P632 Transformer Differential Protection Device Version -304 -403/404 -606 ff
Supporting Documents P632/EN IN/A54 (AFSV.11.09640 EN) This document does not replace the Technical Manual
!
Warning When electrical equipment is in operation dangerous voltage will be present in certain parts of the equipment. Failure to observe warning notices, incorrect use or improper use may endanger personnel and equipment and cause personal injury or physical damage. Before working in the terminal strip area, the device must be isolated. Where stranded conductors are used, wire end ferrules must be employed. Proper and safe operation of this device depends on appropriate shipping and handling, proper storage, installation and commissioning, and on careful operation, maintenance and servicing. For this reason only qualified personnel may work on or operate this device. For this reason only qualified personnel familiar with the content of the Safety Guide (SFTY/4LM/B11 or later version) may work on or operate this device. Any modifications to this device must be in accordance with the manual. If any other modification is made without the express permission of AREVA T&D, it will invalidate the warranty, and may render the product unsafe.
Qualified Personnel are individuals who are familiar with the installation, commissioning and operation of the device and of the system to which it is being connected; are able to perform switching operations in accordance with safety engineering standards and are authorized to energize and de-energize equipment and to isolate, ground and label it; are trained in the care and use of safety apparatus in accordance with safety engineering standards; are trained in emergency procedures (first aid).
Note The operating manual for this device gives instructions for its installation, commissioning and operation. However, the manual cannot cover all conceivable circumstances or include detailed information on all topics. In the event of questions or specific problems, do not take any action without proper authorization. Contact the appropriate AREVA technical sales office and request the necessary information. Any agreements, commitments, and legal relationships and any obligations on the part of AREVA, including settlement of warranties, result solely from the applicable purchase contract, which is not affected by the contents of the operating manual.
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
Stückprüfbescheinigung P632 Routine Test Certificate P632
AREVA Energietechnik GmbH ist ein DQS zertifiziertes Unternehmen. Fertigung und Prüfung der Schutzeinrichtungen erfüllen die Anforderungen von DIN EN ISO 9001. AREVA Energietechnik GmbH has been awarded the DQS certificate by the internationally recognized, independent and impartial association for the certification of quality assurance systems, DQS (Deutsche Gesellschaft zur Zertifizierung von Qualitätssicherungssystemen), thereby certifying that ALSTOM has introduced and uses a state-of-the-art quality assurance system that complies with all requirements stated in EN ISO 9001 that apply to its products and services.
Stückprüfung Routine Test
Alle Prüfungen nach IEC 255-6 und DIN EN 60255-6. All tests according to IEC 255-6 and EN 60255-6.
Die folgenden Überprüfungen waren Gegenstand der Stückprüfung bei Referenzbedingungen: The following tests have been carried out as part of the routine test under reference conditions:
1 Übereinstimmung der Schutzeinrichtung mit Bestückungs- und Anschlußplan Conformity of the protection device with components list, location diagram and terminal connection diagram
2 Isolationsprüfung Insulation test
3 Stromversorgung im Bereich 0,8 UH,nom ≤ UH,nom ≤ 1,1 UH,nom Power supply within the range 0.8 VA,nom ≤ VA,nom ≤ 1.1 VA,nom
4 Prüfung der Genauigkeit der Einstellwerte Accuracy of the setting values
5 Ansprech- und Kommandozeiten für alle wesentlichen Funktionen Operate and command times for all essential functions
6 Funktionsprüfung aller binären Signaleingänge und Kontakte Functional testing of all binary signal inputs and contacts
7 100 % kontrollierter Wärmedauerlauf 100 % controlled thermal endurance test
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
Modifications After Going to Press
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
Contents
1
Order Information
10
2
Modifications
11
3 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9 3.10
Dimensional Drawings Surface-Mounting Case 40 T Flush-Mounting Case 40 T Flush-Mounting Case 84 T PE Terminal Panel Cutout for Case 40 T Panel Cutout for Case 84 T Case 40 T, Flush-Mounted Case 84 T, Flush-Mounted Combining 40 T Cases to Form a 19“ Mounting Rack Fitting a 19” Mounting Rack into a Cabinet
12 12 13 15 17 18 20 22 24 26 27
4 4.1 4.2 4.3
Location Diagrams Case 40 T, Pin-terminal Connection Case 84 T, Ring-terminal Connection Ethernet Module
28 28 29 30
5 5.1 5.2 5.3
Terminal Connection Diagrams Case 40 T, Pin-terminal Connection Case 84 T, Ring-terminal Connection Ethernet Module
31 31 37 43
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
9
1 Order Information
1 Order Information MiCOM P632 Name
Order number
Two Winding Transformer Diff. Prot.
