Calculation of Cable Sizing
Short Description
Download Calculation of Cable Sizing...
Description
CALCULATION OF CABLE SIZING 1.
General These design citeria covers choosing the conductor size of power cables for following system. a. 6,3 kV power cable system b. 0,4 kV power cable system
2.
General condition
2.1
Basic deign data : a. b. c. d.
2.2
2.3
Frequency is 50 Hz Ambient air temperature is 40 0C Ambient earth temperature is 20 0C Thermal reistivity (RHO) soil is 90 90 0C.cm/watt
Application of power cable system 6,3 kV power system
:
Up to 400 V power system
:
Insulation and jacket operation temperature a. Normal Continuous Operation
:
90 0C
b. Maximum Emergency Operation
:
130 0C
c. Maximum Short Circuit Operation
:
250 0C
3.
Design Criteria
3.1
Code and Standard a. b. c. d.
3.2
6/10 kV Cooper conductor XLPE insullated, Cooper tapes screen, and Outer sheathed PVC 0,6/1 kV Cooper conductor XLPE insulated, and Outer sheathed PVC
IEC Standard ICEA Standard IEEE Standard NFPA Standard
Cable selection For choosing the conductor size of power cable, the following factor shall be considered : a. Minimum size of conductor conductor based based on short circuit circuit capacity capacity b. Allowable continuous current rating of cable c. Allowable voltage voltage drop cable
3.3
Minimum size of conductor (1) The minimum size of conductor withstand a short circuit current shall be taken into considered following factor : a) Maximum short circuit current b) Maximum duration time of short circuit current c) Under worst conditions, the conductor temperature shall not exceed its maximum short circuit teperature of 250 OC (2) Calculation formula Formula given by the IEC 986 (Shown on below) have been used to select the minimum size of cable. It = K S ( θf + ß )/ ln (θi + ß) The above equation can be simplified as S = I √ t / 143 Where ; I = maximum short circuit current ( r.m.s over duration ) (A) t = maximum duration time of short circuit current(S) K = constant dependig on material of conductor = 226 (AS ½ / mm2) S = cross sectional area of conductor(mm2) O Θf = final temperature of conductor = 250 ( C) O Θi = initial temperature of conductor = 90 ( C) ß = reciprocal of temperature coefficient of resistance of conductor at 0 OC = 234,5 ln = log e (3) The minimum of size of cable to 0,38 kV motor circuit shall be of 2,5 mm2 (4) The minimum size of cable for equipment loads from Distribution Panel Boards ( minimum 6 A MCCB) shall be of 2,5 mm2
3.4
Allowable continuous current rating of cable (1) The allowable continuous current rating cable shall be determined in accordance with standard as follows : a. IEC 287 Calculation of continuous current rating of cables (100 % load factor) b. IEC 364 – 5 – 523 Current –Carrying capacities (2) Cable ampacity shall be at least 100 % of name plate rating full load current for motor. And non motor loads cable ampacity shall be at least 100 % maximum continuous load current. (3) The cable is routed through several type of installation such as run via cable tray, direct burial, underground duct, the cable ampacity shall be base on the part of the cable run with the lowest current rating (4) Calculation of rated currents and starting currents.
The rated current and the starting current of a motor, or a load are based in principle, on the values which provided by the equipment manufacturers (5) If the values not available, the basic equations below shall apply. a. Rated currents In (A) DC AC 1, 2W
Direct Current 2 wire system ........... In = P / V Single phase 2 wire system ........... In = P / V.Cosθ.η
AC 2, 3W
Three phase 3 wire system ........... In = P / √3 V.Cosθ.η
AC 2, 4W
Three phase 4 wire system ........... In = P / √3 V.Cosθ.η
Where : In P V Cosθ η
, Rated Current (A) , Rated Load (kW) or (kVA) , Rated Voltage (V) , Power Factor (at rated load) , Efficiency (at rated load)
b. Starting current; Is(A) Is = Ks x In Where; Is In Ks
, Starting Currents (A) , Rated Currents (A) , Current multiplication at starting
The values for Calculations of Rated Currents and Starting Currents.
