Bridge

May 31, 2016 | Author: Asghar Hussain Shah | Category: N/A
Share Embed Donate


Short Description

Download Bridge...

Description

Department of Civil Engineering, N-W.F.P UET, Peshawar

Introduction to Bridge Engineering

Introduction To Bridge Engineering

Abutment (Substructure)

(Superstructure)

Bridge Deck

Bearing Pier (substructure)

Pile cap Pile

Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 1 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar

Introduction to Bridge Engineering

1. Introduction: Bridges are important to everyone. But they are not seen or understood in the same way by everyone, which is what makes their study so fascinating. A single bridge over a small river will be viewed differently by different people. •

Civic leaders see the bridge as link between the neighborhoods and a way to provide fire and police protection and access to hospitals.



In business community, the bridge is seen as opening up new markets and expanding commerce.

Everyone is looking at the same bridge, but it produces different emotions and visual images in each one of them. Bridges affect people. People use them, and engineers design them and later build and maintain them. Bridges do not just happen. They must be planned and engineered before they can be constructed. 2. A bridge is the key element in a transportation system •

It controls the capacity of the system.



It is the highest cost per mile of the system.



If the bridge fails, the system fails.

Because the bridge is the key element in the transportation system, balance must be achieved between handling future traffic volume and loads and the cost of a heavier and wider bridge structure. Strength must always be foremost, but so should measures to prevent deterioration. The designer of new bridge has control over these parameters and must take wise decisions so that capacity and cost are in the balance, and safety is not compromised. 3. Role of bridge engineer: Oftentimes engineers deceive themselves into believing that if they gather enough information about a bridge site and the traffic loads, the selection of a bridge type for that situation will be automatic. Furthermore the use of analysis/design software will complete the job. Unfortunately, or perhaps fortunately it is not the case.

Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 2 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar

Introduction to Bridge Engineering

A bridge engineer must have three points in mind while working on a bridge project. •

Creative and aesthetic,



Analytical,



Technical and practical,

So as to give a realistic evaluation of the possibilities of the construction technique envisaged and the costs involved. If these three mentalities do not coexist in a single mind, they must always be present on terms of absolute equality in the group or team responsible for the design. 4. Aesthetics in bridge design: There are no equations, no compute programs or design specifications that can make our bridges beautiful. It is an awareness of beauty on our part. Aesthetics must be a part of the bridge design program from the beginning. It cannot be added on at the end to make the bridge look nice. At that time, it is too late. From the beginning, the engineer must consider aesthetics in selection of spans, depth of girders, piers abutments, and the relationship of one to another. It is a responsibility that cannot be delegated. We must demand it of ourselves, because the public demands it of us. 5. Types of bridges: There are a number of ways in which to classify bridges. Bridges can be classified according to: •

Materials (concrete, steel or wood etc),



Usage (pedestrian, highway, or railroad),



Span (short, medium, or long),



Structural form (slabs, girder, truss, arch, suspension, or cable-stayed).

They all seem to contain parts of one another within each other. It is however suitable to classify bridges according to the location of the main structural elements relative to the surface on which the user travels, that is, whether the main structure is below, above, or coincides with the deck line.

Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 3 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar

Introduction to Bridge Engineering

a. Main structure below the deck line: Arched and truss-arched bridges are included in this classification. Examples are the masonry arch, the concrete arch, the steel-truss arch, the steel deck truss, figs 1 to 5, the rigid frame, and the inclined leg frame bridges, With the main structure below the deck line in the shape of an arch, gravity loads are transmitted to the supports primarily by axial compressive forces. At the supports, both vertical and horizontal reactions must be resisted. The arch rib can be solid or it can be a truss of various forms. Salient features of arch type bridges are: •

The arch form is intended to reduce bending moments (and hence tensile stresses) in the superstructure and should be economical in material compared with an equivalent straight, simply supported girder or truss.



The efficiency is achieved by providing horizontal reactions to the arch rib. If these are external reactions, they can be supplied at reasonable cost only if the site is suitable. The most suitable site for this form of structure is a valley, with the arch foundation located on dry rock slopes.



The conventional curved arch rib may have high fabrication and erection costs, although these may be controlled by skilled labor. The arch is predominantly a compression structure. For example, the open spandrel arch with the rib below the deck consists of deck, spandrel columns, and arch rib. The last two are compression members. The design must include accurate estimates of buckling behavior and should be detailed so as to avoid excessive reductions in allowable stress. The classic arch form tends to favor concrete as a construction material.



