1 FEEDER DATA 1.1 Incoming / Outgoing & Designation
Incoming
1.2 Rating, 3 PH
kVA
1.3 Voltage
kV
12000 6.600
1.4 Power Factor (p.f)
0.8
1.5 Efficiency (Effy)
0.9 Earthed / Unearthed (Amp.)
1.6 Type of Earthing 1.7
(a) Current IFL
kVA
1049.73
3 * kV kW (Motor)
(b) Current IFL
Solidly Earthed.
(Amp.)
3 * kV * Effy. * p.f 1.8 Type of Protection (CB / Fuse / MCB / MCCB)
CB
1.9 (a) 3 Phase - Fault Current (Ish)
kA
40
(b) Fault Clearing Time (t)
( Secs)
0.5
1.10 Estimated Length (L)
m
500
1.11 Permissible Voltage drop (a) Running
%
5
%
15
(b) Starting 2 LAYING CONDITIONS
2.1 Ambient Temperature
Tray/
Buried
Trench/
in
Air
ground
Deg. C
Refer TCE design guide
Duct
Derating
Refer cable
Factor
catalogue.
45
0.86 1.00
2.2 Grouping / Spacing with other cables
1
2.3 Thermal Resistivity
Deg.C cm /W
200
2.4 Depth of Burial
mm
750
2.5 Overall Derating Factor
ODF
Value of k (Amp./ sq.mm)
3 TYPE OF CABLE TO BE USED (To be
1.00 0.860
Marked)
Al (Cond.)
Cu (Cond.)
3.1 PVC
75
112
3.2 XLPE (a) 22 / 33 kV
94
140
(b) 11 kV
94
140
(c) 6.6 kV
94
140
(d) 415V
94
140
3.3
4 CABLE SIZING 4.1 Based on Full Load Current (a) Cable rating required
(I / ODF)
1220.61
Amp.
(b) Cable for above rating
Type XLPE 1 CORE
Size (Sq.mm.) No.of runs 800
4.2 Based on Short Circuit Current (For breaker protected feeders only) (a)
Ish * t k
= Area of cond.
Sq. mm 300.897
2
For Contactor Controlled Feeder (b) (HT only) I2t of cable chosen shall be 1.5*I2t of associated fuse
Sq. mm
4.3 Estimated Cable Size ( Higher of 4.1 & 4.2 )
Sq. mm
-
400 5 CHECK FOR VOLTAGE DROP 5.1 Cable Size 5.2 R (at cond. temp) X 5.3
5.4
3 * I FL ( R Cos + X Sin ) * L kV*10000
800
Sq. mm ohm/ph./kM
0.047
ohm/ph./kM
0.091
Load Angle
36.86
% Drop 0.635
3 * ISTG ( R Cos + X Sin ) * L % Drop kV*10000
(Refer Note - 1 below) 5.5 Is the voltage drop within permissible limits? (If not select higher size of cable and check for voltage drop) Cable Size considering Voltage 5.6 Drop 6.0 RECOMMENDED CABLE SIZE (Higher of 4.3 and 5.6)
4.572 Yes / No YES Sq. mm Type XLPE 1 CORE
NOTE: 1) Load angle shall correspond to starting condition of Motor.
1 FEEDER DATA 1.1 Incoming / Outgoing & Designation
Incoming
1.2 Rating, 3 PH
kVA
1.3 Voltage
kV
2500 6.600
1.4 Power Factor (p.f)
0.8
1.5 Efficiency (Effy)
0.9 Earthed / Unearthed (Amp.)
1.6 Type of Earthing 1.7
(a) Current IFL
kVA
218.69
3 * kV kW (Motor)
(b) Current IFL
Solidly Earthed.
(Amp.)
3 * kV * Effy. * p.f 1.8 Type of Protection (CB / Fuse / MCB / MCCB)
CB
1.9 (a) 3 Phase - Fault Current (Ish)
kA
40
(b) Fault Clearing Time (t)
( Secs)
0.16
1.10 Estimated Length (L)
m
50
1.11 Permissible Voltage drop (a) Running
%
5
%
15
(b) Starting 2 LAYING CONDITIONS
2.1 Ambient Temperature
Tray/
Buried
Trench/
in
Air
ground
Deg. C
Refer TCE design guide
Duct
Derating
Refer cable
Factor
catalogue.
