Download approved_construction_details_uk...
CI/SfB (47)
Nh2
Nov 2002
Approved Construction Details for Part L2 (England and Wales) and Part J (Scotland) Building Regulations & Standards for Conservation of Fuel & Power (Non-Domestic Buildings)
Insurer Approved Systems
2
Contents
Building Regulations Com
Building Regulations Compliance in 7 steps
2
Parts L2 and J Project Design, Specification, Construct ion, Testing & Handover Compliance Checklist
4
Building Regulations 2000 Part L2
6
Conservation of Fuel & Power (England & Wales)
Building Regulations 2000 Part L2
7
Elemental Method Kingspan Roof & Wall Solutions
a. Reduced heat loss by improved U-values and limits on thermal bridging. b. Limit on air leakage for building envelope. c. Measures to quantify the risk of condensation. d. Certificate or declaration by a suitably qualified competent person(s) that the as-built roof and walls comply with the requirements of Part L2. Architects and designers now need to take an integrated and holistic design approach to achieve regulatory compliance.
STEP 1 - DESIGN
Building Standards 1990 Part J
8
6th Amendments: Conservation of Fuel & Power (Scotland)
Building Standards 1990 Part J
Part L2: 2002 Conservation of Energy includes four major changes to traditional insulated metal roofing and cladding.
9
The design will need to be based on a complete integrated system solution for roof and/or wall cladding. Kingspan can provide construction solutions and details to achieve regulatory compliance with U-values, thermal bridging, air leakage and insulation continuity to the approved standard suitable for the intended use of the building e.g. industrial, office, swimming pool, etc.
Elemental Method Kingspan Roof & Wall Solutions
Building Heating Loss through Thermal Bridging
10
Thermal Bridging & Heat Loss Calculation Example
12
Air Leakage Risk Areas
14
Standard Construction Details
16
Enhanced Construction Details
50
Two sets of details have been produced to give the Building Designer flexibility within the calculation for the total building heat loss. The decision on the choice of standard or enhanced details is taken by the Building Designer and is determined from the total building heat loss methodology demonstrated on pages 10 & 11 of this guide. A mixture of both standard and enhanced details maybe required for some projects.
STEP 2 - BUILDING CONTROL APPLICATIONS Architects or designers have to calculate the a-value (alpha) for the building envelope to achieve compliance of a equal to or less than 0.10 or demonstrate compliance via the alternative trade off route. In order to make the a calculation, the architects or designers as competent person(s) will most likely need the assistance of the envelope system manufacturer to provide f and Y values for the roof and wall cladding design. Any changes to specification of the cladding after the a-value is calculated will mean that the value has to be recalculated. If the a-value is too high the design and/or products will have to be amended to achieve compliance.
STEP 3 - TENDER The architects or designers have to specify roof and wall cladding systems which can achieve compliance with the requirement to minimise heat loss at all junctions or thermal bridges. Detailed drawings should be provided for each part of the roof and wall system, including all junctions, penetrations, abutments, internal gutters, smoke vents, louvres, soakers, doors, windows, rooflights, curtain walling, brickwork and floor slab edge etc. Kingspan as a roof and wall system manufacturer provide a comprehensive package of details for which the f, Y and air leakage seals have been optimised for differing building uses.
3
pliance in 7 Steps STEP 4 - CONSTRUCTION The duties of competent person(s) may be carried out by the developer/main contractor from step 4 onwards. The competent person(s) will be responsible for ensuring that the approved design is built and that workmanship quality also achieves compliance. Should alternative roof and wall systems or products be substituted to that specified it is necessary that they are fully regulatory compliant. Kingspan’s construction details have been designed to be installer friendly and robust so that a high level of workmanship quality can be achieved combined with fast installation speed.
STEP 7 - CONTINUITY OF INSULATION Provide a declaration that appropriate design and installation has been carried out to achieve reasonable conformity. Alternatively carry out a thermographic survey by competent person to demonstrate that the insulation is reasonably continuous over the visible envelope of the building and that excessive thermal bridging is avoided. Note: Building Control should be asked to confirm in advance who they consider is competent to complete the various declarations required before the completion certificate is issued.
Failure to achieve regulatory compliance will result in project handover delays and subsequent rectification costs.
KINGSPAN PARTS L2 & J SERVICE AND TOOLKIT Construction Solutions Service
• Industry
awareness and education programme for property investors, agents/advisers, design teams, constructors, installers and building control.
• Project specific roof and wall system solutions and construction details for designers, contractors and installers.
STEP 5 - INSPECTION & TESTING Materials being installed and workmanship quality will need to be checked during construction so that the competent person(s) can provide the required certificate or declaration following air pressurisation testing and thermographic inspection survey.
• Contractor and site installer training programme. • Specialist site service support. • Independent design - construction, air leakage testing and infra-red service available through alliance with Building Sciences Ltd. Toolkit
STEP 6 - AIR TIGHTNESS TESTING On buildings of any size, an air leakage test has to be carried out to provide a declaration from a competent person(s) that the test result demonstrates regulatory compliance. Alternatively for buildings of less than 1000m2 floor area a declaration that appropriate design and installation has been carried out to achieve conformity to specification for regulatory compliance.
For further information contact our Technical Services Department on: Hotline: 01352 716101 or Email:
[email protected] All construction details are available in AutoCAD and DXF format from the Kingspan website.
www.kingspanpanels.com
4
Parts L2 and J Project Design, Specification, Construct PARTS L2 & J ELEMENTAL METHOD REQUIREMENTS U-Value Requirements (W/m2K) Part L2 (England & Wales) Roofs Walls Rooflights Max 20% Area Max 12% Area*
Part J (Scotland)
PRE-TENDER SPECIFICATION
DESIGN 1
Calculation by Elemental method.
2
Select type of roof and wall systems.
• Roof products - Type and reference.
3
Select U-Value requirements.
• Wall products - Type and reference.
1
Specify selected roof and wall system
0.25 0.35
0.25 0.30
2.20 3.00
2.20 3.00
4
Determine insulation continuity integrity.
• U-Value requirements.
* Rooflights may be permitted up to 12% of roof area at 3.0W/m2K however, there is significant risk of condensation.
5
Determine solar gain and rooflight requirements.
• Thermal and insulation continuity requirements.
6
Determine cold bridges and heat loss risk areas.
Part L2 Additional Calculation Requirements
• Calculation to assess risk of surface mould growth and condensation introduced Surface Temperature f-factor. Internal humidity classes and the minimum temperature factor necessary to prevent condensation.
7
8
Table A Humidity Class Building Type 1 2 3 4
5
Minimum f value
Storage areas Offices & shops Dwellings with low occupancy Dwellings with high occupancy, sports halls, kitchens, canteens; buildings heated with un-flued gas heaters Special buildings, e.g. laundries breweries, swimming pools
Determine airtightness standard (Part L2 only). Develop compliant designs and details for envelope joints, junctions, internal gutters, penetrations, rooflights and abutment details.
• Solar gain and rooflight requirements. • Air tightness requirement (Part L2 only). 2
Specify ancillary components i.e. doors, windows, rooflights, gutters, smoke vents, louvres and soakers etc.
3
Specify f-factor and Y-values for all junctions, penetrations, abutments, internal gutters and provide project specific design solutions, construction details and specifications.
0.30 0.50 0.65 0.80
9
0.90
10 Calculate Y-values for envelope system and details indicated in 8 above.
4
Indicate whole building’s a-value for specified envelope system.
11 Calculate whole building’s a-value and check this is within the limits for building use (see Table B).
5
Specify lifecycle durability requirements.
6
Agree with building control body that the design and specification complies with Part L2 or J requirements and that the person providing certificates or declarations for insulation standards/continuity, air tightness and testing is suitably qualified and competent.
7
Incorporate compliant design(s) and specification(s) into employer’s tender package.
The BS EN 13788 methodology leads to the temperature factors necessary to avoid condensation shown in the table above.
• Calculation to establish extent of heat losses through thermal bridges at details - Y Value (psi). • Calculation to assess total heat loss through all thermal bridges a-value must not exceed limits stated in BRE Information Paper 17/01. Table B a-value must be less than or equal to: 0.16 domestic buildings 0.10 non-domestic buildings
Part L2 Completed Building Compliance Testing Air Leakage Testing Requirements
• Maximum air leakage rate up to 30 September 2003 is 11.5m3/hr/m2 @ 50PA • Maximum air leakage rate from 1 October 2003 is 10m3/hr/m2 @ 50PA Infra-Red Thermographic Surveys • Infra-red thermographic report confirming that insulation “is reasonably continuous over the whole visible envelope”. where required.
Calculate f-factor value for intended building use (see Table A) and details indicated in 8 above.
12 Determine lifecycle durability warranties. • • • •
U-Value and insulant integrity Airtightness level External coatings Structural performance
13 Determine design parameters for heating, ventilation and HVAC system and subsequent energy usage levels and operating costs.
5
ion, Testing & Handover Compliance Checklist MAIN OR DESIGN - BUILD CONTRACTORS 1
Obtain from employer or employer agent(s) project specific Part L2 or J envelope compliant pre-tender package which includes: • U-values, insulation continuity integrity, cold bridges and heat loss solutions.
ROOFING & CLADDING CONTRACTORS 1
• Roof products - Type and reference.
• Airtightness standard (Part L2 only).
• Wall products - Type and reference.
• Solar gain and rooflight requirements.
• U-values.
• Calculated f-factor and Y-values for all junctions, penetrations, abutments, internal gutters and approved design and construction details (Part L2 only).
• Insulation/thermal continuity solutions. • Solar gain and rooflight requirements. • Airtightness requirement (Part L2 only) and sealing methods.
• Calculated whole building’s a-value (Part L2 only).
• f-factor and Y-values for junctions, penetrations, abutments, internal gutters, smoke vents, louvres and soakers etc.
• Parts L2 or J compliant solutions for doors, windows, rooflights, smoke vents, louvres, soakers, brickwork, curtain walling, floor slab and other elements.
• Whole building’s envelope a-value. • Specified doors, windows, rooflights, internal gutters, smoke vents, penetrations, soakers, curtain walling, brickwork and floor slab edge systems/solutions and details.
• Windows, doors and other openings maybe treated as adiabatic junctions. 2
Plan airtightness testing (Part L2 only).
3
No infra-red thermographic testing is required with Kingspan roof and wall systems as insulation continuity is guaranteed within the panels.
4
Agree with building control body prior to work starting suitably qualified competent person(s) who can audit and verify design, sub-contractor’s workmanship quality and give certificates or declarations for insulation/thermal continuity and airtightness testing (Part L2 only).
5
Select tender list from suitably qualified roofing and cladding contractor’s .
6
Audit returned bids for Parts L2 or J compliance prior to contract award.
7
Alternatively Establish own project specific Part L2 or J compliant design and specification pre-tender package in conjunction with a suitably qualified competent person(s).
Obtain from employer or employer agent(s) Part L2 or J compliant design and envelope specification package including:
PROJECT APPROVAL, TESTING & HANDOVER 1 All Buildings Suitably qualified competent person(s) to prepare written report confirming design, specification and site workmanship quality compliance with regard to U-Values, insulation continuity, limiting thermal bridges and air leakage. 2 Buildings larger than 1,000m2 floor area Airtightness test (Part L2 only) in accordance with CIBSE TM 23, the whole building envelope has a maximum air leakage rate of 10m3/hr/m2 @ 50 Pa. Note: Until 30 September 2003 reasonable provision in the event that initial airtightness test results are unsatisfactory would be the results of further tests carried out after appropriate remedial work showing:an improvement of 75% of the difference between the initial test result and the target standard of 10m3/hr/m2 @ 50 Pa; or, if less demanding a performance no worse than 11.5m3/hr/m2 @ 50 Pa.
3 A suitably qualified person(s) to issue a certificate or declaration that appropriate design details and building techniques have been used and that the work has been carried out in ways that can be expected to achieve reasonable conformity with the specifications that have been approved for the purpose of compliance with Part L2.
2
Any change to selected or specified system or product will alter system compliance. Assess and verify alternative systems/solutions for compliance.
3
Agree method of compliance with suitably qualified competent person(s) appointed by main contractor. Obtain details of airtightness testing (Part L2 only), insulation continuity and infra-red thermographic surveys where appropriate.
4
Agree lifecycle durability warranty package.
5
Provide site installation team(s) with project specific construction assembly specifications, details and instructions/ training to achieve Parts L2 and J compliant site workmanship quality standards.
6
Agree site supervision and workmanship quality control audit requirements.
6 Building log-book - the owner and/or occupier of the building to be provided with a log-book giving details of the installed building services plant and controls, their method of operation and maintenance and other details that collectively enable energy consumption to be monitored and controlled.
7
Alternatively Establish own project specific Part L2 or J compliant design and specification pre-tender package in conjunction with a suitably qualified competent person(s).
7 Buildings less than 1,000m2 floor area Air leakage testing is not compulsory on buildings below 1000m2 floor area provided that a suitably qualified competent person(s) issues the required certificates or declarations.
Alternatively an infra-red thermographic survey of completed building envelope to show that the insulation is reasonably continuous over the whole building envelope by a competent person in accordance with BRE Report 176 and BS EN 13187.
4 CDM - Health and Safety File for the building including COSHH data sheets for products incorporated in building and copies of maintenance recommendations plus guarantee certificates. 5 Written report on commissioning of all HVAC plant and controls by a suitably qualified competent person(s).
6
Building Regulations 2000 Part L2 Conservation of Fuel & Power (England & Wales) Part L2 Compliance Requirements Effective from 1st April 2002 (U-Value W/m2K)
Standard U-Values of Construction Elements
• Flat roof (not exceeding 10˚) or roof with integral insulation • Walls, including basement walls • Floors, including ground floors and basement floors • Windows, roof windows and personnel doors (area weighted average
0.25 0.35 0.25 2.20
for the whole building), glazing in metal frames
3
• Windows, roof windows and personnel doors (area weighted average
2.00
for the whole building), glazing in wood or PVC frames3
• Rooflights • Vehicle and similar large doors
2.20
4,5
0.70
Notes to table: 1. Any part of a roof having a pitch greater or equal to 70° can be considered as a wall. 2. For the sloping parts of a room-in-the-roof constructed as a material alteration, a U-value of 0.30W/m2K would be reasonable. 3. Display windows, shop entrance doors and similar glazing are not required to meet the standard given in this table. 4. This standard applies only to the performance of the unit excluding any upstand. Reasonable provision would be to insulate any upstand, or otherwise isolate it from the internal environment. 5. For the purposes of Approved Document L2, a roof window may be considered as a rooflight.