The arch rib is usually shaped to take dead load without bending moments. This load is then called the form load. If the form load is large, the live load becomes essentially a small disturbance applied to a compressed member.



The conventional arch has two moments resisting components-the deck and the arch rib. Undesirable and unanticipated distributions of moment may occur, particularly in regions where the spandrel columns are short, normally near the crown of the arch, which may be avoided by careful detailing; for example by using pin ended columns.

Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 4 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar

Introduction to Bridge Engineering

Figure 1: Masonry arch bridge.

Figure 2: Masonry arch bridge.

Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 5 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar

Introduction to Bridge Engineering

Figure 3: Concrete arch bridge.

Figure 4: Steel truss arch bridge.

Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 6 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar

Introduction to Bridge Engineering

Figure 5: Steel deck truss bridge. b. Main structure above the deck line: Suspension, cable stayed, and through-truss bridges are included in this category. Both suspension and cable-stayed bridges are tension structures whose cables are supported by towers, fig. 6 and 8. Suspension bridges are constructed with two main cables from which the deck, usually a stiffened truss is hung by secondary cables. Cable-stayed bridges, fig 7, have multiple cables that support the deck directly from the tower. Analysis of the cable forces in a suspension bridge must consider non linear geometry due to large deflections, while linear elastic analysis is usually sufficient for cable stayed bridges. Salient features of suspension bridges: •

The major element of a stiffened suspension bridge is a flexible cable, shaped and supported in such a way that it can transfer the major loads to the towers and anchorages by direct tension.



This cable is commonly constructed from high strength wires.

Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 7 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar



Introduction to Bridge Engineering

The deck is hung from the cable by hangers constructed of high strength wire ropes in tension.



This use of high strength steel in tension, primarily in the cables and secondarily in the hangers, leads to an economical structure, particularly if the self-weight of the structure becomes significant, as in the case of long spans.



The main cable is stiffened either by a pair of stiffening trusses or by a system of girders at deck level:



This stiffening system serves to (a) control aerodynamic movements and (b) limit local angle changes in the deck. It may be unnecessary in the cases where the load is great.



It is the only alternative of spans over 600 m, and it is greatly regarded as competitive for spans down to 300 m.

Salient features of cable-stayed bridges: •

As compared with suspension bridges, the cables are straight rather than curved. As a result, the stiffness is greater.



The cables are anchored to the deck and cause compressive forces in the deck.



Compared with the stiffened suspension bridge, the cable-braced bridge tends to be less efficient in supporting dead load, but more efficient in supporting live load. As a result is not likely to be economical in the longest spans.



The cables may be arranged in a single plane, at the longitudinal centerline of the deck.



Aerodynamics instability has not found to be a problem in such structures.

Salient features of through bridges, fig 9 & 10: •

A bridge truss has two main structural advantages: (1) the primary member forces are axial loads; (2) the open web system permits the use of a greater overall depth than for an equivalent solid web girder. Both these factors lead to economy in material and a reduced dead weight. The increased depth also leads to reduced deflection, that is, a more rigid structure,



Economical for medium spans,



Aesthetically pleasing.

Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 8 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar

Introduction to Bridge Engineering

Figure 6: Suspension bridge.

Figure 7: Suspension bridge.

Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 9 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar

Introduction to Bridge Engineering

Figure 8: Cable stayed bridge.

Figure 9: Through Bridge. Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 10 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar

Introduction to Bridge Engineering

Figure 10: Through Bridge c. Main structure coinciding with the deck line: Girder bridges of all types are included in this category. Examples are: •

Slab (solid and voided),



T-beam,



I-beam,



Wide-flange beam,



Concrete box girder,



Steel box,



Steel plate girder.

Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 11 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar

Introduction to Bridge Engineering

Figure 11: Box Girder Bridge.

