Chp133 Bbp Ms

April 29, 2018 | Author: fahara | Category: Relay, Phase (Waves), Electrical Impedance, Ct Scan, Electronic Filter
Share Embed Donate


Short Description

reb500...

Description

Topic:

Technology and Solutions Protection and Substation Automation

Busbar Protection

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 1

Measurement System

ABB

Busbar Protection – Measurement System Objectives / Overview r r r r r r r

Introduction BBP Requirement BBP Basics Special Condition for the BBP (≠ LP, TP, GP ….) The “problem” on CT Saturation High Impedance Measurement Principle Low Impedance Measurement Principle

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 2

q

Example and Features of different Methods / Algorithms q q q q

INX-2 INX-5 REB500 REB670

r Calculation examples: Differential & Restraining Current / Differential Voltage r Open CT / Differential current Supervision r Additional Release / Tripping Criterias r Intertripping

ABB

Introduction q It is extremely important for Busbar Protection applications to have good security since an unwanted operation might have severe consequences

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 3

q The unwanted operation of the Busbar Protection will have the similar effect as simultaneous faults on all power system elements connected to the bus q On the other hand, the BBP has to be dependable as well. Failure to operate or even slow operation in case of a busbar fault can have fatal consequences. Human injuries, power system blackout, transient instability or considerable damage to the surrounding substation equipment and the close- by generators are some of the possible outcomes

ABB

Introduction q A fault on a busbar in the network is relatively seldom: Statistically once in every 20 – 30 years per switchgear q A fault on an overhead line in the network is statistically more than factor 100 higher

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 4

q The life time of busbar protection systems could be more than 30 – 40 years q According to studies all costs to integrate a BBP system will be covered in case of ONE successful trip in it’s life time q Remember: maloperating / unwanted operating as well as non operating BBP system can and have caused blackouts

ABB

BBP Requirements Number the requirements depending on the importance ___ SIMPLE OPERATION (Maintenance & Commissioning) ___ SELEKTIVITY (only the fault affected busbar is allowed to trip)

___ easily EXTENDABLE ___ SENSITIVITY

___ extensive SELFSUPERVISION

___ RELIABILITY (extensive self- supervision)

___ TRIPPING SPEED ___ STABILITY in case of external faults (even with extreme CT saturation)

___ integration of BREAKER FAILURE PROTECTION CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 5

(additional protection & monitoring functions)

___ MALOPERATION extremely unacceptable ___ matching to all switchgear CONFIGURATIONS ___ low CT REQUIREMENTS

ABB

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 6

BBP Basics

Who knows Mr. Kirchhoff ?

ABB

BBP Basics Kirchhoff’s 1st Law: Node Rule

The sum of all

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 7

currents must be zero

I1 + I2 + I3 = Σ I = 0

ABB

BBP Basics Kirchhoff’s 1st Law: Node Rule

If

I1 + I2 + I3 = Σ I

≠ CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 8

0 ⇒ Fault on the busbar ⇒ Trip circuit breaker

ABB

BBP Basics Differential current measurement

Σ I = I1 + I2 + I3 If

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 9

Σ I > differential current setting ⇒Trip Busbar Protection the measurement (system) has to be phase segregated 3 (4) measurement systems: R; S; T (& special: N)

ABB

BBP Basics External Fault ⇒ No Differential Current

I2

I1

⇒ No Trip

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 10

ΣI

ABB

BBP Basics Internal Fault

⇒ High Differential Current ⇒ Trip

I2

I1

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 11

ΣI

ABB

BBP Basics External Fault – with DC component ⇒ No Differential Current

I2

I1

⇒ No Trip

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 12

ΣI

A DC component will be superimposed if the short circuit does not occur at the voltage peak The DC component will decade with the network time constant τ=L/R

ABB

BBP Basics Internal Fault – with DC component ⇒ High Differential Current ⇒ Trip

I1

I2

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 13

ΣI

ABB

Line

Busbar Transformer

Generator Transformer

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 14

Busbar

Special Condition for the BBP (≠ LP, TP, GP ….)

Protection Zones

G BB

ABB

Special Condition for the BBP (≠ LP, TP, GP ….) All protection system (excl. BBP): The current in the current transformer (CT) due to a fault inside the protection zone is usually higher than the current in the CT due to a fault outside the protection zone. The reason for this is: • In case on a feeder fault (near the busbar) the current in the feeders CT is equal to the sum of all feeder currents connected to the busbar. • In case on a busbar fault the currents in the CTs are limited by the line or transformer reactance.

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 15

I external fault < I internal fault • Stability condition: on relatively low currents - CT saturation unlikely • Tripping condition: on extremely high currents - CT saturation very likely

ABB

Special Condition for the BBP (≠ LP, TP, GP ….) Busbar protection system: The current in the current transformer (CT) due to a fault outside the protection zone is usually higher than the current in the CT due to a fault inside the protection zone. The reason for this is: • In case on a feeder fault (near the busbar) the current in the feeders CT is equal to the sum of all feeder currents connected to the busbar. • In case on a busbar fault the currents in the CTs are limited by the line or transformer reactance.

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 16

I external fault > I internal fault • Stability condition: on extremely high currents - CT saturation very likely • Tripping condition: on relatively low currents - CT saturation unlikely

ABB

CT Saturation ⇒ the CT saturation will produce a differential current which could result in a MALOPERATION

External Fault I2

I1

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 17

ΣI

ABB

CT Saturation External Fault – with DC component ⇒ the CT saturation will produce a differential current which could result in a MALOPERATION

I2

I1

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 18

ΣI

The DC component will increase the saturation

ABB

High Impedance Measurement Principle

q The only BBP system which can handle CT saturation without any other quantity than Idiff (Σ I ) is the High Impedance Protection System.

