C264 - Expertise Maintenance Guide
Short Description
Expertise...
Description
Transmission & Distribution Protection & Contrôle
PACIS C264 – EXPERTISE MAINTENANCE GUIDE
APPROVAL OF THE DOCUMENT NAME
FUNCTION
S.GADAY
CHEF PROJET C264
JM. BOISSET
PACIS PROJECT MANAGER
DATE
VISA
EVOLUTION OF THE DOCUMENT EDITION Z
DATE 15/10/07
DRAFT JM. BOISSET
DESCRIPTION OF THE EVOLUTION Creation of the document
Désignation: C264 – Expertise Maintenance Guide Date: 15/10/07
Page: 1/29
Edition: Z
Transmission & Distribution Protection & Contrôle
1
INTRODUCTION.........................................................................................................6
2
Connecting the shell.................................................................................................7
3
General traces...........................................................................................................8 3.1
HELP.............................................................................................................................. 8
3.2
help................................................................................................................................ 8
3.3
OdLogLevel x................................................................................................................ 8
3.4 SET_TRACES(task ID,msk,status)..............................................................................8 3.4.1 Main Task identification number...............................................................................8 3.4.2 Communication Task identification number..............................................................9 3.4.3 Traces mask............................................................................................................. 9 3.4.4 Communication traces............................................................................................10
4
5
6
7
3.5
S_DBTEST_print_bay.................................................................................................11
3.6
S_DBTEST_print_norgint_list....................................................................................11
3.7
S_DBTEST_print_computer_wiring..........................................................................12
TRACES FOR OPERATING MODE.........................................................................13 4.1
SET_DEV_MODE x......................................................................................................13
4.2
SET_MAINT................................................................................................................. 13
4.3
SET_ACTIVE................................................................................................................ 13
Traces for the drivers and the communication protocols..................................14 5.1
traces_sccx=y.............................................................................................................14
5.2
traces_apieth x............................................................................................................ 14
5.3
TunRSLines.................................................................................................................14
5.4
TunRSIed x..................................................................................................................14
5.5
S_DBTEST_print_line_info........................................................................................14
Traces for DIGITAL Inputs (DI)...............................................................................15 6.1
active_di board,input,state,valid...............................................................................15
6.2
aff_di_info board,input...............................................................................................15
6.3
aff_di_state board,input.............................................................................................15
6.4
aff_di_board_state board,type...................................................................................15
Traces for ANALOGUE Inputs (AI)........................................................................16 7.1
aff_ai_info board,input...............................................................................................16
7.2
aff_ai_data board,input..............................................................................................16
Désignation: C264 – Expertise Maintenance Guide Date: 15/10/07
Page: 2/29
Edition: Z
Transmission & Distribution Protection & Contrôle
7.3
aff_ai_board_data board............................................................................................16
7.4
set_ai_data index,state,value....................................................................................16
8
Traces for CT/VT measurements...........................................................................17 8.1
CTVT_GET_MEAS.......................................................................................................17
8.2
aff_ctvt_config............................................................................................................17
8.3
aff_ctvt_data............................................................................................................... 17
9
Traces for DIGITAL OUTputs (DO).........................................................................18 9.1
aff_do_data.................................................................................................................18
9.2
get_state_do board.....................................................................................................18
9.3
active_ccu board,channel,order................................................................................18
9.4
active_dou board,channel,order................................................................................18
10
Traces for Binary Inputs (BI)...............................................................................19
10.1
aff_bi_info bi_norgint..............................................................................................19
10.2
aff_bi_grp_info bi_norgint......................................................................................19
10.3
aff_bi_state2 bi_norgint.........................................................................................19
10.4
active_bi norgint, order...........................................................................................19
10.5
get_di_norgint..........................................................................................................19
11
Traces for Controls..............................................................................................20
11.1
aff_co_info co_norgint...........................................................................................20
11.2
aff_all_co_info norgdeb, norgfin............................................................................20
11.3
aff_sp_info sp_norgint...........................................................................................20
12
Traces for counters (CT).....................................................................................21
12.1
aff_ct_data ct_norgint............................................................................................21
12.2
aff_ct_info ct_norgint.............................................................................................21
13
Traces for measurements (MV)...........................................................................22
13.1
aff_dm_info dm_norgint.........................................................................................22
