Centum VP Engneering Course Training Day 1
Short Description
Centum VP Engneering Course Training Day 1...
Description
Yokogawa Electric Corporation
Yokogawa Vietnam Company Ltd. Training Center
CENTUM VP Engineering Course Trainer: Email:
@vn.yokogawa.com
Schedule for the day: Session Starts: Tea Break: Lunch: Session Resume: Tea Break: Sessions Ends:
9:00 – 10:30 10:30 – 10:45 12:00 – 1:00 1:00 – 3:00 3:00 – 3:15 5:00
am am pm pm pm pm
Yokogawa Vietnam Company Ltd. Training Center
2
Course Contents
Day 1
Day 3
Centum VP System specifications
Regulatory Control Function
Project Creation/Attribution Utility
Sequence Control Function
Project Common Definition Day 4
FCS Configuration I/O Module Configuration Day 2
HIS Configuration Window Configuration
Software Switches Configuration Message Configuration Control Drawing Builder
Day 5
Graphic Builder
Yokogawa Vietnam Company Ltd. Training Center
3
What is CENTUM VP CENTUM VP is the integrated production control system to achieve the safe, reliable, and optimum plant operation for various industries
Yokogawa Vietnam Company Ltd. Training Center
4
35 years History and the continuity Dual redundant Token-passing bus for our DCS since 1975 as reliable & robust control bus
2008
2011
CENTUM VP CENTUM VP R5
2001
CENTUM CS 3000 R3
1998 CENTUM CS 3000
1993 10 MBPS Dual Redundant Token Pass V net
1MBPS Dual Redundant Token Pass
1983
1988
CENTUM V
CENTUM-XL
COPS2 COPSV
HF-Bus
ENGS
CENTUM CS
HIS HIS
PICS
EWS
HIS
ICS
ABC
2005
AVR FFCS
PFCS
Vnet/IP
NFCS
1Gbps Dual Redundant
FFCS
LFCS KFCS
EOPS
1975 CENTUM COPS
CFCS2 CFCD2 CFFS
F-Bus 250 KBPS Dual Redundant Token Pass
CFCS EFCD
• CENTUM series has been keeping the operation continuity and the application compatibility for customers to use the CENTUM continuously for a long term. • 20,000 + systems have been installed worldwide
Yokogawa Vietnam Company Ltd. Training Center
5
Yokogawa DCS Evolution
Yokogawa Vietnam Company Ltd. Training Center
6
Centum Capacity
System Max. no. of tags
Centum VP 100 000 (When using LHS4000, up to 1,000,000 per system)
Max. no. of stations Max. no. of domains Max. no. of stations per domain
256 16 64 (HIS (16) , FCS, BCV, CGW)
HIS : Human Interface Station FCS : Field Control Station BCV : Bus Converter CGW : Communication Gateway Yokogawa Vietnam Company Ltd. Training Center
7
CENTUM VP System Configuration - Overview Client PC
Operator Station (HIS) Asset management station for FF/HART devices PRM
3rd party wireless gateway
Ethernet Enclosed Display Open Display Style Console Style Console Desktop type TSE server HIS HIS and/or ENG HIS
Dual Redundant Vnet/IP Real-time Control Network
FCS
ProSafe-RS SENG
Plant Information Management System OPC server Exaquantum Exaopc
Sub system gateway
Safety Instrumented System Controller ESD / F&G
Field Network ProSafe-RS SCS
Unified Gateway Station (UGS) 3rd party Sub systems
STARDOM -Vnet/IP: Real-time Control Network -Ethernet: Information Network -Exaopc: OPC Server -Exaquantum : Plant information management system Yokogawa Vietnam Company Ltd. Training Center
8
System Specification Centum VP Integration Highlights
HIS-TS
Web Server Ethernet Console
Open
HIS EWS
APCS
GSGW
SOE
VnetIP router
Vnet ABC-H
LFCS
PFCS
KFCS
FFCS
Pro-SAFE
HF-Bus
Safety Loop Digital IOs
CENTUM-XL
Conventional Analog
Subsystems
Fieldbus
Yokogawa Vietnam Company Ltd. Training Center
9
CENTUM VP VNET/IP System Components
Yokogawa Vietnam Company Ltd. Training Center
10
Plant Resource Manager (1)
Plant Resource Manager (PRM) is designed to improve the efficiency of the management and maintenance of field devices, that were registered and assigned to plant hierarchy. Also, it automatically creates management documents on devices so that they can be managed electronically. It can also access devices with a field communication function such as devices that support FOUNDATION fieldbus, manage device parameters, and execute device adjustment and diagnosis available with devices and so forth.
