January 29, 2017 | Author: Hasir Chelat | Category: N/A
The PG&E Pacific Energy Center Presents:
Optimizing the Design and Control of Chilled Water Plants
Presented by:
Mark Hydeman Steve Taylor
Taylor Engineering LLC Alameda, CA http://www.taylor-engineering.com
April 3, 2014
Logistics Safety Restrooms Recycling Cell phone etiquette Lunch Review forms Webinar etiquette PG&E Resources
• • •
Rebates Tool Lending Library Marlene Vogelsang (
[email protected]) 2
Handouts You can get a copy of the handouts in PDF format as follows:
• Type the following link into your web browser: http://www.taylorengineering.com/ftp/PECClassHandouts.html
• Click on the link for the Chilled Water Plant Class on 4/3/2014 to download the Acrobat file of the presentation.
3
About Mark Hydeman Founding Principal, Taylor Engineering Education
• •
Stanford University, BS General Engineering, 1982 Stanford University, MS Mechanical Engineering, 1983
ASHRAE
• • • • • • • •
Fellow Exceptional Service Award Standard 90.1 Energy Standard, two tours of duty, Vice-Chair Technical Committee 1.5, Computer Applications, Past Chair Technical Committee 9.9, Mission Critical Facilities Technical Committee 9.10, Laboratory Systems Electronic Communications Committee, Vice-Chair SPC 205, Vice Chair
Research
• • • • • •
Developed a simulation and assessment toolkit for data centers with LBNL Principal Investigator for NBI PIER project on Large HVAC System design Principal Investigator for ASHRAE RP 1455, Best of Class Control Sequences Developer of the Universal Translator Principal Investigator for the CoolTools™ Market Transformation Project PMSC Lead for ASHRAE Research on Humidity Control for Data Centers and Alternate Gas for Hood Testing (ASHRAE 110)
Other • Lead author of Title 24 HVAC compliance and acceptance requirements • Design and commissioning experience on dozens of chilled water plants
4
About Steve Taylor Principal, Taylor Engineering Education
• •
Stanford University, BS Physics, 1976 Stanford University, MS Mechanical Engineering, 1977
ASHRAE
• • • • • • • • • •
Fellow Standard 62 Indoor Air Quality, 8 years, chair Standard 90.1 Energy Standard, Chair HVAC Subc., 14 years Standard 55 Thermal Comfort Guideline 16 Economizer Dampers, chair Guideline 13 Specifying Direct Digital Control Systems, chair TC 4.3 Ventilation, vice-chair TC 1.4 Control Theory & Applications, chair Author “Fundamentals of Design and Control of Central Chilled Water Plants” Course Distinguished Lecturer
USGBC LEED
•
Indoor Environmental Quality TAG, vice chair
UMC/IAPMO (California Mechanical Code)
•
Mechanical Technical Committee, member and ASHRAE Liaison
CSU
•
Mechanical Review Board, member 5
Who are You? Consulting Engineers? Design/Build Engineers? Contractors? Energy/Green Building Consultants? Building Owners/Engineers? Equipment rep/supplier/manufacturer? Commissioning authority? Other? 6
Agenda Introduction CHW Distribution Systems Break CHW Distribution System Balancing CW Distribution Systems Lunch Selecting CHW Distribution Systems Selecting CHW ∆T Selecting CW ∆T Selecting Chillers Optimizing control sequences Questions Completion
9:00 AM 9:15 AM 10:45 AM 11:00 AM 11:45 AM 12:00 PM 1:00 PM 1:30 PM 2:00 PM 2:30 PM 3:00 PM 4:15 PM 4:30 PM
7
Articles (1 of 2) Available at this URL: http://www.taylor-engineering.com/publications/articles.shtml
8
Articles (2 of 2) Available at this URL: http://www.taylor-engineering.com/publications/articles.shtml
9
Design Guide and Tools Available at this URL: http://www.taylor-engineering.com/publications/design_guides.shtml
10
Design Guide Scope New Construction
• • • • •
Hydronic design Chiller selection Cooling tower selection Control optimizations Commissioning
Retrofit
• • • •
Replacement chillers Addition of VSDs Control optimization Commissioning
11
Optimizing Energy Usage Chillers
•
Type, efficiency, size, VSD
Cooling Towers
•
Fan type, efficiency, approach, range, speed control, flow turndown
Chilled Water Pumps
•
Arrangement, flow rate (delta-T), pressure drop, VSD
Condenser Water Pumps
•
Flow rate (delta-T), pressure drop
Air Handling Units
•
Coil sizing, air-side pressure drop, water-side pressure drop
12
Pop Quiz 1 What happens to component energy usage if we lower CWS setpoint?
