) Check if TCI software is running. • From Dos prompt type C: net start and look for TCI Service (Message: ” TCI (Turbine Control Interface) was started successfully” c)
p40
Check for correct F:Drive substitution. • Type Subst at Dos prompt. The correct path for your project should be returned Ex: F: \: => c:\site\cimproj G:\: => c:\TCI • If path is incorrect stop TCI and enter correct path as follows C: net stop TCI C: Subst F: /D C: Subst C: F: \site\cimproj
d) Check TCI Log File for any errors during startup Start | Programs | Turbine Control Maintenance | HMI Configuration | View TCI log e) Check Stagelink • Addresses agree with those in Config.dat • If Arcnet communication has been established C: Arcwho f) Check Signals C: View0 for each unit. to exit 11
Start CIMPLICITY Project a) Execute *.gef file ___________ The CIMPLICITY project configuration cabinet is accessed by selecting the .gef file in the F:\Cimproj directory. b) Start Project ___________ Select Run Icon (Triangle) from Configuration Cabinet. Observe CIMPLICITY processes are successfully started. c) Make Desktop shortcut for Unit_control.cim screen From F:Cimprog\Screens directory, right click on Unit_Control.cim and select Create Shortcut. Move shortcut to desktop. d) Execute Unit_Control.cim ___________
p23
e) Verify data using point control panel • View any current CIMPLICITY point value in your system Select Point Control Panel from Start | Programs | CIMPLICITY | HMI menu. Select New form the File Menu in the Point Control Panel window displayed. 11
From the Edit menu select Add to a view a point(s). From the popup window Select the desired points to be viewed.
12
Check Alarm Printer Setup The normal procedure for configuring an alarm printer is to rename one of the existing printers. If a new printer needs to be created then use the printer wizard which can be accessed using the following procedure.
p69
To add a printer select Start | Settings | Printers 13 14 15
Check Autostart Check Multi-Unit Configuration Check Remote Access Service
p62 p64 p72
4.0 Overview In its simplest configuration, the Mark V controller is connected via a StageLink , (a Coax cable with T Connectors and terminating resistors) to a HMI (a PC based operator interface).
The HMI consists of three software components • CIMPLICITY HMI – Operator graphics software package for displaying turbine data. Turbine data is stored in a Point Data Base in CIMPLICITY. • TCI (Turbine Control Interface) for displaying high speed (< 1 sec) data and for configuring a turbine control unit. TCI provides display, control and configuration capability. Drives G:, F:, are virtual drive substitutions used by TCI software.
12
• CIMB (CIMPLICITY Bridge) enables CIMPLICITY to collect data and alarms from a turbine unit and the transfer of data between the Data Dictionary and CIMPLICITY i.e. F:\UNIT1. The interface between CIMPLICITY HMI, TCI and Cimbridge is shown in the schematic below.
4.1 Directory Structure • CIMPLICITY HMI Directories • ARC: database files • BSM_DATA: system configuration files • DATA: run-time configuration files • EXE: executable files • LOG: status log files and program error files • TCI Directories consist of two pseudo or substitute drives: G: and F:. The substitution for these drives is normally C:\TCI for G:, and C:\SITE for F:. (ref: GEH 6126 manual for more details) • F: contains the site-specific information \CIMPROJ contains CIMPLICITY HMI project files • ALARM_HELP: alarm help files • ARC : database files • DATA: run-time configuration files • LOCK: project lock file • LOG: status log files and program error files • MASTER: master copies of configuration files • SCREENS: CimView screens (.cim) • SCRIPTS: BCE scripts • EX2000.Dat : EX2000 Alarm configuration • SVR1.gef : project configuration file \RUNTIME contains user defined Display Menu definitions \USER is the default directory specified during TCI start up \UNITn is created for each turbine unit. Contains files which make up the data dictionary including input/output checks. 13
a) UNITDATA.DAT Ex: ; ; Name No. ; #unit_data T1 1 ; #point_data ; ; Memory Offset (Hex) ------------------------------------ + ; Memory Segment (Hex) ----------------------------- + | ; Flags (Hex) -------------------------------- + | | ; High/low limits type -----------------+ | | | ; Plotting limits type -----------+ | | | | ; Scale code type ----------+ | | | | | ; Point type ---------+ | | | | | | ; Point Number -+ | | | | | | | ; Name | | | | | | | | A7 8184 015 0070 0000 0000 0009 0060 2FF0 ACCEL_MPU1 4219 002 0091 0000 0000 0011 0060 10F6 ACCEL_MPU2 4220 002 0091 0000 0000 0011 0060 1 0F8 ACCEL_MPU3 4221 002 0091 0000 0000 0011 0060 10FA ACCEL_MPU4 4222 002 0091 0000 0000 0011 0060 10FC b) ALARM.DAT Ex: QP 0 DIAGNOSTIC ALARM QP 1 FORCED LOGIC SIGNAL DETECTED QP 2 INJECTION TO FUEL RATIO LOW: 4 MIN AVG QP 3 INJECTION TO FUEL RATIO LOW: HOURLY AVG QP 4 EXHAUST TEMPERATURE HIGH c)
CONSTSET.DAT Ex: ; ; CONSTSET.DAT -- Control Constants Adjustment Settings File ; ; ;This file contains the adjusta ble constants for the unit. ; ; ; Point Engr Ramp Min Max ; Name Units Rate Value Value A7 "HEX" 1 AFKAP_SITE "in Hg" 0.1 AFKPEFTD "sec" 0.01 AFKPEMN "inH2O" 0 .1 AFKPEMX "inH2O" 0.1
\UNITn\PROM contains control panel processor Prom-related files \UNITn\HTML contains hardware jumper settings \UNITn\IO_Checks contains IO test screen files • G: contains software common to all turbine control panels \EXEC contains all the executable files\programs that form the basic TCI \DATA contains any data files and template files which are not site-specific. The VERSION.DAT gives the version of the TCI software package that is loaded inside the HMI. The IOPORTS.DAT is an optional data file used if the TCI System Service is to take over any of the RS-232 ports on the computer. This file indicates which communication ports should be used, what the port settings are supposed
14
to be (baud rate, parity… ) and what function the port is used for. Functions include MODBUS Master and MODBUS Slave. Thee TIMESYNC.DAT is an optional data file used if the HMI is to be a time master on the StageLink. It is also used if you wish this HMI to synchronize its clock to an external time source, be it a High Resolution Time Card or a time master on the StageLink. \LOG contains system and error log files. - TCI.LOG is the TCI startup log file - TCI1.LOG is previous TCI startup log - MODBUS.LOG is log file for MODBUS (an optional communication link to a supervisory computer – DCS) - TIMESYNC.LOG is a log file generated by the time synchronization program
5.0 Power Up Sequence for HMI 5.1 Overview 1. Windows NT starts up 2. TCI starts up based on definitions in Control Panel, TCI. 3. CIMPLICITY is started by TCI Note: To auto start a CIMPLICITY screen, the following shortcut needs to be inserted C:\Winnt\Profiles\All Users\Start\Programs\Startup Menu\New Shortcut Cimview /waitforproject cimproj F: \cimproj\screens\unit_control.cim
15
5.2 Detailed Power Up Instructions 1.
2. 3. 4. 5. 6. 7.
Turn on HMI PC. Login USER will default to Administrator. The Password is gepgc (GE power generation controls, must be in lower case!!!!!). This can be changed once logged on from Start | Program | Administrative tools (common) | user manager. Place Software CD located in back of Installation manual in the CDROM drive. From the start button, select RUN and type D:\setup.exe Follow the install shield directions. Project should be installed to the C:\SITE directory. The CIMPLICITY screens will be located in the C:\Site\Cimproj\Screens directory. The main unit control screen will be named Unit_Contol.cim. It can be opened by double clicking on Unit_Control.cim. The CIMPLICITY project is located at C:\Site\Comproj.