Yokogawa Vietnam Company Ltd. Training Center
11
PRM Configuration
Yokogawa Vietnam Company Ltd. Training Center
12
PRM Configuration
Yokogawa Vietnam Company Ltd. Training Center
13
HIS: Human Interface Station Features : ¾ Various types of the operation views are prepared – Graphic, Trend graph, Overview, Tuning etc. ¾ One-touch operation for related information – Alarm dialog, trend graph, Graphics, and faceplates can be called up from each other based on the related tag without engineering Ex. Click alarm message then the related faceplate is shown
¾ Large Capacity – Max. No. of Tags: 1,000,000 per system – Max. Graphic Displays: 4,000 per HIS – Real-time trend Points: 3,328 per HIS
¾ Various types of operation environment are available – – – –
Single, dual, Quad LCD are available. Wide monitor is also available. Mouse operation Operation keyboard and touch screen are also available ¾ Real-time Alarm Management View Yokogawa Vietnam Company Ltd. Training Center
14
HIS Hardware ¾ HIS works on the latest Microsoft Windows OS platform Windows 7 64bit, VISTA, and 2008 server
¾ Three types of hardware can be chosen Desktop, Solid Style Console and Open Style Console
¾ Various Operation Styles Mouse/Operation Keyboard/Touch panel Single, Dual and Quad-monitor are available Solid Style Console
Desktop Type
Open Style Console
Yokogawa Vietnam Company Ltd. Training Center
15
New Screen Design
Yokogawa Vietnam Company Ltd. Training Center
16
Examples of Frames and Pop-Up Window Frame = An element of Container Window System Message Banner Pop-Up Window
Browser Bar
Yokogawa Vietnam Company Ltd. Training Center
17
System Specification Engineering PC (ENG)
Yokogawa Vietnam Company Ltd. Training Center
18
EWS Engineering PC (ENG)
Yokogawa Vietnam Company Ltd. Training Center
19
Operation Keyboard Features ¾ Flat membrane type dedicated keyboard ¾ Various functions for adequate operation – – – – – –
Security key Authorized operator System engineer Alphanumeric buttons Process control and plant monitoring Special window call buttons grouped by function – User-definable function buttons
Yokogawa Vietnam Company Ltd. Training Center
20
Field Control System I. Process Control Functions The FCS is the controller that executes control strategy and computation to control the plant Four Types of FCS to choose from, for Flexible System Configuration: FIO, FCS for RIO, Compact FCS for FIO, and Compact FCS for RIO, according to your application requirements, for system expansion or replacement.