No
1
Type of Load
Medium Voltage Motor
Power Factor
Efficiency
0,85
0,95
Current multiple at Starting 7
Power factor at Starting 0,2 0,3
Low Voltage motor
0,85
0,93
6,5
3
Small motor (motor operating valve)
0,8
0,93
4,5
4
Transformer
0,85
N/A
N/A
5
Ac Single phase circuit
0,8
N/A
N/A
6
DC circuit
N/A
N/A
4.0
2
0,6 N/A N/A N/A
c. Allowable voltage drop cable The allowable voltage drop (%) of cable are ; Circuit
Allowable voltage drop Normal operation Starting of motor
Motor Circuit
2,5 %
15 %
Other circuit
3%
N/A
Allowable Voltage Drop (V) = Rated voltage x (%)/100
Formula for voltage drops are : 1. Voltage drop value at rated load : ∆Vn(V) DC
Direct Current 2 wire system AC1ф 2 W Single phase 2 wire system AC1ф 3 W Single phase 3 wire system
∆Vn = 2 . ln . L . Rdc
AC3ф 3 W Three phase 3 wire system AC3ф 4 W Three phase 4 wire system
∆Vn = √3 In . L . (R Cosθ + X Sinθ)
∆Vn = 2 . In . L . (R Cosθ + X Sinθ) ∆Vn = In . L . (R Cosθ + X Sinθ)
∆Vn = In . L . (R Cosθ + X Sinθ)
2. Voltage drop value at starting : ∆Vs(V) DC
Direct Current 2 wire system AC1ф 2 W Single phase 2 wire system
∆Vs = 2 . ls . L . Rdc
AC3ф 3 W Three phase 3 wire system AC3ф 4 W Three phase 4 wire system
∆Vs = √3 Is . L . (R Cosψ + X Sinψ)
∆Vs = 2 . Is . L . (R Cosψ + X Sinψ)
∆Vs = Is . L . (R Cosψ + X Sinψ)
Where: ∆Vn ∆Vs
In Is L
= = = = =
Voltage drop value at rated load (V) Voltage drop value at starting (V) Rated current (A) Starting current (A) Length of cable
R
= Cable resistance at maximum temperatue of cable conductor( R , AC resistance, Rdc, DC resistance) Cosθ = Power factor at motor rated load Cosψ = Power factor at motor starting
4. Cable data’s and Cable Ampacities Base on the above matters and manufacturers cable data’s, the values of cable ampacities can be found as table below;
Cable Datas and Cable Ampacities for Low Voltage
No
Voltage (kV)
Type and Size of CABLE (mm²)
IN GROUND 20 OC (Amp)
IN AIR 30 O C Amp)
Max DC Cable resistance Ampacities at 20 OC (Amp) (Ω/km)
1
0,6/1
N2XY 4 x 2,5
41
32
7,41
22,4
2
0,6/1
N2XY 4 x 4
53
41
4,61
28,7
3
0,6/1
N2XY 4 x 6
67
53
3,08
37,1
4
0,6/1
N2XY 4 x 10
89
71
1,83
49,7
5
0,6/1
N2XY 4 x 16
116
96
1,15
67,2
6
0,6/1
N2XY 4 x 25
151
130
0,727
91
7
0,6/1
N2XY 4 x 35
181
159
0,524
111,3
8
0,6/1
N2XY 4 x 50
208
193
0,387
135,1
9
0,6/1
N2XY 4 x 70
254
245
0,268
171,5
10
0,6/1