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 19

q The High Impedance Measurement Principle uses the physical behaviour of the CT saturation to prevent (mal-) operation in case of external fault with (high) CT saturation.

ABB

High Impedance Measurement Principle Principle / Components BB 1

RL1

CT1

Im

U1

I2 I1 Idiff = Σ I

RR

UR

RL2

U2

Im

CT2

UR > 0

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 20

feeder 1 CT secondary reactance

feeder 2 High impedance (input)

Line resistance from CT to relay

ABB

High Impedance Measurement Principle CT refresher course:

U [V]

10’000

1’000

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 21

Magnetizing Curve

100 0.001

0.01

0.1

Excitation or magnetizing current

1

2

Im [A]

ABB

High Impedance Measurement Principle CT refresher course: 10’000

U [V]

Knee point voltage

1’000

(when saturation starts)

Dynamical resistant: du/di = r >

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 22

Magnetizing Curve

100 0.001

0.01

0.1

Excitation or magnetizing current

1

2

Im [A]

ABB

High Impedance Measurement Principle Internal Fault BB 1

RL1

CT1

Im

U1

I2 I1 Idiff = Σ I

RR

UR

RL2

U2

Im

CT2

UR > 0 feeder 2

Principle: CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 23

feeder 1

An internal fault will immediately result in a differential current and therefore a (high) voltage on the high impedance. The overvoltage relay which is measuring at the high impedance will pick up instantly. The pick up voltage level must be set depending on the lowest possible fault current and the maximum load.

ABB

High Impedance Measurement Principle Internal Fault BB 1

RL1

CT1

Im

U1

I2 I1 Idiff = Σ I

RR

UR

RL2

U2

Im

CT2

UR > 0

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 24

feeder 1

General setting rule: Uset ≤ Uk (since UR max = Uk)

feeder 2 RR = High Impedance (e.g. 2000Ω) UR = Voltage at the high impedance Uk = CT knee point voltage (e.g. 400V) N = CT ratio (e.g. 4000A/1A) Uset = overvoltage pick up setting

• Uset ≤ 400V

ABB

High Impedance Measurement Principle External Fault (without CT saturation) BB 1

RL1

CT1

Im

U1

I2 I1 Idiff = Σ I

RR

UR

RL2 RW U2

Im

CT2

UR > 0 feeder 2

Principle: CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 25

feeder 1

An external fault (without CT saturation) will practically produce a very low differential current and therefore “no” voltage on the high impedance. The overvoltage relay which is measuring at the high impedance will not pick up.

ABB

High Impedance Measurement Principle External Fault (with CT saturation) BB 1

RL1

CT1

Im

U1

I2 I1 Idiff = Σ I

RR

UR

RL2 RCT U2

Im

CT2

UR > 0

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 26

Principle:

feeder 1

feeder 2

In case of CT saturation the secondary reactance of the saturated CT will practically come to zero. Only the secondary resistant RCT (winding resistant) will result (du/di = r I> CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 30

t

RP

VDR

Trip

Alarm Block

There is also the possibility to insert a current instead of voltage measurement. Advantage: the Ikmin can be set directly in a current value: Ikmin = Iset * N

ABB

High Impedance Measurement Principle Features q simple, sensitive and extremely stable measurement system – CT could theoretically be saturated / pre- magnetised 100% q tripping time around one halfcycle q easily extendable, if the correct CT is available! q CT class TPS (old class X or BS) required – the TPS class defines q the knee point voltage q the magnetising current at half of the knee point voltage q the winding resistance (at 75°C)

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 31

q inexpensive protection system – expensive CTs q all CTs have to be the same type incl. ratio q no other protection devices are allowed in the same CT circuit q therefore no integration of CB Failure Protection etc. is possible

ABB

High Impedance Measurement Principle Features q in case multiple busbar configuration the current switching must be realised mechanically (risk of maloperation during switching; burned / damaged contacts / CTs !). A check zone and therefore a second CT core is strictly required (see following page) q good testing facility of the measurement system but NOT of the current switching logic (which is the sensitive / week part) q the principal is a mix of physical behaviour of the CT and numerical (or mechanical / analogue) current and voltage measurement – it is not possible to realize it 100% numerically (with a low impedance scheme)

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 32

q the possibility to record the CT currents is not given – therefore fault evaluation is not possible

The state of the art: Usually the High Impedance Protection Principle will only be installed in single busbar or 1 ½ CB configuration

ABB

High Impedance Measurement Principle Multiple Busbar with CT Switching and Check Zone I II

X I

II

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 33

X

X

Discriminating Zone

Checkzone

+

ABB

Low Impedance Measurement Principle Additional Quantity (s) to keep the Stability in case of External Fault with CT Saturation q as described in the previous slides the quantity Idiff (Σ I ) is NOT sufficient in a Low Impedance Measurement System to guarantee Stability in case of External Fault with CT Saturation q this additional quantity varies between the products and relay generations

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 34

q some examples of “clever” solutions are shown SIMPLIFIED in the following slides

ABB

Low Impedance Measurement Principle – BBP Type INX-2 – electronic relay generation

Idiff set < | ∑ I | differential current measurement with instantaneous values

Phase Comparison

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 35

phase angle supervision = current direction supervision with instantaneous values

