C264en-cortec_V3_14

Share Embed Donate


Short Description

a...

Description

Ordering information for Modular Compact Bay Controller / Remote Terminal Unit (RTU) MiCOM C264C/264 Disclaimer / Décharge / Descarga Disclaimer Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this document should only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it. We cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.

Décharge Nous avons une politique de développement permanent. Par conséquent, la conception de nos produits risque de subir des modifications à tout moment. Bien que nous nous efforcions de tenir notre documentation à jour, ce brochure ne devra être considérée que comme guide à des fins d’information seulement.

Son contenu n’a pas titre d’offre de vente ou d’assistance technique sur l’application d’un produit mentionné.

Descarga Nuestra política se basa en un desarrollo continuo. Por este motivo, el diseño de nuestros productos puede experimentar cambios en cualquier momento. Realizamos el máximo esfuerzo para producir documentación actualizada. Estas páginas sólo tienen valor informativo. Su contenido no constituye en modo alguno una proposición de venta o asesoramiento en relación con ninguno de los productos mencionados. Declinamos toda responsabilidad por las decisiones que se adopten basándose en su contenido sin notificación al respecto.

MiCOM C264 CORTEC FOR C264-V3/V4, fully assembled device

Version: V3_14

Variants

Notes / Ext. N°

Order N° MiCOM C264C/C264 - Modular Computer for Bay Controller, RTU, PLC application MiCOM C 2 6 4

0

1 1 1

CORTEC CODE Synthesis (for export to Word Docs) : MiCOM C2640111 Basic Model and Components Package rack 4U (CAS2xx) + FBP2xx 1)

Case 40 T for use wo. CT/VT (Compact size), IP52, pin-terminal connection, 6 slots Case 40 T for use with CT/VT (Compact size), IP52, pin-terminal connection, 4 slots

Case 80 T for use without CT/VT (Medium size), IP20, pin-terminal connection, 15 slots

1)

S 1)

1)

L

1)

Case 80 T for use with CT/VT (Medium size), IP20, pin-terminal connection, 14 slots

1)

C

1)

1)

M

Front panel (GHU2xx) Front Panel Leds and L/R switch - IP52 protection -GHU210 (40TE) or GHU211(80TE)

0

Front Panel with Leds + Graphic Display LCD +L/R switch -GHU200(40TE)or GHU201(80TE) - IP52 prot.

1

Simple Blind front panel : GHU220 (40TE ) or GHU 221(80TE)

12)

2

Detachable Front Panel with Graphic Display 40TE (GHU200) + Simple Blind Front panel (GHU22x)

12)

3

Select the cable lenght

Detachable Front Panel with Graphic Display 80TE (GHU201) + Simple Blind Front panel (GHU22x)

12)

4

Select cable

5 6

Select cable Select cable

Detachable Front Panel with Leds 40TE (GHU210) + Simple Blind Front panel (GHU22x) Detachable Front Panel with Leds 80TE (GHU211) + Simple Blind Front panel (GHU22x) Language (including: Front panel labels, HMI)

12) 12)

8)

French ( English)

0

English (English)

1

Spanish (English) German (English)

2 3

Power supply and legacy ports (BIUxxx) about BIU241 :Nominal auxiliary voltage (+/- 20%) for PS - Wetting voltage for 2 digital inputs BIU241-A01 : VA,nom: 24 VDC / Nominal wetting voltage for 2DI: 24 VDC

A

BIU241-A02 : VA,nom: 48 to 60 VDC / Nominal wetting voltage for 2DI: 48/60 VDC

E

BIU241-A03 :VA,nom: 110 to 125 VDC / Nominal wetting voltage for 2 DI: 110/125 VDC

I

BIU241 A04 : VA,nom: 220 VDC and 115 to 230VAC / Nominal wetting voltage for 2 DI: 220 VDC

M

about the BIU100 : only to be interfaced to the Redunded Power supply rack : RPS280 BIU100 : 12V auxiliary voltage, 2 non isolated serial links Factory setted legacy ports N°1/2 on BIU board

15)

R

Consult us for details

8)

Definition : Port N°2:RS232or RS422 or RS485 ; Port N°1: RS232or RS485 Port N°2: RS232 ; Port N°1: RS232

