Power Quality
SIMEAS Q Power Quality Recorder
Catalog SR 10.2.5 · 2003
SIMEAS Q Power Quality Recorder
Catalog SR 10.2.5 · 2003 Supersedes: Catalog SR 10.2.5 · 1998
Power Quality Page
Overview
2
Connection
3
Functions
4 and 5
Software
6 to 9
Connection Examples
10
Technical Data
11 and 12
Selection and Ordering Data
13
Dimension Drawings
13
© Siemens AG 2003
SIMEAS Q Power Quality Recorder
Overview
l
Recording of electrical quantities, e.g. for analyzing power quality
l
Suitable for monitoring of single-phase power supply systems and 3 and 4-wire three-phase power systems
l
Recording of limit violations
l
2 binary outputs for energy pulses or pulse on voltage dip
l
Transmission of recorded values via various communication channels (RS232, RS485, PROFIBUS DP)
l
Link-up to PLC systems
Fields of application l
Recording and evaluation of electrical quantities in power supply systems on the low-voltage level up to 1 kV rated voltage.
l
Acquisition and evaluation of electrical quantities in power distribution systems on the medium-voltage level up to 35 kV rated voltage.
l
Acquisition of all relevant measurement data for evaluating power quality.
l
Monitoring of power quality in terms of applicable standards.
SR2007-afp.eps
Functions
Application The growing use of non-linear or unbalanced loads is increasingly having an effect on power quality in supply systems. However, many electric loads require a defined power quality in order to work properly. Inadequate power quality has an adverse effect on the dependability of loads within the power supply system and can cause outages with serious consequences. Complete recording and evaluation of power quality according to international standards.
2
Siemens SR 10.2.5 · 2003
Fig. 1 SIMEAS Q
SIMEAS Q Power Quality Recorder
Connection
Two different connection methods or system configurations are possible, depending on the application and existing infrastructure. One is to use a central PC as the master. It is then possible to set up a system for measured value acquisition and evaluation using the SICARO Q-Manager software. The other possibility is to link-up to a PLC system where the SIMEAS Q is connected to the central master as a slave.
Telecommunications network
Fig. 2
Using the SICARO Q Manager software and a PC with several SIMEAS Q units
Fig. 3
SIMATIC S7 PLC as the master station with various PROFIBUS-DP slaves
SIMEAS Q with PC as a master The SIMEAS Q units are installed at various points to record electrical quantities in order to analyze power quality. The measured values stored in the device memory are called up with a personal computer via one of 3 possible communication interfaces and can then be evaluated. For connection to a PC, the following communication interfaces are available: l
PROFIBUS-DP interface
l
Modem-capable, serial RS232 interface
l
Serial RS485 interface
SIMEAS Q with PLC systems as master The SIMEAS Q version with a PROFIBUS-DP interface opens up a further field of application. Together with programmable control systems (PLC), the SIMEAS Q can be used as a ”sensor for electrical quantities“. The PROFIBUS interface, implemented and certified according to standard EN 50170 Volume 2, enables fast adaptation to a PLC systems. That way, measured values acquired with the SIMEAS Q can be used for control tasks.
Detailed information on how to retrieve measurement data from SIMEAS P via PROFIBUS is available to everyone in the SIMEAS Q user description. The open communication interface permits data transmission between SIMEAS Q units and all types of PROFIBUS-DP Masters, such as programmable controllers or personal computers (with integrated PROFIBUS-DP hardware).
They permit fast configuration of customer-specific PLC programs for applications combining SIMEAS Q with these PLC systems.
Function blocks are available for the SIMATIC S7-300 and -400 PLC systems, with an internal or external DP interface.
Siemens SR 10.2.5 · 2003
3
SIMEAS Q Power Quality Recorder
Functions
Recording of measured values is possible in two modes, which can be used simultaneously. l
Continuous recording
l
Recording in the case of a limit violation (see page 5)
Continuous recording In continuous recording, depending on the setting for each measured quantity, the rms values are acquired and stored in the memory along with the relevant time and date information. This records a ”chain of measured values“ whose resolution can range from low to very high, depending on the averaging time set. In ”continuous recording“ mode, the SIMEAS Q can record measured quantities as defined in the standards (e.g. EN 50160). Acquisition of maximum and minimum values of measured quantities within the measurement period (averaging time) is also possible. The table on the right shows which measured quantities can be acquired by continuous recording, depending on the type of power system.