• Chiller • Towers • Pumps
Pop Quiz 2 What happens to component energy usage if we lower CW flow?
• Chiller • Towers • Pumps
Pop Quiz 3 What happens to component energy usage if we lower CW flow AND the CWS setpoint?
• Chiller • Towers • Pumps
Optimizing CHW Plant Design Ideal: Design a plant with lowest life cycle costs (first cost plus lifelong operating costs) accounting for all the complexities and interaction among plant components Practical: Design plant subsystems to be near-life cycle cost optimum using techniques that are simple and practical enough to be used without a significant increase in design time
16
Chilled Water Distribution Systems
17
Water Distribution System Classes Constant Flow
• •
No control valves 3-way control valves
Variable Flow
• • • •
Primary-Only Primary/Secondary (/Tertiary) Primary/Distributed Secondary Primary/Variable Speed Coil Secondary
18
Constant Flow Single Chiller, Single Coil, No Control Valve SUPPLY WATER TEMPERATURE CHW PUMP CHILLER
SUPPLY AIR TEMPERATURE OPTIONAL STORAGE TANK COIL
Works also for boilers that have modulating burners and very good turndown, e.g. ≥10 to 1
19
Constant Flow Two Chillers, Single Coil, No Control Valve SUPPLY WATER TEMPERATURE
CHW PUMP CHILLER #2
CHILLER#1
VFD
SUPPLY AIR TEMPERATURE OPTIONAL STORAGE TANK COIL
20
“Constant” Flow 3-Way Valves
3-Way Mixing Valve
∆P
Bypass Balance Valve
Item
Pressure at constant flow Flow at constant Pressure (20’)
Pressure Drop @ 100 GPM 100% to Coil 50% to Coil 0% to Coil
Pipe/Valves Coil and/or Bypass Globe Control Valve Total GPM @ 20’ ∆P*
2 8 10 20
2 2 7.5 11.5
2 6 12 20
100
132
100
*actual ∆P available may change 21
Constant Flow Single Chiller, Multiple Coils CHW PUMP CHILLER
3-WAY VALVES COIL
22
Partially Variable Flow Single Chiller, Multiple Coils SUPPLY WATER TEMPERATURE
CHW PUMP CHILLER
Where to locate 3-way valves?
VFD
COIL 2-WAY VALVE
At the very end: • Engages mass to reduce cycling • More constant pressure so flow is more constant • Still self-balancing Close to pump: • Lower pump energy
DP SENSOR
3-way valves sized for minimum chiller flow
3-WAY VALVE
23
Constant Flow Multiple Parallel Chillers, Multiple Coils SUPPLY WATER TEMPERATURE CHILLER CH1 240 #1 gpm CHW PUMPS
How many chillers do we need to run?
