alstom pd521

March 24, 2018 | Author: Rajesh Bodduna | Category: Power Supply, Electromagnetic Compatibility, Electrical Connector, Electrical Impedance, Relay
Share Embed Donate


Short Description

Download alstom pd521...

Description

PD 521 Distance Protection Device Version -302 -401 -602 -303 -402 -602 with Documentation for Version -303 -402 -502



PD 521 Distance Protection Device Version Version

-302 -303

-401 -402

-602 -602

Update Documentation for Version -303

-402

-502

!

Warning When electrical equipment is in operation, dangerous voltage will be present in certain parts of the equipment. Failure to observe warning notices, incorrect use or improper use may endanger personnel and equipment and cause personal injury or physical damage. Before working in the terminal strip area, the device must be isolated. Where stranded conductors are used as connecting leads, wire end ferrules must be employed. Proper and safe operation of this device depends on appropriate shipping and handling, proper storage, installation and commissioning, and on careful operation, maintenance and servicing. For this reason only qualified personnel may work on or operate this device.

Qualified Personnel are individuals who o are familiar with the installation, commissioning and operation of the device and of the system to which it is being connected; o are able to perform switching operations in accordance with safety engineering standards and are authorized to energize and de-energize equipment and to isolate, ground and label it; o are trained in the care and use of safety apparatus in accordance with safety engineering standards; o are trained in emergency procedures (first aid).

Note The operating manual for this device gives instructions for its installation, commissioning and operation. However, the manual cannot cover all conceivable circumstances or include detailed information on all topics. In the event of questions or specific problems, do not take any action without proper authorization. Contact the appropriate ALSTOM technical sales office and request the necessary information. Any agreements, commitments, and legal relationships and any obligations on the part of ALSTOM, including settlement of warranties, result solely from the applicable purchase contract, which is not affected by the contents of the operating manual.

2

89521-302/-303-401/-402-602/-502 / AFSV.12.06470 EN

Update Documentation: Changes in Version -303 -402 -502

The special version -303 -402 -502 incorporates an extended operating frequency range for the voltage memory and the power swing blocking function in addition to the features and functions of the standard versions -302/-303 -401/-402 -602.

Distance Protection Distance and Directional Measurement The frequency range of the voltage memory is extended. The voltage memory is enabled, if the measured frequency satisfies the following condition:

0.95 × fnom < f < 1.05 × fnom

Power Swing Blocking

When power swing blocking is activated, a distance trip in zones 1 to 5 is prevented if there are power swings in the network.

Three-pole distance protection starting with and without ground initiates the start delay of the power swing blocking function. The start delay is intended to enable release in zone 1. After the settable start delay has elapsed, the device checks to determine whether the phase-to-phase voltage 1VA-B is greater than 0.1 × Vnom . If this condition is satisfied, then the apparent power S is calculated from the quantities 1VA-B and IA-B . The amount of change in apparent power as referred to the apparent power at that moment is determined every 40 ms.

S1 - S 2 S2 S1: apparent power at time t1 S2: apparent power at time t1 + 40 ms If the difference is greater than the set value, a blocking signal is formed to block the distance trip for zones 1 to 5. This signal is extended by the settable release delay. Power swing blocking is blocked if the monitoring function of the voltage-measuring circuit operates.

U-1 Power swing blocking

The following figures show the formation of distance decisions for the Zone 4 operating modes Normal, Section cable-line and Section line-cable.

89521-302/-303-401/-402-602/-502 / AFSV.12.06470 EN

These figures replace figures 29, 32 and 34 in the manual for the standard versions.

U-1

Update Documentation: Changes in Version -303 -402 -502 (continued)

U-2 Formation of distance decisions, with zone 4 operating normally

U-2

89521-302/-303-401/-402-602/-502 / AFSV.12.06470 EN

Update Documentation: Changes in Version -303 -402 -502 (continued)

U-3 Formation of distance decisions, impedance zone 4: cable

89521-302/-303-401/-402-602/-502 / AFSV.12.06470 EN

U3

Update Documentation: Changes in Version -303 -402 -502 (continued)

U-4 Formation of distance decisions, impedance zone 4: line

U-4

89521-302/-303-401/-402-602/-502 / AFSV.12.06470 EN

Update Documentation: Changes in Version -303 -402 -502 (continued)

The new Addresses related to the Power Swing Blocking function are as follows: Setting parameters Address Description x y

14 14 14 14

50 52 53 54

PSB: PSB: PSB: PSB:

Enabled Start delay Release delay Threshold value

Change

Default Range of Values

Unit or Meaning

on on on on

0 0.20 0.20 25

no / yes s s %

Change

Default Range of Values

0 / 1 0.06 ... 1.00 0.06 ... 1.00 1 ... 50

Increment

0.01 0.01 1

State Signals Address Description x y

36 32 36 58

PSB: Blocking initiated PSB: Start delay running

-

0 / 1 0 / 1

Unit or Meaning

Increment

no / yes no / yes

These state signals can be assigned to binary outputs as well as to LED indicators.

89521-302/-303-401/-402-602/-502 / AFSV.12.06470 EN

U5

Modifications After Going to Press

89521-302/-303-401/-402-602/-502 / AFSV.12.06470 EN

3

4

89521-302/-303-401/-402-602/-502 / AFSV.12.06470 EN

Table of Contents

1

Application and Scope

7

2 2.1 2.2 2.3 2.3.1 2.3.2 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11

Technical Data Conformity Statement General Data Tests Type Tests Routine Tests Environmental Conditions Inputs and Outputs Interfaces Information Output Settings Typical Characteristics Deviations Power Supply

8 8 8 8 8 9 9 10 10 11 11 11 11 12

3 3.1 3.2 3.3 3.3.1 3.3.2 3.3.3 3.3.4 3.4 3.5

Operation Modular Structure Man-Machine Communication Distance Protection Starting Selection of Measured Variables Distance and Directional Measurement Impedance-Time Characteristics Measuring Circuit Monitoring Backup Overcurrent-Time Protection (BUOC or Backup DTOC) Switch on to Fault Protection Protective Signaling Circuit Breaker Failure Protection Ground Fault Direction Determination Using Steady-State Values GFD Evaluation (Ground Fault Direction) GF Evaluation (Ground Fault) Ground Fault Data Acquisition Starting Signals and Tripping Logic Overcurrent Signal Operating Data Measurement Fault Recording Fault Logging Measured Fault Data Fault Data Acquisition Self-Monitoring and Fault Diagnosis Serial Interfaces PC Interface ILSA Interface

13 13 13 14 16 24 25 34 42 46

3.6 3.7 3.8 3.9 3.9.1 3.9.2 3.9.3 3.10 3.11 3.12 3.13 3.13.1 3.13.2 3.13.3 3.14 3.15 3.15.1 3.15.2

89521-302/-303-401/-402-602/-502 / AFSV.12.06470 EN

47 48 56 56 57 61 62 65 67 68 71 73 73 77 78 79 80 81

4

Design

82

5 5.1 5.2 5.3 5.4 5.5 5.6 5.6.1 5.6.2 5.6.3 5.6.4 5.6.5

Installation and Connection Unpacking and Packing Checking Nominal Data and Design Type Location Requirements Installation Protective and System Grounding Connection Measuring and Auxiliary Circuits Binary Control Inputs Tripping and Signaling Circuits PC Interface ILSA Interface

84 84 84 84 85 87 87 87 93 93 93 93

6 6.1 6.2 6.3 6.4 6.5 6.5.1 6.5.2 6.6 6.7 6.8

Control Display and Keyboard Address Selection Change-Enabling Function Changing Settings Memory Readout Signal Memory Readout Monitoring Signal Memory Readout Resetting Password-Protected Control Operations Keyboard Lock

94 94 95 95 96 97 97 99 100 101 102

7 7.1 7.1.1 7.1.2 7.2 7.2.1 7.2.2 7.2.3 7.2.4 7.3 7.3.1 7.3.2 7.3.3

Settings Device Identification Ordering Information Design Version Configuration Parameters Control Interfaces Binary Inputs Binary Outputs LED Indicators Function Parameters Global Main Functions Supplementary Functions

103 103 103 104 104 104 106 106 107 107 107 108 111

8 8.1 8.2 8.3 8.4

Information and Control Functions Measured Values State Signals Counters Control and Testing

116 116 118 119 120

5

Table of Contents (continued)

9

Commissioning

122

10

Troubleshooting

137

11

Maintenance

140

12

Storage

143

13

Accessories and Spare Parts

144

14

Ordering Information

145

Appendix

147

6

89521-302/-303-401/-402-602/-502 / AFSV.12.06470 EN

1 Application and Scope

PD 521 distance protection devices are used for selective short-circuit protection in high-voltage systems. The systems can be operated with impedance grounding, with ground fault compensation or with isolated neutral. The PD 521, a single-system distance protection device, has the following protective functions: ¨

Overcurrent fault detection logic with optional undervoltage fault detection logic

¨

Underimpedance fault detection logic with load blinding

¨

Distance measurement with selection of polygonal or circular characteristic

Besides the functions listed above, as well as measuring circuit monitoring and comprehensive self-monitoring, the following functions are always available in the PD 521 for optimum fault evaluation and system management: ¨

Measuring circuit monitoring

¨

Operating data measurement

¨

Event counting

¨

Ground fault data acquisition

¨

Time-tagged fault logging

¨

Fault data acquisition (including fault localization)

¨

Fault recording

¨

Four distance stages, including one that can be used as a special stage

¨

Six timer stages, including two that act as backup timer stages

¨

Direction voltage memory

¨

Circuit breaker failure protection

¨

Switch on to fault protection

¨

Backup overcurrent time protection (Backup DTOC)

¨

Protective signaling (teleprotection)

o 2 binary signal inputs (optical couplers) with freely configurable function assignment

¨

Ground fault direction determination using steady-state values

o 8 output relays with freely configurable function assignment

The PD 521 has a multifunctional case design that is equally well suited to either wall surface mounting or flush panel mounting due to the reversible terminal blocks and adjustable mounting brackets. The auxiliary voltage for the power supply can be switched internally from 110-250 V DC or 100-230V AC to 24-60 V DC. The PD 521 has the following inputs and outputs: o 4 current-measuring and 3 voltage-measuring inputs

Control and display: o Local control panel o 12 LED indicators, 9 of which allow freely configurable function assignment o PC interface o Optional ILSA interface Information is exchanged either through the integrated local control panel, the integrated PC interface or the optional ILSA interface. The optional ILSA interface provides a system interface for serial link-up of the numerical protection device to a central protection control unit or to a central substation control system.

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

7

2 Technical Data

2.1 Conformity Statement

2.3 Tests

Applicable to the PD 521, version 302-402/403/404-604

2.3.1 Type Tests

Article 10 of EC Directive 72/73/EC. The product designated as "PD 521 Distance Protection Device" has been developed and manufactured in conformity with the international standard EN 60255-6 and in accordance with the EMC Directive and the Low Voltage Directive issued by the European Community. 2.2 General Data Design Case suitable for surface or flush mounting Installation position Vertical ± 30° Degree of device protection IP 51 according to DIN VDE 0470 and EN 60529 or IEC 529 Weight Approx. 4.0 kg Dimensions and connections See Dimensional Drawings and Terminal Connection Diagrams PC interface Connector DIN 41 652, type D-Sub, 9-pin A special connecting cable is required for electrical isolation. ILSA Interface (optional) Optical fibers (-X7 and -X8): optical fiber interface F-SMA. Leads (-X9): Mini Combicon MC 1.5/5-STF-3.81 for wire cross-sections up to 1.5 mm2 flexible. Connections Threaded terminal ends M4, self-centering with wire protection for conductor crosssections from 0.5 mm² to 6 mm² or 2 ´ 2.5 mm²

§

All tests according to EN 60255-6 and DIN 57 435 Part 303 Electromagnetic Compatibility (EMC) Interference suppression According to EN 55022 and DIN VDE 0878 Part 3, class B 1 MHz burst disturbance test § According to IEC 255 Part 22-1, class III Common mode test voltage: 2.5 kV Differential test voltage: 1.0 kV Test duration: >2s Source impedance: 200 W Immunity to electrostatic discharge § According to EN 60801 Part 2, severity level 3 Contact discharge, Single discharges: > 10 Holding time: >5s Test voltage: 6 kV Test generator: 50 to 100 MW, 150 pF/330 W Immunity to radiated electromagnetic energy § According to ENV 50140 , level 3 Antenna distance to tested device: > 1 m on all sides Test field strength, frequ. band 80 to 1000 MHz: 10 V/m Test using AM: 1 kHz / 80 % Single test at 900 MHz: AM 200 Hz / 100 % Electrical fast transient / burst requirements According to IEC 801-4, test severity level 3 Rise time of one pulse: 5 ns Impulse duration (50% value): 50 ns Amplitude: 2 kV / 1 kV Burst duration: 15 ms Burst period: 300 ms Source impedance: 50 W

Creepage distances and clearances § Per EN 61010-1 or IEC 664-1 Pollution degree 3, working voltage 300 V overvoltage category III, impulse test voltage 5 kV

8

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

2 Technical Data (continued)

Surge immunity test According to IEC 1000-4-5, test level 3 Testing of power supply circuits, unsymmetrically / symmetrically operated lines Open-circuit voltage front time / / time to half-value: 1.2 / 50 ms Short-circuit current front time / / time to half-value: 8 / 20 ms Amplitude: 1 / 2 kV Pulse frequency: > 5 / min Source impedance: 12 / 42 W Immunity to conducted disturbances induced by radio frequency fields According to IEC 65A/77B (Sec) 145/110, test level 2 Disturbing test voltage: 3 V Power frequency magnetic field immunity § According to EN 61000-4-8 , level 4 Frequency: 50 Hz Test field strength: 30 A/m

Mechanical Robustness Vibration test § According to IEC 255-21-1 , test severity class 1 Frequency range, in operation: 10 to 60 Hz, 0.035 mm, 60 to 150 Hz, 0.5 g Frequency range, during transport: 10 to 150 Hz, 1 g Shock response and withstand test, bump test § According to IEC 255-21-2 , test severity class 1 Acceleration: 5 g/15 g Pulse duration: 11 ms Seismic test § According to EN 60255-21-3 , test procedure A, class 1 5 to 8 Hz, 3.5/1.5 mm, 2 8 to 35 Hz, 10/5 m/s 3 ´ 1 cycle

Interruptions to and alternating component (ripple) in d.c. auxiliary energizing quantity of measuring relays According to IEC 255-11 12% / 50 ms

2.3.2 Routine Tests

Insulation

Additional thermal test 100 % controlled thermal endurance test, inputs loaded

Voltage test According to IEC 255-5 2 kV AC, 60 s For the voltage test of the power supply inputs, direct voltage (2.8 kV DC) must be used. The PC interface must not be subjected to the voltage test. Impulse voltage withstand test According to IEC 255-5 Front time: 1.2 µs Time to half-value: 50 µs Peak value: 5 kV Source impedance: 500 W

§

All tests according to EN 60255-6 and DIN 57 435 Part 303

2.4 Environmental Conditions Allowable ambient temperatures Operating temp.: - 5 °C to + 55 °C (+ 23 °F to + 131 °F) Storage temp.: - 25 °C to + 55 °C (- 13 °F to + 131 °F) Shipping temp.: - 25 °C to + 70 °C (- 13 °F to + 158 °F) Ambient humidity range Relative humidity to preclude any condensation; 45 to 75 % (annual mean), up to 56 days at £ 95% and 40°C (104 °F)

____________________________________________ Key: § For this EN, ENV or IEC standard, the DIN EN, DINV ENV or DIN IEC edition, respectively, was used in the test.

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

9

2 Technical Data (continued)

2.5 Inputs and Outputs

Binary Outputs (Output Relays)

Measurement Inputs

Number, function assignment and connections: see address list (Appendix C) and terminal connection diagrams (Appendix E)

Current Connection to current transformers Nominal current Inom (per order): 1 A AC or 5 A AC Load rating, continuous: 4 Inom for 10 s: 30 Inom for 1 s: 100 Inom Rated surge current: 250 Inom Nominal consumption: < 0.3 VA per phase at Inom Voltage Connection to voltage transformers Nominal voltage Vnom: 100 V AC Suitable for connection to transformers with Vnom = 100 to 130 V AC Load rating, continuous: 1.5 Vnom Nominal consumption: < 0.3 VA per phase at Vnom Frequency Nominal frequency fnom: 50 Hz or 60 Hz (settable) Operating range: 0.95 to 1.05 fnom Dynamic range

Fitted: 8 output relays, all freely configurable Contact load rating: - Rated voltage: 250 V DC, 250 V AC - Continuous current: 5 A - Short-time current: 30 A for 0.5 s - Making capacity: 1000 W (VA) at L/R = 40 ms - Breaking capacity: 0.2 A at 220 V DC, L/R = 40 ms, 4 A at 220 V AC, cos j = 0.4 2.6 Interfaces Local control panel Input and output of protection data: via six keys and two four-digit displays State and fault indications: 12 LED indicators (3 permanently assigned, 9 freely configurable) Function assignment: see address list (Appendix C) PC interface Transmission rate: 300 to 9600 Baud (adjustable) For connection to a PC, a special connection cable is required (see Accessories).

Binary Inputs (Optical Couplers)

ILSA interface (optional) Per IEC 60870-5-103 Transmission rate: 50 to 19,200 Baud (adjustable)

Function assignment and connections: see address list (Appendix C) and terminal connection diagrams (Appendix E)

Plastic fiber connection optical wave length: typ. 655 nm distance to be bridged: max. 45 m

Fitted: 2 optical couplers, both freely configurable

Glass fiber connection G 50/125 or G 62.5/125 optical wave length: typ. 820 nm distance to be bridged: max. 2000 m

For the three phase currents at 1 A or 5 A: 100 Inom For the residual current at 1 A or 5 A: 10 Inom

Nominal input voltage Vin,nom: 24 to 250 V DC Operating range: 0.8 to 1.1 Vin,nom with residual ripple of up to 12% of Vin,nom

Wire leads per RS 485, 2kV-isolation distance to be bridged: max. 1200 m

Current consumption per input: Vin = 19…110 V DC: 0.5 W ± 30% Vin > 110 V DC: 5 mA ± 30%

10

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

2 Technical Data (continued)

2.7 Information Output

2.9 Typical Characteristics

Counters, measured data and indications: see address list (Appendix C)

Min. starting time: 25 ms Starting reset time: 30 ms ± 10 ms

Time-Tagged Fault Logging Up to 5 faults are stored, then the oldest fault is erased. Up to 64 signals per fault can be stored, subsequent signals trigger the overflow indication.

Directional sensitivity up to 2 s after general start: ¥ beginning 2 s after general start and with switch on to fault: 200 mV ± 20% Shortest command time: 35 ms

Fault counting: 0 to 9999. Minimum trip command output time: 100 ms Time-tagging: Date and time are assigned via an internal clock.

Reset ratio for starting and measurement: 0.95

Fault Data Acquisition

2.10 Deviations

Phase currents IA, IB, IC: to 100 Inom (IN is calculated at output) Phase-to-ground voltages VA-G, VB-G, VC-G: to 1 Vnom (VN-G is calculated at output)

Deviations relative to the set value with sinusoidal measured variables, total harmonic distortion £ 2%, ambient temperature 20°C and nominal auxiliary voltage VA,nom.

Resolution for sampled values ó 6% dynamic range: for Inom = 1 A : 6.1 mA (r.m.s.) for Inom = 5 A, : 30.5 mA or 6.1 mV (r.m.s.)

Distance Protection

Resolution for sampled values > 6% dynamic range for Inom = 1 A : 97.6 mA (r.m.s.) for Inom = 5 A, : 488 mA or 97.6 mV (r.m.s.) Time resolution: 2 ms Fault logging period Pre-fault period: 10 to 100 ms Post-fault period: 10 to 250 ms For a single fault, recording ceases after 4.35 s / 3.33 s (including the pre- and post-fault periods) at a nominal frequency of 50 Hz / 60 Hz. The maximum recording period of 4.35 s / 3.33 s can be divided between up to 5 faults. For a recording period in excess of 4.35 s / 3.33 s, the analog data of the oldest fault are erased; for a number of faults in excess of five, all data of the oldest fault are erased. Self-monitoring Up to 30 monitoring signals can be stored. 2.8 Settings

Fault detector I>, IN> Setting 0,2 Inom: Deviation: ± 3% Influence at 20°C ± 20 K: ± 0.5% Influence at fnom ± 5%: ± 0.5% Fault detector I>> Deviation: ± 3% Influence at 20°C ± 20 K: ± 0.5% Influence at fnom ± 5%: ± 0.5% Fault detector V, VN-G>> Deviation: ± 3% Influence at 20°C ± 20 K: ± 0.5% Influence at fnom ± 5%: ± 2.0% Impedance measurement Z< Deviation at jsh = 0°, 90°: ± 3% Deviation at jsh = 30°, 60°: ± 5% Direction determination Deviation: ± 3° Influence at 20°C ± 20 K: ± 1° Influence at fnom ± 5%: ± 8°

Settings, ranges and increments: see address list (Appendix C)

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

11

2 Technical Data (continued)

Backup Overcurrent Time Protection (Backup DTOC)

Fault Localization

Threshold operate value I> Deviation: ± 3% Influence at 20°C ± 20 K: ± 1% Influence at fnom ± 5%: ± 0.2%

Deviation: ± 5%

Ground Fault Direction Determination Using Steady-State Values Threshold operate values and sector angles Deviation: ± 3% or 1 ° Influence at 20°C ± 20 K: ± 1% or 1° Influence at fnom ± 5%: ± 5% or 2° Measuring Circuit Monitoring

Internal Clock With free-running internal clock Deviation: < 1 min/month With synchronization via DCF77 clock Deviation: < 10 ms 2.11 Power Supply Nominal auxiliary voltage VA,nom 1 24 to 60 V DC / 110 to 250 V DC, 100 to 230 V AC (selectable using internal plug-in jumper)

Threshold operate values Ineg, Vneg Deviation: ± 3% Influence at 20°C ± 20 K: ± 1%

Operating range: 0.8 to 1.1 VA,nom with residual ripple of up to 12% VA,nom

Timer stages

fnom: 50 Hz / 60 Hz

Deviation: ± 10 ms or 3% Influence at 20°C ± 20 K: ± 1%

Nominal consumption at VA,nom = 220 V DC: 8 / 10 W (VA) (initial condition / operated condition)

Operating Data Measurement

Start-up peak current for a duration of 0.25 ms: < 13 A

2

Deviations relative to the relevant nominal value with sinusoidal measured variables, total harmonic distortion £ 2%, ambient temperature 20°C and nominal auxiliary voltage VA,nom. Current, voltage Deviation: ± 3% Influence at 20°C ± 20 K: ± 1% Influence at fnom ± 5%: ± 0.2% Active and reactive power Deviation: ± 11% Influence at 20°C ± 20 K: ± 7% Influence at fnom ± 5%: ± 6% Load angle j Deviation: ± 2°

12

1

Factory setting underlined

2

For AC voltage supply 89521-302/-303-401/-402-602 / AFSV.12.06470 EN

3 Operation

3.1 Modular Structure

3.2 Man-Machine Communication

The PD 521, a numerical protection device, is one of the pieces of instrumentation in Subsystem P of the Integrated Protection and Control System for Substations (ILS). The devices that are part of this system are built from identical uniform hardware modules. Figure 1 shows the basic hardware structure of the PD 521 distance protection device.

The following interfaces are available for the exchange of information between operator and device: ¨

Integrated local control panel

¨

PC interface

¨

ILSA interface

Each piece of information and each parameter is coded with an ‘address’ consisting of two two-digit decimal numbers x and y. Changing x or y allows selection of any desired address for display or where necessary modification of the information stored at that address. (Please refer to Chapter 6.) The addresses are standardized for all systems with the advantage that the same information is coded with the same address in each device type. The entire address range is divided into the following three groups:

1 Basic hardware structure

The input transformers and optical couplers convert the external analog and binary variables - electrically isolated to the internal processing levels. Commands and signals generated within the device are accessible via floating contacts. The external auxiliary voltage is applied to the power supply module which provides the voltages required internally.

¨

Parameters: This group contains all set values including the device identification data, the configuration parameters for adapting the device interfaces to the system and the function parameters for adapting the protective function to the process. All values of this group are stored in a non-volatile memory, that is the values will be preserved even if the power supply fails.

¨

Operation: This group includes all information relevant for operation, such as measured operating values and binary signal states. This information is updated periodically and consequently is not stored. In addition, various control parameters are grouped here, for example those for resetting counters, memories and displays.

¨

Events: The third group is reserved for the recording of events. Hence all information contained in this group is stored. In particular the start/end signals during a fault, the measured fault data as well as sampled fault records are stored here and can be read out at a later time.

The appendix, section C, documents the addresses of the numerical protection device PD 521. This address list is complete and thus contains all addresses used with the PD 521.

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

13

3 Operation (continued)

3.3 Distance Protection The secondary phase currents and voltages of the system transformer are fed to the PD 521 and – electrically isolated – are converted to normalized electronics levels. The analog quantities are digitized and are thus available for further processing. Settings that do not refer to nominal quantities are converted by the PD 521 to nominal quantities. The nominal current of the PD 521 must be set for this purpose. The connection arrangement of the distance protection measuring circuit on the PD 521 must be set. (Figure 2 shows the standard connection.) The phase of the digitized phase current is rotated 180° by this setting.

14

From these currents (IA, IB and IC) the phase-to-phase currents IA-B, IB-C and IC-A are formed. The current with the highest magnitude (IP,max) and the current with the intermediate magnitude (IP,med) are determined from the phase currents. The ground current 1IN is calculated by summation of IA, IB and IC. The phase-to-phase voltages 1VA-B, 1VB-C and 1VC-A are formed from the digitized phase-to-ground voltages 1VA-G, 1VB-G and 1VC-G and the neutral displacement voltage 1VN-G.

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

3 Operation (continued)

2 Conditioning the measured data

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

15

3 Operation (continued)

3.3.1 Fault Detection Logic The purpose of distance protection fault detection logic is phase-selective short-circuit detection. Fault detection logic is divided into the following areas: ¨

Overcurrent detection

¨

Ground fault detection

¨

Undervoltage detection

¨

Underimpedance detection

The fault detection decisions of the individual areas are linked by fault detection logic. Short-circuit currents that are greater than the maximum operating load currents can be detected by overcurrent detection logic. Undervoltage detection logic is provided for short circuits that cannot be detected by overcurrent detection logic. Ground fault detection logic distinguishes between grounded and ungrounded faults.

The fault detection logic function starts the timer stages of the trigger levels and – as a function of the phaseselective fault detection decision – selects the measuring loop in which the fault impedance is determined. Fault detection logic is blocked in the following cases: ¨

if protection is disabled from the local control panel or through appropriately configured binary signal inputs;

¨

if measuring-circuit monitoring detects a fault in the voltage-measuring circuit.

Protection can only be deactivated or activated through binary signal inputs if the M A I N : D e a c t i v a t e p r o t . E X T and M A I N : A c t i v a t e p r o t . E X T functions are both configured. When only one or neither of the two functions is configured, this is interpreted as “Protection externally activated.” If the triggering signals of the binary signal inputs are implausible, as for example when they both have a logic value of “1,” then the last plausible state remains stored in memory.

3 Fault detection blocking

16

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

3 Operation (continued)

Overcurrent Detection Logic Overcurrent detection logic monitors the phase currents for values in excess of the threshold values I>> and I>>>. The I>> threshold can be set. I>>> is 2 × I >> . The thresholds are identical for all three phases. The output signals of the I>> trigger assume a logic value of "1" if the threshold is exceeded in two consecutive halfwaves. Overcurrent detection is delayed by the set time tI>> if the current is below 5 × I>>. Thereby, false fault detection decisions caused by inrush currents on switching can be suppressed for lines with connected transformers. In the case of the I>>> trigger only one halfwave must exceed the threshold for the output signals to assume a logic value of "1."