Custom setup: To create an auto boot up feature which will allow the CIMPLICITY project to start and the unit control screen to open automatically upon system boot up: 1. From the start button, select settings then control panel. 2. Double click on the services icon. 3. Select CIMPLICITY HMI Service and then press startup button. 4. Select manual startup option, then OK. 5. Scroll down and select TCI (Turbine Control Interface) and then the startup button. 6. Ensure TCI startup option is set for Automatic. 7. Select OK and then exit Control Panel /services. 8. Go to start/programs/Cimplicity/HMI/Cimplicity Options. Under the Start options tab, add the Cimplicity project (*.gef) to the system boot options. Then select the start projects option, and then OK. 9. From WindowNT explorer, go to C:\SITE\CIMPROJ\SCREENS directory. 10. Right click on UNIT_CONTROL.cim file and select CREATE SHORTCUT option. 11. Then go to C:\WINNT\PROFILES\OPER\START MENU\PROGRAMS\STARTUP directory and paste shortcut. 12. Right click on the shortcut and select properties. 13. Select the shortcut tab. 14. The target path should be edited to read as follows: C:\Cimplicity\hmi\exe\CimView.exe /alwaysmaximized /waitforproject {Cimplicity Project name) C:\Site\cimproj\screens\Unit_control.cim
15. Also under the Shortcut tab, set the start in path to C:\Cimplicity\HMI\exe & set run to Maximized. Note: If for instance, while logged on as Administrator and the Cimplicity project is manually stopped and then one re-logs on as operator, the Cimplicity service will not restart and the unit control display will not appear. The cimplicity project will need to be restarted while logged in as Administrator. Or, the entire computer has to be rebooted and then the TCI and Cimplicity services will start automatically and the unit control screen will open regardless of the logon user. In short, when logging off as ADMINISTRATOR and logging back on as OPERATOR or any other user, ensure that the CIMPLICITY project is running prior to logging off or do a hard reboot.
6.0 Windows NT 6.1 User Administration/ Passwords CIMPLICITY usernames (passwords) are pre-configured at the factory. To determine existing usernames, set/change passwords or create new users • Select users icon from the HMI configuration cabinet. Set/change passwords or create new users from the File menu. Ensure password needed and enabled boxes are checked when configuring new users. Note: Detailed information is available on-line using the book-reader in GFK-1180G/ Chapter 22 NT users (Administrator, Operator, Supervisor… ) and CIMPLICITY users must have the same user names and same passwords, exactly. (You should verify that NT Users are Administrator, oper or maint) To configure NT users/passwords , while logged on as Administrator • Select | Programs | Administrative Tools | User Manager
16
Note: detailed information on groups/ profiles is available from the NT help file accessed from the menu bar in NT Explorer. As long as the passwords and usernames for NT and CIMPLICITY are kept consistent, whoever logs into NT at system boot (Oper, Maint, Admin) will automatically be logged into CIMPLICITY. Notes: 1. With regard to automatically coming up to log in operator(oper), or maintenance(maint), or administrator, the last user name/person to successfully log in on boot, will be the default user for the next boot. Either way a password must be entered manually at that time. 2. You shouldn’t even need the operator password if you want to change it, if you are logged in as administrator. While logged in as administrator, go start | programs | administrative tools | user manager . Then double click on the user name ‘oper’(upper box). Type in the desired password and type in the confirmed password(same thing). Make sure you deselect ‘user must change password at next log in’. Log off administrator, log in oper with the new password. 3. User names are not case sensitive, passwords are. The computers are shipped out with the following passwords Computer HMI Servers
Historian
Administrator oper maint Administrator User Operator
Password gepgc maint gepgc (or Administrator) gepgc (or Administrator) gepgc (or Administrator)
6.2 Windows NT Version & Service Pack The Windows NT version, build and service pack used in the installation can be determined by selecting: Start | Windows NT Explorer | Help | About Windows NT Selecting the help icon and About Windows NT will bring up the following window
17
6.3 Performance Monitor • Select the Start | Programs | Administrative Tools and then select Performance Monitor. The following screen will appear:
This display is a dynamic chart used to view current system activity. It can be configured to graphically represent system performance for a wide variety of system services and processes. To access the dialog box to assign chart values, click on the “+” button on the toolbar. The following screen will appear:
. Clicking the Add button will immediately add the selected object and counter to the chart as well as assign the color shown. You can see a description of the chosen selection by clicking on the Explain>> button. Choose “Process” under Object and appearing under Instance, you will see a series of CIMPLICITY processes, which you can chart: As you choose these instances, they will immediately become active in the chart display: You can change the Performance Monitor chart settings by choosing Options and Chart from the top menu:
18
The important processes to look for in the chart are the processor time and especially the CIMPLICITY related processes and their amount of time utilization. These processes typically are amrp, calrp, CfgCAb, Cimview, (xx… )rp, Project Name. If the time utilization of the process is particularly large then it is likely to be a problem.
Once you have completed the configuration of the Performance Monitor, choose File and Save Chart Settings from the menu. Save your file within your Peppers Project Directory.
6.4 Windows NT Task Manager Task Manager enables you to monitor and control your computer and what’s running on it. To change display options in Task Manager, select either the Applications, Processes, or Performance tab. Then on the View menu, click the view option you want. Under the Applications tab, you can choose to view details or icons. Under the Processes tab, you can select the columns you want to display. Under the Performance tab, you can change the CPU History graph and show kernel times. To change update speed, select the View menu, point to Update Speed, and then click the speed at which you want Task Manager to update its display. Under the Applications tab:
19
These are the programs that are currently running. The Applications tab shows the status of the programs (also known as tasks) that are currently running on your computer. From this window, you can end, switch to, or start a program. To end a program with Task Manager, select the task that you want to end then click on End Task. Note: Any data you have not saved will be lost. To switch to another program, select the program you want to switch to, and then click Switch To. Under the Processes tab:
20
These are the processes that are currently running on your computer. The Processes tab shows usage information about each of the active processes on your computer. From this window, you can end a process. The important processes to monitor are To view additional information about a process, click View, and then click on Select Columns. To end a process, highlight the process that you want to end, then click on End Process. Task Manager enables you to monitor and control your computer and what’s running on it. To change display options in Task Manager, select either the Applications, Processes, or Performance tab. Then on the View menu, click the view option you want. Under the Performance tab:
21
Note: 1. Average CPU usage should be below 75%
2. Memory Usage should be below 80% The Performance tab displays a dynamic overview of your computer’s performance including graphs for CPU and memory usage, the number of items running (including handles, threads, and processes), information about physical, kernel, and commit memory. You can graph both CPU History and Kernel Times by clicking the View menu and selecting the options you want. You can also enlarge any one of the graphs by double clicking on them, to reduce the graph, simply double click on the graph again. Click on the Windows close “X” button when you are finished exploring the Task Manager.
7.0 CIMPLICITY HMI CIMPLICITY HMI Version 3.2 introduces an electronic book reader based on Adobe Acrobat® that lets you easily search, view, and print out any of the CIMPLCITY HMI documentation. All documents have been electronically indexed which allows the book reader to quickly scan volumes of information and find the topics you are seeking. The installation process is described in the manuals section. • The complete CIMPLCITY HMI library of documentation is stored on the product CD. • The book reader will answer the majority of your questions in a rapid and efficient manner.
CIMPLICITY HMI also has extensive online help. It is strongly recommended you use it!! 7.1 Project Configuration CIMPLICITY HMI should be configured with the following project properties Project Name: Appropriate name Ex: SVR1 Sub Directory: Must be Cimproj Path: C:\SITE\.Cimproj Options: None Protocols: MarkV+ Communication
(this is the CIMPLICITY bridge)
22
The project properties can be examined from the project configuration cabinet by selecting Project | Project Settings from the menu bar. 7.2 Project Configuration Cabinet The CIMPLICITY project configuration cabinet is accessed by selecting the .gef file in the F:\Cimproj directory. The configuration cabinet contains all the tools necessary to configure a CIMPLICITY project. A detailed description of the cabinet and project configuration is described in the CIMPLICITY user manual GFK-1180. An electronic copy is available on the CIMPLICITY distribution CD and can be downloaded from the menu pick on the CD. (Acrobat Reader which is required to read the files can be downloaded as part of the installation.
7.3 CIMPLICITY Version From Project Configuration cabinet menu Select Help | About CfgCab…
7.4 Run CIMPLICITY Project Select Run Icon (Triangle) from Configuration Cabinet. Observe CIMPLICITY processes are successfully started. Check Status Log.
7.5 CIMPLICITY Registration Registration of CIMPLICITY HMI can be checked by selecting :-
23
Start | Programs | CIMPLICITY | HMI | Registration If you do not get a response “ Valid Site License”, then your system needs to be registered. The registration number is 518464-4642. 7.6 Desktop Shortcut for Unit Control Screen From F:Cimprog\Screens directory, right click on Unit_Control.cim and select Create Shortcut. Move shortcut to desktop Directory. If you use autologin, add /waitforproject to the shortcut.