Figure 12: Girder Bridge under construction. Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 12 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar

Introduction to Bridge Engineering

Figure 13: Girder Bridge. 6. General Design Considerations: A general statement for assuring safety in engineering design is that the resistance of the materials and cross section supplied exceed the demands put on them by applied loads, that is, Resistance ≥ Effect of loads When applying this simple principle, it is essential that both sides of the inequality be evaluated for the same conditions. For example if the effect of applied loads is to produce compressive stress on a soil, it is obvious that this should be compared to the bearing resistance of the soil, and not some other quantity. In other words, the evaluation of the inequality must be done for a specific loading condition that links together resistance and the effect of loads. Evaluating both sides at the same Limit State provides this common link. When a particular loading condition reaches its limit, failure is the assumed result, that is, the loading condition becomes a failure mode. Such a condition is referred to as a limit state that can be defined as:

Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 13 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar

Introduction to Bridge Engineering

A limit state (in case of bridges) is a condition beyond which a bridge system or bridge component ceases to fulfill the function for which it is designed. Example of limit states for girder type bridges include: •

Deflection,



Cracking,



Fatigue,



Flexure,



Shear,



Torsion,



Buckling,



Settlement,



Bearing,



Corrosion,



Sliding etc.

Well defined limit states are established so that a designer knows what is considered to be unacceptable. An important goal of design is to prevent a limit state from being reached. However, it is not the only goal. Other goals that must be considered and balanced in the overall design are function, appearance, and economy. It is not economical to design a bridge so that none of its components could ever fail. Therefore, it becomes necessary to determine what is an acceptable level of safety or probability of failure. The determination of an acceptable margin of safety (how much greater the resistance should be compared to the effect of loads) is not based on the opinion of one individual but based on the collective experience and judgment of a qualified group of engineers and officials. In the highway bridge design community, AASHTO (American Association of State Highway and Transportation Officials) is such a group.

Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 14 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar

Introduction to Bridge Engineering

7. Design procedures: Over the years, design procedures have been developed by engineers to provide satisfactory margin of safety. These procedures were based on the engineer’s confidence in the analysis of the load effects and the strength of the materials being provided. As analysis techniques improved and quality control on materials became better, the design procedures changed. Two important design techniques/ philosophies are: a. Allowable stress Design (ASD) design philosophy: The earliest design procedures were developed with the primary focus on metallic structures kept in mind. Structural steel was observed to behave linearly up to a relatively well defined yield point that was safely below the ultimate strength of the material. Safety in the design was obtained by specifying that the effect of the loads should produce stresses that were a fraction of the yield stress fy; say one half. This value would be equivalent to providing as safety factor of 2, that is, F = resistance (R)/ effect of loads (Q) = fy / (0.5fy) = 2 Because the specification set limits on the stresses, this became known as allowable stress design (ASD). Shortcomings of the ASD: •

In the ASD method it is assumed that stress in the member is zero before any loads are applied, that is, no residual stresses exist. The assumption is seldom completely accurate.



ASD methods were developed for the design of statically determinate metallic structures. They do not necessarily apply in a straightforward logical way to other materials and other levels of redundancy.



The safety factor chosen is based on experience and judgment; quantitative measures of risk cannot be determined for ASD. Only the trend is known: if the safety factor is higher, the number of failures is lower. However, if the safety factor is increased by a certain amount, it is not known by how much this increases the probability of survival. Also it is more meaningful to decision makers to say. “This bridge has a probability of 1 in 10,000 of failing in 75 years of service,” than to say, “This Bridge has a safety factor of 2.3”.

Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 15 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar



Introduction to Bridge Engineering

Allowable stress design does not recognize that different loads have different levels of uncertainty. Dead, live and wind loads are all treated equally in ASD. The safety factor is applied to the resistance side of the design inequality, and the load side is not factored.

b. LRFD Load Resistance Factor Design: In this method the resistance side of the basic equation is multiplied by a statistically based resistance factor Φ, whose value is usually less than 1, and the load side is multiplied by a statistically based load factor γ, whose value is larger than 1. Because the load effect at a particular limit state involves a combination of different load types (Qi) that have different degrees of predictability, the load effect side is represented by a summation of γiQi values. If the nominal resistance is given by Rn, the safety criterion is: ΦRn ≥ effect of Σ γiQi Because this equation involves both load factors and resistance factors, the design method is called Load Resistance Factor Design (LRFD). The resistance factor Φ for a particular limit state must account for the uncertainties in 1. Material properties. 2. Equations that predict strength, 3. Workmanship, 4. Quality control, 5. Consequences of failure. The load factor γ chosen for a particular load type must consider the uncertainties in: 1. Magnitudes of loads, 2. Arrangement (positions of loads), 3. Possible combination of loads. In selecting resistance factors and load factors for bridges, probability theory has been applied to data on strength of materials, and statistics on weights of materials and vehicular loads.

Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 16 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar

Introduction to Bridge Engineering

i. Advantages of LRFD: •

Accounts for variability of loads,



Achieves fairly uniform levels of safety for different limit states bridge types,



Provides a rational and consistent method of design.

ii. Disadvantage of LRFD: •

Requires a change in design philosophy,



Requires an understanding of basic concepts of probability and statistics,



Require availability of sufficient statistical data and probabilistic design algorithms to make adjustments in resistance factors to meet individual situations.

8. Important concepts in Bridge Engineering: Bridge: A structure having an opening not less than 6000 mm that forms part of a highway or over, or under which the highway passes. Collapse: A major change in geometry of the bridge rendering it unfit for use. Design: Proportioning and detailing the components and connections of a bridge. Design life: Period of time up on which the statistical derivation of a transient load is based: 75 years for AASHTO specifications. Service life: The period of time that the bridge is expected to be in operation. Force effect: A deformation stress or stress resultant i.e. axial force, shear force, torsional or flexure moment, caused by applied loads, imposed deformations or volumetric changes. Load factors: A factor accounting for variability of loads, the lack of accuracy in analysis, and the probability of simultaneous occurrence of different loads. Load modifier: A factor accounting for ductility, redundancy and the operational importance of the bridge. Resistance factor: A factor accounting for the variability of material properties, structural dimensions, and the workmanship, and the uncertainty in the prediction of resistance.

Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 17 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar

Introduction to Bridge Engineering

The resistance of components and connections is determined, in many cases, on the basis of inelastic behavior, although the force effects are determined by using elastic analysis in LRFD design specifications. Limit state: A condition beyond which the bridge or component of the bridge ceases to satisfy the provisions for which it was designed. Strength limit state shall be taken to ensure that strength and stability, both local and global, are provided to resist the specified statistically significant load combination that a bridge is expected to experience in its design life. Service limit state: The service limit state shall be taken as restriction on stress, deformation and crack width under regular service conditions. Fatigue limit state shall be taken as a set of restrictions on stress range due to a single design truck occurring at the number of expected stress range cycles. Fracture limit state shall be taken as a set material toughness requirements of AASHTO material specifications. Extreme event limit state shall be taken to ensure the structural survival of a bridge during a major earthquake or flood, or when collided by a vehicle, vehicle or ice flow under scored conditions. Ductile behavior is characterized by the significant inelastic deformations before any loss of load carrying capacity occurs. The owner (of bridge) may specify a minimum ductility factor an assurance that ductile failure modes will be obtained. Ductility factor µ = ∆u/ ∆y ∆u = deformation at ultimate.

Pu

∆y = deformation at the elastic limit.

Py

∆y

Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

∆u

Page 18 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar

Introduction to Bridge Engineering

Traditional minimum depth (span to depth ratio) for constant depth super structure is given as follows: i. R.C.C Slabs: Simple span = 1.2(S + 3000)/30 = 1.2(S + 10)/30 (in fps system) Continuous spans = (S + 3000)/30 ii. R.C.C T-Beams: Simple span = 0.070L Continuous = 0.065L iii. Prestressed I Beams: Simple span = 0.045L Continuous spans = 0.040L iv. Steel I Beams: Simple span (over all depth) = 0.040L Continuous = 0.032L v. Trusses = 0.100L Major reason of Bridge failure: A majority of bridges that have failed in the United States and else where have failed due to scour. Permit vehicle: Any vehicle whose right to travel is administratively restricted in anyway due to its weight or size. Super structure: structural parts of the bridge which provides the horizontal span. Sub structure: Structural parts of the bridge which supports the horizontal span. Maximum ADT: Research has shown that average daily traffic ADT, including all vehicles, i.e, cars and trucks, is physically limited to about 20,000 vehicles per lane per day under normal conditions. ADTT: Average daily truck traffic. Compatibility: the geometrical equality of movement at the interface of joined components. Deformation: A change in structural geometry due to force effects, including axial displacements, shears displacements and rotations. Skin friction: acts upward on the side of piles or piers and thus supports the foundation. Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 19 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar

Introduction to Bridge Engineering

c/c distance between piles: It should be ≥ 750 mm (30″) or 2.5 times pile dia. Distance between centre of pile to edge of pile cap: should be ≥ 225 mm (9 inches) Piers: The part of the bridge structure between the super structure and the connection with the foundation. Abutments: A structure that supports the end of a bridge span, and provides lateral support for fill material on which the road way rests immediately adjacent to the bridge. Counterfort: A counterfort wall consists of a thin concrete face slab, usually vertically supported at intervals on inner side by vertical slabs or counterforts that meet the face slab at right angles. Pile: A relatively slender deep foundation unit, wholly or partly embedded in the ground, installed by driving, drilling, jetting or otherwise, and which derives its capacity from surrounding soil and/or from the soil or rock strata below its tip. Use of piles: piling should be considered when footings cannot be founded on rock, stiff cohesive or granular foundation material at reasonable cost. Pile may be used as a protection against scour. Minimum design penetration (Embedment length in the soil): 3000 mm for hard cohesive or dense granular. 6000 mm for soft cohesive or loose granular. Resistance of piles: shall be determined through subsurface investigations, laboratory and/or in-situ tests, analytical methods, pile load test, and by referring to the history of past performance. Down drag: Down drag results from settlement of the ground adjacent to the pile or shaft. It acts downward and loads the foundation. 9. Important points for bridge design: Road way widths: When the traffic is crossing the bridge, there should not be a sense of restriction. To avoid a sense of restriction requires that the roadway width on the bridge be the same as that of the approaching highway. Loads: to be considered in bridge design can be divided into two broad categories: ¾ Permanent loads, and, ¾ Transient loads. Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 20 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar

Introduction to Bridge Engineering

Permanent loads: Self weight of girders and deck, wearing surface, curbs and parapets and railings, utilities and luminaries and pressures from earth retainments. Two important dead loads are: DC: Dead load of structural components and non structural attachments. DW: Dead load of wearing surface. γbitumen = 2250 kg/m3 = 22.1 kN/m3 γconcrete = 2400 kg/m3 = 23.6 kN/m3 The maximum load factor for DC = 1.25 The maximum load factor for DW = 1.5 Transient loads: Gravity loads due to vehicular, railway and pedestrial traffic. Lateral loads due to water and wind i.e., floes (sheet of floating ice), ship collisions and earthquake, temperature fluctuations, creep and shrinkage etc. Some loads such as ship collision etc are important loads for substructure design. The effects of these loads will be different for super structure and sub structure. The automobile is one of the most common vehicular live load on most bridges; it is the truck that causes the critical load effects. AASHTO design loads attempt to model the truck traffic that is highly variable, dynamic and may occur independent of, or in unison with other truck loads. The principal load effect is the gravity load of the truck but other effects are significant and must be considered. Such effect includes impact (dynamic effects), braking forces, centrifugal forces (if present) and the effects of other trucks simultaneously present. Different design limit states may require slightly different truck models. Design Lanes: The number of lanes a bridge may accommodate must be established and is important design criterion. Two such terms are used in the lane design of the bridge: ¾ Traffic lane, ¾ Design lane. Traffic lane: is the number of lanes of traffic that the traffic engineer plans to route across the bridge. Lane width is associated with a traffic lane and is typically 3600 mm = 3.6 m = 12 ft.

Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 21 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar

Introduction to Bridge Engineering

Design lane: is the lane designation used by the bridge engineer for live load placement. The design lane width and location may or may not be the same as that of the traffic lane. AASHTO uses a 3000 mm = 3.0 m = 10.0 ft design lane and Vehicles is to be positioned within the lane for extreme effects. No of Design lanes [A361.1.1] = Clear roadway width (mm) / 3600 mm = rounded to larger integer. Clear roadway width is the distance between the curbs or barriers. When traffic lane width < 3600 mm No. of design lanes = No. of traffic lanes, and Width of design lane = Width of traffic lane For roadway width from 6000 to 7200 mm (20 ft to 24 ft), two design lanes should be used. And, Design lane width = ½ × Roadway width The direction of traffic in the present and future scenarios should be considered and the most critical cases should be used for design. Additionally, there may be construction and/or detour plans that cause traffic patterns to be significantly restricted or altered. Vehicular design loads: A study by the Transportation Research Board (TRB) was used as a basis for AASHTO loads (TRB, 1990). It was felt by the engineers developing the load model that the exclusion truck (over loaded or more than allowed legally) best represented the extremes involved in the present truck traffic (Kulicki 1992). The AASHTO design loads model consists of three distinctly different loads: ¾ Design truck, ¾ Design Tandem, ¾ Design lane. Design truck: The configuration of design truck as given in figure 14 is the same that has been presented by AASHTO (1996) standard specifications since 1944 and

Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 22 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar

Introduction to Bridge Engineering

commonly referred to as HS. The H denotes highway and S denotes Semi tractor and 20 is the weight of tractor in tons (USC units). The new vehicle combination as described in AASHTO (1994) LRFD Bridge specifications are designated as HL-93 for Highway Loading accepted in 1993.