13.2
aff_meas_info norgint............................................................................................22
13.3
aff_meas_data norgint...........................................................................................22
13.4
active_meas norgint,value,quality.........................................................................22
13.5
active_from_ai norgint,type,value,quality.............................................................22
13.6
active_meas_ctvt norgint,value,quality.................................................................22
13.7
active_meas_ied norgint,value,quality..................................................................22
Désignation: C264 – Expertise Maintenance Guide Date: 15/10/07
Page: 3/29
Edition: Z
Transmission & Distribution Protection & Contrôle
13.8
aff_sig_info norgint................................................................................................23
13.9
aff_sig_data norgint...............................................................................................23
13.10
active_sig norgint,value,quality.............................................................................23
13.11
aff_spi_info norgint................................................................................................23
13.12
aff_spi_data norgint...............................................................................................23
13.13
active_spi norgint,value,quality.............................................................................23
14
Traces for autorecloser, switchgear and modules...........................................24
14.1
S_DBTEST_print_ar_item x...................................................................................24
14.2
S_AUTREC_get_ar_context....................................................................................24
14.3
S_AUTREC_get_ar_state........................................................................................24
14.4
S_DBTEST_print_cb_item x..................................................................................24
14.5
aff_sp_cb_info x.....................................................................................................24
14.6
aff_discsw_info........................................................................................................24
14.7
aff_module_info.......................................................................................................24
15
Traces for time synchronisation.........................................................................25
15.1
synchroInfoShow....................................................................................................25
15.2
synchroBdShow......................................................................................................25
16
Traces for alarms.................................................................................................26
16.1
aff_alarm_info x......................................................................................................26
16.2
ALARM_HELP..........................................................................................................26
16.3
read_alarm_header..................................................................................................26
16.4
read_diff_alarm_header..........................................................................................26
17
Traces for ATCC...................................................................................................27
17.1
18
ccaCatcAff
donGen,group,node,nivTens,device,transf.....................................27
Traces for Fast Automatism et Interlock...........................................................28
18.1
aff_eql_info..............................................................................................................28
18.2
aff_eql_data
19
index_eql.........................................................................................28
Traces for Redundancy.......................................................................................29
19.1
aff_red_data............................................................................................................. 29
Désignation: C264 – Expertise Maintenance Guide Date: 15/10/07
Page: 4/29
Edition: Z
Transmission & Distribution Protection & Contrôle
1 INTRODUCTION The aim of this document is to propose the basis of expertise of the C264 application, based on the shell traces concept.
Désignation: C264 – Expertise Maintenance Guide Date: 15/10/07
Page: 5/29
Edition: Z
Transmission & Distribution Protection & Contrôle
2 CONNECTING THE SHELL To connect the shell you need : a straight cable. a tool like Tera-Term-Pro or HyperTerminal. Communication parameter are : 19200 bauds 8 bits No parity 1 stop No control
Désignation: C264 – Expertise Maintenance Guide Date: 15/10/07
Page: 6/29
Edition: Z
Transmission & Distribution Protection & Contrôle
3 GENERAL TRACES 3.1
HELP
Action : display the debug control available in the C264 application Parameters : none
3.2
help
Action : display the debug control available in the VxWorks kernel Parameters : none
3.3
OdLogLevel x
Action : display traces in the UCA2 / IEC61850 agency Parameters : x = 1 : trace activated X = 0 : trace desactivated
3.4
SET_TRACES(task ID,msk,status)
Action : activate / desctivate the traces Parameters : task_ID : task identification number (refer to the table below) Msk : traces level (refer to the table below) Status : 1 trace activated with the specified level 0 trace desactivated 3.4.1 N° 01 02 04 06 13 18 20 21 22 24 25 28 37 46
Main Task identification number Name T01CTRL T02SUPERV T04HDLDI T06HDLAI T13SYNCHRO T18COND T20GESTTS T21GESTCT T22GESTTM T24GESTTC T25ALARM T28ISAGRAF T37ILOCK T46AUTREC
Role Control Task (used to managed the Digital Output selfcheck) Supervision task Handler for DI acquisition Handler for AI acquisition Time synchronisation task Control management task xPS management task Counters management task MV management task xPC management task Alarm management task ISAGRAF management task Interlock / PSL management task Autorecloser management task
Désignation: C264 – Expertise Maintenance Guide Date: 15/10/07
Page: 7/29
Edition: Z
Transmission & Distribution Protection & Contrôle
N° 47 49 53 54 62 63
3.4.2
Name T47RED T49SYCHECK T53ATC T54HMILCD T62TMU210 T63MICOMS1
Communication Task identification number
N° 32 35 36 38 40 42 48 51 55 58 59 60 61 3.4.3
Role Redundancy management task Synchrocheck management task ATCC management task Local HMI management task Protection function management task MiCOM S1 for protection management task
Name T32DNP3M T35IECM2 T36T103M7 T38SERMAN T40CLIMAN T42MODBM2 T48MODBM7 T51DNP3S T55T101S T58T101M7 T59T104S T60MODBS7 T61DNP3E
Role Master DNP3 communication task Master T101/T103 level 2 communication task Master T103 level 7 communication task Station Bus Server management task Station Bus Client management task Master Modbus level 2 communication task Master Modbus level 7 communication task Slave DNP3 communication task Slave T101 communication task Master T101 level 7 communication task Server T104 communication task Slave Modbus level 7 communication task Slave DNP3 IP communication task
Traces mask
Bit 0 1 2 3 4 5 6 7
Description Input messages Output messages Messages during task treatment Level 2 traces (if exist) Not used Not used Not used Not used
Example : SET_TRACES(20,3,1) activates display of input / output messages of the GESTTS task.