If I>> is exceeded in one phase, then it is sufficient for overcurrent detection if I>>> is exceeded in the other phases. In this case the fault detection time is shortened since there is no longer any need to wait for the second half-wave. Evaluation of the trigger decisions is a function of the type of neutral-point treatment set in the PD 521. If isolatedneutral/resonant-grounded or short-time grounding is set, then I>> overcurrent detection occurs in the phase(s) in which the I>> threshold is exceeded. With the setting impedance-grounded the following condition must also be satisfied:



2 3

× IP,max

4 Overcurrent detection logic

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

17

3 Operation (continued)

Ground Fault Detection Logic

Ground fault detection logic monitors the average magnitude of the ground current 1IN and the neutral-point displacement voltage 1VN-G for values exceeding set thresholds.

5% of the current maximum phase current is added to the set threshold IN>, which means that the operate value of the ground current function increases with an increasing phase current level as a form of stabilization.

5 Monitoring the ground current 1IN and the neutral-point displacement voltage 1VN-G

18

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

3 Operation (continued)

Even in the case of a single-phase fault, that is, in the event that only one base point is detected, ground fault starting will occur, but not until tIN> has elapsed.

The ground fault detection mode is a function of the neutral-point treatment set in the PD 521. ¨

¨

MAIN: Neutral-point treat(ment) Low impedance-grounding Ground fault starting SG occurs with this setting when the threshold of the IN> or VN-G> trigger is exceeded. MAIN: Neutral-point treat(ment) Isolated neutral/resonant-grounding If the setting isolated neutral/resonant-grounding is selected, instantaneous starting SG occurs when there is multiple phase-to-ground fault detection if the threshold value of the IN> or VN-G> trigger is exceeded.

¨

MAIN: Neutral-point treat(ment) Short-duration grounding Operation in this mode corresponds to operation with the setting isolated neutral/resonant-grounding except that timer stage tIN> is started when the IN> or VN-G> trigger operates. In the case of a sustained ground fault the timer stage tIN> remains in the elapsed state due to the operating trigger VN-G>>. If the ground fault changes to a phase-to-ground fault then ground fault starting operates without delay when the threshold of the IN> or VN-G> trigger is exceeded.

6 Evaluation of trigger signals

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

19

3 Operation (continued)

Ground Fault Starting Signals Signals are derived from ground fault detection trigger decisions. If neutral-point treatment is set for Low impedance-grounding, then the following signals are issued: ¨

When VN-G>> is exceeded, S T A R T : V N - G > > t r i g g e r e d is signaled.

¨

By selecting the appropriate setting the user can specify whether a “trip” should occur after the timer stage tVN-G>> has elapsed.

With the settings Isolated neutral/resonant-grounding or Short-duration grounding the M A I N : G r o u n d f a u l t signal is issued after tVN-G>> elapses (see Figure 6) if there is no multi-phase starting.

Enabling Undervoltage and Underimpedance Detection Logic

Undervoltage and underimpedance detection logic are enabled by I>(Imin) in the corresponding measuring systems. In order to control contention problems when current and voltage appear at the same time (branch voltage transformers), enabling of the measuring systems is delayed by 15 ms. In isolated-neutral systems or resonant-grounded systems, one of the two phases may carry just a small load current falling below the base point current I>(Imin). In this case, the undervoltage decisions are enabled if the V< condition is met in two phases whereas the I> condition is satisfied in one phase only. This extended enabling logic will operate only for the neutral-point treatment settings Isol./reson. w. start. P-G and Shortduration grounding.

7 Ground fault starting signals

20

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

3 Operation (continued)

8 Enabling undervoltage and underimpedance detection logic

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

21

3 Operation (continued)

Ground fault detection brings about a switch from phase-to-phase to phase-to-ground loops.

Undervoltage Detection Logic

¨

Undervoltage detection logic monitors the phase-toground voltages or the phase-to-phase voltages to determine whether they fall below the set threshold V may occur.

35 Monitoring signals

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

45

3 Operation (continued)

Measuring circuit monitoring can be deactivated by the appropriate setting. In the event of a fault, measuring circuit monitoring is blocked. Monitoring the Current-Measuring Circuits The current-measuring circuit monitoring function is enabled when the current exceeds the value 0.125 × I nom in at least one phase. Once monitoring is enabled, the absolute value of the negative-sequence component of the current system is determined in accordance with the definition of the Symmetrical Components.

I neg =

1 3

a = e j 120

 IA + a 2 × IB + a × IC 0

a 2 = e j 240

0

This value is divided by the maximum phase current I P,max and compared to the set threshold operate value. If the set threshold operate value is exceeded, a monitoring signal is issued after 10.1 s. In addition, a setting can be selected that will determine whether a trip shall occur.

36 Monitoring the current-measuring circuits

46

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

3 Operation (continued)

Monitoring the Voltage-Measuring Circuits

The voltages used by distance protection as measured variables are monitored by the voltage-measuring circuit monitoring function for plausibility. However, this does not replace the auxiliary contact of the voltage transformer m.c.b., which is absolutely necessary in the case of activated undervoltage and underimpedance starting. Monitoring of the voltage-measuring circuits is based on the following criteria: ¨

Monitoring the phase-to-phase voltages for voltages that fall below the default threshold of 0.4 × Vnom . This monitoring function is enabled when the phase current is greater than 0.05 × I nom or for the “closed“ position of the circuit breaker provided that MON: Meas . volt. c irc uit is set to Vneg w. CB contact enabl.

¨

Monitoring the negative-sequence component of phase-to-ground voltages in accordance with the definition of the symmetrical components. Monitoring is enabled when a phase-to-ground voltage exceeds the default threshold of 0.7 × Vnom / 3 . In addition to this criterion, a minimum current having the default threshold setting of I > 0.05 × I nom or the closed position of the circuit breaker can be used as enabling criteria. If there is an enable, the absolute value of the negative-sequence component of the voltage system is determined in accordance with the definition of symmetrical components. Vneg = a = e j 120



1 × 1VA - G + a2 × 1VB - G + a × 1VC - G 3

If one of the monitoring functions described above operates, then distance protection is blocked and the device switches to backup overcurrent time protection – if the appropriate setting was selected. In addition, the monitoring signal “M O N : M e a s . v o l t . O K ” is issued if all phase-to-phase voltages exceed the default threshold of 0.65 × Vnom and negative-sequence monitoring has not operated. Monitoring Starting

If ground starting SG is present for more than 10 s without phase starting, the following monitoring signal is issued: M O N : M e a s u r i n g c i r c u i t s "Ground fault starting" (see Figure 35).



0

a 2 = e j 240

0

This value is compared with the default threshold operate value 0.2 × Vnom / 3 . If the threshold operate value is exceeded, a monitoring signal is issued after 9.8 s.

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

47

3 Operation (continued)

37 Monitoring the voltage-measuring circuit

48

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

3 Operation (continued)

3.5 Backup Overcurrent-Time Protection (BUOC or Backup DTOC)

tI> is started. After the set time period has elapsed, a trip signal is issued.

If there is a fault in the voltage-measuring circuit, distance protection is blocked, since accurate impedance measurement is not possible. Backup overcurrent time protection is automatically activated – if set accordingly.

If the "Low impedance-grounding" setting has been selected, the ground current 1IN is also monitored by the settable trigger IN>, in addition to the phase currents. If the ground current exceeds the set value, timer stage tIN> is started. After the set time has elapsed, a trip signal is issued.

Backup overcurrent time protection is enabled if there is a fault in the voltage-measuring circuit. It monitors the phase currents for overcurrents exceeding the set values I>. If a phase current exceeds the set value, timer stage

38 Backup overcurrent time protection

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

49

3 Operation (continued)

3.6 Switch on to Fault Protection When the circuit breaker is closed manually it is possible to switch on to an existing fault. This is especially critical if the line in the remote station is grounded since the distance protection would not clear the fault until t2 had elapsed. The fastest possible clearance is desirable in this situation, however.

is converted to an internal pulse. The pulse time can be set. It is possible to specify whether the following shall occur during operation of the timer stage: ¨

The appearance of general starting (see Section “Tripping Logic” for a definition of general starting) shall cause a trip (S O T F : T r i p a f t . m a n . c l o s e ). or

To guarantee rapid clearing with manual closing, the manual close signal must be issued not only to the circuit breaker but also to the PD 521. The manual close signal

¨

A zone extension of impedance zone 1 shall occur (SOTF: Zone extension).

39 Switch on to fault protection

50

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

3 Operation (continued)

3.7 Protective Signaling The reach of the first impedance zone of the distance protection function is normally set for values less than 100%. Protective signaling is used to extend protection to 100% of the section. This is achieved by logical linking of the signals that are transmitted by the remote station’s protection device.

In order for protective signaling (PSIG) to function, the following requirements must be satisfied: ¨

It must be activated.

¨

There must be no external block.

¨

There must be no transmission fault.

¨

The function PSIG : Rec eive EX T must be configured to a binary signal input.

Protective signaling can be activated or deactivated from the local control panel.

40 Protective signaling enable

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

51

3 Operation (continued)

Once protective signaling is ready, distance protection timer stage t1 is blocked. A trip enable in distance protection zone 1 is then issued after the protective signaling tripping time has elapsed.

41 Protective signaling tripping time

¨

Direct transfer trip underreaching

¨

Permissive underreaching transfer tripping (PUTT)

¨

Zone extension

¨

Signal comparison release scheme

¨

Signal comparison blocking scheme

For operation in the mode referred to as "Signal comparison pilot wire," pilot wires are required for signal transmission. P S I G : O p e r a t i n g m o d e "Direct transfer trip underreaching"

A communication malfunction or failure leads to a protective signaling block. If protective signaling is carried out by a signal transmission or communication device, the device’s fault signal can be connected. In the case of protective signaling via pilot wires or in the operating mode referred to as "reverse interlocking," an internal monitoring function detects any fault in the communication channel. Protective signaling can be operated in seven different modes. The following operating modes require a signal transmission device:

When there is a “Distance trip zone 1" a signal is sent to the remote station’s protection device. Upon receipt of the signal by the remote station, the remote station’s circuit breaker is tripped. P S I G : O p e r a t i n g m o d e "Permissive underreaching transfer tripping (PUTT)” With a "Distance trip zone 1" a signal is sent to the remote station’s protection device. Upon receipt of the signal by the remote station, the remote station’s circuit breaker is transfer tripped as a function of starting.

42 Transmission fault

52

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

3 Operation (continued)

P S I G : O p e r a t i n g m o d e "Zone extension" With "Distance trip zone 1" a signal is sent to the remote station’s protection device. Upon receipt of the transmitted signal the measuring range of zone 1 in the remote station is increased by the zone extension factor kze HSR. If the fault lies within the extended zone, the remote station’s protection device also decides in favor of “Distance trip zone 1.” 44 Zone reaches with the release scheme (broken line: measuring range extended by the zone extension factor kze HSR)

43 Reaches with zone extension (broken line: measuring range increased by the zone extension factor kze HSR)

If both zone extension factors (kze P-G HSR and kze P-P HSR) are set at a value of "1.0," a trip enable is issued only if the second of the conditions given above is satisfied. In the event of a change in direction the received signal is ignored for 80 ms (“transient blocking”) so that false tripping will not occur in double line protection.

P S I G : O p e r a t i n g m o d e “Signal comparison release scheme"

P S I G : O p e r a t i n g m o d e "Signal comparison blocking scheme"

In the idle state the measuring range of zone 1 in both protection devices is extended by the zone extension factor kze HSR. The “Distance trip zone 1” of both protection devices is blocked.

In the idle state the measuring range of zone 1 in both protection devices is extended by the zone extension factor kze HSR. The “Distance trip zone 1” of both protection devices is enabled.

If distance protection starting begins and the fault lies in the forward direction, a signal is sent to the remote station. In the event of a fault, both protection devices measure by using the normal measuring range and the range extended by the zone extension factor kze HSR. A trip enable is issued if one of the following conditions is satisfied after the distance protection timer stage t1 has elapsed: ¨

The fault lies within the non-extended measuring range.

¨

The fault lies within the extended measuring range and a transmitted signal is received by the remote station.

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

If distance protection starting begins and the fault lies in the backward direction, a signal is sent to the remote station. In the event of a fault, both protection devices measure by using the normal measuring range and the range extended by the zone extension factor kze HSR. A “Distance trip zone 1” can be issued instantaneously (t0) with the normal reach. The “Distance trip zone 1” is blocked if the following conditions are satisfied simultaneously after distance protection timer stage t1 has elapsed: ¨

The fault lies within the extended measuring range.

¨

A transmitted signal is received by the remote station.

53

3 Operation (continued)

kze HSR. The “Distance trip zone 1” of both protection devices is enabled. If distance protection starting begins and a fault lies in the backward direction or if the overcurrent starting originates from the distance protection starting, then a signal is sent to the remote station without delay.

45 Zone reaches with the blocking scheme (broken line: measuring range extended by the zone extension factor kze HSR)

If both zone extension factors (kze P-G HSR and kze P-P HSR) are set at a value of "1.0," a trip is only possible after t1 has elapsed. P S I G : O p e r a t i n g m o d e "Signal comparison pilot wire" To form the communication link it is necessary to connect either the break contact or the make contact of the transmitting relay, depending on the transmitting relay mode selected (Transm. relay make contact or Transm. relay break contact), to the P S I G : R e c e i v e E X T input of the remote station by means of pilot wires.

In the event of a fault both protection devices measure by using the normal measuring range and the measuring range extended by the zone extension factor kze HSR. A “Distance trip zone 1” can be issued instantaneously (t0) with the normal reach. The “Distance trip zone 1” is blocked if the following conditions are satisfied simultaneously after distance protection timer stage t1 has elapsed: ¨

The fault lies within the extended measuring range.

¨

A transmitted signal is received by the remote station.

If both zone extension factors (kze P-G HSR and kze P-P HSR) are set at a value of "1.0," a trip is only possible after t1 has elapsed. The pilot wires are monitored for interruptions. If, during fault-free operation, that is, when there is no distance protection starting, no signal is received by the remote station for a period longer than the set transmitted signal reset time plus 600 ms, then a P S I G : T e l e c o m . f a u l t y signal (see Figure 42) is issued, and protective signaling is blocked.

In the idle state there is a received signal in both protection devices (DC loop closed), and the measuring range of zone 1 is extended by the zone extension factor

46 Protective signaling via pilot wires

54

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

3 Operation (continued)

P S I G : O p e r a t i n g m o d e "Reverse interlocking" In radial networks with infeed from a single end it is possible under certain conditions for busbar protection to be configured by sampling the starting of feeder protection devices. By means of appropriate interconnection, a send signal is then formed when a feeder protection device starts. The receipt of this signal by the PD 521 blocks the “Distance trip zone 1.” The blocking signal reset is delayed by approximately 80 ms. The pilot wires are monitored. If a received signal is present for more than 10 s without any distance protection starting, then the distance trip zone 1 block is canceled. A new block cannot occur until the received signal has dropped out.

48 Zone extension by protective signaling

47 Reverse interlocking

49 P S I G : R e c e i v e & g e n e r a l s t a r t i n g signal

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

55

3 Operation (continued)

50 Trip enable by protective signaling

56

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

3 Operation (continued)

51 PSIG send

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

57

3 Operation (continued)

Echo Function It is possible to select "without or with" echo on receive. This setting is only active in the following modes:

The further transmission of a received signal as a send signal is then blocked for 20 s. This prevents a permanent signal from being transmitted. Testing the Communication Channel

¨

PUTT (permissive underreaching transfer trip)

¨

Zone extension

¨

Signal comparison release scheme

¨

Signal comparison blocking scheme

If the "with" echo setting is selected, a signal is sent to the remote station if the received signal is present for more than 50 ms and no “distance protection starting” is active.

The communication link can be tested. For this purpose a 500 ms send signal is issued through a binary signal input or the integrated local control panel. The remote station receives this signal if the transmission section is OK. In the mode referred to as "Direct transfer trip underreach" no test is possible, since a received signal will immediately lead to a “Trip” in the remote station. Likewise, testing is not possible with the "Reverse interlocking" setting.

52 Testing protective signaling and the echo function

58

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

3 Operation (continued)

3.8 Circuit Breaker Failure Protection Circuit breaker failure protection is activated by a general trip command from the PD 521 or – when a general starting state exists – through an appropriately configured binary signal input. After the settable time period C B F : t C B F has elapsed, the fault must be cleared. Otherwise it can be assumed that the circuit breaker has failed. In this case the C B F : C B f a i l u r e signal is issued.

3.9 Ground Fault Direction Determination Using Steady-State Values Ground fault direction determination using steady-state values requires the neutral-point displacement voltage formed from the three phase-to-ground voltages - and the ground current as measured variables. A special transformer is provided in the PD 521 for the residual current. The current transformer is designed specifically for this application so that it has a low phase-angle error. When there is a trip of the voltage transformer circuit breaker, ground faults can be determined by steady-state evaluation of the ground current. The user can specify whether both ground current and displacement voltage will be evaluated (steady-state power) or if only the ground current will be evaluated (steady-state current). The switch from steady-state power evaluation to steady-state current evaluation can also be carried out through a binary signal input – given appropriate configuration. When switching from steady-state power to steady-state current evaluation or vice versa, the outputs of the nonactive function are blocked.

53 Circuit breaker failure protection

If the system frequency is set to 60 Hz, ground fault direction determination using steady-state values (GFDSS) is blocked.

54 Switching from steady-state power to steady-state current evaluation

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

59

3 Operation (continued)

3.9.1 Steady-State Power Evaluation In order to detect the ground fault direction, ground fault direction determination by steady-state power evaluation

requires the neutral-point displacement voltage 1VN-G and the ground current 2IN.

55 Connection of ground fault direction determination by steady-state power evaluation

60

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

3 Operation (continued)

The settable frequency f0 is filtered out from these quantities using Fourier analysis. Three periods are used for analysis if the setting selected for the timer stage G F D S S : t V N - G > is greater than 60 ms. This means that typical ripple control frequencies are suppressed in addition to all integer-frequency harmonics. If the timer stage has been set at values less than 60 ms, only one period is used for filtering purposes.

Measurement is enabled after timer stage t V N - G > has elapsed; this module is started by the trigger VN-G>. Depending on the operating mode selected – either cos phi circuit or sin phi circuit – the sign of active power (G F D S S : O p e r a t i n g m o d e cos phi circuit ) or reactive power (G F D S S : O p e r a t i n g m o d e sin phi circuit ) is used. Connection of the measuring circuits is taken into account by the setting G F D S S : C o n n e c t . m eas . c ir c . With the standard (forward) connection (see Figure 55) a decision for "LS" is reached in the case of a ground fault on the line side and "BS" in the case of a ground fault on the busbar side.

56 Direction determination

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

61

3 Operation (continued)

G F D S S : O p e r a t i n g m o d e "cos phi circuit"

GFDSS: Operating mode "sin phi circuit“

The direction decision is not enabled until the following additional conditions are satisfied: the active component of the ground current 2IN exceeds the set value, and the phase displacement between ground current 2IN and neutral-point displacement current 1VN-G is smaller than the set sector angle. The sector angle makes it possible to extend the “dead zone” to take into account the expected phase-angle errors of the measured variables. With these settings the characteristic shown in Figure 57 can be realized.

The direction decision is enabled if the reactive component of current 2IN has also exceeded the set threshold operate value. With these settings the characteristic shown in Fig 58 can be realized. Output of the direction decisions is operate- and resetdelayed.

Output of the direction decisions is operate- and resetdelayed.

57 Characteristic of ground fault direction determination by steadystate power evaluation, operating mode cos j

62

58 Characteristic of ground fault direction determination by steadystate power evaluation, operating mode sin j

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

3 Operation (continued)

59 Output of direction decisions

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

63

3 Operation (continued)

Counting the Ground Faults

3.9.2 Steady-State Current Evaluation

The number of ground faults and direction decisions is counted. The counters can be reset at the address at which they are displayed by pressing the enter key (E) twice.

The settable frequency f0 is filtered out of the ground current 2IN using Fourier analysis. Three periods are used for steady-state current evaluation. If the current exceeds the set threshold value, then a ground fault signal is issued after the set operate delay has elapsed.

60 Counting the ground faults

61 Evaluation of ground current 2IN GFD: Determination of ground fault direction by steady-state power evaluation GF: Ground fault detection by steady-state current evaluation

64

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

3 Operation (continued)

Counting the Ground Faults

3.9.3 Ground Fault Data Acquisition

The number of ground faults is counted. The counter can be reset at the address at which it is displayed by pressing the enter key (E) twice.

The PD 521 stores the following measured ground fault data: ¨

Ground fault duration

¨

Ground current IN

¨

With steady-state power evaluation:

¨

n

Active or reactive component of ground current

n

Neutral-point displacement voltage VN-G

With steady-state current evaluation: n

Filtered ground current

62 Counting the ground faults

Resetting the Counters The counters can be reset both individually at the address at which they are displayed and as a group.

63 General counter reset

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

65

3 Operation (continued)

Acquisition of Ground Fault Duration ¨

Steady-state power evaluation: Ground fault duration is defined as the time between operation and dropout of the VN-G> trigger. However, there is only a time output after the end of a ground fault if the VN-G> trigger operated at least for the set time tVN-G>. After tVN-G> has elapsed, the display of the ground fault duration of the last ground fault is automatically cleared and the symbol for “no value measured” (....) is displayed. Once the VN-G> trigger has dropped out, the newly measured value is displayed.

¨

Steady-state current evaluation: Ground fault duration is defined as the time between operation and dropout of the IN> trigger. However, there is only a time output after the end of a ground fault if the IN> trigger operated at least for the duration of the set operate delay (G F D S S : O p e r a t e d e l a y I N ). After the operate delay has elapsed, the display of the ground fault duration of the last ground fault is automatically cleared and the symbol for “no value measured” (....) is displayed. Once the IN> trigger has dropped out, the newly measured value is displayed.

64 Measurement and storage of ground fault duration, steady-state power evaluation

65 Measurement and storage of ground fault duration, steady-state current evaluation

66

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

3 Operation (continued)

Acquisition of Ground Current If the steady-state current evaluation function is active, then the unfiltered and filtered ground currents at the point when the operate delay elapses are stored. If the steadystate power evaluation option of ground fault direction determination has been activated, then the ground current flowing at the point when timer stage tVN-G> elapses is stored in memory. In addition, the active or reactive component of the ground current at the time of the direction decision output is also stored. All measured data are output as per-unit quantities referred to the nominal current Inom of the protection device. Acquisition of Neutral-Point Displacement Voltage The voltage 1VN-G is only acquired if the steady-state power evaluation function of ground fault direction determination has been activated. The voltage that is present at the point when timer stage tVN-G> elapses is stored in memory. Resetting the Measured Data The measured values are reset together as a group. It is possible to specify whether resetting shall be done together with the LED indicators. After resetting, the symbol for “no value measured” (....) appears in the value display.

66 Storing the measured ground fault data

67 Resetting the measured ground fault data

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

67

3 Operation (continued)

3.10 Starting Signals and Tripping Logic The distance protection and backup overcurrent time protection starting signals are linked to form common starting signals. The number of general starting signals (GS) is counted.

The following signals of the protection device are combined to form common trip signals and trip commands: ¨

Distance trips for zones 1 to 6

¨

START: Trip VN-G>>

¨

MON: Trip by Ineg

¨

BUOC: Tripping signal

¨

SOTF: Trip after manual close

If the PD 521 is operating with protective signaling, then a zone 1 trip can be issued by protective signaling in the "Direct transfer trip underreach" and "PUTT (Permissive underreaching transfer tripping)" operating modes. In all other protective signaling modes an enable must be issued by protective signaling. If protective signaling is not ready, then the zone 1 distance trip is automatically enabled. The trip signals are present only as long as the conditions for the signal are satisfied. If a general starting condition exists, then a non-delayed, three-pole "starting trip" can occur by triggering an appropriately configured binary signal input. A trip command can be issued not only by the protection function but also through a control parameter (address 03 40) or an appropriately configured binary signal input, in which case it is issued for 100 ms. 68 Starting signals

The trip commands can be blocked by a control parameter (address 21 12) or an appropriately configured binary signal input. The trip signals are not affected by the block. If trips are blocked this is indicated by a steady light at yellow LED indicator H3 on the local control panel and by output relay K8 if configured accordingly. The phase-selective trip commands, the general trip command and the final trip are counted. The counters can be reset either individually or as a group.

68

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

3 Operation (continued)

69 Tripping logic

70 Counting the trip commands

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

69

3 Operation (continued)

3.11 Pass-Through Functions

mode can be set. The user can choose between the following modes:

The PD 521 distance protection device offers the possibility of collecting external binary signals for the purpose of indicating and recording them during a fault. The protection functions are not affected by these passthrough functions.

¨

Operate-delayed

¨

Passing make contact

Input 1 for the freely configurable pass-through functions triggers a settable timer stage. The timer stage operating

¨

Passing break contact

71 Pass-through functions

70

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

Operation (continued)

3.12 Overcurrent Signal The PD 521 offers the possibility of monitoring the phase currents for values that exceed a settable value. If the set value is exceeded in a phase, a signal will be issued after the set time period has elapsed.

72 Overcurrent signal

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

71

3 Operation (continued)

3.13 Operating Data Measurement

¨

Active and reactive power

The PD 521 displays the following measured operating data:

¨

Active power factor

¨

Load angle j in all three phases

¨

Frequency

¨

Phase currents for all three phases

¨

Ground current IN, which is either calculated from the three phase currents or, if ground fault direction determination using steady state values is active, is the current measured by the PD 521’s T4 transformer.

¨

Active or reactive current, determined by steady-state power evalution (see Section “Ground Fault Direction Determination Using Steady-State Values”).

¨

Phase-to-ground and phase-to-phase voltages on the line side

¨

Neutral-point displacement voltage

¨

Filtered ground current IN, determined by steady-state current evaluation (see Section “GF Evaluation (Ground Fault)“)

72

The measured values for current, voltage and power are displayed both as referred to the nominal quantities of the PD 521 and as primary quantities. In order for these quantities to be displayed as primary values, the primary nominal current of the current transformer or the nominal transformation ratio multiplied by the nominal device current and the primary nominal voltage of the voltage transformer must be set in the PD 521. The measured data are updated at 1 s intervals. Updating is interrupted if a general starting state occurs.

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

3 Operation (continued)

73 Current and voltage operating data

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

73

3 Operation (continued)

The active and reactive power and the active power factor are determined when currents and voltages in all three phases are within the acceptable measuring range. Current measuring range: Voltage measuring range:

0.05 × Inom < I < 5 × Inom 0.1 × Vnom < V < 2 × Vnom

are within the acceptable measuring ranges (see the ranges given above). If the values are outside the measuring ranges, a symbol for “overrange” (-..-) is displayed. If values cannot be updated or determined, a symbol for “value not determined” (....) appears.

The load angles are only determined when the associated phase current and the associated phase-to-ground voltage

74 Measured operating data: load angle, power and active power factor

74

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

3 Operation (continued)

3.14 Fault Recording A fault exists and therefore fault recording begins if at least one of the following signals is present: ¨

START: General starting

¨

S T A R T : VN-G>> triggered, if the setting is yes for Trip tVN-G>>

¨

MAIN: General trip signal

¨

MAIN: General trip command (address 36 71)

¨

PSIG: Receive & gen. start (address 37 29)

¨

FREC: Trigger

(address 36 00)

(address 36 05)

The faults are counted (address 04 20) and identified by serial number. In addition, the date of each fault is also assigned by the internal clock and stored. The internal clock also assigns the absolute time to a fault’s individual start or end signals. The date and time assigned to a fault when the fault begins can be read out from the signal memory on the local control panel or through the PC and ILSA interfaces. The time information assigned to the signals can be called up only through the PC or ILSA interfaces. The fault recordings are stored in non-volatile memory.

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

75 Fault counting and time tagging

75

3 Operation (continued)

The fault records can be erased in different ways. The following mechanisms are available: ¨

¨

Automatic resetting of the fault signals indicated by LED indicators and of the measured fault data displayed at the appropriate addresses whenever a new fault occurs. Resetting of LED indicators and measured fault data on the local control panel by pressing the reset key (R) on the panel.

¨

Area-specific resetting, such as only the signal memory, for example, through addresses on the local control panel or appropriately configured binary signal inputs.

¨

General reset.

In the first two cases listed above only the displays on the local control panel are cleared but not internal memories such as the signal memory. In the event of a cold restart, for example by control via address 00 85, all stored signals and values will be lost.