145 kN 145 kN 4.3 to 9.0 m 4.3 m

35 kN

OR 32 k = 14.5 Tons 32 k = 14.5 Tons 8 k = 3.5 Tons 14' to 30' 14'

Figure 14: Design truck. The variable range, in figure 14 means that the spacing used should cause critical load effect. The long spacing typically only controls where the front and rear positions of the truck may be positioned in adjacent structurally continuous spans, such as continuous short span bridges. Design Tandem: The other configuration is the design tandem as shown in figure 15.

110 kN

110 kN 1.2 m

OR 24 k = 11 Tons

24 k = 11 Tons 4'

Figure 15: Design Tandem.

Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 23 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar

Introduction to Bridge Engineering

Design lane load: 9.3 kN/m and is assumed to occupy a region of 3.0 m (10 ft). It is applied as 3.1 kN/m2 or 0.064 k/ft2 (64 lb/ft2) of pressure to a width of 3.0 m or 10 ft over the entire length of bridge for FEM.

9.3 kN/m

OR 0.64 k/ft Figure 16: Design lane load. In summary three design loads should be considered: the design truck, design tandem, and the design lane. These loads are superimposed two ways to yield the live load effects, which are combined with the other load effects (D loads) are: ¾ Truck + lane, ¾ Tandem + lane,

Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 24 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar

Introduction to Bridge Engineering

Design Pb: Design the simply supported slab bridge of fig. 17, with a span length of 35 ft centre to centre of bearings for a HL-93 live load. The roadway width is 44 ft curb to curb. Allow for a future wearing surface of 3 inch thick bituminous overlay. Use fc′ = 4000 psi and fy = 60 ksi. S = 35 ft

H.W Abutment 2

Abutment 1

2 1

(a) Elevation 10' shoulder

Centreline of bridge 12' 12' 10' shoulder

(b) Plan W1 = 46.5' W = 44' Roadway

15"

15"

3" F.W.S

h

(c) Section

Figure 17: Solid Slab Bridge design example Solution: Step No 1: Sizes. Span length of bridge (S) = 35 ft c/c Clear roadway width (W) = 44 ft (curb to curb) For a curb width of 15 inches, total width of the bridge (W1) = 44 + 2 × 15/12 = 46.5 ft According to AASHTO (1994) LRFD Bridge specifications (table A.2.5.2.6.3-1), minimum thickness of bridge slab is given by formula: Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 25 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar

Introduction to Bridge Engineering

hmin = 1.2(S + 10)/30 = 1.2 (35 + 10)/30 = 1.8 ft = 21.6 inches Use h = 22 inches. Step No 2: Loads. Slab load (wDC) = (22/12) × 0.15 = 0.275 ksf Wearing surface load (wDW) = (3/12) × 0.14 = 0.035 ksf Step No 3: Analysis. (1) Dead load moments: Slab moments (MDC) = 0.275 × (352)/8 = 42 ft-kip/ft Wearing surface moment (MDW) = 0.035 × 352/8 = 5.3 ft-kip/ft (2) Live load moments: (a) Truck Load moments: 32 kip 3.5'

32 kip 14'

14'

8 kip 3.5'

S = 35'

45.6 kip

26.4 kip

45.6 kip 13.6 kip -18.4 kip -26.4 kip 350 ft-kip 158.1 ft-kip

90.56 ft-kip

Figure 18: Shear force and bending moment diagrams for truck load. Therefore, MTruck = 350 ft-kip Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 26 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar

Introduction to Bridge Engineering

(b) Lane moment: Mlane = 640 × 352/8 = 98 ft-kip 640 lb/ft 35'

Figure 19: Lane load. (c) Tandem moment: Mtandem = 372 ft-kip 24 kip

24 kip

4' 35'