4
Siemens SR 10.2.5 · 2003
Measured quantity
Possible averaging time
Max/min possible
Rms values phase-to-ground voltages or phase-to-phase voltages
1, 2, 5, 6, 10, 15, 30, sec 1, 2, 5, 6, 10, 15, 30, 60 min
yes
Rms value phase currents
1, 2, 5, 6, 10, 15, 30, sec 1, 2, 5, 6, 10, 15, 30, 60 min
yes
System frequency (always measured at input VPH1)
1, 2, 5, 6, 10, 15, 30, sec 1, 2, 5, 6, 10, 15, 30, 60 min
yes
Active power per phase and total active power
1, 2, 5, 6, 10, 15, 30, sec 1, 2, 5, 6, 10, 15, 30, 60 min
yes
Reactive power per phase and total reactive power
1, 2, 5, 6, 10, 15, 30, sec 1, 2, 5, 6, 10, 15, 30, 60 min
yes
Apparent power per phase and total apparent power
1, 2, 5, 6, 10, 15, 30, sec 1, 2, 5, 6, 10, 15, 30, 60 min
yes
Power factor per phase and total power factor
1, 2, 5, 6, 10, 15, 30, sec 1, 2, 5, 6, 10, 15, 30, 60 min
yes
Voltage unbalance
1, 2, 5, 6, 10, 15, 30, sec 1, 2, 5, 6, 10, 15, 30, 60 min
yes
Current unbalance
1, 2, 5, 6, 10, 15, 30, sec 1, 2, 5, 6, 10, 15, 30, 60 min
yes
Flicker factor short-term per phase voltage (Ast or Pst)
10 min fixed to standards IEC 60868 and IEC 60868 A1 - Flickermeters
no
Flicker factor long-term per phase voltage (Alt or Plt)
120 min fixed to standards IEC 60868 no and IEC 60868 A1 - Flickermeters
1st to 40th harmonic voltage per phase
1, 2, 5, 6, 10, 15, 30, sec 1, 2, 5, 6, 10, 15, 30, 60 min
yes
1st to 40th harmonic current per phase
1, 2, 5, 6, 10, 15, 30, sec 1, 2, 5, 6, 10, 15, 30, 60 min
yes
Total harmonic distortion (THD) per phase
1, 2, 5, 6, 10, 15, 30, sec 1, 2, 5, 6, 10, 15, 30, 60 min
yes
Active energy – import / active energy – export Reactive energy – inductive / reactive energy – capacitive Apparent energy
1, 2, 5, 6, 10, 15, 30, 60 min
no
Table 1
Possible measured quantities in continuous recording
SIMEAS Q Power Quality Recorder
Functions
Recording in the case of limit violation
Measured quantity
Possible averaging time
Number of thresholds
Recording in the case of limit violation means that measurement data are recorded when the average measured value violates one or more defined upper or lower limits (thresholds). When a limit is violated, the current time and date information and the mean value since the last limit violation of that measured quantity are stored in the memory. This type of recording is primarily used for recording voltage dips. To record voltage dips, the lowest possible averaging time of 10 ms is selected. During measurement, the SIMEAS Q compares the rms values = 10 ms with the set thresholds and is thus able to record very short voltage dips. The table on the right shows the measured quantities for which limit violations can be parameterized.
