With ithout out Bus Busbar bar Prot Prote ecti ction on (1)
F1
F2
There There are are fewer faults faults on bus bars than on other parts of the pow er system.
No dislocation of s ystem due to accidental accidental operation of busbar protection.
Slow f ault c learance. learance. Bus bar faults at F1 and F2 are cleared cleared by r emote tim e delayed delayed protection on c ircuits feeding feeding the faults: faults: Time Delayed Overcurrent or Time Delayed Delayed Distance Protect ion
With ithout out Bus Busbar bar Prot Prote ecti ction on (2)
BUSBAR ZONE F1
F2
Fast Fast cleara c learance nce by breake b reakers rs at the th e busbars busb ars
Where bus bars are section alised, Where Protection can limit the amount amount of system disrupti on for a busbar fault fault
Busbar Faults Are Usually Permanent CAUSES : Insulation failures Circuit breaker failures Falling debris Isolators operated out side their ratings Safety earths left connected Current transfor mer failures
THEREFORE : Circuit breakers should be tripp ed and lo cked out by bus bar protection
Busbar Protection must be:
RELIABLE
STABLE
False trippi ng can cause widespread interruption of supplies to custo mers
DISCRIMINATING
Failur e could cause widespread damage to th e substation
Should trip the minimum n umber of breakers to clear the fault
FAST
To limit damage and poss ible power system instabilit y
Methods of Providing Busbar Protection
Frame to Earth (Leakage) Protection
Differential Protection :
High Impedance Low Impedance
Directional Comparison (Blocking Schemes)
Protection
Frame Leakage Protection
Frame Earth Protection Scheme
Only an earth fault s yst em
Involves measuring fault curr ent f rom s wi tchgear frame to earth
Switchg ear insul ated by standing on c oncrete plinth
Only one earthin g poi nt allowed on sw itchg ear
C.T. mount ed on singl e earth cond uctor used to energise instantaneous relay
All cabl e gland s must be insulated
Current Distribution for External Fault Outgoing feeder IF
Switchgear frame bonding bar
Switchgear frame Frame-leakage current transformer
= I1 + I2
Generator
System earthing resistor
Earth bar
I1
I1
Frame insulation resistance to earth (> 10Ω)
I1
I2
+ I2
Earthing electrode resistance (< 1Ω)
High Impedance Protection
High Impedance Protection (1)
This is a versatile and reliable prot ection system applied to many different Busbar configurations.
If CT requirements are met, scheme performance may be predicted by calculation without heavy current conjunctive tests.
High Impedance Protection (2) Simple system to apply and extend. High sensitivity f or phase and earth faults . Extremely stable for external faults .
RST 87
CT requirements: Equal ratios METROSIL Class ‘X’ May require stabilising resistor s, RST. May require non-linear resistor s (Metrosils).
Effective Setting
Since in each zone of pro tecti on th ere are several CT’s in p arallel with the relay and each o ther, the combin ed CT magnetising c urrents w ill increase the primary operating current (P.O.C). P.O.C. = CT ratio ( IR + INLR + n IM) where :IR IM
n
INLR
= = = =
Relay setting current CT magnetising current (one CT at relay setting vol tage) Number of paralleled CT’s Non linear resistor current at relay setting voltage
Primary Operating Current (P.O.C)
The value of primary operating current should be around 30% of minimum fault current available. This ensures suffi cient relay current during int ernal fault conditions for high speed operation.
Through Fault Stability
Busbar protection stability li mit is based on maximum t hrough fault cur rent.
Generally this value is derived from the rating of the associated sw itchgear irrespective of exist ing fault level, since it can be expected that system will develop up to limit of rating.
Check Feature Usually provided by duplication of pri mary protection using second set of CTs on all cir cuits other than bus section and coup ler unit s. Check system forms one zone only, covering whole of b usbar systems and not discrimin ating between faults on various sections.
Zone A 87A
87A
Check zone 87A
Zone B
Current Transformers
CT Wiring Supervision (1)
Open circu it connection s between CT’s and relay circu it result in unbalance currents which may operate the protection. Supervision is applied by a voltage relay acros s dif ferential relay circuit . Supervision relay is time delayed, gives alarm and also s hort s out bu s w ires to protect differential relay cir cuit. Typical effective setting is 25 prim ary amps or 10% of low est circ uit rating, whi chever is greater.