&

t

TRIP CBs

t= integration time

Setting: - Maximum load < Ikmin < minimum short circuit current to prevent false operation in case of shorted CT and to detect lowest possible fault current

ABB

Low Impedance Measurement Principle – BBP Type INX-2

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 36

– electronic relay generation Typical INX-2 Feature: q centralised protection system, location in a centralised panel q automatic test cycle which supervises around 50 – 60 % of all HW components in the protection system and will block the system automatically in case of a HW fault q sometimes it is tricky to find faulty components since the fault indication of the automatic test is not very detailed and a lot of modules / electronic cards are available q differential current and phase comparison (phase angle) measurement system which evaluates instantaneous current values. The system includes no special CT saturation detection facility q low CT requirements: 2-3 ms of current signal must be available. This represents 5 times saturation on symmetrical fault currents (see following page) q tripping time around 12ms q integration of CB failure and End fault Protection is possible q installation from around year 1968 – 1985 q at present, the systems are still being extended (relatively seldom) q around 1200 systems are / were installed

ABB

Low Impedance Measurement Principle CT refresher course: Saturation at symmetrical current due to overburdening or to high primary current

A1

3

Ial = 1: current on which the CT starts to saturates

2 1

A2

A3

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 37

0

5 – times saturation means 5 – times Ial

-1 -2 -3

T 0

The areas

5

10ms A1 = A 2 = A 3 = ∫ i(t) • dt

10

15

are equal

t

20 ms

ABB

Low Impedance Measurement Principle – BBP Type INX-5 – static relay generation

Ikmin < | ∑ I | differential current measurement with instantaneous values

kset < |∑ I | / ∑ | I |

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 38

stabilising / restraining measurement with quantity Ires = ∑ | I | with instantaneous values

CT saturation detection CT saturation detection with instantaneous values

&

t

TRIP CBs

t= integration time

ABB

Low Impedance Measurement Principle – BBP Type INX-5 – static relay generation

Differential current Idiff= | Σ I |

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 39

Stabilised / Restraint Characteristic

k= 1 k= 0,8

in

r te

n

f al

l u a

no fault

Ikmin 0

t

Setting: - Maximum load < Ikmin < minimum short circuit current to prevent false operation in case of shorted CT and to detect lowest possible fault current - K typically to 0.8

Restraint current IRest = Σ | I |

ABB

Low Impedance Measurement Principle – BBP Type INX-5 – static relay generation

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 40

Internal Fault

ABB

Low Impedance Measurement Principle – BBP Type INX-5 – static relay generation

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 41

External Fault – without CT saturation

ABB

Low Impedance Measurement Principle – BBP Type INX-5 – static relay generation

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 42

External Fault – with CT saturation

ABB

Low Impedance Measurement Principle – BBP Type INX-5 – static relay generation External Fault –

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 43

with CT saturation

ABB

Low Impedance Measurement Principle – BBP Type INX-5 – static relay generation External Fault –

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 44

with CT saturation

ABB

Low Impedance Measurement Principle – BBP Type INX-5 – static relay generation

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 45

External Fault – with CT saturation

Depending on the saturation degree; the k – factor is reached for a longer or shorter time. Maloperation is still possible.

ABB

Low Impedance Measurement Principle – BBP Type INX-5 – static relay generation

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 46

External Fault – with CT saturation

Depending on the saturation degree; the k – factor is reached for a longer or shorter time. Maloperation is still possible.

ABB

Low Impedance Measurement Principle – BBP Type INX-5 – static relay generation

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 47

External Fault – with CT saturation

ABB

Low Impedance Measurement Principle – BBP Type INX-5 – static relay generation

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 48

Electronic circuit to generate Blocking Signals”: e.g. Negative Blocking Signal

ABB

Low Impedance Measurement Principle – BBP Type INX-5 – static relay generation External Fault – with CT saturation

POS BLOCKING SIGNAL (B+)

(B+)

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 49

Neg BLOCKING SIGNAL (B+)

(B-)

The CT saturation detection will send blocking signals: Positive CT saturation blocking signal will block the trip on negative differential current Negative CT saturation blocking signal will block the trip on positive differential current

ABB

Low Impedance Measurement Principle – BBP Type INX-5 – static relay generation External Fault – with CT saturation

pos (B+)

I diff

neg

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 50

I diff

(B-)

pos (B+)

I diff

neg I diff

(B-)

ABB

Low Impedance Measurement Principle – BBP Type INX-5 – static relay generation The CT saturation detection will send blocking signals: Positive CT saturation blocking signal will block the trip on negative differential current Negative CT saturation blocking signal will block the trip on positive differential current

Idiff pos B-

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 51

Idiff neg B+

&

t

&

t

≥1 t= integration time

TRIP CBs

ABB

Low Impedance Measurement Principle – BBP Type INX-5 – static relay generation External Fault – with CT saturation

pos (B+)

I diff

neg

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 52

I diff

(B-)

pos (B+)

I diff

neg I diff

The Stability is maintained

(B-)

ABB

Low Impedance Measurement Principle – BBP Type INX-5 – static relay generation

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 53

External Fault – with CT saturation & full DC offset

(B+)

(B+)

(B+)

(Idiff -)

(Idiff -)

(Idiff -)

(B+)

(Idiff -)

The Stability is maintained BLOCKING METHOD: tripping in case of external fault with CT saturation will be blocked till the next zero crossing is reached

ABB

Low Impedance Measurement Principle – BBP Type INX-5 – static relay generation Internal Fault – with CT saturation & full DC offset

