Double Skin Air Handling Units Screwless Cabinet for low leakage and assured Indoor Air Quality

User’s Manual

DOUBLE SKIN AHUs SCREWLESS

First published February 2009 No part of this publication may be reproduced in any manner whatsoever without permission in writing from the President, Electro Mechanical Projects, Blue Star Limited. While due care has been taken to avoid errors or misinterpretation, Blue Star Limited is neither liable nor responsible for consequence of any action taken, on the basis of this publication. Since ASHRAE standards use the FPS system, FPS nomenclature is used in some places in this publication for convenient reference. Published by Blue Star Limited, Airconditioning Projects Division. For restricted circulation only. Not for sale.

2

USER'S MANUAL

CONTENTS Introduction ..................................................................................................................................

4

Features of Double Skin Horizontal Floor Mounted AHU ...........................................................

6

Technical Data .............................................................................................................................

8

Features of Double Skin Vertical Floor Mounted AHU ................................................................ 10 Technical Data ............................................................................................................................. 11 Features of Double Skin Ceiling Suspended AHU ...................................................................... 13 Technical Data ............................................................................................................................. 14 Transportation and Storage ......................................................................................................... 25 Packing List (typical) ................................................................................................................... 27 Double Skin Horizontal AHU Assembly Procedure ..................................................................... 33 Assembly the AHU ....................................................................................................................... 35 Recommended Tools ................................................................................................................... 50 Electrical Information .................................................................................................................. 51 Cooling and Heating Coil Installation .......................................................................................... 52 Condensate Drain Piping ............................................................................................................ 54 Air System ................................................................................................................................... 55 Pre-Start Up ................................................................................................................................. 56 Operation ..................................................................................................................................... 58 Maintenance ................................................................................................................................ 59 Wintering System Components .................................................................................................. 61 Removal or Reinstallation of Components ................................................................................. 62 Installation of Double Skin Vertical AHU ..................................................................................... 64 Installation of Double Skin Ceiling Suspended AHU .................................................................. 65 Troubleshooting ........................................................................................................................... 66 Spare Parts List ........................................................................................................................... 69 Field Feed Back Card .................................................................................................................. 82 Warranty Claim ............................................................................................................................ 84 Blue Star Service Centres .......................................................................................................... 86

3

DOUBLE SKIN AHUs SCREWLESS

Introduction Double Skin Air Handling Units with Screwless Cabinet For assured air quality Blue Star, India’s largest and preferred airconditioning company has been providing expert cooling solutions for nearly six decades. It is with this expertise we bring to you a wide range of air handling units manufactured at our own world-class factories. The Double Skin Air Handling Unit, as the name suggests has an outer casing made of sandwicthed panels, resulting in low noise, sturdy construction and better thermal insulation. These have been completely redesigned in “Screwless Cabinet” construction. Taper Wedges are used for fixing and locking of the insulated panels with aluminum frame.

Advantages of new ‘Screwless Cabinet’ construction: •

Reliability and Longer Life Rigid framework comprises an assembly of externally rounded extruded aluminum anodized profiles that are anticorrosive and fiberglass corner joints that avoid condensation at corners. The panels are pressure injected with polyurethane foam, using CFC free R-141 b blowing agent. High and uniform PUF density of 38 ±2 kg/m3 provides better thermal conductivity and sound attenuation properties.



Better Aesthetics No gaps and level difference at panel joints. Fixing screws are avoided in assembling panels. The colour of the AHU is texture finish gray.



High Indoor Air Quality Double skin panel construction allows easy inspection, cleaning and maintenance of the smooth inner surface, reducing the risk of dirt and bacteria accumulation. There is no erosion of internal insulation material to contaminate the air stream. Improved Panel frame arrangement by overlapping wedge and special gasket reduces air leaks into the casing significantly. This maintains the Indoor Air Quality (IAQ) and also provides the better thermal and acoustic performance.



Low Noise Usage of double skin casing, imported AMCA certified fans, anti vibration spring isolators, which isolated the fan from the main structure thus minimizing vibration and results in low operation noise.



Energy Efficiency The units utilize Blue Star free flow coils (Coil Nomenclature CDW, CDX, YDW, YDX). The Fins of these coils have a mild ripple, die formed channels to improve heat transfer efficiency and hence are energy efficient.

4

USER'S MANUAL



Ease of Assembly and Maintenance New construction leads to faster assembly. The coil is placed on the sliding channel for ease in service and maintenance.



Reduces Air bypass in Filter Section New Design of Filter Frame flush with the cabinet minimizes the chance of air leakage between the filter frame and the casing.



Standard Filter Sizes The filter sizes are standardized to the internationally recognized standard of four sizes in all horizontal AHUs. The filters are pleated to provide more filtration area.



Compact Design Floor Mounted Equipment footprint has been optimized to make the units more compact. Key components like Cooling Coil, Blower Assembly and Filters are redesigned for compact design and better performance.

5

DOUBLE SKIN AHUs SCREWLESS

Features Double Skin Horizontal Air Handling Units – Floor Mounted Type The horizontal floor mounted units are ideal units to handle high air quantity. The composite design sections offer both sturdy construction and flexible combination of components such as coils, filters, etc to suit specific applications hence they are widely used in industrial, clean room and large commercial airconditioning. As all major components are aligned to the base tray, it is maintenance and service friendly. These Double Skin Horizontal Floor mounted Air Handling Units are available in 37 models with air quantity varying from 3250 to 60600 CMH.

Standard features of the Units: a. Casing Rigid framework, comprising of smooth, rounded extruded aluminium anodized profiles with fibre glass corner joints. •

Double skin sandwiched panels: - Outer skin: 0.5 mm pre-painted galvanized sheet steel. - Inner skin: 0.5 mm plain galvanized sheet steel with 180 GSM Zinc Coating.



Panels are 24+1 mm thick, pressure injected with polyurethane foam, using CFC-free R-141b blowing agent. Uniform PUF density of 38+/- 2 kg/Cu.m provides better thermal insulation (K factor not exceeding 0.02 W/m-C.)



Insulated Panels are fixed on the aluminium frame using overlap design wedges. The design avoids use of screws for assembly of panels. 3 mm thick gasket is fixed on frame below the panels. The construction leads to improved air tightness of the cabinet and hence results in better Indoor Air Quality. It also improves the Thermal and Acoustic Performance.



The AHU base frame is of 14 G GSS and of 80 mm height.



Drain pan is made of 0.8 mm thick, Powder Coated Galvanized Sheet steel. The drain pan is insulated with 5 mm thick closed cell elastomeric Insulation to avoid surface condensation.

6

USER'S MANUAL

b. Cooling Coils The Coils are made of ½” Copper tube of thickness 0.36mm and the aluminium fins of thickness 0.12mm. Free flow fin configuration is formed in plain aluminium fin stock with mild ripples die formed channels provide excellent heat transfer capability with low air side Pressure drop. Mechanical expansion of copper tubes with aluminum fins assure good thermal bonding and improve heat transfer. Coils are complete with copper headers provided with air vent and drain plugs. In and out connections are of mild steel for convenience to connect to water line at site. The coils are placed on sliding channels for ease in service and maintenance. c. Fans Fans are of double inlet, double width type with forward curved impeller. The scroll and impeller are made of galvanized steel sheet. The fans are AMCA certified and are statically and dynamically balanced. The whole fan assembly is trim-balanced to ISO1940 & AMCA 204 – G2.5 Standard. Belt-Driven Fans are supplied with three phase, 415V, 50Hz, TEFC squirrel cage Hindustan / Spartan (A batiliboi group of company) make motor with IP55 protection and with Class ‘F’ insulation. d. Pre-Filters The Pre filter is 50 mm deep in box type construction of efficiency 90% down to 10 microns confirming to EU – 3 class of EN779 specification. The filter media is synthetic, non-woven fire retardant type. Pre-filter is pleated to provide more filtration area. The Pleated air filter incorporates a 100% synthetic thermal bonded media with an average arresting exceeding 80% by weight. The filter media is bonded to a metal grid on the air exiting side, Preventing fluttering and maintaining uniformity of the pleats. The filter pack is enclosed in an aluminium frame. e. Hinges and Handles The fan section is provided with an access door for ease in serviceability of fan and motor. Nylon handles can be operated from both inside and outside the casing and are user-friendly. f. View Port and Marine Lamp View Port is provided on fan door panel which helps to monitor fan and motor status. Marine lamp provides easy visibility. This needs to be electricity connected at site. g. Limit Switch Door limit switch automatically trips the motor when the door is opened and hence stop the blower. This needs to be connected up in series with no volt coil of the AHU starter. h. Damper Every AHU is supplied with a factory fitted GI, powder coated, opposed blade volume control damper to facilitate air balancing.

7

8

2700

2700

2700

2700

2700

2700

2935

2935

2935

2935

DHW4- 445 -C

DHW4- 455 -C

DHW4- 470 -C

DHW4- 490 -C

DHW4- 500 -C

DHW4- 520 -C

DHW4- 540 -C

DHW4- 570 -C

DHW4- 600 -C

2540

DHW4- 340 -C

DHW4- 430 -C

2335

DHW4- 325 -C

2700

2335

DHW4- 300 -C

2635

2335

DHW4- 290 -C

DHW4- 410 -C

2390

DHW4- 265 -C

DHW4- 390 -C

2175

DHW4- 255 -C

2635

2175

DHW4- 240 -C

2635

2175

DHW4- 230 -C

DHW4- 370 -C

2175

DHW4- 220 -C

DHW4- 355 -C

2035

1865

DHW4- 150 -C

2035

2175

DHW4- 135 -C

DHW4- 200 -C

1670

DHW4- 190 -C

1670

DHW4- 110 -C

DHW4- 120 -C

1865

1670

DHW4- 100 -C

2035

1510

DHW4- 080 -C

DHW4- 175 -C

1715

1510

DHW4- 070 -C

DHW4- 160 -C

1510

1370

DHW4- 050 -C

900

3290

3290

2935

2935

3290

3290

3290

3000

2935

2935

2635

2635

2635

2635

2635

2635

2390

2390

2220

2175

2035

2015

2015

2015

2015

1875

1875

1875

1460

1715

1370

1370

1105

1105

1370

1370

mm

mm

DHW4- 035 -C

Width

2575

2465

2510

2510

2130

2130

2130

2150

2210

2210

2205

2150

2150

2150

1890

1815

1890

1890

1890

1815

1815

1815

1815

1575

1495

1475

1495

1495

1515

1200

1200

1200

1170

950

950

885

885

mm

Height

AHU Overall Dimension

Length

DHW4- 040 -C

AHU MODEL

2896

2896

2642

2642

2946

2896

2794

2692

2642

2591

2337

2337

2286

2337

2337

2337

2083

1981

1829

1829

1727

1676

1575

1727

1727

1575

1473

1422

1168

1422

1372

1168

1067

1067

813

711

559

mm

Fin Length

2286

2159

2223

2159

1842

1842

1842

1842

1842

1842

1905

1842

1778

1651

1588

1524

1588

1588

1588

1524

1524

1524

1524

1270

1207

1207

1207

1143

1270

953

889

953

889

699

699

635

635

mm

Fin High

6.62

6.25

5.87

5.70

5.43

5.33

5.15

4.96

4.86

4.77

4.45

4.30

4.06

3.86

3.71

3.56

3.31

3.15

2.90

2.79

2.63

2.55

2.40

2.19

2.08

1.90

1.78

1.63

1.48

1.35

1.22

1.11

0.95

0.75

0.57

0.45

0.35

Sq.m.

Coil Area

35625

33646

31597

30694

29400

28698

27650

26684

26181

25300

23958

23160

21875

20800

19965

19167

17795

16927

15625

15000

14167

13750

12904

11806

11200

10226

9566

8825

7986

7292

6470

5990

4861

4010

3056

2431

1910

CFM

60563

57198

53715

52180

49980

48787

47005

45363

44508

43010

40729

39372

37188

35360

33941

32584

30252

28776

26563

25500

24084

23375

21937

20070

19040

17384

16262

15003

13576

12396

10999

10183

8264

6817

5195

4133

3247

CMH

Air Qty

Standard Coil Size

FDA 1000 TM

FDA 1000 TM

FDA 1000 TM

FDA 1000 TM

FDA 900 TM

FDA 900 TM

FDA 900 TM

FDA 900 TM

FDA 900 TM

FDA 900 TM

FDA 900 TM

FDA 800 TM

FDA 800 TM

FDA 800 TM

FDA 800 TM

FDA 710 CM

FDA 710 CM

FDA 710 CM

FDA 710 CM

FDA 630 CM

FDA 630 CM

FDA 630 CM

FDA 630 CM

FDA 560 CM

FDA 560 CM

FDA 560 CM

FDA 500 CM

FDA 500 CM

FDA 500 CM

FDA 450 CM

FDA 450 CM

KAT18 X 18CM

KAT18 X 13CM

KAT15 X 15CM

KAT12 X 12CM

KAT12 X 9CM

KAT10 X 10CM

Kruger

1266 * 1266

1266 * 1266

1266 * 1266

1266 * 1266

1130 * 1130

1130 * 1130

1130 * 1130

1130 * 1130

1130 * 1130

1130 * 1130

1130 * 1130

1006 * 1006

1006 * 1006

1006 * 1006

1006 * 1006

898 * 898

898 * 898

898 * 898

898 * 898

800 * 800

800 * 800

800 * 800

800 * 800

714 * 714

714 * 714

714 * 714

638 * 638

638 * 638

638 * 638

568 * 568

568 * 568

557 * 478

430 * 478

471 * 404

395 * 341

309 * 341

331 * 289

W - mm X H - mm

Fan Opening

Fan & Motor Details Fan Model

Double Skin Floor Mounted Horizontal Draw Through Units 40mm TSP

10.49

9.91

9.31

9.04

10.87

10.61

10.22

9.87

9.68

9.35

8.86

10.81

10.21

9.7

9.31

11.23

10.42

9.92

9.15

11.07

10.45

10.14

9.55

10.93

10.37

9.47

11.1

10.24

9.26

10.67

9.47

10.62

11.17

9.95

10.71

10.89

9.43

m/sec.

65.9%

66.1%

65.8%

65.5%

63.3%

63.7%

64.3%

64.7%

64.9%

64.9%

64.5%

63.3%

63.7%

64.6%

64.9%

66.0%

67.0%

67.4%

68.0%

63.2%

63.7%

63.8%

63.9%

66.3%

67.0%

67.5%

62.7%

63.4%

63.8%

64.3%

64.6%

67.3%

68.6%

64.7%

62.0%

63.4%

63.3%

η

15

15

11

11

11

11

11

11

11

11

11

11

9.3

7.5

7.5

7.5

7.5

7.5

5.5

7.5

5.5

5.5

5.5

5.5

5.5

5.5

5.5

3.7

3.7

3.7

3.7

2.2

2.2

1.5

1.5

1.1

0.75

kW

65.9%

65.2%

63.9%

63.1%

64.8%

64.9%

64.8%

64.4%

64.0%

63.2%

61.8%

64.7%

64.9%

64.7%

64.4%

67.3%

67.9%

68.2%

67.4%

63.9%

64.0%

64.0%

64.0%

67.4%

67.4%

66.2%

63.5%

63.8%

63.3%

64.7%

62.9%

65.8%

69.2%

63.8%

60.9%

64.5%

61.0%

η

18.5

15

15

15

15

15

15

15

15

15

11

11

11

11

11

9.3

7.5

7.5

7.5

7.5

7.5

7.5

7.5

5.5

5.5

5.5

5.5

5.5

5.5

3.7

3.7

3.7

2.2

2.2

1.5

1.5

1.1

kW

Motor Power

50 mm TSP

Fan Outlet Fan Motor Fan Velocity Effieiency Power Efficiency

1550

1525

1500

1465

1425

1400

1380

1365

1340

1325

1300

1200

1180

1160

1140

1060

850

840

750

735

715

705

675

615

590

560

505

475

450

435

425

415

350

340

245

235

200

Kg.

With 4 RD Coil

1685

1650

1625

1590

1565

1540

1525

1500

1480

1465

1440

1325

1300

1285

1265

1150

940

925

825

800

785

775

735

655

640

615

555

525

500

470

460

445

375

365

260

250

215

Kg.