Rms values phase-to-ground voltages or phase-to-phase voltages
10, 20, 50, 100, 500 ms 1, 2, 5, 6, 10, 15, 30, sec 1, 2, 5, 6, 10, 15, 30, 60 min
5
Rms value phase currents
10, 20, 50, 100, 500 ms 1, 2, 5, 6, 10, 15, 30, sec 1, 2, 5, 6, 10, 15, 30, 60 min
5
System frequency (always measured at input VPH1)
1, 2, 5, 6, 10, 15, 30, sec 1, 2, 5, 6, 10, 15, 30, 60 min
2
Active power per phase and total active power
1, 2, 5, 6, 10, 15, 30, sec 1, 2, 5, 6, 10, 15, 30, 60 min
2
Reactive power per phase and total reactive power
1, 2, 5, 6, 10, 15, 30, sec 1, 2, 5, 6, 10, 15, 30, 60 min
2
Apparent power per phase and total apparent power
1, 2, 5, 6, 10, 15, 30, sec 1, 2, 5, 6, 10, 15, 30, 60 min
2
Power factor per phase and total power factor
1, 2, 5, 6, 10, 15, 30, sec 1, 2, 5, 6, 10, 15, 30, 60 min
2
Voltage unbalance
1, 2, 5, 6, 10, 15, 30, sec 1, 2, 5, 6, 10, 15, 30, 60 min
5
Current unbalance
1, 2, 5, 6, 10, 15, 30, sec 1, 2, 5, 6, 10, 15, 30, 60 min
5
1st to 40th harmonic voltage per phase
1, 2, 5, 6, 10, 15, 30, sec 1, 2, 5, 6, 10, 15, 30, 60 min
2 per harmonic
1st to 40th harmonic current per phase
1, 2, 5, 6, 10, 15, 30, sec 1, 2, 5, 6, 10, 15, 30, 60 min
2 per harmonic
Total harmonic distortion (THD) per phase
1, 2, 5, 6, 10, 15, 30, sec 1, 2, 5, 6, 10, 15, 30, 60 min
2
Data memory and data transmission
Table 2
The SIMEAS Q has a measurement memory with a capacity for 70,000 measured values. The information on time and date of the measurement are stored along with each measured value. In normal measurement mode, the capacity of the data memory indirectly defines the intervals at which the PC must retrieve measurement data in order to obtain an unbroken chain of values. Retrieving measurement data frees capacity in the SIMEAS Q, which is then available again for new measurement data.
Possible measured quantities in the case of a limit violation
If the measurement data are not retrieved, the SIMEAS Q goes into memory overflow/ring buffer mode, which causes loss of data and gaps in the measured value chain. It must therefore be ensured that the measured data are always retrieved before memory overflow/ring buffer mode occurs.
Relay outputs The SIMEAS Q is fitted with 2 relay outputs (opto-relays). One of the following functions can be assigned to these outputs: l
Indication device active (switched on)
l
Energy metering pulse per settable energy value for:
l
Pulses on voltage dips (contact closed for 500 ms if violation of the first threshold below rated voltage detected)
The relay outputs enable the SIMEAS Q to be used for acquisition of measured values and for energy metering.
– Active energy, energy import – Active energy, energy export – Reactive energy, capacitive – Reactive energy, inductive – Apparent energy l
Indication active power import (contact open) or active power export (contact closed)
l
Limit power factor (p.f. (cos j)) (contact closed for as long as p.f. is lower than a settable limit value)
Siemens SR 10.2.5 · 2003
5
SIMEAS Q Power Quality Recorder
Software
Various software products are provided for working with the SIMEAS Q. This software is required for parameterization, configuring a substation, acquisition and storage of the measurement data, and also for displaying and evaluating the measured values. If SIMEAS Q units are connected to a PLC system as slaves, only the SIMEAS Q parameterization software is required to set the SIMEAS Q parameters.
Fig. 4
Connection between SIMEAS Q and PC for the configuration of device parameters with the SIMEAS Q parameterization software
Fig. 5
SIMEAS Q parameterization, main menu
Fig. 6
SIMEAS Q parameterization, typical settings
SIMEAS Q parameterization configuration software
l
SR2011-afpen.tif
The SIMEAS Q parameterization software, executable under the Windows 95/98/NT/ 2000 and XP operating systems, is a software product for carrying out basic settings on the SIMEAS Q Power Quality Recorder before commissioning. The software allows you to configure the SIMEAS Q for the communication protocol to be used (RS232, RS485 or PROFIBUS DP) and to prepare it for the measurement task. Functional scope
SR2012-afpen.tif
– Definition of the device address so that each device is uniquely identified – Definition of the connection parameters: Interface used (RS232, RS485, PROFIBUSDP) and transmission rate – Calibration of the unit – Updating of the unit firmware to enable new functions or to update the whole firmware in case of an error – Parameterization of the measurement settings of each unit. The measured quantities to be acquired can be defined separately for each unit.