CHILLER CH2 240#2 gpm
COIL
Ballroom A 240 gpm 3-WAY VALVE
Ballroom B 240 gpm
Ballroom A 240 gpm 100% Loaded
Ballroom B 0 gpm Unoccupied 24
Variable Flow Vary Flow Through Coil Circuit
• Two-way valves • Variable speed coil pump Configurations
• Primary-secondary • Primary-secondary variations • Primary-only
25
Variable Flow Chilled Water Systems Old Paradigm
• Controls respond to changes in CHW • •
temperature Variable flow causes low temperature trips, locks out chiller, requires manual reset (may even freeze) Hence: Maintain constant flow through chillers
26
Primary/Secondary
27
Primary/Secondary 100 gpm ON
100 gpm
ON
100 gpm
0 gpm OFF
ON
100 gpm
100 gpm 28
Variable Flow Primary/Secondary, Multiple Chillers and Coils
CHILLER #1 PRIMARY PUMPS CHILLER #2
COMMON LEG (DECOUPLER)
VFD
VFD
SECONDARY PUMPS
COIL 2-WAY VALVE DP SENSOR
29
Variable Flow Primary/Secondary, Series Flow, Multiple Chillers
30
Variable Flow Primary/Distributed Secondary
31
Variable Flow Primary/Secondary/Tertiary
32
Variable Flow Chilled Water Systems New Paradigm
• Modern controls are robust and very •
responsive to both flow and temperature variations Variable flow OK within range and rate-ofchange spec’d by chiller manufacturer
33
Variable Flow Primary-only, Multiple Chillers PRIMARY PUMPS CHILLER #1 VFD
CHILLER #2 VFD
FLOW METER BYPASS
COIL 2-WAY VALVE DP SENSOR
34
Variable Flow Primary, Bypass Valve
Location • Near chillers Best for energy Controls less expensive Control more difficult to tune – fast response
•
Remote Smaller pressure fluctuations (easier to control) Keeps loop cold for fast response Less likely to unequally load chillers
Sizing • Sizing critical when at
•
chillers/pumps Different size if pump has VFD or not
Flow measurement • Flow meter Most accurate Needed for Btu calc for staging
•
DP across chiller Less expensive Accuracy reduced as tubes foul One required for each chiller 35
Primary CHW Pump Options
Dedicated Pumping Advantages: • Less control complexity • Custom pump heads w/ unmatched chillers • Usually less expensive if each pump is adjacent to chiller served • Pump failure during operation does not cause multiple chiller trips
Headered Pumping Advantages: • Better redundancy • Valves can “soft load” chillers with primaryonly systems • Easier to incorporate stand-by pump 36
Balancing Variable Flow Systems See “Balancing Variable Flow Hydronic Systems” ASHRAE Journal Oct 2002
37
Variable Flow Balancing Issues Ensure “adequate” flow available at all coils to meet loads
•
Less than design flow may be “adequate” most of the time
Ensure differential pressure across control valves is not so high as to cause erratic control
• •
“Two-positioning” Unstable control at low loads
Cost considerations
• • •
First costs (installed costs and start-up costs) Pump energy costs (peak demand and annual) Rebalancing costs (if any) as coils are added to system
Reference
•
“Balancing Variable Flow Hydronic Systems,” Steve Taylor and Jeff Stein, October 2002, ASHRAE Journal 38
Variable Flow Balancing Options No balancing
1.
•
Relying on 2-way control valves to automatically provide balancing
Manual balance
2.
• •
Using ball or butterfly valves and coil pressure drop Using calibrated balancing valves (CBVs)
Automatic flow limiting valves (AFLVs) Reverse-return Oversized main piping Undersized branch piping Undersized control valves Pressure independent control valves
3. 4. 5. 6. 7. 8.