With 6 RD Coil

Operating Wt. (Approx)

DOUBLE SKIN AHUs SCREWLESS

Technical Specifications

DHW4 - 035-C DHW4 - 040-C DHW4 - 050-C DHW4 - 070-C DHW4 - 080-C DHW4 - 100-C DHW4 - 110-C DHW4 - 120-C DHW4 - 135-C DHW4 - 150-C DHW4 - 160-C DHW4 - 175-C DHW4 - 190-C DHW4 - 200-C DHW4 - 220-C DHW4 - 230-C DHW4 - 240-C DHW4 - 255-C DHW4 - 265-C DHW4 - 290 -C DHW4 - 300-C DHW4 - 325-C DHW4 - 340-C DHW4 - 355-C DHW4 - 370-C DHW4 - 390-C DHW4 - 410-C DHW4- 430-C DHW4- 445-C DHW4- 455-C DHW4- 470-C DHW4- 490-C DHW4- 500-C DHW4- 520-C DHW4- 540-C DHW4- 570-C DHW4- 600-C

AHU MODEL

1910 2431 3056 4010 4861 5990 6470 7292 7986 8825 9566 10226 11200 11806 12940 13750 14167 15000 15625 16927 17795 19167 19965 20800 21875 23160 23958 25300 26181 26684 27650 28698 29400 30694 31597 33646 35625

CFM 3247 4133 5195 6817 8264 10183 10999 12396 13576 15003 16262 17384 19040 20070 21998 23375 24084 25500 26563 28776 30252 32584 33941 35360 37188 39372 40729 43010 44508 45363 47005 48787 49980 52180 53715 57198 60563

CMH

Air Qty

22 28 32 42 42 46 54 56 46 56 58 62 68 68 62 66 68 72 72 78 82 92 92 92 90 92 92 102 104 106 110 114 116 104 104 114 114

Inch

Fin

20 20 22 22 28 30 28 30 40 36 38 38 38 40 48 48 48 48 26+24 26+24 26+24 48 26+24 26+26 28+28 30+28 30+30 30+28 30+28 30+28 30+28 30+28 30+28 34+34 36+34 34+34 36+36

3.82 4.86 6.11 8.02 10.21 11.98 13.13 14.58 15.97 17.50 19.13 20.45 22.43 23.61 25.83 27.50 28.33 30.00 31.25 33.85 35.59 38.33 39.93 41.53 43.75 46.32 47.92 51.35 52.36 53.37 55.38 57.40 58.40 61.39 63.19 67.29 71.25

Sq.Ft.

Tube High Coil Area Length

2 2 2 2 2 2 2 2 2 2 2

2 2 2 2 2 2 2

1 1 1 1

1 1 1/4 1/2 1/2 1/2 2 2 2 2 2 2 2 2 2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 2 2 2 2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2

Inch1

Coil In/Out Size

Standard Coil Size

D D D D D D B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B

4 Row C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C

6 Row

Coil Circuit

1 1 1 2 2 2 2 2 4 4 4 4 6 6 6 6 6 6 6 6 6 8 8 12 12 12 12 12 12 12 15 15 15 12 12 15 15 4 4 5 5

3 3 3 3 3 3 3 4 4

2 2 2 2

610 X 305 Qty

3 3

3 3

2 2

2 2 2

1 1

1 1

305 X 610

Filter sizes in mm (W X H) 610 X 610

Double Skin Floor Mounted Horizontal Draw Through Units

1 1

1 1

1 1

305 X 305

USER'S MANUAL

9

DOUBLE SKIN AHUs SCREWLESS

Features Vertical Double Skin Air Handling Units Vertical Air Handling Units are designed to occupy lesser floor space than the horizontal units. These units are preferred when floor space is a constraint. They are available in 10 models with airflow ranging from 3500 CMH to 30280 CMH and an external static pressure at 12 mm and 20 mm. These are predominantly used for applications where multiple units are required to aircondition a floor constrained by ceiling heights; duct sizing, floor space etc.

10

730

780

830

980

830

980

980

1041

1132

1132

DVW-4-050

DVW-4-070

DVW-4-100

DVW-4-140

DVW-4-170

DVW-4-200

DVW-4-250

DVW-4-270

DVW-4-300

mm

3466

3164

2932

2932

2728

2220

1763

1591

1388

1032

mm

2372

2372

2244

2009

2009

1892

1852

1525

1349

1283

mm

LENGTH WIDTH HEIGHT

DVW-4-035

AHU MODEL

3048

2794

2642

2642

2438

1930

1473

1321

1118

762

mm

FL

1080

1080

1016

826

762

762

762

572

508

508

mm

FH

Coil Details

3.29

3.02

2.68

2.18

1.86

1.47

1.12

0.75

0.57

0.39

Sq.m

Coil Area

Floor Mounted Vertical Double Skin Air Handling Unit

17708

16233

14444

11736

10000

7917

6042

4063

3056

2083

CFM

30104

27595

24556

19951

17000

13458

10271

6906

5194

3542

CMH

Air Qty.

557*478 - 1#

471*404 - 1#

395*341 - 1#

331*289 - 1#

H-mm

W-mm X

Fan

FDA 500C2M

FDA 500C2M

FDA 450C2M

KAT 18/18S2L

638*638 - 2#

638*638 - 2#

568*568 - 2 #

557*478 - 2#

KAT 18/13S2L 430*478 - 2 #

KAT 15/15S2L 471*404 - 2 #

KAT 18/18SL

KAT 15/15SL

KAT 12/12SL

KAT 10/10SL

Dia. in

Fan Model Opening Velocity

10.27

9.42

10.57

10.41

11.49

9.82

10.72

10.08

10.71

10.28

M/Sec

Fan Outlet

7.5

5.5

5.5

5.5

3.7

3.7

2.2

1.5

1.1

0.75

ESP

7.5

7.5

7.5

5.5

5.5

3.7

3.7

2.2

1.5

1.1

ESP

12 mm 20 mm

Motor kW

850

750

670

590

560

470

395

330

225

190

Kg.

950

815

745

650

610

520

435

360

245

205

Kg.

With 4 RD With 6 RD Coil Coil

Operating Wt. (Approx.)

USER'S MANUAL

11

12

W

110 120

DVW - 4 - 300 17708 30080

2

600

W 600

H 400

W 400

1

H 600

W 500

H 500

W 500

4

10

6

DVW - 270

DVW - 300

4

DVW - 200

DVW - 250

8

DVW - 170

6

6

8

500

6

600

DVW - 140

600

2 1/2

2 1/2

2 1/2

2

2

2

1 1/2

1 1/4

1 1/4

1

Inch

SIZE

DVW - 100

DVW - 070

DVW - 050

DVW - 035

H

500

W

600

6

2 5/8

2 5/8

2 5/8

2 1/8

2 1/8

2 1/8

1 5/8

1 3/8

1 3/8

1 1/8

Inch

H

W

35.42 CDW-12-A-4-H-B-34-L/R-120-L

32.47 CDW-12-A-4-H-B-34-L/R-110-L

28.89 CDW-12-A-4-H-B-32-L/R-104-L

MS

6 Rows Deep

SIZE

COIL NOMENCLATURE

400

W 400 2

H 500

35.5

32.3

29.1

23.3

20.7

17.2

12.9

9.0

6.5

4.3

FT²

Area

FILTER

CDW-12-A-6-H-B-34-L/R-120-L

CDW-12-A-6-H-B-34-L/R-110-L

CDW-12-A-6-H-B-32-L/R-104-L

CDW-12-A-6-H-B-26-L/R-104-L

CDW-12-A-6-H-B-24-L/R-96-L

CDW-12-A-6-H-C-24-L/R-76-L

CDW-12-A-6-H-C-24-L/R-58-L

CDW-12-A-6-H-C-18-L/R-52-L

CDW-12-A-6-H-C-16-L/R-44-L

CDW-12-A-6-H-D-16-L/R-30-L

H

HEADER CONNECTOR

MODEL

2

H

CDW-12-A-4-H-B-24-L/R-96-L

CDW-12-A-4-H-C-24-L/R-76-L

CDW-12-A-4-H-C-24-L/R-58-L

CDW-12-A-4-H-C-18-L/R-52-L

CDW-12-A-4-H-D-16-L/R-44-L

CDW-12-A-4-H-D-16-L/R-30-L

23.47 CDW-12-A-4-H-B-26-L/R-104-L

20.00

15.83

12.08

8.13

6.11

4.17

4 Rows Deep

COIL NOMENCLATURE

COPPER

FLAT FILTER SIZE (48mm THK.)

34

34

32

26

24

24

24

18

16

16

FT²

AREA

COIL

AHU

Frontal Flat Filter Sizes

104

DVW - 4 - 270 16233 27574

76

58

13448

10263

DVW - 4 - 250 14444 24536

7917

DVW - 4 - 140

52

44

96

6042

DVW - 4 - 100

6901

5190

104

4063

DVW - 4 - 070

30

Inch

High

Length

DVW - 4 - 200 11736 19936

3056

DVW - 4 - 050

3539

CMH

Tube

Fin

DVW - 4 - 170 10000 16987

2083

CFM

AIR QTY.

DVW - 4 - 035

AHU MODEL

Coil Details

Vertical Double Skin Air Handling Unit

2 5/8

2 5/8

2 5/8

2 1/8

2 1/8

2 1/8

1 5/8

1 3/8

1 3/8

1 1/8

Inch

SIZE

HEADER

COPPER

2 1/2

2 1/2

2 1/2

2

2

2

1 1/2

1 1/4

1 1/4

1

Inch

SIZE

CONNECTOR

MS

DOUBLE SKIN AHUs SCREWLESS

USER'S MANUAL

Features Ceiling Suspended Units These units as the name suggests should be suspended from the ceiling thus requiring no floor space. These units are ideal for commercial application where floor space is at a premium. As they are compact and can be tucked away above the false ceiling, they find a place inside the conditioned area itself. Thereby reducing installation costs and also remains unobtrusive giving flexibility to the design of the interior. Panels are fixed to the framework by wedges thus avoiding usage of screws. They are available in 18 models with air quantity ranging from 1770 CMH to 13568 CMH and an external static pressure range of 12 mm and 20 mm. The three models DCWSL-035,DCWSL-050 & DCWSL-070 are available in both direct driven with 3 speed single phase motor or belt driven with 3 phase motor and the other AHUs are available in belt driven models only.

13

14

556

556

556

662

662

810

810

810

810

810

810

1238

1238

1743

1743

DCW4SL-027-B 908

DCW4SL-035-B 908

DCW4SL-042-B 948

DCW4SL-050-B 948

DCW4SL-060-B 1048 2200

DCW4SL-070-B 1048 2200

DCW4SL-078-B 1048 2130

DCW4SL-085-B 1048 2130

DCW4SL-093-B 1099 2097

DCW4SL-100-B 1099 2097

DCW4SL-110-B 1149 2333

DCW4SL-118-B 1149 2333

DCW4SL-127-B 1149 2638

DCW4SL-135-B 1149 2638

mm

556

556

556

556

mm

784

H

W

mm

L

DCW4SL-017-B 908

AHU Model

AHU Overall Dimensions

(b) Belt Driven Type

2337

2184

2032

1880

1727

1778

1829

1676

1930

1727

1473

1219

965

762

508

mm

FL

0.735

0.561

0.368

Sq. Mt

Coil Area

3958

3021

1979

CFM

635

635

635

635

635

572

508

508

381

381

381

381

381

381

381

mm

FH

1.484

1.367

1.290

1.194

1.097

1.016

0.929

0.852

0.735

0.658

0.561

0.465

0.368

0.290

0.194

Sq. Mt

Coil Area

7986

7465

6944

6424

5903

5469

5000

4583

3958

3542

3021

2500

1979

1563

1042

CFM

13568

12683

11798

10913

10035

9297

8500

7791

6729

6021

5135

4250

3362

2655

1770

CMH

Air Quantity

6729

5135

3365

CMH

Air Quantity

Standard Coil Size

1930 381

DCW4SL-070-D 1048 2200 556

381

965

1473 381

mm

FH

DCW4SL-050-D 948 1743 556

mm

mm

mm mm

FL

H

W

L

Standard Coil Size

DCW4SL-035-D 908 1238 556

AHU Model

AHU Overall Dimensions (Fan, Coil, Prefilter)

(a) Direct Driven Type

Fan Model

395 * 341 – 2 #

395 * 341 – 2 #

309 * 521 – 2 #

309 * 521 – 2 #

331 * 289 – 2 #

265 * 289 – 2 #

265 * 289 – 2 #

232 * 262 – 2 #

331 * 289 - 1#

265 * 289 - 1#

232 * 262 - 1#

W-mm * H-mm

Fan Opening

KAT 15-15 S2L 471 * 404 – 2 #

KAT 15-15 S2L 471 * 404 – 2 #

KAT 15-11 S2L 373 * 404 – 2 #

KAT 15-11 S2L 373 * 404 – 2 #

KAT12-12 S2L

KAT12-12 S2L

KAT12-9 S2L

KAT12-9 S2L

KAT10-10 S2L

KAT10-8 S2L

KAT10-8 S2L

KAT 9 - 7 S2L

KAT10-10 SL

KAT10-8 SL

KAT 9 - 7 SL

Kruger

331 * 289 - 1#

265 * 289 - 1#

331 * 289 - 1#

W-mm * H-mm

Fan Opening

Fan & Motor Details

KDD10-10 S2L

KDD10-08 S2L

KDD10-10 SL

Kruger

Fan Model

9.91

9.26

10.88

10.06

10.35

9.59

11.20

10.27

9.77

10.92

9.31

9.71

9.77

9.64

8.09

m/s

Fan Outlet Velocity

9.77

9.31

9.77

m/s

3.7

3.7

3.7

2.2

2.2

2.2

2.2

2.2

1.5

1.5

1.1

1.1

0.75

0.55

0.55

kW

Motor Power

3.7

3.7

3.7

3.7

3.7

3.7

2.2

2.2

2.2

1.5

1.5

1.1

1.1

0.75

0.55

kW

Motor Power

20mm ESP

0.55

0.55

0.55

Motor Kw.

12 mm ESP

12mm ESP

Fan Outlet Velocity

Fan & Motor Details

Size

610 * 610

610 * 610

4

4

3

610 * 610

3 1

610 * 610 305 * 610

1

3

3

305 * 610

610 * 610

610 * 610

1 3

500 * 500

3

500 * 500 400 * 500

1

4

4

3

3

2

2

1

#

Qty

400 * 500

500 * 400

500 * 400

500 * 400

500 * 400

500 * 400

500 * 400

600 * 400

-mm * H-mm

Size

Pre Filter (50mm thick.)

500 * 400

500 * 400

500 * 400

4

3

2

#

Operating Wt. (Approx.)

290

195

165

Kg.

310

215

180

Kg.

With 4 RD With 4 RD Coil Coil

Operating Wt.

450

440

425

415

395

385

360

345

330

320

225

215

190

175

150

Kg.

49 5

475

460

445

435

425

400

380

360

348

245

230

205

195

170

Kg.

With 4 RD With 4 RD Coil Coil

Qty

Pre Filter (50mm thick.)

W-mm * H-mm

Double Skin Ceiling Suspended AHU-Technical Specification

DOUBLE SKIN AHUs SCREWLESS

1042

1563

1979

2500

3021

3542

3958

4583

5000

5469

5903

6424

6944

7465

7986

DCW-027

DCW-035

DCW-042

DCW-050

DCW-060

DCW-070

DCW-078

DCW-085

DCW-093

DCW-100

DCW-110

DCW-118

DCW-127

DCW-135

CFM

13576

12691

11805

10921

10035

9297

8500

7791

6729

6021

5136

4250

3364

2657

1771

CMH

Air Qty

DCW-017

AHU Model

92

86

80

74

68

70

72

66

76

68

58

48

38

30

20

Inch

Fin Length

20

20

20

20

20

18

16

16

12

12

12

12

12

12

12

Tube High

50.17

47.22

44.27

41.32

38.37

35.42

32.47

28.89

23.47

20.00

15.83

12.08

8.13

6.11

4.17

FT²

Coil Area

CDW-12-A-4-H-B-20-L/R-92-L

CDW-12-A-4-H-B-20-L/R-86-L

CDW-12-A-4-H-B-20-L/R-80-L

CDW-12-A-4-H-B-20-L/R-74-L

CDW-12-A-4-H-B-20-L/R-68-L

CDW-12-A-4-H-B-18-L/R-70-L

CDW-12-A-4-H-B-16-L/R-72-L

CDW-12-A-4-H-B-16-L/R-66-L

CDW-12-A-4-H-B-12-L/R-76-L

CDW-12-A-4-H-B-12-L/R-68-L

CDW-12-A-4-H-C-12-L/R-58-L

CDW-12-A-4-H-C-12-L/R-48-L

CDW-12-A-4-H-D-12-L/R-38-L

CDW-12-A-4-H-D-12-L/R-30-L

CDW-12-A-4-H-D-12-L/R-20-L

4 Rows Deep

Coil Nomenclature

2 1/8

2 1/8

2 1/8

2 1/8

1 5/8

1 5/8

1 5/8

1 5/8

1 3/8

1 3/8

1 1/8

1 1/8

1 1/8

1 1/8

1 1/8

Inch

Copper Header Size

2

2

2

2

1 1/2

1 1/2

1 1/2

1 1/2

1 1/4

1 1/4

1

1

1

1

1

Inch

MS Connector Size

Double Skin Ceiling Suspended AHU - Coil Details

CDW-12-A-6-H-B-20-L/R-92-L

CDW-12-A-6-H-B-20-L/R-86-L

CDW-12-A-6-H -B-20-L/R-80-L

CDW-12-A-6C-H-B-20-L/R-74-L

CDW-12-CA-6-H-B-20-L/R-68-L

CDW-1 2-A-6-H-B-18-L/R-70-L

CDW-12-A-6-H-B-16-L/R-72-L

CDW-12-A-6-H-B-16-L/R-66-L

CDW-12-A-6-H-B-12-L/R-76-L

CDW-12-A-6-H-B-12-L/R-68-L

CDW-12-A-6-H-C-12-L/R-58-L

CDW-12-A-6-H-C-12-L/R-48-L

CDW-12-A-6-H-D-12-L/R-38-L

CDW-12-A-6-H-D-12-L/R-30-L

CDW-12-A-6-H-D-12-L/R-20-L

6 Rows Deep

Coil Nomenclature

2 1/8

2 1/8

2 1/8

2 1/8

1 5/8

1 5/8

1 5/8

1 5/8

1 5/8

1 5/8

1 1/8

1 1/8

1 1/8

1 1/8

1 1/8

Inch

Copper Header Size

2

2

2

2

1 1/2

1 1/2

1 1/2

1 1/2

1 1/2

1 1/2

1

1

1

1

1

Inch

MS Conenctor Size

USER'S MANUAL

15

DOUBLE SKIN AHUs SCREWLESS

½” CDW / CDX Coils: Nomenclature 1. CDW Water Cooling Coils: CDW

12

A

4

H

C

24

R

94

Comfort ½” Water Cooling Coil Fins per Inch, 12 FPI Fins Material, A: Aluminium Rows Deep (RD), 2, 4, 6, 8 Air Flow, H: Horizontal Circuiting (Tubes per Circuit), B=4, C=6, D=8 Tubes High (TH), 12 to 48 Hand, R: Right, L: Left Finned Length (FL), 26” to 114” L: Loose

Note: Field to specify (a) Circuit type: B. C. D; (b) Hand-off connection: LHS, RHS. Coil Specifications: ½” OD Copper tube, Tube thinkness 0.36mm, Fin thickness: 0.12mm Aluminium fins.