6
Siemens SR 10.2.5 · 2003
SIMEAS Q Power Quality Recorder
Software
SICARO Q-Manager – Software for measured value acquisition
SR2008-afpen.tif
The SIMEAS Q parameterization software can be downloaded free of charge via the Internet at www.powerquality.de or www.simeas.com. To configure the SIMEAS Q, a cable is required to connect the PC. A separate parameterization package is available for this, containing the parameterization software and the connecting cable required for the respective unit version.
Fig. 7
SICARO Q Manager Main menu with system structure Menu item for measurement settings
Fig. 8
SICARO Q Manager Display of the currently transmitted measured values
Fig. 9
Presentation of measurement data in ASCII format with Microsoft-Excel
The SICARO Q Manager software, executable under the Windows 95/98/NT/2000 and XP operating systems, is a software product for configuring a system with several SIMEAS Q units and for gathering the measured values from the SIMEAS Q units, displaying them, storing them, and making them available for further processing. – Graphic configuration of a system structure with the connected SIMEAS Q units. The system structure simplifies handling of the software during active operation. – Remote parameterization of the measurement settings of each unit. Which measured quantities will be acquired and how can they be defined separately for each unit. – Remote control of data recording from the PC. – Automatic transmission and storage of the measurement data from the connected units. – Display of retrieved measurement data. The display takes the form of rotary dial instruments, bar charts and numerical values. – Automatic, cyclic time setting of all connected units to align the SIMEAS Q’s internal clock with the system time of the PC.
SR2010-afpen.tif
Functional scope
SR2013-afp.tif
l
Siemens SR 10.2.5 · 2003
7
SIMEAS Q Power Quality Recorder
Software
l
Functional scope (continued)
– Updating of the unit firmware to enable new functions or to update the entire firmware in case of an error. – Conversion of stored measurement data to ASCII format. After conversion, the data can be further processed with suitable software, e.g. Microsoft Excel. – Conversion of stored measurement data for analysis with the SICARO PQ software. l
Evaluation The SICARO Q Manager software can be used to display the measured quantities in various ways on the screen of a PC. The software also provides a function for exporting the measurement data in ASCII format. This makes it possible, for example, to import the data into Microsoft Excel with just a few mouse clicks, where it can be presented in diagrams and analyzed as required. The SICARO Q Manager software can also be used to export the measurement data for analysis in an optionally available program called SICARO PQ. SICARO PQ permits fast analysis of measurement data and automated PQ reporting in terms of the standards EN 50160, IEC 61000, or based on definable limits and compatibility levels.
8
Siemens SR 10.2.5 · 2003
SIMEAS Q Power Quality Recorder
Software
SR2014-afpen.tif
l
Fig. 10 SICARO PQ Parameterization of power quality evaluation criteria or reference levels
SR2015-afpen.tif
The SICARO PQ software, executable under the Windows 95/98/NT/2000 and XP operating systems, is a software product for evaluating measured values with respect to international standards, e.g. EN 50160 or IEC 61000 or according to definable compatibility levels. For analysis with SICARO PQ, the transmitted measured values first have to be exported using the SICARO Q Manager software. The exported data are then the data source for the analysis software. For evaluation and reporting, all that has to be done is to apply the reference levels and select a reporting template.
Fig. 11 SICARO PQ Display and analysis of continuous measured values
SR2016-afpen.tif
SICARO PQ
Fig. 12 SICARO PQ Analysis of voltage dips using a CBEMA plot
Functional scope
– Definition of reference levels for evaluating power quality. – Definition of quality profiles for selecting various features. – Definition of reporting template for setting the report layout. – Export of a report in HTML format, allowing navigation through and display of the report in any HTML browser.
Siemens SR 10.2.5 · 2003
9
SIMEAS Q Power Quality Recorder
Connection Examples
Connection terminals SIMEAS Q
Fig. 13 Single-phase alternating current
Connection terminals SIMEAS Q
Fig. 15 Three-wire three-phase current, same load
Connection terminals SIMEAS Q
Fig. 17 Four-wire three-phase current, any load (low-voltage network)
The input connections shown above are only examples. Currents and voltages up to the maximum permissible values can be connected even without current and voltage transformers.