Figure 20: Tandem load. Mtandem > Mtruck Therefore we will use Mtandem MLL+IM (Including impact) = 1.33Mtandem + Mlane [MLL+IM = 1.33 × 372 + 98 = 593 ft-kip] Now converting MLL+IM to moment/ft, Divide MLL+IM by “E” design lane width. Note: While calculating truck/tandem (live load) moments, it has been assumed that axle load is acting as a point load. However in reality the vehicle will occupy some definite width, hence this live load moment must be divided by this width. AASHTO LRFD gives following procedure for converting this moment to per foot width. Similarly AASHTO LRFD also emphasizes that live load will produce different effects on interior and edge strips of slabs as shown below. Design Lane width “E” for interior strip: (a) For single lane loaded: E = 10.0 + 5.0 √ (L1W1) L1 = Modified span length = Minimum of (S = 35 ft) and 60 ft L1 = 35 ft W1 = Modified edge to edge width = Minimum of (W1 = 46.5 ft) or 30 ft Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 27 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar

Introduction to Bridge Engineering

W1 = 30 ft Therefore, E = 10.00 + 5.0√ (35 × 30.00) = 172 in = 14.3 ft (b) For multilane loaded: E = 84 + 5.0√ (L1W1) ≤ W/NL L1 = 35 ft W1 = Minimum of (W1 = 46.5 ft) or 60 ft W1 = 46.5 ft NL = No. of design lanes. NL = INT (W/12) =INT (44/12) = 3 Therefore, E = 84 + 1.44 √ (35 × 46.5) ≤ 46.5/3 = 142 inch or 11.84 ft ≤ 15.5 Therefore, E = 11.84 ft (Least of all) Hence interior strip moment per foot width is equal to: MLL +IM (Interior strip) = 593/11.84 = 50 ft-kip/ft Now, Mu = 1.05 (1.25MDC + 1.5MDW + 1.75MLL+IM) Mu = 1.05 (1.25 × 42 + 1.5 × 5.33 + 1.75 × 50) Mu (interior strip) = 155.3 ft-kip/ft = 1863.6 in-kip/ft Design lane width for edge strip: According to AASHTO LRFD code A4.6.2.1.4, E = Barrier width at base + 1 ft + (1/2) strip width ≤ Full strip width or 6 ft (whichever is less) Therefore E = 1.25 ft + 1 ft + (1/2) × 11.84 ≤ 11.84 ft or 6ft E = 8.17 ft > 6 ft Therefore E = 6 ft Because the strip width is limited to 6′, one-lane loaded (wheel line = ½ lane load) with a multiple presence factor, m (chapter 4, Barker and Puckett) of 1.2 will be critical. Hence edge strip moment per foot width is equal to: MLL+IM (Edge strip) = ½ × (593) × 1.2/6 = 59.3 ft-kip/ft Mu = 1.05 (1.25MDC + 1.5MDW + 1.75MLL+IM) Mu = 1.05 (1.25 × 42 + 1.5 × 5.33 + 1.75 × 59.3) Mu (edge strip) = 172.48 ft-kip/ft = 2069.79 in-kip/ft

Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 28 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar

15"

12"

Introduction to Bridge Engineering

12'/2 = 6' Wheel lines Lane load

6' maximum Figure 21: Live load placement for edge strip. Step No 4: Design. (a) Design for Interior strip: Interior strip moment (Mu) = 155.3 ft-kip/ft = 1863.6 in-kip/ft Effective depth of bridge slab (d) = h – cover – ½ × Dia of bar used Using #8 bar, effective depth is: Bottom cover for slab is taken equal to 1 inch. d = 22 – 1 – ½ × 1 = 20.5 inch Asmin = 0.0018 × 12 × 22 = 0.47 in2 As = Mu/{Φfy (d – a/2)} Let a = 0.2d = 0.2 × 20.5 = 4.1 inches Therefore, As = 1863.6/{0.9 × 60 × (20.5 – 4.1/2)} = 1.87 in2 > Asmin Trial 1: a = Asfy/(0.85fc′b) = 1.87 × 60/ (0.85 × 4 × 12) = 2.75 inch As = 1863.6/{0.9 × 60 × (20.5 – 2.75/2)} = 1.804 in2 Trial 2: a = 1.804 × 60/ (0.85 × 4 × 12) = 2.65 inch As = 1863.6/{0.9 × 60 × (20.5 – 2.65/2)} = 1.80 in2, O.K. Use #8 bar with bar area = 0.79 in2 Spacing = (0.79/1.80) × 12 = 5.33 inches ≈ 5 inches c/c Use #8 @ 5 inches c/c.

Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 29 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar

Introduction to Bridge Engineering

(b) Distribution reinforcement for interior strip (bottom transverse reinforcement) {A5.14.4.1}: The amount of bottom transverse reinforcement may be taken as a percentage of the main reinforcement required for positive moment as 100/√L ≤ 50 % 100/√L = 100/√35 = 16.9 % < 50 % Therefore, bottom transverse reinforcement = 0.169 × 1.80 = 0.304 in2 Using #5 bar, with bar area = 0.31 in2 Spacing = (0.31/0.304) × 12 = 12 inches c/c Maximum spacing for temperature steel reinforcement in one way slab according to ACI 7.12.2.2 is minimum of: (i) 3hf =3 × 22 = 66″ (ii) 18″ Finally use #5 @ 12 inches c/c. (c) Design for Edge strip: Edge strip moment (Mu) = 172.48 ft-kip/ft = 2069.79 in-kip/ft Effective depth of bridge slab (d) = h – cover – ½ × Dia of bar used Using #8 bar, effective depth is: Bottom cover for slab is taken equal to 1 inch. d = 22 – 1 – ½ × 1 = 20.5 inch Asmin = 0.0018 × 12 × 22 = 0.47 in2 As = Mu/{Φfy (d – a/2)} Let a = 0.2d = 0.2 × 20.5 = 4.1 inches Therefore, As = 2069.79/{0.9 × 60 × (20.5 – 4.1/2)} = 2.00 in2 > Asmin Trial 1: a = Asfy/(0.85fc′b) = 2.00 × 60/ (0.85 × 4 × 12) = 2.94 inch As = 2069.79/{0.9 × 60 × (20.5 – 2.94/2)} = 2.014 in2 Trial 2: a = 2.014 × 60/ (0.85 × 4 × 12) = 2.96 inch Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 30 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar

Introduction to Bridge Engineering

As = 2069.79/{0.9 × 60 × (20.5 – 2.96/2)} = 2.014 in2, O.K. Use #8 bar, with bar area = 0.79 in2 Spacing = (0.79/2.014) × 12 = 4.7 inches ≈ 4.5 inches c/c Finally use #8 @ 4 inches c/c. (d) Distribution reinforcement for edge strip: Bottom transverse reinforcement = 0.169 × 2.014 = 0.34 in2 Spacing = (0.31/0.34) × 12 = 11 inches c/c Maximum spacing for temperature steel reinforcement in one way slab according to ACI 7.12.2.2 is minimum of: (i) 5hf = 3 × 22 = 66″ (ii) 18″ Finally use #5 @ 8 inches c/c. (e) Shrinkage and temperature reinforcement in top of slab (long and transverse both): For grade 60 steel, Ast = 0.0018Ag = 0.0018 × 12 × 22 = 0.47 in2 Use #5 bars, with bar area = 0.31 in2 Spacing = (0.31/0.47) × 12 = 8 inches c/c Finally use #5 @ 8 inches c/c. Final Recommendation: Main steel (bottom) = #8 @ 4″ c/c for interior as well as exterior. Transverse bottom reinforcement = #5 @ 8″ c/c throughout. Top steel (long and transverse) = #5 @ 8″ c/c.

Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 31 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar

Introduction to Bridge Engineering

Step No 5: Drafting. W = 44' roadway

15" 3" F.W.S

15" 34"

22"

W = 46.5'

Transverse Section. #5 @ 8" c/c

#5 @ 8" c/c

#5 @ 8" c/c

22"

#8 @ 4" c/c

3.5"

46.5'/2 = 23.35'

Figure 22: Reinforcement details in half transverse section.

Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 32 of 33

Department of Civil Engineering, N-W.F.P UET, Peshawar

Introduction to Bridge Engineering

References ¾ Design of Concrete Structures by Nilson, Darwin and Dolan (13th ed.), ¾ Design of Highway Bridges by Richard M. Barker.

Prof Dr. Qaisar Ali (http://www.eec.edu.pk)

Page 33 of 33

View more...

Comments

Copyright ©2017 KUPDF Inc.
SUPPORT KUPDF