16

L

USER'S MANUAL

2. CDX Direct Expansion Cooling Coils:

CDX

12

A

4

H

C

24

R

94

L

0156

40

8

12

Comfort ½” Direct Exp. Fins per Inch, 12 FPI Fins Material A: Aluminium Rows Deep (RD), 2, 4, 6, 8 Air Flow, H: Horizontal Circuiting (Tuber per Circuit), B=4, C=6, D=8 Tubes High (TH), 12 to 48 Hand. R: Right, L: Left Finned Length (FL), 26" to 114" L: Loose Total Coil Load in MBH, 1 MBH = 1000 BTU/HR Suction Temp., Deg. F Tubes per Circuit, B=4, C=6, D=8 No. of Circuits

Note: Field to specify (a) Circuit type: B. C. D; (b) Hand-off connection: LHS, RHS. Coil Specifications: ½” OD Copper tube, Tube thinkness: 0.36mm, Fin thickness: 0.12mm Aluminium fins.

17

DOUBLE SKIN AHUs SCREWLESS

Double Skin Horizontal Floor Mounted ('E' Family) Design: Computerised selection AHU selection software is used for optimal model selection for customised needs. The selection software provides the following information: •

Overall dimensional details

• Technical Data Sheet



Sections selected

• GA Drawing



Details of Individual sections

• Costing Sheet

Casing Rigid framework, comprising of externally chamfered extruded aluminum anodised profiles, with fibre glass corner joints. •

Double skin sandwiched panels : Inner Skin

: 0.5mm plain galvanized sheet confirming to IS 277.

Sheet options

: 0.6mm GP, 0.8mm GP, 1.0mm GP, 1.2mm GP, 0.9AI, 1.2mm Al, 0.6mm SS(304), 0.8mm SS(304).

Outer Skin

: 0.5mm pre-painted galvanised sheet.

Sheet options

: 0.6mm PP, 0.8mm PP, 1.0mm PP, 0.9mm AI, 1.2mm Al, 0.6mm SS-304, 0.8mm SS-304.



Panels are pressure injected with polyurethane foam, using CFC-free R-141b blowing agent. High and uniform PUF density of 38+ 2Kg/m3 provide better thermal insulation “K” factor (not exceeding 0.02 Watt / MC) and sound attenuation properties. The following options can be selected based on customer requirement.



Option 1: Panels of 24+ 1mm thickness with standard aluminum extrusions and fiberglass corner joints.



Option 2: Panels of 46+ 1mm thickness with “internally coved” thermal break aluminum extrusions and fiberglass corner joints. Recommended for total static pressure above 85 mm and these AHUs are suitable for outdoor installation.



Panels are fixed to frame with tapered wedges inserted in aluminum extrusions. The gaskets have stable thermal conductivity and less water vapour permeability.



Fan and motor are mounted on aluminium extruded slide rail base frame. It is isolated from main casing by using vibration isolators (using 15mm nominal deflection). To arrest vibration, fan outlet is connected to the AHU casing using fire and moisture resistant canvas.



Hinged service door in fan section provides easy access to fan and motor. View port is provided on fan door panel to help to monitor fan and motor status. Marine lamp provides easy visibility. Door limit switch automatically trips the motor when the door is opened and hence stop the blower.



Drain pan with differential slope assures quick and complete water drainage ensuring high Indoor Air Quality (IAQ). Drain Pan is 80mm deep and fabricated from 0.8 mm thick GI Powder Coated and optional 1.25mm powder coated or corrosion resistant SS-304 stainless steel is available. The drain pan is insulated for thermal protection with 5mm thick closed cell elastomeric insulation to avoid surface condensation.



AHUs with stack coils have additional intermediate G.I powder coated / stainless steel drain pan to collect the condensate of top coil and drain through PVC drop tubes to the main drain pan without flooding the lower coil.

18

USER'S MANUAL



AHU is supplied with factory fitted GI, powder coated, opposed blade volume control damper to facilitate field balancing.



Aluminium die cast powder coated hinges provide adequate strength to the door. Nylon handles can be operated from both inside and outside the casing and are user friendly.

Cooling Coils Free flow fin configuration formed by mild ripples and die formed channels provide excellent heat transfer capability with low air pressure drop. Mechanical expansion of copper tube with aluminium fins assures tight bonding, providing optimum heat transfer. Coils are complete with copper headers. Water or Direct Expansion coils can be selected based on requirement. Water coils are self draining and vented type. Design working pressure is 250 psig. at 300°F. The following options of sectional length can be selected based on requirement: •

Coil Section up to 6 Row Deep



Coil Section up to 8 Row Deep



Cooling Coil 6 Row Deep and Heating Coil 2 Row Deep



Cooling Coil 8 Row Deep and Heating Coil 2 Row Deep

Fans Fans are imported, AMCA certified, energy efficient, with double inlet, double width, forward or backward curved impeller. All wheels are statically and dynamically balanced. Fan bearings are self-aligning, pillow block or flanged type regreasable ball bearings. The scroll and impeller are made of galvanised steel sheet. The fan is V-belt driven through a 3 phase, 415V±6%, 50 Hz AC, squirrel cage, TEFC induction, 4 Pole, IP55, Class ‘F’ motor. AHUs with static pressure requirement of more than 85mm are suggested with backward curved impeller.

Pre Filters (50mm thick) Pre Filters are pleated to provide more filtration area. The filters are of the cassette type. The filter media are of the synthetic non-woven type, supported with aluminium and HDPE mesh and generally conforming to EU-3 of EN-779 specifications. Filter efficiency is 90% down to 10 micron. Filters are provided with handles for easy removal.

Mixing Box / Inlet Section (Optional) Section is designed for interconnecting return air and fresh air. The following options can be selected based on requirement: •

Mixing Box section with one Return Air Damper and Pre Filters



Mixing Box section with one Fresh Air Damper & Pre Filters.



Mixing Box section with Return and Fresh Air Damper and Pre Filters

Mixing sections are fitted with parallel or opposed blade multi-leaf dampers suitable for manual or motorised operations. Select aluminium damper only for requirement with motorised modulating motor operation.

19

DOUBLE SKIN AHUs SCREWLESS

Fine / Bag Filter Section (Optional) Section is designed for 300/500/600mm deep Fine filters or Bag filter with 25 mm flange. The filters are arranged vertically in the specially designed heavy-duty galvanized sheet steel frame to avoid air bypass and are removable from front. Filters are mounted on frame with positive clamping arrangement. Filter section is provided with access door panel, with aluminum die-cast powder coated heavy duty hinges and nylon handles with positive locking. The handle can be operated from both ends for ease in serviceability.

HEPA Filter Section (Optional) Section is designed for 300mm deep HEPA Filters with 25 mm flange. The filters are arranged vertically in the specially designed heavy-duty galvanised sheet steel frame to avoid air bypass and are removable from front. Filters are mounted on frame with positive clamping arrangement. HEPA Filter section is provided with access door panel, with aluminum die-cast powder coated heavy duty hinges and nylon handles with positive locking. The handle can be operated from both ends for ease in serviceability. HEPA Filter should be selected only after Fine or Bag filters.

Combination Filter Section (Optional) Section is designed for combination of 50mm thick Pre Filters mounted together with Fine / Bag Filters. The filters are arranged vertically in the heavy duty galvanised sheet steel frame and removable from front. Filters are mounted on frame with positive clamping arrangement. Fine / Bag filters can be removed only after the removal of prefilter. All filters are also available in Aluminium flange for phama or clean room application.

Face and Bypass Damper Section (Optional) Standard face and bypass dampers are of opposed blade type. Face damper is at the bottom in front of the coil, and bypass damper is on the top. Two dampers are interlocked and provide a single control point. The opening size in the frame for mounting the Face damper will be equal to maximum size of coil Select aluminium damper only for requirement with motorised operation with modulating motor. Motorised actuators are of direct mounting type. It could be two position (on/off) or modulating (input signal 0-10V DC or 4-20mA).

Droplet Eliminator Section (Optional) To avoid condensate or spray of water carryover into the fan section, suggest use the following droplet eliminator after the coil or spray section: • 2 Pass GI / PVC Droplet Eliminator • 4 Pass GI / PVC Droplet Eliminator

Humidification Section (Optional) Celdek type humidification section is provided in AHU for cooling and humidification purpose, this is required in places where the temperature is quite high with low humidity. In humidification section 175 mm high sump is used to store the water and this water is circulated and spread over the cellulose Pad (Celdek Pad) with the help of Pump and piping arrangement. The cellulose pad is designed at 500 FPM (2.54m/sec) of Air velocity and it is available in 6" (150 mm), 8" (200 mm) of thickness. 20

USER'S MANUAL

8" Cellulose pad should be used to get the saturation efficiency of about 90%. The droplet eliminator of 4 pass must be provided after the humidification section to avoid any water carry over in the supply air.

Heater Section Heater section with appropriate capacity of heater should be selected to maintain the RH. These heaters can be provided in number of stages and banks as per the requirement.

Heat Recovery Wheel Heat Recovery wheel is used in applications where we want to utilize the heating or cooling of the supply air without mixing with the fresh air. In other words heat recovery wheels are desirable where we want the heat transfer from supply air to the fresh air without the mass transfer. It is used in fresh air application in double tier arrangement. Heat recovery wheel is placed before the coil and as it recover some quantity of heat (Cooling) from the supply air, it helps reducing the load on the coil and hence lesser capacity of chiller/condensing unit is required. The effectiveness of the heat recovery wheel is about 75 – 80%.

Heat Pipe Run around type (Horse shoe type) or vertical heat pipe can be provided in our AHUs. Run around type Heat Pipe has Pre cooling and Re – Heating coils, connected through the refrigerant piping. The hot air interact with the Pre cooling side of the coil and get cooled, the refrigerant inside the coil get evaporated and get accommodated in the reheating coil. This pre cooling helps in reducing the load on the main coil and the air after passing through the main coil gets further cooled and is with high RH. The Re heating side of the coil exchanges the heat with this cooled and high RH Air, and gets converted into liquid form. This liquid state refrigerant due to gravity gets accumulated in the pre cooling coil. The Air After passing through the Re-Heating Coil gets heated to maintain the desirable temp. 22-24°C in the room with a moderate RH of 50-60% in the room, which is desirable. The effectiveness of the heat Pipe is about 45 – 65 %. The vertical type of heat pipe is used in two tier arrangement, which recovers the sensible heat from return air.

Variable Pitch pulley Variable Pitch Pulley can be provided in AHUs, which can be set as per the Air Quantity requirement.

Flat belt Flat belt with pulley arrangement cab be provided on demand.

Damper Actuator Damper Actuator can be provided to modulate the dampers of the AHUs. 21

DOUBLE SKIN AHUs SCREWLESS

VFD Variable frequency drive can be provided with AHU, which helps in maintaining varying air flow by changing the frequency and thereby Rpm of the motor to maintain the desired conditions. HVAC VFD with inbuilt basic controls can also be provided.

UV emitter UV emitter is used to improve the indoor Air Quality. It can be mounted on the coil and hence does not require any extra space to mount.

Activated carbon filter Activated carbon filter is used to remove the odor from the Air and can be provided in our AHU.

Empty Section Sections with different lengths are available to suit any specific requirement.

Base Channel Entire unit is completely supported by a full-perimeter base rail channel. The base rail is constructed of 2mm thick galvanised sheet steel and has intermediate cross member for unit support.

Unit Assembly Units are despatched ex-factory upto E-500 in Top and Bottom assembled condition, and above that in dismantled condition. The assembly of units will be carried out at site.

Factory Test Each coil is factory tested and checked for leaks at 325 Psig (pneumatic) under water. Performance Standards are: In accordance to • Fans

- AMCA 210

• Coils

- ARI 410

• Motors - IS-325 • Filter

- BS-6540 / ASHRAE 52 - 76

Note: E-Family AHU details can be obtained through E-Family AHU Selection Software.

22

USER'S MANUAL

½” YDW / YDX Coils: Nomenclature 1. YDW Water Cooling Coils: YDW

12

A

4

H

C

24

R

94

L

½” Water Cooling Coil Fins per Inch, 12 FPI Fin Material A: Aluminium Rows Deep (RD), 2, 4, 6, 8 Air Flow, H: Horizontal Circuiting (Tubes per Circuit), B=4, C=6, D=8 Tubes High (TH), 12 to 48 Hand, R: Right, L: Left Finned Length (FL), 26” to 114” L: Loose Note: Field to specify (a) Circuits1/2" Copper) C. D; (b) Hand-off connection: LHS, RHS (viewing from air entering side) Coil Specifications : ½” OD Copper tube of thickness 0.41 mm with 0.14mm Aluminium fins. Coils are ½” OD Copper tube of thickness 0.5 mm with 0.15mm Aluminium fins are available as an option.

23

DOUBLE SKIN AHUs SCREWLESS

2. YDX Direct Cooling Coils: YDX

12

A

4

H

C

24

R

94

L

0156

40

½” Direct Exp. Fins per Inch, 12 FPI Fin Material, A: Aluminium Rows Deep (RD), 2, 4, 6, 8 Air Flow, H : Horizontal Circuiting (Tubes per Circuit), B=4, C=6, D=8 Tubes High (TH), 12 to 48 Hand, R: Right, L: Left Finned Length (FL), 26” to 114” L: Loose Total Coil Load in MBH, 1 MBH = 1000 BTU/HR Suction Temp., Deg. F Tubes per Circuit, B=4, C=6, D=8 No. of Circuits Note: Field to specify (a) Tube per circuit; (b) Hand-off connection: LHS, RHS. Coil Specifications: ½” OD Copper Tube of thickness 0.41mm with 0.14mm Aluminium fins. Coils of ½” OD Copper Tube of thickness 0.5mm with 0.15mm Aluminium fins are available as an option.

24

8

12

USER'S MANUAL

Transportation Storage General This manual is a complete guide for the Installation, Operation and Maintenance of Blue Star's Double Skin Air Handling Units. Proper installation, operation and maintenance are essential to optimise use of the AHU. The services of a qualified technician from a reputed service company must therefore be employed through a suitable contract to install the AHU.

Transportation & Handling The Air Handling Units are inspected prior to despatch to ensure that the coil fins, casing panels, exteriors, fan scroll and impeller are in good condition, cross-checked against items ordered, then packed and carefully loaded.

Material Receipt Carefully inspect all material immediately upon delivery. If any damage is noticed, note the same and inform Factory by telephone, fax or email within one week of receiving the material. Also fill up the Field Feedback Card which accompanies the despatch documents and forward to Factory.