10
Siemens SR 10.2.5 · 2003
Voltage transformers can also be connected in a delta or wye connection. All input or output terminals not needed for measurement remain unconnected.
Connection terminals SIMEAS Q
Fig. 14 Four-wire three-phase current, same load
Connection terminals SIMEAS Q
Fig. 16 Three-wire three-phase current, any load
Connection terminals SIMEAS Q
Fig. 18 Four-wire three-phase current, any load (high-voltage network)
SIMEAS Q Power Quality Recorder
Technical Data
Input Maximum rated system voltage Permissible modulation rate Rated frequency fEN Frequency range fE Waveform
Measurement functions (continued) For connection to AC systems only Y 230/D 400 V VY = 280 V; IE = 6 A 50 Hz, 60 Hz ± 5 Hz Sinusoidal or distorted up to 40th harmonic
Current Measuring range Accuracy Storage
Input alternating current IE Input rated current IE Power consumption per current path Modulation rate Continuous overload Surge withstand capability
Min. 1 A; max. 6 A Approx. 0.06 VA at IE = 6 A 6A 12 A 200 A acc. to IEC/EN 60688
Active power, apparent power, reactive power Accuracy Storage
Input alternating voltage VE Power consumption Input to ground Rated voltage VEN Continuous overload Surge withstand capability
0.02 VA at VEN = 100 V / 3 0.33 VA at VEN = 230 V Max. 230 V (3-phase) 1.2 x VN = 280 V 2 x VN = 460 V acc. to IEC/EN 60688
Power factor Accuracy Storage
Auxiliary voltage Rated voltage variant 1 Permissible tolerance range Rated voltage variant 2 Permissible tolerance range Power consumption
Multi-range PSU AC/DC 24 to 60 V DC ± 20 % of the rated voltage 110 to 250 V DC and 100 to 240 V AC / 45 to 65 Hz +15/-20 % of the rated voltage 3.5 W per connection
Symmetry Measurement Accuracy Storage
Binary outputs Permissible voltage Permissible current Internal resistance Permissible switching frequency
2 via opto-relays ± 100 V AC/DC 150 mA permament 500 mA for 100 ms £ 10 W 10 Hz
Frequency Accuracy Storage
Measurement functions Number of channels
Calculation method Sampling rate
Resolution Voltage Measuring range Accuracy Storage
3 voltage inputs with common neutral N 3 current inputs Fast Fourier transform 6400 Hz for 50 Hz system frequency 7680 Hz for 60 Hz system frequency per voltage or current input 14 bits
Harmonics Frequency range
0 to 280 V Typically £ 0.1 % of rating Continuously selectable averaging time 1 to 3600 s storage of max., min. and average values possible On limit violation selectable averaging time 10 ms to 3600 s 5 settable limits
Flicker factor Measurement
Accuracy Storage
Accuracy Storage
0 to 6 A Typically £ 0.1 % of rating Continuously selectable averaging time 1 to 3600 s storage of max., min. and average values possible On limit violation selectable averaging time 10 ms to 3600 s 5 settable limits
Typically £ 0.2 % of rating Continuously selectable averaging time 1 to 3600 s storage of max., min. and average values possible On limit violation selectable averaging time 1 to 3600 s 2 settable limits each Typically £ 0.2 % Continuously selectable averaging time 1 to 3600 s storage of max., min. and average values possible On limit violation selectable averaging time 1 to 3600 s 2 settable limits For measurement in 3-phase system voltage and current Typically £ 0.2 % Continuously selectable averaging time 1 to 3600 s storage of max., min. and average values possible On limit violation selectable averaging time 1 to 3600 s 2 settable limits £ 5 mHz Continuously selectable averaging time 1 to 3600 s storage of max., min. and average values possible On limit violation selectable averaging time 1 to 3600 s 2 settable limits Up to 40th harmonic per voltage or current input Acc. to IEC 61000-4-7 Class B Continuously selectable averaging time 1 to 3600 s storage of max., min. and average values possible On limit violation selectable averaging time 1 to 3600 s 2 settable limits per harmonic ASt/AIt or PSt/PIt per voltage input Acc. to IEC 61000-4-15 (IEC 60 868) Continuously averaging time Ast and Pst 10 min averaging time AIt and PIt 120 min