Standard U-Values (W/m2K) for Insulated Metal Roof & Wall Cladding Systems – Elemental Method Part L2 Boundary Wall & Valley Gutters 0.25
Rooflights 2.20d
Roofs 0.25
(For pre melt c applications 0.35)
Overhanging Eaves or Soffits 0.35
External Side Walls 0.35
Windows & Personnel Doors 2.00a/2.20b
(When soffits are part of a floor 0.25)
Floors 0.25
Vehicle - Large Doors 0.70
Notes: a. If windows have wood or PVC frames. b. If windows have metal frames. c. For pre melt gutter specifications obtain building control approval at design stage. d. Rooflights may be permitted up to 12% of roof area at 3.0W/m2K by using the ‘Whole building’ or ‘Carbon emission’ method of calculation, however, there is a significant risk of condensation.
7
Elemental Method - Kingspan Roof & Wall Solutions Approved Document L2 Compliance – Kingspan Roof and Wall Systems – CFC Free Roof Systems – U-Values
Product
Thickness
Air Leakage*
Flat roof or roof with integral insulation 0.25 W/m2K
KS1000 RW - TS
80mm (0.25 W/m K)
5m3/h/m2
KS1000 LP - CR
80mm (0.25 W/m2K)
5m3/h/m2
KS500/1000 ZIP Kingzip
90mm (0.25 W/m K)
5m3/h/m2
2
2
Rooflights 2.20 W/m2K
Wall Systems – U-Values 2
5m3/h/m2
Product
Thickness
Air Leakage* 2
0.35 W/m K
KS600/900/1000 - MR/EB/FL-S/WV/CX/MM
70mm (0.35 W/m K)
5m3/h/m2
0.35 W/m2K
KS900/1000 Optimo
70mm (0.35 W/m2K)
5m3/h/m2
0.35 W/m2K
KS1000 RW
60mm (0.35 W/m2K)
5m3/h/m2
Notes: *To achieve a building air leakage performance of 10m3/h/m2 @ 50 Pa, the air leakage performance of the roof/wall system has to be lower to allow for leakage at openings/junctions. Air leakage solutions are available for 2m3/h/m2, consult Kingspan Technical Services Department.
8
Building Standards 1990 Part J 6th Amendments: Conservation of Fuel & Power (Scotland) Part J Compliance Requirements Effective from 4th March 2002 Maximum U-Values of Exposed Building Elements when using the Elemental Method (Note1) Maximum U-Value (W/m2K)
Exposed Building Element
• Roof (all roof slopes) • External Wall (Note 2) • Floor • Windows, personnel doors and rooflights (area weighted
0.25 0.30 0.25 2.20
average for the whole building) (Note 3), glazing in metal frames (Note 4)
• Windows, personnel doors and rooflights (area weighted
2.00
average for the whole building) (Note 3), glazing in wood or PVC frames
• Vehicle access and similar large doors (Note 5)
0.70
Notes to table: 1. When an element is exposed to the outside via an unheated space, the unheated space may be disregarded or the U-value of the element calculated using BS EN ISO 13789: 1999. 2. Solid area of element only (i.e. excluding windows, doors and rooflights). 3. For method of calculation, see Appendix E. 4. Metal framed windows have slimmer frames and therefore provide a passive solar benefit, justifying a less onerous U-value standard. 5. No requirement where for operational reasons doors have to be left open when building is in use.
Standard U-Values (W/m2K) for Insulated Metal Roof & Wall Cladding Systems – Elemental Method Part J Boundary Wall & Valley Gutters 0.25
Rooflights 2.20d
Roofs 0.25
(For pre melt c applications 0.35)
Overhanging Eaves or Soffits 0.30
External Side Walls 0.30
Windows & Personnel Doors 2.00a/2.20b
(When soffits are part of a floor 0.25)
Floors 0.25
Vehicle - Large Doors 0.70
Notes: a. Windows, personnel doors and rooflights (area weighted average for the whole building), glazing in wood or PVC frames. b. Windows, personnel doors and rooflights (area weighted average for the whole building), glazing in metal frames. c. For pre melt gutter specifications obtain building control approval at design stage. d. Rooflights may be permitted up to 12% of roof area at 3.0W/m2K, by using the ‘Whole building’ or ‘Carbon emission’ method of calculation, however, there is a significant risk of condensation.
9
Elemental Method - Kingspan Roof & Wall Solutions Part J Standards Compliance – Kingspan Roof and Wall Systems – CFC Free Roof Systems – U-Values
Product
Thickness
KS1000 RW - TS
80mm (0.25 W/m2K)
KS1000 LP - CR
80mm (0.25 W/m2K)
KS500/1000 ZIP Kingzip
90mm (0.25 W/m2K)
Product
Thickness
0.30 W/m K
KS600/900/1000 - MR/EB/FL-S/WV/CX/MM
80mm (0.30 W/m2K)
0.30 W/m2K
KS900/1000 Optimo
80mm (0.30 W/m2K)
0.30 W/m2K
KS1000 RW
70mm (0.30 W/m2K)
2
0.25 W/m K
Rooflights 2.20 W/m2K
Wall Systems – U-Values 2
10
Building Heating Loss through Thermal Bridging Introduction The Amendments to Part L2 of the Building Regulations 2000 came into force on 1st April 2002. The amendments require that thermal bridges at junctions and around openings be minimised (Items 1.9). Two means of meeting this requirement are described. The first (Item 1.10) requires the use of standard robust “details and practices independently demonstrated as being satisfactory.” This option primarily applies to domestic type constructions. The second option (Item 1.11) is to prove compliance by calculation in accordance with BRE Information Paper IP 17/01 for which MCRMA Technical Report No 14 provides specific guidance for profiled metal roofing and cladding. Means of Proving Compliance A methodology for proving that an acceptable level of heat loss through thermal bridging in buildings has been achieved is contained within MCRMA Technical Paper 14. The methodology is based upon BRE Information Paper IP 17/01 – Assessing the Effects of Thermal Bridges at Junctions and Around Openings. The basic procedure for proving compliance is best shown using a typical worked example:
6m 60m 40m
STEP 2 The linear meterage of thermal bridge junctions within the external envelope of the building is then measured/calculated. These junctions include window/door jambs, eaves details, corner details, cill details etc. The linear meterage of each junction is then multiplied by a calculated Y value (measurement of linear thermal transmittance) for that specific junction. This provides the total heat loss through each junction type for the building. The losses for each junction are then added together to give the total heat loss through thermal bridge junctions within the building (Total B).
A Ridge 120.00 0.01 B Eaves 120.00 0.31 C Verge 80.00 1.01 D Valley Gutter 60.00 1.38 E1 Cladding Drip 195.00 0.86 E2 Ground Floor 195.00 0.16 F Corner 24.00 0.18 0.97 G1 Cladding Window or personnel door head 34.00 G2 Window Frame Head 30.00 0.04 G3 Personnel Door Head 4.00 0.04 H1 Cladding Window Sill 30.00 0.48 H2 Window Frame Sill 30.00 0.04 I1 Window & Personnel Door Jambs 20.00 0.80 I2 Window Frame Jambs 4.00 0.04 I3 Personnel Door Jambs 16.00 0.04 J1 Cladding Head to Vehicle Bay Door 4.00 0.68 J2 Vehicle Unloading Bay Door Head 4.00 0.04 K1 Cladding Jamb to Vehicle Bay Door 8.00 1.70 K2 Vehicle Unloading Bay Door Jambs 8.00 0.04 Total Heat Loss (B) =
The calculation process which should be followed is as follows:
STEP 1 The total heat loss through each plane element in the external envelope (including the floor) of the building is calculated by multiplying the U-value of each element by the total square meterage (m2) of that element within the building. The heat loss for each element is then added together to provide the total heat loss for the plane elements of the building (Total A).
Length Y-value (m) (W/mK)
Detail Junction
Heat Loss 1.20 37.20 80.80 82.80 167.70 31.20 4.32 32.98 1.20 0.16 14.40 1.20 16.00 0.16 0.64 2.72 0.16 13.60 0.32 488.76
STEP 3 To achieve compliance, the total heat loss for the thermal bridge junctions (Total B) should be equal to or less than 10% of the total heat loss through the plane elements of the building (Total A). i.e Heat loss through thermal bridging (Total B) = must be less than 0.1 Heat loss through the plane elements (Total A) For the example above:
Example Building Element Total Roof Area Roof Rooflights (10%) Total Wall Area Exposed Walls Windows & Personnel Doors Vehicle Unloading Bay Doors Ground Floor
Area (m2)
U-value (W/m2K)
Heat Loss
2647.00 2382.30 0.25 595.58 264.70 2.20 582.34 1194.80 1164.80 0.35 407.68 14.00 2.00 28.00 16.00 0.70 11.20 2400.00 0.25 600.00 Total Heat Loss (A) = 2224.80
488.76 (Total B) 2224.8 (Total A)
= 0.22
Therefore the example building has failed to comply through this route as the total heat loss through the thermal bridges equals 22% of the total heat loss through the plain elements. If a building fails to comply two options exist:
11
Building Heating Loss through Thermal Bridging 1. Improvements can be made to the junction details to reduce the levels of heat losses until the 10% threshold is achieved. In some instances it may not be possible or economically viable to minimise the total additional heat losses through the thermal bridges to this level. This may be particularly true with some specific building uses (e.g. Warehouses or Industrial Units) and/or junction detail configurations. 2. Follow the alternative permitted means of compliance outlined below. Alternative Means of Proving Compliance BRE Information Paper 17/01 permits compliance to be proven via a trade off calculation (paragraph 5.4). This methodology can provide a significantly easier route to compliance for many buildings. If the building in question does not contain the full allowable percentage of rooflights (20%) and windows/personnel doors (15% in industrial/storage buildings or 40% in places of assembly/offices/ shops) and these allowances have not been traded off elsewhere, then they can be used as a trade off against heat losses at thermal bridge junctions to prove overall compliance. Additional improved thermal standards of envelope plane elements can also be traded off in this manner. As the Total B is greater than 10% of Total A in the example building, then the trade off route should be followed. The means of proving compliance via this route is as follows:
STEP 4 A further calculation for the plane element heat losses should be undertaken for a “notional building” of identical size and form but which contains the maximum permissible areas of windows/personnel doors and rooflights. The areas of opaque roof and wall elements require to be reduced to allow for the additional rooflight and window/personnel door areas within the notional building. e.g. If the actual building has a total roof area of 1000m2 with 10% rooflights it would break down into plane elemental areas of: 900m2 of roof @ U value of 0.25 100m2 of rooflights @ U value of 2.2 Total roof area =
1000m2
With the notional building, the areas of rooflights can be the maximum permitted 20%. Therefore the revised elemental areas would be: 800m2 of roof @ U value of 0.25 200m2 of rooflights @ U value of 2.2 Total roof area =
1000m2
A similar trade off would be undertaken for windows and personnel doors within the wall areas. The total heat losses for each element are then calculated and added together to provide the total plane element losses for the notional building. (Total C).
For the example building: Notional Building Element
Area (m2)
Total Roof Area Roof Rooflights (20%) Total Wall Area Exposed Walls Windows & Personnel Doors (15%) Vehicle Unloading Bay Doors Ground Floor
U-value (W/m2K)
Heat Loss
2647.00 2117.60 0.25 529.40 529.40 2.20 1164.68 1194.80 999.58 0.35 349.85 179.22 2.00 358.44 16.00 0.70 11.20 2400.00 0.25 600.00 Total Heat Loss (C) = 3013.57
STEP 5 The total plane element heat loss in the notional building (Total C) is then multiplied by 1.1. This allows for the 10% additional heat loss permitted at thermal bridge junctions and provides the total allowable heat losses for the notional building (Total D). For the example building: Total Allowable Notional Losses (D) = 3013.57 x 1.1 = 3314.93
STEP 6 The total heat losses for the actual building are obtained by adding the heat loss through the plane elements (Total A) and the thermal bridge junctions (Total B). If A + B (total heat losses for the actual building) is less than Total D (allowable heat losses for the notional building) then compliance is proven. For the example building: As the total heat losses for the actual building [(A+B) = 2713.36] are less than the total allowable losses for notional building [(D) = 3314.93], the building has complied with the requirements of IP 17/01 and Part L2 of the Building Regulations. Conclusion In many industrial and commercial buildings, the thermal bridging at junctions will not require any significant level of improvement over existing practice in order to prove compliance with IP17/01. This will be particularly true where the areas of rooflights and personnel doors/windows are below the maximum permitted areas within the regulations. The risk of condensation formation at thermal bridges is potentially of greater importance and must be considered. The risk of condensation formation is related to the building use and the internal surface temperatures at details. The minimum surface temperatures at details are defined as ‘f’ factors. Generic building types have minimum ‘f’ factor requirements which are laid down in IP17/01 (See Table A, page 4). Care must be taken to ensure that the degree of thermal bridging present at a detail does not lead to an unacceptable ‘f’ factor for the building use.
12
Thermal Bridging & Heat Loss Calculation Example Parts L2 & J To illustrate the relative effect of different components, junctions and air leakage loss the following has to be considered at design stage:
•
Provide continuity of insulation at junctions, joints, penetrations and abutment interfaces.
• Prevent missing insulation or gaps. • Minimise thermal or cold bridges.
Part L2 Assess condensation and mould growth risk (surface temperature f-factor).
•
• Assess
impact of thermal bridging throughout the building envelope, calculate linear thermal transmissions - Y-value and calculation of whole building’s a-value).