•
Not studied in our ASHRAE paper 39
Piping Systems Analysis Heating system
• • • •
540 gpm 400 VAV reheat coils Constant speed pumps Based on actual building in Oakland
Cooling system
• • •
1,200 gpm 20 Floor-by-floor AHUs Variable speed pumps
All valves: 2-way modulating Analyzed using Pipe-Flo 40
HW Piping Floor Plan
41
Typical Coil Piping
Options 1, 4, 5, 6, & 7
Option 2
42
Typical Coil Piping Option 3
Option 8
43
Option 1: No Balancing Advantages
• •
No balancing labor Coils may be added/subtracted without rebalance
Disadvantages
• •
Imbalance during transients or if setpoints are improper Control valves near pumps can be overpressurized, reducing controllability
44
Option 2: Manual w/CBVs Advantages • •
Valves can be used for future diagnosis (flow can be measured) Reduced overpressurization of control valves at low flow
Disadvantages • Added cost of calibrated • • • • •
balancing valve Higher balancing cost Complete rebalance may be required if coils added/subtracted Slightly higher pump head due to balancing valve Coils may be starved if variable speed drives are used without DP reset Slightly higher pump energy depending on flow variations and pump controls
45
Starved Loads with CBVs and Fixed DP Setpoint: Design Condition 70
PRESSURE PSIG
60 50 40
45 PSID
38 PSID
12 PSID
30 20 10 0 PUMP
CLOSE LOAD
REMOTE LOAD
VFD
Load
Load
100 GPM 5 PSID
100 GPM 5 PSID
DP 5 PSID
5 PSID
28 PSID, Cv=19
2 PSID
46
Starved Loads with CBVs and Fixed DP Setpoint: No Remote Flow Condition 70
PRESSURE PSIG
60 50 40 19 PSID
12 PSID
12 PSID
30 20 10 0 PUMP
REMOTE LOAD
Load
Load
VFD
CLOSE LOAD
56 GPM 1.6 PSID
0 GPM 0 PSID
DP 1.6 PSID
12 PSID
8.8 PSID
0 PSID
47
Option 3: Automatic Flow Limiting Valves Advantages • No balancing labor • Coils may be added/subtracted without rebalance
Disadvantages • Added cost of strainer and • • • • •
flow limiting valve Cost of labor to clean strainer at start-up Higher pump head and energy due to strainer and flow limiting valve Valves have custom flow rates and must be installed in correct location Valves can clog or springs can fail over time Control valves near pumps can be overpressurized, reducing controllability 48
Option 4: Reverse-return
49
Reverse Return Configurations
C/C
H/C
H/C
C/C
H/C
H/C
H/C
H/C
C/C
C/C
Reverse return riser (elevation)
Reverse return on floor (plan) 50
Option 4: Reverse-return Advantages • No balancing labor • Coils may be • •
added/subtracted without rebalance No significant overpressurization of control valves close to pumps. Usually lower pump head due to reverse-return piping having lower pressure drop than mains (due to larger pipe)
Disadvantages • Added cost of reverse•
return piping Not always practical depending on physical layout of system
51
Option 5: Oversized Main Piping C/C
C/C 2”
2”
3” C/C
C/C 4”
4” C/C
C/C 6”
6”
C/C
C/C 3”
6”
6”
Standard main design
6”
6”
Oversized main riser
52
Option 5: Oversized Main Piping Advantages • No balancing labor • Coils may be • • •
added/subtracted without rebalance Reduced overpressurization of control valves close to pumps Lowest pump head/energy due to oversized piping, no balance valves Increased flexibility to add loads due to oversized piping
Disadvantages • Added cost of larger piping
53
Option 6: Undersized Branch Piping Advantages • No balancing labor • Reduced cost of smaller • •
piping Coils may be added/subtracted without rebalance Reduced overpressurization of control valves close to pumps where piping has been undersized
Disadvantages • Limited effectiveness and • • • •
applicability due to limited available pipe sizes High design and analysis cost to determine correct pipe sizing Reduced flexibility to add coils where piping has been undersized Coils may be starved if variable speed drives are used without DP reset Slightly higher pump energy depending on flow variations and pump controls 54
Option 7: Undersized Control Valves Advantages • No balancing labor • Reduced cost of smaller • •
•
control valves Coils may be added/subtracted without rebalance Reduced overpressurization of control valves close to pumps where control valves have been undersized Improved valve authority which could improve controllability where control valves have been undersized
Disadvantages • Limited effectiveness and • • •
applicability due to limited available control valve sizes (Cv) High design and analysis cost to determine correct control valve sizing Coils may be starved if variable speed drives are without DP reset Slightly higher pump energy depending on flow variations and pump controls
55
Option 8: Pressure Independent Control Valves Advantages • No balancing labor • Coils may be • • • •
added/subtracted without rebalance No over-pressurization of control valves close to pumps Easy valve selection – flow only not Cv Perfect valve authority will improve controllability Less actuator travel and start/stop may improve actuator longevity
Disadvantages • Added cost of strainer and • • • •
pressure independent control valve Cost of labor to clean strainer at start-up Higher pump head and energy due to strainer and pressure independent control valve Valves have custom flow rates and must be installed in correct location Valves can clog or springs can fail over time
56
PICVs May Improve ∆T?