76 Resetting

76

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

3 Operation (continued)

3.14.1 Fault Logging

3.14.2 Measured Fault Data

Protection signals during a fault, including the signals during the settable pre-fault and post-fault times, are logged in chronological order with reference to the specific fault. A total of five faults, each involving a maximum of 64 start or end signals, can be stored in a non-volatile ring memory -- the signal memory. After five faults have been logged the oldest fault log will be overwritten, unless faults have been erased in the interim. If more than 64 start or end signals have occurred during a single fault, then “Signal mem. overflow” (address 35 01) will be entered as the last signal. If time and date are changed during the pre-fault time, the signal FREC: Faulty tim e tag is generated.

When there is a fault in the network the PD 521 determines the following measured fault data:

In addition to the fault signals, the measured fault data are also entered in the signal memory. The fault logs can be read on the local control panel or through the PC or ILSA interfaces.

¨

Operating time (duration)

¨

Fault current

¨

Fault voltage

¨

Fault impedance

¨

Fault reactance in percent of line reactance and in W

¨

Fault angle

¨

Fault distance

¨

Ground fault current

¨

Ground fault angle

The operating time is defined as the time between the starting and ending of the general starting state generated in the PD 521.

78 Operating time

77 Signal memory

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

77

3 Operation (continued)

The fault must last for at least 60 ms so that the fault data can be determined. The fault data are determined using the measured variables Imeas and Vmeas selected by the distance protection function, if the fault is detected by distance protection. A phase current is selected as the fault current in accordance with the selected measuring loop. In the case of multi-phase starting this is the current of the leading phase in the cycle. If the measuring-circuit voltage Vmeas < 200 mV, the set angle a is used to determine the fault reactance. The set angle a is then also displayed as the fault angle. The primary short-circuit reactance is calculated from the per unit short-circuit reactance using the set primary nominal current and voltage transformer data. The ground fault data are only determined if a phase-toground loop has been selected for measurement by the distance protection function. The geometric sum of the three phase currents is displayed as the fault current. The ground fault angle is the phase displacement between ground fault current and selected measuring voltage. If the fault is detected by the backup overcurrent time protection function, then only the fault current can be determined. The maximum phase current is displayed. The F L O C : S t a r t d e t e r m i n a t i o n setting determines the actual time during a fault when the fault data are determined and whether output of fault location shall take place. The following settings are possible:

¨

FLOC: Start determination Fault end Determination at the end of the fault. The measured F L O C : F a u l t l o c a t i o n value is output.

¨

FLOC: Start determination Fault end / trip during t1) Determination at the end of the fault. Output of the measured “F L O C : F a u l t l o c a t i o n ” value only occurs if a trip occurred in distance protection zone 1.

¨

FLOC: Start determination Trip or trigger Determination when a trip starts or a correspondingly configured signal input is triggered. Output of the measured F L O C : F a u l t l o c a t i o n value only occurs if a trip occurred or if the binary signal input was triggered. If neither a trip was issued nor the binary signal input was triggered, the fault values are stored at the end of the general starting state. There is then no output of fault location.

In order for the fault location to be determined in percent of line length and in km, the value of the line reactance – 100% of which corresponds to the line section being monitored – and the value of the corresponding line length in km must be set in the PD 521. Fault current and voltage are displayed as per-unit quantities referred to Inom and Vnom. If the measured or calculated values are outside the permissible measuring range, the “overrange” indication (-..-) appears. Permissible current measuring range: Permissible voltage measuring range:

78

I £ 100 × Inom V £ 2 × Vnom

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

3 Operation (continued)

79 Determination of fault data

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

79

3 Operation (continued)

In addition to the fault data, the following load data are determined upon dropout of distance protection starting: ¨

Load impedance

¨

Load angle

¨

Ground current

The same measuring loop used to determine fault impedance is used to determine load impedance and load angle. The load current and the voltage must exceed the

thresholds 0.1 × Inom and 0.1 × Vnom , respectively, in order for the load data to be determined. If the thresholds are not reached or if distance protection starting does not last as long as 60 ms, the symbol for “not measured” (....) is displayed. After the reset key (R) on the local control panel is pressed, the symbol for “not measured” (....) is displayed at the respective addresses. However, the values are not erased and can continue to be read out through the PC and ILSA interfaces.

80 Determination of load data

80

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

3 Operation (continued)

3.14.3 Fault Data Acquisition The phase currents and the phase-to-ground voltages are recorded before, during and after a fault. The times for recording before and after the fault can be set. A maximum time period of 4.35 s / 3.33 s (including the prefault and post-fault recording times) is available for recording if the nominal frequency is 50 Hz / 60 Hz.. If the maximum recording time of 4.35 s (or 3.33 s) is exceeded, the analog values for the oldest fault are overwritten, but not the binary values. If more than five faults have occurred since the last reset, then all data for the oldest fault are overwritten.

Fault recording can also be started manually from the local control panel or externally through a binary signal input. The analog data of the fault record can only be read out through the PC or ILSA interfaces. When the analog data are sampled the neutral displacement voltage VN-G is calculated from the phase-to-ground voltages and the ground current IN is calculated from the phase currents. When the supply voltage is interrupted or after a warm restart, the values of the last fault remain stored.

81 Fault recording

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

81

3 Operation (continued)

3.15 Self-Monitoring and Fault Diagnosis Comprehensive monitoring routines in the PD 521 distance protection device ensure that internal faults are detected and do not lead to malfunctions of the protection system.

If at least one entry is stored in the monitoring signal memory, this fact is signaled by the red LED indicator H1 on the local control panel. Each new entry is indicated by a flashing light. The combined signal for all warnings may also be issued via an output relay. The output relay responds as long as an internal fault is detected.

After the supply voltage has been turned on, various tests are carried out to verify full operability of the PD 521. The local control panel display shows which test is currently being run. If the PD 521 detects a fault in one of the tests, then startup is terminated. The display shows which test was running when termination occurred. No control actions may be carried out. A new attempt to start up the PD 521 can only be initiated by turning the supply voltage off and then on again. After startup has been successfully completed, cyclic selfmonitoring tests will be run during operation. In the event of a positive test result, a specified monitoring signal will be issued and stored in a non-volatile memory – the monitoring signal memory – along with the assigned date and time. A listing of all possible entries in this monitoring signal memory is given in the address list (see Appendix C). The memory depth allows for a maximum of 30 entries. If more than 29 monitoring signals occur without interim memory clearance, the M O N : M o n i t o r s i g . m e m o r y signal “Overflow” (address 90 12, value 9) is entered as the last entry.

82 “Warning” signal

The number of entries stored in the monitoring signal memory can be determined by reading the M O N : N o . o f m o n . s i g n a l s counter (address 04 19). The monitoring signal memory can only be cleared manually by a control action. Entries in the monitoring signal memory are not cleared automatically even if the corresponding test has a negative outcome in a new test cycle. The contents of the monitoring signal memory can be read from the local control panel or through the PC or ILSA interface. The time information assigned to the individual entries can be retrieved via the PC or ILSA interface only.

83 Monitoring signal memory

82

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

3 Operation (continued)

The response of the PD 521 to monitoring signals takes one of the following forms depending on the signal. ¨

Signaling Only If there is no malfunction associated with the monitoring signal, then only a signal is issued, and there are no further consequences. This situation exists, for example, when internal data acquisition memories overflow.

¨

Selective Blocking If a fault is diagnosed solely in an area that does not affect the protective function, then only the affected area is blocked. This would apply, for example, to the detection of a fault on the ILSA bus interface module or in the area of the PC interface.

¨

Warm Restart If the self-monitoring function detects a fault that might be eliminated by a system restart, for example a fault in the hardware, then a procedure called a warm restart is automatically initiated. During this procedure, as with any startup, the computer system is reset to a defined state. A warm restart is characterized by the fact that no stored data and, in particular, no setting parameters are affected by the procedure. A warm restart can also be triggered manually by control action. During a warm restart sequence the protective function and communication through serial interfaces will be blocked. If the same fault is detected after a warm restart has been triggered by the self-monitoring system, then the protective function remains blocked but communication through the serial interfaces will usually be possible again.

¨

Cold Restart If a corrupted parameter subset is diagnosed in the checksum test during self-monitoring, then a cold restart is carried out. This is necessary because the protection device cannot identify the corrupt parameter within the set. A cold restart has the result that all internal memories are returned to a defined state. After a cold restart, this means that all settings of the protection device have been discarded. The default settings as found in the address list in the column headed “Default” apply instead (see Appendix C). In order to establish a safe initial state, the default values have been selected so that the protective function is blocked. Both the monitoring signal that triggered the cold restart and the value indicating parameter loss (address 90 28) are entered in the monitoring signal memory.

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

If the protective function is blocked, the condition is signaled with a steady light by the yellow LED indicator H3 on the local control panel or, if desired, via an output relay configured accordingly.

84 “Blocked/faulty” signal

3.16 Serial Interfaces The PD 521 has a PC interface as standard component. The ILSA interface is optional. Both interfaces allow setting and readout. When tests are run on the PD 521 it is advisable to activate the test mode (address 03 12 or binary signal input) so that the PC or the control system evaluates all incoming signals accordingly.

85 Setting the test mode

83

3 Operation (continued)

3.16.1 PC Interface

An FPC operating program is available as an accessory for PD 521 control.

Communication with a PC is via the PC interface. In order for data transfer between the PD 521 and the PC to function, several settings must be made in the PD 521.

86 PC interface settings

84

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

3 Operation (continued)

3.16.2 ILSA Interface Communication between the PD 521 and the control station’s computer is via the ILSA interface. The interface protocol complies with IEC 60870-5-103 ‘Transmission Protocols - Companion Standard for the Informative Interface of Protection Equipment, First edition, 1997-12’.

In order for data transfer to function properly, several settings must be made at the PD 521. The ILSA interface can be blocked through a binary signal input. Moreover, a signal or measured-data blocking can also be imposed via a binary signal input.

87 ILSA interface settings

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

85

4 Design

The PD 521 is mounted in an aluminium case. Connection is via threaded terminal ends. The case is suitable for either wall surface or flush panel mounting. The angle brackets and connector blocks are adjustable for mounting in the chosen configuration. Figures 88 and 89 show the case dimensions and fixture positions. For flush mounting, a cover frame is available (see Installation and Connection). Regardless of the design version, the PD 521 – as the other device types of the ILS-P system – is equipped with a standard local control panel. In order to protect the device according to the specified degree of protection, the local control panel is covered with a tough film. In addition to the essential control and indication elements, a parallel display consisting of a total of 8 LED indicators is also incorporated into the local control panel. The meaning of the various displays is shown in plain text on a label strip.

The label strip is located in a pocket accessible from the rear of the front panel. It can be replaced by user-specific labels. A further label strip lists the addresses for operation-related protection information and can also be replaced by a strip with customized labeling. The processor module with the local control module is attached to the reverse side of the removable front plate and connected to the I/O module via a ribbon cable. The I/O module incorporates the power supply, the input transformers and the power supply converters as well as eight output relays and two optical couplers for binary signals. The serial interface -X6 for parameter setting via a PC is set into the front panel. The optional ILSA interface -X7 and -X8 or -X9 (Order extension number -302 and up) is located on the underside of the case.

88 Dimensional drawing of the PD 521 in wall surface mounting configuration, -X7 and -X8 or -X9 are optional (dimensions in mm)

86

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

4 Design (continued)

89 Dimensional drawing of the PD 521 in flush panel mounting configuration, -X7 and -X8 or -X9 are optional (dimensions in mm)

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

87

5 Installation and Connection

5.1 Unpacking and Packing

5.3 Location Requirements

The PD 521 is packaged separately in its own carton and shipped inside outer packaging. Use special care when opening the cartons and unpacking the equipment, and do not use force. In addition, make sure to remove from the inside carton the Supporting Documents supplied with each individual device.

The PD 521 has been designed to conform to the standard EN 60255-6. Therefore when choosing the installation location it is important to make sure that it provides the conditions specified in the Technical Data (see Chapter 2). Several important conditions are listed below.

The design revision level of each module included with the device in its as-delivered condition can be determined from the list of modules provided in the ‘Assembly List’ supplied with the device (see ‘Components/Modules’). This list should be carefully saved.

Climatic Conditions

After unpacking the equipment, inspect it visually for sound mechanical condition after transportation. If the PD 521 is to be shipped, both inner and outer packaging must be used. If the original packaging is no longer available, make sure that packaging conforms to DIN ISO 2248 specifications for a drop height £ 0.8 m.

¨

Ambient temperature: - 5 to + 55°C

¨

Air pressure: 800 to 1100 hPa

¨

Relative humidity: 45 to 75 % (annual mean), up to 56 days at £ 95% and 40°C. The relative humidity must not result in the formation of either condensed water or ice in the PD 521.

¨

Ambient air: The ambient air must not be significantly polluted by dust, smoke, gases or vapors, or salt.

5.2 Checking Nominal Data and Design Type The PD 521 nominal data and design type can be determined by consulting the type identification label (see Figure 90). The type label is located on the underside of the unit and on the lower side face in front of the terminal strip. The type label is also affixed to the outside of the PD 521 packaging.

PD 521

Schaltbild/diagram 89521.401

P 89521-0-XXXXXXX-302-401-602 Inom=

Unom=100 V AC UE,nom=24V..250VDC

CE

XX.XX fnom=50/60Hz

UH,nom=24 ... 60 V DC / 110 ... 250 V DC, 100 ... 230 V AC

F 6.XXXXXX.X

ALSTOM-Nr.

Vorschrift / specification DIN EN 60255-6 2kV (III)

Made in Germany

90 PD 521 type identification label

The factory setting for the nominal auxiliary voltage VA,nom (‘UH,nom ’) is underlined on the type identification label. The nominal input voltage Vin,nom (‘UE,nom ’) is also shown on the label.

Mechanical Conditions ¨

Vibration stress: 10 to 60 Hz, 0.035 mm and 60 to 150 Hz, 0.5 g

¨

Earthquake resistance:

5 to 8 Hz, 3.5/1.5 mm and 2 8 to 35 Hz, 10/5 m/s

Electrical Conditions for Auxiliary DC Voltage for the Power Supply ¨

Operating range: 0.8 to 1.1 VA,nom with a residual ripple of up to 12% VA,nom

Electromagnetic Conditions Appropriate measures taken in substations must correspond to the state of the art (see, for example, the VDEW ring binder entitled "Schutztechnik" [Protective Systems], Section 8: "Recommendations for Measures to Reduce Transient Overvoltage in Secondary Lines in High Voltage Substations,” June 1992 edition).

From the Order No. (89521-0-...), the design version of the PD 521 can be derived using the key given in Chapter 14 and in the Supporting Documents. With the auxiliary voltage on, identification via the built-in display is also possible. After selecting the addresses given in Section ‘Device Identification’ in the Appendix C to this manual, the corresponding information is displayed.

88

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

5 Installation and Connection (continued)

5.4 Installation The case and mounting dimensions are given in Chapter 4. The PD 521 is delivered in the wall surface mounting or the flush panel mounting configuration depending on the order specifications. When the PD 521 is being installed in a cabinet door, for example, special sealing steps must be followed in accordance with the IP 51 protection required for the cabinet. Should the PD 521 mistakenly have been ordered for surface instead of flush mounting, the connector blocks and angle brackets can be adjusted as shown in Figure 91. ¨ The two angle brackets D need to be removed after undoing bolts C (three each on the upper and lower face). Subsequently, bolts C are repositioned and tightened.

E A

B

C

¨ The two angle brackets D are now re-mounted using bolts E with the longer leg of the angle bracket mounted flat on the face surface. ¨ The upper sections of the two connector blocks B can be pulled away after opening bolts A and remounted after turning by 180 degrees (see Figure 91).

* Please make sure that all bolts A are loosened before attempting to pull off the upper sections of the connector blocks! For flush panel mounting, a panel cutout as per Figure 92 is necessary. The panel thickness must not exceed 3 mm.

D

Front panel

Surface-mounting

Front panel

Flush-mounting 91 Reconfiguration for flush panel mounting 92 Panel cutout for the PD 521 (dimensions in mm)

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

89

5 Installation and Connection (continued)

For wall surface mounting, the leads to the PD 521 are usually run along the front side of the mounting level. If the wiring is to be behind, an opening can be provided below or above the terminal strip (see Figure 93).

For flush mounting, the PD 521 must be fastened using the four bolts provided within the packing carton. The cutout edges and the bolt heads can be concealed using a cover frame with a snap-on fixture to the bolt heads (see Figure 94).

93 Opening for the connecting leads. Shown for the lower terminal strip (dimensions in mm).

94 Fixing the cover frame (dimensions in mm)

90

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

5 Installation and Connection (continued)

5.5 Protective and System Grounding

5.6 Connection

The device case must be reliably grounded for reasons of protective equipment grounding. This grounding step is also absolutely essential for proper operation of the device and is thus equivalent to system grounding. Potentials that need to be grounded from an operational standpoint are already properly connected to the equipment ground inside the unit.

5.6.1 Measuring and Auxiliary Circuits

Holes for the grounding connection are located in the two mounting brackets of the PD 521 and are labeled accordingly.

Copper leads having a 2.5 mm2 cross-section are generally suitable as connecting leads between the current transformers and the PD 521. Under certain conditions the connecting leads between the main current transformers and the PD 521 must be short and have a larger cross-section in order to handle the permissible burden on the main current transformers. Copper leads 2 having a 1.5 mm cross-section are sufficient for the binary signal inputs, voltage inputs, the signaling and triggering circuits, and for the power supply input.

A ground connection assembly kit is supplied with the unit. The ground connection must be assembled as shown in Figure 95. Grounding must be low-inductance.

Connect the PD 521 in accordance with the terminal connection diagram specified on the type identification label. The terminal connection diagram is included in the Supporting Documents supplied with the unit and is also given in Appendix E of this manual.

As a general principle, all connections run into the system must have a defined potential. Pre-wired connections that are not used must be grounded. Connecting the Measuring Circuits of Distance Protection The current and voltage transformers must be connected to the protection device in accordance with the standard schematic diagram shown in Figure 96. The default and factory setting of the protection device is based on this current transformer connection scheme (“line-side grounding“). Connection of the current transformers in opposition (“busbar-side grounding“) can be taken into account when making the settings (see Section 7). The PD 521 is always equipped with four current inputs.

95 Ground connection assembly kit

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

91

5 Installation and Connection (continued)

Connecting Protective Signaling Depending on the operating mode selected, either a signal transmission device or pilot wires are required for signal transmission. Transposed lines should be used for the pilot wires. Two or four lines are required. If only two lines are available, there must be an all-or-nothing relay in each station for coupling received and transmitted signals. The coils of the all-or-nothing relays must be designed for half the loop voltage. Figure 97 shows the connection with two lines and Figure 98 the connection with four lines. The protective signaling transmitting relay can be set to Transm. relay break contact or Transm. relay make contact. In the first case the break contact must be wired and in the second case the make contact. The figures show the connection for the setting Transm. relay break contact (K1 and K2 are shown in the de-energized state). In addition, the PD 521 can also function together with the SV 35A protective signaling system or the V 34 comparator relay if care is taken to ensure that at least a pilot wire current of 10 mA is flowing.

96 Standard connection diagram for the PD 521

92

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

5 Installation and Connection (continued)

97 Connecting protective signaling with two lines

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

98 Connecting protective signaling with four lines

93

5 Installation and Connection (continued)

Connecting Steady-State Ground Fault Direction Determination If the PD 521 is to function using ground fault direction determination by steady-state values, then the current transformer T4 must be connected to a window-type current transformer or a current transformer in Holmgreen configuration. If the metal sheath of the cable is led through the window-type transformer, then the overhead ground wire must be led (insulated) through the core again before it is connected to ground. The cable sealing end must be attached so that it is insulated from ground. In this way any currents flowing through the sheath will not affect measurement.

94

For ground fault direction determination by steady-state values, the neutral-point displacement voltage - formed from the three phase-to-ground voltages - and the ground current are required as measured variables. Figure 99 shows the standard connection of ground fault direction determination by steady-state values. For this connection “forward/LS“ is displayed if a ground fault occurs on the line side. A different connection scheme for the current transformer can be allowed for by making the appropriate setting (see Chapter 7).

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

5 Installation and Connection (continued)

99 Connecting steady-state ground fault direction determination devices to Holmgreen-configuration and window-type transformers

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

95

5 Installation and Connection (continued)

Connecting the Auxiliary Voltage Before connecting the auxiliary voltage VA for the PD 521 power supply, make sure that the nominal value of the auxiliary device voltage agrees with the nominal value of the auxiliary system voltage.

In the upper portion of the I / O module, between output relay and current input transformers, are plug-in jumpers, which are plugged in as shown as follows, depending on the desired auxiliary voltage range.

Polarity reversal protection is provided in the form of a rectifier bridge. To preserve uniformity with other protection devices (L+ on terminal with smaller number), L+ should therefore be connected to terminal 13. The PD 521 has an auxiliary voltage supply that can be switched between ranges and is factory-set for the voltage range of VA,nom = 110 to 250 V DC or 100 to 230 V AC.

!

Before changing the auxiliary voltage range, turn off any connected auxiliary voltage. The components located behind the front panel are energized!

The voltage range is switched by repositioning plug-in jumpers on the I / O (input / output) module. After loosening four bolts on the front side of the front panel, the local control module (front panel and processor module) can be removed once the following plugs have been removed first: ¨ The tab connector on the case

100 Plug-in jumpers positioned for an auxiliary voltage of 110 to 250 V DC or 100 to 230 V AC (view from component side)

101 Plug-in jumpers positioned for an auxiliary voltage of 24 to 60 V DC (view from component side)

¨ The tab connector on the lower circuit board (I/O module) ¨ The ribbon cable connecting the local control module (front panel and processor module) with the I/O module ¨ The ribbon cable connecting the local control module with the optional ILSA interface (to fiber optics or to wire)

!

96

Where possible, disconnection of the ribbon cable between the processor module and the I/O module should be avoided. Should disconnection have occurred, however, then the device needs to be re-initialized by way of a cold restart.

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

5 Installation and Connection (continued)

5.6.2 Binary Control Inputs

5.6.4 PC Interface

Before connecting the control voltage Vin,nom for the binary inputs in the PD 521, check to see whether the control voltage Vin,nom is within the operating range of 24 V DC to 250 V DC. Polarity reversal protection is provided in the form of a rectifier bridge.

The PC interface is provided so that PS 441 parameters can be assigned from a personal computer (PC). The special connection cable available as an accessory is the only type of PC connection that may be used.

5.6.3 Tripping and Signaling Circuits

!

The freely configurable output relays and their connections are shown in the terminal connection diagram. The output relays are suitable both for tripping and signaling purposes.

The PC interface is not intended for permanent connection. Consequently the socket does not have the extra insulation from circuits connected to the system that is required per VDE 0106 Part 101. Therefore when connecting the connection cable make sure that you do not touch the socket contacts.

After completing device control (parameter setting) via the PC, disconnect the PC connection cable on the interface socket to restore the specified degree of device protection. 5.6.5 ILSA Interface The ILSA interface is provided for stationary linking of the protection device to a control system for substations or to a central substation unit. Connection is - dependeing on the design of the ILSA interface - via a special connector with a fiber-optic conductor or via an RS 485 interface with twisted copper wires. The selection and assembly of an appropriately cut optical fiber connecting cable requires special knowledge and expertise and is therefore not covered by this operating manual.

!

Before connecting or removing the fiber-optic interface, the supply voltage of the protection device must be switched off.

Connection of the RS 485 interface to other devices is via a 2-pole twisted conductor cable. For further guidelines on connecting the ILSA interface, please see the manual Bus Technology in Integrated Protection and Control Systems for Substations (ILS).

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

97

6 Control

All data required for operation of the protection device are entered from the local control panel, and the data important for system management are read out there as well. The local control panel permits the following specific functions: ¨

Readout and modification of settings

¨

Readout of updated measured operating data and state signals as well as stored monitoring signals

¨

Readout and resetting of counters

¨

Resetting of the parallel display (LEDs) and other control functions for testing and startup

¨

Value The value of the information or parameter just selected is displayed.

¨

Address The address of the information or parameter just selected is displayed.

¨

Address Selection: In the normal addressing mode, the two pairs of keys are decoupled from one another and affect the address display. The x coordinate of the address being selected can be set using the left pair of keys, and the y coordinate can be set using the right pair of keys. The respective coordinate can be incremented by pressing the “up” key and decremented by pressing the “down” key.

Control is also possible from the PC interface. In that case the FPC control program is required, along with a special connection cable (see chapter 13 “Accessories and Spare Parts”) and a suitable PC. 6.1 Display and Keyboard The local control panel consists of two 4-digit, 7-segment displays, six function keys and 12 LED indicators.

Changing Parameter Values: Parameter values can only be changed in the input mode, which is signaled by the red LED indicator on the enter key (E). In the input mode the two pairs of “up” and “down” keys are generally coupled and have the same effect on the value display. The system runs through a value range, which is defined separa- tely for each address together with the incrementation (see “Address List” in the appendix). The next higher value is obtained by pressing the “up” key, and the next lower value by pressing the “down” key.

F

0 03 10 x

“Up” and “Down” Keys Addresses can be selected, parameter values changed and event records read out by pressing the “up” and “down” keys.

Value Address

y

"Up" Key

Event Record Readout: "Down" Key Enter Key E

R

Readout of event records is possible after the appropriate memory has been accessed; this is signaled by the red LED indicator on the enter key (E). In this control mode the two pairs of “up” and “down” keys have different functions.

Reset Key

¨ 102 View of the local control panel

Enter To enter the input mode, press enter key (E). Press a second time to leave the input mode. Activation of the input mode is signaled by the red LED indicator on the enter key (E).

The settings, signals and measured values are numerically coded. This code is called the address and is displayed in the lower of the two 7-segment displays on the local control panel. The value associated with the address is displayed in the upper 7-segment display.

98

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

6 Control (continued)

¨ Reset The LED indicators can be reset by pressing the reset key (R). The event records are not affected and remain in the event memories. Other functions of the reset key include deactivation of the input mode (with no further consequences) and keyboard locking. The following diagrams of the individual control steps indicate which specific display can be changed by pressing the “up” or “down” keys. A solid black dot in the upper left corner of the enter key indicates that the red LED indicator is lit up. The addresses used in the examples below are not necessarily valid for the PD 521; they serve to illustrate the principles of local control.

6.3 Change-Enabling Function Although it is possible to select any address and read the associated value by pressing the “up” and “down” keys, it is not possible to switch directly to the input mode. This safeguard prevents unwanted changes in the protective setting. If the protective setting is to be changed, the change-enabling function (address 03 10) must first be activated. The change-enabling function is naturally the only parameter that can be changed when the changeenabling function itself is not activated. Control Step or Description

Action

Display

0

Select the address for the changeenabling function by pressing the “up” and “down” keys.

6.2 Address Selection Addresses are selected by pressing the two pairs of “up” and “down” keys. As long as the keys are being pressed, the value display remains dark. Approximately 1 second after the keys are released the value associated with the selected address will appear in the value display. In principle, any address in the entire address range from 00 00 to 99 99 can be selected. If, however, an address is selected that is not used in the PD 521, the value display will remain dark. The existence of entries in the signal or monitoring signal memories is indicated during operation. This is indicated by the fact that while the “up” and “down” keys are being pressed the value display does not remain dark; instead, the following messages are displayed: ¨

"L..." if there is information in the signal memory

¨

"...E" if there is information in the monitoring signal memory

If “L” and/or “E” still remain in the value display 1 second after the “up” and “down” keys have been released, then there is no information stored for that particular address.

F

0 03 10

1 Press the enter key (E). The red LED indicator on the enter key will light up. The value can now be changed by pressing the “up” or “down” keys.

x

y

E

R

F

E

0 03 10 x

y

E

R

2

Set the value to “1” by pressing one of the two “up” keys.

F

1 03 10 x

y

E

R

Example: Information in Signal Memory

Information in Information in Monitoring Signal Signal and Memory Monitoring Signal Memories

F

F

E

L 47 11 x

F

y

47 11 x

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

y

L

E

3

Press the enter key (E). The red LED indicator on the enter key will go out. The change-enabling function is active.