Parts L2 Whole Building a (alpha) Value - Case Study
A D E
6m
B
60 m
H
G C I G
J K
m 40
F
Standard Details - Specification: Roof KS1000 RW 80mm - Walls KS1000 MR 70mm Actual Building - Y Values
Actual Building - U-values Area (m2)
Element Total Roof Area Roof Rooflights (10%) Total Wall Area Exposed Walls Windows & Personnel Doors Vehicle Unloading Bay Doors Ground Floor
U-value (W/m2K)
A.U (W/K)
2647.00 2382.30 0.25 595.58 264.70 2.20 582.34 1194.80 1164.80 0.35 407.68 14.00 2.00 28.00 16.00 0.70 11.20 2400.00 0.25 600.00 Actual SA.U = 2224.80
Total Heat Loss for Actual Building
2713.36
Notional Building - U-values Area U-value (m2) (W/m2K) 2647.00 2117.60 0.25 529.40 2.20 1194.80 999.58 0.35 179.22 2.00 16.00 0.70 2400.00 0.25 Notional SA.U = Notional Total Heat Loss inc. 10% =
Element Total Roof Area Roof Rooflights (20%) Total Wall Area Exposed Walls Windows & Personnel Doors (15%) Vehicle Unloading Bay Doors Ground Floor
Total Heat Loss Notional Building Heat Loss Actual Building Heat Loss
A.U (W/K) 529.40 1164.68 349.85 358.44 11.20 600.00 3013.57 3314.93
3314.93 2713.36
(W/mK)
L.Y (W/K)
A Ridge 120.00 0.01 B Eaves 120.00 0.31 C Verge 80.00 1.01 1.38 D Valley Gutter 0.35 U-Value (2mm Galv. Steel) 60.00 E1 Cladding Drip 195.00 0.86 E2 Ground Floor* 195.00 0.16 F Corner 24.00 0.18 0.97 G1 Cladding Window or Personnel Door Head 34.00 G2 Window Frame Head* 30.00 0.04 G3 Personnel Door Head* 4.00 0.04 H1 Cladding Window Sill 30.00 0.48 H2 Window Frame Sill* 30.00 0.04 I1 Window & Personnel Door Jambs 20.00 0.80 I2 Window Frame Jambs* 4.00 0.04 I3 Personnel Door Jambs* 16.00 0.04 J1 Cladding Head to Vehicle Bay Door 4.00 0.68 J2 Vehicle Unloading Bay Door Head* 4.00 0.04 K1 Cladding Jamb to Vehicle Bay Door 8.00 1.70 K2 Vehicle Unloading Bay Door Jambs 8.00 0.04 * Assumed value SL.Y = Alpha Value SL..Y/Actual SA.U =
1.20 37.20 80.80 82.80 167.70 31.20 4.32 32.98 1.20 0.16 14.40 1.20 16.00 0.16 0.64 2.72 0.16 13.60 0.32 488.76 0.22
Object Name
Length (m)
Y Value
Vertical panel joints for KS 1000 MR are included within U-Value for the panel Compliance with MCRMA Technical Paper No. 14 = FAILS carry out calculation against notional building Compliance (Actual Heat Loss < Notional Building) = complies Approved Document L2
13
Thermal Bridging & Heat Loss Calculation Example
A D 6m
E
B
60 m
H
G C
J
I
K
m 40
G F
Enhanced Details - Specification: Roof KS1000 RW 80mm - Walls KS1000 MR 70mm Actual Building - Y Values
Actual Building - U-values Area (m2)
Element Total Roof Area Roof Rooflights (10%) Total Wall Area Exposed Walls Windows & Personnel Doors Vehicle Unloading Bay Doors Ground Floor
U-value (W/m2K)
A.U (W/K)
2647.00 2382.30 0.25 595.58 264.70 2.20 582.34 1194.80 1164.80 0.35 407.68 14.00 2.00 28.00 16.00 0.70 11.20 2400.00 0.25 600.00 Actual SA.U = 2224.80
Total Heat Loss for Actual Building
2474.00
Notional Building - U-values Area U-value (m2) (W/m2K) 2647.00 2117.60 0.25 529.40 2.20 1194.80 999.58 0.35 179.22 2.00 16.00 0.70 2400.00 0.25 Notional SA.U = Notional Total Heat Loss inc. 10% =
Element Total Roof Area Roof Rooflights (20%) Total Wall Area Exposed Walls Windows & Personnel Doors (15%) Vehicle Unloading Bay Doors Ground Floor
Total Heat Loss Notional Building Heat Loss Actual Building Heat Loss
A.U (W/K) 529.40 1164.68 349.85 358.44 11.20 600.00 3016.57 3314.93
3314.93 2474.00
(W/mK)
L.Y (W/K)
A Ridge 120.00 0.004 B Eaves 120.00 0.10 C Verge 80.00 0.01 D Valley Gutter* 60.00 0.83 E1 Cladding Drip 195.00 0.60 E2 Ground Floor* 195.00 0.16 F Corner 24.00 0.01 0.62 G1 Cladding Window or Personnel Door Head 34.00 G2 Window Frame Head* 30.00 0.04 G3 Personnel Door Head* 4.00 0.04 H1 Cladding Window Sill 30.00 0.10 H2 Window Frame Sill* 30.00 0.04 I1 Window & Personnel Door Jambs 20.00 0.08 I2 Window Frame Jambs* 4.00 0.04 I3 Personnel Door Jambs* 16.00 0.04 J1 Cladding Head to Vehicle Bay Door 4.00 0.62 J2 Vehicle Unloading Bay Door Head* 4.00 0.04 K1 Cladding Jamb to Vehicle Bay Door 8.00 0.71 K2 Vehicle Unloading Bay Door Jambs 8.00 0.04 * Assumed value SL.Y = Alpha Value SL..Y/Actual SA.U =
0.48 12.00 0.80 49.80 117.00 31.20 0.24 21.08 1.20 0.16 3.00 1.20 1.60 0.16 0.64 2.48 0.16 5.68 0.32 249.24 0.11
Object Name
Length (m)
Y Value
Compliance with MCRMA Technical Paper No. 14 = FAILS carry out calculation against notional building Compliance (Actual Heat Loss < Notional Building) = complies Approved Document L2
14
Air Leakage Risk Areas Parts L2 & J To illustrate the relative effect of different components,
• Roof and wall cladding air leakage will be required to be less than that indicated in Part L2 as the
junctions and air leakage loss the following has to be
regulations refers to the whole building air leakage
considered at design stage:
level. i.e. including doors, windows, dado walls and
• Limit air leakage loss within the envelope fabric
floor slab junctions.
and at junctions, joints, penetrations and abutment
• The air leakage performance of Kingspan’s roof
interfaces to comply with regulatory requirements.
and wall panels is 5m3/hr/m2 when installed to specification.
A D 6m
E
B
60 m
H
G C I G F
The red lines highlight the air leakage risk areas where air seals are required
J K
m 40
15
STANDARD CONSTUCTION DETAILS
16
STANDARD
KS1000 RW Roof Systems Two sets of details have been produced to give the Building Designer flexibility within the calculation for the total building heat loss. The decision on the choice of standard or enhanced details is taken by the Building Designer and is determined from the total building heat loss methodology demonstrated on pages 10 & 11 of this guide. A mixture of both standard and enhanced details maybe required for some projects.
KS1000 RW Roof Systems Standard Details Panel End Lap Detail Ridge Detail Parapet Details - Boundary Wall Gutter Eaves Details - External Gutter Verge Details - Wall Cladding Valley Gutter Detail Valley Hip Detail Hip Detail End Lap Detail (Panel to GRP Rooflight) End Lap Detail (GRP Rooflight to Panel) Rooflight Intermediate Detail Rooflight Side Lap - Fastener Location Detail
17 17 18-19 20 21-22 23 24 24 25 25 26 26
KS1000 LP Roof Systems Standard Details Panel End Lap Detail Ridge Detail Parapet Details - Boundary Wall Gutter Eaves Details - External Gutter Valley Gutter Detail Valley Hip Detail Hip Detail Verge Details - Wall Cladding Barrel Vault End Lap Details Barrel Vault Side Lap Detail End Lap Detail (Panel to GRP Rooflight) End Lap Detail (GRP Rooflight to Panel) Rooflight Intermediate Detail Rooflight Side Lap - Fastener Location Detail
27 27 28-29 30 31 32 32 33-34 35 36 37 37 38 38
KS1000 RW Wall (Vertically Laid) Systems Standard Details Drip Detail External Corner Detail Window Head and Cill Detail Window Jamb Detail & Alternative Option Detail Personnel Door Detail (Door head panel site cut) Door Jamb & Door Head Detail Up and Over Door Head Detail Door Jamb Detail
39 39 40 40 41 41 42 42
KS1000 MR/EB/FL-S/MM/CX/WV Wall (Horizontally Laid) Systems Standard Details External Corner Detail Vertical Joint Details Window Head and Cill Detail Window Jamb Detail Personnel Door Detail - (Door head panel site cut) Door Jamb & Door Head Detail Drip Detail - Above Floor Level & Below Floor Level Up and Over Door Head Detail Door Jamb Detail
43 44 45 45 46 46 47 48 48
17
STANDARD
KS1000 RW Roof Systems PANEL END LAP DETAIL Fixing screw KS1000 RW/LPCB roof panel
150mm
3 runs of 4mm Ø butyl rubber sealant (Site applied)
m Nominal 10m Max. 20mm
50mm
Min. 10mm
Purlin
RIDGE DETAIL Mineral fibre insulation site applied Ridge flashing with 150mm sealed butt straps
KS1000 RW/LPCB insulated roof panel Profiled filler set back 80 to 100mm to prevent bird attack
Profiled filler sealed top and bottom with gun-grade sealant
Max. 50mm Air seal - 8mm Ø butyl rubber sealant Purlin
Building Regulations Part L2 Thermal Data fmin = 0.97
Y = 0.01 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
Internal ridge flashing with 150mm overlap sealed with air seal, Vapourflex or gun-grade sealant
18
STANDARD
KS1000 RW Roof Systems PARAPET DETAIL - BOUNDARY WALL GUTTER
Parapet flashing with 150mm sealed butt straps Mineral fibre insulation site applied Butyl rubber sealant
Air seal - 6mm Ø butyl rubber sealant Profiled filler sealed top and bottom with gun-grade sealant Parapet rail with air seal, Vapourflex tape to rail joints Profiled filler sealed top and bottom with gungrade sealant
Sheeting rail Air seal - 6mm Ø butyl rubber sealant Mineral fibre insulation site applied KS1000 RW/LPCB insulated roof panel
KS1000 RW/ LPCB wall panel vertically laid
35mm Min
Air seal - 8mm Ø butyl rubber sealant 2mm external non-thermally broken factory made gutter with PIR insulation to 0.25 or 0.35 W/m2K U-value
60mm
Purlin
Gutter outlet Eaves beam gutter support
Building Regulations Part L2 Thermal Data 0.25 W/m2K gutter fmin = 0.48 Y = 1.63 W/mK 0.35 W/m2K gutter fmin = 0.48 Y = 1.72 W/mK 0.35 sole width 300mm and depth 150mm, values for other widths available on request. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
19
STANDARD
KS1000 RW Roof Systems PARAPET DETAIL - BOUNDARY WALL GUTTER
Parapet flashing with 150mm sealed butt straps Mineral fibre insulation site applied Butyl rubber sealant Air seal - 6mm Ø bead of gun-grade sealant Air seal - 6mm Ø butyl rubber sealant Profiled filler sealed top and bottom with gun-grade sealant Parapet rail with air seal, Vapourflex tape to rail joints Sheeting rail
KS1000 MR/ LPCB wall panel horizontally laid
Air seal - 6mm Ø butyl rubber sealant Mineral fibre insulation site applied KS1000 RW/LPCB insulated roof panel
KS1000 RW/ LPCB wall panel vertically laid
35mm Min
Air seal - 8mm Ø butyl rubber sealant 2mm external non-thermally broken factory made gutter with PIR insulation to 0.25 or 0.35 W/m2K U-value
60mm
Purlin
Gutter outlet Eaves beam gutter support
Building Regulations Part L2 Thermal Data 0.25 W/m2K gutter fmin = 0.48 Y = 1.63 W/mK 0.35 W/m2K gutter fmin = 0.48 Y = 1.72 W/mK 0.35 sole width 300mm and depth 150mm, values for other widths available on request. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
20
STANDARD
KS1000 RW Roof Systems EAVES DETAIL - EXTERNAL GUTTER
centres 200mm fixing
Gutter support 0.7mm thick doubled sided plastisol coated s re nt ce ing 200mm fix
75mm Approx
9mm x 3mm butyl rubber sealant Air seal - 8mm Ø butyl rubber sealant Air seal - 6mm Ø butyl rubber sealant Mineral fibre insulation site applied Double sided Plastisol “Highline” type gutter
20 35 20 mm mm mm
*
Eaves beam
Building Regulations Part L2 Thermal Data fmin = 0.92
*
Y = 0.27 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
Air seal - Vapourflex sealant is to be applied over any breaks in supporting secondary steelwork to give a continuous bearing face.
EAVES DETAIL - EXTERNAL GUTTER
centres 200mm fixing
Gutter support 0.7mm thick doubled sided plastisol coated centres 200mm fixing
75mm Approx
9mm x 3mm butyl rubber sealant Air seal - 8mm Ø butyl rubber sealant Air seal - 6mm Ø bead of gun-grade sealant Mineral fibre insulation site applied Double sided Plastisol “Highline” type gutter
20 35 20 mm mm mm
*
Eaves beam
Building Regulations Part L2 Thermal Data fmin = 0.91
Y = 0.31 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
*
Air seal - Vapourflex sealant is to be applied over any breaks in supporting secondary steelwork to give a continuous bearing face.