N2XY 4 x 95
305
302
0,193
211,4
11
0,6/1
N2XY 4 x 120
347
349
0,153
244,3
12
0,6/1
N2XY 4 x 150
392
400
0,124
280
13
0,6/1
N2XY 4 x 185
441
464
0,0991
324,8
14
0,6/1
N2XY 4 x 240
511
552
0,0754
386,4
15
0,6/1
N2XY 4 x 300
576
677
0,0601
473,9
Cable Datas and Cable Ampacities for Low Voltage No
Voltage (kV)
Type and Size of CABLE (mm²)
IN GROUND 20 OC (Amp)
IN AIR 30 O C Amp)
Max DC Cable resistance Ampacities at 20 OC (Amp) (Ω/km)
1
0,6/1
N2XY 3 x 2,5
41
32
7,41
22,4
2
0,6/1
N2XY 3 x 4
53
41
4,61
28,7
3
0,6/1
N2XY 3 x 6
65
52
3,08
36,4
4
0,6/1
N2XY 3 x 10
89
71
1,83
49,7
5
0,6/1
N2XY 3 x 16
117
96
1,15
67,2
6
0,6/1
N2XY 3 x 25
153
130
0,727
91
7
0,6/1
N2XY 3 x 35
184
159
0,524
111,3
8
0,6/1
N2XY 3 x 50
217
193
0,387
135,1
9
0,6/1
N2XY 3 x 70
269
245
0,268
171,5
10
0,6/1
N2XY 3 x 95
323
302
0,193
211,4
11
0,6/1
N2XY 3 x 120
367
349
0,153
244,3
12
0,6/1
N2XY 3 x 150
412
400
0,124
280
13
0,6/1
N2XY 3 x 185
470
464
0,0991
324,8
14
0,6/1
N2XY 3 x 240
546
552
0,0754
386,4
15
0,6/1
N2XY 3 x 300
632
677
0,0601
473,9
Cable Datas and Cable Ampacities for Medium Voltage Type and Size of CABLE (mm²)
IN GROU ND 20 O C (Amp)
IN AIR 30 O C Amp)
Max DC Cable resistance Ampacities at 20 OC (Amp) (Ω/km)
No
Voltage (kV)
1
6 kV/10 kV
N2XSY 1 x 25
157
162
0,708
105,3
2
6 kV/10 kV
N2XSY 1 x 35
187
195
0,514
126,75
3
6 kV/10 kV
N2XSY 1 x 50
220
234
0,379
152,1
4
6 kV/10 kV
N2XSY 1 x 70
269
292
0,262
189,8
5
6 kV/10 kV
N2XSY 1 x 95
321
354
0,189
230,1
6
6 kV/10 kV
N2XSY 1 x 120
364
407
0,150
264,55
7
6 kV/10 kV
N2XSY 1 x 150
405
460
0,122
299
8
6 kV/10 kV
N2XSY 1 x 185
457
527
0,097
342,55
9
6 kV/10 kV
N2XSY 1 x 240
528
621
0,074
403,65
10
6 kV/10 kV
N2XSY 1 x 300
593
729
0,059
473,85
11
6 kV/10 kV
N2XSY 1 x 400
665
815
0,046
529,75
Cable Datas and Cable Ampacities for Medium Voltage Type and Size of CABLE (mm²)
IN GROU ND 20 O C (Amp)
IN AIR 30 O C Amp)
Max DC Cable resistance Ampacities at 20 OC (Amp) (Ω/km)
No
Voltage (kV)
1
6 kV/10 kV
N2XSEBY 3 x 25
145
141
0,727
91,65
2
6 kV/10 kV
N2XSEBY 3 x 35
173
168
0,524
109,2
3
6 kV/10 kV
N2XSEBY 3 x 50
205
201
0,387
130,65
4
6 kV/10 kV
N2XSEBY 3 x 70
248
250
0,268
162,5
5
6 kV/10 kV
N2XSEBY 3 x 95
293
299
0,193
194,35
6
6 kV/10 kV
N2XSEBY 3 x 120
330
340
0,153
221
7
6 kV/10 kV
N2XSEBY 3 x 150
367
385
0,124
250,25
8
6 kV/10 kV
N2XSEBY 3 x 185
409
434
0,099
282,1
9