P632-
9
0
1
-304
-4xx
-606
-46x
-9x x -95 x
-8xx
Basic device: Basic device 40TE, pin-terminal connection,
3
-403
Basic device 84TE, ring-terminal connection,
8
-404
basic complement with 4 binary inputs and 8 output relays Mounting option and display: Surface-mounted, local control panel with text display
3
Flush-mounted, local control panel with text display
4
Processor extension and Current transformer: With DSP-Coprocessor, Inom = 1 A / 5 A (T11...T13 / T21...23) Inom = 1 A / 5 A (T11...T14 / T21...24) Voltage transformer:
2)
8 9
2)
Vnom = 50 ... 130 V (1-pole)
1
Additional binary I/O options: Without
0
With 1 binary module (add. 6 binary inputs and 8 output relays)
1
Power supply and additional outputs: VA,nom = 24 VDC
3
VA,nom = 48 ... 250 VDC / 100 ... 230 VAC
4
VA,nom = 24 VDC and 6 output relays, 4 with thyristor
6
VA,nom = 48 ... 250 VDC / 100 ... 230 VAC
7
and 6 output relays, 4 with thyristor VA,nom = 24 VDC and 6 output relays
8
VA,nom = 48 ... 250 VDC / 100 ... 230 VAC and 6 output relays
9
Further add. options: Without
0
With analogue module
2
With binary module (add. 24 binary inputs)
4
Switching threshold on binary inputs: >18 V (standard variant)
(Without order extension no.)
>90 V (60...70% of VA,nom = 125...150 V)
>155 V (60...70% of VA,nom = 220...250 V) >73 V (67% of VA,nom = 110 V)
-461
8)
-462
8)
-463
8)
-464
8)
>146 V (67% of VA,nom = 220 V) With communication / information interface: Only IRIG-B input for clock synchronization
-90 0
Protocol IEC 60870-5-103
-91
Protocol can be switched between:
-92
IEC 60870-5-101/-103, Modbus, DNP3, Courier and IRIG-B input for clock synchronization and 2nd interface (RS485, IEC 60870-5-103) For connection to wire, RS485, isolated
1
For connection to plastic fibre, FSMA connector
2
For connection to glass fibre, ST connector
4
Protocol UCA2
-93
For connection to 10 MHz Ethernet, glass fibre ST and wire RJ45
5
and 2nd interface (RS485, IEC 60870-5-103) For connection to 100 MHz Ethernet, glass fibre SC and wire RJ45
6
and 2nd interface (RS485, IEC 60870-5-103) Language: English (German) German (English) French (English)
4)
(On request)
-800
(On request)
-802
(On request)
-803
(On request)
-804
(On request)
-805
-801
4)
4)
Spanish (English) Polish (English)
(Without order extension no.)
4)
Px40 English (English)
4)
4) 4) 7)
Russian (English) 2) Switching via parameter, default setting is underlined! 4) Second included language in brackets
7) Hardware option, supports cyrillic letters instead of special West. Europe characters 8) Standard variant recommended, if higher pickup threshold not explicitly required by the application
10
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
2 Modifications
2 Modifications The following area is reserved for documentation of design version modifications of this device, e.g. add-ons, by the factory or the user. It contains information on modification date and modifying person.