21
STANDARD
KS1000 RW Roof Systems VERGE DETAIL - WALL CLADDING (END OF ROOF SHEETING) Verge flashing with 150mm sealed butt straps Mineral fibre insulation site applied 9mm x 3mm butyl rubber sealant Verge zed support with 150mm sealed overlaps Cleader angle by steel sub-contractor with air seal - Vapourflex sealant applied at joints Direction of Lay Air seal - 8mm Ø butyl rubber sealant
Purlin Air seal - 6mm Ø butyl rubber sealant
Building Regulations Part L2 Thermal Data fmin = 0.91
Y = 1.01 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
Profiled filler sealed top and bottom with gun-grade sealant
22
STANDARD
KS1000 RW Roof Systems VERGE DETAIL - WALL CLADDING (START OF ROOF SHEETING) Verge flashing with 150mm sealed butt straps Mineral fibre insulation site applied 9mm x 3mm butyl rubber sealant Verge zed support with 150mm sealed overlaps Direction of Lay
Cleader angle by steel sub-contractor with air seal - Vapourflex sealant applied at joints Air seal - 8mm Ø butyl rubber sealant
KS1000 MR/ LPCB wall panel horizontally laid
4mm Ø butyl sealant Purlin
Building Regulations Part L2 Thermal Data fmin = 0.91
Y = 1.01 W/mK
Air seal - 6mm Ø bead of gun-grade sealant
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
VERGE DETAIL - WALL CLADDING (END OF ROOF SHEETING) Verge flashing with 150mm sealed butt straps Mineral fibre insulation site applied Site cut panel to suit Verge zed support with 150mm sealed overlaps 9mm x 3mm butyl rubber sealant
Direction of Lay
Cleader angle by steel sub-contractor with air seal - Vapourflex sealant applied at joints Air seal - 8mm Ø butyl rubber sealant
4mm Ø butyl sealant Purlin Air seal - 6mm Ø bead of gun-grade sealant Building Regulations Part L2 Thermal Data fmin = 0.91
Y = 1.01 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
KS1000 MR/ LPCB wall panel horizontally laid
23
STANDARD
KS1000 RW Roof Systems VALLEY GUTTER DETAIL KS1000 RW/LPCB insulated roof panel
Air seal - 8mm Ø butyl rubber sealant Stanchion head tie if necessary as steelwork design
Building Regulations Part L2 Thermal Data 0.25 W/m2K gutter fmin = 0.74 Y = 1.07 W/mK 0.35 W/m2K gutter fmin = 0.71 Y = 1.38 W/mK 0.35 sole width 600mm and depth 150mm, values for other widths available on request. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
2mm external non-thermally broken factory made galvanised sheet gutter with PIR board insulation to 0.25 or 0.35 W/m2K U-value Gutter outlet offset to miss stanchion head tie
Air seal - 8mm Ø butyl rubber sealant Purlin
24
STANDARD
KS1000 RW Roof Systems VALLEY HIP DETAIL KS1000 RW/LPCB insulated roof panel
Double sided Plastisol coated flashing
Air seal - 8mm Ø butyl rubber sealant Air seal - 8mm Ø butyl rubber sealant Edge protection lacquer applied to all panels cut on site to suit rake angle Cleader angle by steel sub-contractor
2mm external non-thermally broken factory made galvanised sheet gutter with PIR board insulation to 0.25 or 0.35 W/m2K U-value
Hip rafter
Purlin
Building Regulations Part L2 Thermal Data fmin = 0.85
Y = 0.41 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
HIP DETAIL Internal ridge flashing with 150mm overlap sealed with Vapourflex or gun-grade sealant
Mineral fibre insulation site applied
Panels site cut to suit rake angle Hip flashing with 150mm sealed butt straps
KS1000 RW/LPCB insulated roof panel
Max. 50mm
Rake cut profiled filler sealed top and bottom with gun-grade sealant
Profiled filler set back 80 to 100mm to prevent bird attack
Cleader angle by steel sub-contractor
Air seal - 8mm Ø butyl rubber sealant
Hip rafter
Building Regulations Part L2 Thermal Data fmin = 0.97
Y = 0.01 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
Purlin
25
STANDARD
KS1000 RW Roof Systems END LAP DETAIL - (PANEL TO GRP ROOFLIGHT) . end lap 150mm Min
Position of 6 No. main fixings with 29mm Ø washers at end laps
9mm x 3mm sealant strip or bead either side of fixing
KS1000 RW/LPCB roof panel
Silicone or mastic sealant strip at bottom of lap
Sealant
Triple skin GRP integral rooflight system
5mm expansion gap
Support bearing plate (Ref: LP2)
END LAP DETAIL - (GRP ROOFLIGHT TO PANEL) . end lap 150mm Min
Position of 6 No. main fixings with 29mm Ø washers at end laps
9mm x 3mm sealant strip or bead either side of fixing Silicone or mastic sealant strip at bottom of lap
Triple skin GRP integral rooflight system Sealant
5mm expansion gap KS1000 RW/LPCB roof panel
Support bearing plate (Ref: LP2)
26
STANDARD
KS1000 RW Roof Systems ROOFLIGHT INTERMEDIATE DETAIL
Galvanised steel plate at filler positions for high thread fixing High density filler
Triple skin GRP integral rooflight system
Position of 6 No. main fixings with 29mm Ø washers Purlin
ROOFLIGHT SIDE LAP - FASTENER LOCATION DETAIL Direction of Prevailing Wind
Direction of Lay
4mm Ø butyl rubber sealant Position of main fixings 6 No. with 29mm Ø washers at: i) Ridge ii) Intermediate iii) End laps
KS1000 RW/LPCB roof panel
Triple skin GRP rooflight system
Note: The GRP translucent rooflight illustrated above is generic in detail. Kingspan GRP rooflight details to comply with Part L2 and Part J will be made available later. These details DO NOT represent our product.
4mm Ø butyl rubber sealant Aluminium strip in underlap
Stitcher screw into aluminium 3mm Ø hole to be drilled prior to fixing/p side lap fixings at 300mm centres
27
STANDARD
KS1000 LP Roof Systems END LAP DETAIL panel m between Min. of 300m ver cap end lap co end lap and
Cover cap complete with joggle factory applied Continuous run of non-setting gun-grade sealant
End lap stitching plate
18mm x 4mm ‘U’ shaped butyl sealant
RIDGE DETAIL Ridge flashing with 150mm sealed butt straps
Outer sheet turned up with roof slopes below 4˚
Cover cap
Mineral fibre insulation site applied Apex dam (Ref: LP1)
Profiled filler set back 80 to 100mm to prevent bird attack
20mm x 3mm butyl rubber sealant
Max. 50mm Profiled filler sealed top and bottom with gun-grade sealant
2 No. runs silicone sealant
Air seal - 8mm Ø butyl rubber sealant
KS1000 LP/LPCB insulated roof panel
Internal ridge flashing with 150mm overlap sealed with Vapourflex or gun-grade sealant Building Regulations Part L2 Thermal Data fmin = 0.97
Y = 0.01 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
Purlin
28
STANDARD
KS1000 LP Roof Systems PARAPET DETAIL - BOUNDARY WALL GUTTER Parapet flashing with 150mm sealed butt straps Mineral fibre insulation site applied Butyl rubber sealant Parapet rail with air seal - Vapourflex tape to rail joints Air seal - 6mm Ø butyl rubber sealant Profiled filler sealed top and bottom with gun-grade sealant
Air seal - 6mm Ø bead of gun-grade sealant Air seal - 6mm Ø butyl rubber sealant 4mm Ø butyl rubber sealant KS1000 LP/LPCB insulated roof panel
KS1000 MR/ LPCB wall panel horizontally laid
75mm
Top sheet turned down on site with roof pitches below 4˚
KS1000 RW/ LPCB wall panel vertically laid
Gun-grade seal at panel joints inline with 8mm butyl
Mineral fibre insulation site applied
35mm Min
Sheeting rail
60mm
Air seal - 8mm Ø butyl rubber sealant 2mm external non-thermally broken factory made gutter with PIR insulation to 0.25 or 0.35 W/m2K U-value
Direction of Lay
Purlin
Gutter outlet Eaves beam gutter support
Building Regulations Part L2 Thermal Data 0.25 W/m2K gutter fmin = 0.48 Y = 1.63 W/mK 0.35 W/m2K gutter fmin = 0.48 Y = 1.72 W/mK 0.35 sole width 300mm and depth 150mm, values for other widths available on request. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
29
STANDARD
KS1000 LP Roof Systems PARAPET DETAIL - BOUNDARY WALL GUTTER Parapet flashing with 150mm sealed butt straps Mineral fibre insulation site applied Butyl rubber sealant Parapet rail with air seal - Vapourflex tape to rail joints Air seal - 6mm Ø butyl rubber sealant Profiled filler sealed top and bottom with gun-grade sealant
Air seal - 6mm Ø bead of gun-grade sealant Air seal - 6mm Ø butyl rubber sealant 4mm Ø butyl rubber sealant KS1000 LP/LPCB insulated roof panel
KS1000 RW/ LPCB wall panel vertically laid
75mm
Top sheet turned down on site with roof pitches below 4˚
KS1000 RW/ LPCB wall panel vertically laid
Gun-grade seal at panel joints inline with 8mm butyl
Mineral fibre insulation site applied
35mm Min
Sheeting rail
60mm
Air seal - 8mm Ø butyl rubber sealant 2mm external non-thermally broken factory made gutter with PIR insulation to 0.25 or 0.35 W/m2K U-value
Direction of Lay
Purlin
Gutter outlet Eaves beam gutter support
Building Regulations Part L2 Thermal Data 0.25 W/m2K gutter fmin = 0.48 Y = 1.63 W/mK 0.35 W/m2K gutter fmin = 0.48 Y = 1.72 W/mK 0.35 sole width 300mm and depth 150mm, values for other widths available on request. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
30
STANDARD
KS1000 LP Roof Systems EAVES DETAIL - EXTERNAL GUTTER Gutter support 0.7mm thick double sided plastisol coated Top sheet turned down on site with roof pitches below 4˚ 9mm x 3mm butyl rubber sealant
g centres 200mm fixin
g centres 200mm fixin
Stitching screw fixings for gutter brackets
75mm Approx
KS1000 LP/LPCB insulated roof panel Gun-grade seal at panel joints inline with 8mm butyl Air seal - 8mm Ø butyl rubber sealant Air seal - 6mm Ø bead of gun-grade sealant Mineral fibre insulation site applied
*
Double sided plastisol Highline type gutter
20 35 20 mm mm mm
Eaves beam
*
Air seal - Vapourflex sealant is to be applied over any breaks in supporting secondary steelwork to give a continuous bearing face.
KS1000 MR/LPCB wall panel horizontally laid
Building Regulations Part L2 Thermal Data fmin = 0.91
Y = 0.31 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
EAVES DETAIL - EXTERNAL GUTTER Gutter support 0.7mm thick double sided plastisol coated Top sheet turned down on site with roof pitches below 4˚ 9mm x 3mm butyl rubber sealant
g centres 200mm fixin
g centres 200mm fixin
Stitching screw fixings for gutter brackets
75mm Approx
KS1000 LP/LPCB insulated roof panel Gun-grade seal at panel joints inline with 8mm butyl Air seal - 8mm Ø butyl rubber sealant Air seal - 6mm Ø butyl rubber sealant Mineral fibre insulation site applied
Double sided plastisol Highline type gutter
* 20 35 20 mm mm mm
Eaves beam KS1000 RW/ LPCB wall panel vertically laid
*
Air seal - Vapourflex sealant is to be applied over any breaks in supporting secondary steelwork to give a continuous bearing face.