(Idiff +)

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 54

(B+)

(Idiff +)

(B+)

(Idiff +)

(B+)

TRIP (no blocking) The CT saturation detection will send blocking signals: Positive CT saturation blocking signal will block the trip on negative differential current

ABB

Negative CT saturation blocking signal will block the trip on positive differential current

Low Impedance Measurement Principle – BBP Type INX-5

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 55

– static relay generation Typical INX-5 Feature: q centralised protection system, location in a centralised panel q automatic test cycle which supervises around 75 – 85 % of all HW components in the protection system and will block the system automatically in case of a HW fault q easy to find faulty components since the fault indication of the automatic test is very detailed and a small number of modules / electronic cards are available q restrained differential current measurement characteristic which evaluates instantaneous current values. The system includes a CT saturation detection facility: BLOCKING METHOD. A blocking time which is too long delays the tripping command in case of evolving faults (fault evolves from external to internal)

ABB

Low Impedance Measurement Principle – BBP Type INX-5 – static relay generation

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 56

Typical INX-5 Feature: q low CT requirements: 2 ms of current signal must be available. This represents 5 times saturation on symmetrical fault currents q tripping time around 12ms q integration of CB failure and End fault Protection is possible q installation from around year 1980 – 2003 q at present, the systems are still being extended frequently q around 800 systems are / were installed

ABB

Low Impedance Measurement Principle - BBP Type REB500 – numerical relay generation

First harmonic (fundamental) filtering by Fourier filter

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 57

Ikmin < | ∑ I | differential current measurement with fundamental current values

kset < |∑ I | / ∑ | I | stabilising / restraining measurement with quantity Ires = ∑ | I | with fundamental current values

&

TRIP CBs

Phase Comparison phase angle supervision = current direction supervision with fundamental current values

The REB500 BBP system will evaluate only the fundamental frequency current signal. This increases accuracy in the case of relatively small, offset differential currents

ABB

Low Impedance Measurement Principle - BBP Type REB500 – numerical relay generation Restrained differential current and phase comparison algorithms which evaluates “only” the fundamental wave of the current signal:

Primary current I1

I1

I2

I1 I1

I2

I2

I2

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 58

I2

0

t

0

t

ABB

Low Impedance Measurement Principle - BBP Type REB500 – numerical relay generation Restrained differential current and phase comparison algorithms which evaluates “only” the fundamental wave of the current signal:

Secondary current

I1

I1

I2

I1 I1

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 59

I2

I2

I2

I1

0

I2

t

0

t

ABB

Low Impedance Measurement Principle - BBP Type REB500 – numerical relay generation Restrained differential current and phase comparison algorithms which evaluates “only” the fundamental wave of the current signal:

Fundamental frequency component

I1

I1

I2

I1 I1

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 60

I2

I2

I2

I1

0

I2

t

0

t

ABB

Low Impedance Measurement Principle - BBP Type REB500 – numerical relay generation Restrained differential current and phase comparison algorithms which evaluates “only” the fundamental wave of the current signal:

I

Fundamental frequency component

Δa

0

t

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 61

Δα

The result is a huge amplitude change (Δ a) and a big phase shift (Δ α) between the two current signals which could result in a maloperation in condition of extreme CT saturation

ABB

Low Impedance Measurement Principle - BBP Type REB500 – numerical relay generation Restrained differential current and phase comparison algorithms which evaluates “only” the fundamental wave of the current signal:

Result with extreme CT saturation

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 62

I / In

50 IN

t

ms

Ires / In

Restrained differential current algorithm

ABB

Low Impedance Measurement Principle - BBP Type REB500 – numerical relay generation Restrained differential current and phase comparison algorithms which evaluates “only” the fundamental wave of the current signal:

Result with extreme CT saturation

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 63

k

I / In

50 IN

t

ms

t

Restrained differential current algorithm

ABB

Low Impedance Measurement Principle - BBP Type REB500 – numerical relay generation Restrained differential current and phase comparison algorithms which evaluates “only” the fundamental wave of the current signal:

Result with extreme CT saturation

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 64

k

I / In

Phase shift Δ α

50 IN

t

ms

t

Phase comparison algorithm

ABB

Low Impedance Measurement Principle - BBP Type REB500 – numerical relay generation

Restrained differential current and phase comparison algorithms which evaluate the fundamental wave of the reconstructed current signal:

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 65

q The REB500 system will evaluate reconstructed fundamental current values (Fourier filtered values). The system will approximate the saturated current values to it’s origin q This is realized with the from ABB patented so called “Maximum Prolongation Algorithm”. With this it can be obtained that the system is never blocked due to CT saturation: UNBLOCKING METHOD

ABB

Low Impedance Measurement Principle - BBP Type REB500 – numerical relay generation

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 66

Maximum Prolongation Algorithm

ABB

Low Impedance Measurement Principle - BBP Type REB500 – numerical relay generation Restrained differential current and phase comparison algorithms which uses the “Maximum Prolongation Algorithm” followed by the fundamental wave filter (Fourier filter) I1

I1

I2

I1 I1

I2

I2

I2

Reconstructed current signal I2

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 67

I1

0

t

0

t

ABB

Low Impedance Measurement Principle - BBP Type REB500 – numerical relay generation Restrained differential current and phase comparison algorithms which uses the “Maximum Prolongation Algorithm” followed by the fundamental wave filter (Fourier filter) I Δa