NBCIP Test Lab (as reported by manufacturer) 57
Controllability & Transients Balancing Method
Maximum pressure drop of control valve required for design flow, feet CHW
1
No balancing
2
Manual balance using calibrated balancing valves
3
Automatic flow limiting valves
4
HW
Percent of design flow (percent of design coil sensible capacity) with all control valves 100% open Maximum flow through closest coil CHW
HW
Minimum flow through most remote coil CHW
HW
20.5
44.4
143% (106%)
212% (119%)
73% (89%)
75% (96%)
0
0
100% (100%)
100% (100%)
100% (100%)
100% (100%)
20.5*
44.4*
100% (100%)
100% (100%)
100% (100%)
100% (100%)
Reverse-return
1.2
10.4
103% (100%)
150% (109%)
99% (100%)
85% (97%)
5
Oversized main piping
7.0
20.9
122% (103%)
173% (112%)
94% (99%)
82% (97%)
6
Undersized branch piping
19.5
NA
142% (106%)
NA
73% (100%)
NA
7
Undersized control valves
8.0
NA
120% (103%)
NA
86% (89%)
NA
58
Energy & First Costs Balancing Method
Pump head, feet CH W
Annual Pump Energy, $/yr
HW
CHW
HW
Incremental First Costs vs. Option 1 $ per design gpm
$ CHW
HW
CHW
HW
1
No balancing
58.5
82.7
$1,910
$3,930
–
–
–
–
2
Manual balance using calibrated balancing valves
60.3
83.6
$1,970
$3,970
$7,960
$47,530
$6.60
$88.00
3
Automatic flow limiting valves
66.6
90.8
$2,170
$4,310
$11,420
$50,750
$9.50
$94.00
4
Reverse-return
55.3
80.0
$1,810
$3,800
$28,460
$17,290
$23.70
$32.00
5
Oversized main piping
45.0
59.3
$1,470
$2,820
$12,900
$7,040
$10.80
$13.00
6
Undersized branch piping
58.5
NA
$1,910
NA
($250)
NA
($0.20)
NA
7
Undersized control valves
58.5
NA
$1,910
NA
($2,340)
NA
($2.00)
NA
59
Ranks Balancing Method
Controllability (all conditions)
Pump Energy Costs
First Costs
1
No balancing
7
3
3
2
Manual balance using calibrated balancing valves
4
6
6
3
Automatic flow limiting valves
4
Reverse-return
5
Oversized main piping
6
Undersized branch piping
7
Undersized control valves
7 2 3 6 5
7 2 1 4 4
7 5 4 2 1
8
Pressure independent control valve
1
78
8
60
Conclusions & Recommendations for Variable Flow Hydronic Systems Automatic flow-limiting valves are not recommended on any variable flow system
•
They only limit flow for transients which has little or no value
Calibrated balancing valves are also not recommended for balancing variable flow systems
•
But useful for future diagnostics on small low pressure drop coils – just leave them wide open (no throttling)
Oversized mains may have reasonable pump energy savings payback on 24/7 chilled water systems Undersizing piping and valves near pumps improves balance and costs are reduced, but significant added engineering time required Pressure independent valves should be considered on very large systems (>100 ft head) for coils near pumps
• •
Cost is high but going down now with competition When costs are competitive, this may be best choice for all jobs
For other than very large distribution systems, option 1 (no balancing) appears to be the best option
•
Low first costs with minimal or insignificant operational problems 61
Break
Problems caused by Degrading ∆T
Q= 500 X GPM X ∆T For a Given Load Q, When ∆T Goes Down, GPM Goes up Result:
• • •