6 kV/10 kV
N2XSEBY 3 x 240
459
496
0,0754
322,4
10
6 kV/10 kV
N2XSEBY 3 x 300
503
548
0,0601
356,2
11
6 kV/10 kV
N2XSEBY 3 x 400
552
607
0,047
394,55
5. Calculation of Cable Size for Low Voltage and Medium Voltage 5. 1 Calculation of Cable Size for Low Voltage (0,6/1 kV)
CALCULATION OF CABLE SIZE (N2XY,N2XBY, 0,6/1 kV) FOR MOTORS BASE ON CABLE AMPACITY
No
Cap Motor 3ф (kW)
Current of Motor (Im)
Ratio Im/Ia
Safety Factor (%)
Justify for Safety Factor (25%)
1
4
4 x 2,5
0,30
70
ok
2
0,33
4x4
0,33
67
ok
37,1
0,34
4x6
0,34
66
ok
18,70
37,1
0,50
4x6
0,50
50
ok
15
25,50
49,7
0,51
4 x 10
0,51
49
ok
6
18,5
31,45
49,7
0,63
4 x 10
0,63
37
ok
7
22
37,40
67,2
0,56
4 x 16
0,56
44
ok
8
25
42,50
91
0,47
4 x 25
0,47
53
ok
9
30
51,00
91
0,56
4 x 25
0,56
44
ok
10
37,5
63,75
111,3
0,57
4 x 35
0,57
43
ok
11
45
76,50
111,3
0,69
4 x 35
0,69
31
ok
12
55
93,51
135,1
0,69
4 x 50
0,69
31
ok
13
75
127,51
171,5
0,74
4 x 70
0,74
26
ok
14
95
161,51
244,3
0,66
3 x 120
0,66
34
ok
15
110
187,01
292
0,64
3 x 150
0,64
36
ok
16
132
224,41
324,8
0,69
3 x185
0,69
31
ok
17
160
272,02
386,4
0,70
3 x240
0,70
30
ok
18
200
340,02
509,54
0,67
2x3x120
0,67
33
ok
19
250
425,03
649,6
0,65
2X3x185
0,65
35
ok
20
315
535,53
772,8
0,69
2X3X240
0,69
31
ok
Ampacities of Cable( Ia)
Core size (sq.mm)
Cable size (sq.mm)
6,80
22,4
0,30
5,5
9,35
28,7
3
7,5
12,75
4
11
5
CALCULATION OF CABLE SIZE (N2XY,N2XBY, 0,6/1 kV) FOR MOTORS BASE ON CABLE AMPACITY
No
Cap Motor 3ф (kW)
Current of Motor (Im)
Rated of Cable( Ic)
Core size (sq.mm)
Cable size (sq.mm)
Ratio Im/Ia
Safety Factor (%)
Justify for Safety Factor (25%)
1
4
6,80
32
0,21
4 x 2,5
0,21
79
ok
2
5,5
9,35
41
0,23
4x4
0,23
77
ok
3
7,5
12,75
53
0,24
4x6
0,24
76
ok
4
11
18,70
53
0,35
4x6
0,35
65
ok
5
15
25,50
71
0,36
4 x 10
0,36
64
ok
6
18,5
31,45
71
0,44
4 x 10
0,44
56
ok
7
22
37,40
96
0,39
4 x 16
0,39
61
ok
8
25
42,50
130
0,33
4 x 25
0,33
67
ok
9
30
51,00
130
0,39
4 x 25
0,39
61
ok
10
37,5
63,75
159
0,40
4 x 35
0,40
60
ok
11
45
76,50
159
0,48
4 x 35
0,48
52
ok
12
55
93,51
193
0,48
4 x 50
0,48
52
ok
13
75
127,51
245
0,52
4 x 70
0,52
48
ok
14
95
161,51
349
0,46
3 x 120
0,46
54
ok
15
110
187,01
400
0,47
3 x 150
0,47
53
ok
16
132
224,41
464
0,48
3 x185
0,48
52
ok
17
160
272,02
552
0,49
3 x240
0,49
51
ok
18
200
340,02
698
0,49
2x3x120
0,49
51
ok
19
250
425,03
928
0,46
2X3x185
0,46
54
ok
20
315
535,53
1104
