Building Plan Submission - What Bomba Wants

April 21, 2017 | Author: Richard Leong | Category: N/A
Share Embed Donate


Short Description

Download Building Plan Submission - What Bomba Wants...

Description

8/9/2011

By IR WONG SEE FOONG Immediate Past President Institution of Fire Engineers (U.K.) Malaysia Branch

BACKGROUND •

Statistics from both Bomba Kuala Lumpur and Bomba Selangor show a rejection rate of 47% for building plan submissions



Bomba has been asked to look into reducing plan approval period to within 7 days.



To achieve this, the rejection rate must be minimized.

1

8/9/2011

ARCHITECTURAL CONSIDERATIONS •







Purpose group to be established based on 5th Schedule (By-law 134); Percentage perimeter road access based on volume of building (By-law 140); Limit of compartment to be based on 5th Schedule (By-law 136); Maximum travel distance to be based on 7th Schedule (By-law 165)

ARCHITECTURAL CONSIDERATIONS •







Capacity of exits to be based on occupant load based on 7th Schedule (By-law 175); Location of exits to be within maximum permissible travel distances (By-law 164); Dead end limits to be within maximum permissible under 7th Schedule (By-law 164); Internal finishes to comply with Restriction of Spread of Flame under 8th Schedule (By-law 206);

2

8/9/2011

FIRE REQUIREMENTS Fire requirements must be checked against the following: • •

Purpose group of building; Height and size of building;

The active fire safety systems must follow the fire requirements approved with the building plan

FIRE REQUIREMENTS

3

8/9/2011

BOMBA REQUIREMENTS SITE PLAN 1.

2. 3. 4. 5. 6.

Provide XX No. of two-way outlet pillar hydrants with discharge of 1135 l/min at each hydrant as shown in the plans; Provide 2 length of hose of 65mm dia. 30 m. long with jet and spray nozzle in a box cabinet near each hydrant; Provide fire appliance access road of not les than 6 m. wide and capable of withstanding a load of 25 tons; Gradient of access road shall be not more than 1 in 12; Overhead clearance for access road shall be not less than 5 m. Distance between buildings shall comply with the Sixth Schedule of the Uniform Building By-laws.

BOMBA REQUIREMENTS GENERAL REQUIREMENTS 1.

2. 3. 4. 5. 6.

All electrical wiring for emergency systems shall be in metal conduit or of mineral insulated fire rated cables routed in areas of minimum fire risks; All structural elements shall have the fire resistance period complying with the UBBL; Provide ventilation system of the natural or mechanical type for escape staircases; LPG system of the bulk storage type shall comply with the requirements of MS830 and MS930; For buildings exceeding 30 m. all exit staircases shall extend to the roof to provide access; All fire safety signs shall comply with MS982.

4

8/9/2011

BOMBA REQUIREMENTS ACTIVE FIRE REQUIREMENTS Provide wet riser system complying with MS1489 Part 1 and as required in the UBBL; 2. Provide first aid hose reel complying with MS1489 Part 1 or as required by the Fire and Rescue Department; 3. Provide fire alarm of the manual break glass type in accordance with the requirements of the Fire and Rescue Department; 4. Provide smoke extractor system complying with MS1780 or requirements as approved by the Fire and Rescue Department; 1.

BOMBA REQUIREMENTS ACTIVE FIRE REQUIREMENTS 1.

Provide fire lift as indicated in the plan in accordance with BS 2655;

2.

Provide fire extinguishers complying with MS1539 Part 1

1.

2.

as indicated in the plans; Provide fixed gaseous extinguishing systems accordingly to the requirements of the Fire and Rescue Department as indicated in the plans; Provide automatic sprinkler system complying with MS1910 or requirements accepted by the Fire and Rescue Department;

5

8/9/2011

BOMBA REQUIREMENTS ACTIVE FIRE REQUIREMENTS 1.

2.

3.

Provide firemen intercom system with 3-way communication in the escape staircase/ fire lobby, lift motor room, fire pump room and generator room; Provide public address system in accordance with the requirements of the Fire and Rescue Department; Provide electrical isolation switch in accordance with the requirements of the UBBL;

BOMBA REQUIREMENTS ACTIVE FIRE REQUIREMENTS 1.

2.

3.

4.

Lift lobbies to be constructed of materials with 2 hour fire rating and protected with smoke detectors in accordance with UBBL; Provide emergency exit signs with dual source of current as indicated in the plans; Provide emergency lights with dual source of current as indicated in the plans; Staircases and fire lift lobbies are to be provided with pressurization systems in accordance with MS 1472.

6

8/9/2011

BOMBA REQUIREMENTS PASSIVE FIRE REQUIREMENTS 1.

2.

3.

4.