CT Wiring Supervision (2) I1
CT1
I2
RST R
V Super vision relay
I4
ZM4
ZM3
ZM2
I3
RR I1
Voltage measured by supervision relay V
= Ι1
(R // Z M2 // Z M3 // Z M4 )
If supervision relay setting
=
VSP
Out - of - balance current to operate the supervision relay Ι =
VSP R
+
VSP Z M2
+
VSP Z M3
+
VSP Z M3
Differential Relay Circuit A B C N
Zone bus wires
95X 95X
Bus wire short contacts
95X 95
Metrosil resistors
v
v 87
Stabilising resistors
v 87
Supervision relay
87
Current Transformer Wiring
Lead bur dens between various sets of CT’s must be kept low . Usually busw ires are run in clos ed ring between breaker contro l p anels.
Typical rou te is :
CT’s to m arshalling k iosk
Marshallin g kios k to isol ator auxili aries
Loop between marshallin g kio sks
Conducto r size :
Normally 2.5mm2
Effect of C.T. Location on Busbar Protection Performance
One trippi ng relay (device 96) is required for each feeder breaker and 2 for each bus section or bus coupler breakers. Both main and check relays must be energised before tripping relays trip all breakers associated with zone.
Typical Trip Relay Arrangement Double Busbar System -
+ In Out
87M1 - 1
M1 M2R
87CH - 1 96D1
CSS - M1 87M2 - 1
96D2
a1 96E
CSS - M2 87R - 1
c1
CSS - R
96F1
96F2
b1 96G
c2 96H1 96H2
D.C. Buswires 80T
Double Busbar with Transfer Facilities
Main
Reserve / Transfer
By-pass Isolator
By-pass Isolator
Triple Busbar
Main
Reserve
Transfer
Transfer CB
Transfer CB
1½ Breaker Scheme
1½ Breaker Bus Protection
87
87
Mesh Busbar F1
F3
T1
T3
T4
T2
F4
F2
Mesh Busbar Protection F1
F3
87 R1
87 R3
T1
T3
T4
T2
87 R4
87 R2
F4
F2
Busbar Protection and Breaker Fail
Where breaker fail pro tection is appli ed to a syst em, back trip ping o f associated breakers is requir ed in the event of a breaker failu re.
Often, breaker fail protection is arranged in conjunc tion with busbar protection trip ping circui ts to initi ate tripping o f breakers on a busbar zone associated with the failed breaker.
Low Impedance Protection
Low Impedance Busbar Protection Fast Modular scheme design allows r elays t o relate to each c ircui t and func tion of the protection. This enables the user to easily un derstand the principles of application. High sensit ivity for phase and earth faults. Protection for each phase can be relatively independent. Earli er schemes were less stable than hig h impedance schemes. Modern schemes incor porate saturation detectors and are extremely stable. Duplicate measuri ng cir cuit s are inclu ded. Current transformers can be : of dif ferent ratio of relatively small outp ut shared w ith other pr otections Current transform er secondary cir cuits are not sw itched. Continuous sup ervision of CT circuits and constant monitoring of vital circuits are included.
Single Bus Protection
Z2
Z1 F1
BS
F2
F M1
F M2
BSM
F3
F4
F M3
F M4
Z2 ZCK
Z1 ZCK
Z1
ZCK
Z2
Double Bus Protection
BS
Z1
Z2 Z4
Z3
BC1
F2
F1
BCM 1
FM 2
FM 1
BSM
BC2
F4
F3
FM 4
FM 3
BCM 2
Z1 Z3 ZCK
Z2 Z4 ZCK
Z1
Z3
ZCK
Z2
Z4
Blocking Schemes
Busbar Blocking Protection Incomer O/C Relay
BLOCK
IF2
O/C Relay
IF1
O/C Relay
O/C Relay
O/C Relay
Directional Comparison Busbar Protection Bus zone protection and unit pr otection of feeders Forward DOC F1
Thank you for interesting in our services. We are a non-profit group that run this website to share documents. We need your help to maintenance this website.