1

Port N°2: RS232 ; Port N°1: RS485 Port N°2: RS485 ; Port N°1: RS485

2 6

CPU and Base Communications (CPU260) Power PC processor board with Ethernet port(s) , 2 serial links, IRIGB input- CPU260-based

14)

CPU260(Type2) , with 1 Ethernet RJ45, IRIG-B input, 2 Serial links (Ref CPU2 = 45196300A5)

5

CPU260(Type2)-based with Pack 2 = IRIG-B input +2 serial links+ 100BaseFL MultiMode Ethernet CPU270(Type3) , with 2*Ethernet RJ45, 64Mb FlashMemory, 1 ppm Oscillator accuracy (Ref CPU270 = 2071590A02 )

6 8

Consult us Consult us

CPU270(Type3) , with 2*Ethernet RJ45, 64Mb FlashMemory, 50ppm Oscillator accuracy (Ref CPU270 = 2071590A01 )

9

Consult us

For CPU with 2 serial links: Factory setted legacy ports N°3/4

8)

Configuration of the legacy Ports N°3/4 :RS232 (non isolated), RS485, Optical settable Port N°3:RS232 (non isolated) Port N°3: Port N°3:

no serial link

; Port N°4: RS232 (non isolated)

RS485(ECU201) Optical(ECU200)

; Port N°4: ; Port N°4:

1

RS485(ECU201) Optical(ECU200)

5 9

Inputs / outputs boards and Ethernet-based switch boards Manufacturing process

0)

Automatic affectation (as standard) of the I/O modules in the basic rack

0

Preferred affectation (customized with extra cost) of the I/O modules in the basic rack

1

consult us

Varnish I/O boards for installations demanding tropicalized conditions No

0

Yes

1

Transducerless Measurements Unit - Direct measuring value acquisition: AC inputs CT/VT

consult us

3) 5) 9)

S=1

Without

2)

0

with TMU200 ( measurement 4*I + 4*U) , Inom: 1 A / 5A, Vnom: 50 to 250 VAC -

9)

With TMU210 A01 (protection) : Vnom: 50 to 250 VAC, Iph=1A, In=1A, Io operating range= 0,1-40Ion With TMU210 A01 (protection) : Vnom: 50 to 250 VAC, Iph=1A, In=5A, Io operating range= 0,1-40Ion With TMU210 A01 (protection) : Vnom: 50 to 250 VAC, Iph=5A, In=5A, Io operating range= 0,1-40Ion With TMU210 A01 (protection) : Vnom: 50 to 250 VAC, Iph=5A, In=1A, Io operating range= 0,1-40Ion With TMU210 A02 (protection) : Vnom: 50 to 250 VAC, Iph=1A, In=1A, Io operating range= 0,01-8Ion With TMU210 A02 (protection) : Vnom: 50 to 250 VAC, Iph=1A, In=5A, Io operating range= 0,01-8Ion With TMU210 A02 (protection) : Vnom: 50 to 250 VAC, Iph=5A, In=5A, Io operating range=0,01-8Ion With TMU210 A02 (protection) : Vnom: 50 to 250 VAC, Iph=5A, In=1A, Io operating range= 0,01-8Ion

17) 17) 17) 17) 17) 17) 17) 17) 17)

With TMU210 A03 (protection) : Vnom: 50 to 250 VAC, Iph=1A, In=1A, Io operating range=0,002-1Ion

17)

With TMU210 A03 (protection) : Vnom: 50 to 250 VAC, Iph=1A, In=5A, Io operating range=0,002-1Ion With TMU210 A03 (protection) : Vnom: 50 to 250 VAC, Iph=5A, In=5A, Io operating range=0,002-1Ion With TMU210 A03 (protection) : Vnom: 50 to 250 VAC, Iph=5A, In=1A, Io operating range=0,002-1Ion

17) 17)

With TMU220 (measurement 4*I / 5*U) : Inom: 1 A / 5A, Vnom: 50 to 250 VAC - 9) Nominal wetting voltage for digital inputs (DIU200(-) or DIU220 (+) or CCU200 (-) or DSP210(-)

18)

)

S -M

1

S -M

2

Refer to note 20)

S -M

3

Refer to note 20)

S -M

4

Refer to note 20)

S -M

5

Refer to note 20)

S -M

6

Refer to note 20)

S -M

7

Refer to note 20)

S -M

8

Refer to note 20)

S -M

9

Refer to note 20)