Storage 1. Protect the units from dust and dirt. 2. Do not store internal parts such as fans, motors, cooling coils, etc., in the open. If external parts are stored in the open, ensure that they are well protected against the weather. 3. Do not place sections on top of each another. 4. Do not walk or place weight on top of the units. 5. Do not lean any materials on the units that can damage them, such as panels, aluminum profiles or other external components. 6. Do not store any kind of materials inside sections. 7. Keep the units away from all passageways. 8. Protect protruding parts, coil connection, damper shafts, etc. 9. Place wooden wedges between the units and the ground. 10. Motors must not be stored in damp areas. 11. Filters must be left within packing cartons until ready for installation. 12. Protect fans from debris and dust.

25

DOUBLE SKIN AHUs SCREWLESS

Rigging Instruction Proper rigging and handling of the equipment is mandatory during unloading and leading the AHU into position. Care must be taken to keep the unit upright during rigging. Avoid unnecessary jarring or rough handling. Proper hoisting straps should be used when rigging (nylon flat rope). It is also mandatory that an experienced and reliable rigger be selected to handle unloading and final placement of the equipment. The rigger must be advised that the unit contains internal components that require to be kept in an upright position. Care must be exercised to avoid twisting of the equipment.

When the equipment is installed in its position, check the following: 1. Check all choke seams and air seals (below fan, motor etc.). 2. Check all door latches and re-adjust if necessary to maintain a good tight seal. 3. Fill up the Field Commissioning Report which accompanies the despatch documents and forward to Factory upon commissioning of the AHU.

26

USER'S MANUAL

Packing List 25mm STANDARD-SKD Condition CFM : AHU Model

:

AHU Tag No.

:

Fan Model

:

Discharge Location

:

Coil Connection

:

SP : 50

630 CM

AHU Overall Dimensions (W * H * L) : ICO No.

:

Batch Quantity

:

Sr. No.

Item Description

1 U.M.

CASE No.

SIZE

Q/S

Puf Panels FAN + COIL SECTION 1 4

TOP /BOTTOM ASSEMBLY Panel TOP (CUTOUT)

No.

4 -A

Panel TOP

No.

4 -B

Panel TOP

No.

5

Panel BOT

No.

5 - A

Panel BOT

No.

6 - B

Aluminum Extrusion Screwless - Length

No.

6

Aluminum Extrusion Screwless - Width

No.

7

Aluminum Extrusion Screwless ‘B‘ Type - Width

No.

8 - A

Aluminum Wedge

No.

8 - B

Aluminum Wedge

No.

8 - C

Aluminum Wedge

No.

8 - E

Aluminum Wedge

No.

19

Blower Sssly

19 - A

Spring isolator chanel

No.

19 - B

C - Fabrication

No.

19 - C

Motor mount

No.

19 - D

M - 12 Nut plate - 1

No.

19 - E

M - 12 Nut plate - 2

No.

20

CASE - 1 (Assembled in Top / Bottom Assembly)

Base Assly

20 - A

Base length - RH

No.

20 - B

Base length - LH

No.

20 - C

Base Width

No.

27

DOUBLE SKIN AHUs SCREWLESS

Sr. No.

Item Description

U.M.

20 - D

Base Center

No.

20 - E

Base Corner

No.

25

Drain Pan

No.

22

Discharge flange Assly (Welded)

22 - A

CASE No.

Discharge flange No.

17

Antivibrant Flexible Canvas Connection

No.

21

Coil Support No.

33

Motor Base Plate (50mm S.P)

No.

34

Spring Isolators - Fan Side Mounting

No.

35

Spring Isolators - Near to Motor

Set.

36

Spring Isolators - Away From Motor

No.

Back, LH and RH panels

Case 2

1

Panel LH - DOORNo.

27

Hinges ( Assembled with Door)

No.

37

“BLUE STAR“ Logo (FIXED ON DOOR PANEL)

No.

1 - A

Panel LH

No.

1 - B

Panel LH

No.

2

Panel BACK

No.

2 - A

Panel BACK

No.

3

Panel RH

No.

3 - A

Panel RH

No.

3 - B

Panel RH

No.

6 - A

Aluminum Extrusion Screwless - Height

No.

7 - A

Aluminum Extrusion Screwless ‘B‘ Type - Height

No.

8 - A

Aluminum Wedge

No.

8 - B

Aluminum Wedge

No.

8 - C

Aluminum Wedge

No.

8 - D

Aluminum Wedge

No.

8 - F

Aluminum Wedge

No.

Loose Items 9

Blower

No.

12 - A

Blower Pulley (50mm S.P)

No.

10 - A

Coil

No.

Rubber Bush / Washer For Coil Header fixed on header.

Set.

11 - A

Motor (50mm S.P)

No.

13 - A

Motor Pulley (50mm S.P)

No.

42

28

case 3

case 4 case 4

case 5 case 5

SIZE

Q/S

USER'S MANUAL

Sr. No.

Item Description

U.M.

CASE No.

15

Damper : SA

No.

case 6

16

Pre Filter :

No.

case 7

16 - A

Pre Filter :

No.

SIZE

Q/S

Fabrication List 18

case 8

Filter frame Assly (Welded) size

23

Coil Frame Assly

23 - A

Coil frame - TOP

No.

23 - B

Coil frame - LH

No.

23 - C

Coil frame - RH

No.

23 - D

Coil frame - BOT

No.

24

case 9

Spool Assly

24 - A

A

No.

24 - B

B

No.

Hardwares 26

Plastic Corner

No.

28

Handle

No.

29

Marine Light

No.

30

Limit Switch

No.

31

Hardware Set.

Set.

38

Door Switch Bracket.

No.

39

PTTJoint (25mm Standard) (FIXED WITH EXTRUSION)

No.

Belt (50mm S.P) - in hardware box

No.

40

Stickers

Set.

41

Rubber Bush / Washer For Cable Entry

Set.

14 - A

case 10

29

DOUBLE SKIN AHUs SCREWLESS

Packing List 25mm STANDARD-CKD Condition AHU Model

:

AHU Tag No.

:

Fan Model

:

Discharge Location

:

Coil Connection

:

CFM

SP : 50

FDA

1000 CM UPBLAST

AHU Overall Dimensions (W * H * L) : ICO No.

:

Batch Quantity

:

Sr. No.

Item Description

U.M.

Puf Panels FAN + COIL SECTION 1

Panel LH

No.

Panel LH - DOOR

No.

2

Panel BACK

No.

2 - A

Panel BACK

No.

3

Panel RH

No.

4

Panel TOP

No.

4 -A

Panel TOP (CUTOUT)

No.

4 -B

Panel TOP (CUTOUT)

No.

Panel BOT

No.

1 - A

5

Aluminium Extrusions

30

6

Aluminum Extrusion Screwless - Width

No.

6 - A

Aluminum Extrusion Screwless - Height

No.

6 - B

Aluminum Extrusion Screwless - Length

No.

7

Aluminum Extrusion Screwless ‘B' Type - Width

No.

7 - A

Aluminum Extrusion Screwless ‘B' Type - Width

No.

7 - B

Aluminum Extrusion Screwless ‘B' Type - Width

No.

7 - C

Aluminum Extrusion Screwless ‘B' Type - Height

No.

8 - A

Aluminum Wedge

No.

8 - B

Aluminum Wedge

No.

8 - C

Aluminum Wedge

No.

8 - D

Aluminum Wedge

No.

8 - E

Aluminum Wedge

No.

8 - F

Aluminum Wedge

No.

8 - G

Aluminum Wedge

No.

Case No.

Size

Q/S

USER'S MANUAL

Sr. No.

Item Description

U.M.

Case No.

Size

Q/S

Loose Items 9

Blower

No.

11

Coil

No.

11 - A

Coil

No.

12- A

Motor (50mm S.P)

No.

13 - A

Blower Pulley (50mm S.P)

No.

14 - A

Motor Pulley (50mm S.P)

No.

15 - A

Belt (50mm S.P)

No.

16

Damper : SA

No.

17

Pre Filter :

No.

17 - A

Pre Filter :

No.

Antivibrant Flexible Canvas Connection .

No.

18

Fabrication List 19

Filter frame Assly (Welded)

19 - A

Filter frame top

No.

19 - B

Filter frame side

No.

19 - C

Filter center support

No.

19 - D

Spring back down

No.

19 - E

Spring back up

No.

20

Blower Sssly

20 - A

Spring isolator chanel

No.

20 - B

C - Fabrication

No.

20 - C

Motor mount

No.

20 - D

M - 12 Nut plate-1

No.

20 - E

M - 12 Nut plate-2

No.

21

Base Assly

21 - A

Base length - RH

No.

21 - B

Base length - LH

No.

21 - C

Base Width

No.

21 - D

Base center

No.

21 - E

Base center - 2

No.

21 - F

Base Corner

No.

22

Coil Support

No.

23

Discharge flange Assly (Welded)

23 - A

Discharge flange

No.

31

DOUBLE SKIN AHUs SCREWLESS

Sr. No.

Item Description

U.M.

24

Coil Frame Assly

24 - A

Coil frame - TOP

No.

24 - B

Coil frame - LH

No.

24 - C

Coil frame - RH

No.

24 - D

Coil frame - BOT

No.

25

Intermediate coil support

No.

26

Spool Assly

26 - A

A

No.

26 - B

B

No.

Drain Pan

No.

27

Hardwares 28

Plastic Corner

No.

29

Hinges (Assembled with Door)

No.

30

Handle

No.

31

Marine Light

No.

32

Limit Switch

No.

33

Hardware Set

Set.

35

Motor Base Plate (50mm S.P)

No.

36

Spring Isolators - Fan Side Mounting .

No.

37

Spring Isolators - Near to Motor

Set.

38

Spring Isolators - Away From Motor

No.

39

“BLUE STAR“ Logo (FIXED ON DOOR PANEL)

No.

40

Door Switch Bracket No.

41

PTT Joint (25mm Standard)(FIXED WITH EXTRUSION)

42

Stickers

43

Rubber Bush / Washer For Cable Entry

Set.

44

Rubber Bush / Washer For Coil Header

Set.

34

Set.

(FIXED WITH COIL HEADER)

32

No.

Case No.

Size

Q/S

USER'S MANUAL

Assembly Procedure of Double Skin Horizontal Floor Mounted AHU The Handling units models DHW - 035C to DHW - 500C are dispatched in SKD condition with Top and Bottom panels assembled. The models DHW - 520C to DHW - 600 C are dispatched in CKD Condition. A sample packing List for AHUs despatched in SKD and CKD Conditions are shown below:

Packing List 25mm STANDARD (Screwless Construction) AHU Model

:

AHU Tag No

:

DHW - 070 3750 CFM

Fan Model

:

FDA 355 CM

Air Flow

:

3750 CFM

Static Pressure

:

50 mm

RPM

:

1038

Discharge Location

:

Up blast (CCW 360)

AHU Overall Dimensions :

1370 (W) x 869 (H) x 1555 (L)

Customer Name

:

431-162-RVP-AGI-09

ICO No

:

431-162-RVP-AGI-09

Batch Quantity

:

Sr. No.

1 Item Description

U.M.

CASE No.

Size

Q / S

TOTAL QTY.

Puf Panels 1 .

Pre Flat Filter

2 .

Cooling Coil 6 Row

2 . 1

Panel : Left

460

784

1

1

2 . 2

Panel : Right

460

784

1

1

2 . 3

Panel : Top

460

1285

1

1

3 .

Fan Section

3 . 1

Panel : Top

460

1285

1

1

3 . 2

Panel : Top

460

1285

1

1

3 . 3

Panel : Bottom

460

1285

1

1

3 . 4

Panel : Bottom

460

1285

1

1

3 . 5

Panel : Back

620

784

1

1

3 . 6

Panel : Back

620

784

1

1

3 . 7

Panel : Access Door Right

460

784

1

1

3 . 8

Panel : Right

460

784

1

1

3 . 9

Panel : Left

460

784

1

1

3 . 10

Panel : Left

460

784

1

1

13

13

Total No. of Panels:

Aluminium Extrusions Aluminium Extrusion ‘A’ Type - Height

756

4

4

Aluminium Extrusion ‘A’ Type - Width

1257

4

4

Aluminium Extrusion ‘A’ Type - Length

1442

4

4

Aluminium Extrusion ‘B’ Type

756.4

5

5

Aluminium Extrusion ‘B’ Type

1257.4

3

3

Aluminium Extrusion ‘B’ Type

624.4

1

1

Aluminium Extrusion ‘B’ Type

181.4

1

1

Aluminium Wedges - TOP

463

6

6

Aluminium Wedges - TOP

1268

4

4

Aluminium Wedges - TOP

628.5

2

2

Aluminium Wedges - TOP

185.5

2

2

Aluminium Wedges - LEFT

463

6

6

Aluminium Wedges - LEFT

767

6

6

33

DOUBLE SKIN AHUs SCREWLESS

Aluminium Wedges - RIGHT

463

4

4

Aluminium Wedges - RIGHT

767

4

4

Aluminium Wedges - BOTTOM

463

4

4

Aluminium Wedges - BOTTOM

1268

4

4

Aluminium Wedges - BACK

623

4

4

Aluminium Wedges - BACK

767

4

4

Aluminium Wedges - For Frontal Flat Filter Frame(Height)

767

2

2

Aluminium Wedges - For Frontal Flat Filter Frame(Width)

1288

2

2

Aluminum Extrusion BAS-40C-Type ‘Fan side’

820

2

2

Aluminum Extrusion BAS-40C-Type ‘Motor side’

635

2

2

Sections 1

2

3

Pre Flat Filter Prefilter: Box Type 48mm, Al Frame EU-3 (90% down to 10 micron)

Nos

610 (W) X 610 (H)

2

2

Frontal Flat Filter Frame

Set

1285(W) x 784(H)

1

1

Cooling Coil

Nos

YDW-12-A-6-H-C-22-L-40-L

1

1

Cooling Coil Frame

Nos

1299(W) x 798(H)

1

1

1240(W) x 415(L)

1

1

Cooling Coil 6 Row Section

Insulated Bottom Drain Pan (0.8 mm S.S-304) New Design

Nos

Drain Pan Deflector Plate

Nos

1235

1

1

Coil Support for Drain pan

Nos

1302

2

2

Rubber Bush / Washer For Coil Header

Nos

2

2

Fan Section Fan

Nos

FDA 355CM

1

1

Motor

Nos

3HP, 4Pole

1

1

S.A. DAMPER ,GI(Standard)

Nos

452(W) x 452(H)

1

1

Blower Pulley

Nos

140mm PCD 30mm ID

1

1

Motor Pulley

Nos

100mm PCD 28mm ID

1

1

Belt (PACKED IN HARDWARE BOX)

Nos

1060 SPA (1)

1

1

Antivibrant flexible canvass connection

Nos

452(W)X452(L)

1

1

Motor Base Plate

Nos

3HP

1

1

T-Bolt

Nos

M10 X 20

12

12

Anti Vibration Isolater - As Shown in Fig. Point 1

Nos

RM 19. 100. B

1

1

Anti Vibration Isolater - As Shown in Fig. Point 2

Nos

RM 19. 100. R

1

1

Anti Vibration Isolater - As Shown in Fig. Point 3

Nos

RM 19. 100. R

1

1

Anti Vibration Isolater - As Shown in Fig. Point 4

Nos

RM 19. 100. B

1

1

Marine Light

Nos

1

1

Limit Switch

Nos

1

1

Polycarbonated Window

Nos

1

1

Spool for Vertical Discharge

Nos

1

1

Door Switch Bracket

Nos

1

1

Rubber Bush / Washer For Cable Entry

Nos

1

1

Handle For Access Door

Nos

2

2

Hinges

Nos

2

2

BLUE STAR Logo .(FIXED ON DOOR PANEL)

Sets

1

1

452(W) x 452(L) x 29(H)

Spring Isolater Channel

Set

1301 (L) x 85 (W)

2

2

S.A. Flange

Nos

452 (W) x 452 (H) x 75

1

1

Channels Channel, Base. (Width)

Nos

1244

2

2

Channel, Base. (Length)

Nos

1429

2

2

Channel, Base. (Centre)

Nos

1344

1

1 8

Hardwares

34

Plastic Corner (for 25mm)

Nos

8

GI Base (25mm)

Nos

4

4

Gasket : PTT Joint (25mm Standard )(FIXED WITH EXTRUSION)

Roll Nos

4 18

4 18

Hardware Set

Set

1

1

Stickers

Set

1

1

20 * 3 mm

USER'S MANUAL

Assembly the AHU Base Channel Assembly 1. Assemble GI base channel and corner piece with M6x25 mm long bolt and nut with one plain and one spring washer on each side. 2. Overall dimensions of the base channel frame should be 30 mm less in length and width than the length and width of the AHU / AHU Module.

• Diagonally, the base frame should not be out by more than 1 mm. • All the base corners must be fitted from the inside.