Modification
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
Name
Date
11
3 Dimensional Drawings
3 Dimensional Drawings 3.1 Surface-Mounted Case 40 T
1
12
Dimensional drawing for surface-mounted case 40 T (dimensions in mm)
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
3 Dimensional Drawings (continued)
3.2 Flush-Mounted Case 40 T
2
Dimensional drawing for flush-mounted case 40 T, flush-mount method 1 (without angle brackets and frame)
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
(dimensions in mm)
13
3 Dimensional Drawings (continued)
3
14
Dimensional drawing for flush-mounted case 40 T, flush-mount method 2 (using the angle brackets and frame)
(dimensions in mm)
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
3 Dimensional Drawings (continued)
3.3 Flush-Mounted Case 84 T
4
Dimensional drawing for flush-mounted case 84 T, flush-mount method 1 (without angle brackets and frame)
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
(dimensions in mm)
15
3 Dimensional Drawings (continued)
5
16
Dimensional drawing for flush-mounted case 84 T, flush-mount method 2 (using the angle brackets and frame)
(dimensions in mm)
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
3 Dimensional Drawings (continued)
3.4 Protective Conductor Terminal (PCT) / Case Grounding / Protective Earth Terminal
19Y5220A_EN
6
Mounting the PCT / Mounting set for case grounding PCT: Protective Conductor Terminal, formerly "Protective Earth Terminal" The clamp bracket is marked with a PCT symbol:
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
17
3 Dimensional Drawings (continued)
3.5 Panel Cutout for Case 40 T
7
18
Dimensional drawing of panel cutout for case 40 T, flush-mount method 1 (without angle brackets and frame) (dimensions in mm)
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
3 Dimensional Drawings (continued)
8
Dimensional drawing of panel cutout for case 40 T, flush-mount method 2 (using the angle brackets and frame) (dimensions in mm)
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
19
3 Dimensional Drawings (continued)
3.6 Panel Cutout for Case 84 T
9
20
Dimensional drawing of panel cutout for case 84 T, flush-mount method 1 (without angle brackets and frame) (dimensions in mm)
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
3 Dimensional Drawings (continued)
10
Dimensional drawing of panel cutout for case 84 T, flush-mount method 2 (using the angle brackets and frame) (dimensions in mm)
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
21
3 Dimensional Drawings (continued)
3.7 Case 40 T, Flush-Mounted
11
Installation of case 40 T for flush-mounting, flush-mount method 1 (without angle brackets and frame) Protective Conductor Terminal (PCT) / Case Grounding / Protective Earth Terminal: See Chapter 3.4
22
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
3 Dimensional Drawings (continued)
12
Installation of case 40 T for flush-mounting, flush-mount method 2 (using the angle brackets and frame) Protective Conductor Terminal (PCT) / Case Grounding / Protective Earth Terminal: See Chapter 3.4
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
23
3 Dimensional Drawings (continued)
3.8 Case 84 T, Flush-Mounted
13
Installation of case 84 T for flush-mounting, flush-mount method 1 (without angle brackets and frame) Protective Conductor Terminal (PCT) / Case Grounding / Protective Earth Terminal: See Chapter 3.4
24
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
3 Dimensional Drawings (continued)
14
Installation of case 84 T for flush-mounting, flush-mount method 2 (using the angle brackets and frame) Protective Conductor Terminal (PCT) / Case Grounding / Protective Earth Terminal: See Chapter 3.4
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
25
3 Dimensional Drawings (continued)
3.9 Combining 40 T Cases to Form a 19” Mounting Rack
15
Combining 40 T flush-mounting cases to form a 19” mounting rack Protective Conductor Terminal (PCT) / Case Grounding / Protective Earth Terminal: See Chapter 3.4
26
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
3 Dimensional Drawings (continued)
3.10 Fitting a 19” Mounting Rack into a Cabinet
16
Fitting a 19” mounting rack Protective Conductor Terminal (PCT) / Case Grounding / Protective Earth Terminal: See Chapter 3.4
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
27
4 Location Diagrams
4 Location Diagrams 4.1 Case 40 T, Pin-terminal Connection
17
Location diagram P632 in case 40 T, pin-terminal connection Location diagram of the Ethernet module see Chapter 4.3
28