Siemens SR 10.2.5 · 2003
11
SIMEAS Q Power Quality Recorder
Technical Data
Measurement functions (continued)
Electromagnetic compatibility
Active energy, import Active energy, export Reactive energy, capacitive Reactive energy, inductive Apparent energy Accuracy Storage
Immunity 1 MHz burst disturbance test Electrostatic discharge Radiated electromagnetic field disturbance test Burst Surge Conducted disturbances induced by radio-frequency fields
Typically £ 0.2 % Continuously, selectable averaging time 1 to 60 min
Other technical data Stress tests Dielectric test Input circuits against each other Aux. voltage against interface and relay outputs Input circuits against interface and relay outputs Impulse voltage withstand test Input circuits against each other Aux. voltage against interface and relay outputs Input circuits against interface and relay outputs Temperature and climatic stress
Industrial atmosphere SO2 H2S Mechanical stress Vibrations, sinusoidal stationary use Vibrations, sinusoidal transportation Seismic stress stationary use Shock, half-sine wave, stationary use Shock, half-sine wave, for resistance Shock, half-sine wave, continuous shock
Acc. to IEC/EN 61010-1 Acc. to EN 61010-1 3.7 kV, 50 Hz, 1 min 3.7 kV, 50 Hz, 1 min 5.55 kV, 50 Hz, 1 min Acc. to EN 61010-1 6.8 kV, 1.2/50 µs
Acc. to IEC 61000-4-3, ENV 50204 Acc. to IEC 61000-4-4 Acc. to IEC 61000-4-5 Acc. to IEC 61000-4-6 Class III Acc. to EN 61000-4-8 Class IV, IEC 60688, IEC 60255-6
Emission
Acc. to EN 50081-1, EN 50081-2
Conducted interference
Acc. to CISPR 22, EN 55022, VDE 0878 Part 22
Noise field intensity
Acc. to CISPR 11, EN 55011, VDE 0875 Part 11
Disturbances power supply systems
Acc. to IEC 61000-3-3, IEC 61000-3-2
6.8 kV, 1.2/50 µs Communication interface 10.2 kV, 1.2/50 µs Acc. to IEC/EN 60688 -10 °C to 55 °C, no condensation during operation Acc. to IEC 60068-2-42 DIN 40046 Part 36 Acc. to IEC 60068-2-43 DIN 40046 Part 37 Acc. to IEC 60068-2-6, IEC 60255-21-1 Acc. to IEC 60068-2-6, IEC 60255-21-1 Acc. to IEC 60068-3-3, IEC 60255-21-3 Acc. to IEC 60068-2-27, IEC 60255-21-2 Acc. to IEC 60068-2-27, IEC 60255-21-2 Acc. to IEC 60068-2-29, IEC 60255-21-2
Safety Mechanical resistance to shock and impact Degree of protection Housing Terminals Safety class Temperature and protection from propagation of fire Insulation Clearance and creepage distance
Magnetic field
Acc. to EN 61000-6-2, EN 60688 Acc. to IEC 60255-22-1, 2.5 kV, 400 Hz Acc. to IEC 61000-4-2 Class III
Interface Connection technique Transmission options PROFIBUS DP Transmission rate
9-pin SUB-D connector female
From 9 600 Bit/s to 12 MBit/s
RS232 interface Transmission rate
Modem-capable From 300 Bit/s to 115 200 Bit/s
RS485 interface Transmission rate
From 300 Bit/s to 115 200 Bit/s
Data memory Memory for measurement data
Memory up to 70 000 measured values, each with time information
Program memory
256 kByte EEPROM
Real-time clock Internal real-time clock Format Deviation Back-up Synchronization and setting
Year, month, day, hour, minute, second 100 ppm With lithium battery Via communication interface
Dimensions and housing Acc. to IEC 61010-1, IEC 60068-3-75 IP 40 IP 20 Safety class 1 Acc. to IEC 60255-6, IEC 61010-1 Acc. to EN 61010-1, pollution degree 2, overvoltage category III
Dimensions
90 x 75 x 105 mm (W x H x D)
Housing
Snap-on housing for DIN rail mounting Degree of protection IP40
Connection elements - Aux. power supply - Voltage inputs - Current inputs - Binary outputs - Communication interface
Degree of protection IP20 Terminal for max. 2.5 mm2 Terminal for max. 2.5 mm2 Terminal for max. 4 mm2 Terminal for max. 2.5 mm2 9 pin SUB-D connector
Weight Approx. 0.7 kg
12
Siemens SR 10.2.5 · 2003
SIMEAS Q Power Quality Recorder
Selection and Ordering Data
Description
Order No.