Increases pump energy Can require more chillers to run at low load, or coils will be starved of flow Can result in reduced plant effective capacity: chiller capacity without the capability of delivering it
Resource January 2002 ASHRAE Symposium Paper, “Degrading Chilled Water Plant Delta-T: Causes and Mitigation
63
Primary/secondary “death spiral” Chillers staged by Load 80%
42oF 46oF 42 VFD
When ∆T Degrades, Secondary Flow Exceeds Primary VFD
50oF 52
64
∆T Degradation in Large Chiller Plant (January through March)
Design ∆Τ=10oF
9.5°F-10.0°F
Evaporator Delta T (°F)
Coincident Wet Bulb Ranges 7.0°F-7.5°F
35°F-40°F 40°F-45°F 45°F-50°F 50°F-55°F 55°F-60°F
4.5°F-5.0°F
2.0°F-2.5°F
0
100
200
300
400 Approximate hrs/yr
500
600
700
800
Causes of Degrading ∆T 1. Causes that can be avoided by proper design or operation of the chilled water system; 2. Causes that can be mitigated, but through measures that may not result in overall energy savings; and 3. Causes that are inevitable and simply cannot be avoided
66
Degrading ∆T #1. Causes that can be eliminated by design/operation
Improper Setpoints or Calibration
•
e.g. dropping coil SATsp by 2ºF will double the flow rate and halve the ∆T
Use of Three-way Valves
•
Instant response is not a valid reason for 3-way valves
No Control Valve Interlock
•
i.e. valve open when fan is off
Coils Piped Backwards (parallel flow vs. counter-flow) ...
67
Degrading ∆T #1. Causes that can be eliminated by design/operation (continued)
Uncontrolled Process Loads
•
need isolation valves
Incorrectly Selected Control Valves
• •
Oversized valves hunt and result in higher average flow Undersized actuators have insufficient close-off pressure
Incorrectly Selected Coils
•
Common problem when new buildings don’t follow the campus standard ∆T
Improper “Bridge” Connection & Control
•
Bridge valve cannot raise the CHWRT without starving the load
68
Degrading ∆T
#2 Measures that improve ∆T but energy trade-off
Chilled Water Reset to Lower Chilled Water Supply Temperature
• Lowering CHWST by 1ºF increases ∆T by 1 •
to 2ºF but reduces chiller efficiency Net effect could be better (if high pump energy) or worse (low pump energy)
69
Degrading ∆T
#2 Measures that improve ∆T but energy trade-off
Coil Pumps to Prevent ∆T Degradation at Low Flow Due to “Laminar Flow Effect”
• May (or may not) improve ∆T at low flow but coil pump energy is very high
70
Laminar Flow “Problem:” Real or Myth? 20 18
Dual Row, 5/8" Tubes Full Row, 5/8" Tubes Full Row, 1/2" Tubes
14 12 10 8 6 4 Laminar Flow
2 0
100%
80%
60%
40%
% Sensible Load
20%
0%
Delta-T (degrees-F)
16
Data from Major Coil Manufacturer’s ARI certified rating program developed from lab tests
Primary/Secondary vs. Primary/Secondary with Coil Pumps 50.00 45.00
P/S/T with constant ∆T
40.00
Pump kW
35.00 30.00 25.00
P/S with degrading ∆T
20.00 15.00 10.00 5.00 0.00 0%
20%
40%
60%
80%
100%
3-chiller/3-pump plant, total 1440 gpm
% Plant Load Conclusion: even if the laminar flow problem were real, coil pumps are not a good solution. They add to both first costs and energy costs.
72
Causes of Degrading ∆T #3. Causes That Cannot Be Eliminated
Air Economizers and 100% Outdoor Air Systems 42oF CHWST
60oF EAT
55oF SAT
(Design CHWRT of 62, based on design EAT of 80)