Fundamental frequency Component of the Maximum Prolongation signal

0

t

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 68

Δα

The result is a relatively small amplitude change (Δ a) and more important a very small phase shift (Δ α) between the two current signals

ABB

Low Impedance Measurement Principle - BBP Type REB500 – numerical relay generation

Result using the “Maximum Prolongation Algorithm” with extreme CT saturation

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 69

I / In

50 IN

t

ms

Ires / In

Restrained differential current algorithm

ABB

Low Impedance Measurement Principle - BBP Type REB500 – numerical relay generation

Result using the “Maximum Prolongation Algorithm” with extreme CT saturation

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 70

k

I / In

50 IN

t

ms

t

Restrained differential current algorithm

ABB

Low Impedance Measurement Principle - BBP Type REB500 – numerical relay generation

Result using the “Maximum Prolongation Algorithm” with extreme CT saturation

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 71

k

I / In

Phase shift Δ α

50 IN

t

ms

t

Phase comparison algorithm

ABB

Low Impedance Measurement Principle - BBP Type REB500 – numerical relay generation

Conclusion:

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 72

By prolonging the maximum value, the signal is compensated such that the best possible approximation of the PHASE ANGLE and AMPLITUDE of the origin primary signal is achieved

ABB

Low Impedance Measurement Principle - BBP Type REB500 – numerical relay generation

First harmonic (fundamental) filtering by Fourier filter

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 73

maximum prolongation on all CT Current signal

Ikmin < | ∑ I | differential current measurement with reconstructed fundamental current values

kset < |∑ I | / ∑ | I | stabilising / restraining measurement with quantity Ires = ∑ | I | with reconstructed fundamental current values

&

TRIP CBs

Phase Comparison phase angle supervision = current direction supervision with reconstructed fundamental current values

ABB

Low Impedance Measurement Principle - BBP Type REB500 – numerical relay generation Measurement Algorithm: Stabilized differential current

k= 1 k= 0,85 Differential current IDiff

r

F

No Fault CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 74

I

e nt

l na

lt u a

Ikmin 0

Restraint Current IRest

ABB

Low Impedance Measurement Principle - BBP Type REB500 – numerical relay generation Measurement Algorithm: Phase comparison Case 1: external fault ∆ϕ ≥ 74°

I1

I2

Im

ϕ12 =139°

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 75

Phase difference ∆ϕ

I2 Tripping area

I1

Re

180° No Fault ∆ϕ min = 74°

74° 0° Fall

Im

Internal Fault 1

I1

2

I2

Re ϕ12 =40°

Case 2: internal fault ∆ϕ < 74°

ABB

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 76

Low Impedance Measurement Principle - BBP Type REB500 – numerical relay generation Typical REB500 Feature: q decentralised protection system, location might be in a a centralised panel or distributed (e.g. in the feeder protection panels) q continuous self- supervision which supervises around 90 – 95 % of all HW components and SW tasks in the protection system and will block the system automatically in case of a HW / SW fault q very easy to find faulty components since the fault indication of the continuous self- supervision is very detailed and a very small number of modules / electronic cards are available q restrained differential current measurement (INX-5) and phase comparison (phase angle) (INX-2) algorithm which evaluates reconstructed fundamental current values (Fourier filtered values). The system will approximate the saturated current values to it’s origin with a from ABB patented (so called “maximum prolongation”) algorithm: UNBLOCKING METHOD (the system is never blocked due to CT saturation). No problem in case of evolving faults (fault evolves from external to internal)

ABB

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 77

Low Impedance Measurement Principle - BBP Type REB500 – numerical relay generation Typical REB500 Feature: q the restrained differential current measurement; phase comparison (phase angle) measurement and the maximum prolongation algorithm could be activated individually for special application q typical tripping time around 25ms q integration of CB failure and End fault Protection as well as Line & Transformer Protection Functions is possible. Additional measurement functions as event- & disturbance recorder as well as additional release functions like I> or U< are available q low CT requirements: 2 ms of current signal must be available. This represents 5 times saturation on symmetrical fault currents q state of the art: installation from year 1994 – future q over 1500 systems are in service (so far)

ABB

Low Impedance Measurement Principle - BBP Type REB670 – numerical relay generation

• Ikmin < | ∑ I | differential current measurement with RMS current values

‚sset < |∑ I | / ∑ | Iin | stabilising / restraining measurement with quantity Ires = ∑ | Iin | with RMS current values

&

TRIP CBs

ƒ external fault detection CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 78

(decision 1.2 ms after zero crossing) detection internal / external fault with instantaneous / sampled current values

ABB

Low Impedance Measurement Principle - BBP Type REB670

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 79

– numerical relay generation Representation of the protection zone:

ABB

Low Impedance Measurement Principle - BBP Type REB670 – numerical relay generation Calculation of the instantaneous value of the differential current:

Calculation of the instantaneous sum of positive currents:

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 80

Calculation of the instantaneous sum of negative currents:

ABB

Low Impedance Measurement Principle - BBP Type REB670 – numerical relay generation Calculation of the incoming and outgoing currents:

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 81

Calculation of the RMS value of e.g. Iin (same for Iout and Idiff)

ABB

Low Impedance Measurement Principle - BBP Type REB670

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 82

– numerical relay generation Condition at Internal Fault:

ABB

Low Impedance Measurement Principle - BBP Type REB670

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 83

– numerical relay generation Condition at Internal Fault:

sudden split between of RMS Iin and RMS Iout will indicate an internal fault if • & ‚ (Ikmin & s) is fulfilled the protection will trip since ƒ will not see an external fault

ABB

Low Impedance Measurement Principle - BBP Type REB670

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 84

– numerical relay generation Condition at External Fault with CT Saturation:

ABB

Low Impedance Measurement Principle - BBP Type REB670

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 85

– numerical relay generation Condition at External Fault with CT Saturation:

ƒ will detect an external fault within 1.2ms after the Iin zero crossing (before the CT gets into saturation) and will block till the next zero crossing is reached

ABB

Low Impedance Measurement Principle - BBP Type REB670 – numerical relay generation

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 86

Test assembly:

ABB

Low Impedance Measurement Principle - BBP Type REB670 – numerical relay generation

Test values & result: The CT TX war pre- magnetised with a DC current in order to get maximum remanence. Therefore the CT saturates within 1.2 ms!