7.6 CIMPLICITY Point Control panel The point control panel provides the following capability: View any current CIMPLICITY point value in your system Select Point Control Panel From Start | Programs | CIMPLICITY | HMI menu. Select New form the File Menu in the Point Control Panel window displayed. From the Edit menu select Add to a view a point(s). From the popup window Select the desired point(s) to be viewed. 7.7 CIMPLICITY Project Backup You can use any standard backup tool which supports long file names to backup your project, provided that you backup the entire project directory (including the .GEF file) and all subdirectories together. If you wish to ZIP the contents of a project (for example, remember to use a 32-bit version ZIP tool which supports long file names. The various 16-bit ZIP programs used the old DOS 8.3 file naming convention; it is almost impossible to recover a project from a 16-bit archive.
8.0 Network Configuration Sketch and use a Network Topology drawing similar to the drawing shown below as your reference when configuring the network on site. It will contain most of the information you will need to properly configure the network. Information on Stagelink and communication requirements can be found in GEH-6126
24
8.1 Update drawing to show IP addresses and computer names
8.2 Verify Cable connections Three types of cable are commonly used in Ethernet installations. The cables are physically distinct, and have different connection and termination requirements. 8.2.1 10BaseT (Twisted pair) 10BaseT consists of multiple twisted pairs of wires, and uses RJ-45 modular plugs similar to phone plugs at each end. 10BaseT is commonly used in a hub and spoke topology, in which each computer talks through a hub to other computers on the network. Two computers can also be wired point to point with 10BaseT using a modified cable. Note: Detailed instructions on how to make up 10BaseT cables are available in the user manual from Cabletron in sections SEHI-22 or 32 . The manuals are provided on the product CD or can be down loaded from the following URL. http://www.cabletron.com/support/manuals/n-s.html. 8.2.2 10Base2 ThinWire (Coax) ThinWire is 50 Ω coaxial cable, typically RG-58. It is similar in appearance to TV cable. In a ThinWire system, computers are daisy-chained together, using a ‘Tee’connectors to connect the network to each node’s Ethernet adapter. Each end of each Thinwire segment must be terminated with a 50 Ω terminating resistor. This can be done externally by using a special BNC connector/terminator on the open leg of the ‘Tee’. Some equipment can be terminated internally, eliminating the need for the external BNC connector/terminator. It is critically important to use the proper value (50 Ω ) terminating resistors on Ethernet. Mixing 93 Ω ARCNET terminators and 50 Ω Ethernet terminators on an Ethernet network will result in excessive communication errors, or a non-operational network. 8.2.3 ThickWire (AUI) ThickWire is typically used for plant backbones, but is sometimes used to connect individual devices. ThickWire systems use special transceivers to connect devices to the actual ThickWire segment. The connection to an individual computer, hub, bridge, etc. is done through an AUI connector. AUI connectors are ‘D’connectors, similar to those used on serial ports. 8.3 Network Adapter: Verify Setup (Ethernet Card Adapter Drivers, I/O Address, Interrupt, etc.) These should be configured (by computer vendor) when the equipment is received. Check them if trouble is encountered. 8.3.1 Driver An Ethernet Card Adapter Driver is provided with the system software. To verify the settings for the driver: From the Start Menu select Settings/Control Panel/Network. Select the Adapters tab. 25
The Network adapter should be 3Com Etherlink XL Adapter in the 3C900 or 3C509 series. (Verify if this is the adapter used) Select Properties button. Note: Depending on the system, there may be more than one Adapter. Each will need to be configured separately. Select OK from the intermediate dialog box, if present.
26
Make note of Node Address, I/O Address, Device ID NOTE: If more than one Ethernet card (e.g. 3Com Etherlink XL #2) is present, select the down arrow and choose the “other” card to obtain additional information. You can then proceed to view Media Type and Other Driver Settings for the “other” card as outlined below. Select Properties tab
Highlight Media Type in the Individual Settings box
27
From the drop down menu in the Individual Settings box, choose the media type. However, the specific configuration should be selected if there is no doubt of the type or there is not a mixed media used, otherwise Auto Select can be used.
Other Driver Settings From Start menu select: Settings/Control Panel/Network Select the Adapters tab, Select Properties button, Select OK from the intermediate dialog box, if present. Select NIC Details button.
28
Make note of the NIC Details.
8.4 Windows NT Windows provides graphical and text based tools for network configuration and troubleshooting. 8.4.1 Name/Domain/Workgroup • From the Start menu select Settings/Control Panel/Network. On the Identification tab, look at the Computer Name and Workgroup entries. All of the HMI computers are delivered with the name HMI1. Each computer must have a unique name. Names should be descriptive to the function, such as SVR1(server), VWR1(viewer), REM1, etc. On a multi-unit system names such as SVR1, SVR2, may be appropriate.
29
To change the name and Domain/Workgroup select the Change… button. Place the cursor in the appropriate box and type in the name. Current standards are to use a Workgroup. Select the Workgroup. Use the Customer’s site name or Site name abbreviation for the Workgroup name. Do not enter any name in the Domain box, leave it blank.
30
When entries are complete, select OK. Changing the name will require rebooting the computer for the change to take effect. 8.5 TCP/IP TCP/IP is the protocol used to communicate between HMI boxes. Those systems with Mark VI also use TCP/IP to communicate control data. TCP/IP requires configuration. All of the following settings are accessed from the TCP/IP properties. Open TCP/IP properties as follows: • From the Start menu select Settings/Control Panel/Network. • Select the Protocols tab and Highlight TCP/IP Protocol. The Properties button will become active.
31
• Select the Properties button.
32
Note: If more than one adapter card exists, use the down arrow to access the “other” card to configure IP Address, Subnet Mask and Default Gateway. 8.5.1 IP Address, Subnet mask, Default Gateway • Select the IP address tab of TCP/IP Properties. • Select Specify an IP Address (Do not use Obtain an IP Address from a DHCP server) • Enter the IP address, Subnet mask, and Default Gateway from the Topology drawing. For detailed information see below 8.5.2 IP Address All computers come with I/P Address 192.168.1.20 • Leave one computer with this address. • Change the second computer to I/P Address 192.168.1.21 • Change the third computer to I/P Address 192.168.1.22 • Index each subsequent computer I/P Address by a value of 1. 8.5 .3 Subnet Mask • Use the value of
255.255.255.0
8.5.4 Default Gateway Check if a Gateway is present. If a gateway is present then enter the Gateway address ensure all signals have the computer name as a pre-fix Leave or make this box void of any value. Changing these values will require rebooting the computer for the changes to take effect. 8.5.5 DNS Entry • Select the DNS tab of TCP/IP Properties. • Enter the Domain Name Server name (if there is one) from the Topology drawing. If not available from the drawing, get the correct DNS from the customer. Most likely there will not be a Domain Name Server.
33
8.6 Host File Entries • Use Wordpad to edit the file C:\winNT\system32\drivers\etc\Hosts. • Create entries for each of the computers in the system, according to the names and IP addresses assigned. An example of a Host File is shown below. The host file should be provided by the requisition engineer. Identical copies of this file should be on each computer. # Copyright (c) 1993-1995 Microsoft Corp. # # This is a sample HOSTS file used by Microsoft TCP/IP for Windows NT. # # This file contains the mappings of IP addresses to host names. Each # entry should be kept on an individual line. The IP address should # be placed in the first column followed by the corresponding host name. # The IP address and the host name should be separated by at least one # space. # # Additionally, comments (such as these) may be inserted on individual # lines or following the machine name denoted by a '#' symbol. # # For example: # # 102.54.94.97 rhino.acme.com # source server # 38.25.63.10 x.acme.com # x client host 192.168.1.20 192.168.1.21 192.168.1.22 192.168.1.23
SVR1 SVR2 VWR1 VWR2
#Local server #Remote server #Local viewer for gas turbine unit Tn #Local viewer for steam turbine unit S1
8.7 Stagelink Stagelink is used in Mark V turbine controls to communicate control data between controllers, and between controllers and computers. 8.8.1 Cable connection/termination ARCNET networks use 93 Ω coaxial cable (typically RG-62) in a daisy chained configuration similar to 10Base2 Ethernet. Each ARCNET segment must be terminated with a 93 Ω resistor, which is usually part of a special coax connector/terminator. It is critically important to use the proper value (93 Ω ) terminating resistors on ARCNET. Mixing 93 Ω ARCNET terminators and 50 Ω Ethernet terminators on an ARCNET network will result in excessive communication errors, or a non-operational network. 8.7.2 Address Check the ARCNET address: • From the Start menu select Settings/Control Panel/TCI (Turbine Control Interface). • Select the ARCNET tab of the Turbine Control Interface. The address information should match the dip switches on the ARCNET card and the information on the Topology drawing. Note:
34
8.8 Troubleshooting The first step in troubleshooting should always be to check physical connections. Once these are verified, several utility programs can be used to get more information about the problem. The following utilities are run from a DOS window. 8.8.1 Ping Ping can be used to determine whether or not the computers can “see” (communicate with) each other over ethernet. To use ping, simply type ping address or ping name at the DOS prompt, where name is the computer name, and address is the IP address. More ping options can be viewed by typing ping –h. Below is shown a successful Ping from a computer which detected HMI_SVR2. Note: Names and addresses are samples only.