0,49
2X3X240
0,49
51
ok
5. 2 Calculation of Cable Size for Medium Voltage (6/10 kV)
CALCULATION OF CABLE SIZE (N2XSY,N2XSEBY, 6/10 kV) FOR MOTORS BASE ON AMPACITY AND RATED CURRENT OF CABLE Rated Curren t of Cable (Ia)
Ratio Current (Ifm/Ia)
Safety Factor
N2XSEBY 3 x 25
141,00
0,12
88,09
ok
0,32
N2XSEBY 3 x 25
141,00
0,20
79,57
ok
91,25
0,42
N2XSEBY 3 x 25
141,00
0,27
72,77
ok
39,20
91,25
0,43
N2XSEBY 3 x 25
141,00
0,28
72,20
ok
5
40,00
91,25
0,44
N2XSEBY 3 x 25
141,00
0,28
71,63
ok
6
42,40
91,25
0,46
N2XSEBY 3 x 25
141,00
0,30
69,93
ok
7
57,60
91,25
0,63
N2XSEBY 3 x 25
141,00
0,41
59,15
ok
8
57,60
113,75
0,51
N2XSEBY 3 x 25
175,00
0,33
67,09
ok
9
121,60
130,65
0,93
N2XSEBY 3 x 25
201,00
0,60
39,50
ok
10
137,60
130,65
1,05
N2XSEBY 3 x 25
201,00
0,68
31,54
ok
11
183,20
264
0,69
N2XSY 3 x 1 x 120
407
0,45
54,99
ok
12
200,80
194,35
1,03
N2XSEBY 3 x 95
299,00
0,67
32,84
ok
13
211,20
194,35
1,09
N2XSEBY 3 x 95
299,00
0,71
29,36
ok
14
229,60
264
0,87
N2XSY 3 x 1 x 120
407
0,56
43,59
ok
15
275,20
267,8
1,03
N2XSY 3 x 1 x 120
412
0,67
33,20
ok
16
275,20
261,3
1,05
N2XSEBY 2 x 3 x 50
402
0,68
31,54
ok
17
275,20
327,6
0,84
N2XSEBY 3 x 3 x 35
504
0,55
45,40
ok
18
324,00
299
1,08
N2XSY 3 x 1 x 150
460
0,70
29,57
ok
19
344,00
299
1,15
N2XSY 3 x 1 x 150
460
0,75
25,22
ok
20
630,00
299
2,11
N2XSY 3 x 2 x 1 x 150
460,00
0,65
35,00
ok
21
613,60
299
2,05
N2XSY 3 x 2 x 1 x 150
460,00
0,67
33,30
ok
22
630,40
342,55
1,84
N2XSY 3 x 2 x 1 x 185
527
0,60
40,19
ok
23
739,20
342,55
2,16
N2XSY 3 x 2 x 1 x 185
527
0,70
29,87
ok
24
872,00
403
2,16
N2XSY 3 X 2 x 1 X240
621,00
0,70
29,79
ok
25
1250,00
403
3,10
N2XSY 3 X 2 x 1 X240
621,00
0,67
32,90
ok
26
1132,80
403
2,81
N2XSY 3 X 2 x 1 X240
621
0,61
39,19
ok
27
1176,00
403
2,92
N2XSY 3 X 2 x 1 X240
621,00
0,63
36,88
ok
28
1600,00
473,85
3,38
N2XSY 3 x 3 x 1 x 300
729
0,73
26,84
ok
29
1516,80
473,85
3,20
N2XSY 3 x 3 x 1 x 300
729
0,69
30,64
ok
30
2243,20
473,85
4,73
N2XSY 3 x 5 x 1 x 300
729
0,62
38,46
ok
31
3150,00
473,85
6,65
N2XSY 3 x 7 x 1 x 300
729
0,62
38,27
ok
32
3670,40
473,85
7,75
N2XSY 3 x 8 x 1 x 300
729
0,63
37,06
ok
No
Rated Current of Feeder/Mot or (Ifm)
Ampacities of Cable ( Ia)
Core size (sq.mm)
1
16,80
91,25
0,18
2
28,80
91,25
3
38,40
4
Cable size (sq.mm)
Note, Cable No, 8,15,16, and 17 are 12/20 kV
Justify for Safety Factor (25%)
View more...
Comments