Building Regulations Part L2 Thermal Data fmin = 0.92
Y = 0.27 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
31
STANDARD
KS1000 LP Roof Systems VALLEY GUTTER DETAIL Gun-grade seal at panel joints inline with 8mm butyl
Cover cap 75mm
Top sheet turned down on site with roof pitches below 4˚
Air seal - 8mm Ø butyl rubber sealant Stanchion head tie if necessary as steelwork design
2mm external non-thermally broken factory made gutter with PIR insulation to 0.25 or 0.35 W/m2K U-value Gutter outlet offset to miss stanchion head tie
Air seal - 8mm Ø butyl rubber sealant Purlin
Building Regulations Part L2 Thermal Data 0.25 W/m2K gutter fmin = 0.74 Y = 1.07 W/mK 0.35 W/m2K gutter fmin = 0.71 Y = 1.38 W/mK 0.35 sole width 600mm and depth 150mm, values for other widths available on request. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
32
STANDARD
KS1000 LP Roof Systems VALLEY HIP DETAIL
Double sided plastisol coated flashing
Cover cap KS1000 LP/LPCB insulated roof panel
Gun-grade seal at panel joints inline with 8mm butyl
Edge protection lacquer applied to all panels cut on site to suit rake angle
Air seal - 8mm Ø butyl rubber sealant Cleader angle by steelwork contractors
2mm external non-thermally broken factory made gutter with PIR insulation to 0.25 W/m2K U-value
Building Regulations Part L2 Thermal Data fmin = 0.85
Hip rafter
Purlin
Y = 0.41 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
HIP DETAIL Hip flashing with 150mm sealed butt straps Panels site cut to suit rake angle
Mineral fibre insulation site applied Outer sheet turned up on site with roof pitches below 4˚
Apex dam (Ref: LP1/A) Rake cut profiled filler sealed top and bottom with gun-grade sealant KS1000 LP/LPCB insulated roof panel
Air seal - 8mm Ø butyl rubber sealant Internal ridge flashing with 150mm overlap sealed with Vapourflex or gun-grade sealant Building Regulations Part L2 Thermal Data fmin = 0.97
Y = 0.01 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
Cover cap 20mm x 3mm butyl rubber sealant 2 No. runs of silicone sealant
Purlin Cleader angle by steelwork contractor Hip rafter
33
STANDARD
KS1000 LP Roof Systems VERGE DETAIL - WALL CLADDING (START OF ROOF SHEETING) Verge flashing with 150mm sealed butt straps Mineral fibre insulation site applied
Direction of Lay
20mm x 3mm butyl rubber sealant Cleader angle by steel sub-contractor with air seal Vapourflex sealant applied at joints KS1000 LP/LPCB insulated roof panel
Purlin Air seal - 8mm Ø butyl rubber sealant Air seal - 6mm Ø bead of gun-grade sealant Gable rafter KS1000 MR/LPCB insulated wall panel horizontally laid 4mm Ø butyl rubber sealant
Building Regulations Part L2 Thermal Data fmin = 0.96
Y = 0.18 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
VERGE DETAIL - WALL CLADDING (START OF ROOF SHEETING) Verge flashing with 150mm sealed butt straps Direction of Lay
Mineral fibre insulation site applied 20mm x 3mm butyl rubber sealant Cleader angle by steel sub-contractor with air seal Vapourflex sealant applied at joints KS1000 LP/LPCB insulated roof panel
Purlin Air seal - 8mm Ø butyl rubber sealant Air seal - 6mm Ø butyl rubber sealant Gable rafter KS1000 RW/LPCB insulated wall panel vertically laid Building Regulations Part L2 Thermal Data fmin = 0.96
Y = 0.18 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
Profiled filler sealed top & bottom with gun grade sealant
34
STANDARD
KS1000 LP Roof Systems VERGE DETAIL - WALL CLADDING (END OF ROOF SHEETING) Verge flashing with 150mm sealed butt straps Mineral fibre insulation site applied Direction of Lay 20mm x 3mm butyl rubber sealant Cleader angle by steel sub-contractor with air seal Vapourflex sealant applied at joints KS1000 LP/LPCB insulated roof panel
Purlin Air seal - 8mm Ø butyl rubber sealant Air seal - 6mm Ø bead of gun-grade sealant Gable rafter KS1000 MR/LPCB insulated wall panel horizontally laid 4mm Ø butyl rubber sealant
Building Regulations Part L2 Thermal Data fmin = 0.96
Y = 0.18 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
VERGE DETAIL - WALL CLADDING (END OF ROOF SHEETING) Verge flashing with 150mm sealed butt straps Mineral fibre insulation site applied Direction of Lay 20mm x 3mm butyl rubber sealant Cleader angle by steel sub-contractor with air seal Vapourflex sealant applied at joints KS1000 LP/LPCB insulated roof panel
Purlin Air seal - 8mm Ø butyl rubber sealant Air seal - 6mm Ø butyl rubber sealant Gable rafter KS1000 RW/LPCB insulated wall panel vertically laid Profiled filler sealed top & bottom with gun grade sealant
Building Regulations Part L2 Thermal Data fmin = 0.96
Y = 0.18 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
35
STANDARD
KS1000 LP Roof Systems BARREL VAULT END LAP DETAIL
9mm x 3mm butyl rubber sealant GRP barrel vault rooflight system fixed at 225mm centres with 30mm Ø sealed washers
Single skin GRP barrel vault rooflight system lap 75mm end
Apex dam (Ref: LP1)
Double skin GRP rooflight system
20mm x 3mm butyl rubber sealant Cover cap
5mm expansion gap Position of 4 no. main fixings with 29mm Ø washers at end lap
2 No. runs silicone sealant
Main panel fixing at side profile joint
KS1000 LP/LPCB insulated roof panel Support bearing plate (Ref: LP2)
BARREL VAULT END LAP DETAIL GRP barrel vault rooflight system fixed at 225mm centres with 30mm Ø sealed washers Single skin GRP barrel vault rooflight system
In-situ GRP weather seal
GRP site applied water deflector
lap 75mm end
Cover cap over GRP weather seal
9mm x 3mm butyl rubber sealant
External closure flashing Main panel fixing at side profile joint Double skin GRP rooflight system Support bearing plate (Ref: LP2)
5mm expansion gap Position of 4 no. main fixings with 29mm Ø washers at end lap
36
STANDARD
KS1000 LP Roof Systems BARREL VAULT SIDE LAP DETAIL
Single skin GRP barrel vault rooflight Self tap screw with 30mm Ø washers at 255mm centres, stitched to galv. support angle. 20mm x 3mm butyl rubber sealant
Continuous 1.6mm thick galv steel angle for rooflight fixings bulb type rivets at 300mm centres
Continuous 1.6mm thick galv. steel zed support for rooflight fixings stitched to panel at 200mm centres 2 runs of 20mm x 3mm butyl rubber sealant between top & bottom galv. support Double skin GRP rooflight system
1000mm KS1000 LP/LPCB roof panel
Main fixing at purlin locations
37
STANDARD
KS1000 LP Roof Systems END LAP DETAIL (PANEL TO GRP ROOFLIGHT) lap 75mm end
5mm expansion gap
9mm x 3mm butyl rubber sealant Triple skin GRP integral rooflight system
Cover cap KS1000 LP/LPCB roof panel High density filler
Support bearing plate (Ref: LP2) Main panel fixings at side profile joint
Position of 4 No. main fixings with 29mm Ø washers at end laps
END LAP DETAIL (GRP ROOFLIGHT TO PANEL) 75mm end lap
Cover cap
9mm x 3mm butyl rubber sealant
KS1000 LP/LPCB roof panel
Triple skin GRP integral rooflight system Main panel fixings at side profile joint Support bearing plate (Ref: LP2)
Position of 4 No. main fixings with 29mm Ø washers at end laps 5mm expansion gap
38
STANDARD
KS1000 LP Roof Systems ROOFLIGHT INTERMEDIATE DETAIL
Triple skin GRP rooflight system
High density filler
Position of 4 No. main fixings with 29mm Ø washers
ROOFLIGHT SIDE LAP - FASTENER LOCATION DETAIL
1000mm
KS1000 LP/LPCB roof panel
Cover cap snaps on without external fixings Note: Position cap on rooflight side first
Cover caps
Triple skin GRP rooflight system
39
STANDARD
KS1000 RW Wall Systems Vertically laid DRIP DETAIL KS1000 RW/LPCB vertically laid
Air seal - 6mm Ø butyl rubber sealant Air seal - continuous bead of gun-grade sealant required at angle edge Internal closure flashing
Mineral fibre insulation site applied
Alfas C foam seal
Galvanised ledger angle
Drip flashing
Building Regulations Part L2 Thermal Data fmin = 0.52
Y = 0.60 W/mK
The appropriate Y value for the brickwork, blocks or concrete must be added to the above Y value to obtain the total loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
EXTERNAL CORNER DETAIL
Corner column Sheeting rail KS1000 RW/LPCB insulated wall panel vertically laid Air seal - 6mm Ø butyl rubber sealant
Internal cleader angle by steel sub-contractor with air seal Vapourflex sealant applied at joints Zed support lapped 100mm at joints Site cut vertical sheeting Mineral fibre insulation site applied
External corner flashing with 100mm sealed overlaps
Direction of Lay
9mm x 3mm butyl rubber sealant KS1000 RW/LPCB insulated wall panel vertically laid
Building Regulations Part L2 Thermal Data fmin = 0.95
Y = 0.02 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
40
STANDARD
KS1000 RW Wall Systems Vertically laid WINDOW HEAD AND CILL DETAIL Air seal - 6mm Ø butyl rubber sealant
Building Regulations Part L2 Thermal Data fmin = 0.44
Y = 1.01 W/mK
Optional internal head flashing
The appropriate Y value for the window system must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
Mineral fibre insulation site applied Window support rail
Head flashing 9mm x 3mm butyl rubber sealant
Window depth to suit panel module
External soffit flashing with no connection to internal Polyethylene backing rod with silicone sealant by window installer Window unit by others
Window cill flashing with 3° slope to facilitate drainage (no connection to internal) Profiled filler sealed top and bottom with gun-grade sealant
Mineral fibre insulation site applied
Building Regulations Part L2 Thermal Data fmin = 0.52
Air seal - 6mm Ø butyl rubber sealant
Y = 0.83 W/mK
The appropriate Y value for the window system must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
WINDOW JAMB DETAIL OPTION 1
Internal cill flashing
WINDOW JAMB DETAIL OPTION 2
Window width
Mineral fibre insulation site applied Jamb steelwork Window unit by others
Polyethylene backing rod with silicone sealant Air seal - 6mm Ø butyl rubber sealant External jamb flashing with no connection to internal Site cut panel Building Regulations Part L2 Thermal Data 9mm x 3mm butyl rubber sealant
fmin = 0.59
Y = 0.53 W/mK
The appropriate Y value for the window system must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
41
STANDARD
KS1000 RW Wall Systems Vertically laid PERSONNEL DOOR DETAIL (DOOR HEAD PANEL SITE CUT) B
+2100mm
B A
A
Door frame by others
Expanding type anchor fixing by others
Pressed metal base channel or RSA by others
F.F.L. 0.00mm 900mm
DOOR JAMB DETAIL A-A
DOOR HEAD DETAIL B-B
Galvanised door post by steel sub-contractor with Vapourflex sealant applied to joints Polyethylene backing rod with silicone sealant by door installer
Air seal - 6mm Ø butyl rubber sealant Internal head flashing (optional)
Mineral fibre insulation site applied
Galvanised door head
Mineral fibre insulation site applied Door & frame by others fixed to steel support frame
Site cut panel
External soffit flashing with no connection to internal
Air seal - 6mm Ø butyl rubber sealant
9mm x 3mm butyl rubber sealant External jamb flashing with no connection to internal
9mm x 3mm butyl rubber sealant
Door head flashing Note: For opening outward door ensure drip flashing is clear top of door
Building Regulations Part L2 Thermal Data fmin = 0.59
Y = 0.53 W/mK
The appropriate Y value for the door system must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
Building Regulations Part L2 Thermal Data fmin = 0.44
Y = 1.01 W/mK
The appropriate Y value for the door system must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
42
STANDARD
KS1000 RW Wall Systems Vertically laid
Air seal - 6mm Ø butyl rubber sealant Mineral fibre insulation site applied 9mm x 3mm butyl rubber sealant
Head flashing External soffit flashing
Drum
pe slo ble ia r Va
Roller guide supported from main structure
Clear door height
Optional internal closure flashing
See door manufacturers details for height required
UP AND OVER DOOR HEAD DETAIL
RSC door post
Building Regulations Part L2 Thermal Data fmin = 0.30
Y = 0.66 W/mK
The appropriate Y value for the door system must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
DOOR JAMB DETAIL Door guide by others Door by others
Air seal RSC door post Mineral fibre insulation site applied Sheeting rail
Internal cleader angle by steel sub-contractor with Vapourflex seal applied to joints Air seal - 6mm Ø butyl rubber sealant Site cut panel
Door jamb flashing 9mm x 3mm butyl rubber sealant Note: Roller shutter doors to be well insulated and have sealed joints, head, jamb and at floor.
9mm x 3mm butyl rubber sealant
Clear door width
Building Regulations Part L2 Thermal Data fmin = 0.37
Y = 1.33 W/mK
The appropriate Y value for the door system must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
43
STANDARD
KS1000 MR/EB/FL-S/MM/CX/WV Wall Systems Horizontally laid EXTERNAL CORNER DETAIL KS1000 MR/LPCB horizontally Laid
Air seal - 4mm Ø bead of gun-grade sealant Corner column
Air seal - 4mm Ø bead of gun-grade sealant Air seal - gun-grade sealant to male joint Internal cleader angle by steel sub-contractor with air seal - Vapourflex sealant applied at joints
Vertical sheeting rail
AWP joint filler and silicone sealant
Mineral fibre insulation site applied
External corner flashing with 100mm overlaps
KS1000 MR/LPCB horizontally laid
4mm Ø butyl rubber sealant
Building Regulations Part L2 Thermal Data fmin = 0.91
Y = 0.18 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
44
STANDARD
KS1000 MR/EB/FL-S/MM/CX/WV Wall Systems Horizontally laid VERTICAL JOINT DETAILS VERTICAL JOINT OPTION A
Min. Steel bearing face 130mm
35mm
Air seal - EPDM bubble gasket 95x10mm. Kingspan (Ref: VJ2)
40mm
Mineral fibre insulation site applied Air seal - gun-grade sealant to male joint
35mm
“Snap on” cover flashing
AWP joint filler and gun-grade sealant
OPTION A RECESSED
30mm 15 15
KS1000 MR/LPCB insulated wall panel horizontally laid
35mm
30mm
35mm
“Snap on” receiver flashing (30mm deep)
15mm recess to“Snap on” cover flashing Building Regulations Part L2 Thermal Data
4mm Ø butyl rubber sealant site applied
fmin = 0.97
Y = 0.03 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values. For joint spacings of 1000mm or more, the above Y value is included within the U value of the insulated panel.
VERTICAL JOINT OPTION B
Min. Steel bearing face 130mm Mineral fibre insulation site applied
Air seal - EPDM bubble gasket 95x10mm. Kingspan (Ref: VJ2)
35mm
35mm
35mm
AWP joint filler and gun-grade sealant
Air seal - gun-grade sealant to male joint
30mm KS1000 MR/LPCB insulated wall panel horizontally laid
Building Regulations Part L2 Thermal Data 35mm
30mm
35mm
“Snap on” receiver flashing (30mm deep)
Y = 0.03 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values. For joint spacings of 1000mm or more, the above Y value is included within the U value of the insulated panel.
4mm Ø butyl rubber sealant site applied
VERTICAL JOINT OPTION F
fmin = 0.97
Min. Steel bearing face 130mm
Air seal - EPDM bubble gasket 95x10mm. Kingspan (Ref: VJ2)
Mineral fibre insulation site applied 35mm
35mm
35mm
AWP joint filler and gun-grade sealant
Air seal - gun-grade sealant to male joint
25mm KS1000 MR/LPCB insulated wall panel horizontally laid 9mm x 4mm PVC sealant (site applied)
Optional push in MG02 or snap in MXS02 28mm 19mm 28mm Building Regulations Part L2 Thermal Data fmin = 0.96
TH25 extruded aluminium top hat section (25mm deep)
Y = 0.03 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values. For joint spacings of 1000mm or more, the above Y value is included within the U value of the insulated panel.