Installation of ceilings shall comply with the requirements of Schedule Eight of the UBBL; All exit staircases shall be of masonry of 115mm thick or open in accordance with the requirements of UBBL as shown in the plans; Provide 1 hour rated fire doors of the self-closing type as indicated in the plans; Walls for store rooms of hazardous materials shall be of 100mm thick masonry with 1 hour rated fire doors and door-closers;

BOMBA REQUIREMENTS PASSIVE FIRE REQUIREMENTS 1.

2.

3.

4.

All service shafts shall be sealed at every floor with 2 hour rated fire seal; All fire pump rooms and generator rooms shall be constructed with masonry walls of 2 hour fire rating with fire doors of 1 hour fire rating; Separating walls shall be of masonry 200mm thick constructed to a height of 225mm above the roof level or as approved by the Fire and Rescue Department; Provide deflector wall of 450mm and 115mm thick as indicated in the plans.

7

8/9/2011

SITE PLAN •

Fire hydrants to be indicated along fire appliance access roads at not more than 90 meters apart.



Complete list of fire requirements to be described.



Bomba file reference no. to be stated.

M&E ASPECTS Active fire systems to be identified in the building plans include: • • • • •

External hydrants Portable fire extinguishers; Hose reels; Dry or Wet risers; Fixed gaseous extinguishing systems

8

8/9/2011

M&E ASPECTS (Cont.) Other active fire systems to be identified in the building plans are: • • • •

Manual call point and alarm bells Fire lifts Emergency lights Emergency exit signs;

PORTABLE FIRE EXTINGUISHERS •

Type, number and capacity of extinguishers to be stated;



Locations to be identified;



Preferred to be beside staircase exit doors;



Design to be in accordance with MS 1539 Part 3

9

8/9/2011

HOSE REELS •

Number and locations of hose reels to be indicated;



All spaces to be covered with a 30 m hose with a 6 m throw;



Preferred to be beside staircase exit doors;



Design to be based on MS1489 Part 1

DRY OR WET RISERS •

Number and locations of landing valves to be indicated;



All spaces to be covered with a 30 m hose with a 15 m throw;



Preferred to be within fire lobby with access to staircase;



Design to be based on MS1489 Part 1

10

8/9/2011

FIXED GASEOUS EXTINGUISHING SYSTEM •

Electrical rooms to be provided with fixed gaseous extinguishing system;



Extinguishing agent can be carbon dioxide;



Type of clean agent to be identified otherwise;

FIRE ALARM SYSTEM •

Number and locations of manual call points and alarm bells to be indicated;



Occupant to travel not more than 30 m to reach manual call point;



Preferred to be beside staircase exit doors;



Design to be based on MS1745 Part 14

11

8/9/2011

FIRE LIFTS •

Number and locations of fire lifts to be indicated;



Distance between fire lifts must not exceed 60 m;



Fire lift must have hoistway segregated from other passenger lifts;

EMERGENCY LIGHTS Number and locations of self-contained emergency lights to be indicated for: • • • • • •

Emergency generator room; Main electrical switch room; Fire pump room; Lift motor room; Staircases and lift lobbies; Along escape corridors.

12

8/9/2011

EMERGENCY EXIT LIGHTS Number and locations of self-contained emergency exit lights to be indicated for: •

Along escape corridors;



Entry doors into staircases;



Entry doors into smoke lobbies;

SUMMARY Description

Requirement

1.

Perimeter road access

Based on By-law 140

2.

Compartment size

Based on 5th Schedule

3.

Max. travel distances

Based on 7th Schedule

4.

Dead end limits

Based on 7th Schedule

5.

Staircase and exit widths Based on 7th Schedule

6.

Interior finishes

Based on 8th Schedule

7.

Fire doors

To be at compartment walls

8.

Ventilation

Smoke control required if not naturally ventilated

Yes/No/ NA

13

8/9/2011

SUMMARY Description

Requirement

1.

Fire requirements

Complete list shown on site plan

2.

Fire hydrants

Indicate on site plan along access road

3.

Bomba File Ref.

Indicate on site plan top right hand

4.

Fire extinguishers

Locate beside staircase exit doors

5.

Hose reels

Locate beside staircase exit doors

6.

Dry or Wet risers

Locate within fire lobby on each floor

7.

Fixed gas system

Indicate system for electrical rooms

Yes/No/ NA

SUMMARY Description

Requirement

8.

Manual call points Locate beside staircase exit doors

9.

Alarm bells

Yes/No/ NA

Locate beside staircase exit doors

10. Fire lifts

Indicate no. and location on floor plans

11. Emergency lights

Provide in fire pump rooms, generator room, main switch room, lift motor room and in escape staircases

12. Exit lights

Locate above staircase and other exit doors and escape corridors

13. Colour

Fire safety devices to be shown in red

14. Signature

All plans signed and stamped by submitting architect

14