Following is an example of an unsuccessful ping.
8.8.2 Ipconfig Ipconfig reports the Ethernet TCP/IP network configuration on which the computer runs. To use Ipconfig, type ipconfig. To view Ipconfig options, type ipconfig /? Shown below is a sample Ipconfig.
35
NOTE: A computer may operate on more than one network e.g. Plant Data Highway (Plant Ethernet) and Unit Data Highway (Control Ethernet). In this case Ipconfig will show the network configurations for both networks.
8.8.3 Netstat Netstat shows what network connections the local computer has made, as well as the status of these connections. Protocol, Foreign Address, Local Address, and Connection state are included in the default display. Type netstat This will show the connections between computers on the network.
. Type netstat /? To display netstat options. 8.8.4 Arcwho To determine if ARCNET communication is established: From a DOS prompt, type arcwho. ARCNET devices will respond with their hexadecimal ARCNET drop numbers. G:\EXEC>ARCWHO Your ARCNET address is : 1E LUNS FOUND: FE FC 1F The example shows 1E assigned to the HMI. The three visible addresses at FE, FC, 1F would be typical for a site for two MARK V controllers (FE &FC) and another HMI (1F)
36
9.0 Turbine Control Interface 9.1 TCI Configuration Files Two files are required for TCI to operate F:\CONFIG.DAT and the F:\TIMEZONE.DAT (Converts UTC to local time, further details can be found in GEH 6126). The file config.dat contains: • List of Mark V controllers • Internal Unit Number for each turbine • Name associated with the unit • Type of turbine control • Addresses on each controller on Stagelink • TCI Options used on the site such as Modbus
9.2 TCI Configuration Settings To configure the TCI settings • Autologin: Select the AUTOLOGIN tab of the Turbine Control Interface from the Start | Settings | Control | TCI icon. Select Autologin from the menu.
• Site: Select SITE tab . Ensure correct path setting for project
37
• TimeSync: Low Resolution should be enabled if the time acquistion hardware is not present
• ARCNET: The address information should match Ex: Hardware Dip Switch Settings. The units are shipped with a dip switch setting of 1F (shown below, note the reversal in 1F in the dip switch setting)
38
Arcnet Hardware Settings 0
1 x x x x x
F
1
9.3 MARKV Time Synchronization If HMI is not displaying the correct time and date in the Header of the Turbine screens then the Prom version should be checked using • Card_id The version needs to 4.0 or higher. • Start | Settings | Control Panel | TCI icon. Low Resolution should be enable if the time acquisition hardware is not present.
9.4 HMI Unit-Specific Directory Unit specific assignment files IO.ASG, FACTORY.ASG, ALLOCSSP.ASG and SITE.ASG are used to create UNITDATA.DAT. In addition data dictionary files ALARM.DAT, ENUMDATA.DAT,ENGLISH.DAT, and METRIC.DAT are present.
9.5 Rebuild Start Menu If TCI menu becomes corrupted or additional units added to the site then the Rebuild Start Menu can be used to delete existing icons and folders and replace them with a standard set generated by referencing local units F:CONFIG>DAT The Maintenance function menu is accessed from Start | Programs | Turbine Control Maintenance Rebuild Start Menu
SK-HMI-C322 Release 2.0, December 1, 1999
9.6 Net start/stop To re-establish communication on the ARCNET: or anytime files in UNIT1\ are modified requiring a MK5Make to be performed and requiring a download to the MK5 – TCI will need to be cycled to assure these changes are available to the HMI. The procedure for cycling TCI is 1. 2. 3.
Close all screens Stop CIMPLICITY project From a DOS prompt type: • net stop tci • net start tci.
9.0 HMI Trouble Shooting Guide a)
Check if TCI software is running. • From Dos prompt type net start and look for “ The requested service has already been started” b) Check for correct F:Drive substitution. • Type Subst at Dos prompt. The correct path for your project should be returned F: \site\cim_proj\ProjectName.gef G:\exec • If path is incorrect stop TCI :C: net stop TCI C: Subst F: /D C: Subst C: F: \site\cim_proj\Enron.gef c) Check definition in Start | Control Panel |TCI | Site. d) Check Log Files • TCI TCI.LOG (Checks if TCI started successfully) • CIMPLICITY - System - COR_STATUS.LOG (system status log file) - W32rtr.out and w32rtr.err (files the router) - Project - COR_RECSTAT.CLG (provides messages which are related to the project) - .OUT and .ERR files (for all CIMPLICITY HMI processes other than user processes) • Windows NT SYSTEM.LOG (C:\WINNT\SYSTEM32\CONFIG… )
e)
Check if the CIMPLICITY project is started. • From Start | Programs | CIMPLICITY | HMI | Options, see project is running f) Check if Data from the Controller is being received by TCI • From Start | Programs | Turbine Control Maintenance | Unit T1 | Demand Display . Enter a data point such as L4 g) Check if there is any undefined CIMPLICITY points. • If a screen has a blank field, right click on the display background and select Point View. Undefined points have a red X next to them. h) Check if there are any CIMPLICITY points which are not defined in the Control Signal database (CSDB) using the CIMPLICITY COR_STATUS.LOG. • Import the missing points only using the Import key under the Actions tab from Signal Manager. i) Check if CIMPLICITY Master and Runtime data are the same. This is verified by stopping and restarting the CIMPLICITY project from the configuration cabinet. CIMPLICITY will prompt for a configuration update. j) Check if CIMPLICITY is running. • Right click on the NT task bar and select Task Manager. Look for CIMPLICITY.exe in the Processes tab. k) Check if the CIMPLICITY bridge is running. • Right click on the NT task bar and select Task Manager. Look for MARKV_RP.exe in the Processes tab. 40
l)
Check if the ARCNET address as specified in F:\CONFIG.DAT agrees
with the setting in the controller using Arcwho
10.1 TCI Troubleshooting Tools If TCI has successfully started (see TCI.log file above) then a set of tools is available for further troubleshooting.These tools are executed from Start | Programs | Turbine Control Maintenance menu. They may also be executed from the Dos Prompt
10.2 Arcwho To determine if ARCNET communication is established a) Type Arcwho at Dos prompt or b) Start | Programs | Turbine Control Maintenance | HMI Configuration | ARCNET Node list ARCNET devices will respond with their hexadecimal ARCNET drop numbers. Ex: 1. Successful Communication
2.