Description
Order No.
SIMEAS Q
7KG8000-8oo20
RS232-RS485 converter incl. cable Connecting cable SIMEAS Q to PC Connector: PC side: 9-pin SUB-D connector female SIMEAS Q side: 9-pin SUB-D connector male
7XV5700-oBB00
Interface With PROFIBUS-DP interface With modem-capable RS232 interface With RS485 interface
A B C
Auxiliary voltage 24 to 60 V DC 110 to 250 V DC and 100 to 240 V AC 45 to 65 Hz
SIMEAS Q parameterization package for SIMEAS Q with RS232 interface Comprising: Software SIMEAS Q parameterization for configuration and calibration of SIMEAS Q units with an RS232 interface on a PC Connecting cable SIMEAS Q to PC Length 4 m Connector: PC side: 9-pin SUB-D connector female SIMEAS Q side: 9-pin SUB-D connector male
SIMEAS Q parameterization package for SIMEAS Q with RS485 interface or PROFIBUS DP interface Comprising: Software SIMEAS Q parameterization for configuration and calibration of SIMEAS Q units with RS485 or PROFIBUS-DP interface on a PC Connecting cable SIMEAS Q to PC incl. RS232/RS485 converter Connector: PC side: 9-pin SUB-D connector female SIMEAS Q side: 9-pin SUB-D connector male Plug-in power supply unit for converter Auxiliary voltage 230 V AC 50 Hz 110 V AC 60 Hz
A B
Plug-in power supply unit for converter Auxiliary voltage 230 V AC 50 Hz 110 V AC 60 Hz
0 1
7KG8050-8BC20 SIMEAS Q function module PLC systems For SIMATIC S7-300 and S7-400 with internal or external PROFIBUS-DP interface Delivered on 3 ½ inch diskette
7KG8000-5AA00-0Ao1
Manual German English
7KG8050-8Ao20
Software SICARO Q manager Version 2 Delivered on CD-ROM for connection and operation of more than 10 SIMEAS Q units
A B
7KG8000-5BB20-0Ao1
Manual German English
A B
A B
Siemens SR 10.2.5 · 2003
13
SIMEAS Q Power Quality Recorder
Dimension Drawings
Terminal block
Fig. 19 SIMEAS Q Front view
Side view
Aux.Volt.
Input: Current AC IL1 IL1 IL2 IL2
IL3 IL3
Input: Volt. AC ULN UL1 UL2 UL3
Fig. 20 SIMEAS Q Terminals
14
Siemens SR 10.2.5 · 2003
Notes
The technical data dimensions and weights are subject to change unless otherwise stated on the individual pages of this catalog. The illustrations are for reference only. All product designations used are trademarks or product names of Siemens AG or other suppliers. All dimensions in this catalog are given in mm. For more information about SIMEAS and power quality, see the Internet download area of www.simeas.com The information in this document contains general descriptions of the technical options available, which do not always have to be present in individual cases. The required features should therefore be specified in each individual case at the time of closing the contract.
Responsible for Technical contents: Manfred Unterweger Siemens AG, Abt. PTD PA 13 Nürnberg General editing: Claudia Kühn-Sutiono Siemens AG, Abt. PTD CC Erlangen KGK 10.03 PDF 15 EN 100800 6101/D6298
Siemens SR 10.2.5 · 2003
15
If you have any questions about Power Transmission and Distribution, our Customer Support Center is available around the clock. Tel: +49 180 / 524 70 00 (Subject to charges, Fax: +49 180 / 524 24 71 e.g..: 12 ct/min.) E-Mail:
[email protected] www.siemens.com/ptd-support
Published by Siemens AG Power Transmission and Distribution Power Automation Division Postfach 48 06 90026 Nuernberg Germany www.siemens.com/ptd
Order-No. E50001-K4025-A101-A3-7600