F

E

1 03 10 x

y

E

R

47 11 x

y

99

6 Control (continued)

To prevent the change-enabling function from accidentally remaining active after a protective setting has been changed, the enabling function is automatically canceled 100 sec after the last key has been pressed (or once the return time set at address 03 14 has elapsed). The address display immediately jumps to the settable return address (set at address 03 13). The factory-set return address is the address for the change-enabling function. The return time is restarted when any of the six control keys is pressed. Even when the change-enabling function is activated, not all parameters can be changed. For many settings it is also necessary to deactivate the protective function (address 03 30). Such settings include, for example, the configuration parameters by means of which the device interfaces can be adapted to the system. The following entries in the “Change” column of the address list (see Appendix C) indicate whether values can be changed or not:

1 Select the desired address

F

(address 03 13, for example) by pressing the “up” or “down” keys.

2 Press the enter key (E). The red LED indicator on the enter key will light up. The value can now be changed by pressing the “up” or “down” keys.

03 10 03 13

E

"on": The value can be changed even when the protective function is enabled.

¨

"off": The value can be changed provided that the protective function has been disabled.

¨

"-":

When the change-enabling function is activated, the protective function can be deactivated from address 03 30 by setting the value to “0.” The protection device is factoryset so that the protective function is deactivated. 6.4 Changing Settings

Set the new value (04 20, for example) by pressing an “up” or “down” key. During this process the device continues to operate with the old value.

change-enabling function is activated and the protective function, if applicable, is deactivated.

4 Press the enter key (E). The red LED indicator on the enter key will go out, and the device will now operate with the new value. Another address can be selected for value changing by pressing the “up” and “down” keys.

F

1 03 10

E

100

5 If the intended value change is

Display

x

R

F

03 10

x

y

E

R

F

04 20 03 13

E

y

rejected during the setting process (red LED indicator on enter key is lit up), then press the reset key (R). The red LED indicator on the enter key will go out, and the device will continue to operate unchanged with the old value. Another address can be selected for value changing by pressing the "up" or "down" keys.

x

y

E

R

F

04 20 03 13

If all the conditions given above for a value change are satisfied, the desired setting can be entered.

0 Example of a display. The

E

03 13

The value cannot be modified by control action.

Action

y

3

¨

Control Step or Description

x

R

x

y

E

R

F

03 10 03 13 x

y

E

R

R

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

6 Control (continued)

6.5 Memory Readout

Control Step or Description

Memories can be read out after they are accessed via the appropriate entry address. For this purpose it is not necessary to activate the change-enabling function or even to deactivate the protective function. Accidental clearance of a memory via its entry address is not possible.

Press the enter key (E). The address display changes from 03 00 to 04 20. A period is displayed after each digit in the address. This indicates that a special memory mode is now active. The fault number of the most recent fault (e.g. number 2) appears in the value display for address 04 20. In every fault record the fault number is placed at the beginning of the related fault log for identification purposes. Since for each new fault record the actual value of address 04 20 is increased by the value of "1" in order to count faults, the fault number of the most recent fault also corresponds to the number of recorded faults since the signal memory was last reset. If, after entry into the signal memory, the address 04 20 and the value "0" are indicated, then no fault is stored in the signal memory.

6.5.1 Signal Memory Readout Control Step or Description

Action

Display

0 Example of a display.

F

0 03 10

1 Select the address for entering the signal memory (03 00) by pressing the “up” or “down” keys.

x

y

E

R

Action

2

Display F

E

2 0.4. 2.0. x

y

E

R

3

When the “up” key is pressed there is no response.

F

--

- L

E

2 0.4. 2.0.

03 00 x

F

x

y

E

R

y

R

4 When the “down” key for y is pressed repeatedly, the date and time at fault inception appear. ¨ Year

Address 03 98

¨ Day/Month

Address 03 97

¨ Hour/Minute

Address 03 96

¨ Seconds

Address 03 94

¨ Milliseconds

Address 03 93

F

19 9 3 0.3. 9. 8. x

y

E

R

5 When the “down” key for y is pressed again, the oldest signal that appeared during the pre-fault period is displayed. Here the value “1” in the value display means that the signal has started. The end of the signal is indicated by the value “0” in the value display.

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

F

1 0.3. 8.6. x

y

E

R

101

6 Control (continued)

Control Step or Description

6 If the “down” key for y continues to be pressed, the fault signal log is read in chronological order, i.e., in the direction of more recent signals. Signals that have appeared during the fault are marked with an extra “L” in the value display. After the signals that appeared during the post-fault period, the measured fault data are displayed. If a fault value was not measured, the display will show the symbol “....” If the measured fault value is outside the acceptable range, the symbol “-..-” will appear in the display.

Action

Display F

L

102

Display

10

If the display does not change when the “down” key for y is pressed, then the end of the record for the oldest stored fault has been reached.

F

0 4.1. 0.1.

y

x

y

E

R

E

R

11

F

1

When the x "down" key is pressed, the display jumps to the beginning of the next older fault. If the display already showed the oldest fault, nothing changes when the x “down” key is pressed.

F

1 0.4. 2.0. x

y

E

R

0.3. 8.6. x

y

E

R

12

When the x “up” key is pressed the display jumps to the beginning of the fault.

F

2 0.4. 2.0.

F

x

y

E

R

1 0.4. 2.0. x

y

E

R

9 When the “up” key for y is pressed the display does not jump again to the last entry for the next most recent fault log but rather back to address 04 20 (= fault number) and thus back to the beginning of the record for the next most recent fault.

Action

x

8 After the last entry in a fault log has been reached by repeatedly pressing the “down” key for y, then the next time the “down” key for y is pressed the display switches to the beginning of the next oldest fault. The beginning of this fault log is indicated again by the respective fault number, which appears first in the top display (number 1 in this example).

1

4.1. 0.1.

7 The next oldest signal is displayed by pressing the “up” key for y.

Control Step or Description

F

2 0.4. 2.0. x

y

E

R

13

The signal memory is exited by pressing the reset key at any location in the signal memory. The periods displayed after each digit disappear, and the address for entry into the signal memory is displayed (03 00). Any address can then be selected by pressing the “up” or “down” keys.

R

F

- -

- L

03 00 x

y

E

R

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

6 Control (continued)

6.5.2 Monitoring Signal Memory Readout Control Step or Description

Action

5 The next most recent signal is displayed by pressing the “down” keys.

Display

0 Example of a display.

F

0 03 10

1

Select the address for entry into the monitoring signal memory (03 01) by pressing the “up” or “down” keys.

x

y

E

R

most recent monitoring signal appears in the address and value displays (address 90 28 and the value 1, for example). A period is displayed after each digit in the address. This indicates that a special memory mode is now activated. If, after entry into the monitoring signal memory, the address 00 00 and the value "0" are displayed, then no monitoring signals are stored in the monitoring signal memory.

x

y

E

R

F

when the “up” keys are pressed, then the oldest stored monitoring signal has been reached.

7 The monitoring signal memory is

F

E- -03 01

2 Press the enter key (E). The

6 If the display no longer changes

exited by pressing the reset key (R) at any location in the monitoring signal memory. The periods displayed after each digit in the address display disappear, and the address for entry into the monitoring signal memory (03 01) is displayed. Any address can then be selected by pressing the “up” or “down” keys.

1

9.0. 2.8.

R

x

y

E

R

F

E- -03 01 x

y

E

R

F

E

1

9.0. 2.8. x

y

E

R

3 When the two “down” keys are

F

pressed there is no response.

1

9.0. 2.8. x

y

E

R

4 The next oldest monitoring signal is displayed by pressing one of the two “up” keys. All monitoring signals can be read in reverse chronological order, i.e., in the direction of older signals, by repeatedly pressing one of the two “up” keys.

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

103

6 Control (continued)

6.6 Resetting

2 Press the enter key (E). The

All information memories – particularly the signal and monitoring signal memories – and LED indicators can be reset manually. In addition, the LED indicators are automatically cleared and reset at the start of a new fault so that they always display the last fault. The user can also reset the LED indicators manually by pressing the reset key; this is always possible when the device is in the normal control mode. It always triggers an LED indicator test. The signal memory is not affected by this process so that accidental erasing of the fault record associated with the reset signal pattern is reliably prevented. Because of the signal memory’s ring structure the information in this memory is automatically updated for five consecutive events, so that in principle a manual reset would not be necessary. However, if the signal memory should need to be cleared completely – after function tests, for example – this can be done via the corresponding reset address. Control Step or Description

Action

Display

0 Example of a display.

F

0 03 10 x

y

E

R

1 Press the “up” or “down” keys to select the address for resetting the signal memory (03 06). The number of faults recorded since the signal memory was last reset will appear in the value display (the number 2, for example).

104

F

E

red LED indicator on the enter key will light up. When the “up” and “down” keys are pressed there is no response.

2 03 06

3 Press the enter key (E). This

control mode (red LED indicator is lit up), the request to erase fault records is rejected, press the reset key (R). The red LED indicator on the enter key will go out, and the fault records continue to be stored in the device unchanged. Then any address can be selected by pressing the “up” and “down” keys.

y

E

R

F

E

triggers an LED indicator test. After it is completed the red LED indicator on the entry key will go out, and all fault records will be erased. Any address can then be selected by pressing the “up” and “down” keys.

4 If, after exiting the normal

x

0 03 06 x

y

E

R

F

R

2 03 06 x

y

E

R

F

2 03 06 x

y

E

R

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

6 Control (continued)

6.7 Password-Protected Control Operations

4 Press the “down” key for y.

F

0

Certain actions from the local control panel, such as a manual trip command for testing purposes, have a special access lock to prevent accidental output. This special lock, called a password, consists of a specifically defined sequential combination of keys pressed within a certain time period. The following example shows the passwordprotected output of a manual trip command: Control Step or Description

Action

Display

03 40 x

y

E

R

5 Press the “up” key for y.

F

0

0 Example of a display. The

F

change enabling command has been issued (03 10=1).

03 40

1

x

y

E

R

03 10 x

y

E

R

1

F

trip command (03 40) by pressing the “up” and “down” keys. A zero will appear in the value display.

03 40

0

x

y

E

R

03 40 x

y

E

the red LED on the enter key will light up. Although the change mode is active, the value cannot be changed by pressing the “up” and “down” keys. A “change of value” is only possible in this case by means of a specified sequential key combination (control steps 3 to 6) within a specific time period. The following control steps, steps 3 to 6, must therefore be carried out within 4 seconds.

F

value display will change from 0 to 1.

1 Select the address for the manual

2 After the enter key (E) is pressed

6 Press the “down” key for x. The

R

F

E

0 03 40 x

the trip command. The value display will drop back to zero. If the reset key (R) is pressed instead of the enter key, no trip command will be issued (value display returns to 0).

F

E

0 03 40 x

y

E

R

y

E

3 Press the “up” key for x.

7 Press the enter key (E) to issue

R

F

0 03 40

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

x

y

E

R

105

6 Control (continued)

6.8 Keyboard Lock

Control Step or Description

After all settings have been made, the keyboard can be locked. This means that unauthorized or unintentional changes are no longer possible. To lock the keyboard the value “1” must be set at address 03 11 (password). When the keyboard is locked the only key still functionally active is the reset key. When the “up” or “down” keys are pressed there is no response from the device.

0 Example of the display when the

Control Step or Description

Action

Display

0 Example of a display. The

address. All LEDs will light up.

2 Wait until the LEDs go out. Press the reset key (R) again. After this nothing will happen when the x or y “up” and “down” keys are pressed. After the automatic return time has elapsed the address display will show the return address, and the associated value will appear in the value display. The return address in this example is 03 10.

keyboard is locked. The reset key (R) is enabled for resetting the LED indicators.

F

0 03 10 x

y

E

R

1 Press the “up” key for x.

F

0

0

03 10

03 10 x

y

E

R

x

y

E

R

2 Press the “down” key for y.

F

0 R

03 10 x

y

E

R

F

R

0 03 10 x

y

3 Press the “up” key for y.

F

0 E

R

If there is no response when the “up” and “down” keys or the enter key are pressed (but the R key is active and causes the LED indicators to be reset), then the keyboard is locked. The lock can be released by carrying out the following operations. However, the four keys must be pressed within 4 seconds.

03 10 x

y

E

R

4 Press the “down” key for x.

F

Now the “up” and “down” keys for x and y are enabled for selection of a new address.

106

Display

F

keyboard is unlocked. Note: for this procedure the value “1” must be set at address 03 11 (password).

1 Press the reset key (R) at any

Action

0 03 10 x

y

E

R

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

7 Settings

The PD 521 distance protection device must be adjusted to the system and to the protected equipment by means of appropriate settings. This section gives instructions for determining the proper settings. The address list in the Appendix lists all parameters with their setting ranges and incrementation or selection tables. The Set Value Record Sheets in the Appendix make it possible to keep a complete and well-organized record of all settings. The units are supplied with a factory-set configuration of settings that in most cases correspond to the “default setting” given in the address list. If the factory settings differ from the default settings, then this is indicated below at the appropriate points.

7.1 Device Identification The device identification settings are used to record the ordering information and the design version of the protection device. They have no effect on the protective function. These settings should only be changed if the design version of the protection device is modified. 7.1.1 Ordering Information 00 00

IDENT: Device type The type designation numbers are displayed, for example, “521” for PD 521. The display cannot be altered.

00 48 00 49

IDENT: Device password 1 IDENT: Device password 2 This setting is used by the FPC software for identification. For further details regarding these settings see the description of the FPC operating program.

00 50

IDENT: Auxiliary voltage Setting of the auxiliary voltage employed, for example, “220” for 220 V DC.

00 51

IDENT: Nominal voltage Nominal voltage setting, for example, “100” for Vnom = 100 V.

00 52

IDENT: Nominal current The nominal current setting of the phase current transformers, for example, “1.0” for Inom = 1 A.

00 53

IDENT: Nominal frequency The nominal frequency setting of the measuring circuits, for example, “50” for 50 Hz.

00 54

IDENT: Nominal current IN The nominal current setting of the residual current transformer, for example, “1.0” for Inom = 1 A.

00 80

IDENT: Add. HW modules The hardware expansion setting for the protection device. The PD 521 automatically carries out a warm restart in accordance with this setting. The value can be increased but not decreased. If a lower value is to be set, a cold restart must be carried out. This setting can only be made from the integrated local control panel.

The default settings given in the address list are activated after a cold restart. All settings must be re-entered after a cold restart.

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

107

7 Settings (continued)

7.1.2 Design Version

7.2 Configuration Parameters

The software version of the modules used in the PD 521 can be read out at the addresses in this group.

The interfaces are adapted to the system conditions by setting the configuration parameters.

02 00

02 20

IDENT: Data model The value displayed provides information about the data model that must be installed in the PC so that the PD 521 can be operated using the FPC operating program. This display cannot be altered.

7.2.1 Control Interfaces 03 11

LOC: Access lock active Since the local control panel is always accessible, measures have been taken to allow the local control panel to be locked. A “0” setting means “Locking not possible,” and a setting of “1” means “Locking possible”. The keyboard is then locked by pressing the R key twice at any address.

03 12

Fig. 85 PC/ILSA: Test mode USER When the test mode is activated signals or measured data for PC and ILSA are identified as “test mode”. One of the procedures that demand activation of the test mode is the testing of the output relays via the integrated local control panel.

03 13

LOC: Autom. return addr. The address to which the display will return after the automatic return time has elapsed is set here. Thus the units will display welldefined information during operation.

03 14

LOC: Autom. return time If no key on the local control panel is pressed during this set time, the following will occur automatically:

IDENT: SW version The software version installed in the hardware is displayed. This display cannot be changed.

¨

The display returns to the address defined under 03 13

¨

The change-enabling function is canceled.

This ensures that the change-enabling function will not remain inadvertently activated over a long period of time. The keyboard is not automatically locked.

108

03 50

Fig. 87 ILSA: Delta V A measured voltage value is transmitted via the ILSA interface if it differs by the set delta quantity from the last measured value transmitted.

03 51

Fig. 87 ILSA: Delta I A measured current value is transmitted via the ILSA interface if it differs by the set delta quantity from the last measured value transmitted.

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

7 Settings (continued)

03 52

Fig. 87 ILSA: Delta f The measured frequency is transmitted via the ILSA interface if it differs by the set delta quantity from the last measured value transmitted.

03 53

Fig. 87 ILSA: Delta t All measured data are transmitted again through the ILSA interface after this time period has elapsed.

03 54

Fig. 87 ILSA: Delta P The active power is transmitted through the ILSA interface if it differs by the set delta quantity from the last measured value transmitted.

03 70

Fig. 87 ILSA: Command enable USER ILSA interface communication enabling function.

Note: If the ILSA interface has been activated from address 00 80 and there is no ILSA connection or it is inactive, then the command enable should be set at "0". For this setting, the commands are rejected and the time synchronization signal is received and reset; cyclic measured data are not transmitted. 03 71

Fig. 87 ILSA: Baud rate The ILSA interface baud rate setting.

03 74

Fig. 87 ILSA: Transm. cycl. data The measured data that are to be transmitted cyclically through the ILSA interface are selected.

03 76

03 55

Fig. 86 PC: Delta V A measured voltage value is transmitted via the PC interface if it differs by the set delta quantity from the last measured value transmitted.

03 56

Fig. 86 PC: Delta I A measured current value is transmitted via the PC interface if it differs by the set delta quantity from the last measured value transmitted.

Fig. 87 ILSA: Sig./meas.blck. USER When the signal and measured data block is activated, no signals or measured data are transmitted through the ILSA interface. Commands to the ILSA interface are rejected.

03 57

Fig. 86 PC: Delta f The measured frequency is transmitted via the PC interface if it differs by the set delta quantity from the last measured value transmitted.

Note: When the ILSA interface is activated via address 00 80 and there is no ILSA connection or it is not active, the signal and measured value blocking should be set to“1”.

03 58

Fig. 86 PC: Delta t All measured data are transmitted again through the PC interface after this time period has elapsed.

03 59

Fig. 86 PC: Delta P The active power is transmitted through the PC interface if it differs by the set delta quantity from the last measured value transmitted.

03 68 03 69

Fig. 86 PC/ILSA: Device addr. (CU) Fig. 86 PC/ILSA: Device addr. (PU) The device address is used for device identification when communication is being carried out through the serial interfaces. The device address of the communication unit (CU) and the device address of the process unit (PU) must have the identical setting.

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

03 77

Fig. 87 ILSA: Contin. general scan A continuous or background general scan means that the PD 521 transmits all settings, signals and monitoring signals through the ILSA interface during slow periods when there is not much activity. This ensures that there will be data consistency with a connected control system. The time to be set defines the minimum time difference between two telegrams.

03 80

Fig. 86 PC: Command enabling PC interface communication enabling function.

03 81

Fig. 86 PC: Baud rate Baud rate setting for the PC interface.

03 84

Fig. 86 PC: Transm. cycl. data The measured data that are to be transmitted cyclically through the PC interface are selected.

109

7 Settings (continued)

03 86

Fig. 86 PC: Sig./meas. val.block. When the signal and measured value blocking is activated, no signals or measured data are transmitted through the ILSA interface. Commands to the ILSA interface are rejected.

7.2.2 Binary Inputs The PD 521 has two optical coupler inputs for processing binary signals from the system. The connection scheme for the binary inputs is shown in the terminal connection diagrams. The address list gives information about the configuration options for all binary inputs (see Appendix C). When configuring binary inputs it is essential to ensure that the same information cannot be processed by two binary signal inputs. This means that a given function can only be assigned to one binary signal input and not to both. A standard setting that differs from the “default setting” given in the address list has been factory-set. The factory setting is given in the terminal connection diagrams in the Supporting Documents supplied with each device and also in Appendix E of this manual.

Configurable Functions Value 03 26 03 27 04 61 04 64 36 34 36 38 36 45 36 46 36 47 36 48 36 49 36 51 36 88 36 89 37 18 37 70 37 72 37 74 38 16 38 20 40 16 40 17 65 01

Description

Min. triggering time

MAIN: Deactivate prot. EXT MAIN: Activate prot. EXT MAIN: M.c.b. trip VLS EXT PSIG: Telecom. faulty EXT CBF: Input EXT PSIG: Test telecom. EXT MAIN: Trip cmd. block EXT DIST: Zone extension EXT SOTF: Manual close EXT PSIG: Receive EXT PSIG: Blocking EXT MAIN: CB closed sig. EXT FLOC: Trigger EXT FREC: Trigger EXT MAIN: Man. trip cmd. EXT PC/ILSA: Test mode EXT ILSA: Command enable EXT ILSA: Sig./meas.block EXT MAIN: Starting trig. EXT GFDSS: GF evaluation EXT PASS. Input 1 EXT PASS. Input 2 EXT MAIN: Reset indicat. EXT

20 ms 20 ms 20 ms 20 ms 20 ms 20 ms 20 ms 20 ms 20 ms 20 ms 20 ms 20 ms 20 ms 20 ms 20 ms 20 ms 20 ms 20 ms 20 ms 20 ms 20 ms 20 ms 20 ms

Fig. 3 3 35 42 54 52 69 23 39 50 40 37 79 81 69 85 87 87 69 54 71 71 76

In order to ensure that the protection device will recognize the input signals, the triggering signals must persist for at least as long as the time periods given in the following table.

110

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

7 Settings (continued)

The operating mode of every binary signal input can be selected. It is possible to specify whether the presence or absence of a voltage (mode active “high” or active “low,” respectively) shall be interpreted as the logic “1” signal. 54 01 54 04

INP: Fct. assignm. U 1 INP: Fct. assignm. U 2 Assign functions to binary signal inputs.

54 02 54 05

INP: Operating mode U 1 INP: Operating mode U 2 Specify operating mode of binary signal inputs.

7.2.3 Binary Outputs The PD 521 has output relays for outputting binary signals. The number and connection scheme of the available output relays are given in the terminal connection diagrams. The address list gives information about the configuration options for all binary outputs (see Appendix C). The contact data for the all-or-nothing relays permits them to be used either as command relays or as signal relays. One signal can also be assigned to several output relays simultaneously for the purpose of contact multiplication. A standard setting that differs from the “default setting” given in the address list has been factory-set for some of the freely configurable output relays. The factory setting is given in the terminal connection in the Supporting Documents supplied with each device and also in Appendix E of this manual. 51 01 51 03 51 05 51 07 51 09 51 11 51 13 51 15

7.2.4 LED Indicators The PD 521 has a total of 12 LED indicators for parallel display of binary signals. The address list gives information about the configuration options for all LED indicators (see Appendix C). A standard setting that differs from the “default setting” given in the address list has been factory-set for some of the freely configurable LED indicators. The factory setting is given in the terminal connection diagrams of the Supporting Documents supplied with the device and in Appendix E of this manual. 57 01 57 03 57 05 57 07 57 09 57 11 57 13 57 15 57 17 57 19 57 21 57 23

LED: Fct. assignm. H 1 LED: Fct. assignm. H 2 LED: Fct. assignm. H 3 LED: Fct. assignm. H 4 LED: Fct. assignm. H 5 LED: Fct. assignm. H 6 LED: Fct. assignm. H 7 LED: Fct. assignm. H 8 LED: Fct. assignm. H 9 LED: Fct. assignm. H 10 LED: Fct. assignm. H 11 LED: Fct. assignm. H 12 Assign functions to LED indicators. LED indicators H 1, H 2 and H 3 have permanently assigned functions.

OUTP: Fct. assignm. K 1 OUTP: Fct. assignm. K 2 OUTP: Fct. assignm. K 3 OUTP: Fct. assignm. K 4 OUTP: Fct. assignm. K 5 OUTP: Fct. assignm. K 6 OUTP: Fct. assignm. K 7 OUTP: Fct. assignm. K 8 Assign functions to output relays.

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

111

7 Settings (continued)

7.3 Function Parameters

10 48

Fig. 4 MAIN: Neutral-point treat. The neutral-point treatment for the network must be set.

10 49

Fig. 16 MAIN: Rotary field The rotary field direction, either clockwise or counterclockwise, must be set.

21 12

Fig. 69 MAIN: Trip cmd. block USER The trip command is blocked from the local control panel. On delivery, the trip command is not blocked.

7.3.1 Global The PD 521 can be adjusted to the network and system conditions by means of a few global settings. 03 30

10 03

10 04

10 30

10 40

10 41

112

Fig. 3 MAIN: Protection active Deactivation or activation of the protective function. The parameters indicated by “off” in the address list can only be changed when protection is deactivated. The devices are shipped with the protection functions disabled. Fig. 2 MAIN: Nominal current Distance protection includes this setting when calculating all settings and measured data in 9. Therefore for proper operation of distance protection, the PD 521’s nominal current, 1 A or 5 A, must be entered. Fig. 2 MAIN: Connect. meas. circ. Connection of the measuring voltage circuits determines directional measurement of the distance protection function. If the connection is made as described in Chapter 5, then the “Forward” setting (1) should be selected if the PD 521’s “forward” decision will be in the direction of the outgoing feeder. If the connection direction is reversed or, given the connection direction according to Chapter 5, if the decision for “forward” is to be in the busbar direction, then the setting must be “2.”

MAIN: System frequency The nominal frequency of the network must be set. If the chosen setting is “60“ = 60 Hz, the ground fault direction determination by steady-state values cannot be enabled. Fig. 13 MAIN: Transfer for 1p For single-phase overcurrent starting without ground starting either ground starting or another phase starting needs to be transfertripped. The user may choose to always trip the ground starting function or, depending on current magnitude, ground or phase starting. See the section on “Starting Logic” in Chapter 3 for more information. Fig. 14 MAIN: Phase priority 2pN The selection of measured variables in the event of two-phase grounded faults is a function of the set phase priority.

7.3.2 Main Functions 10 36

Fig. 4 START: tI>> Setting for the operate delay of overcurrent starting.

10 50

START: Xfw Setting for the reactance limit of underimpedance starting.

10 51

Fig. 12 START: Rfw P-G Setting for the resistance limit of underimpedance starting for phase-to-ground loops.

10 52

Fig. 12 START: Rfw P-P Setting for the resistance limit of underimpedance starting for phase-to-phase loops.

10 53

Fig. 12 START: Zbw/Zfw Setting for the limit of underimpedance starting in the backward direction.

10 54

Fig. 4 START: I>> Setting for the threshold operate value for overcurrent starting.

10 55

Fig. 5 START: IN> Setting for the threshold operate value of the ground current stage for ground starting.

10 56

Fig. 5 START: VN-G> Setting for the threshold operate value of the voltage trigger VN-G> for ground starting. If the nominal voltage of the station transformer differs from 100 V, the setting must always be referred to the nominal voltage of the PD 521 (see type identification label) and not to the nominal voltage of the station transformer.

Fig. 12

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

7 Settings (continued)

10 57

Fig. 5 START: tIN> In systems with isolated/resonant neutralpoint grounding, the operate delay tIN> should be set so that the ground currents IN that flow as the result of phase-to-ground capacitance reversals do not lead to erroneous ground starting.

10 67

Note:

Starting does not occur in the case of ungrounded single-phase faults until tIN> has elapsed.tIN> should never be set less than 20 ms so that starting transfer will not anticipate starting in another phase. 10 60

Fig. 7 START: Trip tVN-G>> Using this setting it is possible to specify whether, for operation of the S T A R T : V N - G > > trigger, a trip command shall be issued after the S T A R T : t V N - G > > timer stage has elapsed.

Fig. 5 START: tVN-G>> The operate delay time setting for the S T A R T : V N - G > > trigger.

10 62

Fig. 5 START: VN-G>> Setting for the threshold operate value of the VN-G>> trigger for ground starting. If the nominal voltage of the station transformer differs from 100 V, the setting must always be referred to the nominal voltage of the PD 521 (see type identification label) and not to the nominal voltage of the station transformer.

10 63

Fig. 12 START: > Angle setting for load masking during underimpedance starting.

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

o

Without V< starting. Undervoltage starting is deactivated.

o

With V< starting, P-G. Undervoltage starting evaluate decisions of phase-to-ground loops only.

o

With V< start. P-G, P-P. Undervoltage starting measurement systems are switched by ground starting from phase-to-phase to phase-to-ground systems.

10 68

Fig. 8 START: I> (Imin) Base current setting above which undervoltage and underimpedance starting is enabled.

10 69

Fig. 9 START: V< Threshold operate value setting for undervoltage starting.