Unsuccessful Communication
41
Look for statement “ -------- Network appears UNSTABLE. ---------( for further information see section 10.3)
10.3 Stage Link Communication (ARCNET) • Attempting to access TCI tools: Logic Forcing | Demand Display | DIAGC brings up, up error message: BMS ERROR – Unable to determine path • Demand Displays show stale, inverse video date/Time field or “No valid Data” • Running Arcwho from DOS prompt shows unstable network: For a Stable Network, Arcwho should give : For example: Your ARCNET address is 28 LUNS found: 44 (LUNS – local unit number) An unstable network can also be caused by only one ARCNET node being alive on the network (i.e. HMI is powered up, but controller isn’t). Possible Causes of a bad Stage Link • • • • • • • • •
“T” Connection not terminated Wrong termination resistor (i.e. Ethernet terminator resistor is used) Wrong Coax cable used (look for RG62 stamping on cable, Do not use Ethernet cable). Coax cable connection is broken Loose connection. Bad cable or T or Terminator TCI Service failed Wrong IRQ address (should be 15) Wrong hardware address
Note: Information for obtaining the correct cabling and tools for constructing Stage Link cabling can be obtained Milestek, Tel no: 1-800-524-7444
10.4 Card_id Determines the versions of Proms in the Mark V control. (Check with Salem for correct versions)
42
10.5 Checkcrc Checks that all TCI product files exist on the PC, they are not corrupted and that they are the correct versions. Start | Programs | Turbine Control Main tenance | HMI Configuration | Check TCI Files
10.6 Constset & Constdsp CONSTSET is a configuration utility used to make all control constants adjustable and to set the default ramp rate for each control constant. A command line utility (used from the Command line (Dos) prompt) F:\UNITn>constset \UNIT: creates a CONSTSET.DAT file for the unit TCI version 1.2 or higher allows the user to start running CONSTSET.DAT. This is done by using the line "*MARKV_DEFAULT" in the CONSTSET.DAT file. The MARKV_DEFAULT parameter directs the Data Dictionary loader to make all Mark V control constants adjustable, and computes each point's ramp rate as one "display digit" per second. If any values are to be excluded from adjustability, or if their ramp rate should be changed, then these lines can be added after the DEFAULT line to apply those overrides. Here is an example: ; ; *MARKV_DEFAULT ; ; Point Engr ; Name Units KLNPTSJ "rpm" KNPTNOMJ "rpm" KMINRSTDJ "sectd" KMINRSTUJ "sectd" KBASE_MW "mw" KDLEACC_G "pph/r" KNCDCAPJM "N/D" KDLE_DEC_G "N/D" KNCDOSPRX "pph" KNGGERRMIN "rpm" ; ;
Ramp Rate 1 100 1 1 1 1 .5 .5 100 100
Min Max Value Value 3600.0 3610.0 2900.0 6300.0 0.0 15.0 0.0 15.0 15.0 30.0 0.0 4.0 0.0 2.0 0.0 4.0 -9999.99 0.0 -10000.0 0.0
The control constants displays the value of all the control constants in a unit. The Display can be accessed from the command line prompt by selecting the unit CONSTDSP /UNIT:Tn 43
A Control Constant with a plus sign next to it denotes the constant is adjustable. When the F:\UNIT\Const_q.src is changed the following must be completed to allow access to the new constants in constants adjust 1. Close all TCI displays 2. Stop CIMPLICITY Project • Using Stop Button in CIMPLICITY Configuration Cabinet • Use menu from Start | Programs | CIMPLICITY | HMI | CIMPLICITY Options 3. From Dos prompt type • net stop tci • Del constset.dat • constset \unit:T1 • net start tci • Mk5make • EEPROM download 4. Start CIMPLICITY Project 5. Open Unit_control.cim screen
10.7 CONSTCHK The control constants are checked using CONSTCHK from the Dos prompt. F:\UNITn>constchk \UNIT: Executing the program results in a report which reports only the values of control constants that have different values between RAM. The /ALL qualifier allows all values to be displayed.
10.8 Logic Forcing Display Logic Forcing provides the capability of forcing any logic data point to a “0” or a “1” regardless of the permissive driving the data point. This is a valuable tool during maintenance or troubleshooting. The tool is only available from a Server.
“Only qualified personnel knowledgeable about turbine control and protection should create and execute commands. The commands can affect the state and action of the unit control” Logic Forcing can be accessed from: Start | Settings | Control | Panel | TCI | Logic Forcing or from the Tools button on the Unit_Control Screen Note: Detailed information is available in GEH-6126
10.9 Demand Display The demand display allows several data points to be monitored at a time and simple commands to be applied. “Only qualified personnel knowledgeable about turbine control and protection should create and execute commands. The commands can affect the state and action of the unit control” The demand display program contains two types of display windows. • Demand Display Menu Screen ~ Contains a list of the demand display screens. Selecting one of the demand display screens accesses the screen. • Demand Display Data Screen ~ Display screen shows Demand Displays. The demand display is accessed from
44
• Start | Programs | Turbine Control Maintenance | Unitn | Demand Display • Start | Run and typing Demand.exe The configuration arguments are /UNIT: Tn executes the Demand Display program for the unit specified /FILE: executes the Demand Display and loads a requested Demand Display file /DISPLAY: displays Demand Display screen in a particular file F:\RUNTIME>DEMAND /FILE:OPERATOR:DM2 /DISPLAY:”LUBE OIL” /TYPE: displays the data screen with points specified at the command line. F:\RUNTIME>DEMAND /TYPE:(L1,F4) The demand display files can be loaded in three ways
1) If the Demand display program is started at the command line, the name of the file can be added after Demand display execution command, Demand. Ex : F:\RUNTIME>DEMAND / FILE:{FILENAME}.DM2 (note extension DM2 is required) 2) To load an existing Demand Display after starting the Demand Display program, select the menu option File:Open from the drop down menu. The open command allows file selection. 3) If no existing file is specified when executing the Demand Display program a default file DEMAND01.DM2 file located in the F:\RUNTIME directory is loaded. To create a new file select New from the file menu.
45
The menu screen shows the list of available demand displays for the selected unit. From this screen, the user selects the actual Demand Display Screen.
11.0 CIMPLICITY HMI Troubleshooting CIMPLICITY provides tools and features that are available for system management, troubleshooting and status reporting.
11.1 Process Control Process Control is a utility for monitoring and controlling all CIMPLICITY processes, which support a project. It can be used on a local project or run over the network for other CIMPLCITY applications. • From Start | Programs | CIMPLICITY | HMI program group double click on the Program Control applet. (To be able to access Process Control, you must have Process Control set as a privilege in your Role) Choose the project that you want to connect to and click on the “Connect” button. All of the processes associated with the project will appear. For a definition of the processes, simply choose “Help.”
11.2 CIMPLICITY Options This utility is used to display, start and stop projects, as well as setup a node to run as a viewer and start a specified Project as a server.
46
• From Start | Programs | CIMPLICITY | HMI program group double click on the CIMPLICITY Options applet. The CIMPLICITY Options dialog box, shows the projects running on the computer, as well as the projects available. At this point, a project can be stopped or started, a project can be added to the list of available projects. Clicking on the Startup Options tab and designate the node as a viewer. (ref section 6.6). Click OK to Exit CIMPLICITY
11.3 CIMPLICITY HMI Log files All system log files and system associated messages are logged to files residing in the C:\CIMPLICITY\HMI\LOG directrory These files include • The system status log file COR_RECSTAT.CLG • The w32rtr.out and w32rtr.err files for the Router The project’s log directory contains all the project log files. • COR_RECSTAT.CLG contains the status log • .OUT and .ERR files for all CIMPLICITY HMI processes other than user processes • .OUT_ and .ERR_ backup files for all CIMPLICITY HMI processes other than user processes. To view log files : • click on the Status Log applet in the \HMI program group double. This opens the CIMPLICITY Log Viewer. • Select the COR_RECSTAT.CLG. To view details of a particular log message, simply double click on the message and a dialog box will appear:
47
The CIMPLICITY Log Viewer screen displays the following information for each record it finds in the status log file: Date/Time Status Process Procedure Source Code Reference Message
The date and time the message was logged The type of message. This can be “Failure”, “Warning” or “Success”. The name of the process which generated the log message The name of the procedure which generated the message A symbolic name for the error class The primary value used by the software for expressing the type of error A number that can be used to determine the location of the condition that caused the error An explanation of the condition that caused the error.
Each entry in the list is preceded by a color-coded dot which corresponds to the Status field entry. The correlations are Red (Failure), Yellow (Red), Green (Success). All details of a message can be viewed by double-clicking on the message.
48
n the log folder for a project, you will also find a set of current and backup .ERR and .OUT files. These files may contain additional information if you are experiencing problems with your CIMPLICITY software. The status log files are binary files which can be viewed directly. You can however, copy the contents of a status log file to a text file that you can view with Notepad. To save the status log file as a text file, select Save as Text from the Log Menu.
Note: You can only examine backup .OUT and .ERR files while the project is running. Some of the basic CIMPLICITY filenames and their associated programs are: Filename
Associated Process
49
COM0 MAC_AM MAC_DL MAC_DYN MAC_EMRP MAC_PTDL MAC_PTDP MAC_PTM MAC_PTX MAC_UR MARKV_RP PB PCIM TCPIP
Serial device communications where is the port number Alarm Manager Data Logger Dynamic Configuration Basic Control Engine Point Data Logger Virtual Point Processor Point Manager Point Translation User Registration Mark V Process Point Bridge Genius device communications where is the port number Series 90 TCP/IP device communications where is the port number.