S -M

A

Refer to note 20)

S -M

B

Refer to note 20)

S -M

C

Refer to note 20)

S -M

D

Refer to note 20)

S -M

F

Consult us

S=12)

U

VA,nom: 24 V DC (- to earth) DIU200-A01 board or CCU200-A01 board or DSP210-A01

0

VA,nom: 48/60 V DC (- to earth) - DIU200-A02 board or CCU200-A02 board or DSP210-A02

1

VA,nom: 110/125 V DC (- to earth) - DIU200-A03 board or CCU200-A03 board or DSP210-A03

2

VA,nom: 220 V DC (- to earth) : DIU200-A04 board or CCU200-A04 board or DSP210-A04

3

VA,nom: 110-125 VDC (-to earth) - DIU200-A03 board or CCU200-A07 board (input setted if > 68% Vn)

6

consult us

VA,nom: 48 V DC (+ to earth) -DIU220-A02 (+ to earth) or CCU200-A02 (- to earth) board or DSP210-A02 (- to earth) VA,nom: 110-125V DC (+ to earth) -DIU220-A03 (+ to earth) or CCU200-A03 (- to earth) board or DSP210-A03 (- to earth)

9 A

consult us consult us

Digital inputs (16 DI) module, each with 16 digital inputs (DIU200A0x or DIU220A0x)

3) 21)

S=12)

16 optically insulated inputs in 8 isolated groups DIU200(or DIU220) quantity = 0 to 4 or 6 for 40TE racks, 0 to 9,A,B,C,D,E or F for 14 or 15 slots in 80TE racks Multi tension-peak-current Digital inputs (16 DI) module, each with 16 digital inputs DIU210

X

3) 13)

S=12)

16 optically insulated inputs in 8 isolated groups DIU210 quantity = 0 to 4 or 6 for 40TE racks, =0 to 9,A,B,C,D,E or F for 14 or 15 slots in 80TE racks

check 13) for quantities

X

3)

Digital outputs (10 DO) module, each with 10 digital outputs (DOU200)

S=12)

8 outputs NO contacts and 2 outputs NO/NC contacts DOU quantity = 0 to 4 or 6 for 40TE racks, =0 to 9,A,B,C,D,E or F for 14 or 15 slots in 80TE racks Mixed (8 DI + 4 DO) module each with 8 digital inputs and, 4 digital outputs

4)

(CCU20x)

X

3)

S=12)

8 optically insulated inputs (in 4 isolated groups) and 4 direct command relays (2 NO contacts) CCU quantity = 0 to 3 or 6 for 40TE racks, =0 to 9,A,B,C,D,E or F for 13 or 15 slots in 80TE racks DC 4 Analog inputs module (C or V transducer connection) each with 4 analogue inputs (AIU201)

19)

X

3)

4 DC Analog Inputs in current or voltage (4 isolated groups) - Maximum of 6*AIU2xx in one case AIU201 quantity = 0 to 4 or 6 for 40TE racks , =0 to 6 for 80TE racks DC 8 Analog inputs module (Current),with 8 analogue inputs (AIU210)

S=12)

X 3)

8 DC Analog Inputs in current (4 isolated groups) - Maximum of 6*AIU2xx in one case AIU210 quantity = 0 to 4 or 6 for 40TE racks , =0 to 6 for 80TE racks Analog output module (Currents) ,with 4 analogue ouputs (AOU200) 4 Analog Outputs

S=12)

X

3), 16)

Consult us

(dedicated to C264-R , RTUs application only)

AOU200 quantity = 0 to 4 for 40TE racks , 0 to 4 for 80TE racks Ethernet-based Switch Unit (SWU20x)

S=12) S=12)

x

3)

Without

0

SWU200 - With four 10/100BaseT Ethernet ports (RJ45)

1

SWU202- With two 100BaseF MultiMode Ethernet ports (ST) and four 10/100BaseT Ethernet ports (RJ45)

3

SWU204- With two 100BaseF MonoMode Ethernet ports (SC) and four 10/100BaseT Ethernet ports (RJ45)

5

Ethernet-based Switch Redundant Unit (SWR20x)

3) -

S=12)

For Ethernet Redunded Ring

SWR202 or SWR212 -With two 100BaseF MultiMode Ethernet ports (ST) + four 10/100BaseT Ethernet ports (RJ45)

6

refer note 21)