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 87

The primary test current level was 26kA RMS with the full DC offset

The BBP system REB670 remains fully stable !!!

ABB

Low Impedance Measurement Principle - BBP Type REB670 – numerical relay generation

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 88

Stabilised / Restraint Characteristic

ABB

Low Impedance Measurement Principle - BBP Type REB670 – numerical relay generation Stabilised / Restraint Characteristic Setting: - Maximum load < Ikmin (Diff Oper Level) < minimum short circuit current to prevent false operation in case of shorted CT and to detect lowest possible fault current

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 89

The sensitive (non restraint) operational level is designed to be able to detect internal busbar faults in low impedance earthed power systems: Limited earth fault current to certain level (300 – 2000A)

ABB

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 90

Low Impedance Measurement Principle - BBP Type REB670 – numerical relay generation Typical REB670 Feature: q centralised protection system, location in a centralised panel q continuous self- supervision which supervises the most of the HW components and SW tasks in the protection system and will block the system automatically in case of a HW / SW fault q very easy to find faulty components since a very small number of modules / electronic cards are available q restrained differential current measurement algorithm which evaluates RMS current values. The system can decides within 1.2ms after the zero crossing of the current if the fault is external or internal. In case of external fault the measurement will be blocked till the next zero crossing: BLOCKING METHOD. A blocking time which is too long delays the tripping command in case of evolving faults (fault evolves from external to internal)

ABB

Low Impedance Measurement Principle - BBP Type REB670 – numerical relay generation

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 91

Typical REB670 Feature: q very low (“almost no”) CT requirements: the system was successfully tested with just 1.2 ms of current signal. This represents >> 5 times saturation on symmetrical fault currents q tripping time around one halfcycle q integration of CB Failure, OC protection as well as event- & disturbance recorder, monitoring function is possible q state of the art: installation from year 2005 – future q the system is a consequently further development / improvement of the well proven BBP systems RADSS, REB103, RED521

ABB

Internal fault condition

Calculation examples

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 92

Busbar fault condition single injection

I1 = 1000A

ABB

Internal fault condition

Calculation examples

Low Impedance Low Impedance Measurement System Measurement System REB500

REB670

High Impedance System (with CT ratio: N = 2000A / 1A; Impedance: RR = 2000 Ω; Knee Point V: UK = 400V)

∆ I = + I1

CHP133_BBP_MS / 200709 / RW

∆ Isec = I1/N

= + 1 kA

= + 1 kA

= 1 kA / 2000

= 1 kA

= 1 kA

= 0.5 A

Σ I = + + I1 © ABB Switzerland Ltd. - 93

∆ I = + I1

Σ Iin = + + I1

∆ U = ∆ Isec * RR

= + 1 kA

= + 1 kA

= 0.5A * 2000Ω

= 1 kA

= 1 kA

= 1 kV (spike) à TRIP

ABB

Internal fault condition

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 94

Differential current Idiff= | Σ I |

Calculation examples

k= 1

I

e nt

r

l na

f al n ter In

Ikmin 0

f

R lt u a

lt au

EB

0 50

70 6 B RE

kREB500= 0,85 kREB670= 0,53

no fault Restraint current IRest = Σ | I | Restraint current IRest = Σ | Iin |

►trip measurement system !!! ⇒ ( if I∆ > Ikmin)

ABB

Internal fault condition

Calculation examples

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 95

Busbar fault condition

multiple injection

I1 = 1000A

I2 = 2500A

I3 = 1500A

I4 = 2000A

ABB

Internal fault condition

Calculation examples

Low Impedance Low Impedance Measurement System Measurement System REB500

REB670

High Impedance System (with CT ratio: N = 2000A / 1A; Impedance: RR = 2000 Ω; Knee Point V: UK = 400V)

∆ I = + I1 + I2 + I3 + I4 = + 1 kA + 2.5 kA + 1.5 kA + 2 kA

= + 1 kA + 2.5 kA + 1.5 kA + 2 kA

= 7 kA

= 7 kA

CHP133_BBP_MS / 200709 / RW

Σ I = ++ I1++ I2+ + I3+ + I4 © ABB Switzerland Ltd. - 96

∆ I = + I1 + I2 + I3 + I4

Σ Iin = ++ I1++ I2+ + I3++ I4

= + 1 kA + 2.5 kA + 1.5 kA + 2 kA

= + 1 kA + 2.5 kA + 1.5 kA + 2 kA

= 7 kA

= 7 kA

∆ Isec = I1/N = 7 kA / 2000 = 3.5 A

∆ U = ∆ Isec * RR = 3.5A * 2000Ω = 7 kV (spike) à TRIP

ABB

Internal fault condition

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 97

Differential current Idiff= | Σ I |

Calculation examples

load depending tripping value!!! k= 1

I

e nt

r

l na

f al n ter In

Ikmin 0

f

R lt u a

lt au

EB

0 50

70 6 B RE

kREB500= 0,85 kREB670= 0,53

no fault Restraint current IRest = Σ | I | Restraint current IRest = Σ | Iin |

►trip measurement system !!! ⇒ ( if I∆ > Ikmin)