45
STANDARD
KS1000 MR/EB/FL-S/MM/CX/WV Wall Systems Horizontally laid WINDOW HEAD AND CILL DETAIL Building Regulations Part L2 Thermal Data fmin = 0.49
Air seal - 6mm bead of gun-grade sealant
Y = 0.97 W/mK Optional internal head flashing
The appropriate Y value for the window system must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
Mineral fibre insulation site applied
Panel bearer at 1500mm centres Window support rail Head flashing 4mm Ø butyl rubber sealant
Window depth to suit panel module
External soffit flashing with no connection to internal
Polyethylene backing rod with silicone sealant by window installer
Window unit by others
Mineral fibre insulation site applied
Window cill flashing with 3° slope to facilitate drainage (no connection to internal)
Air seal - 6mm bead of gun-grade sealant Building Regulations Part L2 Thermal Data fmin = 0.67
Internal cill flashing
Y = 0.48 W/mK
The appropriate Y value for the window system must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
4mm Ø butyl rubber sealant
WINDOW JAMB DETAIL Window opening Jamb steelwork Mineral fibre insulation site applied
Polyethylene backing rod with silicone sealant by window installer
Window unit by others External jamb flashing with no connection to internal Air seal - 6mm bead of gun-grade sealant Site cut panel Air seal - Gun-grade sealant to male joint AWP joint filler and gun-grade sealant 4mm Ø Butyl rubber sealant Building Regulations Part L2 Thermal Data fmin = 0.62
Y = 0.67 W/mK
The appropriate Y value for the window system must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
46
STANDARD
KS1000 MR/EB/FL-S/MM/CX/WV Wall Systems Horizontally laid PERSONNEL DOOR DETAIL (DOOR HEAD PANEL SITE CUT)
DOOR JAMB DETAIL A-A
Galvanised door post by steel sub-contractor with Vapourflex sealant applied to joints B
Mineral fibre insulation site applied
+2100mm
B
A
A Polyethylene backing rod with silicone sealant by door installer External jamb flashing with no connection to internal
Door frame by others
Air seal - 6mm Ø bead of gun-grade sealant AWP joint filler and gun-grade sealant
Pressed metal base channel or RSA by others
Building Regulations Part L2 Thermal Data fmin = 0.60
Expanding type anchor fixing
900mm
4mm Ø butyl rubber sealant
Y = 0.80 W/mK
The appropriate Y value for the door system must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
F.F.L. 0.00mm
DOOR HEAD DETAIL B-B
Air seal - 6mm bead of gun-grade sealant Optional internal head flashing Mineral fibre insulation site applied Galvanised door head
Door & frame by others fixed to steel support frame External soffit flashing with no connection to internal Note: For opening outward door ensure door head flashing is sufficiently high enough to clear top of door
4mm Ø butyl rubber sealant Door head flashing Building Regulations Part L2 Thermal Data fmin = 0.44
Y = 0.91 W/mk
The appropriate Y value for the door system must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
47
STANDARD
KS1000 MR/EB/FL-S/MM/CX/WV Wall Systems Horizontally laid DRIP DETAIL - ABOVE FLOOR LEVEL Column face Vertical rail KS1000 MR/LPCB insulated wall panel horizontally laid Optional internal closure flashing to mask insulation from view Galvanised drip support angle Mineral fibre insulation site applied
Air seal - 6mm bead of gun-grade sealant
Panel bearer at ends of panel & max. 1500mm centres between Building Regulations Part L2 Thermal Data fmin = 0.50
Y = 0.86 W/mK
Drip flashing Air seal - continuous bead of gun-grade sealant
The appropriate Y value for the brickwork, blockwork or concrete must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
DRIP DETAIL - BELOW FLOOR LEVEL Column face Vertical rail
KS1000 MR/LPCB insulated wall panel horizontally laid Optional internal closure flashing to mask insulation from view Air seal - 6mm bead of gun-grade sealant Galvanised drip support angle Air seal - continuous bead of gun-grade sealant
Both support angles fixed together prior to placing Mineral fibre insulation site applied Galvanised drip support angle
Building Regulations Part L2 Thermal Data fmin = 0.58
Y = 1.12 W/mK
The appropriate Y value for the brickwork, blockwork or concrete must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
Panel bearer at ends of panel & max. 1500mm centres between Drip flashing
Alfas C foam seal
48
STANDARD
KS1000 MR/EB/FL-S/MM/CX/WV Wall Systems Horizontally laid
Air seal - 6mm Ø bead of gun-grade sealant Mineral fibre insulation site applied 4mm Ø butyl rubber sealant
Head flashing External soffit flashing
Drum
e lop le s iab r a V
Roller guide supported from main structure
Clear door height
Optional internal closure flashing
See door manufacturers details for height required
UP AND OVER DOOR HEAD DETAIL
RSC door post
Building Regulations Part L2 Thermal Data fmin = 0.30
Y = 0.68 W/mK
The appropriate Y value for the door system must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
DOOR JAMB DETAIL Door guide by others Door by others
Air seal RSC door post Mineral fibre insulation site applied Sheeting rail
Internal cleader angle by steel sub-contractor with Vapourflex seal applied to joints Air seal - 6mm Ø butyl rubber sealant Site cut panel
9mm x 3mm butyl rubber sealant Note: Roller shutter doors to be well insulated and have sealed joints, head, jamb and at floor.
Door jamb flashing AWP joint filler and gun-grade sealant
Clear door width
Building Regulations Part L2 Thermal Data fmin = 0.37
Y = 1.70 W/mK
The appropriate Y value for the door system must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
49
ENHANCED CONSTUCTION DETAILS
50
ENHANCED
Construction Details Contents This paragraph of text should explain that the remaining pages contain enhanced details.
KS1000 RW Roof Systems Enhanced Details Ridge Detail Eaves Detail - External Gutter Parapet Detail - Boundary Wall Gutter Verge Detail - Wall Cladding (End of roof sheeting) Valley Gutter Detail Valley Hip Gutter Detail Hip Detail
51 51 52 53 53 54 54
KS1000 LP Roof Systems Enhanced Details Ridge Detail Parapet Details - Boundary Wall Gutter Eaves Details - External Gutter Valley Gutter Detail Verge Details - Wall Cladding Valley Hip Detail Hip Detail
55 56-57 58 59 60-61 62 62
KS1000 RW Wall (Vertically Laid) Systems Enhanced Details Drip Detail External Corner Detail Window Head and Cill Detail Window Jamb Detail & Alternative Option Detail Personnel Door Detail (Door head panel site cut) Door Jamb & Door Head Detail Up and Over Door Head Detail Door Jamb Detail
63 63 64 64 65 65 66 66
KS1000 MR/EB/FL-S/MM/CX/WV Wall (Horizontally Laid) Systems Enhanced Details Parapet Detail - Boundary Wall Gutter Eaves Details - External Gutter Verge Details - Wall Cladding External Corner Detail Pre-formed External Corner Detail Vertical Joint Details Window Head and Cill Detail Window Jamb Detail Personnel Door Detail - (Door head panel site cut) Door Jamb & Door Head Detail Drip Detail - Above Floor Level & Below Floor Level Up and Over Door Head Detail Door Jamb Detail
67 68 69 70 70 71 72 72 73 73 74 75 75
51
ENHANCED
KS1000 RW Roof Systems RIDGE DETAIL
Site applied Alfasbond fire rated (FR) canister insulation
Ridge flashing with 150mm sealed butt straps
KS1000 RW/LPCB insulated roof panel Profiled filler set back 80 to 100mm to prevent bird attack
Profiled filler sealed top and bottom with gun-grade sealant
Air seal - 8mm Ø butyl rubber sealant
Internal ridge flashing with 150mm overlap sealed with air seal, Vapourflex or gun-grade sealant
Purlin
Building Regulations Part L2 Thermal Data fmin = 0.97
Y = 0.004 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
EAVES DETAIL - EXTERNAL GUTTER
centres 200mm fixing
Gutter support 0.7mm thick doubled sided plastisol coated centres ing fix m 0m 20
75mm Approx
9mm x 3mm butyl rubber sealant Air seal - 8mm Ø butyl rubber sealant Air seal - 6mm Ø butyl rubber sealant Site applied Alfasbond fire rated (FR) canister insulation Double sided Plastisol “Highline” type gutter
20 35 20 mm mm mm
*
Eaves beam
Building Regulations Part L2 Thermal Data fmin = 0.92
Y = 0.27 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
*
Air seal - Vapourflex sealant is to be applied over any breaks in supporting secondary steelwork to give a continuous bearing face.
52
ENHANCED
KS1000 RW Roof Systems PARAPET DETAIL - BOUNDARY WALL GUTTER Parapet flashing with 150mm sealed butt straps Site applied PIR board insulation Site applied Alfasbond fire rated (FR) canister insulation
Air seal - 6mm Ø butyl rubber sealant Profiled filler sealed top and bottom with gun-grade sealant Parapet rail with air seal, Vapourflex tape to rail joints Profiled filler sealed top and bottom with gungrade sealant
Sheeting rail Air seal - 6mm Ø butyl rubber sealant Site applied Alfasbond fire rated (FR) canister insulation KS1000 RW/LPCB insulated roof panel
KS1000 RW/ LPCB wall panel vertically laid
35mm Min
Air seal - 8mm Ø butyl rubber sealant Factory made thermally broken membrane lined gutter with PIR board insulation to 0.25 or 0.35 W/m2K U-value
60mm
Purlin
Gutter outlet Eaves beam gutter support
Building Regulations Part L2 Thermal Data 0.25 W/m2K gutter fmin = 0.90 Y = 0.13 W/mK 0.35 W/m2K gutter fmin = 0.90 Y = 0.21 W/mK 0.35 sole width 300mm and depth 150mm, values for other widths available on request. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
53
ENHANCED
KS1000 RW Roof Systems VERGE DETAIL - WALL CLADDING (END OF ROOF SHEETING) Verge flashing with 150mm sealed butt straps PIR board insulation with site applied Alfasbond fire rated (FR) canister insulation to fill any gaps if required to maintain continuity of insulation 9mm x 3mm butyl rubber sealant Verge zed support with 150mm sealed overlaps Cleader angle by steel sub-contractor with air seal - Vapourflex sealant applied at joints Direction of Lay Air seal - 8mm Ø butyl rubber sealant
Purlin Air seal - 6mm Ø butyl rubber sealant Profiled filler sealed top and bottom with gun-grade sealant
Building Regulations Part L2 Thermal Data fmin = 0.96
Y = 0.01 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
VALLEY GUTTER DETAIL KS1000 RW/LPCB insulated roof panel
Air seal - 8mm Ø butyl rubber sealant Stanchion head tie if necessary as steelwork design
Building Regulations Part L2 Thermal Data 0.25 W/m2K gutter fmin = 0.94 Y = 0.27 W/mK 0.35 W/m2K gutter fmin = 0.93 Y = 0.43 W/mK 0.35 sole width 600mm and depth 150mm, values for other widths available on request. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
Factory made thermally broken membrane lined gutter with PIR board insulation to 0.25 or 0.35 W/m2K U-value Gutter outlet offset to miss stanchion head tie
Air seal - 8mm Ø butyl rubber sealant Purlin
54
ENHANCED
KS1000 RW Roof Systems VALLEY HIP DETAIL KS1000 RW/LPCB insulated roof panel
Double sided Plastisol coated flashing
Air seal - 8mm Ø butyl rubber sealant Air seal - 8mm Ø butyl rubber sealant Edge protection lacquer applied to all panels cut on site to suit rake angle Cleader angle by steel sub-contractor
Factory made thermally broken membrane lined gutter with PIR board insulation to 0.25 or 0.35 W/m2K U-value
Hip rafter
Purlin
Building Regulations Part L2 Thermal Data fmin = 0.94
Y = 0.29 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
HIP DETAIL Panels site cut to suit rake angle
Site applied Alfasbond fire rated (FR) canister insulation
Internal ridge flashing with 150mm overlap sealed with Vapourflex or gun-grade sealant Hip flashing with 150mm sealed butt straps
KS1000 RW/LPCB insulated roof panel
Rake cut profiled filler sealed top and bottom with gun-grade sealant
Profiled filler set back 80 to 100mm to prevent bird attack
Cleader angle by steel sub-contractor
Air seal - 8mm Ø butyl rubber sealant
Hip rafter
Building Regulations Part L2 Thermal Data fmin = 0.97
Y = 0.004 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
Purlin
55
ENHANCED
KS1000 LP Roof Systems RIDGE DETAIL Ridge flashing with 150mm sealed butt straps
Outer sheet turned up with roof slopes below 4˚ Site applied Alfasbond fire rated (FR) canister insulation
Cover cap
Apex dam (Ref: LP1)
Profiled filler set back 80 to 100mm to prevent bird attack
20mm x 3mm butyl rubber sealant
Profiled filler sealed top and bottom with gun-grade sealant
Air seal - 8mm Ø butyl rubber sealant
2 No. runs silicone sealant
KS1000 LP/LPCB insulated roof panel
Internal ridge flashing with 150mm overlap sealed with Vapourflex or gun-grade sealant
Purlin
Building Regulations Part L2 Thermal Data fmin = 0.97
Y = 0.004 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
56
ENHANCED
KS1000 LP Roof Systems PARAPET DETAIL - BOUNDARY WALL GUTTER Parapet flashing with 150mm sealed butt straps
Site applied PIR board insulation Site applied Alfasbond fire rated (FR) canister insulation
Air seal - 6mm Ø butyl rubber sealant Profiled filler sealed top and bottom with gun-grade sealant Sheeting rail Profiled filler sealed top and bottom with gungrade sealant
Air seal - 6mm Ø butyl rubber sealant Site applied Alfasbond fire rated (FR) canister insulation 75mm
Parapet rail with air seal Vapourflex tape to rail joints
KS1000 LP/LPCB insulated roof panel
35mm Min
Top sheet turned down on site with roof pitches below 4˚
KS1000 RW/ LPCB wall panel vertically laid
60mm
Profiled filler sealed top and bottom with gun-grade Air seal - 8mm Ø butyl rubber sealant Factory made thermally broken membrane lined gutter with PIR board insulation to 0.25 or 0.35 W/m2K U-value Purlin
Gutter outlet Eaves beam gutter support
Building Regulations Part L2 Thermal Data 0.25 W/m2K gutter 0.35 W/m2K gutter
fmin = 0.90 fmin = 0.90
Y = 0.13 Y = 0.21
0.35 sole width 300mm and depth 150mm, values for other widths available on request. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
57
ENHANCED
KS1000 LP Roof Systems PARAPET DETAIL - BOUNDARY WALL GUTTER Parapet flashing with 150mm sealed butt straps Site applied PIR board insulation Site applied Alfasbond fire rated (FR) canister insulation Parapet rail with air seal - Vapourflex tape to rail joints Air seal - 6mm Ø butyl rubber sealant Profiled filler sealed top and bottom with gun-grade sealant
Air seal - 6mm Ø bead of gun-grade sealant Sheeting rail 4mm Ø butyl rubber sealant
Air seal - 6mm Ø butyl rubber sealant Site applied Alfasbond fire rated (FR) canister insulation
KS1000 MR/ LPCB wall panel horizontally laid
75mm
35mm Min
KS1000 RW/ LPCB wall panel vertically laid
60mm
KS1000 LP/LPCB insulated roof panel
Top sheet turned down on site with roof pitches below 4˚ Gun-grade seal at panel joints inline with 8mm butyl Air seal - 8mm Ø butyl rubber sealant Factory made thermally broken membrane lined gutter with PIR board insulation to 0.25 or 0.35 W/m2K U-value
Direction of Lay
Purlin
Gutter outlet Eaves beam gutter support
Building Regulations Part L2 Thermal Data 0.25 W/m2K gutter fmin = 0.90 Y = 0.13 W/mK 0.35 W/m2K gutter fmin = 0.90 Y = 0.21 W/mK 0.35 sole width 300mm and depth 150mm, values for other widths available on request. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
58
ENHANCED
KS1000 LP Roof Systems EAVES DETAIL - EXTERNAL GUTTER Gutter support 0.7mm thick double sided plastisol coated Top sheet turned down on site with roof pitches below 4˚ 9mm x 3mm butyl rubber sealant
g centres 200mm fixin
g centres 200mm fixin
Stitching screw fixings for gutter brackets
75mm
KS1000 LP/LPCB insulated roof panel Gun-grade seal at panel joints inline with 8mm butyl Air seal - 8mm Ø butyl rubber sealant Air seal - 6mm Ø butyl rubber sealant Site applied Alfasbond fire rated (FR) canister insulation
Double sided plastisol Highline type gutter
* 20 35 20 mm mm mm
Eaves beam
*
Air seal - Vapourflex sealant is to be applied over any breaks in supporting secondary steelwork to give a continuous bearing face.