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
4 Location Diagrams (Fortsetzung)
4.2 Case 84 T, Ring-terminal Connection
18
Location diagram P632 in case 84 T, ring-terminal connection Location diagram of the Ethernet module see Chapter 4.3
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
29
4 Location Diagrams (continued)
4.3 Ethernet Module
02
-X8 *
-X12
-X13 *
-X7 *
-X10
01
Type A * 01
02 : Alternative module
*
(see order information)
Type
Designation
A
Communication module
Slot
Item
02
-U17; -U18; -U20; -U25; -U26
Px3x_Ethernet_01A_EN
19
30
Location diagram of the Ethernet module applicable to: Case 40 T, pin-terminal connection Case 84 T, ring-terminal connection
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
5 Terminal Connection Diagrams
5 Terminal Connection Diagrams 5.1 Case 40 T, Pin-terminal Connection
20
Terminal connection diagram P632 in case 40 T, pin-terminal connection, diagram P632.403, part 1 of 6
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
31
5 Terminal Connection Diagrams (continued)
21
32
Terminal connection diagram P632 in case 40 T, pin-terminal connection, diagram P632.403, part 2 of 6
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
5 Terminal Connection Diagrams (continued)
22
Terminal connection diagram P632 in case 40 T, pin-terminal connection, diagram P632.403, part 3 of 6
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
33
5 Terminal Connection Diagrams (continued)
23
34
Terminal connection diagram P632 in case 40 T, pin-terminal connection, diagram P632.403, part 4 of 6
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
5 Terminal Connection Diagrams (continued)
24
Terminal connection diagram P632 in case 40 T, pin-terminal connection, diagram P632.403, part 5 of 6
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
35
5 Terminal Connection Diagrams (continued)
25
36
Terminal connection diagram P632 in case 40 T, pin-terminal connection, diagram P632.403, part 6 of 6 Terminal connection diagram of the Ethernet module see chapter 5.3
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
5 Terminal Connection Diagrams (continued)
5.2 Case 84 T, Ring-terminal Connection
26
Terminal connection diagram P632 in case 84 T, ring-terminal connection, diagram P632.404, part 1 of 6
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
37
5 Terminal Connection Diagrams (continued)
27
38
Terminal connection diagram P632 in case 84 T, ring-terminal connection, diagram P632.404, part 2 of 6
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
5 Terminal Connection Diagrams (continued)
28
Terminal connection diagram P632 in case 84 T, ring-terminal connection, diagram P632.404, part 3 of 6
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
39
5 Terminal Connection Diagrams (continued)
29
40
Terminal connection diagram P632 in case 84 T, ring-terminal connection, diagram P632.404, part 4 of 6
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
5 Terminal Connection Diagrams (continued)
30
Terminal connection diagram P632 in case 84 T, ring-terminal connection, diagram P632.404, part 5 of 6
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
41
5 Terminal Connection Diagrams (continued)
31
42
Terminal connection diagram P632 in case 84 T, ring-terminal connection, diagram P632.404, part 6 of 6 Terminal connection diagram of the Ethernet module see chapter 5.3
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
5 Terminal Connection Diagrams (continued)
5.3 Ethernet Module
+
ITEM DESIGN.
-
CONNECTOR
-X7
MEANING
ITEM REFER. STATUS
LOCATION
REFER.
*
Comm. fiber interface Ethernet (10 Base - FL)
RX
X/Y
-U17
X/Y
-U18
X/Y
-U26
ST
+
ITEM DESIGN.
-
CONNECTOR
-X8
MEANING
ITEM REFER. STATUS
LOCATION
REFER.
*
Comm. fiber interface Ethernet (10 Base - FL)
TX ST
+
ITEM DESIGN.
-
CONNECTOR
-X13
MEANING
ITEM REFER. STATUS
LOCATION
REFER.
*
Comm. fiber interface Ethernet (100 Base - FX)
RX TX SC
+
ITEM DESIGN.
-
CONNECTOR
-X12
MEANING
ITEM REFER. STATUS
LOCATION
REFER.
*
Comm. interface Ethernet (10 Base T / 100 Base TX)
1
X // Y
-U25
RJ45
+
ITEM DESIGN.
-
CONNECTOR
-X10
MEANING Comm. interface Channel 2
ITEM REFER. STATUS
LOCATION
REFER.
X // Y
* 1
-
2
+
D2[R]
3
-U20
4
-
5
+
D1[T]
RS 485
*
: Alternative module (see order inform.)
Px3x_Ethernet_02A_EN
32
Terminal connection diagram of the Ethernet module applicable to: Case 40 T, pin-terminal connection, diagram P632.403 Case 84 T, ring-terminal connection, diagram P632.404
P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN
43
Publication: P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN