Topic Objectives Objectives r Fault condition in a power grid r Protection zones r System behavior in case of breaker failure situation r BFP solutions
supervision of the feeder current (with an overcurrent criteria) after a tripping command OR
2.
supervision of the CB auxiliary contacts after a tripping command OR
3.
supervision of the feeder current (with the BBP measurement algorithm) after a tripping command (only applicable if the BFP is installed in the BBP system) - BBP unbalancing
Breaker Failure Protection Solutions solution 1:
t ~ higher than the highest possible CB opening time + arc extinguish time
the trip from the protection device is called „Starting BFP“
An advanced BFP (& BBP) system offers all 3 solutions !!!
???
Breaker Failure Protection Solutions Application & features of solution 1: ⇒ standard BFP application (most common used) ⇒ for line, transformer, generator, generator- transformer, reactors and coupler CBs ⇒ for all voltage levels and switchgear configurations ⇒ overcurrent settable independently for all feeders (depending on the minimum feeder short current) ⇒ operation independent on the CB auxiliary contacts (aux. contacts are a week part of the protection chain) ⇒ for single, double and three phase auto- reclosure (tripping), (phase segregated starting inputs)
⇒ for detection of evolving faults (phase segregated timers for t1) ⇒ remote tripping signal settable after timer 1 or timer 2 ⇒ advanced trip- redirection functionality in case of CB SF6 underpressure condition ⇒ not applicable for very low fault currents (e.g. generator reverse power function) -> solution 2
Breaker Failure Protection Solutions solution 1: Start R S T Start R IR
phase segregated starting inputs for single and double pole auto reclosure
Start R S T Start R IR
Start S IS
Start T IT
≥1 &
t1
remote tripping settable after t1 or t2
I> ≥1 &
t1 ≥1
I>
t2
≥1 &
t1
I>
remote tripping re-trip to faulty CB
Trip Redirection
set t1 & t2 to 10ms
advanced trip redirection functionality
(coil 1 & 2)
trip to the surrounding CBs by intertripping
Breaker Failure Protection Solutions Application & features of solution 2: ⇒ applicable for very low fault currents (e.g. generator reverse power function) ⇒ remote tripping signal settable after timer 1 or timer 2 ⇒ advanced trip- redirection functionality in case of CB SF6 underpressure condition ⇒ very good addition to solution 1 ⇒ no overcurrent (fault current) supervision ⇒ the starting signal must be switch off by the CB “OFF” aux. contact to prevent an unwanted trip
⇒ operation dependent on the CB auxiliary contacts (aux. contacts are a week part of the protection chain) ⇒ not applicable for single and double phase auto- reclosure (tripping) ⇒ not applicable for detection of evolving faults
Breaker Failure Protection Solutions solution 2 in addition to solution 1: Start R S T Start R IR
Breaker Failure Protection Solutions Application & features of solution 3: ⇒ applicable as basic BBP coupler functionality for the detection of faults between coupler CB and CT (coupler function - CB reclaim time) ⇒ not applicable for line, transformer, generator, generator- transformer, reactors feeders in HV systems ⇒ overcurrent (fault current) supervision depending on the BBP differential current setting (high short current required) ⇒ functionality depending on the BBP ⇒ not applicable for single and double phase auto- reclosure (tripping) ⇒ not applicable for detection of evolving faults
⇒ the starting signal must be switch off by the CB “OFF” aux. contact to prevent an unwanted trip to the CB after timer 1 ⇒ operation dependent on the CB auxiliary contacts (aux. contacts are a week part of the protection chain) ⇒ no trip- redirection functionality in case of CB SF6 underpressure condition ⇒ remote tripping signal fixed to timer 1
Breaker Failure Protection Solutions Coupler function: Zone 2
Thank you for interesting in our services. We are a non-profit group that run this website to share documents. We need your help to maintenance this website.