ABB

External fault condition

Calculation examples e.g. line fault

I1 =

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 98

6000A

I2 =

I3 =

2500A

1500A

I4 = 2000A

ABB

External fault condition

Calculation examples

Low Impedance Low Impedance Measurement System Measurement System REB500

REB670

High Impedance System (with CT ratio: N = 2000A / 1A; Impedance: RR = 2000 Ω; Knee Point V: UK = 400V)

∆ I = + I1 + I2 + I3 + I4

= - 6 kA + 2.5 kA + 1.5 kA + 2 kA

= - 6 kA + 2.5 kA + 1.5 kA + 2 kA

= 0 kA

= 0 kA

Σ I = ++ I1++ I2+ +I3++ I4 CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 99

∆ I = + I1 + I2 + I3 + I4

Σ Iin = + I2+ +I3++ I4

= + 6 kA + 2.5 kA + 1.5 kA + 2 kA

= 2.5 kA + 1.5 kA + 2 kA

= 12 kA

= 6 kA

∆ Isec = I1/N = 0 kA / 2000 =0A

∆ U = ∆ Isec * RR = 0A * 2000Ω = 0 kV à NO TRIP

ABB

External fault condition

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 100

Differential current Idiff= | Σ I |

Calculation examples

k= 1

I

e nt

r

l na

f al n ter In

Ikmin 0

f

R lt u a

lt au

EB

0 50

70 6 B RE

kREB500= 0,85 kREB670= 0,53

no fault Restraint current IRest = Σ | I | Restraint current IRest = Σ | Iin |

►no trip ►stable !!!

ABB

Current transformer failure (Ι)

Calculation examples

during fault condition (Ι)

I1 =

CT shorted !!!

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 101

6000A

I2 =

I3 =

2500A

1500A

I4 = 2000A

ABB

Current transformer failure (Ι)

Calculation examples

Low Impedance Low Impedance Measurement System Measurement System REB500

REB670

High Impedance System (with CT ratio: N = 2000A / 1A; Impedance: RR = 2000 Ω; Knee Point V: UK = 400V)

∆ I = + I1 + I2 + I3 + I4

= - 6 kA + 2.5 kA + 1.5 kA + 0 kA

= - 6 kA + 2.5 kA + 1.5 kA + 0 kA

= 2 kA

= 2 kA

Σ I = + + I1+ + I2 + + I3 + + I4 CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 102

∆ I = + I1 + I2 + I3 + I4

= + 6 kA + 2.5 kA + 1.5 kA + 0 kA = 10 kA

Σ Iin = + + I1

∆ Isec= I1/N = 2 kA / 2000 =1A

∆ U = ∆ Isec * RR

= + 6 kA

= 1A * 2000Ω

= 6 kA

= 2 kV (spike) à TRIP !!!

ABB

Current transformer failure (Ι)

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 103

Differential current Idiff= | Σ I |

Calculation examples

k= 1

I

e nt

r

l na

f al n ter In

Ikmin 0

f

R lt u a

lt au

EB

0 50

70 6 B RE

kREB500= 0,85 kREB670= 0,53

no fault Restraint current IRest = Σ | I | Restraint current IRest = Σ | Iin |

REB500: no trip ►stable REB670: no trip ►stable

ABB

Current transformer failure (ΙΙ)

Calculation examples

during fault condition (ΙΙ)

CT shorted !!! I1 =

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 104

6000A

I2 =

I3 =

2500A

1500A

I4 = 2000A

ABB

Current transformer failure (ΙΙ)

Calculation examples

Low Impedance Low Impedance Measurement System Measurement System REB500

REB670

High Impedance System (with CT ratio: N = 2000A / 1A; Impedance: RR = 2000 Ω; Knee Point V: UK = 400V)

∆ I = + I1 + I2 + I3 + I4

= + 0 kA + 2.5 kA + 1.5 kA + 2 kA

= + 0 kA + 2.5 kA + 1.5 kA + 2 kA

= 6 kA

= 6 kA

Σ I = + + I1+ + I2 + + I3 + + I4 CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 105

∆ I = + I1 + I2 + I3 + I4

Σ Iin = + + I2 + + I3 + + I4

= + 0 kA + 2.5 kA + 1.5 kA + 2 kA

= + 2.5 kA + 1.5 kA + 2 kA

= 6 kA

= 6 kA

∆ Isec= I1/N = 6 kA / 2000 =3A

∆ U = ∆ Isec * RR = 3A * 2000Ω = 6 kV (spike) à TRIP !!!

ABB

Current transformer failure (ΙΙ)

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 106

Differential current Idiff= | Σ I |

Calculation examples

k= 1

I

e nt

r

l na

f al n ter In

Ikmin 0

f

R lt u a

lt au

EB

0 50

70 6 B RE

kREB500= 0,85 kREB670= 0,53

no fault Restraint current IRest = Σ | I | Restraint current IRest = Σ | Iin |

⇒ trip measurement system !!! (worst case condition)

ABB

Current transformer failure (ΙΙΙ)

Calculation examples

during load condition

CT shorted !!! I1 =

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 107

600A

I2 =

I3 =

250A

150A

I4 = 200A

ABB

Current transformer failure (ΙΙΙ)

Calculation examples

Low Impedance Low Impedance Measurement System Measurement System REB500

REB670

High Impedance System (with CT ratio: N = 2000A / 1A; Impedance: RR = 2000 Ω; Knee Point V: UK = 400V)

∆ I = + I1 + I2 + I3 + I4

= + 0 kA + 250 A + 150 A + 200 A

= + 0 kA + 250 A + 150 A + 200 A

= 600 A

= 600 A

Σ l = + + I1+ + I2 + + I3 + + I4 CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 108

∆ I = + I1 + I2 + I3 + I4

Σ Iin = + + I1+ + I2 + + I3 + + I4

= + 0 kA + 250 A + 150 A + 200 A

= + 250 A + 150 A + 200 A

= 600 A

= 600 A

∆ Isec = I1/N = 0.6 kA / 2000 = 1.2 A

∆ U = ∆ Isec * RR = 1.2A * 2000Ω = 2.4kV (spike) à possible TRIP !!!

ABB

Current transformer failure (ΙΙΙ)

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 109

Differential current Idiff= | Σ I |

Calculation examples

k= 1

I

e nt

r

l na

f al n ter In

Ikmin 0

f

R lt u a

lt au

EB

0 50

70 6 B RE

kREB500= 0,85 kREB670= 0,53

no fault Restraint current IRest = Σ | I | Restraint current IRest = Σ | Iin |

⇒ measurement system stable !!! ⇒ differential current alarm !!!

ABB

Open CT / Differential Current Alarm With a Differential Current Supervision it is possible to detect open / missing CTs during load condition The Differential Current Supervision sends a TIME DELAYED ALARM and there is a setting option to BLOCK the Protection system zone selectively (REB670: also Phase selectively)

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 110

The Supervision is able to detect q a missing CT input (e.g. CT circuit not connected to the system) q a wrong CT ratio q a wrong current direction Therefore the PICK UP VALUE of the Differential Current Supervision should be set lower than the lowest possible load current. The time delay 2–5 seconds)

ABB

Open CT / Differential Current Alarm

⇒ the “differential current / Open CT alarm” is able to detect a missing / wrong CT input ⇒ therefore the “differential current alarm” is very important and must not be ignored by the operating personal

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 111

If not, there is a risk of maloperation !!!

ABB

Additional Tripping / Release Criterias

Additional Tripping / Release Criterias are used to get q Additional SECURITY or

The usage is depending on the CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 112

q Additional FAULT LOCATION

CUSTOMERS PHILISOPIE

ABB

Additional Tripping / Release Criterias Measurement System

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 113

Release for SECURITY

& ≥1

TRIP CBs

Tripping for FAULT LOCATION

ABB

Additional Tripping / Release Criterias Measurement System

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 114

Release for SECURITY

& ≥1

TRIP CBs

Neutral Differential Current Measurement

ABB

Additional Tripping / Release Criterias Neutral Differential Current Measurement is designed to be able to detect internal busbar faults in low impedance earthed power systems: Limited earth fault current to certain level (300 – 2000A)

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 115

No Trip for Phase Differential Measurement !!!

ABB

Additional Tripping / Release Criterias Neutral Differential Current Measurement

Δ I = │∑IN │ IRest = ∑│IN │ (IN = Neutral Current)

K = │∑IN │ / ∑│IN │ = IK / IK = 1 CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 116

and therefore:

►TRIP

ABB

Additional Tripping / Release Criterias Measurement System

Check

&

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 117

Zone

≥1

TRIP CBs

Neutral Differential Current Measurement

ABB

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 118

Additional Tripping / Release Criterias Check Zone

ABB

Additional Tripping / Release Criterias

Differential current Idiff= | Σ I |

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 119

Check Zone

k= 1

I

e nt

rn

f al

a

tR l u

EB

50

0

fault

k Ikmin 0

no fault

Restraint current IRest = Σ | I |

ABB

Additional Tripping / Release Criterias Check Zone q The stability factor k must be calculated very carefully !

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 120

q The Phase Comparison Algorithm is not used in the REB500 system

ABB

Additional Tripping / Release Criterias Measurement System

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 121

Over Current

& ≥1

TRIP CBs

Neutral Differential Current Measurement

ABB

Additional Tripping / Release Criterias Over Current Release

Only that feeders on which a settable over current value is reached will be tripped in case of a trip of the busbar protection I>

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 122

I>

I>

I>

I1 =

I2 =

I3 =

I4 =

300A

250A

50A

100A

ABB

Additional Tripping / Release Criterias Over Current Release

Only that feeders on which a settable over current value is reached will be tripped in case of a trip of the busbar protection I>

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 123

I>

I1 = 1000A

I>

I2 = 2500A

I>

I3 = 1500A

I4 = 2000A

ABB

Additional Tripping / Release Criterias Measurement System

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 124

U< Under Voltage

& ≥1

TRIP CBs

Neutral Differential Current Measurement

ABB

Additional Tripping / Release Criterias Under Voltage Release

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 125

The busbar zone which should be tripped must fulfil a settable under voltage value U

U

U

U

ABB

Additional Tripping / Release Criterias Under Voltage Release

CHP133_BBP_MS / 200709 / RW

© ABB Switzerland Ltd. - 126

The busbar zone which should be tripped must fulfil a settable under voltage value U

View more...

Comments

Copyright ©2017 KUPDF Inc.
SUPPORT KUPDF