FFCS (Compact) FIO
PFCS (Compact) RIO
KFCS/KFCS2 (Standard/Enhanced) FIO
LFCS/LFCS2 (Standard/Enhanced) RIO
Yokogawa Vietnam Company Ltd. Training Center
21
Field Control System
Yokogawa Vietnam Company Ltd. Training Center
22
Field Control System
Yokogawa Vietnam Company Ltd. Training Center
23
FCS (Field Control Station)
Address setting on the backside of the FCS (CPU card) Yokogawa Vietnam Company Ltd. Training Center
24
Setting Domain Number
Yokogawa Vietnam Company Ltd. Training Center
25
Setting Station Number
Yokogawa Vietnam Company Ltd. Training Center
26
Redundant Configuration of CENTUM VP All data are equalized in real time without affecting the control communication among all HIS’s Dual CPU module
Dual Power
Dual Vnet/IP
Dual Vnet/IP
Dual I/O modules
Dual Power
Dual ER bus
Analog, Digital, Fieldbus, Serial
Dual ESB/ER bus
Yokogawa Vietnam Company Ltd. Training Center
27
Pair & Spare CPU Architecture ¾ Both CPU modules are processing independently, so CENTUM achieves real bumpless switchover (For Redundancy purpose) Vnet/IP
Vnet/IP I/F
CPU 1
CPU 1
CPU 2
CPU 2
Comparator
Comparator
CPU module Main memory with ECC
Vnet/IP I/F
PIO I/F
PIO I/F
PIO I/F
PIO I/F
Power card
IO bus I/F
IO bus I/F
Coupler
Coupler
CPU module Main memory with ECC
Power card
¾ A pair of CPU chips is on each CPU module – Each CPU is processing independently • This is not for redundancy purpose ¾ Result checking – Processed results of CPUs are every time compared each other – If the results are not congruous, control switches to the stand-by module (To avoid the effect of transient error)
I/O bus
Error-Correcting Code repairs transient bit inversion errors Yokogawa Vietnam Company Ltd. Training Center
28
Control Network (Vnet/IP) ¾ Vnet/IP is the control network that incorporates general communication function without losing highly reliable, real-time, and stable communication – High reliability and real-time capability of Vnet are succeeded – Open communication capability is incorporated ¾ 1G bps Ethernet based control network – 100 Mbps is also available ¾ Being published by IEC as industrial communication standard PAS (IEC/PAS 62405/Ed.1) PAS: Publicly Available Specification Open
Reliable
Realtime
Yokogawa Vietnam Company Ltd. Training Center
29
Vnet/IP Specifications ¾ General specifications – Topology: Star topology – Transmission speed: 1 Gbps for Yokogawa hardware, 100 Mbps for general Ethernet equipment – Access control: Full duplex – Scale: 64 stations/domain – Configuration: Redundant – Control communication: Functionally compatible with Vnet – Open communication: TCP/IP – Network equipment: Commercially available switching hubs and routers (Layer 2 switches and Layer 3 switches) – Cables: CAT5e or higher UTP cables or single-mode fiber optic cables
Yokogawa Vietnam Company Ltd. Training Center
30
Vnet/IP Network Configuration HMI
ENG
Vnet Router
Vnet System
Controller
Plant Asset Management
OPC Server
ProSafe-RS
Domain1
Third party system Interface
Field network
OPC Server
ENG
HMI
Controller
Plant Asset Management
ProSafe-RS
Field network
Domain2 Yokogawa Vietnam Company Ltd. Training Center
31
Vnet/IP – 1 Gbps Control Network
PIMS
OPC
HIS/ENG
HIS
3rd Pty Appl.
Open
Open Vnet
Open Vnet
Open Vnet
Open
LAN2 cable Open Communication (TCP/IP) Control Communication (Vnet Protocol)
Control Communication (Vnet Protocol) LAN1 cable
Vnet
Open
Vnet Open
Open
FCS
Field Eye Server
GSGW
PLC
Yokogawa Vietnam Company Ltd. Training Center
32
1 GBps Bandwidth
Vnet/IP Features (bandwidth partitioning Control)
In case of errors in BUS 1, control is shrift to BUS 2
Yokogawa Vietnam Company Ltd. Training Center
33
Control Network
Yokogawa Vietnam Company Ltd. Training Center
34
IP addressing Vnet/IP HISDDSS
DD = Domain Number SS = Station Number
Vnet: 172.16. DD.SS VnetOpen: 192.168.[128+DD]. [SSx2] HIS0156
Domain 1 Station 56
Network Address: Vnet: 172.16. 1.56 Open: 192.168.129.112
HIS0324
Domain 3 Station 24
Network Address: Vnet: 172.16. 3.24 Open: 192.168.131.48
HIS0234
Domain 2 Station 34
Network Address: Vnet: 172.16. 2.34 Open: 192.168.130.68
Alternate Addressing for VnetOpen: 192.168.[128+DD]. [128+DD+SS] Yokogawa Vietnam Company Ltd. Training Center
35
Cables Use a CAT5e (enhanced category 5) or higher UTP (Unshielded Twisted Pair) cable for 1000BASE-T. It is required that the number of layer 2 switches be increased or the maximum distances be expanded by fiber cabling according to the system configuration or equipment installation location
Connection
Cable Standard
Transmission Rate
Max Distance
Between stations &L2 Switch
1000BASE-T
1GBps
100m
1000BASE-T
1GBps
100m
Between L2 Switches
1000BASE-LX
1GBps
5km
1000BASE-T
1GBps
100m
1000BASE-LX
1GBps
5km
Between L2- & L3 Switches
Yokogawa Vietnam Company Ltd. Training Center
36
I/O Node
Node
The Node is a signal processing devices that convert process input/output signals to or from the field equipment and transmit them to the field control unit.