Désignation: C264 – Expertise Maintenance Guide Date: 15/10/07
Page: 8/29
Edition: Z
Transmission & Distribution Protection & Contrôle
3.4.4
Communication traces
The shell function « TRANS_PRINT_TRACE_LEVELS » lists the different trace levels. Trace name TRANS_TRACE_NONE TRANS_TRACE_ERROR TRANS_TRACE_TRAME TRANS_TRACE_DATA TRANS_TRACE_CNX TRANS_TRACE_MES_EMI TRANS_TRACE_MES_REC TRANS_TRACE_TRT_TS TRANS_TRACE_TRT_TC TRANS_TRACE_TRT_TM TRANS_TRACE_TRT_PERT TRANS_TRACE_TRT_TUN TRANS_TRACE_SYNCHRO TRANS_TRACE_TRT_EVT TRANS_TRACE_EMI_TM TRANS_TRACE_EMI_TS TRANS_TRACE_INIT TRANS_TRACE_TRT_GI TRANS_TRACE_TRT_CT TRANS_TRACE_PROTOCOL TRANS_TRACE_TRT_GEN TRANS_TRACE_TRT_FIC TRANS_TRACE_TRT_SPI TRANS_TRACE_TRT_SOE TRANS_TRACE_TRT_POL TRANS_TRACE_TRT_SP TRANS_TRACE_TRT_SIG
Level 0x0000 0x0001 0x0002 0x0004 0x0008 0x0010 0x0020 0x0040 0x0080 0x0100 0x0200 0x0400 0x0800 0x1000 0x2000 0x4000 0x8000 0x10000 0x20000 0x40000 0x80000 0x100000 0x200000 0x400000 0x800000 0x1000000 0x2000000
Comment No trace are allowed Trace of error Trace of sent / received frames Trace of sent / received data Trace of indication of connection / disconnection of IED Trace of sent messages Trace of received message Trace of BI management Trace of command management Trace of measurement management Trace of disturbance management Trace of tunneling management Trace of synchronisation frames sent to IED Trace of events in modbus protocol Trace of TM sent to Application after processing Trace of TS sent to Application after processing Trace of initialisation. Trace of General Interrogation Trace of Counter management Trace from Triangle SCL Stack General treatment Trace for file upload or download Trace for SPI management Trace for SOE management Trace for polling Trace of SetPoint management Trace of SIG (MPS) Management
Désignation: C264 – Expertise Maintenance Guide Date: 15/10/07
Page: 9/29
Edition: Z
Transmission & Distribution Protection & Contrôle
The following table indicates which trace levels are implemented for which process : Trace name TRANS_TRACE_ERROR TRANS_TRACE_TRAME TRANS_TRACE_DATA TRANS_TRACE_CNX TRANS_TRACE_MES_EMI TRANS_TRACE_MES_REC TRANS_TRACE_TRT_TS TRANS_TRACE_TRT_TC TRANS_TRACE_TRT_TM TRANS_TRACE_TRT_PERT TRANS_TRACE_TRT_TUN TRANS_TRACE_SYNCHRO TRANS_TRACE_TRT_EVT TRANS_TRACE_EMI_TM TRANS_TRACE_EMI_TS TRANS_TRACE_INIT TRANS_TRACE_TRT_GI TRANS_TRACE_TRT_CT TRANS_TRACE_PROTOCOL TRANS_TRACE_TRT_GEN TRANS_TRACE_TRT_FIC TRANS_TRACE_TRT_SPI TRANS_TRACE_TRT_SOE TRANS_TRACE_TRT_POL
IECM2 X X X X
X X
X
T103M7 MODBM2 MODBM7 X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
DNP3M X X X X X
T101S X
X
X
X X X
X
X
X X X X X X
X
X X X X X X X X
Nota : to have the complete list of task, type « i » on the shell
3.5
S_DBTEST_print_bay
Action : display the electrical configuration Parameters : none
3.6
S_DBTEST_print_norgint_list
Action : display the list of configured norgint Parameters : none
Désignation: C264 – Expertise Maintenance Guide Date: 15/10/07
Page: 10/29
Edition: Z
Transmission & Distribution Protection & Contrôle
3.7
S_DBTEST_print_computer_wiring
Action : display the computer wiring Parameters : none
Désignation: C264 – Expertise Maintenance Guide Date: 15/10/07
Page: 11/29
Edition: Z
Transmission & Distribution Protection & Contrôle
4 TRACES FOR OPERATING MODE 4.1
SET_DEV_MODE x
Action : change the computer operating mode Parameters : x=1 -> test mode x=2 -> active mode x=3 -> stand-by mode x=4 -> maintenance mode
4.2
SET_MAINT
Action : change the computer mode to maintenance Parameters : none
4.3
SET_ACTIVE
Action : change the computer mode to operational Parameters : none
Désignation: C264 – Expertise Maintenance Guide Date: 15/10/07
Page: 12/29
Edition: Z
Transmission & Distribution Protection & Contrôle
5 TRACES FOR THE DRIVERS AND THE COMMUNICATION PROTOCOLS 5.1