SWR204 or SWR 214 -With two 100BaseF MonoMode Ethernet ports (SC) + four 10/100BaseT Ethernet ports (RJ45)

7

refer note 21)

A

refer note 21)

Ethernet-based Switch Dual Humming Unit (SWD20x)

3)

SWD202 or SWD212 - With two 100BaseF MultiMode Ethernet ports (ST) + four 10/100BaseT Ethernet ports (RJ45)

190235036.xls.ms_office C264 CORTEC 11/21/2013

2)

S=1

Page 2

MiCOM C264 CORTEC FOR C264-V3/V4, fully assembled device

Version: V3_14

Variants

Notes / Ext. N°

Order N° MiCOM C264C/C264 - Modular Computer for Bay Controller, RTU, PLC application MiCOM C 2 6 4 SWD204 or SWD214 -With two 100BaseF MonoMode Ethernet ports (SC) + four 10/100BaseT Ethernet ports (RJ45)

0

1 1 1 refer note 21)

B

Communications Ethernet-based SCADA communication protocol ( to upper levels SCADA, DCS, Master Station, ...) Without IEC 60870-5-104

0 1

Legacy serial SCADA communication protocols (to upper levels: SCADA, DCS, Master station, etc)

10)

Without Up to two SCADA links in: IEC 60870-5-101, DNP3, Modbus Legacy IED communication protocols (To lower levels: Relays, PLC, RTU, etc)

0 1 11)

Without Up to 4 IEDs links in: DNP3, MODBUS, IEC 60870-5-103, IEC 60870-5-101

0 1

PLC Automation User applications

6)

Disabled Enabled ISaGRAF run-time for Programmable Logic, Automation, etc.

0 1

Softwares version Specific software version

11)

No Software loaded

N

Option CD3: No Software loaded, delivered with one CD-ROM including the C264 software (PACIS V3)

C

Option CD4 : No Software loaded, delivered with one CD-ROM including the C264 software (PACIS V4)

D

Option V4 : With the C264 current Software version loaded (for PACIS V4.xx) -No CD delivered

R

Option V3 : With the C264 current Software version loaded (for PACIS V3.xx) -No CD delivered

S

Built in applications

6)

Disabled Synchrocheck/Voltage Regulation/ Autorecloser enabled

0 1

Cable Lenght for Detachable front Panel No cable

0

Cable For Detachable Front Panel : 3 m

3

Associated equipments, Accesories, Softwares and Manuals Equipments : Fitting a 19" mounting rack

FXOO21101

Wall Mounted Adaptater - for 40TE Racks (WMA 40TE) Ref = A00043409100031

Consult us

Wall Mounted Adaptater - for 80TE Racks - (under validation - Consult us)

Consult us

Serial printer (80 columns) - 115/230 VAC Power supply inverter 48 VDC / 115/230 VAC

Consult us

Power supply inverter 125 VDC / 115/230 VAC Ethernet cable (crossed-Blue) for PC connection - 2m

Consult us

Ethernet cable (direct-Yellow) for Switch/Hub connection - 20cm

9565934

Ethernet cable (direct-Yellow) for Switch/Hub connection - 2m

9565935

Ethernet cable (direct-Yellow) for Switch/Hub connection - 3m

9565936

RS232 cable for PC Front panel connection (3m) Cable for Detachable front Panel (3 m)

9565996

Cable for direct connection of front Panel (30 cm)

2071098A01

Clock synchoniser - DIN rail model / IRIG-B output Clock synchoniser - 19" mounting rack / IRIG-B output

Consult us

Boards extractor Cache for empty I/O slots

2070860

I/Os connectors (24 points)

9565869

Connectors (3 points)

9566235

Consult us

9565933

2071098A04

Consult us

2071038

Softwares : C264 Standalone Configuration tool - SCT

6)

6)

PACIS SCE Configuration tool 6) ISaGRAF software PLC Editor PACIS SMT System Management tool Manuals :

Consult us Consult us Consult us

6)

Consult us

Technical and Operation guides in English Technical and Operation guides in French

Consult us

Technical and Operation guides in Spanish Technical and Operation guides in German

Consult us

Consult us

Consult us

CD-ROM documentation: Technical and Operation guides - multilingual pdf documentations (English, French, Spanish and German)

Consult us

Remind of the CORTEC Code Synthesis : for export to Word documents : MiCOM C2640111 Legend: No commercial availability - consult us for more info. Available fo commercial orders, in association with Pacis system order

0)

The automatic affectation is the following: from "C" to "P" slot : SWX20x, AIU201 AIU210, DOU200, AOU200, free slots if any, CCU200, DIU210, DIU200 ,TMU200 The preferred affectation of the I/O modules will be defined separately with the "CUSTOMISATION" datasheet. This manufacturing process induce extra costs. You are strongly advised to contact the marketing department to calculate the associated extra cost.