KS1000 RW/LPCB wall panel vertically laid
Building Regulations Part L2 Thermal Data fmin = 0.92
Y = 0.27 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
EAVES DETAIL - EXTERNAL GUTTER Gutter support 0.7mm thick double sided plastisol coated Top sheet turned down on site with roof pitches below 4˚ 9mm x 3mm butyl rubber sealant
g centres 200mm fixin
g centres 200mm fixin
Stitching screw fixings for gutter brackets
75mm Approx
KS1000 LP/LPCB insulated roof panel Gun-grade seal at panel joints inline with 8mm butyl Air seal - 8mm Ø butyl rubber sealant Air seal - 6mm Ø bead of gun-grade sealant Site applied Alfasbond fire rated (FR) canister insulation
Double sided plastisol Highline type gutter Eaves beam KS1000 MR/LPCB wall panel horizontally laid
* 20 35 20 mm mm mm
*
Air seal - Vapourflex sealant is to be applied over any breaks in supporting secondary steelwork to give a continuous bearing face.
Building Regulations Part L2 Thermal Data fmin = 0.95
Y = 0.13 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
59
ENHANCED
KS1000 LP Roof Systems VALLEY GUTTER DETAIL Gun-grade seal at panel joints inline with 8mm butyl
Cover cap 75mm
Top sheet turned down on site with roof pitches below 4˚
Air seal - 8mm Ø butyl rubber sealant Stanchion head tie if necessary as steelwork design
Factory made thermally broken membrane lined gutter with PIR board insulation to 0.25 or 0.35 W/m2K U-value Gutter outlet offset to miss stanchion head tie
Air seal - 8mm Ø butyl rubber sealant Purlin
Building Regulations Part L2 Thermal Data 0.25 W/m2K gutter fmin = 0.96 Y = 0.13 W/mK 0.35 W/m2K gutter fmin = 0.96 Y = 0.25 W/mK 0.35 sole width 600mm and depth 150mm, values for other widths available on request. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
60
ENHANCED
KS1000 LP Roof Systems VERGE DETAIL - WALL CLADDING (START OF ROOF SHEETING)
Direction of Lay
Verge flashing with 150mm sealed butt straps PIR board insulation with site applied Alfasbond fire rated (FR) canister insulation to fill any gaps if required to maintain continuity of insulation 20mm x 3mm butyl rubber sealant Cleader angle by steel sub-contractor with air seal Vapourflex sealant applied at joints KS1000 LP/LPCB insulated roof panel
Purlin Air seal - 8mm Ø butyl rubber sealant Air seal - 6mm Ø butyl rubber sealant Gable rafter KS1000 RW/LPCB insulated wall panel horizontally laid Building Regulations Part L2 Thermal Data fmin = 0.96
4mm Ø butyl rubber sealant
Y = 0.01 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
VERGE DETAIL - WALL CLADDING (START OF ROOF SHEETING)
Direction of Lay
Verge flashing with 150mm sealed butt straps PIR board insulation with site applied Alfasbond fire rated (FR) canister insulation to fill any gaps if required to maintain continuity of insulation 20mm x 3mm butyl rubber sealant Cleader angle by steel sub-contractor with air seal Vapourflex sealant applied at joints KS1000 LP/LPCB insulated roof panel
Purlin Air seal - 8mm Ø butyl rubber sealant Air seal - 6mm Ø bead of gun-grade sealant Gable rafter KS1000 MR/LPCB insulated wall panel horizontally laid Building Regulations Part L2 Thermal Data fmin = 0.96
Y = 0.01 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
4mm Ø butyl rubber sealant
61
ENHANCED
KS1000 LP Roof Systems VERGE DETAIL - WALL CLADDING (END OF ROOF SHEETING) Verge flashing with 150mm sealed butt straps PIR board insulation with site applied Alfasbond fire rated (FR) canister insulation to fill any gaps if required to maintain continuity of insulation 20mm x 3mm butyl rubber sealant Cleader angle by steel sub-contractor with air seal Vapourflex sealant applied at joints KS1000 LP/LPCB insulated roof panel
Direction of Lay
Purlin Air seal - 8mm Ø butyl rubber sealant Air seal - 6mm Ø butyl rubber sealant Gable rafter KS1000 RW/LPCB insulated wall panel vertically laid Profiled filler sealed top and bottom with gun-grade sealant
Building Regulations Part L2 Thermal Data fmin = 0.96
Y = 0.01 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
VERGE DETAIL - WALL CLADDING (END OF ROOF SHEETING) Verge flashing with 150mm sealed butt straps PIR board insulation with site applied Alfasbond fire rated (FR) canister insulation to fill any gaps if required to maintain continuity of insulation
Direction of Lay
20mm x 3mm butyl rubber sealant Cleader angle by steel sub-contractor with air seal Vapourflex sealant applied at joints KS1000 LP/LPCB insulated roof panel
Purlin Air seal - 8mm Ø butyl rubber sealant Air seal - 6mm Ø bead of gun-grade sealant Gable rafter KS1000 MR/LPCB insulated wall panel horizontally laid 4mm Ø butyl rubber sealant
Building Regulations Part L2 Thermal Data fmin = 0.96
Y = 0.01 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
62
ENHANCED
KS1000 LP Roof Systems VALLEY HIP DETAIL
Double sided plastisol coated flashing
Cover cap KS1000 LP/LPCB insulated roof panel
Gun-grade seal at panel joints inline with 8mm butyl
Edge protection lacquer applied to all panels cut on site to suit rake angle Air seal - 8mm Ø butyl rubber sealant Cleader angle by steelwork contractors
Factory made thermally broken membrane lined gutter with PIR board insulation to 0.25 or 0.35 W/m2K U-value
Building Regulations Part L2 Thermal Data fmin = 0.94
Hip rafter
Purlin
Y = 0.29 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
HIP DETAIL Hip flashing with 150mm sealed butt straps Panels site cut to suit rake angle
Site applied Alfasbond fire rated (FR) canister insulation Outer sheet turned up on site with roof pitches below 4˚
Apex dam (Ref: LP1/A) Rake cut profiled filler sealed top and bottom with gun-grade sealant KS1000 LP/LPCB insulated roof panel
Air seal - 8mm Ø butyl rubber sealant Internal ridge flashing with 150mm overlap sealed with Vapourflex or gun-grade sealant Building Regulations Part L2 Thermal Data fmin = 0.97
Y = 0.004 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
Cover cap 20mm x 3mm butyl rubber sealant 2 No. runs of silicone sealant
Purlin Cleader angle by steelwork contractor Hip rafter
63
ENHANCED
KS1000 RW Wall Systems Vertically laid DRIP DETAIL
Stanchion Optional internal closure flashing to mask insulation from view Sheeting rail Air seal - 6mm Ø butyl rubber sealant PIR board insulation with Alfasbond (FR) canister applied insulation to fill any gaps if required to maintain continuity of insulation 100mm min. 35mm lap over wall min
Panels specified with flush ends will have a minimum cut back of 10mm
Drip flashing Air seal - continuous bead of gun-grade sealant Building Regulations Part L2 Thermal Data fmin = 0.64
Y = 0.54 W/mK
The appropriate Y value for the brickwork, blocks or concrete must be added to the above Y value to obtain the total loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
EXTERNAL CORNER DETAIL
Corner column Sheeting rail KS1000 RW/LPCB insulated wall panel vertically laid Air seal - 6mm Ø butyl rubber sealant
Internal cleader angle by steel sub-contractor with air seal Vapourflex sealant applied at joints Zed support lapped 100mm at joints Site cut vertical sheeting PIR board insulation with site applied air seal Alfasbond fire rated (FR) canister insulation to fill any gaps if required to maintain continuity of insulation External corner flashing with 100mm sealed overlaps On site remove overlap leg from panel Direction of Lay
9mm x 3mm butyl rubber sealant KS1000 RW/LPCB insulated wall panel vertically laid
Building Regulations Part L2 Thermal Data fmin = 0.95
Y = 0.01 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
64
ENHANCED
KS1000 RW Wall Systems Vertically laid WINDOW HEAD AND CILL DETAIL Air seal - 6mm Ø butyl rubber sealant
Building Regulations Part L2 Thermal Data fmin = 0.50
Y = 0.61 W/mK
PIR board insulation
The appropriate Y value for the window system must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
Optional internal head flashing Window support rail
Head flashing
Internal head flashing (optional) with no connection to external soffit flashing
9mm x 3mm butyl rubber sealant
Window depth to suit panel module
25mm thick PIR board insulation
External soffit flashing with no connection to internal flashing Polyethylene backing rod with silicone sealant by window installer
Window unit by others Site applied Alfasbond fire rated (FR) canister insulation Window cill flashing with 3° slope to facilitate drainage (no connection to internal flashing) Profiled filler sealed top and bottom with gun-grade sealant
Ferrules used to fix windows
Building Regulations Part L2 Thermal Data fmin = 0.95
Air seal - 6mm Ø butyl rubber sealant
Y = 0.07 W/mK
The appropriate Y value for the window system must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
WINDOW JAMB DETAIL OPTION 1
WINDOW JAMB DETAIL OPTION 2
Window width Internal jamb flashing with no connection to external flashing 25mm thick PIR board insulation Jamb steelwork Window unit by others
Polyethylene backing rod with silicone sealant Air seal - 6mm Ø butyl rubber sealant External jamb flashing with no connection to internal flashing Site cut panel Building Regulations Part L2 Thermal Data 9mm x 3mm butyl rubber sealant
fmin = 0.96
Y = 0.08 W/mK
The appropriate Y value for the window system must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
65
ENHANCED
KS1000 RW Wall Systems Vertically laid PERSONNEL DOOR DETAIL (DOOR HEAD PANEL SITE CUT) B
+2100mm
B A
A
Door frame by others
Expanding type anchor fixing by others
Pressed metal base channel or RSA by others
F.F.L. 0.00mm 900mm
DOOR JAMB DETAIL A-A Galvanised door post by steel sub-contractor with Vapourflex sealant applied to joints
DOOR HEAD DETAIL B-B Air seal - 6mm Ø butyl rubber sealant PIR board insulation
Internal jamb flashing with no connection to external flashing
Optional internal head flashing
25mm thick PIR board insulation Ferrules used to fix doors
Galvanised door head 25mm thick PIR board insulation Internal head flashing (optional) with no connection to external soffit flashing Door & frame by others fixed to steel support frame
Polyethylene backing rod with silicone sealant
External soffit flashing with no connection to internal flashing
Air seal - 6mm Ø butyl rubber sealant
External jamb flashing with no connection to internal flashing
Building Regulations Part L2 Thermal Data fmin = 0.96
Y = 0.08 W/mK
The appropriate Y value for the door system must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
9mm x 3mm butyl rubber sealant
9mm x 3mm butyl rubber sealant
Door head flashing Note: For opening outward door ensure drip flashing is clear top of door Building Regulations Part L2 Thermal Data fmin = 0.50
Y = 0.61 W/mK
The appropriate Y value for the door system must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
66
ENHANCED
KS1000 RW Wall Systems Vertically laid
Air seal - 6mm Ø butyl rubber sealant PIR board insulation Head flashing
9mm x 3mm butyl rubber sealant 70mm thick PIR board insulation
Drum
e lop le s iab r a V
Roller guide supported from main structure
Clear door height
Optional closure flashing
See door manufacturers details for height required
UP AND OVER DOOR HEAD DETAIL
60mm return to soffit flashing External soffit flashing RSC door post Building Regulations Part L2 Thermal Data fmin = 0.51
Y = 0.62 W/mK
The appropriate Y value for the door system must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
DOOR JAMB DETAIL Door guide by others Door by others
Air seal RSC door post Sheeting rail 70mm thick PIR board insulation with site applied Alfasbond fire rated (FR) canister insulation filling gaps Internal cleader angle by steel sub-contractor with Vapourflex seal applied to joints Air seal - 6mm Ø butyl rubber sealant Site cut panel
Door jamb flashing 9mm x 3mm butyl rubber sealant Note: Roller shutter doors to be well insulated and have sealed joints, head, jamb and at floor.