TCPRD Series 90 TCP/IP redundancy where is the port number. W32RTR Message Router In addition to these files, you may also find files for alarm log printers and device communication drivers. To view the contents of an .ERR or .OUT file:
• Use the Explorer to check for any non-zero length .ERR and .OUT files in the project's log directory. • Use Notepad view the contents of these files.
12.0 CIMPLICITY HMI 12.1 Signal Manager All points defined on your CIMPLICITY screens need to be defined within the CIMPLICITY Points Database. • The Project should come with all points configured. • If a point is missing then it can be “matched” and “imported” from the unitdata.dat file.
50
• It is necessary to Stop Project and Close all screens before importing (adding or deleting) points into CIMPLICITY. After importing points it is necessary to perform a CIMPLICITY project configuration update. • It is strongly recommended that only matched points be imported and not all points as this may impact system operation. For example in a system with remote viewers running on a 56K phone line, you won’t be able to run the turbine remotely unless you have only the points required by the screens. • The Signal Manager is used to, “Match” and “Import” CIMPLICITY points using the Signal Manager icon in the Project Configuration cabinet file. (The icon executes the file G:\EXEC\CSDButil.exe).
12.2 Adding a Point to the CIMPLICITY database To Add a Point from Unitdata.dat/tpl to the CIMPLICITY database • Select the Signal Manager icon in configuration cabinet • Click on File then New. Accept Defaults and click OK. • Scroll down until you get to the desired point, for example: Tn_L1START_CPB. With the pointer over Tn_L1START_CPB click once to highlight it. • From the Actions Menu choose ‘Import’. From the next pop up menu, go to C:\Site\Cimproj\SVRn.gef to choose project. Click OK • Repeat steps above steps for units T2, T3 and T4. • Close Signal Manager. • Stop the project and perform a configuration update.
12.3 Alarms Diagnostic Alarms are imported into the CIMPLICITY database using Signal Manager. The Project should come with all alarm points configured. If an alarm point is missing then it can be imported using the Signal Manager. • TCI handles Alarm Printing and not CIMPLICITY. If the Alarm Log Printer – Configuration is accessed by selecting the Alarm Printer icon in the Project Configuration, no entries will be found. • From Signal Manager, click on menu bar item ‘Actions’and select Alarms • Select F:\CimpProj\SVR1(VWR1, REM1… ).Gef
and open this file. A pop up window will show the alarms being
imported, click OK when it is complete. 12.3.1 Alarm Viewer To display alarms a stand-alone Alarm Viewer (ocx object) is embedded into a CIMPLICITY screen. Custom TCI executables are used to enhance the CIMPLICITY alarm viewer for Turbine applications. TCI provides the Silence, Lock and Unlock alarm viewer features. The procedures for Silence/Lock/Unlock buttons are usually configured such that an alarm must be selected and highlighted prior to depressing the Silence/Lock/Unlock buttons. This method allows data pertinent to the alarm (%res, %id, %ref, etc) to be passed to the Silence/Lock/Unlock command (typically used for multi-unit sites or sites with multiple servers and viewers). Required data and data format can be viewed from the command prompt (dos window) by typing SILENCE and LOCKOUT. To Edit 'Custom' Alarm Procedures, 1. The procedure can be found by right clicking on the white background of the alarm window, choosing 'CIMPLICITY AMV Control Object' and then choosing 'Properties'. 3. From the pop up window select the 'Buttons' tab, then select 'Dynamic' by choosing the Dynamic radial button. The alarm procedures and 'Custom #' procedures for a specific button can be accessed by selecting the button as follows:
51
selecting “Modify”
The correct Command String protocol for the Silence button should be silence %res (HMI%res) or the resource can be hard coded for single unit sites like this... Silence T7 Network -> Services tab • Look for Microsoft TCP\IP Printing • If it is not there add it. If it is there, skip to “Adding the printer to the HMI/Historian” • Place the Windows NT Workstation CD into the CD-ROM drive. • Click on Add • Pick Microsoft TCP\IP Printing • Click on OK • Click on Continue • Click on Close • Reboot now? Yes 14.2.2 Adding the printer to the HMI/Historian • Log into Administrator account. • Start -> Settings -> Printers • Printers Menu • Double click on Add Printer • Add Printer Wizard appears • Select My Computer • Click on Next 70
• • • • • • • • • • • • • • • • • • • •
Select Add Port Select LPR Port Click on New Port Add LPR Compatible Printer Name or address of server providing LPD: Name of printer or print queue on that server: (leave blank) Click on OK Click on Close Click on Next Find and click on Manufacturer HP Find and click on HP Color LaserJet 5 Click on Next Type in name of this printer: (use default) Do you want your Windows-based programs to use this printer as the default printer? YES Click on Next Indicate whether this printer will be shared with other network users: Not Shared Click on Next After … would you like to print a test page? YES Click on Finish Did it print your test page correctly? YES
14.2.3 Reinstall NT Service Pack 3 • Log into Administrator account. • Click on Start -> Programs -> Command Prompt • c:\> cd nt40_sp3 • c:\nt40_sp3> nt4sp3_i.exe (Do not create an uninstall directory) (After the installation, the PC will reboot.)
14.3 Printer Setup on HMI and Historian connected over Parallel Port Connection Setup, connect parallel cable, and power on the printer. Reference the printer documentation to print printer setup. 14.3.1 Adding the printer to the HMI/Historian • Log into Administrator account. • Start -> Settings -> Printers • Printers Menu • Double click on Add Printer • Add Printer Wizard appears • Select My Computer • Click on Next • Select LPTn • Click on Next • Find and click on Manufacturer HP • Find and click on printer model (e.g. HP Color LaserJet 5) • Click on Next • Type in name of this printer: (use default) • Do you want your Windows-based programs to use this printer as the default printer? YES • Click on Next • Indicate whether this printer will be shared with other network users: Not Shared • Click on Next • After … would you like to print a test page? YES • Click on Finish • Did it print your test page correctly? YES
71
15.0 Creating the IO_TEST Screens The IO_TEST screens are used to examine physical analogue and digital inputs and are invaluable during the checkout phase of the installation. 1. Create a subdirectory named IO_TEST under the Unitn directory (where n is the unit number). 2. Copy the files mkiotestscr.cim, contacts.cim, and analog.cim to the IO_TEST directory, from the product CD 3. Make sure that the CIMPLICITY project is started. 4. Create the I/O test screens by double clicking on mkiotestscr.cim. This screen runs scripts that do the following: • Create digitals.txt and analogs.txt from digital and analog input point data extracted from io.asg, located in the Unitn directory. • Insert point data from digitals.txt and analogs.txt into the screen template files contacts.ctx and analog.ctx. • Create enough screen files of the form contactsn.ctx and analogn.ctx to hold all the digital and analog points. • Convert ctx files to cim files. • Create a file, signals.csv, containing the point information for import into the CIMPLICITY point database. • Dynamically import the point information into CIMPLICITY.
5. Repeat for multiple units.
72
16.0 Modbus Configuration with HMI The Configuration description shown below has been tested with - a laptop Compaq Armada 7770DMT, with infra-red port disabled. - COM1 is used on the laptop - COM2 used on the HMI
16.1 File Config.dat (Only the lines needed for Modbus are shown) The file Config.dat is located in D:\Site The Modbus option has to be activated as follows: OPTIONS MODBUS=YES
16.2 File IO_ports.dat (Only the lines needed are shown) Located in D:\Site [MODBUS_SLAVE_PORT] port com2 baud 9600 parity 0 ;0-4 (none,odd,even,mark,space) databits 8 ;5-8 stopbits 0 ;0-2 (1, 1.5, 2 stop bits) xonxoff 0 ;0-1 port_it 40 ;Timeout interval between characters, msec. Default=40 port_tt 200 ;Timeout for total message, msec. Default=200 [MODBUS_ASSIGNMENT] SLAVE 1 UNIT T1 MODE NATIVE [MODBUS_SLAVE_TIMEOUT] modbus_timeout 4000 ;Time (milliseconds) before we give up and send nak modbus_timeout_nak 6 ;Nak code used if unit timeout occurs.