35

DOUBLE SKIN AHUs SCREWLESS

Top Panel Assembly 1. Refer panel arrangement drawing. Assemble ‘A’ type extrusion with glass filled nylon corners to form a top frame required for fixing top panel - Drill the hole of Ø4.2mm & Rivet it with 7/16"x1/2" long rivet. 2. Place the ‘B’ type extrusion on the specified distance mentioned in the panel arrangement Drawing. 3. Place the panel as shown in the drawing and maintain equal gap of 2 – 3mm between frame and panel all around. 4. Insert the taper lock wedge in to the groove of ‘A’ type and ‘B’ type extrusion to lock the panel with extrusion. 5. Rivet the ‘B’ type extrusion on ‘A’ type extrusion by using 3/16" Ø x 1/2" long rivet from inside. 6. If the fan orientation in the AHU is upblast, then fix the canvas connection flange on the cut out of the panel. Reverse the top panel and fix the canvas connection from inside on connection flange.

• Taper lock wedge should be inserted inside the groove of the extrusion until it’s step touches to extrusion.

36

USER'S MANUAL

Bottom Panels Assembly 1. Refer panel arrangement drawing .Assemble ‘A’ type extrusion with glass filled nylon corners to form a bottom frame required for fixing bottom panel . 2. Place the ‘B’ type extrusion on the specified distance mentioned in the panel arrangement Drawing. 3. Place the panel as shown in the drawing and maintain equal gap of 2 – 3 mm between frame and panel all around. 4. Insert the taper lock wedge in to the groove of ‘A’ type and ‘B’ type extrusion to lock the panel with extrusion. Empty space left is for drain pan. 5. Rivet ‘B’ type extrusion on ‘A’ type extrusion by using 3/16"Ø x 1/2" long rivets.

• Taper lock wedge should be inserted inside the groove of the extrusion until it’s step touches to extrusion.

37

DOUBLE SKIN AHUs SCREWLESS

Base Channel & Bottom Frame Assembly 1. Position the base channel frame on the bottom frame. Maintain equal distance from all sides. 2. After positioning the frame, fix it with self drilling and tapping screws of size 4.2 mm Ø x 25 mm long. 3. Use battery operated screw driver / power screw driver with Philips head for fixing self drilling and tapping screws. 4. Turn the assembly upside down.

• Normally bottom panel frame is 25mm more in size from all the side than GI base channel assembly.

38

USER'S MANUAL

Drain Pan Assembly 1. Position the drain pan in the space left by panels in the bottom frame. Drain nipple should be on the header side. 2. Place the drain pan in position and rivet it to the main frame with rivets of size 3/16" Ø x 1/2" long. 3. Place the coil channel on the top of the drain pan and fix it on ‘A’ type extrusion with the help self drilling / tapping screws. 4. Apply some silicon gel at the periphery / edges of drain pan to avoid leakage. • Ensure that the drain nipple side of the drain pan should be on the side of header of the coil.

39

DOUBLE SKIN AHUs SCREWLESS

Rubber Mount /Spring Isolator Assembly 1. Refer packing list for the type of rubber mount / spring isolator to be used and position it accordingly. Each type of rubber mount or spring isolator is having different load carrying capacity. 2. Fix the rubber mount / spring isolator on the isolator channel .Place ‘C’ type channel used for blower and motor mounting on the top of spring Isolator as shown in the figure. 3. Level the spring Isolator height and tighten the nuts and bolts properly after providing spring and plain washer. Fix the whole assembly to the bottom frame in the fan section. Note: Rubber mounts are used for smaller model up to CDHW -120.

• Positioning and fixing of rubber mount / spring isolator at the specified location is very important since the load carrying capacity of the springs are different.

40

USER'S MANUAL

Vertical Extrusions Assembly 1. Refer the packing list .Pick up vertical ‘A’ type extrusion and confirm the dimension of the extrusion. 2. Insert it in the glass filled nylon corner of the bottom frame assembly.You may hammer the extrusion by plastic or rubber hammer / mallet for the proper fitment. 3. Rivet the extrusion with corner from out side. Rivet size is 3/16" Ø x 1/2" long. Ensure the length of ‘A’ type extrusion before fixing it, otherwise it may create the problem for vertical panel fitment.

41

DOUBLE SKIN AHUs SCREWLESS

Top Frame Assembly 1. Place the top frame on top of the vertical extrusion. Confirm proper support to the top frame to avoid the breakage of corner. 2. Rivet them together as explained earlier. Diagonally, the frame dimensions should not be out by more than 1 - 2 mm. 3. Overall dimension of the frame should be equal to the length, width and height of the AHU.

• Verify the diagonal distance after placing the top panel assembly and then only rivet the frame with corners.

42

USER'S MANUAL

Blower and Motor Assembly 1. Put the self adhesive gasket on the flange of canvas connector and fix it on the cut out panel with the help of aluminium rivet of dia 3/16" * 25 mm long . 2. Place the blower on the mounting channel such that the fan opening matches with the cut out of the panel. Put the self adhesive gasket on the periphery of the fan opening .Fix the other end of canvas connector on the fan opening with the help of rivet of size 3/16" * 25 mm .In case of up blast orientation of fan, spool is to be provided in between fan opening and canvas connector. 3. Mount the motor on the motor mounting base plate and fit it with the help of M8 /M10/M12 Bolt with bigger dia of plain washer and spring washer as per the rating of the motor 4. Refer the packing list and mount pulley on fan and motor shaft Align both the pulleys with the help of straight edge .Mount the v-belt , give the proper tension to v-belt with the help of tension gauge .Tight the motor mounting base plate on channel. 5. Fix both the end of spring isolator channel on ‘A’ type extrusion by using rivets of size 3/16" * 25 mm . 6. Level the height of all the springs by using spirit level and tight the lock nut of the spring Isolator.

• Ensure proper tension of V belt by using belt tension gauge. • Ensure the leveling of spring isolator height.

43

DOUBLE SKIN AHUs SCREWLESS

Coil Frame Assembly 1. Paste self adhesive foam gasket of size 20 x 3 mm on the end flanges of all four blank off of coil frame. 2. Paste self adhesive foam tape on top, bottom, and side plate of coil. Place the coil frame inside the unit and position along the ‘A’ or ‘B’ type extrusion. 3. If the coil frame is placed on ‘A’ type, then fix one side of coil frame on ‘A’ type and other side on the sides of coil with the help of self drill and tapping screw. 4. Screws for fixing top and bottom blank off should be fixed from air entry side. Ensure that the 175 mm side coil frame blank off is fixed on the header side of the coil. 5. Once the coil is positioned properly, fixed the coil support on the ‘A’ type with the help of self drill& tapping screws of size 4.2 mm Ø x 25 mm long.

• Ensure the 175 mm width coil blank off is fixed on the header side of the coil.

44

USER'S MANUAL

Coil Assembly 1. Put the self adhesive foam gasket on the periphery of the coil flanges. 2. Position the coil on top of coil support channel which is fixed on the drain pan. 3. Header should be on 175 mm side of the coil frame. Coil inlet should be towards the blower side in the draw through AHUs. 4. After positioning the coil, fix it with coil frame with the help of 4.2 Ø x 25mm long self drilling and tapping screws.

• Coil inlet should be towards the blower side.

45

DOUBLE SKIN AHUs SCREWLESS

Side panel assembly 1. Refer the panel arrangement drawing and place the ‘B’ type extrusion at specified distance and fix it with rivet of size 3/16" * 12 mm long from inside of AHU. 2. Place the panel as per drawing and maintain equal gap of 2 – 3mm between extrusion and panel all around. Insert the taper lock wedge inside the groove of ‘A’ and ‘B’ type of extrusion. 3. Mark the position of the coil header on the panel and make the hole on the header panel. Roll on the rubber collar on the coil header on the either side of the panel.

• Do not forget to put the sleeve and rubber collar on the header. • Taper lock wedge should be inserted in side the groove of the extrusion until it’s step touches to extrusion

46

USER'S MANUAL

Door assembly 1. Keep 4 -5 mm distance from ‘B’ type extrusion or ‘A’ type extrusion depend on which the hinge is going to be fixed to the edge of access door for the smooth movement of the door. 2. One end of the hinge is fixed on ‘B’type or ‘A’ type extrusion and other end is fixed on the door. 3. Fix the handle in the hole provided on the door.Also fix the view port with gasket. • Holes to be drilled on ‘A’ type and ‘B’ type extrusion and fit the nut sert in it for fixing auxiliary and access door. Ensure the Nut sert machine is available at site.

47

DOUBLE SKIN AHUs SCREWLESS

Filter frame 1. Put the self adhesive foam gasket on the periphery of filter frame. Mount the filter frame on A/B’ type extrusion and fix it by self drilling and tapping screw.. 2. Mount the filters in the filter grid. Filters will get automatically locked because of the spring action of the supports provided in the filter frame.

48

USER'S MANUAL

Sticker Position

49

DOUBLE SKIN AHUs SCREWLESS

Recommended Tools Tools required in the Assembly of Screwless AHU

50



Hand Drill Machine – (Reverse/Forward) 1 No.



Rivet Machine with Jig – (Manual) 1 No.



Nut Sert Machine – (Manual)



Spanner 10mm – One side Fix & One Side ring. 2 Nos.



Spanner 13mm – One side Fix & One Side ring. 2 Nos.



Spanner 16/17mm Fix 2 Nos.



Spanner 19mm – One side Fix & One Side ring. 2 Nos.



Spanner 24/25 mm Fix 2 Nos.



Adjustable Spanner – 1 No. (Maximum Opening 40mm)



Ratchet Spanner set with socket – 10mm, 13mm, 15mm, 17mm, 19mm, and 24mm.



Allen key set – 1 No. of Inch and 1 No. of mm.



Screwdriver – (Flat type – 4 Inch and 8 Inch. Length)



Screwdriver – (Star type – 6 Inch. Length)



Tester – 1 No.



Knife – 1 No. (Small)



Pliers – 1 No.



Hacksaw (frame with Blade)



Measuring tape – 5m



Silicon RTV Sealant – 1 No.



Plastic Hammer – 1.5 Inch. - 1 No.



Rubber Mallet – 4 Inch – 1No.



Metal Hammer – 250 g – 1 No.



Spirit level – 1 No.



Chisel – 3 Nos.



Screw Bit for 4.2mm Dia, 25mm length Screw – 5 No.



Screw bit Holder – 150mm, 75 mm For 4.2mm Dia, 25mm length Screw



M6 Bolt Socket of Drill Machine – 1No.



Hole Saw cutter and Arbor – 25mm, 40mm, 60mm, 75mm, 100mm – 1No Each.



Drill bit – 5mm – 10 Nos.



Drill Bit – 6 mm – 2 Nos.



Drill Bit – 10 mm – 2 Nos.



Drill bit – 12 mm – 2 Nos.



C Clamp – 6" – 4 Nos.



Carpenter’s Vice – 12 Feet long – 1Nos.



Try Square – 1 No. – 6 Inch long.



Belt Tension Gauge



Vacuum Cleaner – 1 No.

USER'S MANUAL

Electrical Information •

Connect the power supply in accordance with local regulations. Earth all equipment at each section.



All wiring must confirm to IS and IE rules and possible local codes.



The power characteristics, voltage, phase and frequency are stamped on the name plate of the motor.



Whenever possible, electrical conduit/cable should be run to the unit from the bottom of the side panel/skid.



If junction box is provided, electrical cable connection made to the junction boxes on units must be made on the bottom of the box. Installation must comply with code requirements. The installation should be made watertight. All exposed electricals MUST be checked for tight fastening prior to actual startup. A poor connection can cause overheating and component failure through inadequate current handling capacity.



A motor connection diagram is affixed on the inside of the motor terminal box cover. Be sure that extra cable length is made available at the motor to permit fan belt adjustment.



All fan motors are three phase; totally enclosed fan cooled (TEFC) types with squirrel cage rotors.



The fan motors for Ceiling Suspended direct driven types are with single phase.



Standard motors have radial flow fan allowing fully reversible rotation. The motors are dynamically balanced. Bearings are greased for life with considerable grease reserve.



Terminate the cable for DOL or Star/Delta as the case may be.



Check the cable size with respect to motor rating from the approved electrical single line drawing.



Complete both the cable termination and required earthing.



The AHU starter panel should be close to the AHU. Otherwise provide an isolator switch (disconnect) or on/ off push button station near the AHU.



The marine light inside will need a single phase 230V, 50 Hz AC supply. Provide an MCB in the AHU panel.



The limit switch (for fan access door) should be wired in the control panel of the AHU starter.

51

DOUBLE SKIN AHUs SCREWLESS

Cooling Coil Installation Coil Hand Selection Coil hand connections (LHS or RHS) should depend on space availability for maintanance. Check the exact inlet and outlet connection of the pipes to the coils. Water enters from the inlet nozzle at the bottom and exits at the top. The water inlet should be at the air-leaving side.

General •

Consult the job specifications and approved drawings for specific piping requirements, coil connection sizes and location. The unit must be levelled to ensure proper venting and draining of coils. The piping arrangement must be for a balanced flow in multiple coil installations.



The coil will meet performance ratings only if the air velocity is uniform over the face of the coil. High air velocity spots on the coil may cause the carry-over of moisture from the coil. Low air velocity areas of the coil will not deliver published rating. The duct connection must be designed to provide for uniform flow of air across the face of the coil. In case of ducted return air, the entering duct must have a smooth transition from any high velocity effects.



The heating coil will normally be for reheating. It must be located after the cooling coil in the direction of the air flow.



Support all connecting piping independent of the coils. Provide swing joints or, preferably flexible fittings in all piping connections, particularly adjacent to heating coils, to absorb expansion and contraction strains. Rigid piping connection can cause coil damage.



The coils supply and return pipe connections are labelled. When connecting the piping to coil header; make the connection only tight enough to prevent leaks. Excessive tightening may cause damage to the header.

52

USER'S MANUAL

Water Coils – Drainable Water





Connect the water inlet to the bottom of the cooling coil header on the air-leaving side of the coil and the water outlet to the top of the header at the airentering side of the coil to achieve counter flow of water and air. Positive coil freeze protection must be used in installations where any part of the coil is subjected to temperature of 0 o C or lower. This may be accomplished by using a suitable antifreeze solution. If the coil is not in use, it is recommended that the coil be completely drained and the inside of the tubes blown dry with compressed air. Other means of protection such as the full constant flow of water can be used.

Direct Expansion (DX) Coils Each coil must be installed with suction header towards the air-entering face of the coil and with the suction connection at the lower end. The orientation of the refrigerant distributor is not critical but the distributor tubes should not be pinched or bent in a non-uniform configuration. These coils are despatched from the factory with Dry Air Pressure of 7-15 psig. An individual expansion device must be provided for each coil at the field. Thermostatic expansion valves are to be equipped with external equaliser connection that are field connected to the suction lines. The valve should be sized in accordance with manufacturer's recommendations, allowing approximately 35 psig pressure drop through the coil and distributor at full load. Do not oversize the valve. Follow the manufacturer's instruction on the location of the thermostatic bulb. Proper expansion valve operation is necessary in order to realise the rated coil capacity. When a DX coil is operated with suction temperature below 00C, a build up of frost will occur on the finned surface. It is, therefore, not recommended to use DX coils for airconditioning below freezing temperature. If the full load operating point for the coil is selected at a safe temperature, a system analysis is required to check for the lowest probable suction temperature at light load conditions. Suction pressure controlled hot gas by-pass valves are available from various control manufacturers to maintain an adequate minimum suction temperature.

Air Velocity through Coils The air velocity across the chilled water coil and direct expansion coils should be generally 2.54 m/sec. However it must not exceed 2.8 m/s to prevent water carry-over. Air velocity, which is too low, will result in a low load situation on the cooling coil, which will effect compressor operation. Air flow (m3/s) and air velocity (m/s) can be adjusted by changing the fan/motor pulley sizes or by adjusting the fan outlet damper.

53

DOUBLE SKIN AHUs SCREWLESS

Condensate Drain Piping The majority of cooling coils are located in the units so that the supply air is drawn through them. This results in condensate being subjected to negative pressure. Unless some means of pressure equalisation is provided in the condensate drain, the air rushing back through the drain pipe will cause the condensate to build up in the drain pan. As the unit continues operation, the accumulated water will be carried with the air stream. A trap should be installed to prevent this condensate water build up. On initial startup, it may be necessary to fill the trap manually or, after the unit has operated for some time, to allow for a small unit to fill the trap automatically.

Drain Pan Drain pan

G.I. Elbow

IN NO RUN CONDITION

NORMAL RUNNING CONDITION TRAP

G.I. Elbow DIFFERENTIAL

Drain Pan

G.I. Elbow

CONDITION WHEN AN START

TOTAL HEAD

Condensate Drain Trap and Line Installation Install a trapped condensate drain line at unit drain connection. For Draw Through applications, the trap dimension must be at least 1/2 inch greater than negative static pressure in the unit drain pan area. To determine trap dimension, first determine the negative static pressure in the unit. Always assume the worst condition, such as dirty filter in the return air circuit to the fan. Example: Negative Static Pressure

:

- 0.5" - 0.5"

Minimum of 1/2"

:

- 0.5" - 0.5"

Drain pipe size

:

- 1.25" - 1.0"

Trap

:

- 2.25" - 2.0"

For Blow Through units, the same practice is followed, but the drain leaving the drain pipe should not be above the bottom of the drain nipple. Provide adequate foundation height to accommodate trap. Do not connect the AHU drain trap directly to any plumbing line. Contamination of air may take place. Condensate drain pipe should be insulated to avoid sweating.