Yokogawa Vietnam Company Ltd. Training Center
37
I/O Nodes ¾ Up to 13 I/O nodes can be connected per FCS (EC402) One I/O node has 8 I/O module slots I/O nodes are connected by the remote I/O bus (ESB Bus) – Up to 10 m from the FCS CPU node to the end of the I/O node if electric cables are used as the ESB bus – Up to 50 km in case of optical cables as the ESB bus
Max 9 I/O nodes/Line Total Max 13 I/O nodes (without CPU node)
Yokogawa Vietnam Company Ltd. Training Center
38
System Specification (FFCS)
Eight FIO slots
Centum VP Compact type Detachable bottom unit EC401 ESB bus coupler(Note)
Power supply unit
CP401 CPU module AIP504 VnetIP coupler (10BASE2 VnetIP cable is used.) Note: Two I/O slots are to be used for NIU extension. Yokogawa Vietnam Company Ltd. Training Center
39
HW/SW Requirement: Software Operating system: Windows XP, Service Pack 3, Windows 7 64Bits Processor:
Intel Core 2 Duo
Color pallet :
Above High color (65536). With at least 8MB of VRAM, 16000000 colors can be specified.
Memory :
2 GB or more RAM 80GB HDD (recommended minimum)
Memory :
CRT or LCD (21” min recommended) Video memory (512 MB minimum)
PCI/Express Slot: Vnet/IP card (VF701/VI701/VI702) Ethernet port
LAN connection (for Vnet only)
Yokogawa Vietnam Company Ltd. Training Center
40
Test Function The Test function allows combination of monitoring/operation and control functions to be tested before being put into operation. The Engineers use this tool to debug the changes they are about to do. Virtual Test
Target Test
ooo
Yokogawa Vietnam Company Ltd. Training Center
41
Types of Test Function 1. Virtual Test Function It uses an FCS simulator instead of an actual FCS. The FCS simulator simulates the functions and operation of the FCS and runs under an HIS.
Virtual Test
FCS simulator
Operation and monitoring Function
ooo
HIS01XX FCS01XX Yokogawa Vietnam Company Ltd. Training Center
42
Types of Test Function 2. Target Test It uses an actual FCS. When there are no I/O modules and I/O test devices, an FCS input and output can be simulated by using the I/O Disconnect and Wiring Functions. These use actual HIS and FCS for the test.
Tag01 PID
I/O simulator HIS01XX
FCS01XX ooo
Yokogawa Vietnam Company Ltd. Training Center
43
Engineering Work Flow Specification Review Review the I/O list, process control methods and necessary hardware. Basic Design Using organized and structured windows to realize the desired control functions (regulatory control, sequence control and unit supervision) and the operation and monitoring functions.
Detailed Design Design detailed items (program configuration, creation of data list) for the regulatory control, sequence control, unit supervision and the operation and monitoring windows according to the basic design.
Yokogawa Vietnam Company Ltd. Training Center
44
Engineering Work Flow System Generation Construct a system using various builders based on the basic design and detailed design.
Unit Test Check the control loop operation as well as the operation and monitoring windows by using the virtual test function.
Integration Test Using the actual FCS, check the overall validity of functions and execution timings that were checked individually through the unit test.