Note: A trip command is issued only if MAIN: Neutral-point treat. is set to Low-impedance grounding. 10 61

Fig. 9 START: Operating mode Operating mode setting for underimpedance and undervoltage starting. The following settings are possible:

Note: The undervoltage fault detection logic can be disabled with the setting “0“. This is permitted only if a starting by the overcurrent fault detection logic is assured for near faults (Vsh < 2% Vnom). 25 93

Fig. 12 START: Z evaluation This setting determines whether the PD 521 will carry out the impedance calculation of the phase-to-ground loops using the phase current corrected by the set ground factor or using twice the phase current.

113

7 Settings (continued)

12 00

Fig. 28 DIST: Zone 4 Zone 4 can be used as a special zone. This setting determines the way in which zone 4 will be utilized. The following settings are possible: o

Normal A directional and timer stage is assigned to each impedance zone.

o

Section cable - line With this setting the impedance setting of impedance zone 4 is assigned to timer stage t1 and directional setting N1. The settings t4 and N4 are inactive. If a trip occurs in impedance zones 1 and 4 after t1 has elapsed, an external ARC can be blocked.

o

12 01 12 02 12 03 12 04

Section line - cable With this setting the impedance setting of impedance zone 4 is assigned to timer stage t1 and directional setting N1. The settings t4 and N4 are inactive. If a tripoccurs in impedance zone 1 only, after t1 has elapsed, an external ARC can be blocked.

Fig. 23 DIST: R1 P-G (polygon) Fig. 22 DIST: R2 P-G (polygon) Fig. 22 DIST: R3 P-G (polygon) Fig. 22 DIST: R4 P-G (polygon) Resistance limit setting for impedance zones 1 to 4 in secondary values for the phase-toground loops.

Note:

114

Zone 4 can be used as a special zone (see D I S T : Z o n e 4 setting). This must be taken into account when setting X4.

Zone 4 can be used as a special zone (see D I S T : Z o n e 4 setting). This must be taken into account when setting R4.

Fig. 23 DIST: R1 P-P (polygon) Fig. 22 DIST: R2 P-P (polygon) Fig. 22 DIST: R3 P-P (polygon) Fig. 22 DIST: R4 P-P (polygon) Resistance limit setting for impedance zones 1 to 4 in secondary values for the phase-tophase loops.

Note:

Zone 4 can be used as a special zone (see D I S T : Z o n e 4 setting). This must be taken into account when setting R4.

12 13

Fig. 22 DIST: = (polygon) The inclination of the trip polygon in the R direction for the polygonal impedance characteristic is determined using this setting.

12 23 12 24 12 25 12 26 12 27

Fig. 28 DIST: Direction N1 Fig. 28 DIST: Direction N2 Fig. 28 DIST: Direction N3 Fig. 28 DIST: Direction N4 Fig. 28 DIST: Direction N5 The directional setting specifies in what direction the respective impedance stage measures – referred to the basic measuring direction determined by the connection direction of the measuring circuits and setting 10 04. The following settings are possible:

Fig. 23 DIST: X1 (polygon) Fig. 22 DIST: X2 (polygon) Fig. 22 DIST: X3 (polygon) Fig. 22 DIST: X4 (polygon) Reactance limit setting for impedance zones 1 to 4 in secondary values.

Note:

12 05 12 07 12 09 12 11

12 06 12 08 12 10 12 12

o o o

12 28 12 29 12 30 12 31 12 32 12 33

Forward directional Backward directional Non-directional

Fig. 28 DIST: t1 Fig. 28 DIST: t2 Fig. 28 DIST: t3 Fig. 28 DIST: t4 Fig. 28 DIST: t5 Fig. 28 DIST: t6 Settings for the impedance zone stage times and the backup times.

Note:

Zone 4 can be used as a special zone (see D I S T : Z o n e 4 setting). This must be taken into account when setting t4. If the PD 521 is operating with protective signaling or autoreclosing control, timer stage t1 is deactivated. It is replaced by the starting time for protective signaling.

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

7 Settings (continued)

12 34 12 35

Fig. 23 DIST: kze P-G HSR Fig. 23 DIST: kze P-P HSR The zone extension factors kze HSR can be set separately for phase-to-ground and for phase-to-phase loops. When the polygon characteristic has been selected, the zone extension factor setting changes the reactance and resistance limits for impedance zone 1. The following applies to the measurement:

12 36

kG =

R1,ze HSR:

impedance changed by the zone extension factor.

Zone extension is controlled by the following functions:

zero-sequence impedance

k G angle = arc tan

X 0 - X pos R0 - Rpos

- arc tan

Rpos

X0 : zero-sequence impedance reactance X pos : positive-sequ. impedance reactance

If the calculated value cannot be set exactly, then the next smaller value should be set. 12 37

Fig. 2 DIST: kG abs. value Setting the absolute value for the complex ground factor kG.

kG =

Z 0 - Z pos 3 × Z pos

o

Protective signaling

o

Switch on to fault protection

Z0:

An appropriately configured binary signal input.

Z pos : positive-sequence impedance

o

X pos

R0 : zero-sequence impedance resistance Rpos : positive-sequ. impedance resistance

When the circular characteristic has been selected, the The following applies to the measurement:

Z1,ze HSR:

3 × Z pos

Z pos : positive-sequence impedance

reactance changed by the zone extension factor. resistance changed by the zone extension factor.

Z1,ze HSR = (kze HSR) × Z1

Z 0 - Z pos

Z0:

X1,ze HSR = (kze HSR) × X1 R1,ze HSR = (kze HSR) × R1 X1,ze HSR:

Fig. 2 DIST: kG angle Angle setting for the complex ground factor kG.

kG =

zero-sequence impedance

 X 0 - X pos 2 + R0 - Rpos 2 3 × Rpos 2 + X pos 2

R0 : zero-sequ. impedance resistance Rpos : positive-sequ. impedance resistance X 0 : zero-sequ. impedance reactance X pos : positive-sequ. impedance reactance

If the calculated value cannot be set exactly, the next smaller value should be set.

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

115

7 Settings (continued)

12 38

Fig. 25 DIST: Arc. comp. (circle) Enabling / disabling the arc compensation.

Note:

This setting is active for the setting DIST : Characteristic “Circle“ only.

12 40

Fig. 18 DIST: Characteristic Selection of the characteristic for the distance measurement.

12 41

Fig. 26 DIST: = (circle) This setting is of significance with the circular characteristic only when the setting “With arc compensation“ is active. In this case, the setting of = determines the point at which arc compensation becomes active.

12 42 12 43 12 44 12 45

Operating Value Measurement 10 01

Fig. 73 OMEAS: Inom,prim. C.T. Setting for the primary nominal current of the main current transformer. This setting rule only applies if the secondary nominal current of the main current transformer and the nominal current of the protection device are identical. Generally speaking, the setting must be in accordance with the expression Tnom,CT × Inom,relay (where T is the transmission ratio).

10 02

Fig. 73 OMEAS: Vnom,prim. V.T. Setting for the primary nominal voltage of the main voltage transformer. This setting rule only applies if the secondary nominal voltage of the main voltage transformer and the nominal voltage of the protection device are identical. Generally speaking, the setting must be in accordance with the expression Tnom,VT × Vnom,relay (where T is the transmission ratio).

Fig. 27 DIST: Z1 (circle) Fig. 26 DIST: Z2 (circle) Fig. 26 DIST: Z3 (circle) Fig. 26 DIST: Z4 (circle) Impedance limit setting for impedance zones 1 to 4 in secondary values.

Note:

116

7.3.3 Supplementary Functions

Zone 4 can be used as a special zone (see D I S T : Z o n e 4 setting). This must be taken into account when setting Z4.

Pass-Through Functions 17 21

PASS: tEM1 Timer stage setting.

17 30

Fig. 71 PASS: Op. mode tEM1 Selection of timer stage operating mode.

Fig. 71

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

7 Settings (continued)

Ground Fault Direction Determination Using Steady-State Values 16 60

Fig. 54 GFDSS: Enabled Deactivation or activation of steady-state ground fault direction determination. The GFDSS function may be enabled only if the nominal frequency is set to 50 Hz.

16 61

Fig. 56 GFDSS: tVN-G> Setting for the operate delay VN-G>.

16 62

Fig. 56 GFDSS: VN-G> Setting for the neutral-point displacement voltage threshold value.

16 63

Fig. 56 GFDSS: Operating mode Setting for the operating mode of ground fault direction determination using steady-state values. The following settings are possible: ¨ “cos phi circuit” for networks having ground fault compensation, ¨ “sin phi circuit” for networks having an isolated neutral.

16 64

16 65

GFDSS: IN,act>/IN,reac> LS Fig. 59 Setting for the threshold value of the active or reactive component of the ground current, the value that must be exceeded in order for the LS (line side) direction decision to be enabled. Fig. 59 GFDSS: Sector angle LS Sector angle setting for measurement in the direction of the line side.

Note:

This setting is only active if the operating mode “cos phi circuit” has been selected.

16 66

Fig. 59 GFDSS: Operate delay LS Operate delay setting for the direction decision in the forward direction.

16 67

GFDSS: IN,act>/IN,reac> BS Fig. 59 Setting for the threshold value of the active or reactive component of the ground current, the value that must be exceeded in order for the BS (busbar side) direction decision to be enabled.

16 68

Fig. 59 GFDSS: Sector angle BS Sector angle setting for measurement in the direction of the busbar side.

Note:

This setting is only active if the operating mode “cos phi circuit” has been selected.

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

16 69

Fig. 59 GFDSS: Operate delay BS Operate delay setting for the direction decision in the backward direction.

16 70

Fig. 56 GFDSS: Connect. meas.circ. Connection of the measuring circuits determines the directional measurement function of steady-state ground fault direction determination. If the connection is as shown in Chapter 5, then the setting must be Forward (value “1“) if the PD 521’s “forward” decision is to be in the direction of the outgoing feeder. If the connection direction is reversed or – given the connection direction according to Chapter 5 – if the “forward” decision will be in the busbar direction, then the setting must be “2.”

16 71

Fig. 67 GFDSS: Common reset This setting determines whether the measured data of steady-state ground fault direction determination and the LED indicators shall be reset together.

16 72

Fig. 59 GFDSS: Release delay LS Release delay setting for the direction decision in the forward direction.

16 73

Fig. 59 GFDSS: Release delay BS Release delay setting for the direction decision in the backward direction.

16 90

Fig. 54 GFDSS: Select GFD/GF This setting determines whether a steadystate power evaluation or a steady-state current evaluation shall be carried out.

16 91

Fig. 56 GFDSS: f0 (GFD) Frequency setting for the measured variables that will be evaluated by steadystate power evaluation.

16 92

Fig. 61 GFDSS: f0 (GF) Frequency setting for the measured variables that will be evaluated by steadystate current evaluation.

16 93

Fig. 61 GFDSS: IN> Operate value setting for steady-state current evaluation.

16 94

Fig. 61 GFDSS: Operate delay IN Operate delay setting for steady-state current evaluation.

16 95

Fig. 61 GFDSS: Release delay IN Release delay setting for steady-state current evaluation.

117

7 Settings (continued)

Backup Overcurrent-Time Protection (Backup DTOC)

Fault Localization 10 05

Fig. 79 FLOC: Line length This setting defines in km the section that the fault locator considers to be 100 % when calculating the fault distance.

10 11

Fig. 79 FLOC: Start determination This setting determines at what point during a fault the fault data shall be measured.

10 12

Fig. 79 FLOC: Line reactance This setting defines the reactance (X) that the fault locator considers to be 100% when calculating the fault distance.

14 00

Fig. 38 BUOC: Operating mode The operating mode of backup overcurrenttime protection is selected. The following operating modes are possible: Without backup DTOC With backup DTOC

17 00

Fig. 38 BUOC: I> Threshold operate value for phase currents in backup overcurrent-time protection.

17 03

Fig. 38 BUOC: IN> Threshold operate value for ground fault current in backup overcurrent-time protection.

Note:

Overcurrent (I>) Signal 14 04

Fig. 72 I>SIG: Threshold value Threshold setting for the overcurrent signal.

14 08

I>SIG: t Operate delay setting.

Fig. 72

Circuit Breaker Failure Protection 11 67

118

Fig. 53 CBF: tCBF Setting for the operate delay time after which a “circuit breaker failure” signal shall be issued.

A trip command is issued only if MAIN: Neutral-point treat. is set to Low-impedance grounding.

17 04

Fig. 38 BUOC: tI> Operate delay for backup overcurrent-time protection.

17 08

Fig. 38 BUOC: tIN> Operate delay for backup overcurrent-time protection.

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

7 Settings (continued)

Fault Recording 03 78

Fig. 81 FREC: Pre-fault time Setting for the period during which data are recorded before the start of a fault.

03 79

Fig. 81 FREC: Post-fault time Setting for the period during which data are recorded after the end of a fault.

03 95

Fig. 75 FREC: Time-switching Specification of standard time or daylight saving time. This setting is necessary so that the times assigned to signals and fault data, which can be read out from the PC or ILSA interfaces, will not be incorrectly interpreted.

03 96

03 97

03 98

Protective Signaling 15 00

Fig. 50 PSIG: Operating mode The protective signaling operating mode setting. The following settings are possible:

Direct transfer trip underreaching PUTT (Permissive underreaching transfer tripping) Zone extension Signal comparison, releasing scheme Signal comparison, blocking scheme Signal comparison, pilot wire Reverse interlocking 15 02

Fig. 51 PSIG: Reset time send This setting determines the duration of the send signal.

15 03

Fig. 75 FREC: Date Day and month setting for dating faults and monitoring signals.

Fig. 52 PSIG: Echo on receive This setting determines whether protective signaling shall operate with or without an echo.

15 04

Fig. 75 FREC: Year Year setting for dating faults and monitoring signals.

Fig. 40 PSIG: Enabled USER Deactivation or activation of protective signaling.

15 11

Fig. 41 PSIG: Tripping time The tripping time replaces distance protection timer stage t1 when protective signaling is ready.

15 12

Fig. 51 PSIG: DC loop op. mode This setting determines whether the transmitting relay shall be operated in an energize-on-signal or in a normally-energized arrangement (‘open-circuit’ or ‘closed-circuit’ operation).

Fig. 75 FREC: Time of day Time of day setting for time tagging of signals.

Note:

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

This setting is only possible in the operating mode referred to as Signal comparison, pilot wire.

119

7 Settings (continued)

Self-Monitoring 03 15

Fig. 35 MON: Peripheral fault This setting determines whether monitoring signals issued in the event of faults in the measuring circuits are also entered into the monitoring signal memory.

14 01

Fig. 36 MON: Meas.circuit mon. Deactivation or activation of measuring-circuit monitoring.

Note:

If measuring-circuit monitoring is deactivated, backup overcurrenttime protection will operate only if the binary signal input configured MAIN: M.c.b. trip VLS EX T is triggered.

14 02

Fig. 36 MON: Threshold value Ineg The threshold value setting determines the permissible unbalance in the current measuring circuit.

14 03

Fig. 36 MON: Trip by Ineg This setting determines whether a “trip” shall occur in the event of unbalance in the circuit.

14 07

Fig. 37 MON: Meas. volt. circuit One of the following monitoring mechanisms is selected: o Vneg o Vneg with current enable o Voltage monitoring with CB contact enable

Switch on to Fault Protection 11 60

Fig. 39 SOTF: Manual close timer Setting for the timer stage that will be started by a manual close.

11 61

Fig. 39 SOTF: Operating mode The operating mode setting determines whether during elapsing of the timer stage a general start will lead to a trip (“Trip with starting”) or whether the measuring range of impedance zone 1 will be extended by the D I S T : k z e H S R zone extension factor (“Zone extension”).

120

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

8 Information and Control Functions

The PD 521 generates a large number of signals, processes binary input signals and acquires measured data during fault-free operation of the protected object; it also acquires measured fault-related data. For statistical purposes a number of counters is maintained. This information can be read out from the integrated local control panel.

04 55 04 56 04 57

Fig. 74 OMEAS: Load angle phi A Fig. 74 OMEAS: Load angle phi B Fig. 74 OMEAS: Load angle phi C Display of the updated load angle value in phases A, B and C.

05 40 05 41

Fig. 73 OMEAS: Current A prim. Fig. 73 OMEAS: Current A p.u. Display of the updated phase current value in A as a primary quantity or referred to Inom.

05 42 05 43

Fig. 73 OMEAS: Voltage A-G prim. Fig. 73 OMEAS: Voltage A-G p.u. Display of the updated value for the phaseto-ground voltage A-G as a primary value or referred to Vnom.

05 44 05 45

Fig. 73 OMEAS: Current IN prim. Fig. 73 OMEAS: Current IN p.u. Display of the updated ground current value as a primary quantity or referred to Inom. Either the current calculated by the PD 521 or - if ground-fault direction determination using steady-state values is ready – the measured current is displayed.

Fig. 73 OMEAS: Voltage A-B prim. Fig. 73 OMEAS: Voltage A-B p.u. Display of the updated value for the phaseto-phase voltage A-B as a primary value or referred to Vnom.

06 40 06 41

Fig. 73 OMEAS: Current B prim. Fig. 73 OMEAS: Current B p.u. Display of the updated value for the phase current in B as a primary quantity or referred to Inom.

04 45

Fig. 59 OMEAS: Curr. IN,act p.u. Display of the updated value of the active ground current component referred to Inom.

06 42 06 43

04 46

Fig. 59 OMEAS: Curr. IN,reac p.u. Display of the updated value of the reactive ground current component referred to Inom.

Fig. 73 OMEAS: Voltage B-G prim. Fig. 73 OMEAS: Voltage B-G p.u. Display of the updated value for the phaseto-ground voltage B-G as a primary quantity or referred to Vnom.

04 47

OMEAS: Current IN filt. p.u. Display of the updated value for the harmonic content of the ground current, referred to Inom. This is only displayed if steady-state current evaluation is enabled.

06 44 06 45

Fig. 73 OMEAS: Voltage B-C prim. Fig. 73 OMEAS: Voltage B-C p.u. Display of the updated value for the phaseto-phase voltage B-C as a primary quantity or referred to Vnom.

07 40 07 41

Fig. 73 OMEAS: Current C prim. Fig. 73 OMEAS: Current C p.u. Display of the updated phase current value in C as a primary quantity or referred to Inom.

07 42 07 43

Fig. 73 OMEAS: Voltage C-G prim. Fig. 73 OMEAS: Voltage C-G p.u. Display of the updated value for the phaseto-ground voltage C-G as a primary quantity or referred to Vnom.

07 44 07 45

Fig. 73 OMEAS: Voltage C-A prim. Fig. 73 OMEAS: Voltage C-A p.u. Display of the updated value for the phaseto-phase voltage C-A as a primary quantity or referred to Vnom.

8.1 Measured Values 04 40

OMEAS: Frequency f Display of system frequency.

04 41 04 42

Fig. 73 OMEAS: Volt. VN-G prim. Fig. 73 OMEAS: Volt. VN-G p.u. Display of the updated value for the neutralpoint displacement voltage as a primary quantity or referred to Vnom.

04 43 04 44

04 50 04 51

04 52 04 53

04 54

Fig. 73

Fig. 73

Fig. 74 OMEAS: Act. power P prim. Fig. 74 OMEAS: Act. power P p.u. Display of the updated value of active power as a primary quantity or referred to Snom. Fig. 74 OMEAS: Reac. power Q prim. Fig. 74 OMEAS: Reac. power Q p.u. Display of the updated value of reactive power as a primary quantity or referred to Snom. Fig. 74 OMEAS: Power factor Display of the updated power factor value.

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

121

8 Information and Control Functions (continued)

04 21

Fig. 78 FMEAS: Operating time Display of the operating time of the last fault.

04 28

Fig. 79 FMEAS: Fault reactance Display of the fault reactance of the last fault in 9 as secondary quantity. This value is only displayed if the fault has been detected by the PD 521’s distance protection function.

04 29

Fig. 79 FMEAS: Fault react. prim. Display of the fault reactance of the last fault in 9 as primary quantity. This value is only displayed if the fault has been detected by the PD 521‘s distance protection function.

The operating time is defined as the time between starting and ending of PD 521 general starting. 04 22

Fig. 79 FLOC: Fault location The fault location of the last fault is displayed in km.

This value is only displayed if the fault has been detected by the PD 521’s distance protection function. 04 23

Fig. 79 FMEAS: Fault impedance The fault impedance of the last fault is displayed in 9. This value is only displayed if the fault has been detected by the PD 521’s distance protection function.

04 37

Fig. 80 FMEAS: Load impedance Display of load impedance in 9 when distance protection starting ends. This value is only displayed if the fault has been detected by the PD 521’s distance protection function.

04 24

Fig. 79 FMEAS: Fault loop angle The fault angle of the last fault is displayed in degrees. This value is only displayed if the fault has been detected by the PD 521’s distance protection function. If fault voltages are lower than 2 V, the set angle = is displayed.

04 38

Fig. 80 FMEAS: Load angle Display of the load angle in degrees when distance protection starting ends. This value is only displayed if the fault has been detected by the PD 521‘s distance protection function.

04 39

04 25

Fig. 79 FMEAS: Fault current p.u. The fault current of the last fault is displayed referred to Inom.. If the fault was detected by the PD 521’s distance protection function, a phase current is displayed depending on the measuring loop selected. If the fault was detected by the backup overcurrent-time protection function, then the maximum phase current is displayed.

Fig. 80 FMEAS: Residual current Display of the ground current of the last fault referred to Inom. This value is only displayed if the fault has been detected by the PD 521‘s distance protection function.

04 48

Fig. 79 FMEAS: GF angle Display of the ground fault angle of the last fault in degrees. This value is only displayed if the PD 521’s distance protection function selects a phaseto-ground loop for measurement.

04 49

Fig. 79 FMEAS: Fault IN p.u. Display of the ground fault current of the last fault referred to Inom. This value is only displayed if the PD 521’s distance protection function selects a phaseto-ground loop for measurement.

09 20

Fig. 66 GFDSS: Voltage VN-G p.u. Display of the neutral-point displacement voltage of the last ground fault referred to Vnom. This value is only displayed if the steady-state power evaluation function of ground-fault direction determination is activated.

04 26

04 27

122

Fig. 79 FMEAS: Fault voltage p.u. The fault voltage of the last fault is displayed referred to Vnom. This value is only displayed if the fault has been detected by the PD 521’s distance protection function. Fig. 79 FLOC: Fault location % The fault location of the last fault is displayed referred to the “F L O C : L i n e r e a c t a n c e ” setting. This value is only displayed if the fault has been detected by the PD 521’s distance protection function.

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

8 Information and Control Functions (continued)

09 21

09 22

Fig. 66 GMEAS: Current IN p.u. Display of the ground current of the last ground fault referred to Inom. This value is only displayed if the steady-state power evaluation function of ground fault direction determination is activated. Fig. 66 GMEAS: Curr. IN,act p.u. Display of the active component of the ground current of the last ground fault referred to Inom. This value is only displayed if the steady-state power evaluation function of ground fault direction determination is activated.

09 23

Fig. 66 GMEAS: Curr. IN,reac p.u. Display of the reactive component of the ground current of the last ground fault referred to Inom. This value is only displayed if the steady-state power evaluation function of ground-fault direction determination is activated.

09 24

Fig. 64 GMEAS: GF durat.steady-st Display of the ground fault duration of the last ground fault when steady-state power evaluation is being carried out by the ground fault direction determination function.

09 25

Fig. 66 GMEAS: IN filtered p.u. Display of the ground current component of the last ground fault with the set filter frequency, referred to Inom.

09 26

Fig. 65 GMEAS: GF durat. curr.meas Display of the ground fault duration of the last ground fault when steady-state current evaluation is being carried out.

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

8.2 State Signals After the respective address is selected, the value display shows a value of "0" for "signal not transmitted" or "1" for "signal transmitted." The conditions that must be satisfied for a signal to be transmitted are shown in the figures in Chapter 3. 03 26 03 27 03 28 04 60 04 61 04 62 04 63 04 64 04 65 09 35 09 36 09 37 09 38 15 08 21 13 35 00 35 01 35 02 36 00 36 01 36 02 36 03 36 04 36 05 36 09 36 13 36 14 36 15 36 16 36 17 36 18 36 19 36 20 36 21 36 26 36 27 36 28 36 29 36 30 36 31 36 34 36 35 36 38 36 45 36 46 36 47 36 48

MAIN: Deactivate prot.EXT MAIN: Activate prot. EXT MAIN: Prot. ext. activated MAIN: Protect. not ready MAIN: M.c.b. trip VLS EXT I>SIG: Overcurrent MAIN: Ground fault PSIG: Telecom. faulty EXT MAIN: Blocked/faulty GFDSS: Direct. forw. /LS GFDSS: Direct. backw. /BS GFDSS: tVN-G> elapsed GFDSS: GF curr. meas. PSIG: Enabled MAIN: Trip cmd. blocked FREC: Fault occurrence FREC: Signal mem.overflow FREC: Faulty time tag START: General starting START: Starting A START: Starting B START: Starting C START: Starting GF MAIN: General trip signal DIST: Trip signal BUOC: Starting BUOC: Trip signal START: VN-G>> triggered START: tVN-G>> elapsed CBF: CB failure DIST: Fault forward/LS DIST: Fault backward/BS PSIG: t1 revers.interlock START: Zero sequ. start DIST: t1 elapsed DIST: t2 elapsed DIST: t3 elapsed DIST: t4 elapsed DIST: t5 elapsed DIST: t6 elapsed CBF: Input EXT PSIG: Send (signal) PSIG: Test telecom. EXT MAIN: Trip cmd. block EXT DIST: Zone extension EXT SOTF: Manual close EXT PSIG: Receive EXT

Fig.: 3 Fig.: 3 Fig.: 3 Fig.: 84 Fig.: 35 Fig.: 72 Fig.: 6 Fig.: 42 Fig.: 84 Fig.: 59 Fig.: 59 Fig.: 56 Fig.: 61 Fig.: 40 Fig.: 69 Fig.: 75 Fig.: 77 Fig.: 68 Fig.: 68 Fig.: 68 Fig.: 68 Fig.: 68 Fig.: 69 Fig.: 69 Fig.: 38 Fig.: 38 Fig.: 7 Fig.: 7 Fig.: 53 Fig.: 17 Fig.: 17 Fig.: 50 Fig.: 68 Fig.: 28 Fig.: 28 Fig.: 28 Fig.: 28 Fig.: 28 Fig.: 28 Fig.: 53 Fig.: 51 Fig.: 52 Fig.: 69 Fig.: 23 Fig.: 39 Fig.: 50

123

8 Information and Control Functions (continued)

36 49 36 51 36 60 36 63 36 64 36 65 36 66 36 69 36 70 36 71 36 88 36 89 37 18 37 20 37 21 37 24 37 27 37 28 37 29 37 30 37 31 37 34 37 35 37 70 37 71 37 72 37 73 37 74 37 75 37 76 38 06 38 07 38 16 38 20 38 23 38 24 38 26 38 27 38 28 38 29 38 37 38 46 38 48 40 16 40 17 40 20

124

PSIG: Blocking EXT MAIN: CB closed sig. EXT PSIG: Telecom. faulty SOTF: tManual-close runn. SOTF: Trip aft. man.close DIST: Zone extension CBF: tCBF running MON: Trip by Ineg MON: Warning MAIN: General trip cmd. FLOC: Trigger EXT FREC: Trigger EXT MAIN: Man. trip cmd. EXT MON: Measuring circ.mon. BUOC: Backup DTOC mode PSIG: Send (transm. relay) PSIG: Ready PSIG: Not ready PSIG: Receive & gen.start PASS: Output 1 (updating) PASS: Output 2 (updating) PASS: Output 1 (latching) PASS: Output 2 (latching) PC/ILSA: Test mode EXT PC/ILSA: Test mode ILSA: Command enable EXT ILSA: Command enable ILSA: Sig./meas.block EXT ILSA: Sig./meas.block FREC: Trigger MAIN: Auxiliary address PSIG: Trip signal MAIN: Starting trig. EXT GFDSS: GF evaluation EXT MON: Volt. meas. circuits MON: Peripheral fault GFDSS: GFD ready GFDSS: GFD not ready GFDSS: GF ready GFDSS: GF not ready DIST: Fault in cable run MAIN: Prot. ext. disabled MON: Meas. volt. ok PASS: Input 1 EXT PASS: Input 2 EXT PASS: Output 1 (t)

Fig.: 40 Fig.: 37 Fig.: 42 Fig.: 39 Fig.: 39 Fig.: 23 Fig.: 53 Fig.: 36 Fig.: 82 Fig.: 69 Fig.: 79 Fig.: 81 Fig.: 69 Fig.: 35 Fig.: 38 Fig.: 51 Fig.: 40 Fig.: 40 Fig.: 49 Fig.: 71 Fig.: 71 Fig.: 71 Fig.: 71 Fig.: 85 Fig.: 85 Fig.: 87 Fig.: 87 Fig.: 87 Fig.: 87 Fig.: 81 Fig.: 3 Fig.: 50 Fig.: 69 Fig.: 54 Fig.: 37 Fig.: 35 Fig.: 54 Fig.: 54 Fig.: 54 Fig.: 54 Fig.: 32 Fig.: 3 Fig.: 37 Fig.: 71 Fig.: 71 Fig.: 71

54 00 54 03

INP: State U 1 INP: State U 2 The state of the binary inputs is displayed as follows: ¨

Value of "0": not energized

¨

Value of "1": energized

This display appears regardless of the mode setting for the binary signal inputs. 51 00 51 02 51 04 51 06 51 08 51 10 51 12 51 14

57 00 57 02 57 04 57 06 57 08 57 10 57 12 57 14 57 16 57 18 57 20 57 22

OUTP: State K 1 OUTP: State K 2 OUTP: State K 3 OUTP: State K 4 OUTP: State K 5 OUTP: State K 6 OUTP: State K 7 OUTP: State K 8 The state of the output relays is displayed as follows: ¨

Value of "0": output relay not activated

¨

Value of "1": output relay activated

LED: State H 1 LED: State H 2 LED: State H 3 LED: State H 4 LED: State H 5 LED: State H 6 LED: State H 7 LED: State H 8 LED: State H 9 LED: State H 10 LED: State H 11 LED: State H 12 The state of the LED indicators is displayed as follows: ¨

Value of "0": LED indicator not activated

¨

Value of "1": LED indicator activated

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

8 Information and Control Functions (continued)

8.3 Counters 04 00

09 01

MAIN: No. general starts Number of general startings.