16.3 Procedure 1) The Modbus.dat (located in your unit directory) file has to contain less than 300 point names without any logic pointnames. Erase any unwanted pointname in this file. 2) Execute Modbus_L.exe in your Unitn directory (located in C:\TCI\Exec). This program creates a Modbus.LST file in your unit directory. 3) Copy Modbus.LST onto your laptop in the directory where you installed MODCOMM. Both Modbus.LST on the HMI and your laptop HAVE TO MATCH ! 4) Copy Modbus.Dat into Modbus_N.Dat 5) Stop and restart the TCI (via Start Menu ? Settings ? Control Panel ? Services) 6) Run MODCOMM on your laptop with the following configuration.
73
16.4 MODCOMM Configuration Modcomm has to be installed on your laptop. Your infra-red port has to be disabled. Baud................9600 Parity...............None DataBits........... 8 StopBits...........1 Port..................COM 1 ComLink........... Continuous Output.............. Your_Output_File_Name Connect............Direct Modbus............ Function Code...03 Slave Address...01
16.5 Troubleshooting 16.5.1 Modbus Log File A log file named Modbus.LOG is created each time TCI is started (in C:\TCI\LOG), and should look like this:
12-FEB-1999 07:56:18.210 Modbus Server Program is starting. -- Processing section header in MODBUS_SETUP_FILE: "[MODBUS_SLAVE_PORT]" PORT="COM2", BAUD = 9600, PARITY = 0, DATABITS = 8 STOPBITS = 0, XONXOFF = 0, PORT_IT = 40, PORT_TT = 200 -- Processing section header in MODBUS_SETUP_FILE: "[MODBUS_ASSIGNMENT]" SLAVE = 1, MODE = 4, UNIT = T1 -- Processing section header in MODBUS_SETUP_FILE: "[MODBUS_SLAVE_TIMEOUT]" TIMEOUT = 4000, TIMEOUT_NAK = 6 -- Processing data for slave 1. -- Timer thread started. -- Mark V data thread is ready. "COM2" serial port thread is ready.
Some errors may be related to point names that Modbus doesn’t recognize, but it shouldn’t prevent modbus from functioning. 16.5.2 Modbus Trace file When debug is on (on by default), global section trace buffer may be viewed with the command: gbl2file MModbus_trace# where # is 1,2,3...8 depending on which [MODBUS_MASTER_PORT] section corresponds to the information we want. If only one [MODBUS_MASTER_PORT] section exists, then the global section trace command could be viewed with: gbl2file MModbus_trace1 modbus1.dat This will display some debugging and program status information. The trace option may be turned off by adding /NOTRACE to the command line: MModbus /NOTRACE. If the program encounters a serious error or warning, the result is placed into a log file as well as the global section trace buffer. The user should check file
74
17.0 Remote Access Server The HMI Server is equipped with a Modem, which enables a remote PC to access the HMI Server via a dial-up Connection. Before the Modem can be used for a dial-up connection, the Remote Access Service (RAS) needs to be configured in Windows NT.
17.1 To Configure Remote Access (RAS)
1.
Click on Start, then Settings, then Control Panel.
2.
Double click on the Network Configuration icon. The Network Dialog box displays
75
3.
Select the Services tab
4.
Highlight Remote Access Service, and click on the Properties button. The Remote Access Setup dialog box displays
5.
From the Remote Access Setup dialog box, click on the Configure… button. The Configure Port Usage dialog box displays
76
6.
From the Configure Port Usage dialog box, select Dial out and Receive calls, or Receive Calls only
7.
Receive calls can be set, on only one port
8.
Click on the OK button. The Remote Access Setup dialog box displays
9.
Click on the Network … button. The Network Configuration dialog box displays
10. If dial out protocols were enabled, from the Network Configuration dialog box, in the Dial out Protocols : box, select TCP/IP 11. In the Server Settings: box, select TCP/IP and Require Microsoft encrypted authentication 12. Click on the TCP/IP Configure… button. The RAS Server TCP/IP Configuration dialog box displays 13. From the RAS Server TCP/IP Configuration dialog box, select entire network
14. Select Use static address pool : and enter 192.168.1.50 in the Begin : field and 192.168.1.60 in the End : field 15. Click the OK button. The Network Configuration dialog box displays
77
16. In the Network Configuration dialog box, click on the OK button. The Remote Access Setup dialog box displays 17. Click on the Continue button. The Network dialog box displays 18. From the Network dialog box, click the Close button. This completes the configuration 19. After the Binding update, the Network Settings Change dialog box displays 20. Click on the Yes button. The HMI Server reboots now.
17.2 Configure Administrator Privileges 1. 2. 3.
Select Start | Programs | Administrative Tools | User Mananger Double click on the A dministrator Option Click on the Dialin button
78
4. Select the Grant dialin permission to user
79
17.3 To manually start RAS using Windows Starting the Remote Access Service Once the Remote Access Service is Configured, RAS can be started 1.
Click on Start, then Programs, then Administrative Tools (Common), then Remote Access Admin.
2.
Click on Server, then Start Remote Access Server… . RAS starts
To set up RAS to start after each reboot
1.
Click on Start, then Settings, then Control Panel, then Services
80
2.
From the Services window, double click on Remote Access server
3.
Change Startup Type to be Automatic
Click on OK 4.
Reboot the computer. RAS will start after each reboot
81
18.0 Manuals and Service Packs 18.1 CIMPLICITY HMI Manuals The CIMPLICITY HMI product CD includes an electronic book reader based on Adobe® Acrobat® that lets you easily search, view, and print out any of the CIMPLICITY HMI manuals. The complete CIMPLICITY HMI library of documentation is stored on the CD. All documents have been electronically indexed which allows the book reader to quickly scan volumes of information and find the topics you are seeking. • Installation of the Book reader and documentation can be performed directly from the list of options in the CIMPLICITY HMI Setup window with a valid CIMPLICITY license. 1. 2. 3. 4. 5. 6.
Run the setup.bat file on the CIMPLCITY HMI CD. The CIMPLCITY HMI Setup window opens. Select Install Documentation Reader from the list of options in the CIMPLCITY HMI Setup window. Verify that you want to install Adobe Acrobat Reader Accept the license agreement Choose a destination location for the Adobe Acrobat Reader When the setup is complete, you have the option to review the Adobe Acrobat Reader readme file.
Hardcopy documents as a complete library are supplied with each valid CIMPLICITY license, further copies can be obtained from
[email protected] 18.2 CIMPLICIY Service Packs Updates to CIMPLICITY HMI software SHOULD ONLY BE OBTAINED FROM SALEM !!!. and should not be downloaded from the web. Caution !! Make sure you have a backup of your project before installing any updates. Information on service packs can be obtained from http://www.gefanuc.com/support/CIMPLICITY/sp303c.htm 18.3 Mark V HMI Application Manual The Mark V HMI Application can be accessed using the shortcut provided. ?????? 18.4 CIMPLICITY Upgrades CIMPLICITY upgrades are obtained through the local GE Sales Office 1. 2.