45
0.86 1.00
2.2 Grouping / Spacing with other cables
1
2.3 Thermal Resistivity
Deg.C cm /W
200
2.4 Depth of Burial
mm
750
2.5 Overall Derating Factor
ODF
Value of k (Amp./ sq.mm)
3 TYPE OF CABLE TO BE USED (To be
1.00 0.860
Marked)
Al (Cond.)
Cu (Cond.)
3.1 PVC
75
112
3.2 XLPE (a) 22 / 33 kV
94
140
(b) 11 kV
94
140
(c) 6.6 kV
94
140
(d) 415V
94
140
3.3
4 CABLE SIZING 4.1 Based on Full Load Current (a) Cable rating required
(I / ODF)
254.29
Amp.
(b) Cable for above rating
Type XLPE 3 CORE
Size (Sq.mm.) No.of runs 185
4.2 Based on Short Circuit Current (For breaker protected feeders only) (a)
Ish * t k
= Area of cond.
Sq. mm 170.213
1
For Contactor Controlled Feeder (b) (HT only) I2t of cable chosen shall be 1.5*I2t of associated fuse
Sq. mm
4.3 Estimated Cable Size ( Higher of 4.1 & 4.2 )
Sq. mm
-
185 5 CHECK FOR VOLTAGE DROP 5.1 Cable Size 5.2 R (at cond. temp) X 5.3
5.4
3 * I FL ( R Cos + X Sin ) * L kV*10000 3 * ISTG ( R Cos + X Sin ) * L kV*10000
(Refer Note - 1 below) 5.5 Is the voltage drop within permissible limits? (If not select higher size of cable and check for voltage drop) Cable Size considering Voltage 5.6 Drop 6.0 RECOMMENDED CABLE SIZE (Higher of 4.3 and 5.6)
Sq. mm
185
ohm/ph./kM
0.21
ohm/ph./kM
0.0969
Load Angle
36.86
% Drop 0.065 % Drop Yes / No YES Sq. mm Type XLPE 3 CORE
NOTE: 1) Load angle shall correspond to starting condition of Motor.
1 FEEDER DATA 1.1 Incoming / Outgoing & Designation
Incoming
1.2 Rating, 3 PH
kW
1.3 Voltage
kV
1500 6.600
1.4 Power Factor (p.f)
0.85
1.5 Efficiency (Effy)
0.95 Earthed / Unearthed (Amp.)
1.6 Type of Earthing 1.7
(a) Current IFL
kVA 3 * kV kW (Motor)
(b) Current IFL
Solidly Earthed.
(Amp.) 162.50
3 * kV * Effy. * p.f 1.8 Type of Protection (CB / Fuse / MCB / MCCB)
CB
1.9 (a) 3 Phase - Fault Current (Ish)
kA
40
(b) Fault Clearing Time (t)
( Secs)
0.16
1.10 Estimated Length (L)
m
50
1.11 Permissible Voltage drop (a) Running
%
5
%
15
(b) Starting 2 LAYING CONDITIONS
2.1 Ambient Temperature
Tray/
Buried
Trench/
in
Air
ground
Deg. C
Refer TCE design guide
Duct
Derating
Refer cable
Factor
catalogue.
45
0.86 1.00
2.2 Grouping / Spacing with other cables
1
2.3 Thermal Resistivity
Deg.C cm /W
200
2.4 Depth of Burial
mm
750
2.5 Overall Derating Factor
ODF
Value of k (Amp./ sq.mm)
3 TYPE OF CABLE TO BE USED (To be
1.00 0.860
Marked)
Al (Cond.)
Cu (Cond.)
3.1 PVC
75
112
3.2 XLPE (a) 22 / 33 kV
94
140
(b) 11 kV
94
140
(c) 6.6 kV
94
140
(d) 415V
94
140
3.3
4 CABLE SIZING 4.1 Based on Full Load Current (a) Cable rating required
(I / ODF)
188.95
Amp.
(b) Cable for above rating
Type XLPE 3 CORE
Size (Sq.mm.) No.of runs 95
4.2 Based on Short Circuit Current (For breaker protected feeders only) (a)
Ish * t k
= Area of cond.