Fig. 68

The counter is reset through the following addresses:

The counter is reset through address 03 02. 04 05

MAIN: No. def. trip cmds Number of final trip commands.

Fig. 70

The counter is reset through address 03 02. 04 10

09 02

Fig. 75 FREC: No. system disturb. Number of system disturbances since the last signal memory reset.

04 19

MAIN: General reset

03 06

MAIN: Res et s ig. m em ory

Fig. 83 MON: No. of mon.signals Number of entries into the monitoring signal memory.

The counter is reset through address 03 08. 04 20

Fig. 75 FREC: No. of faults Number of faults since the signal memory was last reset.

03 02

MAIN: General reset

03 04

GFDSS: Reset counter

Fig. 60 GFDSS: No. GF steady-st. Number of ground faults detected by steadystate power evaluation.

The counter is reset through the following addresses:

The counter is reset through the following addresses: 03 02

Fig. 60 GFDSS: No. GF backwd./BS Number of ground faults in the backward direction.

09 03

03 02

MAIN: General reset

03 04

GFDSS: Reset counter

Fig. 62 GFDSS: No. of GFs. (curr.) Number of ground faults detected by steadystate current evaluation.

The counter is reset through the following addresses: 03 02

MAIN: General reset

03 04

GFDSS: Reset counter

The counter is reset through the following addresses:

09 00

03 02

MAIN: General reset

03 06

MAIN: Reset sig. memory

Fig. 60 GFDSS: No. GF forwd./LS Number of ground faults in the forward direction.

The counter is reset through the following addresses: 03 02

MAIN: General reset

03 04

GFDSS: Reset counter

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

125

8 Information and Control Functions (continued)

8.4 Control and Testing 00 85

03 06

MAIN: Cold restart A cold restart is executed. The setting is password-protected (see Section 6.7 “Password-Protected Control Operations”). A cold restart means that all settings are erased. The values that the protection device operates with after a cold restart are given in the address list in the “Default” column. They are selected so that the protection device is blocked after a cold restart. A cold restart only needs to be carried out if modules that are activated through address 00 80 (IDENT: Add. HW modules) are to be deactivated.

03 02

MAIN: General reset The following memories are reset: ¨

All counters

¨

LED indicators

¨

Signal memory

¨

Fault counter

¨

Measured fault data

¨

Measured ground fault data

¨

Fault records

03 03

Fig. 67 GFDSS: Reset meas. values All measured ground fault data are reset.

03 04

Fig. 63 GFDSS/TGFD: Reset counter The counter for ground faults detected by steady-state power evaluation is reset.

¨

LED indicators

¨

Signal memory

¨

Fault counter

¨

Measured fault data

¨

Fault records

MON: Reset mon. sig. mem. The following memories are reset: ¨

Monitoring signal memory

¨

Monitoring signal counter

Fig. 76

Fig. 83

03 10

LOC: Param. change enabl. This enabling function allows values to be changed from the local control panel.

03 39

MAIN: Warm restart In a warm restart the protection device functions as it does when the power supply voltage is turned on.

03 40

Fig. 69 MAIN: Man. trip cmd. USER A trip command is issued from the local control panel for a period of 100 ms. The setting is password-protected (see Section 6.7, "Password-Protected Control Operations").

03 41

Fig. 81 FREC: Triggering USER Fault recording is enabled from the local control panel for 500 ms.

03 42

OUTP: Relay assign.f.test The relay that is to be tested is selected.

03 43

OUTP: Relay test The relay selected for testing is triggered for the set time period (O U T P : H o l d - t i m e f o r t e s t , address 03 44). The operation is password-protected (see Section 6.7 "Password-Protected Control Operations"). Additionally, the test needs to be enabled by activating the test mode (address 03 12 set to “1“).

03 44

OUTP: Hold-time for test Setting for the triggering time for the selected output time during a function test.

Fig. 76

The operation is password-protected (see Sec. 6.7 "Password-Protected Control Operations").

126

03 08

FREC: Reset sig. memory The following memories are reset:

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

8 Information and Control Functions (continued)

15 09

Fig. 52 PSIG: Test telecom. USER A send signal is transmitted for 500 ms. This possibility does not exist if “P S I G : O p e r a t i n g m o d e ” is set for "Direct transfer trip underreaching."

21 10

Fig. 76 MAIN: Reset indicat. USER The following memories and storage devices are reset: ¨

LED indicators

¨

Measured data for steady-state ground fault direction determination, if “G F D S S : C o m m o n r e s e t ” has been set accordingly

¨

Measured fault data.

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

127

9 Commissioning

Preparation After the PD 521 has been installed and connected in accordance with Chapter 5, the commissioning procedure can begin. Before turning on the power supply voltage, the following items must be checked again:

If the protection device is to be set and fault records read out through the PC or ILSA interface, then the following settings must first be made from the integrated local control panel. (These settings are only possible from the local control panel.) ¨

PC: Baud rate

(address 03 81)

¨

PC: Command enabling

(address 03 80)

¨

PC: Sig./meas.val.block

(address 03 86)

¨

ILSA: Baud rate

(address 03 71)

¨

I L S A : C o m m a n d e n a b l e U S E R (address 03 70)

¨

I L S A : S i g . / m e a s . b l c k . U S E R (address 03 76)

¨

IDENT: Device password 1

(address 00 48)

¨

IDENT: Device password 2

(address 00 49)

After the wiring work is completed, check the system to make sure it is properly isolated. The conditions given in VDE 0100 must be satisfied.

¨

PC/ILSA: Device addr. (CU)

(address 03 68)

¨

PC/ILSA: Device addr. (PU)

(address 03 69)

Once all checks have been made, the power supply voltage may be turned on. After voltage has been applied, the protection device starts up. During startup various startup tests are carried out (see Section 3.18, "SelfMonitoring"). The LED indicators for "Operation" (H2) and "Blocked/Faulty" (H3) light up. After approximately 11 s the PD 521 is ready for operation. This is indicated when the display changes from address 99 00 to the preset address (factory-set default: 03 10).

¨

FREC: Time-switching

(address 03 95)

¨

FREC: Time of day

(address 03 96)

¨

FREC: Date

(address 03 97)

¨

FREC: Year

(address 03 98)

¨

¨

¨

¨

Is the protection device connected to the protective ground at the specified location? Does the nominal value of the auxiliary device voltage VA,nom agree with the nominal value of the auxiliary system voltage? Does the nominal value of the device control voltage Vin,nom agree with the nominal value of the system control voltage? Are the current and voltage transformer connections, grounding and phase sequence correct?

Further instructions regarding these settings are given in Chapters 7 and 8.

In as-received condition the keyboard is not locked. Therefore all settings can be made after the change enabling command (address 03 10) has been issued. The procedure for entering settings from the integrated local control panel is described in Chapter 6.

128

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

9 Commissioning (continued)

After the settings have been made, the following checks should be carried out once again: ¨

Does the function assignment of the binary signal inputs agree with the terminal connection diagram?

¨

Has the correct operating mode been selected for the binary signal inputs?

¨

Does the function assignment of the output relays agree with the terminal connection plan?

¨

Have all settings been made correctly?

Now the blocks at the following addresses can be cleared: ¨

Address 03 30: M A I N : P r o t e c t i o n a c t i v e "on".

¨

Address 21 12: MAIN: T r i p c m d . b l o c k U S E R .

Testing By using the signals and displays generated by the PD 521 it is possible to determine whether the PD 521 is correctly set and properly interconnected with the station. Signals are signaled by output relays and LED indicators and entered into the signal memory. In addition, the signals can be checked by selecting the appropriate signal addresses.

Checking the Binary Signal Inputs When the binary signal inputs are configured for the appropriate signals, then it is possible to determine from the signals (see Section 8.2) whether the protection device recognizes the binary signals correctly. ¨

Address 54 00: display of the current state of binary signal input U1

¨

Address 54 03: display of the current state of binary signal input U2

The displayed values have the following meanings: ¨

Value of "0": Not energized.

¨

Value of "1": Energized.

This display appears regardless of the binary signal input mode selected. Checking the Output Relays It is possible to trigger the output relays for a settable time period for test purposes (time setting at address 03 44). First set value „1“ at address 03 12 ( PC/ILSA: T es t m ode USER), then select the output relay to be tested (address 03 42). Test triggering then occurs through address 03 43. It is password-protected (see Chapter 6, Section "Password-Protected Control Operations").

If the circuit breaker will not be operated during testing, the trip command can be blocked through address 21 12 or an appropriately configured binary signal input. If a test of the circuit breaker is desired, it is possible to issue a trip command for 100 ms through address 03 40 or an appropriately configured binary signal input. Selection of the trip command from the integrated local control panel is password-protected (see Section 6.7, "PasswordProtected Control Operations"). If the PD 521 is connected to a control station it is advisable to activate the test mode via address 03 12 or an appropriately configured binary signal input. The messages are then identified accordingly (reason for transmission: test mode).

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

129

9 Commissioning (continued)

Checking the Protective Function Checking Distance Protection When checking distance protection with a single-phase test device, the measuring circuit monitoring function should be deactivated (address 14 01) since it would otherwise always operate and thus block distance protection after approximately 10 s. If the signal M A I N : M . c . b . t r i p V L S E X T is assigned to a binary signal input then the latter must have a logic value of "0." Checking the Fault Detection Logic The fault detection settings can be illustrated in a V-I diagram (see Figure 104). The slope of the impedance line plotted in the V-I diagram is a function of the settings for underimpedance fault detection logic and the phase displacement between the measured variables (see Figure 104).

104 Characteristic of underimpedance fault detection logic

When checking underimpedance fault detection logic using single-phase test current we obtain the following relation for the operate condition for a phase-to-phase loop:

V test = 2 × Z< I test V test × e jjtest I test × e j0 °

= 2 × Z < × e j jZ

For absolute value (modulus) and angle this means:

V test 103 Example of the fault detection settings in a V-I diagram

I test

= 2 × Z< 0

jtest = j Z Checking I> (IN), V< and I>>: The phase displacement between the measured variables V and I should be selected so as to be smaller than the set angle “START: b . ” Checking Z triggers operate if the test voltage exceeds the following value:

For absolute value and angle this means:

V test I test

V test = 3 × VN-G > ×

Vnom

or setting

For a single-phase test where I B = I C = 0 , the following applies to currents: I test = IN > ×Inom IN>:

= 2 × Z<

j test = j Z

3

VN-G>: S T A R T : V N - G > START: VN-G>>

= 2 × Z < × e jj Z

“S T A R T : I N > “ s e t t i n g

Operation of ground starting is only signaled by the LED indicator if starting in a phase also operates. The operation of ground starting independent of operation of phase starting can be observed at address 36 21.

where

Z: M O N : T h r e s h o l d v a l u e I n e g

setting

With a single-phase test current we obtain I neg =

1 ×I 3 test

I P,max = I test For the operate conditions that means: 1 ×I ³ (Ineg > ) × I test 3 test

0.333 ³ (Ineg >) Therefore operation of current measuring circuit monitoring with single-phase test current is only possible if the threshold operate value is set smaller than 0.333.

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

9 Commissioning (continued)

For two-phase test current in phase opposition we obtain:

I neg =

1 1 × I test + a 2 × ( - I test ) = × I test 3 3

IP,max = Itest For the operate condition this means: 1 3

× I test ³ (Ineg >) × I test

0.577 ³ (Ineg> ) Therefore operation of current measuring circuit monitoring with a two-phase test current in phase opposition is only possible if the threshold operate value is set smaller than 0.577. If the threshold operate value satisfies the respective condition, then current measuring circuit monitoring operates with a test current greater than 0.125 Inom after the operate delay of 10.1 s has elapsed. Negative-sequence monitoring of the voltage measuring circuits is enabled if at least one phase-to-ground voltage exceeds the value 0.7 × Vnom / 3 . Other enabling criteria that can be activated on an optional basis are the following (selection of enabling criteria at address 14 07): ¨

A phase current must exceed 0.05 × Inom.

¨

The signal at the binary signal input configured for A R C : C B c l o s e d s i g . E X T must have a logic value of "1."

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

If negative-sequence monitoring has been enabled, the PD 521 determines the absolute value of negativesequence voltage according to the following formula:

V neg =



1 × V A - G + a2 × V B - G + a × V C - G 3



0

a = e j 120 0 a 2 = e j 240 The trigger threshold of Vneg is set permanently at 0.2 × Vnom / 3 . In the case of a single-phase test using

V B - G = V C - G = 0 , the result of that and of the previously cited calculation formula for Vneg is that the trigger operates when the test voltage exceeds the following value:

V test ³ 3 × 0.2 ×

Vnom 3

A signal is not issued until the operate delay totaling 9.8 s has elapsed.

137

9 Commissioning (continued)

Checking Backup Overcurrent Time Protection

Checking Protective Signaling

The switch to backup overcurrent time protection (BUOC) — if it has been appropriately set — is brought about by measuring circuit monitoring or the tripping of the voltage transformer miniature circuit breaker on the line side.

The protective signaling function can only be checked if protective signaling is ready. This is displayed at address 37 27 (P S I G : R e a d y ).

If the current exceeds the set threshold operate value BUOC: I > , then starting occurs in the corresponding phase(s). After the set time delay B U O C : t I > has elapsed, the PD 521 trips. If M A I N : N e u t r a l p o i n t t r e a t ( m e n t ) is set to "Low-impedance-grounding“, then an SN start occurs if the residual current IN calculated by the PD 521 exceeds the set threshold B U O C : I N > . After the set time delay B U O C : t I N > has elapsed, the PD 521 trips. The PD 521 calculates the residual current IN according to the following formula:

I N = I A + I B + IC From this we obtain in the case of a single-phase test (for example, IB = IC = 0) a test current of

I test = IN > ×Inom at which the operate threshold BUOC: I N > is reached. If the PD 521 is operating with protective signaling or ARC, tripping of the backup overcurrent time protection proceeds after the corresponding tripping times have elapsed.

If protective signaling is not ready, this may be caused by the following reasons: ¨

Protective signaling is not activated. This can be checked at address 15 04 P S I G : E n a b l e d U S E R . (The address is set to "0".)

¨

Protective signaling has been blocked by triggering a correspondingly configured binary signal input (P S I G : B l o c k i n g E X T , address 36 49).

¨

A fault has been detected in the communications channel. (This can be checked at address 36 60.)

If the conditions for testing are satisfied, it is possible to generate a send signal for test purposes from the integrated local control panel (address 15 09) or by triggering a correspondingly configured binary signal input (P S I G : T e s t t e l e c o m . E X T ). This pulse will be present for 500 ms and is extended for the set reset time. If the “with echo" setting has been selected in the protection device at the remote station, then the received signal is returned. The "with echo" setting is only active in the following protective signaling operating modes: ¨

PUTT (permissive underreaching transfer tripping)

¨

Zone extension

¨

Signal comparison release scheme

¨

Signal comparison blocking scheme

The possibility for testing does not exist if P S I G : O p e r a t i n g m o d e has been set for Direct transfer trip underreaching.

138

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

9 Commissioning (continued)

Checking Steady-State Ground Fault Direction Determination

If both the ground current and the neutral-point displacement voltage formed from the three phase-toground voltages are available as measured variables, the PD 521 determines the ground fault direction through evaluation of the ground fault using steady-state values. Switching between steady-state power evaluation and steady-state current evaluation is done from the integrated local control panel or by triggering an appropriately configured binary signal input.

Auxiliary Circuit in Resonant-Grounded Systems First the fuse in phase A of the voltage transformer is removed and the associated secondary side is shortcircuited (see Figures 107 and 108). As a result a displacement voltage VN-G is obtained whose magnitude is smaller by a factor of 3 than that of the displacement voltage in the case of a dead fault to ground. If the current is measured in a Holmgreen group then the current transformer in A on the secondary side must be disconnected and short-circuited (see Figure 107).

If allowed by system operation, a ground fault can be closed on the busbar side (BS) or the line side (LS). The PD 521 must then transmit the corresponding signals. However, a requirement is that the set thresholds for ground current (G F D S S : I N , a c t > / I N , r e a c > B S or L S ) and for the neutral-point displacement voltage (G F D S S : V N - G > ) are exceeded. Because of the danger of a double ground fault, a function test involving the closing of a ground fault will not be possible in most cases. In these cases the current and voltage transformers in the system can be connected so that a function test is possible without a ground fault. The ground current measured by the PD 521 and the neutral-point displacement voltage are displayed as operating data in primary quantities and referred to the nominal quantities of the protection device (see Appendix C, "Measured Operating Data").

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

139

9 Commissioning (continued)

107 Auxiliary circuit in resonant-grounded systems with Holmgreen group, ground fault in BS direction

140

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

9 Commissioning (continued)

A pilot wire is threaded into window-type current transformers, and through it a current is taken from phase B (see Figure 108). The vectorial assignment of currents and voltages is shown in the phasor diagrams included with the terminal connection diagrams.

In the example shown below a ground fault is simulated on the line side. In order to check a ground fault on the busbar side, the pilot wire must be threaded in the opposite direction.

108 Auxiliary circuit in resonant-grounded systems with window-type current transformer, ground fault in BS direction

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

141

9 Commissioning (continued)

Auxiliary Circuit in Systems with Isolated Neutral First the fuse in phase A on the primary side of the voltage transformer is removed and the corresponding secondary side is short-circuited (see Figures 109 and 110). The result is a displacement voltage VN-G whose magnitude is

smaller by a factor of 3 than that of the displacement voltage in the case of a dead fault to ground. If the current is measured in a Holmgreen group, then the current transformers in A and B on the secondary side must be disconnected and short-circuited (see Figure 109).

109 Auxiliary circuit in systems with isolated neutral and Holmgreen group, ground fault in LS direction

142

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

9 Commissioning (continued)

A pilot wire is threaded into window-type current transformers, and through it a current is taken from phases B and C (see Figure 110). The vectorial assignment of currents and voltages is shown in the phasor diagrams included with the terminal connection diagrams.

In the example shown below a ground fault is simulated on the line side. In order to check a ground fault on the busbar side, the pilot wire must be threaded in the opposite direction.

110 Auxiliary circuit in systems with isolated neutral and window-type current transformer, ground fault in LS direction

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

143

9 Commissioning (continued)

Completion of Commissioning

Before the protection device is released for operation, make sure that ¨

All memories are reset (resetting at addresses 03 02 (password-protected) and 03 08)

¨

The desired reset address is set (setting at address 03 13)

¨

The block of the trip command is canceled (address 21 12, value of "0")

¨

Protection is activated (on) (address 03 30, value of "1")

¨

The password is active (only necessary if the keyboard is to be locked) (address 03 11, value of "1").

As the last step the keyboard may be locked, as described in Chapter 6. When you leave the device, only the green LED indicator signaling "Operation" (H2) should be lit up.

144

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

10 Troubleshooting

Listed below are several conceivable problems, their causes, and possible methods for eliminating them. This section is intended as a general orientation only, and in cases of doubt it is better to return the PD 521 to the manufacturer. In such cases the packaging instructions in the “Unpacking and Packing” section of Chapter 5 must be followed.

90 00

MON: EPROM Checksum errors in the EPROM area. Response: warm restart or blocking Output relay: latching

90 01

MON: RAM Write or read error in the RAM area. Response: warm restart or blocking Output relay: latching

90 02

MON: Exception Processor malfunction. Response: warm restart or blocking Output relay: latching

90 03

MON: Parameters Checksum error in settings area. Response: cold restart Output relay: latching

90 08

MON: PC interface The PC interface is defective and blocked. Protection continues to operate. Response: PC interface blocking Output relay: updating

90 09

MON: ILSA interface The ILSA interface is defective and is blocked. Protection continues to operate. Response: ILSA interface blocking Output relay: updating

90 10

MON: Battery Common-RAM The voltage of the built-in battery is too low. Replace the battery. For additional instructions see Chapter 11. Response: none Output relay: updating

90 12

MON: Monitor sig. memory The number of monitoring signals that can be stored has been exceeded. Response: No additional monitoring signals are stored. Output relay: latching

90 13

MON: Signal memory Checksum error(s) in fault signal area. Response: warm restart or clearing of signals for defective fault Output relay: latching

90 14

MON: Monitor sig. memory Checksum error in the area of the monitoring signal memory. Response: warm restart or clearing of monitoring signals Output relay: latching

Malfunctioning after Connection to the System: ¨

The 7-segment displays do not light up. n Check to see whether there is supply voltage at the equipment connection points. n Check to see whether the magnitude of the auxiliary voltage is correct. The PD 521 is protected against damage resulting from polarity reversal.

!

Turn off the power supply voltage before carrying out further checks. Components behind the front panel are energized.

n Check to see whether the ribbon cable between input-output module and processor board is plugged in. (To do so, remove the front panel.)

!

Where possible, disconnection of the ribbon cable between the processor module and the I/O module should be avoided. Should disconnection have occurred, however, then the device needs to be re-initialized by way of a cold restart.

n Check to see whether fuse F1 (type M1C) on the lower printed circuit board (I/O module) is OK. If the fuse is defective it should not be replaced without first determining the cause of failure. If a fuse is replaced without eliminating the problem, there is danger that the damage will spread. ¨

The protection device signals “Warning” (LED H1). Identify the specific problem by reading out the monitoring signal memory (see 6.5.2 “Monitoring Signal Memory Readout”). The following table lists the possible monitoring signal entries, the faulty area, the PD 521 response and the mode of the output relay configured for the warning.

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

145

10 Troubleshooting (continued)

90 16

MON: PC interface The PC interface is defective. Response: none Output relay: latching

90 35

MON: Spontan. sig.buffer Memory overflow. Response: none Output relay: latching

90 17

MON: PC interface Fault in the PC communications area. Response: no PC communication possible Output relay: latching

90 36

90 18

MON: PC interface Fault in the PC communications area. Response: no PC communication possible Output relay: latching

MON: ILSA/PC telegram Telegram error (message transmission error) Response: none Output relay: latching

90 37

MON: ILSA interface Telegram error (message transmission error) Response: none Output relay: latching

90 42

MON: Common-RAM Unknown fault. Response: none Output relay: latching

90 43

MON: PC/ILSA interface Fault in area of PC/ILSA communication. Response: none Output relay: latching

90 70

MON: Checksum Checksum error in the RAM area. Response: warm restart or blocking Output relay: latching

94 02

MON: Clock Hardware clock fault. Response: warm restart or blocking Output relay: latching

98 00

MON: Voltage meas. VLS The voltage transformer m.c.b. on the line side has tripped. Response: blocking of distance protection Output relay: updating

98 01

MON: Volt.meas.circuits Negative-sequence monitoring has operated. Response: blocking of distance protection Output relay: updating

98 02

MON: Backup DTOC Distance protection has been blocked, but there has been no switch to backup overcurrent-time protection (BUOC or Backup DTOC). Response: none Output relay: updating

90 21

90 25

90 27

90 28

90 31

90 32

MON: Operat. watchdog Processor malfunction. Response: warm restart or blocking Output relay: latching MON: NMI Processor malfunction. Response: warm restart or blocking Output relay: latching MON: Clock Processor timer defective. Response: warm restart or blocking Output relay: latching MON: Cold restart A cold restart was carried out. Response: none Output relay: latching MON: ILSA interface Fault in the ILSA communication area. Response: none Output relay: latching MON: ILSA interface General scan fault. Response: none Output relay: latching

90 33

MON: ILSA interface Background general scan fault. Response: none Output relay: latching

90 34

MON: Spontan. sig.buffer Fault in spontaneous signal buffer area. Response: none Output relay: latching

146

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

10 Troubleshooting (continued)

98 03

98 05

98 06

MON: Backup DTOC The device has switched to backup overcurrent-time protection. Response: none Output relay: updating MON: Curr. meas. circuits Negative-sequence monitoring has operated. Response: none Output relay: updating MON: Protect.sig.transm. The protective signaling transmission channel is faulty. Response: blocking of protective signaling Output relay: updating

98 07

MON: Measuring circuits Ground starting has operated. Response: none Output relay: updating

98 09

MON: Low voltage A phase-to-phase voltage has fallen below the 0.4 × Vnom threshold. Response: none Output relay: updating

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

¨

The PD 521 signals "Block/faulty" (LED H3). n

Check to see whether a “Warning” signal is present. If so, the warning must be identified more closely, as described above.

n

Check to see whether the PD 521 is deactivated (off). (This can be checked at address 03 30.)

n

Check to see whether the trip command is being blocked from the local control panel (this can be checked at address 21 12).

n

Check to see whether the trip command is being blocked via a binary input.

If none of the checks listed above are successful and the problem is not eliminated, send the unit to the manufacturer along with a detailed description of the problem.

147

11 Maintenance

The PD 521 is a low-maintenance device. The components used in the units are selected so that they meet exacting requirements. Recalibration is not necessary. The PD 521 is equipped with a lithium battery for nonvolatile storage of event data and for continued operation of the internal clock in the event of a failure of auxiliary voltage. Loss of capacity due to module-internal selfdischarging amounts to less than 1% per year over a period of availability of 10 years. Since the terminal voltage remains virtually constant until capacity is exhausted, usefulness is maintained until a very low residual capacity is reached. Given a nominal capacity of 800 mAh and discharge currents of only a few mA during device storage and/or in the range of the self-discharge current during device operation, a correspondingly long service life results. It is therefore recommended that the lithium battery only be replaced after a period of about ten years. The lithium battery can be replaced without soldering. Maintenance work may only be carried out by trained personnel with the auxiliary voltage turned off. The lithium battery is located on the input-output module.

Components located behind the front panel are energized. Turn off the power supply voltage before opening the unit.

!

After loosening four bolts on the front side of the front panel, the local control module (front panel and processor module) can be removed once the following plugs have been removed first: ¨ The tab connector on the case ¨ The tab connector on the lower circuit board (I/O module) ¨ The ribbon cable connecting the local control module (front panel and processor module) with the I/O module ¨ The ribbon cable connecting the local control module with the optional ILSA interface (-X7 and -X8 or -X9) Check the position of the connector. Do not allow the connecting cable to kink.

!

Where possible, disconnection of the ribbon cable between the processor module and the I/O module should be avoided. Should disconnection have occurred, however, then the device needs to be re-initialized by way of a cold restart.