54

USER'S MANUAL

Air System

Duct Connection Guidelines All discharge air duct connections to the unit may be directly connected only for Horizontal AHUs, Vertical AHUs with multiple blower. All other AHUs, terminate the ducting through canvas connections. Duct turn and transition must be made carefully to hold frictional losses to a minimum. Avoid short turns. Duct elbows should contain splitters or turning vanes. Duct work connected to the fan discharge must run in a straight length for at least two equivalent outlet diameters and should not be reduced in cross sectional area. A duct turn should be in the same direction as the fan rotation. Installations of the elbow and other abrupt flow area changes directly at the fan outlet will cause system losses. These losses must be taken into account during the design phase and must be added to any field measurements.

Sound and Vibration Transmission All Air Handling Units generate some sound and vibration that may or may not require special treatment of the air handling duct/rooms. The noise generated by the air handling unit is dependent on the speed of the fan, the amount of air, the type of fan and the static efficiency of the fan. In applications where sound and vibration transmission may be objectionable, good acoustical engineering practices must be incorporated in the system design. It is better to locate the AHU away from noise sensitive areas. The supply ducts should be internally lined. Silencers may also be installed. On units with return fans, it is especially important to consider the effects of sound transmission into the conditioned space.

55

DOUBLE SKIN AHUs SCREWLESS

Pre-Start Up Adjustment and Checks Belt and Sheaves Improper sheave alignment and belt tension are frequent causes of excessive vibration as well as shortened belt and bearing life. The Vee Belts used are SPA, SPB , SPZ, SPC as required. Please check the above provided.

Air Filters All filters are shipped loose. It is mandatory that filters be in place in the filter frames of each unit before putting the unit into operation to protect the coil and keep them clean. When the unit is first started, dirt and debris from the building/duct is likely to be sucked in. Hence, place a muslin cloth in front of the filters to prevent them from getting choked.

Air Flow Control Dampers Dampers are intended for use with individual controllers, actuators or manually.

Start-up checks •

Have transportation restraints been removed?



Check supply voltage, in all three phases and voltage unbalance



Check fan's wheel and drive sheaves



Set screw tight and check drive alignment



Check bearing for alignment and locking collars for tightness



Rotate wheels and motors to ensure freedom of movement



Are drain traps of correct shape and size?



Check to see that proper air filters are installed



Check the AHU is connected to the duct



Check the fan outlet damper is operational

Operational Checks •

Momentarily start the fan motor and ensure correct rotation



Check belt tightness



Check RPM of, and amperes drawn by, supply fan motor



Check cabinet for air leakage



Check cabinet for possible water leaks



Latch/Tighten all panels

56

USER'S MANUAL

Safety Checks Be sure all door latches (locks) are secured before starting unit. Fans are dynamically balanced at fan manufacturer's works. However, there are certain operating speeds at which the natural frequency of the rotating member is attuned to the natural frequency of certain panels which are the part of the enclosure. These vibrations can tend to reinforce each other in such a way that excessive vibration can be encountered under certain conditions. It is difficult to predetermine such condition, as it is affected by mounting arrangement, the various modules used in the make up of assembly and the duct connections and operating condition. Under no condition should the unit be allowed to operate when excessive unit vibration is apparent. Permanent damage may result due to this. After 24 hours of satisfactory operation, shut down the equipment and check all foundation bolts, shaft bearing and drive set screws and tighten wherever required. If the above check reveals no apparent discrepancies and vibrations still persist, the speed of the unit should be lowered by approximately 10% to determine if a natural frequency is causing the vibration. If the unit contains water coils, they must be filled when this check is made. Trained personnel should be available at the time of start up of the Air Handling Units.

Motor Do not operate fan motors in overload amperage condition. Do not energise the motor if earthing is not completed.

Before mounting the V belts, it is preferable to run the motor at no load condition and check the no load current and verify the direction of rotation. It is not desirable to run the AHU for long periods without providing filters and connecting to duct work since the fan will draw more current and the coil will also choke with dust. Motor amperage should be checked again after the connecting duct is installed and an air flow check made on the air distribution system. Only in those cases where the airflow at the outlet is insufficient to meet specification should the blower speed be changed. However, when the speed is changed, check the adequacy of fan motor as BHP increases by an order of the cube of the ratio of increase in RPM. Also check the adequacy of switch gear.

Belt Belt should be checked for correct tension at start up and should be checked again after 24 hours of operation. On multiple belt adjustable pulleys, the pitch depth should be checked to ensure identical belt travel, power transfer and wear. An adjustable motor base is provided for belt adjustment. Figure on page 43 illustrates the belt tension guage. Do not operate fan motor until lubrication has been checked and drive adjusted. If the motor operates at incorrect voltage or on 2 phases, the motor may draw full load current at no load condition.

57

DOUBLE SKIN AHUs SCREWLESS

Operation Pre-Operation Check •

Lock out electrical power to prevent accidental fan operation. Check the inside of the unit and duct work to make sure that no loose nuts, bolts, trash, sheet metal parts etc. have been left behind, which may be sucked into fan and result in permanent damage. At the same time, check to make certain that air filters have been placed in the filter section, with fill pieces in place.



Recheck the tightness of the mounting hardware, set screws and locking collars on the bearing, and motor mount adjustment nuts.



Rotate the fan shaft by hand to make sure that it is free and no obstruction has been caused during transportation.



Check the bearing for proper lubrication by referring to the bearing lubrication instructions. At the same time if the bearing contains locking collars, make sure that the locking collars have been locked in the direction of the fan rotation. All transportation hold nuts must be removed completely to permit fan to ride freely on the isolators.



Recheck the fan and motor sheave alighment with a straight edge and belt tension for proper values.



Refer to the fan motor manufacturer’s instructions attached to the fan motor and check each item for compliance prior to start-up.

Operational Check •

After the pre-operational check, apply power to the motor for a short interval to observe that the fan is rotating in right direction as indicated by arrow on the side of the blower scroll. Check the fan speed with tachometer.



Check the current drawn by motor with an ammeter. Correct rotation and speed if required. Do not exceed maximum speed or amperage.

Stop the machine immediately if any unusual sound or vibration occurs and recheck all items.

If the vibration continues, the belt should be removed from the drive and motor allowed to run unloaded to determine if the motor shaft is possibly bent, if there are defective motor bearing or if the motor is unbalanced or the pulley is out.

58

USER'S MANUAL

Maintenance General A programmed regular maintenance will avert possible costly and unexpected downtime. It is the responsibility of the owner to provide the necessary maintenance for the Air Handling Units and coils. If a system failure occurs due to improper maintenance during warranty period, BSL will not be liable for the cost incurred to bring the unit back to satisfactory operation. Removable access door fitted with viewport has been provided on all units for necessary maintenance and to provide access to various components which in time may require replacement.

Note:

Filter used during building construction must be replaced with clean filter prior to the occupancy

of the building.

Periodic Maintenance Every Month Check the cleanliness of the filters and clean as required. Examine the damper and operating linkages to ensure that each is free and operating smoothly.

Every Three to Six Months •

Add grease (Servogem 3) to the fan shaft bearing as indicated by the schedule from the bearing manufacturer which has been attached to the unit. The exact period between lubrication is related to the rotational speed and the atmosphere surrounding the bearing.



For normal operating conditions, the grease should confirm to NL GL. Grade 2 consistency. It is important that the grease be free of chemical impurities, moisture, and dust, metal particles or abrasives. The bearing should be lubricated while the shaft is turning. The grease should be pumped in slowly until a slight bead forms around the outside of the seals. This bead, in addition to an indication of the adequate lubrication, provides protection against the entry of the foreign matter. Excessive grease should be removed from the internal bearing to prevent it from being picked up by the fan. Dirt will collect on the fan and eventually cause imbalance, resulting in vibration and component failure.



If the grease fitting must be changed, it is important to see that the locking pin is in place when the fitting is replaced. If an adapter or grease fitting of improper size and length is used, the locking pin may be either too tight or loose and can affect the alignment and re lubrication of the bearing.



Adjust the belt tension if necessary. Never use a belt dressing on the belt. If belt slips in spite of proper tension, use a good grade of belt cleaner to clean the belt. Use the motor base plate for adjusting the belt tension. Never use excessive tension as this could result in damaging the bearing.

59

DOUBLE SKIN AHUs SCREWLESS



When it is necessary to replace one belt in a given set, the entire set of belts must be replaced by a matched set. Check the lubrication instruction for the installed motor and lubricate the motor as indicated.



Inspect the condensate drain trap and ensure that it is clear and free.



Check the bearing locking collars or set screw for tightness. Inspect the coils for cleanliness. If necessary, hose the coils down with a low pressure water hose or low pressure air. Never use hot water or steam on refrigerant coils as dangerous pressure can build up within the coil.

Every Year •

Clean the fan and inspect the drain pan for sludge and foreign material. Clean if required.



Observe the operation of all dampers and make any necessary adjustment in linkages and blade orientation for proper operation.



Inspect the coil for cleanliness. if necessary, hose the coil down with low-pressure water hose or low-pressure air.

60

USER'S MANUAL

Winterising System Components Freeze Protection All Chilled Water coils can be damaged during freezing weather. Precautionary measures must be taken to prevent freezing such as: •

For all year operation and shut-down such as power failure, night shut-down and weekend shut-down, the controls must be installed so that the valves will go to the full heat position, and all fresh air dampers go to the full closed position. The water circulation pump must be kept circulating water through the coil and/or auxiliary heat must be maintained inside the cabinet.



Drain each coil and related piping such as traps and make sure that all the areas are drained.



After draining, flush coils with antifreeze solution such as ethylene glycol. A solution of 50% ethylene glycol and 50% water will protect freezing below zero at sea level.

Winterising Drain Traps During the winter months when the cooling system is turned off and the unit is exposed to freezing condition, an antifreeze solution should be poured in the condensate drain trap to prevent freezing and possible damage. The condense drain trap may also be drained.

Dampers Dampers, operators, control and linkages must be checked prior to applying power to the operators, making sure nothing will obstruct the operation of the damper. Do not overdrive damper operator as this may cause damage to the damper.

61

DOUBLE SKIN AHUs SCREWLESS

Removal or Reinstallation of Components Blower Follow these steps to remove the blower from casing: •

Remove the belts from the drive



Loosen the retaining bolts of the blower



Fix the clamp below the blower base as shown in figure below



Remove the blower retaining bolt completely



Remove blower

If a new blower is installed, make sure that the spring selection matches the blower and motor. The blower should also be properly balanced.

Coil Replacement Access to the coil is obtained by removing the connecting piping from the coil and the panels at each end of the coil. For direct expansion coils, it is necessary that the refrigerant be pumped down into the condenser and contained. Under no circumstances should the piping joints in DX coils be heated for unseating while refrigerant is within the coil. Dangerous pressure, gases and fire can result.

62

USER'S MANUAL

Belt Replacement Always replace belts as a matched set. Used belts will always be longer because of stretching and belts should never be installed singly on a multiple drive. The adjusting nuts on the fan motor should be loosened and the belt placed in the sheaves. Never place the belts on the sheaves by using a screwdriver to try each belt over the rim of the sheaves. Once the belts are in place, the sheaves on the fan shaft and motor should be checked with a straight edge for alignment. Check the middle groove of each sheave when multi groove pulleys are used. Next, adjust the belt tension using the adjusting bolts on the motor mount. Use a recognized gauge such as one shown in figure for adjusting the tension. To determine the deflection force required, use the formula: Deflection = Belt Span / 64

Do not over tighten the belt or the bearing may get damaged. The best tension for a belt drive is the lowest tension at which the belt will not slip under the highest required load.

63

DOUBLE SKIN AHUs SCREWLESS

Installation Double Skin Vertical Air Handling Units These units are fully assembled at the factory, packed properly and despatched. Upon receipt at site, these units are to be unloaded carefully as illustrated in this manual and lead carefully to the place of installation. Vertical D S Air Handling Units, with single blower arrangement are not provided with canvass connection at the factory. Canvass connections are provided within the unit at factory for units with multiple blowers. Install these units at site on 25 mm thick ribbed rubber pads of size 150 mm X 150 mm (2 layers of 12 mm thick each placed one on top of other with a GI sheet of same size in between) at four corners. Ensure that the units are leveled properly. The units with single blower outlet are to be connected through a fire retardant canvass connection to the ducting at site. It is preferable to install a Volume Control Damper of opposed blade type at the blower outlet to adjust the air quantity of the AHU. Units with multiple blower arrangement are not required to be provided with canvass connection at site, whereas one Volume Control Damper is recommended to be provided in the ducting to adjust the air quantity.

64

USER'S MANUAL

D S Ceiling-suspended Air Handling Units These units are fully assembled at the factory, packed properly and despatched. Upon receipt at site, these units are to be unloaded carefully as illustrated in this manual and lead carefully to the place of installation.

Typical Ceiling suspension by fully threaded rods

These units are ceiling suspended with the help of 4 suspension rods. The anchor fasteners used for suspending the units from the ceiling should be able to withstand the weight of the unit. The Units can be suspended from an M S structural work also.

Ensure that the corner pieces are provided at the bottom of the vertical extrusion at all four corners as shown in the following illustrations. These corner pieces are shipped alongwith the units from the factory.

Bottom corners (supplied loose)

For critical and sensitive installations, where non transmission of vibration is very important, special suspension arrangement is to be incorporated while suspending the units as shown.

Special isolator (if required)

These units are not provided with any canvass connection at the fan outlet from the factory. Hence fire retarded canvass connection is to be provided at the outlet of the unit prior to connecting to the ducting. It is preferable to install a Volume Control Damper of opposed blade type at the fan outlet to adjust the air quantity.

65

DOUBLE SKIN AHUs SCREWLESS

Troubleshooting If your Air Handling Unit is not functioning properly, do check the following before calling for service.

Trouble Air flow is less

Cause

Remedy

Filter clogged

Clean filter.

Cooling coil clogged

Clean cooling coil.

Belt loose

Tighten the V belt.

Low Voltage

Ensure that correct voltage is available.

Volume Control Damper stuck or partially closed.

Check and adjust the volume control damper.

RPM of fan less

Check the rpm with design and change pulley if required.

Static pressure high

System static pressure has increased. Check with design.

Air leaving temperature of cooling coil high

Chilled water in temperature high

Ensure that the design water temperature is available at cooling coil inlet.

Less water flow

Check any clogged water strainer and clean. Check water balancing. Check any valve stuck in partially open position.

Accumulation of water in AHU

Water carry over

66

Cooling coil clogged

Clean the cooling coil.

Quantity of air flow is more

Adjust the flow rate by volume control damper or changing the pulleys.

U trap not provided

Provide U trap in the condensate drain line of adequate depth.

Drain line clogged

Clean the drain line.

Air quantity too high

Adjust the air quantity.

Face velocity of coil high

Measure the velocity and adjust to the design value.

USER'S MANUAL

Trouble Noise and vibration

AHU motor trips

AHU not starting

Cause

Remedy

Unbalanced impeller

Check the static balancing at site. If required get the impeller balanced dynamically.

Unbalanced pulleys

Balance the pulleys.

V Belt loose

Tighten the V belt.

Air quantity too high

Change the pulleys to obtain required air quantity.

Low voltage

Ensure that correct voltage is available.

Air quantity too high

Adjust the air quantity.

Two AHUs working in parallel and one AHU stopped

Close the discharge damper of the AHU not working.

Faulty overload

Check the overload and replace.

Single phasing

Check all the phases and replace burnt out fuse.

Low voltage

Check and ensure that correct voltage is applied.

Single phasing

Check all the fuses and take corrective action.

67

DOUBLE SKIN AHUs SCREWLESS

Preventive Maintenance SOP (Standard Operating Procedure) for Pre Filter Cleaning Aim: Routine cleaning of prefilter Standard followed: As per filter manufacturer. Scope of work: To monitor and verify cleanin of prefilter Percentage of cleaning required: 100% Note: Before starting work check the house keeping in Pre filter mounting room. Every worker should be in proper clothing & should wash the hands with soap water before starting the process.

Steps to be followed for Pre Filter cleaning: Step - A a. Check the house keeping in the prefilters mounting area b. Remove the dust with proper tools c. Transfer the filters to cleaning area d. Avoid cleaning filters near to the Air Handling unit e. Take out the filters from covers individually. f. Use 1.5 to 2bar compreseed air to clean g. Clean the filters from the outlet side h. The distance from air nozzle to filters should be 6 inch. i.

Starting from one corner move the nozzle all over the area.

j.