Sq. mm 170.213
1
For Contactor Controlled Feeder (b) (HT only) I2t of cable chosen shall be 1.5*I2t of associated fuse
Sq. mm
4.3 Estimated Cable Size ( Higher of 4.1 & 4.2 )
Sq. mm
-
185 5 CHECK FOR VOLTAGE DROP 5.1 Cable Size 5.2 R (at cond. temp) X 5.3
5.4
3 * I FL ( R Cos + X Sin ) * L kV*10000 3 * ISTG ( R Cos + X Sin ) * L kV*10000
(Refer Note - 1 below) 5.5 Is the voltage drop within permissible limits? (If not select higher size of cable and check for voltage drop) Cable Size considering Voltage 5.6 Drop 6.0 RECOMMENDED CABLE SIZE (Higher of 4.3 and 5.6)
Sq. mm
185
ohm/ph./kM
0.21
ohm/ph./kM
0.089
Load Angle
36.86
% Drop 0.047 % Drop 0.340 Yes / No YES Sq. mm Type XLPE 3 CORE
NOTE: 1) Load angle shall correspond to starting condition of Motor.
1 FEEDER DATA 1.1 Incoming / Outgoing & Designation
Incoming
1.2 Rating, 3 PH
kW
350
1.3 Voltage
kV
6.600
1.4 Power Factor (p.f)
0.85
1.5 Efficiency (Effy)
0.95 Earthed / Unearthed (Amp.)
1.6 Type of Earthing 1.7
(a) Current IFL
kVA 3 * kV kW (Motor)
(b) Current IFL
Solidly Earthed.
(Amp.) 37.92
3 * kV * Effy. * p.f 1.8 Type of Protection (CB / Fuse / MCB / MCCB)
CB
1.9 (a) 3 Phase - Fault Current (Ish)
kA
40
(b) Fault Clearing Time (t)
( Secs)
0.16
1.10 Estimated Length (L)
m
100
1.11 Permissible Voltage drop (a) Running
%
5
%
15
(b) Starting 2 LAYING CONDITIONS
2.1 Ambient Temperature
Tray/
Buried
Trench/
in
Air
ground
Deg. C
Refer TCE design guide
Duct
Derating
Refer cable
Factor
catalogue.
45
0.86 1.00
2.2 Grouping / Spacing with other cables
1
2.3 Thermal Resistivity
Deg.C cm /W
200
2.4 Depth of Burial
mm
750
2.5 Overall Derating Factor
ODF
Value of k (Amp./ sq.mm)
3 TYPE OF CABLE TO BE USED (To be
1.00 0.860
Marked)
Al (Cond.)
Cu (Cond.)
3.1 PVC
75
112
3.2 XLPE (a) 22 / 33 kV
94
140
(b) 11 kV
94
140
(c) 6.6 kV
94
140
(d) 415V
94
140
3.3
4 CABLE SIZING 4.1 Based on Full Load Current (a) Cable rating required
(I / ODF)
(b) Cable for above rating
44.09
Amp.
Ish * t k
= Area of cond. Type XLPE 3 CORE
Size (Sq.mm.) No.of runs 35
4.2 Based on Short Circuit Current (For breaker protected feeders only) (a)
Sq. mm 170.213
1
For Contactor Controlled Feeder (b) (HT only) I2t of cable chosen shall be 1.5*I2t of associated fuse
Sq. mm
4.3 Estimated Cable Size ( Higher of 4.1 & 4.2 )
Sq. mm
-
185 5 CHECK FOR VOLTAGE DROP 5.1 Cable Size 5.2 R (at cond. temp) X 5.3
5.4
Sq. mm
185
ohm/ph./kM
0.21
ohm/ph./kM
0.089
Load Angle
36.86
3 * I FL ( R Cos + X Sin ) * L % Drop kV*10000
0.022
3 * ISTG ( R Cos + X Sin ) * L % Drop kV*10000
(Refer Note - 1 below) 5.5 Is the voltage drop within permissible limits? (If not select higher size of cable and check for voltage drop) Cable Size considering Voltage 5.6 Drop 6.0 RECOMMENDED CABLE SIZE (Higher of 4.3 and 5.6)
0.159 Yes / No YES Sq. mm Type XLPE 3 CORE
NOTE: 1) Load angle shall correspond to starting condition of Motor.