Never apply upgrades without authorization since the entire configuration may fail. TCI & Cimbridge must be upgraded at time of CIMPLICITY Upgrade (refer to compatibility table in section 8.1.1
82
19.0 List of Documentation The following documentation maybe found on the Customer CD. 1 1.1 1.2 1.3 1.5 1.6 1.7 2 3
MARK V Reference HMI for SPEEDTRONIC Turbine Controls.pdf Fiber Optics for the Stage Link.doc External Communications Link.doc HMI FAQ’s HMI Field Service handbook.pdf HMI Turbine Screen Standards CIMPLICITY BASE SYSTEM MANUAL.pdf MARK V additional files
83
20.0 Problem Report To continue providing improvements, striving toward our 6-Sigma goal, it is imperative that any new problems encountered are reported for the benefit of other field service engineers. Please take the time to complete the following report. Please be precise as to the nature of the problem and the solution. section and content of the document where problems were found Return report by email to Mark.Phelps at:
[email protected] or Brad Lewis at:
[email protected] The current FAQ problem is included in the installation CD and can also be accessed on the GE Intranet at http://vasalwpgmisge.salem.ge.com/tribal/hmi/index.htm Please check off appropriate box TCI CIMPLICITY HMI Network Configuration
Windows NT Printers
Historian
Problem Description
Problem Solution
84
21.0 HMI Installation & Checklist Table 3.1: Installation Checklist Complete
Installation Checklist 1 2 3
4
5
Connect system per A108 Configuration Topology drawing provided by Salem Power up System Install CIMPLICITY project using CD provided with Installation Manual a) Match computer name with project directory e.g. SVR1 and open directory. b) Run Setup.exe to install CIMPLICITY project. This is a self-extracting file. Check NT Usernames & Passwords. • From the Start menu select Settings/Control Panel/Network. On the Identification tab, look at the Computer Name and Workgroup entries. • All of the HMI computers are delivered with the name HMI1. Each computer must have a unique name. Names should be descriptive to the function, such as SVR1(server), VWR1(viewer), REM1, etc. On a multi-unit system names such as SVR1, SVR2, may be appropriate. • NT users (Administrator, Operator, Supervisor… ) and CIMPLICITY Users must have the same user names and same passwords, exactly. (You should verify that NT Users are Administrator, oper or maint) • To configure NT users/passwords , while logged on as Administrator Select Programs | Administrative tools | User Manager • Computer Passwords Computer Password HMI Servers Administrator gepgc oper maint maint Historian Administrator gepgc (or Administrator) User gepgc (or Administrator) Operator gepgc (or Administrator) Check CIMPLICITY Project configuration by confirming the following: f) Check CIMPLICITY Version • From Configuration Cabinet Select Help | About CfgCab g) Check CIMPLICITY Configuration • Select Project | Project Settings from the menu bar of Project Configuration Cabinet • CIMPLICITY HMI should be configured with the following project properties Project Name: Appropriate name
Reference p15
p16
p22
Ex: SVR1, VWR1 Sub Directory: Must be Cimproj (Check using Windows Explorer) Path: C:\SITE ( Check in TCI : see section 9) Options: None h) Check CIMPLICITY Protocol should be MARK V+ Communication i) Check CIMPLICITY Registration • Select Start | Programs | CIMPLICITY | HMI | Registration j) Create Desktop Shortcut • From c:\Site\Cimprog\Screens directory, right click on Unit_Control.cim and select Create Shortcut. Move shortcut to desktop. 85
and select Create Shortcut. Move shortcut to desktop.
• If you use autologin, add /waitforproject SVR1(project name) to the 6
shortcut. Check Network Configuration d) IP Address All computers come with I/P Address 192.168.1.20 Select Start | Settings | Control | Network | Protocols | TCP/IP vii. Leave one computer with this address. viii. Change the second computer to I/P Address 192.168.1.21 ix. Change the third computer to I/P Address 192.168.1.22 x. Index each subsequent computer I/P Address by a value of 1. xi. Subnet Mask should be 255.255.255.0 xii. Select DNS Entry (not normally used) e) Cable Connections iv. Check if correct cable is being used v. Network Adapter Verify driver by selecting Start | Settings | Control | Network | Adapters . Select Adapter Tab and verify adapter to be 3COM Etherlink XL Adapter or equivalent vi. Media Type Select Properties Tab under Network Adapter. Use Auto select unless there is no doubt of media type. f) Host Files Use Wordpad to edit the file C:\winNT\system32\drivers\etc\Hosts. Create entries for each of the computers in the system, according to the names and IP addresses assigned. An example of a Host File is shown below. The host file should be provided by the requisition engineer. Identical copies of this file should be on each computer. 192.168.1.20 192.168.1.21 192.168.1.22 192.168.1.23
7
8
9
SVR1 SVR2 VWR1 VWR2
p62 p24
#Local server #Remote server #Local viewer for gas turbine unit Tn #Local viewer for steam turbine unit S1
Check TCI Version • Select Start | Programs | Turbine Control Maintenance | HMI Configurtion | View TCI Version • The Version.dat file in G:\Data gives the version of TCI Site Installation Check the overall system configuration by checking the Config.dat file for the following: a) Options supplied ____________ b) Number of Units ____________ c) Unit Names ____________ d) Unit ARCNET addresses ____________ TCI Settings Check TCI Settings by selecting Start | Settings | Control Panel | TCI and the appropriate tab (4) Autologin Select Enabled
(5) Site c:\site\SVR1 Default Scale (6) TimeSync Time Acquistion Card
Select Select
p14
p37
p37
English or Metric Low Resolution 86
10
(4) ARCNET Network Type Select Stagelink or CSF Base IO Address Select Default 0x2B0 (hex) Base Memory Address Select Default 0xD0000 (hex) Interrupt Number 15 (Normally 15 unless there is more than 1 Arcnet Card) Arcnet Link Address ( set at “1F” when shipped ) TCI (Turbine Control Interface) Running Correctly g) Reboot Computer h) Check if TCI software is running. • From Dos prompt type C: net start and look for TCI Service (Message: ” TCI (Turbine Control Interface) was started successfully” i)
p40
Check for correct F:Drive substitution. • Type Subst at Dos prompt. The correct path for your project should be returned Ex: F: \: => c:\site\cimproj G:\: => c:\TCI • If path is incorrect stop TCI and enter correct path as follows C: net stop TCI C: Subst F: /D C: Subst C: F: \site\cimproj
j)
Check TCI Log File for any errors during startup Start | Programs | Turbine Control Maintenance | HMI Configuration | View TCI log k) Check Stagelink • Addresses agree with those in Config.dat • If Arcnet communication has been established C: Arcwho l) Check Signals C: View0 for each unit. to exit 11
Start CIMPLICITY Project f) Execute *.gef file ___________ The CIMPLICITY project configuration cabinet is accessed by selecting the .gef file in the F:\Cimproj directory. g) Start Project ___________ Select Run Icon (Triangle) from Configuration Cabinet. Observe CIMPLICITY processes are successfully started. h) Make Desktop shortcut for Unit_control.cim screen From F:Cimprog\Screens directory, right click on Unit_Control.cim and select Create Shortcut. Move shortcut to desktop. i) Execute Unit_Control.cim ___________
p23
j) Verify data using point control panel • View any current CIMPLICITY point value in your system
12
Select Point Control Panel from Start | Programs | CIMPLICITY | HMI menu. Select New form the File Menu in the Point Control Panel window displayed. From the Edit menu select Add to a view a point(s). From the popup window Select the desired points to be viewed. Check Alarm Printer Setup The normal procedure for configuring an alarm printer is to rename one of the
p69
87
existing printers. If a new printer needs to be created then use the printer wizard which can be accessed using the following procedure. To add a printer select Start | Settings | P rinters 13 14 15
Check Autostart Check Multi-Unit Configuration Check Remote Access Service
p62 p64 p72
22.0 Site Installation Information Complete the relevant information and E-Mail/ Fax information back to the Project Manager at SALEM. 1) Usernames and Passwords Include all HMI Servers, HMI Viewers, Historians Computer Name
Username
User Password
2) UNIT CONFIGURATION
Provide a Network Topology of the Installation. Complete the project configuration below and E-Mail it back to Salem. Unit 1
Unit 2
Unit 3
Unit 4
Unit 5
Unit 6
Unit 7
Unit 8
1. PROJECT NAME 2. Computer Workgroup 3. IP Address 4. ARCNET Address 5. TCI Version 6. CIMBridge Version 7. CIMPLICITY Version & Build 8. Microsoft NT Version 9. Ethernet Adapter Driver 10. Ethernet Node Address 11. Ethernet I/O Address 12. Ethernet media Type
88
23.0 CCS Warranty Form Comprehenive Computer Solutions COMPLAINT / WARRANTY INFORMATION FORM GEDS PRODUCT SERVICE CONTACT
CCS CONTACT
NAME: ___RAJ SEN______ PHONE: (540) 387 - 7742 FAX: (540) 387-8606
SERVICE TEAM - JEFF BRIGGS PHONE: (540) 382-4234 ex 161 FAX: (540) 382-1801
DATE RECEIVED: ____________________________ DATE TO CCS: _________________________________ DATE SHIPPED: ___________________________________
1.
Customer Name:
2:
GEDS Requisition #:
3.
GEDS Complaint # (FRN/WC/QAR if applicable):
4.
Customer Contact Name:
5. 6. 6.
Customer Contact Phone:
7.
Description and Part Number (and Serial Number if available) of Failed Component:
8.
Brief Description of Complaint:
9.
Date failed:
Serial Number and Model Number of : (available on the right side of the CPU chassis)
RETURN FAILED MATERIAL TO :
SHIP TO ADDRESS:
COMPREHENSIVE COMPUTER SOLUTIONS ATTN: SERVICE DEPT. 105 INDUSTRIAL DRIVE CHRISTIANSBURG, VA 24073
NAME:
CCS R/A #: _______________ FAILED PART: ___________________
ADDRESS:
PHONE:
89