Cleaning to be done anywhere between 2-5 minutes depending on size of filter and area of filteration.

k. After cleaning filter medium remove dust on the frame by cloth dipped in IPO. l.

Transfer the cleaned filters to clean polythene cover and shit it to safe place.

m. Shift the cleaned filters to mounting area n. Clean the mounting frames totally, any dust e.t.c. are not acceptable on finished filter o. Fix it with appropriate fastners.

Final Ovservation Tighten the fastners for no leakage of air.

68

USER'S MANUAL

Spare Parts List / CDHW AHU MODEL

V-BELT CODE

DISCRIPTION

QTY/AHU

CDHW - 035

SPZ-750

750

SPZ (1)

1

CDHW - 040

SPZ-750

750

SPZ (1)

1

CDHW - 050

SPZ-1000

1000

SPZ (1)

1

CDHW - 070

SPZ-1000

1000

SPZ (1)

1

CDHW - 080

SPZ-1000

1000

SPZ (1)

1

CDHW - 100

SPZ-1120

1120

SPA (1)

1

CDHW - 110/120

SPZ-760

760

SPZ (1)

CDHW - 135

SPZ-950

950

SPZ (2)

CDHW - 150

SPZ-950

950

SPZ (2)

CDHW - 160

SPZ-950

950

SPZ (2)

CDHW - 175

SPZ-1160

1160

SPZ (2)

CDHW - 190

SPZ-1160

1160

SPZ (2)

CDHW - 200

SPZ-1120

1120

SPZ (2)

CDHW - 220

SPA-1220

1220

SPA (2)

CDHW - 230/240

SPA-1220

1220

SPA (2)

CDHW - 255

SPA-1320

1320

SPA (2)

CDHW - 265

SPA-1320

1320

SPA (2)

CDHW - 290

SPA-1450

1450

SPA (2)

SPA-1220

1220

SPA (2)

CDHW - 325

SPA-1650

1650

SPA (2)

CDHW - 340

SPA-1650

1750

SPA (2)

CDHW - 355/370/390

SPA-1950

1950

SPA (2)

CDHW - 410

SPB-2000

2000

SPB (2)

CDHW - 430/445

SPB-2000

2000

SPB (2)

CDHW - 470/490/500

SPB-2150

2150

SPB (2)

CDHW - 520/540

SPB-2120

2120

SPB (2)

CDHW - 570

SPB-2120

2120

SPB (2)

CDHW - 600

SPB-2120

2120

SPB (2)

CDHW - 300

CDHW - 455

69

DOUBLE SKIN AHUs SCREWLESS

AHU MODEL CODE

DISCRIPTION

QTY/AHU

CDHW - 035

AHF610617

Prefilter-EU3-AL-BOX-610W610H

1

CDHW - 040

AHF610617

Prefilter-EU3-AL-BOX-610W610H

1

CDHW - 050

AHF610617

Prefilter-EU3-AL-BOX-610W610H

1

CDHW - 070

AHF610617

Prefilter-EU3-AL-BOX-610W610H

2

CDHW - 080

AHF610617

Prefilter-EU3-AL-BOX-610W610H

2

AHF610309

Prefilter-EU3-AL-BOX-610W305H

2

AHF610617

Prefilter-EU3-AL-BOX-610W610H

2

AHF610309

Prefilter-EU3-AL-BOX-610W305H

2

AHF610617

Prefilter-EU3-AL-BOX-610W610H

2

AHF610309

Prefilter-EU3-AL-BOX-610W305H

2

AHF305614

Prefilter-EU3-AL-BOX-305W610H

1

AHF305309

Prefilter-EU3-AL-BOX-305W305H

1

CDHW - 135

AHF610617

Prefilter-EU3-AL-BOX-610W610H

4

CDHW - 150

AHF610617

Prefilter-EU3-AL-BOX-610W610H

4

AHF305614

Prefilter-EU3-AL-BOX-305W610H

2

AHF610617

Prefilter-EU3-AL-BOX-610W610H

4

AHF305614

Prefilter-EU3-AL-BOX-305W610H

2

AHF610617

Prefilter-EU3-AL-BOX-610W610H

4

AHF305614

Prefilter EU3-AL-BOX-305W610H

2

CDHW - 190

AHF610617

Prefilter-EU3-AL-BOX-610W610H

6

CDHW - 200

AHF610617

Prefilter-EU3-AL-BOX-610W610H

6

CDHW - 220

AHF610617

Prefilter-EU3-AL-BOX-610W610H

6

AHF610309

Prefilter-EU3-AL-BOX-610W305H

3

AHF610617

Prefilter-EU3-AL-BOX-610W610H

6

AHF610309

Prefilter-EU3-AL-BOX-610W305H

3

AHF610617

Prefilter-EU3-AL-BOX-610W610H

6

AHF610309

Prefilter-EU3-AL-BOX-610W305H

3

AHF610617

Prefilter-EU3-AL-BOX-610W610H

6

AHF610309

Prefilter-EU3-AL-BOX-610W305H

3

AHF610617

Prefilter-EU3-AL-BOX-610W610H

6

AHF610309

Prefilter-EU3-AL-BOX-610W305H

3

CDHW - 100

CDHW - 110/120

CDHW - 160

CDHW - 175

CDHW - 230/240

CDHW - 255

CDHW - 265

CDHW - 290

70

FILTER

USER'S MANUAL

AHU MODEL

FILTER CODE

DISCRIPTION

QTY/AHU

AHF305309

Prefilter-EU3-AL-BOX-305W305H

1

AHF305614

Prefilter-EU3-AL-BOX-305W610H

2

AHF610617

Prefilter-EU3-AL-BOX-610W610H

6

AHF610309

Prefilter-EU3-AL-BOX-610W305H

3

AHF305309

Prefilter-EU3-AL-BOX-305W305H

1

AHF305614

Prefilter-EU3-AL-BOX-305W610H

2

AHF610617

Prefilter-EU3-AL-BOX-610W610H

8

AHF610309

Prefilter-EU3-AL-BOX-610W305H

4

AHF610617

Prefilter-EU3-AL-BOX-610W610H

8

AHF610309

Prefilter-EU3-AL-BOX-610W305H

4

CDHW - 355/370/390

AHF610617

Prefilter-EU3-AL-BOX-610W610H

12

CDHW - 410

AHF610617

Prefilter-EU3-AL-BOX-610W610H

12

CDHW - 430/445

AHF610617

Prefilter-EU3-AL-BOX-610W610H

12

AHF305614

Prefilter-EU3-AL-BOX-305W610H

3

AHF610617

Prefilter-EU3-AL-BOX-610W610H

12

AHF305614

Prefilter-EU3-AL-BOX-305W610H

3

CDHW - 470/490/500

AHF610617

Prefilter-EU3-AL-BOX-610W610H

15

CDHW - 520/540

AHF610617

Prefilter-EU3-AL-BOX-610W610H

12

AHF610309

Prefilter-EU3-AL-BOX-610W305H

4

AHF305309

Prefilter-EU3-AL-BOX-305W305H

3

AHF305614

Prefilter-EU3-AL-BOX-305W610H

1

AHF610617

Prefilter-EU3-AL-BOX-610W610H

15

AHF610309

Prefilter-EU3-AL-BOX-610W305H

5

AHF610617

Prefilter-EU3-AL-BOX-610W610H

15

AHF610309

Prefilter-EU3-AL-BOX-610W305H

5

CDHW - 300

CDHW - 325

CDHW - 340

CDHW - 455

CDHW -5701

CDHW - 600

71

DOUBLE SKIN AHUs SCREWLESS

AHU MODEL CODE

DISCRIPTION

QTY/AHU

AHI065000

Rubber Mount : RM.19B

3

AHI068000

Rubber Mount : RM.19Y

1

AHI065000

Rubber Mount : RM.19B

3

AHI068000

Rubber Mount : RM.19.Y

1

AHI062800

Rubber Mount : RM.19R

1

AHI065000

Rubber Mount : RM.19.B

3

AHI065000

Rubber Mount : RM.19B

2

AHI065000

Rubber Mount : RM.19B

2

AHI065000

Rubber Mount : RM.19B

2

AHI062800

Rubber Mount : RM.19R

2

CDHW - 100

AHI062800

Rubber Mount : RM.19R

4

CDHW - 110/120

AHI062800

Rubber Mount : RM.19R

4

CDHW - 135

AHI251000

Spring isolator : OS 25-100

3

HI256000

Spring Isolator : OS 25-60

1

AHI251000

Spring isolator : OS 25-100

3

AHI256000

Spring Isolator : OS 25-60

1

AHI251000

Spring isolator : OS 25-100

3

AHI256000

Spring Isolator : OS 25-60

1

AHI251000

Spring isolator : OS 25-100

3

AHI251600

Spring Isolator : OS 25-60

1

AHI251000

Spring isolator : OS 25-100

3

AHI251600

Spring Isolator : OS 25-60

1

AHI251000

Spring isolator : OS 25-100

3

AHI251600

Spring Isolator : OS 25-60

1

AHI251000

Spring isolator : OS 25-100

3

AHI251600

Spring Isolator : OS 25-60

1

AHI251000

Spring isolator : OS 25-100

3

AHI251600

Spring Isolator : OS 25-160

1

AHI251000

Spring isolator : OS 25-100

3

AHI251600

Spring Isolator : OS 25-160

1

AHI251600

Spring Isolator : OS 25-160

2

AHI252500

Spring Isolator : OS 25-250

1

AHI251000

Spring isolator : OS 25-100

1

CDHW - 035

CDHW - 040

CDHW - 050

CDHW - 070

CDHW - 080

CDHW - 150

CDHW - 160

CDHW - 175

CDHW - 190

CDHW - 200

CDHW - 220

CDHW - 230/240

CDHW - 255

CDHW - 265

72

RUBBER MOUNT / SPRING ISOLATOR

USER'S MANUAL

AHU MODEL

CDHW - 290

CDHW - 300

CDHW - 325

CDHW - 340

CDHW - 355/370/390

CDHW - 410

CDHW - 430/445

CDHW - 455

CDHW - 470/490/500

CDHW - 520/540

CDHW - 570

CDHW - 600

RUBBER MOUNT / SPRING ISOLATOR CODE

DISCRIPTION

QTY/AHU

AHI251600

Spring Isolator : OS 25-160

2

AHI252500

Spring Isolator : OS 25-250

1

AHI251000

Spring isolator : OS 25-100

1

AHI251600

Spring Isolator : OS 25-160

2

AHI252500

Spring Isolator : OS 25-250

1

AHI251000

Spring isolator : OS 25-100

1

AHI251600

Spring Isolator : OS 25-160

1

AHI252500

Spring Isolator : OS 25-250

3

AHI252500

Spring Isolator : OS 25-250

3

AHI251600

Spring Isolator : OS 25-160

1

AHI252500

Spring Isolator : OS 25-250

3

AHI251600

Spring Isolator : OS 25-160

1

AHI252500

Spring Isolator : OS 25-250

3

AHI251600

Spring Isolator : OS 25-160

1

AHI253000

Spring Isolator : OS 25-250

3

AHI252000

Spring Isolator : OS 25-200

1

AHI253000

Spring Isolator : OS 25-300

3

AHI252000

Spring Isolator : OS 25-200

1

AHI253000

Spring Isolator : OS 25-300

3

AHI252000

Spring Isolator : OS 25-200

1

AHI254000

Spring Isolator : OS 25-400

3

AHI252000

Spring Isolator : OS 25-200

1

AHI254000

Spring Isolator : OS 25-400

3

AHI252000

Spring Isolator : OS 25-200

1

AHI254000

Spring Isolator : OS 25-400

3

AHI252000

Spring Isolator : OS 25-200

1

73

DOUBLE SKIN AHUs SCREWLESS

AHU MODEL

LIMIT SWITCH CODE

DISCRIPTION

QTY/AHU

CDHW - 035

AHL001600

Limit Switch LSR Bohmen make

1

CDHW - 040

AHL001600

Limit Switch LSR Bohmen make

1

CDHW - 050

AHL001600

Limit Switch LSR Bohmen make

1

CDHW - 070

AHL001600

Limit Switch LSR Bohmen make

1

CDHW - 080

AHL001600

Limit Switch LSR Bohmen make

1

CDHW - 100

AHL001600

Limit Switch LSR Bohmen make

1

CDHW - 110/120

AHL001600

Limit Switch LSR Bohmen make

1

CDHW - 135

AHL001600

Limit Switch LSR Bohmen make

1

CDHW - 150

AHL001600

Limit Switch LSR Bohmen make

1

CDHW - 160

AHL001600

Limit Switch LSR Bohmen make

1

CDHW - 175

AHL001600

Limit Switch LSR Bohmen make

1

CDHW - 190

AHL001600

Limit Switch LSR Bohmen make

1

CDHW - 200

AHL001600

Limit Switch LSR Bohmen make

1

CDHW - 220

AHL001632

Limit Switch LSR Bohmen make

1

CDHW - 230/240

AHL001708

Limit Switch LSR Bohmen make

1

CDHW - 255

AHL001752

Limit Switch LSR Bohmen make

1

CDHW - 265

AHL001828

Limit Switch LSR Bohmen make

1

CDHW - 290

AHL001862

Limit Switch LSR Bohmen make

1

CDHW - 300

AHL001914

Limit Switch LSR Bohmen make

1

CDHW - 325

AHL001914

Limit Switch LSR Bohmen make

1

CDHW - 340

AHL001994

Limit Switch LSR Bohmen make

1

AHL002006

Limit Switch LSR Bohmen make

1

CDHW - 410

AHL002537

Limit Switch LSR Bohmen make

1

CDHW - 430/445

AHL002071

Limit Switch LSR Bohmen make

1

CDHW - 455

AHL002120

Limit Switch LSR Bohmen make

1

CDHW - 470/490/500

AHL002071

Limit Switch LSR Bohmen make

1

CDHW - 520/540

AHL002071

Limit Switch LSR Bohmen make

1

AHL002084

Limit Switch LSR Bohmen make

1

AHL002149

Limit Switch LSR Bohmen make

1

CDHW - 355/370/390

CDHW - 570 CDHW - 600

74

USER'S MANUAL

AHU MODEL

CANVAS CODE

DISCRIPTION

QTY/AHU

CDHW - 035

HACAZ1010

flexible canvas conn-10-10

1

CDHW - 040

HACAZ1209

flexible canvas conn-12-09

1

CDHW - 050

HACAZ1212

flexible canvas conn-12-12

1

CDHW - 070

HACAZ1515

flexible canvas conn-15-15

1

CDHW - 080

HACAZ1813

flexible canvas conn-18-13

1

CDHW - 100

HACAZ1818

flexible canvas conn-18-18

1

CDHW - 110/120

HACAZ0450

flexible canvas conn-450

1

CDHW - 135

HACAZ0500

flexible canvas conn-500

1

CDHW - 150

HACAZ0500

flexible canvas conn-500

1

CDHW - 160

HACAZ0500

flexible canvas conn-500

1

CDHW - 175

HACAZ0560

flexible canvas conn-560

1

CDHW - 190

HACAZ0560

flexible canvas conn-560

1

CDHW - 200

HACAZ0560

flexible canvas conn-560

1

CDHW - 220

HACAZ0630

flexible canvas conn-630

1

CDHW - 230/240

HACAZ0630

flexible canvas conn-630

1

CDHW - 255

HACAZ0630

flexible canvas conn-630

1

CDHW - 265

HACAZ0710

flexible canvas conn-710

1

CDHW - 290

HACAZ0710

flexible canvas conn-710

1

CDHW - 300

HACAZ0710

flexible canvas conn-710

1

CDHW - 325

HACAZ0710

flexible canvas conn-710

1

CDHW - 340

HACAZ0800

flexible canvas conn-800

1

CDHW - 355/370/390

HACAZ0800

flexible canvas conn-800

1

CDHW - 410

HACAZ0900

flexible canvas conn-900

1

CDHW - 430/445

HACAZ0900

flexible canvas conn-900

1

CDHW - 455

HACAZ0900

flexible canvas conn-900

1

CDHW - 470/490/500

HACAZ0900

flexible canvas conn-900

1

CDHW - 520/540

HACAZ1000

flexible canvas conn-1000

1

CDHW - 570

HACAZ1000

flexible canvas conn-1000

1

CDHW - 600

HACAZ1000

flexible canvas conn-1000

1

75

DOUBLE SKIN AHUs SCREWLESS

Spare Parts List / SDVW AHU MODEL

SDVW - 035

SDVW - 050

SDVW - 070

SDVW - 100

SDVW - 140

SDVW - 170

SDVW - 200

SDVW - 250

SDVW - 270

SDVW - 300

76

V - BELT ITEM CODE

DISCRIPTION

QTY/AHU

SPA-800

Belt ( 40 mm SP ),800-SPA-1

1

SPA-800

Belt (32mm SP), 800-SPA-1

1

SPA-800

Belt (40mm SP), 800-SPA-1

1

SPA-800

Belt (32mm SP), 800-SPA-1

1

SPA-1220

Belt (40mm SP),1220-SPA-1

1

SPA-1060

Belt (32mm SP),1060-SPA-1

1

SPA-1060

Belt (40mm SP),1060-SPA-1

1

SPA-1000

Belt (32mm SP),1000-SPA-1

1

SPA-1060

Belt (40 mm SP),1060-SPA-1

2

SPA-1000

Belt (32 mm SP),1000-SPA-1

2

SPA-1120

Belt (40mm SP), 1120-SPA-1

2

SPA-1000

Belt (32mm SP), 1000-SPA-1

2

SPA-1250

Belt (40mm SP),1250-SPA-1

2

SPA-1000

Belt (32mm SP),1000-SPA-1

2

SPA-1400

Belt ( 40 mm SP ),1400-SPA-1

2

SPA-1120

Belt ( 32 mm SP ),1120-SPA-1

2

USER'S MANUAL

FILTER AHU MODEL

ITEM CODE

DESCRIPTION

QTY/AHU

SDVW - 035

AHF400502

Prefilter-EU3-AL(400X500)