Yokogawa Vietnam Company Ltd. Training Center
45
Engineering Work Flow Start Up Install and wire the target machine, carry out test operation and then normal operation.
Maintenance Back up engineering data, inspect hardware, etc.
Expansion and Modification Expand the station, as well as add and change functions. Review the I/O list, process control methods and necessary hardware.
Yokogawa Vietnam Company Ltd. Training Center
46
Project Creation 1. Start System View Start Æ Programs Æ YOKOGAWA CENTUM Æ System View
Yokogawa Vietnam Company Ltd. Training Center
47
Project Creation Start Default Project Creation When the System View could not identify an existing current or default project, it will prompt the user to create a default project with the dialog box as shown below. Click [YES] to create the default project.
Yokogawa Vietnam Company Ltd. Training Center
48
Project Creation Project Outline The project information area allows the project creator to enter arbitrary characters. Enter information on the process and the person in charge of DCS to manage the project.
Yokogawa Vietnam Company Ltd. Training Center
49
Project Creation Project Property Project name is an alphanumeric character string less than 8 characters. The comment within 32 alphanumeric characters or 16 double - byte characters may be entered as the project description. Moreover, an alias can be created for a project. An alias of project can be defined with 8 alphanumeric characters.
Yokogawa Vietnam Company Ltd. Training Center
50
Project Creation Creating an FCS folder A folder for the first FCS database files is created when the default project is created. Assign the correct station type and station address as they cannot be modified upon confirmation. Additional FCS can be created in future for more FCSs.
Yokogawa Vietnam Company Ltd. Training Center
51
Project Creation Creating a HIS folder A folder for the first HIS database files is created when the default project is created. Assign the correct station type and station address as they cannot be modified upon confirmation. Additional HIS can be created in future for more HISs
Yokogawa Vietnam Company Ltd. Training Center
52
Project Creation Project folders The project consists of 3 basic folders – Common, FCS and HIS. Additional FCS, HIS or other stations can be created under the pull down menu. Select project Æ Right click on project Æ Create New Æ HIS or FCS
Yokogawa Vietnam Company Ltd. Training Center
53
Project Creation
Subfolders of your project
Now you have your new project under the name TRAINVP Yokogawa Vietnam Company Ltd. Training Center
54
Project’s Attribution Utility ¾ The Project’s Attribution Utility is an engineering tool that makes it convenient to register a project created from other PC, to change a project’s properties or to remove the registration of a project. ¾ Before using the Project’s Attribution Utility, check that the System View is not running. If it is running, the Project Attribute Change Utility cannot run. ¾ Only one project can exist as default project or current project in System View
Yokogawa Vietnam Company Ltd. Training Center
55
Project’s Attribution -Differences
Default
Current
User-defined
Created the first time when the System View starts
Yes
-
-
Virtual test with the FCS simulator.
Yes
Yes but target test
Yes
Yes but off line
Yes but on line
No
Can be downloaded to HIS.
Yes
Yes
No
Multiple projects can be created in System View.
No
No
Yes
Can be downloaded to the FCS of the target system
When any one of the FCS’s created in default project is successfully downloaded, the attribute changes to a current project. Yokogawa Vietnam Company Ltd. Training Center
56
Project’s Attribution Utility
Click “Programs” Click “start”
Click “Project’s Attribution Utility”
Click “YOKOGAWA CENTUM” Yokogawa Vietnam Company Ltd. Training Center
57
Project’s Attribution Utility
Click
To change the Attribute of a Project
To remove a Project from System View Yokogawa Vietnam Company Ltd. Training Center
58
Project’s Attribution Utility
Yokogawa Vietnam Company Ltd. Training Center
59
Project Common Item Definition ¾ ¾ ¾ ¾ ¾ ¾
Station Configuration Viewer Security Builder Operation Mark Builder Engineering Unit Symbol Builder Switch Position Label Builder Alarm Builder 9 Alarm Priority Builder 9 Alarm Processing Table Builder 9 System Fixed Status Character String Viewer
Yokogawa Vietnam Company Ltd. Training Center
60
Project Common Item Definition From the System View
Yokogawa Vietnam Company Ltd. Training Center
61
Project Common Item Definition Station Configuration Viewer
The Station Configuration Viewer displays the overview of the station configured for the project and a print out can be generated. However, modification to the configuration is not allowed in this viewer Yokogawa Vietnam Company Ltd. Training Center
62
Project Common Item Definition Security Builder
The security policy is set to prevent illegal operations and other problems and ensuring the safety of the system.