The PD 521 is used as a safety device and must therefore be routinely checked for proper operation. It is recommended that the first functional test be carried out after about 6 to 12 months. Additional functional tests should be carried out at intervals of about 2 to 3 years – 4 years at the maximum. Routine Functional Testing The PD 521 digital protection device incorporates in its system a very extensive self-monitoring function for hardware and software. The internal structure guarantees, for example, that communication within the processor system will be checked on a continuing basis. Nonetheless, there are a number of subfunctions that cannot be checked by the self-monitoring feature without running a test from the device terminals. The respective device-specific properties and setting parameters must be observed in such cases. In particular, none of the control and signaling circuits run to the device from the outside are checked by the selfmonitoring function.

148

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

11 Maintenance (continued)

Analog Input Circuits Within the PD 521 an analog-digital converter is used to convert analog measured variables. However, an instrument transformer, filter, analog multiplexer and 1/16 amplifier are also incorporated in each single measuring channel so that a test from the device terminals is required in order to verify proper functioning. The supply voltages are monitored continuously. In conjunction with self-monitoring, moreover, the measuring circuit monitoring feature integrated into the protection function can in many cases exhibit a higher sensitivity and thus detect additional deviations, depending on the parameter assignment. A static test of the analog input circuits is best carried out by operating data measurement of the primary measured operating data or by using a suitable testing device. A “small” measured value (in the current path the nominal current, for example) and a “large” measured value (in the voltage circuit the nominal voltage, for example) should be used to check the effective range of the A/D converter. In this way the total modulation range is checked, including gain change-overs. The gain change-over occurs at a modulation of 1/16 of full scale. In the distance protection function this would be at approximately 6 × Inom in the current path where full modulation is 100 × Inom , and in the voltage path it would be at approximately 6 V phase-toground voltage at the device terminals.

This dynamic test is not absolutely necessary since it only checks the stability of a very few passive components. On the basis of reliability analysis one can expect statistically that in 10 years in 1000 devices only one component will be outside the tolerance zone. Additional testing in the analog area, such as for the impedance or starting characteristics, is not necessary in our opinion since complete digital processing of this information is carried out on the basis of the measured analog current and voltage values. Proper operation will have been demonstrated in conjunction with the type test. The function ‘ground fault direction determination using steady-state values’ can be checked in a similar way, that is by means of operating data measurement and a test device.

A check of the change-over point of gain change-over is hardly possible since the latter is determined by the hardware configuration. The only indication lies in a change in the measurement resolution. In the current path we obtain quantization levels of approximately 0.006 × Inom in the lower range and 0.1 × Inom in the upper range. The accuracy of operating data measurement is SIG: Overcurrent (I>) signal IDENT: Device identification ILSA: ILSA communications link INP: Binary input LED: LED indicators LOC: Local control panel MAIN: Main function MON: Self-monitoring OMEAS: Operating value measurement OUTP: Binary and analog output PASS: Pass-through functions PC: PC communications link START: Starting SOTF: Switch on to fault protection PSIG: Protective signaling

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

157

A Glossary (continued)

A 2 Symbols

Symbol

Graphic symbols for block diagrams Binary elements according to DIN 40900 Part 12, September 1992, IEC 617-12: amended 1991 Analog information processing according to DIN 40900 Part 13, January 1981

Description Components of a symbol A symbol consists of a contour or contour combination and one or more qualifiers.

To document the linking of analog and binary signals, additional symbols have been used, taken from several DIN documents. As a rule, direction of the signal flow is from left to right and from top to bottom. Other flow directions are marked by an arrow. Input signals are listed on the left side of the signal flow, output signals on the right side.

Symbol

Description

=

To obtain more space for representing a group of related elements, contours of the elements may be joined or cascaded if the following rules are met:

Control block A control block contains an input function common to several symbols. It is used for the collective setting of several trigger elements, for example.

Output block An output block contains an output function common to several symbols.

There is no functional linkage between elements whose common contour line is oriented in the signal flow direction. Note: This rule does not necessarily apply to configurations with two or more signal flow directions, such as for symbols with a control block and an output block. There exists at least one logical link between elements whose common contour line runs perpendicularly to the signal flow direction.

158

Settable control block The four digits represent the address under which the function shown in the text after the colon may be set via the local control panel. Settable control block with function blocks The digits in the function block show the settings that are possible at this address. The text below the symbol shows the setting and the corresponding unit or meaning.

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

A Glossary (continued)

Symbol

Description Static input Only the state of the binary input variable is effective.

Dynamic input Only the transition from value 0 to value 1 is effective.

Negation of an output The value up to the border line is negated at the output.

Negation of an input The input value is negated before the border line.

Dynamic input with negation Only the transition from value 1 to value 0 is effective.

AND element The output variable will be 1 only if all input variables are 1. OR element The output variable will be 1 only if at least one input variable is 1. Threshold element The output variable will be 1 only if at least two input variables are 1. The number in the symbol may be replaced by any other number.

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

Symbol

Description (m out of n) element The output variable will be 1 only if just one input variable is 1. The number in the symbol may be replaced by any other number if the number of inputs is increased or decreased accordingly. Delay element The transition from value 0 to 1 at the output occurs after a time delay of t1 relative to the corresponding transition at the input. The transition from value 1 to 0 at the output occurs after a time delay of t2 relative to the corresponding transition at the input. t1 and t2 may be replaced by the actual delay values (in seconds or strobe ticks). Monostable flip-flop The output variable will be 1 only if the input variable changes to 1. The output variable will remain 1 for 100 ms, independent of the duration of the input value 1 (non-retriggerable). Without a 1 in the function block the monostable flip-flop is retriggerable. The time is 100 ms in this example, but it may be changed to any other duration.

159

A Glossary (continued)

Symbol

Description Analog-digital converter An analog input signal is converted to a binary signal.

Subtractor The output variable is the difference between the two input variables. A summing element is obtained by changing the minus sign to a plus sign at the symbol input. Schmitt Trigger with binary output signal The binary output variable will be 1 if the input signal exceeds a specific threshold. The output variable remains 1 until the input signal drops below the threshold again. Memory, general Storage of a binary or analog signal.

Non-stable flip-flop When the input variable changes to 1, a pulse sequence is generated at the output.

Symbol

Description Amplifier The output variable is 1 only if the input variable is also 1.

Band pass filter The output only transmits the 50 Hz component of the input signals. All other frequencies (above and below 50 Hz) are attenuated. Counter At the + input the input variable transitions from 0 to 1 are counted and stored in the function block. At the R(eset) input a transition of the input variable from 0 to 1 resets the counter to 0. Electromechanical drive in general, here a relay, for example.

Signal level converter with electrical isolation between input and output. L+ = pos. voltage input L- = neg. voltage input U1 = device identifier

The ! to the left of the G indicates that the pulse sequence starts with the input variable transition (synchronized start). If there is a ! to the right of the G, the pulse sequence ends with the ending of the 1 signal at the input (synchronized stop).

160

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

A Glossary (continued)

Symbol

Description Input transducer with conductor and device identifiers (according to DIN EN 60445) Conductor identifiers for current inputs: for A: A1 and A2 for B: B1 and B2 for C: C1 and C2 for N: N1 and N2 Conductor identifiers for voltage inputs via transformer 1: for A: 1U for B: 1V for C: 1W for N: 1N via transformer 2: for A: 2U for B: 2V Device identifiers for current transformers: for A: T1 for B: T2 for C: T3 for N: T4 for voltage transformer 1: for A: T5 for B: T6 for C: T7 for N: T8 for VG-N transformer: T90 for voltage transformer 2: for A: T15

Symbol

Description PC interface with pin connections

Multiplier The output variable is the result of the multiplication of the two input variables. Divider The output variable is the result of the division of the two input variables. Comparator The output variable becomes 1 only if the input variable(s) are equal to the function in the function block. Formula block The output variable becomes 1 only if the input variable(s) satisfy the equation in the function block.

Change-over contact with device identifier

Special symbol Output relay in normallyenergized arrangement (‘closed-circuit operation’).

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

161

A Glossary (continued)

A 3 Examples of Signal Names All settings and signals relevant for protection are shown in the block diagrams of Chapter 3 as follows: Signal Name

Description

K FREC: Fault start

Internal signal names are not coded by an address. In the block diagrams they are marked with a diamond. The internal signal names used and their origins are listed in Appendix B.

DIST: Z1' triggered [ 3904 ]

Signal names coded by an address are referred to once by their address (in square brackets). The source is documented in Chapters 7 and 8.

DIST: Z1' triggered

Subsequent references use the signal name only.

MAIN: Control ext. ­ no (off)

A specific setting to be used later on is shown with its signal name and the setting with preceding setting arrow.

162

A 4 Symbols Used Symbol

Meaning

t

Time, duration

V

Voltage, potential difference

V

Complex voltage

I

Electrical current

I

Complex current

Z

Complex impedance

Z

Modulus of complex impedance

f

Frequency

d

Temperature in °C

S

Sum, result

W

Unit of electrical resistance

a

Angle

j

Phase angle. With subscripts: specific angle between a defined current and a defined voltage.

t

Time constant

DT

Temperature difference in K

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

B List of Signals

B 1 Internal Signal Names

Internal Signal Names

Internal signal names are not coded by an address. They are indicated by a diamond in the block diagram. Internal Signal Names

Figure

BUOC: Blocked by DTOC

38

BUOC: I N> trigd.

38

BUOC: IA triggered

38

BUOC: IB triggered

38

BUOC: IC triggered

38

BUOC: SN

38

DIST: jcorr

15

DIST: jF

16

DIST: jX

16

DIST: jZ

19

DIST: 1VA-B (stored)

Figure

DIST: RF

20

DIST: Selected meas.loop A-B

14

DIST: Selected meas.loop A-G

14

DIST: Selected meas.loop B-C

14

DIST: Selected meas.loop B-G

14

DIST: Selected meas.loop C-A

14

DIST: Selected meas.loop C-G

14

DIST: Selected meas.loop P-G

14

DIST: Selected meas.loop P-P

14

DIST: t0

28

DIST: Trip zone 1

29,32,34

DIST: Trip zone 2

29,32,34

DIST: Trip zone 3

29,32,34

DIST: Trip zone 4

29,32,34

15

DIST: Trip zone 5

29,32,34

DIST: Dist. decision Z1

23,27

DIST: Trip zone 6

29,32,34

DIST: Dist. decision Z1E

23,27

DIST: Vmeas

14

DIST: Dist. decision zone 1

23,27

DIST: Voltage memory enabled

15

DIST: Dist. decision zone 2

22,26

DIST: XF

20

DIST: Dist. decision zone 3

22,26

DIST: Zmeas

25

DIST: Dist. decision zone 4

22,26

FREC: Fault start

75

FREC: Reset signal mem.

76

GFDSS: 2IN filtered

61

GFDSS: 2VN-G filtered

56

DIST: Imeas

14

DIST: kze HSR = 1.0

23,27

DIST: Meas. zone 1

28

DIST: N1bw

28

GFDSS: Direction BS

56

DIST: N1fw

28

GFDSS: Direction LS

56

DIST: N2bw

28

GFDSS: GF enabled

54

DIST: N2fw

28

GFDSS: GFD enabled

54

DIST: N3bw

28

GFDSS: IN> triggered

61

DIST: N3fw

28

GFDSS: Meas. reset

67

28

GFDSS: Op. delay IN elapsed

61

DIST: N4bw

GFDSS: P

56

DIST: N4fw

28

GFDSS: Q

56

DIST: N5bw

28

GFDSS: VN-G> triggered

56

DIST: N5fw

28

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

163

B List of Signals (continued)

Internal Signal Names MAIN: Automatic reset MAIN: kInom

Figure

Internal Signal Names 76 2

Figure

START: Block

3

START: Dist. prot. starting

13

MAIN: Manual trip cmd.

69

START: Enable 1

8

MAIN: Manuel reset

76

START: Enable 2

8

3

START: Enable 3

8

MAIN: Protection active MAIN: Reset counter GFDSS

63

START: Enable ZA-G

11

MAIN: Time tag

75

START: Enable ZB-G

11

MAIN: Trip zone 1

69

START: Enable ZC-G

11

MON: Current

36

START: Enable ZA-B

11

MON: Vneg triggered

37

START: Enable ZB-C

11

PSIG: Send int.

52

START: Enable ZC-A

11

PSIG: Telecom. faulty int.

50

START: IA>> triggered

4

PSIG: Trip 1

50

START: IB>> triggered

4

PSIG: Trip 2

50

START: IC>> triggered

4

PSIG: Trip enable

50

START: IN> triggered

5

PSIG: Tripping time elapsed

41

START: P-G switching

6

PSIG: Zone ext.

48

START: SA

13

SOTF: Zone extension

39

START: SB

13

START: SC

13

START: SG

6

START: SN0

13

START: SN1

13

164

START: tIN> elapsed

5

START: Trip VN-G>>

7

START: tVN-G>> elapsed

5

START: VA< triggered

9

START: VB< triggered

9

START: VC< triggered

9

START: VN-G> exceeded

5

START: VN-G>> exceeded

5

START: VPP< triggered

9

START: ZA< triggered

12

START: ZB< triggered

12

START: ZC< triggered

12

START: ZPP< triggered

12

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

B List of Signals (continued)

B 2 Protection Communication Signals The interface protocol complies with IEC 60870-5-103, Revision 1.5, February 3rd, 1995 ”Protection Communication Companion Standard 1“, compatibility level 2. B 2.1 Monitoring Direction B 2.1.1 State Signals Inf.

No. Address

Description

Dec Hex

B 2.1.2 Monitoring Signals Inf.

No. Address

Description

Dec Hex 32

20

98 05

MON: Curr.meas. circuits

33

21

38 23

MON: Volt.meas. circuits

35

23

98 01

MON: Volt.meas. circuits

37

25

37 21

BUOC: Backup DTOC mode

17

11

15 08

PSIG: Enabled

38

26

04 61

MAIN: M.c.b. trip VLS EXT

18

12

03 30

MAIN: Protection active

39

27

36 60

PSIG: Telecom. faulty

19

13

21 10

MAIN: Reset indicat. USER

46

2E

36 70

MON: Warning

20

14

37 75

ILSA: Sig./meas.block

47

2F

04 65

MAIN: Blocked/faulty

21

15

37 71

PC/ILSA: Test mode

22

16

-- --

27

1B

40 16

PASS: Input 1 EXT

28

1C

40 17

PASS: Input 2 EXT

29

1D

40 18

PASS: Input 3 EXT

B 2.1.3 Ground Fault Signals not supported Inf.

No. Address

Description

Dec Hex

30

1E

40 19

48

30

-- --

not supported

49

31

-- --

not supported

50

32

-- --

not supported

51

33

09 35

GFDSS: Direct. forw./LS

52

34

09 36

GFDSS: Direct. backw./BS

PASS: Input 4 EXT

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

165

B List of Signals (continued)

B 2.1.4 Fault Signals Inf.

No. Address

B 2.1.5 Operating Value Measurement Description

Inf.

Dec Hex

No. Address

Scal Description

Dec Hex

64

40

36 01

START: Starting A

65

41

36 02

START: Starting B

66

42

36 03

START: Starting C

67

43

36 04

START: Starting GF

68

44

36 71

MAIN: General trip cmd.

72

48

36 14

BUOC: Tripping signal

73

49

04 29

FMEAS: Fault react. prim.

144

90

06 41

2.4

OMEAS: Current B p.u.

145

91

06 41 05 45

2.4 2.4

OMEAS: Current B p.u. OMEAS: Voltage A-B p.u.

146

92

06 41 05 45

2.4 2.4

04 51

2.4

04 53

2.4

OMEAS: Current B p.u. OMEAS: Voltage A-B p.u. OMEAS: Act. power P p.u. OMEAS: Reac. power Q p.u.

1

2

3

147

93

04 44 04 42

2.4 2.4

OMEAS: Current IN p.u. OMEAS: Voltage VN-G, p.u.

148

94

05 41 06 41 07 41 05 43

2.4 2.4 2.4 2.4

06 43

2.4

07 43

2.4

04 51

2.4

04 53

2.4

OMEAS: Current A p.u. OMEAS: Current B p.u. OMEAS: Current C p.u. OMEAS: Voltage A-G p.u. OMEAS: Voltage B-G p.u. OMEAS: Voltage C-G p.u. OMEAS: Act. power P p.u. OMEAS: Reac. power Q p.u. OMEAS: Frequency f

04 40

2.4

4

74

4A

36 18

DIST: Fault forward/LS

75

4B

36 19

DIST: Fault backward/BS

5

76

4C

36 35

PSIG: Send (signal)

77

4D

37 29

PSIG: Receive & gen.start

78

4E

36 26

DIST: t1 elapsed

79

4F

36 27

DIST: t2 elapsed

80

50

36 28

DIST: t3 elapsed

81

51

36 29

DIST: t4 elapsed

82

52

36 30

DIST: t5 elapsed

83

53

36 31

DIST: t6 elapsed

84

54

36 00

START: General starting

85

55

36 17

CBF: CB failure

Scal: Scaling

1

only if address 03 74 is set to the value “1“ only if address 03 74 is set to the value “2 3 only if address 03 74 is set to the value “3 4 only if address 03 74 is set to the value “4“ 5 only if address 03 74 is set to the value “5“ 2

166

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

B List of Signals (continued)

B 2.2 Control Direction

B 2.4 System Function Coordination

B 2.2.1 General Commands

Control Direction

Inf.

No. Address

Description

Initiation of general interrogation

supported

Time synchronization

supported

Dec Hex 17

11

15 08

PSIG: Enabled

18

12

03 30

MAIN: Protection active

19

13

21 10

MAIN: Reset indicat. USER

B 2.3 Fault Data Transmission Channels Channel

Description

1

Phase current IA

2

Phase current IB

3

Phase current IC

4

Residual current IN

5

Phase-to-ground voltage VA-G

6

Phase-to-ground voltage VB-G

7

Phase-to-ground voltage VC-G

8

Neutral point displacement voltage VN-G

Note:

Monitoring Direction End of general interrogation

supported

Time synchronization

supported

Reset FCB

supported

Reset CU

supported

Start / restart

supported

Identification

not supported

The neutral point displacement voltage is calculated from the phase voltages.

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

167

C Address List

GLOSSARY

Changing Values

Function Groups

on: "on" (on-line) means that the value can be changed even when the protective function is enabled. off: "off" (off-line) means that the value can be changed provided that the protective function is disabled. -: "-" means that the value cannot be modified by control action.

BUOC: CBF: DIST: FLOC: FMEAS: FREC: GFDSS:

Back-up overcurrent-time protection Circuit breaker failure protection Distance and directional measurement Fault localization Fault data acquisition Fault recording Ground fault direction determination using steady-state values GMEAS: Ground fault measurement data IDENT: Device identification ILSA: ILSA communications link INP: Binary input I>SIG: Overcurrent (I>) signal LED: LED indicators LOC: Local control panel MAIN: Main function MON: Self-monitoring OMEAS: Operating value measurement OUTP: Binary and analog output PASS: Pass-through functions PC: PC communications link PSIG: Protective signaling SOTF: Switch on to fault protection START: Starting

168

KEY f): n): o): p): u):

A change in value is possible without activating the value-change enabling function. Indication "..." is possible and means that no value has been measured. Indication "-..-" is possible and means that the value is out of range. The value change is password-protected. The setting "¥" is represented by the "0--0" display.

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

C Address List (continued)

C 1 Parameters C 1.1 Device Identification C 1.1.1 Ordering Information Address Description x y

Change

Default Range of Values

Increment

00 00

IDENT: Device type

-

00 48 00 49

IDENT: Device password 1 IDENT: Device password 2

off off

0.00 0.00

00 00 00 00 00

IDENT: IDENT: IDENT: IDENT: IDENT:

off off off off off

0 0 0.0 0.0 0.0

0 0 0.0 0.0 0.0

off

4176

4176 4432

Change

Default Range of Values

Unit or Meaning

Increment

-

101 1.2x

Version number Version number For internal use

1 0.01

50 51 52 53 54

00 80

Auxiliary voltage Nominal voltage Nominal current Nominal frequency Nominal current IN

IDENT: Add. HW modules

521

Unit or Meaning

PD 521 0.00 ... 99.99 0.00 ... 99.99 ... ... ... ... ...

999 999 9.9 99.9 99.9

0.01 0.01 V V A Hz A

1 1 0.1 0.1 0.1

Without ILSA interface

C 1.1.2 Design Version Address Description x y

02 00 02 20 02 60

IDENT: Data model IDENT: SW version IDENT: Auxiliary address

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

0 ... 9999 0.00 ... 99.99

169

C Address List (continued)

C 1.2 Configuration Parameters C 1.2.1 Control Interfaces Address Description x y

Change

Default Range of Values

Unit or Meaning

03 11

LOC: Access lock active

on

0

0 / 1

no / yes

03 12

PC/ILSA: Test mode USER

on

0

0 / 1

no / yes

03 13 03 14

LOC: Autom. return addr. LOC: Autom. return time

on on

0310 100

03 03 03 03 03

50 51 52 53 54

ILSA: ILSA: ILSA: ILSA: ILSA:

on on on on on

3.0 3.0 2.0 1 15.0

0.0 0.0 0.0 0 0.0

03 03 03 03 03

55 56 57 58 59

PC: PC: PC: PC: PC:

on on on on on

3.0 3.0 2.0 1 15.0

0.0 0.0 0.0 0 0.0

Delta Delta Delta Delta Delta

Delta Delta Delta Delta Delta

V I f t P

V I f t P

03 68 03 69

PC/ILSA: Device addr.(CU) PC/ILSA: Device addr.(PU)

off off

1 1

03 70

ILSA: Command enable USER

on

0

03 71

ILSA: Baud rate

off

03 74

ILSA: Transm. cycl. data

on

0

03 76

ILSA: Sig./meas.blck.USER

on

0

03 77

ILSA: Contin.general scan

on

¥

03 80

PC: Command enabling

on

1

03 81

PC: Baud rate

off

170

19200

9600

0 ... 60 ...

Increment

9999 1200

xxyy s

1 10

... ... ... ... ...

15.0 15.0 2.0 15 15.0

%Vnom %Inom %fnom min %Snom

0.5 0.5 0.1 1 0.5

... ... ... ... ...

15.0 15.0 2.0 15 15.0

%Vnom %Inom %fnom min %Snom

0.5 0.5 0.1 1 0.5

0 ... 0 ...

254 255

0 / 1 50 100 200 300 600 1200 2400 4800 9600 19.2

1 1

no / yes Baud Baud Baud Baud Baud Baud Baud Baud Baud kBaud

0 1 2 3 4 5 6 9 11 12 13 15 16 19

Without IB IB, VA-B IB, VA-B, P, Q IN, VN-G 1+IA,IC,VAG,VBG,VCG,P,Q,f IN,VN-G, IN,act, IN,reac 6+IN,fil 1+4 2+4 3+4 5+4 5+6 5+9 0 / 1

10 ...

9000/¥

0 / 1 300 600 1200 2400 4800 9600

} must be set } identical

no / yes s

10

u)

no / yes Baud Baud Baud Baud Baud Baud

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

C Address List (continued)

Address Description x y

Change

Default Range of Values

03 84

PC: Transm. cycl. data

on

0

03 86

PC: Sig./meas. val.block.

on

0

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

0 1 2 3 4 5 6 9 11 12 13 15 16 19

Unit or Meaning

Increment

Without IB IB, VA-B IB, VA-B, P, Q IN, VN-G 1+IA,IC,VAG,VBG,VCG,P,Q,f IN,VN-G, IN,act, IN,reac 6+IN,fil 1+4 2+4 3+4 5+4 5+6 5+9 0 / 1

no / yes

171

C Address List (continued)

C 1.2.2 Binary Inputs Address Description x y

Change

Default Range of Values

54 01 54 04

INP: Fct. assignm. U 1 INP: Fct. assignm. U 2

off off

-

54 02 54 05

INP: Operating mode U 1 INP: Operating mode U 2

off off

1 1

172

0326 0327 0461 0464 3634 3638 3645 3646 3647 3648 3649 3651 3688 3689 3718 3770 3772 3774 3816 3820 4016 4017 6501

Unit or Meaning

Increment

Without function MAIN: Deactivate prot.EXT MAIN: Activate prot. EXT MAIN: M.c.b. trip VLS EXT PSIG: Telecom. faulty EXT CBF: Input EXT PSIG: Test telecom. EXT MAIN: Trip cmd. block EXT DIST: Zone extension EXT SOTF: Manual close EXT PSIG: Receive EXT PSIG: Blocking EXT MAIN: CB closed sig. EXT FLOC: Trigger EXT FREC: Trigger EXT MAIN: Man. trip cmd. EXT PC/ILSA: Test mode EXT ILSA: Command enable EXT ILSA: Sig./meas.block EXT MAIN: Starting trig. EXT GFDSS: GF evaluation EXT PASS: Input 1 EXT PASS: Input 2 EXT MAIN: Reset indicat. EXT 0 / 1 0 / 1

active "low" / "high" active "low" / "high"

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

C Address List (continued)

C 1.2.3 Binary Outputs Address Description x y

51 51 51 51 51 51 51 51

01 03 05 07 09 11 13 15

OUTP: OUTP: OUTP: OUTP: OUTP: OUTP: OUTP: OUTP:

Fct. Fct. Fct. Fct. Fct. Fct. Fct. Fct.

Change

assignm. assignm. assignm. assignm. assignm. assignm. assignm. assignm.

K K K K K K K K

1 2 3 4 5 6 7 8

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

off off off off off off off off

Default Range of Values

-

0328 0340 0461 0462 0463 0465 0935 0936 0937 0938 1508 1509 2113 3500 3600 3601 3602 3603 3604 3605 3609 3613 3614 3615 3616 3617 3618 3619 3620 3621 3626 3627 3628 3629 3630 3631 3646 3648 3649 3651 3660 3663 3664 3665 3666 3669 3670 3671 3688 3720 3721 3724 3727 3728 3729 3771 3773 3775 3776 3807 3816 3820 3823 3824

Unit or Meaning

Increment

Without function MAIN: Prot. ext.activated MAIN: Man. trip cmd. USER MAIN: M.c.b. trip VLS EXT I>SIG: Overcurrent MAIN: Ground fault MAIN: Blocked/faulty GFDSS: Direct. forw./LS GFDSS: Direct. backw./BS GFDSS: tVN-G> elapsed GFDSS: GF curr. meas. PSIG: Enabled PSIG: Test telecom. USER MAIN: Trip cmd. blocked FREC: Fault occurence START: General starting START: Starting A START: Starting B START: Starting C START: Starting GF MAIN: General trip signal DIST: Trip signal BUOC: Starting BUOC: Trip signal START: VN-G>> triggered START: tVN-G>> elapsed CBF: CB failure DIST: Fault forward /LS DIST: Fault backward /BS PSIG: t1 revers.interlock START: Zero sequ. start. DIST: t1 elapsed DIST: t2 elapsed DIST: t3 elapsed DIST: t4 elapsed DIST: t5 elapsed DIST: t6 elapsed DIST: Zone extension EXT PSIG: Receive EXT PSIG: Blocking EXT MAIN: CB closed sig. EXT PSIG: Telecom. faulty SOTF: tManual-close runn. SOTF: Trip aft. man.close DIST: Zone extension CBF: tCBF running MON: Trip by Ineg MON: Warning MAIN: General trip cmd. FLOC: Trigger EXT MON: Measuring circ.mon. BUOC: Backup DTOC mode PSIG: Send (transm.relay) PSIG: Ready PSIG: Not ready PSIG: Receive & gen.start PC/ILSA: Test mode ILSA: Command enable ILSA: Sig./meas.block FREC: Trigger PSIG: Trip signal MAIN: Starting trig. EXT GFDSS: GF evaluation EXT MON: Volt. meas. circuits MON: Peripheral fault

173

C Address List (continued)

Address Description x y

Change

Default Range of Values

3826 3827 3828 3829 3837 3848 4016 4017 4020

174

Unit or Meaning

Increment

GFDSS: GFD ready GFDSS: GFD not ready GFDSS: GF ready GFDSS: GF not ready DIST: Fault in cable run MON: Meas.volt. ok PASS: Input 1 EXT PASS: Input 2 EXT PASS: Output 1 (t)

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

C Address List (continued)

C 1.2.4 LED Indicators Address Description x y

Change

Default Range of Values

Unit or Meaning

36.70 03.31 04.65

3670 0331 0465

MON: Warning MAIN: Operation MAIN: Blocked/faulty

0328 0340 0461 0462 0463 0935 0936 0937 0938 1508 1509 2113 3500 3600 3601 3602 3603 3604 3605 3609 3613 3614 3615 3616 3617 3618 3619 3620 3621 3626 3627 3628 3629 3630 3631 3635 3646 3649 3651 3660 3663 3664 3665 3666 3669 3671 3688 3720 3721 3727 3728 3729 3730 3731 3734 3735 3771 3773 3775 3776

Without function MAIN: Prot. ext.activated MAIN: Man. trip cmd. USER MAIN: M.c.b. trip VLS EXT I>SIG: Overcurrent MAIN: Ground fault GFDSS: Direct. forw./LS GFDSS: Direct. backw./BS GFDSS: tVN-G> elapsed GFDSS: GF curr. meas. PSIG: Enabled PSIG: Test telecom. USER MAIN: Trip cmd. blocked FREC: Fault occurence START: General starting START: Starting A START: Starting B START: Starting C START: Starting GF MAIN: General trip signal DIST: Trip signal BUOC: Starting BUOC: Trip signal START: VN-G>> triggered START: tVN-G>> elapsed CBF: CB failure DIST: Fault forward /LS DIST: Fault backward /BS PSIG: t1 revers.interlock START: Zero sequ. start. DIST: t1 elapsed DIST: t2 elapsed DIST: t3 elapsed DIST: t4 elapsed DIST: t5 elapsed DIST: t6 elapsed PSIG: Send (signal) DIST: Zone extension EXT PSIG: Blocking EXT MAIN: CB closed sig. EXT PSIG: Telecom. faulty SOTF: tManual-close runn. SOTF: Trip aft. man.close DIST: Zone extension CBF: tCBF running MON: Trip by Ineg MAIN: General trip cmd. FLOC: Trigger EXT MON: Measuring circ.mon. BUOC: Backup DTOC mode PSIG: Ready PSIG: Not ready PSIG: Receive & gen.start PASS: Output 1 (updating) PASS: Output 2 (updating) PASS: Output 1 (latching) PASS: Output 2 (latching) PC/ILSA: Test mode ILSA: Command enable ILSA: Sig./meas.block FREC: Trigger

57 01 57 03 57 05

LED: Fct. assignm. H 1 LED: Fct. assignm. H 2 LED: Fct. assignm. H 3

-

57 57 57 57 57 57 57 57 57

LED: LED: LED: LED: LED: LED: LED: LED: LED:

off off off off off off off off off

07 09 11 13 15 17 19 21 23

Fct. Fct. Fct. Fct. Fct. Fct. Fct. Fct. Fct.

assignm. assignm. assignm. assignm. assignm. assignm. assignm. assignm. assignm.