2

SDVW - 050

AHF600507

Prefilter-EU3-AL(600X500)

2

SDVW - 070

AHF400603

Prefilter-EU3-AL(400X600)

2

AHF500603

Prefilter-EU3-AL(500X600)

2

SDVW - 100

AHF500407

Prefilter-EU3-AL(500X400)

6

SDVW - 140

AHF500407

Prefilter-EU3-AL(500X400)

8

SDVW - 170

AHF600407

Prefilter-EU3-AL(600X400)

8

SDVW - 200

AHF500407

Prefilter-EU3-AL(500X400)

6

AHF600407

Prefilter-EU3-AL(600X400)

4

AHF500507

Prefilter-EU3-AL(500X500)

6

AHF600507

Prefilter-EU3-AL(600X500)

4

SDVW - 250

SDVW - 270 SDVW - 300

RUBBER MOUNT/ SPRING ISOLATOR AHU MODEL

ITEM CODE

DESCRIPTION

QTY/AHU

SDVW - 035

AHI065000

RM 19 . 100 B

2

AHI068000

RM 19 . 100 . Y

2

AHI062800

RM 19 . 100 R

2

AHI065000

RM 19 . 100 . B

2

AHI062800

RM 19 . 100 R

2

AHI065000

RM 19 . 100 . B

4

AHI062800

RM 19 . 100 R

2

AHI065000

RM 19 . 100 . B

4

AHI062800

RM 19 . 100 R

4]

AHI065000

RM 19 . 100 . B

2

AHI062800

RM 19 . 100 R

2

AHI065000

RM 19 . 100 . B

4

SDVW - 200

AHI062800

RM 19 . 100 R

8

SDVW - 250

AHI062800

RM 19 . 100 R

8

SDVW - 050

SDVW - 070

SDVW - 100

SDVW - 140

SDVW - 170

SDVW - 270 SDVW - 300

77

DOUBLE SKIN AHUs SCREWLESS

CANVAS CONN. AHU MODEL

DESCRIPTION

QTY/AHU

SDVW - 035

NR

SDVW - 050

NR

SDVW - 070

NR

SDVW - 100

NR

SDVW - 140

HACAZ1515

flexible canvas KAT 15X15

2

SDVW - 170

HACAZ1813

flexible canvas KAT 18X13

2

SDVW - 200

HACAZ1818

flexible canvas KAT 18X18

2

SDVW - 250

HACAZ0450

flexible canvas-450

2

SDVW - 270 SDVW - 300

78

ITEM CODE

USER'S MANUAL

Spare Parts List / DCW AHU MODEL

V-BELT ITEM CODE

DESCRIPTION

QTY

SDCW4017B

SPA-850

850

SPA(1)

1

SDCW4027B

SPA-850

850

SPA(1)

1

SDCW4035B

SPA-850

850

SPA(1)

1

SDCW4042B

SPA-850

850

SPA(1)

1

SDCW4050B

SPA-850

850

SPA(1)

1

SDCW4060B

SPA-950

950

SPA(1)

1

SDCW4070B

SPA-850

850

SPA(1)

1

SDCW4078B

SPA-850

850

SPA(1)

1

SDCW4085B

SPA-950

950

SPA(1)

1

SDCW4093B

SPA-900

900

SPA(1)

1

SDCW4100B

SPA-900

900

SPA(1)

1

SPA-800

800

SPA(2)

2

SDCW4110B

SPA-1060

1060

SPA(1)

1

SDCW4118B

SPA-1060

1060

SPA(2)

1

SDCW4127B

SPA-1090

1090

SPA(2)

2

SDCW4135B

SPA-1090

1090

SPA(2)

2

SDCW4035D

NR

SDCW4050D

NR

SDCW4070D

NR

79

DOUBLE SKIN AHUs SCREWLESS

AHU MODEL CODE

DISCRIPTION

QTY

SDCW4017B

AHF600407

Prefilter-EU3-AL-BOX-600W400H

1

SDCW4027B

AHF500407

Prefilter-EU3-AL-BOX-500W400H

2

SDCW4035B

AHF500407

Prefilter-EU3-AL-BOX-500W400H

2

SDCW4042B

AHF500407

Prefilter-EU3-AL-BOX-500W400H

3

SDCW4050B

AHF500407

Prefilter-EU3-AL-BOX-500W400H

3

SDCW4060B

AHF500407

Prefilter-EU3-AL-BOX-500W400H

4

SDCW4070B

AHF500407

Prefilter-EU3-AL-BOX-500W400H

4

SDCW4078B

AHF400502

Prefilter-EU3-AL-BOX-400W500H

1

AHF500507

Prefilter-EU3-AL-BOX-500W500H

3

AHF400502

Prefilter-EU3-AL-BOX-400W500H

1

AHF500507

Prefilter-EU3-AL-BOX-500W500H

3

SDCW4093B

AHF610617

Prefilter-EU3-AL-BOX-610W610H

3

SDCW4100B

AHF400603

Prefilter-EU3-AL-BOX-400W600H

2

AHF500603

Prefilter-EU3-AL-BOX-500W600H

2

AHF305614

Prefilter-EU3-AL-BOX-305W610H

1

AHF610617

Prefilter-EU3-AL-BOX-610W610H

3

AHF305614

Prefilter-EU3-AL-BOX-305W610H

1

AHF610617

Prefilter-EU3-AL-BOX-610W610H

3

SDCW4127B

AHF610617

Prefilter-EU3-AL-BOX-610W610H

4

SDCW4135B

AHF610617

Prefilter-EU3-AL-BOX-610W610H

4

SDCW4035D

AHF500407

Prefilter-EU3-AL-BOX-500W400H

2

SDCW4050D

AHF500407

Prefilter-EU3-AL-BOX-500W400H

3

SDCW4070D

AHF500407

Prefilter-EU3-AL-BOX-500W400H

4

SDCW4085B

SDCW4110B

SDCW4118B

80

FILTER

USER'S MANUAL

AHU MODEL

RUBBERMOUNT/SPRING ISO/PAD CODE

DISCRIPTION

QTY

SDCW4017B

AHI070000

Rubber Pad

4

SDCW4027B

AHI070000

Rubber Pad

4

SDCW4035B

AHI070000

Rubber Pad

4

SDCW4042B

AHI070000

Rubber Pad

4

SDCW4050B

AHI070000

Rubber Pad

4

SDCW4060B

AHI070000

Rubber Pad

4

SDCW4070B

AHI070000

Rubber Pad

4

SDCW4078B

AHI070000

Rubber Pad

4

SDCW4085B

AHI070000

Rubber Pad

4

SDCW4093B

AHI070000

Rubber Pad

4

SDCW4100B

AHI070000

Rubber Pad

4

SDCW4110B

AHI070000

Rubber Pad

4

SDCW4118B

AHI070000

Rubber Pad

8

SDCW4127B

AHI070000

Rubber Pad

8

SDCW4135B

AHI070000

Rubber Pad

8

SDCW4035D

AHI070000

Rubber Pad

4

SDCW4050D

AHI070000

Rubber Pad

4

SDCW4070D

AHI070000

Rubber Pad

4

81

DOUBLE SKIN AHUs SCREWLESS

Field Feedback Card Product:

Air Handing Unit

AHU Model: Unit Sr. No. : Customer Name :

Location :

Date : Observation Quality of Packing

Comments

Details of Defects

OK / Damaged

Receipt of Documents -

Packing List

Yes / No

-

Panel Arrangement Drawing

Yes / No

Condition of Parts : -

Aluminium Extrusion

OK / Damaged

-

Puf Panels

OK / Damaged

-

Hardware

OK / Damaged

-

Drain Pan

OK / Damaged

-

Fabricated Frames

OK / Damaged

-

Coil

OK / Damaged

-

Blower

OK / Damaged

-

Motor

OK / Damaged

-

Drive Set

OK / Damaged

-

Filters

OK / Damaged

-

Dampers

OK / Damaged

Remarks :

Checked by For Factory Use :

82

-

Date of Receipt :

-

Comments :

- Action By :

USER'S MANUAL

Field Commissioning Report To be filled on Com

Product:

Air Handing Unit

AHU Model: Unit Sr. No. : Customer Name :

Location :

Date : Observation

Comments

Details of Defects

Performance Checks : -

Assembly

OK /

-

Installation

OK /

-

Commissioning

OK /

-

Air Quantity ( CMH / CFM )

-

Static Pressure ( Pa / mm )

-

Blower ( RPM )

-

Motor Current ( Amps )

-

Noise Level ( dba )

-

Vibration

OK /

-

Air balancing, If done at site

Yes / No

-

Change in Pulley Size at site

Yes / No

-

Others, if any

-

Commissioning Date

-

Commissioning By

Remarks :

Note: Warranty will be valid only after receipt of this form at Factory. For Factory Use : -

Date of Receipt :

-

Comments :

- Action By :

83

DOUBLE SKIN AHUs SCREWLESS

WARRANTY CLAIM FORM FOR AHU (A copy of this form is to be filled in case of AHU failure, by BSL Engineer) Location (City) ______________________________

Date ______________



AHU MODEL NO:

AHU Serial No

Date of despatch Warranty commencing date Application in which the equipment used

Date of Commissioning Warranty expiry date

Customer’s Name and Address

Dealer’s Name and Address

Starting problem Noise at starting

 Yes  Yes  Yes

 No  No  No

Noise while running If there is noise, indicate the type of noise from the list __________________________________________ Blower Fan: Unbalanced, Vibration, Rubbing, Shaft bent. Electric Motor: Jammed, Bearings failed, Internal noise, Burnt out. (Check voltage, current, insulation resistance).

Voltage at each phase

 Yes  Yes  Yes

Voltage at each phase to phase Insulation resistance (Megger test)

 No _______________ Mohms

Any leakage in the coil

 Yes  Yes  Yes  Yes  Yes  Yes  Yes

Electrical problem Three phase balanced

Filters clogged Filters worn out Condition of V Belts Belt tension correct Alignment checked All bolts of Fan/Motor tightened

 No  No  No  Yes

 No  No  No  No  No  No  No

Signature & Seal of Customer

Signature & Seal of BSL Engineer

Date: ________________

Date: ________________ (For factory use)

Claim Settled  Credit Advice No._________________ Claim Rejected  Reasons for rejection _________________________________________________________________ Settlement authorised by: _____________________ Date: _____________________

84

USER'S MANUAL

Warranty Blue Star AHUs carry a warranty for a period of 12 months from the date of commissioning or 15 months from the date of delivery, whichever is earlier, unless stated otherwise in the contract of sales. Warranty coverage shall be applicable from the date of receipt of Field Commissioning Report (see page 75) at Blue Star Bharuch Factory. While filing a claim for Warranty repairs, please allow our representative to fill in the Warranty Claim Form (see page 76) and send it to Factory for speedy Warranty repairs.

Terms of Warranty Blue Star extends a comprehensive Warranty on its systems, which entitles the customer to the following: 1. Repair/reconditioning, by BSL/BSL Dealer, through whom the machine has been purchased, of any part of the equipment found defective within 12 months from the date of commissioning or 15 months from the date of despatch whichever is earlier. 2. The warranty is valid only if: 2.1 Installation and commissioning is taken care of by BSL/their authorised persons. 2.2 The equipment is operated as per the Company’s operating instructions. 3. The above said warranty does not cover the following: 3.1 Consumables such as V belts, air filters etc. 3.2 Deterioration or failure of equipment due to corrosive atmosphere. 4. This warranty is not valid if any repair and/or modifications are carried out by the customer himself or his representative without written concurrence from Blue Star Limited. 5. The guarantee extended herein is in lieu of all implied conditions/warranties under the law and is confined to the repairs or replacements of defective parts and does not cover any consequential or resulting liability damage or loss arising from such defect. Furthermore, the guarantee in no case, shall extend to the payment or any monetary consideration whatsoever of the replacement or return of the AHU as a whole. 6. Any repair/replacement shall not extend the overall warranty period as specified above. 7. The cost of transportation of material and of persons beyond Municipal jurisdiction shall be borne by the customer. 8. This warranty may be read in conjunction with any other warranty on the installation as a whole, if the AHU is supplied as part of a project.

85

DOUBLE SKIN AHUs SCREWLESS

Service Centres EAST

SOUTH

WEST

BHUBANESHWAR 3A, Satya Nagar, 2nd Floor, Bhubaneswar 751 007. Tel: (0674) 2508270 / 2508239

BANGALORE Ozone Manay Technology Park Sy. No. 56/18 & 55/9 Hongasandra Village Begur Hobli, Garvebhavipalya Bangalore – 560 068 Phone : 41854000

AHMEDABAD 2nd Floor, Shivalik - II, Near Shivranjani Cross Roads, 132 Feet Ring Road, Satellite, Ahmedabad - 380015. Tel: (079) 40224000

GUWAHATI New Star Freeze Building 2nd Floor, Opp. Kunjalata Bibah Bhawan, G. S. Road, Guwahati 781 005. Tel: (0361) 2340619 / 2340620 KOLKATA 7, Hare Street Kolkata 700 001. Tel: (033) 22134200 / 22106609

NORTH CHANDIGARH SCO 1, Madhya Marg, Sector 26, Chandigarh 160 019. Tel: (0172) 2790482 / 5004000 JAIPUR A-19, Main Sahakar Path, Near Sahakar Bhawan, Jaipur - 302 001. Tel: (0141) 5124898 / 2744033 LUCKNOW 177/4, Faizabad Road, Lucknow 226 007. Tel: (0522) 4034000 NEW DELHI E-44/12 Okhla Ind. Area Phase II, Ohkla New Delhi 110 020. Tel: (011) 41494200 / 000

86

CHENNAI 104, ‘Garuda Building’, Cathedral Road, Chennai 600 086. Tel: (044) 42444200 28116707- 8 KOCHI 2nd Floor, Millennium Plaza, MKK Nair Road, Alinchuvadu Junction, Kochi 682 024. Tel: (0484) 4499000 SECUNDERABAD 207, Sikh Road Bantia Estates Secunderabad 500 003. Tel: (040) 27847553 / 27842057-58 / 27815469 TRIVANDRUM T.C. IX/1490 ‘Chandrika’, Sasthamangalam Trivandrum 695 010. Tel: (0471) 2720025 / 2720065 VISAKHAPATNAM D. No. 49-24-65/1, Near Sankarmattam Road, Madhura Nagar, Visakhapatnam 530 016. Tel: (0891) 2748405 / 2748433

BHOPAL “Star Arcade”, 2nd Floor Plot No.165A & 166, Zone-I Maharana Pratap Nagar Bhopal 462 011. Tel: (0755) 2553378 / 4273378 / 79 GOA 1st Floor, Buddhaseth Apartments, Tonca, Caranzalem, Goa 403 002. Tel: (0832) 2461671 / 2462087 MUMBAI Blue Star House 9A, Ghatkopar Link Road Saki Naka, Mumbai 400 072. Tel: (022) 66684200 / 66684000 NAGPUR 219, Bajaj Nagar, 1st Floor, South Ambazari Road, Nagpur 440 010. Tel: (0712) 2229244 / 2249000 PUNE 201/A, Nityanand Complex 1st Floor, 247/A Bund Garden Road Pune 411 011. Tel: (020) 41044000 / 26113031 26127230 / 26122307 VADODARA Ramakrishna Chambers 7th Floor, Productivity Road Alkapuri, Vadodara 390 005. Tel: (0265) 2338561 / 2332021 / 22

USER'S MANUAL

For any assistance, CALL: Blue Star Service: Ph: ............................................................ Cell: ..........................................................

Blue Star Dealer: Ph: ............................................................ Cell: ..........................................................

Blue Star Regional Manager: Ph: ............................................................ Fax: ..........................................................

Blue Star’s/Dealer’s engineer to fill above details before handing over this Manual to customer.