1)

Different racks exist depending of user-selected CT/VT(TMU) & basic case size : For 40T case with TMU200 (Measurement CT/VT): CAS242 (Available slots: N=4) - For 40T case with TMU210 (Protection CT/VT): CAS242 (Available slots: N=3). For 40T case without any TMUxxx (CT/VT) : CAS241 (Available slots: N=6). For 80T case with TMU200 (Measurement CT/VT): CAS282 (Available slots: N=14) - For 80T case with TMU210 (Protection CT/VT): CAS282 (Available slots: N=13). For 80T case without any TMUxxx (CT/VT): CAS281 (Available slots: N=15).

2)

Module slot size

3)

The sum of slots (S) to receive modules must not exceed the maximum value N (available slots), indicated for each case separately

4)

Output relays (2-pole) for switchgear operation

5)

Required for Synchrocheck, disturbance recorder and direct measurements

6)

According to specification

7)

Voltage regulation needs UCA2 Ethernet-based communication

8)

User-selected (factory setting underlined).

9)

With TMU200 and TMU220, the option includes the DSP200 daughter board, plugged on the CPU260 module With TMU210 the option includes the DSP210 daughter board plugged on the CPU260 module - The DSP2x0 are using Floating-Point Digital Signal Processor (DSP)

10) The sum of communication links (legacy SCADA and IEDs) must not exceed the maximum communication ports available. 11) For Specific Software version complete the Software CORTEC (sheet C264 SOFT) For C264-R multirack applications, Select " No software loaded"

12) For Detachable Front panel, define the lenght of the required cable ; the Blind panel size depend on the Rack size. for DIU210 ( Multi tension PeakCurrent board),

13) Not to be mixed with DIU200 in a same rack

Maximum nb of boards depend on the voltage level, the case size, the CT/VT presence :

14) for CPU260:only one Ethernet Port available -> exclusion of use between RJ45 copper link and optical if required in option 15) BIU100 : only in association to RPS280 (consult marketing) , Do not exist for tropicalised /Varnished version Warning : specific EMC levels for this power supply - consult Marketing before use

190235036.xls.ms_office C264 CORTEC 11/21/2013

Page 3

Basic I nterface Unit board

BI U2 4x

PIN Output relays 1

O 2

2 3

O 1

4

Watchdog

5 6 7 8

+ -

VIN -

DI1

+ -

VIN -

DI2

BACK

9 10 11

RS232/

12

RXD / T+

13

G ND

14

TXD / T-

Serial

RS485

link 1 #

15 G ND 16

RS232/ CTS RXD / T+ TXD / TRTS / R+

17 18 19

RS422

link 2

R- (RS422) DCD

20

Serial

RS485

#

21 22 23

+

24

-

Vaux

Power supply -

Central Processing Unit, Ethernet-based and optional communications board

CPU2 60

1 2 3 4 5 6 7 8

CONNECTO RS

10/100 Base-TX Ethernet-based link RJ-45 (female)

OPTIONAL LINKS: 100 Base-FX Ethernet-based link

1 2

DCD RXD / T-

3

TXD / T+

5

GND

7 8

RTS CTS

BACK

RS232

3

Serial link 3

5

9

4

8 7

2

6

1

ST® (female)