traces_sccx=y
Action : display the input and output frames for a legacy bus Parameters : x=[1,2,3,4] : port number defined in configuration y=16 : trace activated y=0 : trace desactivated
5.2
traces_apieth x
Action : display the input and output frames on TCP-IP Parameters : x=16 : trace activated x=0 : trace desactivated
5.3
TunRSLines
Action : display the protocol used on the configured legacy bus Parameters : none
5.4
TunRSIed x
Action : display the information associated to the IEDs connected to the legacy bus number x Parameters : x = legacy bus number (0 for SCC1, 1 for SCC2, …)
5.5
S_DBTEST_print_line_info
Action : display the information associated to the configured legacy bus Parameters : none
Désignation: C264 – Expertise Maintenance Guide Date: 15/10/07
Page: 13/29
Edition: Z
Transmission & Distribution Protection & Contrôle
6 TRACES FOR DIGITAL INPUTS (DI) 6.1
active_di board,input,state,valid
Action : simulate a DI state change Parameters : board : board number input : channel number state : DI state (1=SET, 0=RESET) valid: DI quality (values to be defined)
6.2
aff_di_info board,input
Action : display configuration attributes of a DI Parameters : board : board number input : channel number
6.3
aff_di_state board,input
Action : display current state of a DI Parameters : board : board number input : channel number
6.4
aff_di_board_state board,type
Action : display current state of all board channels Parameters : board : board number type : board type (0=DIU, 1=CCU)
Désignation: C264 – Expertise Maintenance Guide Date: 15/10/07
Page: 14/29
Edition: Z
Transmission & Distribution Protection & Contrôle
7 TRACES FOR ANALOGUE INPUTS (AI) 7.1
aff_ai_info board,input
Action : display configuration attributes of an AI Parameters : board : board number input : channel number
7.2
aff_ai_data board,input
Action : display current state and value of an AI Parameters : board : board number input : channel number
7.3
aff_ai_board_data board
Action : display current state and value of all board channels Parameters : board : board number
7.4
set_ai_data index,state,value
Action : change the value and state of an AI Parameters : index : AI index (input number + board number*number of inputs per board) state : AI quality (values to be defined) value : AI value
Désignation: C264 – Expertise Maintenance Guide Date: 15/10/07
Page: 15/29
Edition: Z
Transmission & Distribution Protection & Contrôle
8 TRACES FOR CT/VT MEASUREMENTS 8.1
CTVT_GET_MEAS
Action : display value and quality of all measurements from TMU200/220 board Parameters : none
8.2
aff_ctvt_config
Action : display configuration attributes of the TMU200/220 board Parameters : none
8.3
aff_ctvt_data
Action : display data from TMU200/220 board associated to the synchrocheck function Parameters : none
Désignation: C264 – Expertise Maintenance Guide Date: 15/10/07
Page: 16/29
Edition: Z
Transmission & Distribution Protection & Contrôle
9 TRACES FOR DIGITAL OUTPUTS (DO) 9.1
aff_do_data
Action : display state of all channels of all configured DOU/CCU board Parameters : none (# : invalid / - : not activated / + : activated)
9.2
get_state_do board
Action : display state of all channels of a board Parameters : board : board number (# : invalid / - : not activated / + : activated)
9.3
active_ccu board,channel,order
Action : activate an output on a CCU board Parameters : board : board number channel : channel number order : 1=activate, 0=desactivate
9.4
active_dou board,channel,order
Action : activate an output on a DOU board Parameters : board : board number channel : channel number order : 1=activate, 0=desactivate
Désignation: C264 – Expertise Maintenance Guide Date: 15/10/07
Page: 17/29
Edition: Z
Transmission & Distribution Protection & Contrôle
