ASHRAE Standard 62 and LEED Certification
Short Description
ashrae standard62...
Description
ASHRAE Standard 62.1 and LEED Certification Ventilation for Acceptable Indoor Air Quality
Stephen Haines, EIT EIT,, LEED AP JBA Consulting Engineers Mechanical Engineering
What is ASHRAE Standard 62.1?
The Industries Ventilation Standard
Purpose: “… to specify minimum ventilation rates and other measures intended to provide indoor air quality that is acceptable to human occupants and that minimizes adverse health health effects.” effects.”
Scope: All commercial, institutional and high-rise residential buildings (excludes low-rise residential)
History of ASHRAE Standard 62.1 1989
Higher Rates (Office – 20 cfm/person)
1981
Lower Rates (Office – 5 cfm/person) 1970
1980
1990
2001
More Mandatory Language
2000
2010
1999 1984
Steve’s birthday
2010
Little Change
Most Current 2004
1973
First Issued (Office – 15 cfm/person)
Key Changes: Ventilation Rate Procedure
2007
Corrections, Clarifications
Key Changes in 62.1-2004
Area-related Area-relat ed and occupancy-re occupancy-related lated ventilation components Minimum Ventilation Rate Table revised to apply only to non-smoking areas (smoking areas are still not addressed) Appendix G – Existing Buildings Buildings Equipment replacements, replacements, Substantial Substantial alterations alterations Additions, Equipment
Indoor Air Humidity (65% max) and pressure requirements (positive when dehumidifying)
Requirement to deliver outside air directly to occupied spaces
Why is ASHRAE 62.1 Important?
It is the basis for many ventilation codes
More stringent than codes in some cases and helps establish the “standard-of-care standard-of-care””
Compliance with ASHRAE Standard 62.1-2007 is a prerequisite for any LEED-NC any LEED-NC credits
Two Paths to Compliance
Ventilation Rate Procedure
Most commonly used method
Table 6-1 Minimum Ventilation Rates in Breathing Zone
Need to determine the zone air distribution effectiveness (E z)
LEED requires this method for compliance
Indoor Air Quality Procedure
Designed to maintain specific contaminant levels
Mass balance analysis
Methods used in similar buildings
Validation by contaminant monitoring verification
Ventilation Rate Procedure
Ventilation Rate Procedure
Note the following f ollowing rooms do not require area-based ventilation per ASHRAE Stan dard 62.1-2007: Electrical equipment rooms Telecommunication elecommunications/data s/data rooms Elevator machine rooms Other similar non-occupied spaces
Clarified under Interpretation IC 62.1-2007-17 approved on January 23, 2010
Correction made for Standard 62.1-2010
Ventilation Rate Procedure
Note the following f ollowing rooms do not require area-based ventilation per ASHRAE Stan dard 62.1-2007: Electrical equipment rooms Telecommunication elecommunications/data s/data rooms Elevator machine rooms Other similar non-occupied spaces
Clarified under Interpretation IC 62.1-2007-17 approved on January 23, 2010
Corrected in the 2010 version of the Standard S tandard
Classroom Example Single Zone - 62.1-2007
High School Classroom 35’ x 35’ (30 people)
Breathing Zone Outdoor Airflow (V bz) = RpPz + Ra Az
Occupancy component - 10 cfm/person – 10 x 30 people = 300 cfm
Area component component - 0.12 cfm/ft cfm/ft 2 – 0.12 x (35’ x 35’) = 147 cfm Zone Air Distribution Effectiveness
Zone Outdoor Airflow (Voz) = Vbz/Ez
Voz = (300 + 147)/1.0 = 447 cfm or 14.9 cfm/person
Be careful with E z values! Most of the time E z = 0.8 in heating mode which yields a higher higher ventilation ventilation rate requirement. Reference Table Table 6-2!
Ventilation Rate Procedure
Multiple Zone Recirculating Systems
Vou = ∑(RpPz + Ra Az) for all zones – Uncorrected Outdoor Air Intake
Vot = Vou/Ev – Outdoor Air Intake
To determine the System Ventilation Efficiency (E v), use Table 6-3 with the Zone Primary Outdoor Air Fraction Z p
Primary Outdoor Air Fraction Z p
Zp = Voz/Vpz
Voz – Zone outdoor airflow
Vpz – Zone primary airflow (for VAV systems V pz is the minimum minimum expected expected primary airflow for design purposes)
Multiple Zone Example Office 15’x10’ 1 Occupant 100 cfm SA Corridor 4’ wide 0 Occupants 150 cfm SA
Break Room 10’x20’ 4 Occupants 200 cfm SA
Storage 10’x10’ 0 Occupants 50 cfm SA
Conference 12’x12’ 6 Occupants 150 cfm SA
Office 15’x10’ 1 Occupant 100 cfm SA
Office 10’x20’ 2 Occupants 150 cfm SA
Note: supply airflows are heating minimum values Office 18’x10’ 2 Occupants 150 cfm SA
Office 18’x10’ 2 Occupants 150 cfm SA
Multiple Zone Example
Vou = ∑(RpPz + Ra Az) for all zones – uncorrected outdoor air intake
Offices
15’ x 10’ x (0.06 cfm/ft2) + 1 person x 5 cfm/person = 14 cfm OA
10’ x 20’ x (0.06 cfm/ft2) + 2 people x 5 cfm/person = 22 cfm OA
18’ x 10’ x (0.06 cfm/ft2) + 2 people x 5 cfm/person = 21 cfm OA
Office total
(14 cfm) x 2 + 22 cfm + (21 cfm) x 2
Office total = 92 cfm OA
Multiple Zone Example
Vou = ∑(RpPz + Ra Az) for all zones – uncorrected outdoor air intake
Break Room 10’ x 20’ x (0.06 cfm/ft2) + 4 people x 5 cfm/person = 32 cfm OA
Conference 12’ x 12’ x (0.06 cfm/ft2) + 6 people x 5 cfm/person = 39 cfm OA
Storage 10’ x 10’ x (0.12 cfm/ft2) = 12 cfm OA
Corridor 296 ft2 x (0.06 cfm/ft2) = 18 cfm OA
Multiple Zone Example
Vou = ∑(RpPz + Ra Az) for all zones – uncorrected outdoor air intake
Office total – 92 cfm
Break room – 32 cfm
Conference – 39 cfm
Storage – 12 cfm
Corridor -18 cfm
Building total = 92 + 32 + 39 + 12 + 18 = 194 cfm
… BUT BUT WAIT!
Multiple Zone Example
Building total = 194 cfm OA
But Vou is the “uncorrected” outdoor air intake – we also have to account for the System Ventilation Efficiency (Ev)
What exactly is the System Ventilation Efficiency?
Here is where it can get a little tricky!
System Ventilation Efficiency
The System Ventilation Efficiency (E v) increases the outside air at the system to account for the critical zones
Example The critical zone is a conference room where the zone requires 50% of the minimum supply air to be outside air Based on the building area and occupant requirements for ventilation, the % outside air at the air handling unit is only 15% always be be underventilated under these conditions The critical zone will always
ASHRAE says we need need to increase increase the outside outside air at the unit unit to compensate for this How does this affect our Multiple Zone Example?
Multiple Zone Example
Lets calculate the Zone Primary Outdoor Air Fraction for each zone
Zp = Voz/Vpz
Office 1 – 15’ x 10’
Office 2 – 10’ x 20’
Zp = (18 cfm OA)/(100 cfm SA) = 0.18
Zp = (28 cfm OA)/(150 cfm SA) = 0.19
Office 3 – 18’ x 10’
Zp = (27 cfm OA)/(150 cfm SA) = 0.18
Multiple Zone Example
Zp = Voz/Vpz
Break Room Zp = (40 cfm OA)/(200 cfm SA) = 0.20
Conference Zp = (49 cfm OA)/(150 cfm SA) = 0.33
Storage Zp = (15 cfm OA)/(50 cfm SA) = 0.30
Corridor Zp = (23 cfm OA)/(150 cfm SA) = 0.16
Multiple Zone Example
Office 1 – Z p = 0.18
Office 2 – Z p = 0.19
Office 3 – Z p = 0.18
Break Room - Z p = 0.20
Conference - Z p = 0.33
Storage - Z p = 0.30
Corridor - Zp = 0.16
Highest Zp – Conference – 0.33
Multiple Zone Example
Vot = Vou/Ev – Outdoor Air Intake
Using Table 6-3 with Zp = 0.33 and by interpolating, Ev = 0.82
Vot = (194 cfm)/0.82
Vot = 236 cfm OA required
Will use 240 cfm OA
0.82
Multiple Zone Example
Now what happens if we increase the VAV VAV box minimums on the critical zones?
Zp = Voz/Vpz
Conference (increased minimum SA from 150 cfm to 250 cfm) Zp = (49 cfm OA)/(250 cfm SA) = 0.20 (previously 0.33)
Storage (increased minimum SA from 50 cfm to 100 cfm) Zp = (15 cfm OA)/(100 cfm SA) = 0.15 (previously 0.30)
Using Table 6-3 with the max Zp = 0.20 and by interpolating, Ev = 0.95
Vot = (194 cfm)/0.95
Vot = 205 cfm cf m OA required
Use 205 cfm OA instead of 240 cfm
0.95
Alternative Procedures
Appendix A calculate System Ventilation Ventilation Efficiency Efficiency (Ev) other Another way to calculate than using Table 6-3 Ev = minimum (Evz) Evz = 1 + Xs – Zd Average Outdoor Air Fraction at the air handling unit Xs is the Average Zd is the Discharge Outdoor Air Fraction at the zone In our Multiple Zone Example, Ev = 1 + (194 cfm)/(1200 cfm) – 0.33 = 1 + 0.16 – 0.33 = 0.83 Vot = (194 cfm)/0.83 = 234 cfm – very similar result All zone Zp values do not necessarily need to be calculated, just the “critical zones”
Title 24 Requirements
But what about Title 24?
Based on Section 121 – Requirements for Ventilation
Mechanical Ventilation
The conditioned floor area of the t he space times the applicable ventilation ventilat ion rate from Table Table 121-A or
15 cfm/person times the expected number of occupants
Cannot be less than the larger of the two!
Multiple Zone Example
Area-based ventilation ventilation rate: Table 121-A for office space (other) is 0.15 cfm/sf Required OA = 1,600 sf x 0.15 cfm/sf = 240 cfm
People-based ventilation rate: People-based 15 cfm/person Required OA = 18 people x 15 cfm/person = 270 cfm
Title 24 Ventilation – 270 cfm
ASHRAE Standard Standard 62.1 Ventilation Ventilation – 240 cfm This result is not always the case!
Title 24 Requirements
Section 144 (d) – Space-cond Space-conditioning itioning Zone Controls
Minimizes reheating to reduce energy use
The volume of primary air that is reheated, re-cooled, or mixed air supply shall not exceed the larger of:
50 percent of the peak primary airflow, or
The design zone outdoor airflow rate per Section 121
May not be possible to increase minimum zone airflows to reduce Zp in the critical zones
Title 24 Requirements
Section 121 (c) – Operation and Control Requirements
Required Demand Control Ventilation
CO2 sensors required in densely occupied spaces (occupant density greater than or equal to 25 people per 1,000 sf)
May reduce OA for these spaces based on CO2 levels
Dynamic Reset not a requirement in ASHRAE ASHRAE Standard 62.1
CO2 sensors are required for LEED OA Delivery Monitoring credit
ASHRAE 62.1 Design Tips Tips
Identify the “critical zones”
High occupant density and low airflow requirement (i.e. little to no envelope load)
Interior conference/meeting rooms
Interior waiting/lobby areas
Interior break rooms
Not necessarily limited to interior zones (north-facing and no glass)
Increase VAV box minimum airflows in critical zones to reduce outside air where possible [ watch out for Title 24 Section 144 (d) ]
May use transfer fans to increase supply air to a critical space
ASHRAE 62.1 Design Tips Tips
May account for Occupant Diversity – the ratio of the system population to the sum of the zone populations
Utilize calculation spreadsheet
Spreadsheet provided with ASHRAE 62.1 User’s Manual Allows you you to input only the critical zones Spreadsheet uses Appendix A approach
Caution!
Don’t forget about building pressurization - a pressurization calc should be done to ensure that the building is positively pressurized which could result in higher air quantities than ASHRAE 62.1 requires Make sure heating minimum supply air values can handle the zone heat losses with the selected reheat coil
LEED Compliance
LEED Version 3.0 requires that the design meet the minimum requirements of Sections 4 through 7 of ASHRAE Standard 62.1-2007
IEQ Prerequisite 1 – Minimum IAQ Performance (mandatory) IEQ Credit 2 – Increased Ventilation (optional)
The Ventilation Rate Procedure must be correctly documented and uploaded to LEED Online for review
Best method – “62MZCalc” spreadsheet
Pre-programmed spreadsheet template Accepted by USGBC Available with purchase of ASHRAE 62.1 User’s Manual Free through LEED Online under “Credit Resources”
LEED Compliance – 62MZCalc Entered Values Critical Zone
System Ev = 0.84 Required Vot = 229 cfm
LEED Compliance – 62MZCalc
“62MZCalc” spreadsheet tips
Required only to input “potentially critical zones” Analyze all operating conditions
Cooling mode
Heating mode
Apply occupant diversity (D) where possible
Check with Architect for a building program or design occupancy
May be based on full-time equivalent (FTE) occupants
Spreadsheet instructions
Cell unlock code
LEED Compliance
LEED Documentation Materials
IEQp1 Submittal Template (LEED Online form v3.0 or Template PDF v2.2) ASHRAE Standard 62.1 Documentation Documentation of the VRP
“62MZCalc” Spreadsheet
Trane Trace Trace 700 Calculation Report
Carrier’s HAP Calculation Report
Other suitable analysis program
Equipment schedules identifying design OA for all systems
Equipment submittals (if applicable)
LEED Compliance
LEED Design Review Process
Design Application Submission Design Application Review GBCI (25 business days) Final Design Review Appeals ($500 per credit)
Design Application Review Pending Issues “It is unclear…” Technic echnical al Advice “Please provide revised VRP calculations demonstrating…”
Design Application Application Review Comments The LEED Submittal Template Template has been provided stating st ating that the project complies with the minimum requirements of ASHRAE Standards 62.1-2004. A narrative has been provided describing the project's ventilation system design. However, specific information regarding the fresh air intake volumes has not been provided. TECHNICAL ADVICE: Please provide a more detailed narrative or resubmit the t he LEED Submittal Template Template to include a more detailed narrative that includes specific information regarding the fresh air intake volumes.
Design Application Application Review Comments The LEED Submittal Template has been provided stating that the project complies with the minimum requirements of ASHRAE Standard 62.1-2004, Ventilat ion for Acceptable Indoor Air Quality, using the Ventilat ion Rate Procedure… However, two issues are pending: 1. The documentation and Ventilation Rate Procedure (VRP) calculations indicate an Ez value of 1.0 for all VRP calculations, and it is unclear whether the operating conditions represented in the calculations reflect the worst-case scenario. 2. It is unclear how the System System Ventilation Efficiency (Ev) value has been determined. In addition, it is unclear which zone, zone, for each unit serving multiple zones, is the critical zone. Therefore, it is unclear whether the critical zone has been used to determine the Primary Outdoor Air Fraction (Zp) and System Ventilation Efficiency (Ev) values. TECHNICAL ADVICE: 1. Please provide revised VRP calculations demonstrating that the values have been adjusted such that they are in compliance with ASHRAE Standard 62.1-2004, Table 6.2. Provide a detailed narrative including specific information regarding the selection of the worst-case design conditions for the VRP calculations. Alternatively, include information explaining the selection of an Ez value of 1.0 for all systems. 2. Indicate in the narrative how the Ev value value has been determined, as well as the critical zone for each unit serving multiple zones. If necessary, provide revised calculations demonstrating that the critical zone has been used to determine the Primary Outdoor Air Fraction (Zp) and System Ventilation Efficiency (Ev) values.
Design Application Application Review Comments The LEED Prerequisite P rerequisite Form has been provided stating that the project is mechanically ventilated and mechanically conditioned, therefore the project applies Case 1. T he project has utilized the VRP Compliance Calculator. However, the tenant guidelines do not indicate the requirements of ASHRAE 62.1-2007 must be met and a copy of the legally binding document (e.g. lease, sales agreement), specifying minimum performance criteria for IEQp1 for the tenant work, has not been bee n provided. TECHNICAL ADVICE: 1. Provide revised tenant guidelines guidelines to include a reference to meeting the minimum minimum requirements of ASHRAE 62.12007 and ensure that a copy of the t he legally binding document (e.g. lease, sales agreement), explicitly explicitly stating the performance requirements for the tenant work is included.
Other Important Sections in ASHRAE 62.1
Minimum MERV ratings for filters (minimum MERV 6 upstream of cooling coils)
Exhaust rates (Table 6.4)
Restrooms Copy/printing rooms Kitchenettes (break rooms) Chemical storage rooms (housekeeping)
Natural ventilation – specifies location and size of openings in lieu of or in addition to mechanical ventilation
Outside air intake minimum separation distances (Table 5.1)
References
ASHRAE Standard Standard 62.1 PDFs available of older versions of the Standard ASHRAE 62.1 62.1 User’s Manual
More detailed explanation of the Ventilation Rate Procedure
Example problems
ASHRAE website website
Questions?
View more...
Comments