1

3 5

5

9

4

8

3

7

2

6

1

2

7 8

DCD RXD / T-

#

RS232

TXD / T+

Serial

GND

link 4

RTS CTS

IRIG-B link

#

CPU270 Connector description : Scheme Under construction

BACK

AIU210- connection

BACK

Digital Output U nit board

PIN

DO U20 0

Signal outputs

1 2

DO 1

3 4

DO 2

5 6

DO 3

7 8

DO 4

9 10

DO 5

11 12

DO 6

13 14

DO 7

15 16

DO 8

17 18 19 20 21

DO 9

22 23 24

DO 10

BACK

Circuit breaker Control Unit board

CCU 2 0x

PIN 1 2

Digital Inputs + -

VIN -

DI1

+ -

DI3

+ -

DI5

+ -

DI7

+ -

VIN -

DI2

3 4 5

+ -

VIN -

VIN -

DI4

6 7 8

+ -

VIN -

VIN -

DI6

9 10 11

+ -

VIN -

VIN -

DI8

BACK

12 13 14 15 16 17

Digital Outputs B A A B

CO 1

CO 2

18 19 20 21 22 23 24

B A A B

CO 3

CO 4

Digital Input U nit

DI U2 0x

board

Signal inputs

PIN 1 2

+ -

VIN -

DI1

+ -

DI3

+ -

DI5

+ -

DI7

+ -

VIN -

DI2

3 4 5

+ -

VIN -

VIN -

DI4

6 7 8

+ -

VIN -

VIN -

DI6

9 10 11

+ -

VIN -

VIN -

DI8

BACK

12 13 14

+ -

VIN -

DI9

+ -

DI11

+

VIN -

DI10

15 16

+

17

-

VIN -

VIN -

-

DI12

18 19

+

20

-

VIN -

DI13

+

VIN -

-

DI14

21 22

+

23

-

24

VIN -

DI15

+ -

VIN -

DI16

Transducerless Measurement U nit 1A connections

Transducerless Measurement U nit 5A connections

Transducerless current inputs

PIN 1

TM U 2 00

N1

1

2

3

4

5

6

7

8

N2

N1 3

4

5

6

7

8

N2

C1 C2

C1 C2

B1

9

10

9

10

11

12

13

14

15

16

17

18

19

20

21

22

24

B2

B1 11

12

13

14

B2

A1 A2

A1 15

16

17

18

19

20

A2

Transducerless voltage inputs U1

21

22

U2 V1

24

V2 W1

23

25

26

W2

25

26

27

28

N2

V2 W1

N1 28

U2 V1

23

27

Transducerless voltage inputs U1

W2 N1 N2

TMU210 : Protection Module : Scheme under preparation

Transducerless current inputs

PIN 2

TM U 2 00

tection Module :

Definitions: AC AIU

Alternative Current Analog Input Unit Commonly Voltage or Current DC signals delivered by transducers

Bay BIU

Set of LV, MV or HV plants (switchs and transformer) and devices (Protective, Measurement…). Usually around a Circuit Breaker and controlled by a bay computer. Basic Interface Unit

CAS CBC CCU CPU CT CT/VT

Package rack CASe Compact Bay Controller Circuit breaker Control Unit Central Processing Unit Current Transformer Current and Voltage Transformers

DC DCS DI DIU DO DOU DSP

Direct Current Digital Control System Digital Inputs Digital Inputs Unit Digital Outputs Digital Output Unit Floating-Point Digital Signal Processor

FBP

Front Back Plane

GHU

Graphic Human interface Unit

HMI

Human Machine Interface

I IED IP52

Current Intelligent Electronic Device IP52 environmental protection Protected against dust and direct sprays of water up to 15 degrees from vertical - Indoor The number 5 means that it is especially protected against the dust The number 2 means that it is especially protected against projections of water

MiCOM C

MiCOM Computer series

NC NEMA

NO

Normally Closed (for a relay or a contact) National Electrical Manufacturers Association A group which issues standards for the manufacture of electrical equipment. NEMA enclosure types: (abbreviated) (IEC equivalents in parenthesis) · Type 1: General purpose - Indoor. (IP10) · Type 5: Dusttight, drip-proof - Indoor (IP52) · Type 12: Dusttight and driptight - Indoor (IP52) · Type 12K: Dusttight and driptight, with knockouts - Indoor (IP52) Normally Open (for a relay or a contact)

PC PLC PQ

Personnal Computer Programmable Logic Controller Power Quality

RTU

Remote Terminal Unit

SCADA ST® SWD SWR SWU TMU

Supervisory Control And Data Acquisition

U

Voltage

VT

Voltage Transformer

Ethernet-based SWitch Dual Humming unit Ethernet-based SWitch Redondant unit Ethernet-based SWitch Unit Transducerless Measurements Unit

View more...

Comments

Copyright ©2017 KUPDF Inc.
SUPPORT KUPDF