10 TRACES FOR BINARY INPUTS (BI) 10.1 aff_bi_info bi_norgint Action : display the configuration attributes of a BI Parameters : bi_norgint : requested BI norgint
10.2 aff_bi_grp_info bi_norgint Action : display the list of BI associated to a group Parameters : bi_norgint : norgint of the BI group
10.3 aff_bi_state2 bi_norgint Action : display relation between DI and BI Parameters : bi_norgint : requested BI norgint
10.4 active_bi norgint, order Action : modify the state of a BI Parameters : norgint : BI norgint order : 1=SET, 0=RESET
10.5 get_di_norgint Action : display relation between DI and BI Parameters : none
Désignation: C264 – Expertise Maintenance Guide Date: 15/10/07
Page: 18/29
Edition: Z
Transmission & Distribution Protection & Contrôle
11 TRACES FOR CONTROLS 11.1 aff_co_info co_norgint Action : display configuration attributes of a control Parameters : co_norgint : norgint of the requested control
11.2 aff_all_co_info norgdeb, norgfin Action : display configuration attributes of controls between norgdeb and norgfin Parameters : norgdeb : norgint of the first control norgfin : norgint of the last control
11.3 aff_sp_info sp_norgint Action : display the configuration attributes of a setpoint Parameters : sp_norgint : norgint of the setpoint
Désignation: C264 – Expertise Maintenance Guide Date: 15/10/07
Page: 19/29
Edition: Z
Transmission & Distribution Protection & Contrôle
12 TRACES FOR COUNTERS (CT) 12.1 aff_ct_data ct_norgint Action : display the current counter value Parameters : ct_norgint : norgint of the counter
12.2 aff_ct_info ct_norgint Action : display the configuration attributes of a counter Parameters : ct_norgint : norgint of the counter
Désignation: C264 – Expertise Maintenance Guide Date: 15/10/07
Page: 20/29
Edition: Z
Transmission & Distribution Protection & Contrôle
13 TRACES FOR MEASUREMENTS (MV) 13.1 aff_dm_info dm_norgint Action : display the configuration attributes of a digital measurements Parameters : dm_norgint : norgint of the measurement
13.2 aff_meas_info norgint Action : display the configuration attributes of an analogue measurements Parameters : norgint : norgint of the measurement
13.3 aff_meas_data norgint Action : display value and status of the measurement Parameters : norgint : norgint of the measurement
13.4 active_meas norgint,value,quality Action : change the value and status of the measurement Parameters : norgint : norgint of the measurement Value : measurement value Quality : 0=valid, 1=faulty, 3=open circuit, 4=saturated
13.5 active_from_ai norgint,type,value,quality Action : change the value and status of the measurement provided by an AIU board Parameters : norgint : norgint of the measurement Type : 0=measurement,1=TPI Value : measurement value Quality : 0=valid, 1=faulty, 2=undefined, 3=open circuit, 4=saturated, 5=unknown
13.6 active_meas_ctvt norgint,value,quality Action : change the value and status of the measurement provided by the CT/VT board Parameters : norgint : norgint of the measurement Value : measurement value Quality : 0=valid, 1=faulty, 3=saturated
13.7 active_meas_ied norgint,value,quality Désignation: C264 – Expertise Maintenance Guide Date: 15/10/07
Page: 21/29
Edition: Z
Transmission & Distribution Protection & Contrôle
Action : change the value and status of the measurement provided by an IED (legacy or IEC61850) Parameters : norgint : norgint of the measurement Value : measurement value Quality : 0=valid, 1=faulty, 2=unknown
13.8 aff_sig_info norgint Action : display configuration attributes of a MPS Parameters : norgint : norgint of the MPS
13.9 aff_sig_data norgint Action : display status of the MPS Parameters : norgint : norgint of the MPS
13.10 active_sig norgint,value,quality Action : change the value and status of the TPI Parameters : norgint : norgint of the TPI Value : TPI value Quality : 0=valid, 1=faulty, 2=undefined, 3=toggling, 4=unknown
13.11 aff_spi_info norgint Action : display configuration attributes of a TPI Parameters : norgint : norgint of the TPI
13.12 aff_spi_data norgint Action : display value and status of the TPI Parameters : norgint : norgint of the TPI
13.13 active_spi norgint,value,quality Action : change the value and status of the TPI Parameters : norgint : norgint of the TPI Value : TPI value Quality : 0=valid, 1=faulty, 2=undefined, 3=open circuit, 4=saturated, 5=unknown
Désignation: C264 – Expertise Maintenance Guide Date: 15/10/07
Page: 22/29
Edition: Z
Transmission & Distribution Protection & Contrôle
14 TRACES FOR AUTORECLOSER, SWITCHGEAR AND MODULES 14.1 S_DBTEST_print_ar_item x Action : display autorecloser data Parameters : x : norgint of the autorecloser (available with S_DBTEST_print_norgint_list)
14.2 S_AUTREC_get_ar_context Action : display all controls used by the autorecloser Parameters : none.
14.3 S_AUTREC_get_ar_state Action : display the current autorecloser status Parameters : norgint of the autorecloser.
14.4 S_DBTEST_print_cb_item x Action : display circuit breaker data Parameters : x : norgint of the circuit breaker
14.5 aff_sp_cb_info x Action : display configuration attributes of a circuit breaker Parameters : x : norgint of the circuit breaker
14.6 aff_discsw_info Action : display configuration attributes of a switch Parameters : x : norgint of the switch
14.7 aff_module_info Action : display configuration attributes of a module Parameters : x : norgint of the module
Désignation: C264 – Expertise Maintenance Guide Date: 15/10/07
Page: 23/29
Edition: Z
Transmission & Distribution Protection & Contrôle
15 TRACES FOR TIME SYNCHRONISATION 15.1 synchroInfoShow Display synchronisation information
15.2 synchroBdShow Display configuration attributes associated to the time synchronisation
Désignation: C264 – Expertise Maintenance Guide Date: 15/10/07
Page: 24/29
Edition: Z
Transmission & Distribution Protection & Contrôle
16 TRACES FOR ALARMS 16.1 aff_alarm_info x Action : display configuration attributes of an alarm Parameters : x : norgint of the alarm.
16.2 ALARM_HELP Action : List of shell action linked to the alarms Parameters : none
16.3 read_alarm_header Action : display global data of the alarm buffer Parameters : none
16.4 read_diff_alarm_header Action : display global data of the differed alarm buffer Parameters : none
Désignation: C264 – Expertise Maintenance Guide Date: 15/10/07
Page: 25/29
Edition: Z
Transmission & Distribution Protection & Contrôle
17 TRACES FOR ATCC 17.1 ccaCatcAff
donGen,group,node,nivTens,device,transf
Action : display of ATCC data Parameters : donGen : ATCC general data Group : data on groups managed by the ATCC Node : data on topological node NivTens : display of data per voltage level device : display of data per devices Transf : display of data per transformer
Désignation: C264 – Expertise Maintenance Guide Date: 15/10/07
Page: 26/29
Edition: Z
Transmission & Distribution Protection & Contrôle
18 TRACES FOR FAST AUTOMATISM ET INTERLOCK 18.1 aff_eql_info Action : display configuration attributes of all EQL Parameters : none
18.2 aff_eql_data
index_eql
Action : display data status of the EQL Parameters : index_eql : EQL number (given by aff_eql_info)
Désignation: C264 – Expertise Maintenance Guide Date: 15/10/07
Page: 27/29
Edition: Z
Transmission & Distribution Protection & Contrôle
19 TRACES FOR REDUNDANCY 19.1 aff_red_data Action : display data linked to C264 redundancy Parameters : none
Désignation: C264 – Expertise Maintenance Guide Date: 15/10/07
Page: 28/29
Edition: Z
Transmission & Distribution Protection & Contrôle
Blank Page
End of the document
Désignation: C264 – Expertise Maintenance Guide Date: 15/10/07
Page: 29/29
Edition: Z
View more...