9mm x 3mm butyl rubber sealant
Clear door width
Building Regulations Part L2 Thermal Data fmin = 0.76
Y = 0.81 W/mK
The appropriate Y value for the door system must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
67
ENHANCED
KS1000 MR/EB/FL-S/MM/CX/WV Wall Systems Horizontally laid PARAPET DETAIL - BOUNDARY WALL GUTTER Parapet fixing with 150mm sealed butt straps 80mm PIR approved insulation board Site applied Alfasbond fire rated (FR) canister insulation Parapet rail air seal Vapourflex tape to rail joints Air seal - 6mm Ø butyl rubber sealant
Profiled filler sealed top and bottom with gun-grade sealant Air seal - 6mm Ø bead of gun-grade sealant 4mm Ø butyl rubber sealant
Air seal - 6mm Ø butyl rubber sealant Site applied Alfasbond fire rated (FR) canister insulation as panel is placed
KS1000 MR/LPCB insulated wall panel horizontally laid
KS1000 RW/LPCB insulated roof panel
35mm Min
KS1000 RW/LPCB insulated roof panel vertically laid
60mm
Factory made membrane lined gutter with PIR board insulation 0.25 or 0.35 W/m2K U value
Air seal - 8mm Ø butyl rubber sealant
Purlin
Direction of Lay
Gutter outlet Eaves beam gutter support with expandable seal
Building Regulations Part L2 Thermal Data 0.25 W/m2K gutter fmin = 0.90 Y = 0.13 W/mK 0.35 W/m2K gutter fmin = 0.90 Y = 0.21 W/mK 0.35 sole width 300mm and depth 150mm, values for other widths available on request. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
68
ENHANCED
KS1000 MR/EB/FL-S/MM/CX/WV Wall Systems Horizontally laid EAVES DETAIL - EXTERNAL GUTTER
Gutter support 0.7mm thick double sided plastisol coated
75mm Approx
centres 0mm fixing centres 20 g in fix m 200m
9mm x 3mm butyl rubber sealant
KS1000 RW/LPCB insulated roof panel Air seal - 8mm Ø butyl rubber sealant
Double sided Plastisol “High line” type gutter
20 35 20 mm mm mm
*
Eaves beam
Site applied Alfasbond fire rated (FR) canister insulation KS1000 MR/LPCB insulated wall panel horizontally laid
Air seal - 6mm Ø bead of gun-grade sealant
Building Regulations Part L2 Thermal Data Direction of Lay
*
Air seal - Vapourflex sealant is to be applied over any breaks in supporting secondary steelwork to give a continuous bearing face.
fmin = 0.95
Y = 0.13 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
69
ENHANCED
KS1000 MR/EB/FL-S/MM/CX/WV Wall Systems Horizontally laid VERGE DETAIL - WALL CLADDING (START OF ROOF SHEETING) Verge flashing with 150mm sealed butt straps PIR board insulation with fire rated Alfasbond (FR) canister insulation to fill any gaps if required to maintain continuity of insulation Verge zed support lapped 150mm at joints
Direction of Lay
Cleader angle by steel sub-contractor with air seal Vapourflex sealant applied to joints KS1000 RW/LPCB insulated roof panel
9mm x 3mm butyl rubber sealant
4mm Ø butyl rubber sealant
KS1000 MR/LPCB insulated wall panel horizontally laid Air seal - 8mm Ø butyl rubber sealant Air seal - 6mm Ø bead of gun-grade sealant Purlin Gable rafter Vertical sheeting rail
Direction of Lay
Building Regulations Part L2 Thermal Data fmin = 0.96
Y = 0.01 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
VERGE DETAIL - WALL CLADDING (END OF ROOF SHEETING) Verge flashing with 150mm sealed butt straps PIR board insulation with fire rated Alfasbond (FR) canister insulation to fill any gaps if required to maintain continuity of insulation Verge zed support lapped 150mm at joints Cleader angle by steel sub-contractor with Vapourflex sealant applied to joints Site cut KS1000 RW/LPCB insulated roof panel to suit
Direction of Lay
9mm x 3mm butyl rubber sealant
4mm Ø butyl rubber sealant
Air seal - 8mm Ø bead of gun-grade sealant
KS1000 MR/LPCB insulated wall panel horizontally laid
Air seal - 6mm Ø bead of gun-grade sealant Purlin Gable rafter Vertical sheeting rail Building Regulations Part L2 Thermal Data fmin = 0.96
Y = 0.01 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
Direction of Lay
70
ENHANCED
KS1000 MR/EB/FL-S/MM/CX/WV Wall Systems Horizontally laid EXTERNAL CORNER DETAIL KS1000 MR/LPCB horizontally Laid
Air seal - 4mm Ø bead of gun-grade sealant Corner column
Air seal - 4mm Ø bead of gun-grade sealant Air seal - gun-grade sealant to male joint Internal cleader angle by steel sub-contractor with air seal - Vapourflex sealant applied at joints
Vertical sheeting rail
AWP joint filler and silicone sealant
PIR board insulation with Alfasbond FR canister applied insulation to fill any gaps if required to maintain continuity of insulation External corner flashing with 100mm overlaps
KS1000 MR/LPCB horizontally laid
4mm Ø butyl rubber sealant
Building Regulations Part L2 Thermal Data fmin = 0.96
Y = 0.01 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
EXTERNAL PRE-FORMED CORNER DETAIL
For vertical joint details see page 71
KS1000 MR/LPCB horizontally laid pre-formed insulated corner panel
Pre-formed panel maximum unsupported length 1000mm. For longer panels additional steelwork is required.
Building Regulations Part L2 Thermal Data fmin = 0.96
Y = 0.01 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
71
ENHANCED
KS1000 MR/EB/FL-S/MM/CX/WV Wall Systems Horizontally laid VERTICAL JOINT DETAILS VERTICAL JOINT OPTION A
PIR board insulation with fire rated Alfasbond (FR) canister insulation to fill any gaps if required to maintain continuity of insulation
Min. Steel bearing face 130mm
35mm
Air seal - EPDM bubble gasket 95x10mm. Kingspan (Ref: VJ2)
40mm
Air seal - gun-grade sealant to male joint
35mm
“Snap on” cover flashing
AWP joint filler and gun-grade sealant
OPTION A RECESSED
30mm 15 15
KS1000 MR/LPCB insulated wall panel horizontally laid
35mm
30mm
35mm
“Snap on” receiver flashing (30mm deep)
15mm recess to“Snap on” cover flashing Building Regulations Part L2 Thermal Data
4mm Ø butyl rubber sealant site applied
fmin = 0.96
Y = 0.01 W/mK
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values. For joint spacings of 1000mm or more, the above Y value is included within the U value of the insulated panel.
Min. Steel bearing face 130mm
VERTICAL JOINT OPTION B Air seal - EPDM bubble gasket 95x10mm. Kingspan (Ref: VJ2)
35mm
35mm
PIR board insulation with fire rated Alfasbond (FR) canister insulation to fill any gaps if required to maintain continuity of insulation
35mm
AWP joint filler and gun-grade sealant
Air seal - gun-grade sealant to male joint
30mm KS1000 MR/LPCB insulated wall panel horizontally laid
Building Regulations Part L2 Thermal Data 35mm
30mm
35mm
“Snap on” receiver flashing (30mm deep)
Y = 0.01
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values. For joint spacings of 1000mm or more, the above Y value is included within the U value of the insulated panel.
4mm Ø butyl rubber sealant site applied
OPTION F
fmin = 0.96
Min. Steel bearing face 130mm
Air seal - EPDM bubble gasket 95x10mm. Kingspan (Ref: VJ2)
35mm
35mm
35mm
AWP joint filler and gun-grade sealant
PIR board insulation with fire rated Alfasbond (FR) canister insulation to fill any gaps if required to maintain continuity of insulation
Air seal - gun-grade sealant to male joint
25mm KS1000 MR/LPCB insulated wall panel horizontally laid 9mm x 4mm PVC sealant (site applied)
Optional push in MG02 or snap in MXS02 28mm 19mm 28mm Building Regulations Part L2 Thermal Data fmin = 0.96
TH25 extruded aluminium top hat section (25mm deep)
Y = 0.01
The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values. For joint spacings of 1000mm or more, the above Y value is included within the U value of the insulated panel.
72
ENHANCED
KS1000 MR/EB/FL-S/MM/CX/WV Wall Systems Horizontally laid WINDOW HEAD AND CILL DETAIL Building Regulations Part L2 Thermal Data fmin = 0.34
Air seal - 6mm bead of gun-grade sealant
Y = 0.83 W/mK PIR board insulation
The appropriate Y value for the window system must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
Optional internal head flashing
Panel bearer at 1500mm centres
Window support rail
Head flashing Internal head flashing (optional) with no connection to external soffit flashing
4mm Ø butyl rubber sealant
Window depth to suit panel module
25mm thick PIR board insulation External soffit flashing with no connection to internal flashing Polyethylene backing rod with silicone sealant by window installer
Window unit by others Site applied Alfasbond fire rated (FR) canister insulation
Ferrules used to fix window
Window cill flashing with 3° slope to facilitate drainage (no connection to internal flashing) Air seal - 6mm bead of gun-grade sealant Building Regulations Part L2 Thermal Data fmin = 0.93
Y = 0.10 W/mK
4mm Ø butyl rubber sealant
The appropriate Y value for the window system must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
WINDOW JAMB DETAIL Window opening Jamb steelwork Internal jamb flashing with no connection to external flashing Site applied 25mm thick PIR board insulation with Alfasbond fire rated (FR) canister insulation filling gaps to maintain insulation prior to placing board Polyethylene backing rod with silicone sealant by window installer
Window unit by others External jamb flashing with no connection to internal flashing Air seal - 6mm bead of gun-grade sealant Site cut panel Air seal - Gun-grade sealant to male joint AWP joint filler and gun-grade sealant 4mm Ø Butyl rubber sealant Building Regulations Part L2 Thermal Data fmin = 0.96
Y = 0.08 W/mK
The appropriate Y value for the window system must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
73
ENHANCED
KS1000 MR/EB/FL-S/MM/CX/WV Wall Systems Horizontally laid PERSONNEL DOOR DETAIL (DOOR HEAD PANEL SITE CUT)
DOOR JAMB DETAIL A-A 25mm thick PIR board insulation with site applied Alfasbond fire rated (FR) canister insulation filling gaps to maintain insulation prior to placing board
Galvanised door post by steel sub-contractor with Vapourflex sealant applied to joints Internal jamb flashing with no connection to external flashing B
+2100mm
Ferrules used to fix doors
B
A
A
Polyethylene backing rod with silicone sealant by door installer External jamb flashing with no connection to internal flashing
Door frame by others
Air seal - 6mm Ø bead of gun-grade sealant
Building Regulations Part L2 Thermal Data fmin = 0.96
Expanding type anchor fixing
900mm
4mm Ø butyl rubber sealant
AWP joint filler and gun-grade sealant
Pressed metal base channel or RSA by others
Y = 0.08 W/mK
The appropriate Y value for the door system must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
F.F.L. 0.00mm
DOOR HEAD DETAIL B-B Optional internal head flashing Air seal - 6mm bead of gun-grade sealant PIR board insulation Galvanised door head 25mm thick PIR board insulation Optional internal head flashing with no connection to external soffit flashing Door & frame by others fixed to steel support frame External soffit flashing with no connection to internal flashing Note: For opening outward door ensure door head flashing is sufficiently high enough to clear top of door
4mm Ø butyl rubber sealant Door head flashing
Building Regulations Part L2 Thermal Data fmin = 0.51
Y = 0.62 W/mK
The appropriate Y value for the door system must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
74
ENHANCED
KS1000 MR/EB/FL-S/MM/CX/WV Wall Systems Horizontally laid DRIP DETAIL - ABOVE FLOOR LEVEL Column face Vertical rail KS1000 MR/LPCB insulated wall panel horizontally laid Optional internal closure flashing to mask insulation from view Galvanised drip support angle 80mm thick PIR board insulation with Alfasbond FR canister applied insulation used to fill gap, if required Air seal - 6mm bead of gun-grade sealant
Panel bearer at ends of panel & max. 1500mm centres between Building Regulations Part L2 Thermal Data fmin = 0.33
Y = 0.60 W/mK
Drip flashing Air seal - continuous bead of gun-grade sealant
The appropriate Y value for the brickwork, blockwork or concrete must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
DRIP DETAIL - BELOW FLOOR LEVEL Column face Vertical rail
KS1000 MR/LPCB insulated wall panel horizontally laid Optional internal closure flashing to mask insulation from view Air seal - 6mm bead of gun-grade sealant Galvanised drip support angle 80mm thick PIR board insulation with Alfasbond FR canister applied insulation used to fill gap, if required Air seal - continuous bead of gun-grade sealant Both support angles fixed together prior to placing Galvanised drip support angle
Building Regulations Part L2 Thermal Data fmin = 0.60
Y = 0.35 W/mK
The appropriate Y value for the brickwork, blockwork or concrete must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
Panel bearer at ends of panel & max. 1500mm centres between Drip flashing
75
ENHANCED
KS1000 MR/EB/FL-S/MM/CX/WV Wall Systems Horizontally laid UP AND OVER DOOR HEAD DETAIL
Air seal - 6mm bead of gun-grade sealant
PIR board insulation
Head flashing
See door manufacturers details for height required
Drum
Internal door head flashing - optional e lop le s iab r a V
Roller guide supported from main structure
70mm thick PIR board insulation
Clear door height
60mm return to soffit flashing. 4mm Ø butyl sealant
Door guide with air seal External soffit flashing RSC door post
Building Regulations Part L2 Thermal Data fmin = 0.51
Y = 0.63 W/mK
The appropriate Y value for the door system must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
DOOR JAMB DETAIL
Door guide with air seals
Site cut panel Air seal - 6mm bead of gungrade sealant
70mm thick PIR board insulation with Alfasbond fire rated (FR) canister insulation filling gaps to maintain insulation prior to placing board
Air seal - 6mm bead of gun-grade sealant Bridging seal to male joint
RSC door posts by steel subcontractor with Vapourflex sealant applied at joints Door jamb flashing
4mm Ø butyl rubber sealant Building Regulations Part L2 Thermal Data fmin = 0.74
Y = 0.71 W/mK
The appropriate Y value for the door system must be added to the above Y value to obtain the total heat loss through this junction detail. The above values are only applicable to the components on this detail. Changes to the components will have an effect on the given values.
Clear door width
AWP joint filler and gungrade sealant
Note: Roller shutter doors to be well insulated and have sealed joints, head, jamb and at floor.
Kingspan Insulated Roof & Wall Systems Roof Systems KS1000 RW Trapezoidal
KS1000 TS Tile Support
KS1000 Kingzip
KS1000 LP Low Pitched
KS1000 CR Curved
Available Q1 2003
Wall Systems KS600, 900 & 1000 Optimo
KS600, 900 & 1000 MR Micro-Rib
KS600, 900 & 1000 MM Mini-Micro
KS600, 900 & 1000 CX Convex
KS600, 900 & 1000 EB Euro-Box
KS600, 900 & 1000 WV Wave
KS600, 900 & 1000 FL-S Flat (Stucco)
KS1000 RW Trapezoidal
Insulated Temperature Control Systems KS1200 CS
Telephone: +44 (0) 1352 716110, Fax: +44 (0) 1352 716161, Email:
[email protected] www.kingspanpanels.com