Yokogawa Vietnam Company Ltd. Training Center
63
Security Level
An attribute called “Security Level” is assigned to the function blocks. The security policy is set to prevent illegal operations and other problems and ensuring the safety of the system
Yokogawa Vietnam Company Ltd. Training Center
64
Security Builder – Tag View OFFUSER
ONUSER
ENGUSER
Yokogawa Vietnam Company Ltd. Training Center
Page.6
Security Builder – Window Monitoring OFFUSER
ONUSER
ENGUSER
Properties of Function Block FIC100
Yokogawa Vietnam Company Ltd. Training Center
Page.6
Security Builder – Window Operation OFFUSER
ONUSER
ENGUSER
Users with S3 rights can write data to Block mode, SV and MV, but users with S2 rights cannot write data to Block mode, SV and MV.
Yokogawa Vietnam Company Ltd. Training Center
Page.6
User Name & User Switching
Yokogawa Vietnam Company Ltd. Training Center
68
Privilege Level
Yokogawa Vietnam Company Ltd. Training Center
69
Automatic User Time-Out
Yokogawa Vietnam Company Ltd. Training Center
70
User Group Users group classified into groups based on their operation and monitoring authorities/Scopes. The following attributes are assigned to each user group: User group name, Operation scope, Operation and monitoring scope, Windows scope, Confirmation operation scope, Messaging scope, Comment
Yokogawa Vietnam Company Ltd. Training Center
71
Valid User Valid User classified into User name based on their users group of operation and monitoring authorities/scopes. Users can be defined to automatic user out time, the users automatically changes to OFFUSER when automatic user out time elapsed
Yokogawa Vietnam Company Ltd. Training Center
72
Operation Mark Builder
Tag Label: Up to 8 single-byte characters can be entered as the text on the label (string). The operation mark label maybe temporarily changed during the operation on the HIS Setup window. Yokogawa Vietnam Company Ltd. Training Center
73
Operation Mark: Privilege level & Color Privilege Level: The privilege level required for a user to attach/remove the operation mark.
Tag Level write access right on function blocks can be changed
Colors: The following colors maybe used on operation Marks and maybe temporarily changed on the HIS Setup window.
Yokogawa Vietnam Company Ltd. Training Center
74
Project Common Item Definition Engineering Unit Symbol Builder
Up to 256 engineering unit symbols can be used for one project
Engineering Unit symbols nos. 1-8 cannot be changed or deleted. Default values are from nos. 9-126
The following symbol cannot be used to define engineering unit: @, /, (‘),(“),(,) and #
Yokogawa Vietnam Company Ltd. Training Center
75
Alarm Priority Builder - Alarm Action
The alarm processing level is defined for each function block. The output operation for each alarm priority can be selected.
Yokogawa Vietnam Company Ltd. Training Center
76
Alarm Priority Builder - Rewarning
Yokogawa Vietnam Company Ltd. Training Center
Page.7
Alarm Processing Table Alarm Processing Level Numbers: 1- 4 System fixed - High - Medium - Low - Alarm Logging 5 – 16 User defined - High - Medium - Low - Alarm Logging - Reference Alarm
Yokogawa Vietnam Company Ltd. Training Center
78
System-fixed Status Character String Viewer/ Alarms
Alarm Status Bit Positions
1- 4 System fixed 5 – 16 User defined
Yokogawa Vietnam Company Ltd. Training Center
Page.7
End of Presentation
THANK YOU FOR YOUR ATTENTION
Yokogawa Vietnam Company Ltd. Training Center
80
View more...
Comments