H 4 H 5 H 6 H 7 H 8 H 9 H 10 H 11 H 12

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

-

Increment

175

C Address List (continued)

Address Description x y

Change

Default Range of Values

3807 3816 3820 3823 3824 3826 3827 3828 3829 3837 3848 4016 4017 4020

176

Unit or Meaning

Increment

PSIG: Trip signal MAIN: Starting trig. EXT GFDSS: GF evaluation EXT MON: Volt. meas. circuits MON: Peripheral fault GFDSS: GFD ready GFDSS: GFD not ready GFDSS: GF ready GFDSS: GF not ready DIST: Fault in cable run MON: Meas.volt. ok PASS: Input 1 EXT PASS: Input 2 EXT PASS: Output 1 (t)

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

C Address List (continued)

C 1.3 Function Parameters C 1.3.1 Global

Address Description x y

Change

Default Range of Values

03 30

MAIN: Protection active

on

0

10 03

MAIN: Nominal current

off

1

1 5

1 A 5 A

10 04

MAIN: Connect. meas.circ.

on

1

1 2

Forward Reverse

10 30

MAIN: System frequency

off

50

50 60

10 40

MAIN: Transfer for 1p

on

1

1 2

Ground P or G =f(IP,med, IP,max)

10 41

MAIN: Phase priority

2pN

on

1

1 2 3 4 5 6 7 8 9 10

Phase-to-phase loop Phase-to-ground loop Vmin C before A acyclic A before B before C cycl. A before C acyclic C before B before A cycl. B before A acyclic A before B acyclic C before B acyclic B before C acyclic

10 48

MAIN: Neutral-point treat

on

1

1 2 3 4

Low-impedance grounding Isol./reson. w. start P-G Isol./reson.w/o start P-G Short-duration grounding

10 49

MAIN: Rotary field

on

1

1 2

Clockwise rotation Anti-clockwise rotation

21 12

MAIN: Trip cmd.block USER

on

1

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

0 / 1

Unit or Meaning

Increment

no (=off) / yes (=on)

50 Hz 60 Hz

0 / 1

no / yes

177

C Address List (continued)

C 1.3.2 Main Functions

Address Description x y

Change

Default Range of Values

Unit or Meaning

Increment

s

0.01

Starting 10 36

START: tI>>

on

0.00

0.00 ...

0.50

10 50

START: Xfw

on

10.0

0.10 ... 300.0 0.020 ... 60.00

W at Inom = 1 A W at Inom = 5 A

0.10 0.020

10 51 10 52

START: Rfw P-G START: Rfw P-P

on on

10.0 10.0

0.10 ... 300.0 0.020 ... 60.00

W at Inom = 1 A W at Inom = 5 A

0.10 0.020

10 53

START: Zbw/Zfw

on

0.50

0.10 ...

4.00

10 54 10 55

START: I>> START: IN>

on on

1.00 0.20

0.50 ... 0.10 ...

8.00 2.00

Inom Inom

0.05 0.05

10 56

START: VN-G>

on

0.10

0.02 ...

1.00

Vnom/Ö3

0.01

10 57

START: tIN>

on

0.10

0.00 ...

0.50

s

0.01

10 60

START: Trip tVN-G>>

on

0

10 61

START: tVN-G>>

on

1.00

0.00 ... 60.00

s

0.01

10 62 10 63

START: VN-G>> START: ß

on on

0.50 30

0.20 ... 15 ...

Vnom/Ö3 °

0.01 1

10 67

START: Operating mode

on

0

10 68 10 69

START: I> (Imin) START: V<

on on

0.20 0.70

25 93

START: Z evaluation

on

1

1 2

ZPG=VPG/(IP + kG*IN) ZPG=VPG/2*IP

on

1

1 2 3 4

Normal Normal Section cable - line Section line - cable

(polygon) (polygon) (polygon) (polygon)

on on on on

10.0 20.0 30.0 40.0

0.10 ... 9.990 10.00 ... 200.0 0.020 ... 1.998 2.00 ... 40.00

W W W W

at at at at

Inom Inom Inom Inom

= = = =

1 1 5 5

A A A A

0.01 0.10 0.002 0.020

(polygon) (polygon) (polygon) (polygon) (polygon) (polygon) (polygon) (polygon)

on on on on on on on on

10.0 10.0 20.0 20.0 30.0 30.0 40.0 40.0

0.10 ... 9.990 10.00 ... 200.0 0.020 ... 1.998 2.00 ... 40.00

W W W W

at at at at

Inom Inom Inom Inom

= = = =

1 1 5 5

A A A A

0.01 0.10 0.002 0.020

on

75

0 / 1

no / yes

1.00 65

0 1 2 0.10 ... 0.00 ...

0.01

W/o V tIN>

0 1

w/o backup DTOC With backup DTOC ... 8.00 ... 2.00 ... 10.00/¥ ... 10.00/¥

Inom Inom s s

0.05 0.05 0.01 0.01

0.00 ... 10.00

s

0.01

0.01 ... 9.99 10.0 ... 500.0

Refer. value (e.g. km)

0.01 0.1

u) u)

Circuit Breaker Failure Protection 11 67

CBF: tCBF Fault Localization

10 05

FLOC: Line length

on

10.0

10 11

FLOC: Start determination

on

1

10 12

FLOC: Line reactance

on

10.0

1 2 3

Fault end Fault end/ trip during t1 Trip or trigger

0.10 ... 9.990 10.00 ... 200.0 0.020 ... 1.998 2.00 ... 40.00

W W W W

at at at at

Inom Inom Inom Inom

= = = =

1 1 5 5

A A A A

0.01 0.10 0.002 0.020

Fault Recording 03 78 03 79

FREC: Pre-fault time FREC: Post-fault time

on on

40 40

10 ... 10 ...

100 250

03 95

FREC: Time-switching

on

0

03 96 03 97 03 98

FREC: Time of day FREC: Date FREC: Year

on on on

0.00 1.01 1989

0.00 ... 23.59 1.01 ... 31.12 1980 ... 2079

hh:mm dd.mm

0 / 1 0.02 ... 9.99 0.02 ... 1.00

no / yes s Vnom

0 1

ms ms

1 1

Standard time Daylight saving time 0.01 0.01 1

Ground Fault Direction Determination Using Steady-State Values 16 60 16 61 16 62

GFDSS: Enabled GFDSS: tVN-G> GFDSS: VN-G>

on on on

0 1.00 0.25

16 63

GFDSS: Operating mode

on

1

16 64 16 65

GFDSS: IN,act>/IN,reac LS GFDSS: Sector angle LS

on on

0.050 86

0.003 ... 1.000 80 ... 89

Inom °

0.001 1

16 66

GFDSS: Operate delay

on

0.10

0.00 ... 10.0 ...

s

0.01 0.1

16 67 16 68

GFDSS: IN,act>/IN,reac BS GFDSS: Sector angle BS

on on

0.050 86

0.003 ... 1.000 80 ... 89

Inom °

0.001 1

LS

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

1 2

0.01 0.01

cos phi circuit sin phi circuit

9.99/¥ 60.0

u)

181

C Address List (continued)

Address Description x y

BS

Change

Default Range of Values

Unit or Meaning

Increment

on

0.10

s

0.01 0.1

16 69

GFDSS: Operate delay

16 70

GFDSS: Connect.meas.circ.

on

1

16 71

GFDSS: Common reset

on

0

16 72 16 73

GFDSS: Release delay LS GFDSS: Release delay BS

on on

0.00 0.00

16 90

GFDSS: Select GFD/GF

on

1

16 91 16 92

GFDSS: f0 (GFD) GFDSS: f0 (GF)

on on

50 50

16 93

GFDSS: IN>

on

0.050

0.003 ... 1.000

Inom

0.001

16 94

GFDSS: Operate delay IN

on

0.10

0.00 ... 10.0 ...

9.99/¥ 60.0

s

0.01 0.1

16 95

GFDSS: Release delay IN

on

0.00

0.00 ...

9.99

s

0.01

0.00 ... 10.0 ...

9.99/¥ 60.0

1 2

u)

Forward Reverse 0 / 1

0.00 ... 0.00 ...

9.99 9.99

1 2 50 / 50 /

no / yes s s

0.01 0.01

Steady-state power Steady-state current 250 250

Hz Hz

u)

Overcurrent (I>) Signal 14 04

I>SIG: Threshold value

on

1.10

0.20 ...

8.00

Inom

0.01

14 08

I>SIG: t

on

5.00

0.00 ... 10.0 ...

9.99/¥ 60.0

s

0.01 0.1

u)

Self-Monitoring 03 15

MON: Peripheral fault

on

1

14 01 14 02 14 03

MON: Meas.circuit mon. MON: Threshold value Ineg MON: Trip by Ineg

on on on

1 0.20 0

14 07

MON: Meas. volt. circuit

on

1

0 1 0 / 1 0.10 ... 1.00 0 / 1 1 2 3

W/o mon.sig. memory entry With mon.sig.memory entry no / yes IP,max no / yes

0.05

Vneg Vneg with current enable Volt.mon.w.CB cont.enable

Operation Value Measurement 10 01 10 02

OMEAS: Inom,prim. C.T. OMEAS: Vnom,prim. V.T.

on on

1000 100.0

1 ... 3000 0.1 ... 800.0

A kV

1 0.1

s

0.01

Pass-Through Functions 17 21

PASS: tEM1

on

0.00

17 30

PASS: Op. mode tEM1

on

1

182

0.00 ... 10.00/¥ 1 2 3

u)

Operate delayed Passing make contact Passing break contact

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

C Address List (continued)

Address Description x y

Change

Default Range of Values

Unit or Meaning

Increment

Protective Signaling 15 00

PSIG: Operating mode

on

3

15 02

PSIG: Reset time send

on

0.25

15 03 15 04

PSIG: Echo on receive PSIG: Enabled USER

on on

0 0

15 11

PSIG: Tripping time

on

0.08

15 12

PSIG: DC loop op. mode

on

1

1 2 3 4 5 6 7

Direct trans.trip underr. PUTT Zone extension Signal comp.releas.scheme Signal comp. block.scheme Signal comp. pilot wire Reverse interlocking

0.00 ... 10.00 0 / 1 0 / 1 0.00 ... 10.00/¥ 1 2

s

0.01

without / with no / yes s

0.01

u)

Transm.relay break cont. Transm.relay make contact

Switch On To Fault Protection 11 60

SOTF: Manual close timer

on

1.00

11 61

SOTF: Operating mode

on

1

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

0.00 ... 10.00 1 2

s

0.01

Trip with starting Zone extension

183

C Address List (continued)

C 2 Operation C 2.1 Measured Operating Data

Address Description x y

Change

Default Range of Values

Unit or Meaning

Increment

04 40

OMEAS: Frequency f

-

0.00 ... 99.99

Hz

0.01

n)

04 41 04 42

OMEAS: Volt. VN-G, prim. OMEAS: Volt. VN-G, p.u.

-

0.00 ... 99.99 0.000 ... 1.500

kV Vnom/Ö3

0.01 0.001

n)o) n)o)

04 04 04 04 04

43 44 45 46 47

OMEAS: OMEAS: OMEAS: OMEAS: OMEAS:

Current IN prim. Current IN p.u. Curr. IN,act. p.u. Curr. IN,reac p.u. Curr. IN filt. p.u

-

0 ... 0.000 ... 0.000 ... 0.000 ... 0.000 ...

9999 9.999 9.999 9.999 9.999

A Inom Inom Inom Inom

1 0.001 0.001 0.001 0.001

n)o) n)o) n)o) n)o) n)o)

04 04 04 04

50 51 52 53

OMEAS: OMEAS: OMEAS: OMEAS:

Act. power P prim. Act. power P p.u. Reac. power Q prim Reac. power Q p.u.

-

-999 ... -7.50 ... -999 ... -7.50 ...

999 7.50 999 7.50

MW Snom MVA Snom

1 0.01 1 0.01

n)o) n)o) n)o) n)o)

0.01

n)

1 1 1

n) n) n)

04 54

OMEAS: Power factor

-

-1.00 ...

1.00

04 55 04 56 04 57

OMEAS: Load angle phi A OMEAS: Load angle phi B OMEAS: Load angle phi C

-

-180 ... -180 ... -180 ...

180 180 180

05 40 05 41

OMEAS: Current A prim. OMEAS: Current A p.u.

-

0 ... 9999 0.00 ... 30.00

A Inom

1 0.01

n)o) n)o)

05 05 05 05

OMEAS: OMEAS: OMEAS: OMEAS:

-

0.0 0.00 0.0 0.00

... 999.9 ... 1.00 ... 999.9 ... 2.00

kV Vnom kV Vnom

0.1 0.01 0.1 0.01

n)o) n)o) n)o) n)o)

42 43 44 45

Voltage Voltage Voltage Voltage

A-G A-G A-B A-B

prim. p.u. prim. p.u.

° ° °

06 40 06 41

OMEAS: Current B prim. OMEAS: Current B p.u.

-

0 ... 9999 0.00 ... 30.00

A Inom

1 0.01

n)o) n)o)

06 06 06 06

OMEAS: OMEAS: OMEAS: OMEAS:

-

0.0 0.00 0.0 0.00

... 999.9 ... 1.00 ... 999.9 ... 2.00

kV Vnom kV Vnom

0.1 0.01 0.1 0.01

n)o) n)o) n)o) n)o)

42 43 44 45

Voltage Voltage Voltage Voltage

B-G B-G B-C B-C

prim. p.u. prim. p.u.

07 40 07 41

OMEAS: Current C prim. OMEAS: Current C p.u.

-

0 ... 9999 0.00 ... 30.00

A Inom

1 0.01

n)o) n)o)

07 07 07 07

OMEAS: OMEAS: OMEAS: OMEAS:

-

0.0 0.00 0.0 0.00

kV Vnom kV Vnom

0.1 0.01 0.1 0.01

n)o) n)o) n)o) n)o)

0.001

n)o)

42 43 44 45

Voltage Voltage Voltage Voltage

C-G C-G C-A C-A

prim. p.u. prim. p.u.

... 999.9 ... 1.00 ... 999.9 ... 2.00

04 74

OMEAS: Auxiliary address

For internal use

04 04 04 04 04 04 04 09 09 09 09

MAIN: MAIN: MAIN: MAIN: MAIN: MAIN: MAIN: MAIN: MAIN: MAIN: MAIN:

For For For For For For For For For For For

184

93 94 95 96 97 98 99 61 62 63 99

Auxiliary Auxiliary Auxiliary Auxiliary Auxiliary Auxiliary Auxiliary Auxiliary Auxiliary Auxiliary Auxiliary

address address address address address address address address address address address

internal internal internal internal internal internal internal internal internal internal internal

use use use use use use use use use use use

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

C Address List (continued)

C 2.2 State Signals C 2.2.1 Functions Address Description x y

03 03 03 04 04 04 04 04 04 09 09 09 09 15 21 35 35 35 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 37 37 37 37

26 27 28 60 61 62 63 64 65 35 36 37 38 08 13 00 01 02 00 01 02 03 04 05 09 13 14 15 16 17 18 19 20 21 26 27 28 29 30 31 34 35 38 45 46 47 48 49 51 60 63 64 65 66 69 70 71 88 89 18 20 21 24

MAIN: Deactivate prot.EXT MAIN: Activate prot. EXT MAIN: Prot. ext.activated MAIN: Protect. not ready MAIN: M.c.b. trip VLS EXT I>SIG: Overcurrent MAIN: Ground fault PSIG: Telecom. faulty EXT MAIN: Blocked/faulty GFDSS: Direct. forw./LS GFDSS: Direct. backw./BS GFDSS: tVN-G> elapsed GFDSS: GF curr. meas. PSIG: Enabled MAIN: Trip cmd. blocked FREC: Fault occurence FREC: Signal mem.overflow FREC: Faulty time tag START: General starting START: Starting A START: Starting B START: Starting C START: Starting GF MAIN: General trip signal DIST: Trip signal BUOC: Starting BUOC: Trip signal START: VN-G>> triggered START: tVN-G>> elapsed CBF: CB failure DIST: Fault forward /LS DIST: Fault backward /BS PSIG: t1 revers.interlock START: Zero sequ. start. DIST: t1 elapsed DIST: t2 elapsed DIST: t3 elapsed DIST: t4 elapsed DIST: t5 elapsed DIST: t6 elapsed CBF: Input EXT PSIG: Send (signal) PSIG: Test telecom. EXT MAIN: Trip cmd. block EXT DIST: Zone extension EXT SOTF: Manual close EXT PSIG: Receive EXT PSIG: Blocking EXT MAIN: CB closed sig. EXT PSIG: Telecom. faulty SOTF: tManual-close runn. SOTF: Trip aft. man.close DIST: Zone extension CBF: tCBF running MON: Trip by Ineg MON: Warning MAIN: General trip cmd. FLOC: Trigger EXT FREC: Trigger EXT MAIN: Man. trip cmd. EXT MON: Measuring circ.mon. BUOC: Backup DTOC mode PSIG: Send (transm.relay)

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

Change

-

Default Range of Values

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

/ / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / /

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Unit or Meaning

no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no

/ / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / /

Increment

yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes

185

C Address List (continued)

Address Description x y

37 37 37 37 37 37 37 37 37 37 37 37 37 37 38 38 38 38 38 38 38 38 38 38 38 38 38 40 40 40

186

27 28 29 30 31 34 35 70 71 72 73 74 75 76 06 07 16 20 23 24 26 27 28 29 37 46 48 16 17 20

PSIG: Ready PSIG: Not ready PSIG: Receive & gen.start PASS: Output 1 (updating) PASS: Output 2 (updating) PASS: Output 1 (latching) PASS: Output 2 (latching) PC/ILSA: Test mode EXT PC/ILSA: Test mode ILSA: Command enable EXT ILSA: Command enable ILSA: Sig./meas.block EXT ILSA: Sig./meas.block FREC: Trigger MAIN: Auxiliary address PSIG: Trip signal MAIN: Starting trig. EXT GFDSS: GF evaluation EXT MON: Volt. meas. circuits MON: Peripheral fault GFDSS: GFD ready GFDSS: GFD not ready GFDSS: GF ready GFDSS: GF not ready DIST: Fault in cable run MAIN: Prot. ext.disabled MON: Meas.volt. ok PASS: Input 1 EXT PASS: Input 2 EXT PASS: Output 1 (t)

Change

Default Range of Values

-

0 0 0 0 0 0 0 0 0 0 0 0 0 0

/ / / / / / / / / / / / / /

1 1 1 1 1 1 1 1 1 1 1 1 1 1

-

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

/ / / / / / / / / / / / / / /

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Unit or Meaning

Increment

no / yes no / yes no / yes no / yes no / yes no / yes no / yes no / yes no / yes no / yes no / yes no / yes no / yes no / yes For internal use no / yes no / yes no / yes no / yes no / yes no / yes no / yes no / yes no / yes no / yes no / yes no / yes no / yes no / yes no / yes

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

C Address List (continued)

C 2.2.2 Binary Inputs Address Description x y

54 00 54 03

Change

INP: State U 1 INP: State U 2

-

Default Range of Values

0 / 1 0 / 1

Unit or Meaning

Increment

"low" / "high" "low" / "high"

C 2.2.3 Binary Outputs Address Description x y

51 51 51 51 51 51 51 51

00 02 04 06 08 10 12 14

OUTP: OUTP: OUTP: OUTP: OUTP: OUTP: OUTP: OUTP:

Change

State State State State State State State State

K K K K K K K K

1 2 3 4 5 6 7 8

-

Default Range of Values

0 0 0 0 0 0 0 0

/ / / / / / / /

1 1 1 1 1 1 1 1

Unit or Meaning

Increment

inactive/active inactive/active inactive/active inactive/active inactive/active inactive/active inactive/active inactive/active

C 2.2.4 LED Indicators Address Description x y

57 57 57 57 57 57 57 57 57 57 57 57

00 02 04 06 08 10 12 14 16 18 20 22

LED: LED: LED: LED: LED: LED: LED: LED: LED: LED: LED: LED:

State State State State State State State State State State State State

Change

H 1 H 2 H 3 H 4 H 5 H 6 H 7 H 8 H 9 H 10 H 11 H 12

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

-

Default Range of Values

0 0 0 0 0 0 0 0 0 0 0 0

/ / / / / / / / / / / /

1 1 1 1 1 1 1 1 1 1 1 1

Unit or Meaning

inactive inactive inactive inactive inactive inactive inactive inactive inactive inactive inactive inactive

/ / / / / / / / / / / /

Increment

active active active active active active active active active active active active

187

C Address List (continued)

C 2.3 Control and Testing Address Description x y

Change

Default Range of Values

00 85 03 02

MAIN: Cold restart MAIN: General reset

off on

0 0

0 / 1 0 / 1

03 03 03 03

03 04 06 08

GFDSS: Reset meas. values GFDSS: Reset counter FREC: Reset sig. memory MON: Reset mon. sig. mem.

on on on on

0 0 0 0

0 / 1 0 / 1 0 ... 9999 0 ... 30

03 03 03 03

10 39 40 41

LOC: Param. change enabl. MAIN: Warm restart MAIN: Man. trip cmd. USER FREC: Triggering USER

on off on on

0 0 0 0

03 42

OUTP: Relay assign.f.test

off

-

03 43

OUTP: Relay test

off

0

03 44

OUTP: Hold-time for test

on

1

09 60

MAIN: Auxiliary address

15 09 21 10

PSIG: Test telecom. USER MAIN: Reset indicat. USER

188

0 0 0 0

/ / / /

Unit or Meaning

Increment

no / yes no / yes

1 1 1 1

Reset: Reset: Reset: Reset: no no no no

5101 5103 5105 5107 5109 5111 5113 5115

/ / / /

2x 2x 2x 2x

p) p) E E E E

key Key Key Key

1 1

yes yes yes yes

p)

without function OUTP: Fct. assignm. OUTP: Fct. assignm. OUTP: Fct. assignm. OUTP: Fct. assignm. OUTP: Fct. assignm. OUTP: Fct. assignm. OUTP: Fct. assignm. OUTP: Fct. assignm. 0 / 1

1 ...

K K K K K K K K

1 2 3 4 5 6 7 8

no / yes 10

s

p) 1

For internal use on on

0 0

0 / 1 0 / 1

no / yes no / yes

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

C Address List (continued)

C 2.4 Monitoring Signals Address Description x y

03 01

MON: Mon. signal memory

Change

Default Range of Values

on

E---

Unit or Meaning

Increment

Entry into memory

1

Possible Entries 90 00

MON: EPROM

-

12 13 14 15

R/W R/W R/W R/W

error error error error

segm. segm. segm. segm.

C000 D000 E000 F000

hex hex hex hex

90 01

MON: RAM

-

0 1 2 3 4

R/W R/W R/W R/W R/W

error error error error error

segm. 0000 segm. 1000 segm. 2000 segm. 3000 NOVRAM

hex hex hex hex

90 02

MON: Exception

-

0 1 2 3 4 5

Undefined op-code Division error Undefined interrupt RMX exception Prot. NMI not active Fault semaphore blocked

90 90 90 90 90

MON: MON: MON: MON: MON:

-

1 1 1 8 9

Checksum error SCC error SCC error Low voltage Overflow

03 08 09 10 12

Parameters PC interface ILSA interface Battery Common-RAM Monitor sig. memory

90 13

MON: Signal memory

-

2 3 4

Checksum error Fault record lost Fault record lost

90 90 90 90 90 90 90

MON: MON: MON: MON: MON: MON: MON:

-

3 2 0 0 7 1 3

Checksum error Time-out Long telegram bef. norm. Unknown status telegram Reset NMI late Time control error

14 16 17 18 21 25 27

Monitor sig. memory PC interface PC interface PC interface Operat. watchdog NMI Clock

90 28

MON: Cold restart

-

0 1 2

Parameter loss EPROM exchange RAM without battery

90 90 90 90 90 90 90 90 90

MON: MON: MON: MON: MON: MON: MON: MON: MON:

-

0 0 0 0 0 0 0 0 0

Invalid telegram recept. Unknown addr. at scan Unknown addr.at cont.scan Wrong data type Buffer overflow Unknown data type field Unknown status telegram Unknown fault Error for general reject.

31 32 33 34 35 36 37 42 43

ILSA interface ILSA interface ILSA interface Spontan. sig.buffer Spontan. sig.buffer ILSA/PC telegram ILSA interface Common-RAM ILSA/PC interface

90 70

MON: Checksum

-

1 2 3

Local checksum Local total checksum Param. comp. local-global

94 02

MON: Clock

-

1

Hardware failure

98 00 98 01

MON: Voltage meas. VLS MON: Volt.meas.circuits

-

1 2

M.c.b. tripped Voltage unbalance

98 02 98 03

MON: Backup DTOC MON: Backup DTOC

-

3 4

Without DTOC With DTOC

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

189

C Address List (continued)

Address Description x y

98 98 98 98

05 06 07 09

MON: MON: MON: MON:

Curr. meas.circuits Protect.sig.transm. Measuring circuits Low voltage

Change

Default Range of Values

-

6 7 8 1

-

0 1 2 3 4 8 9 10 11 12 13 14 30 31 43

Unit or Meaning

Increment

Current unbalance Telecom. faulty Zero sequ. start. Ext. error low voltage

Cold / Warm Start 99 00

190

MON: Initialization

RAM segment 0000 hex RAM segment 1000 hex RAM segment 2000 hex RAM segment 3000 hex NOVRAM EPROM segment C000 hex EPROM segment D000 hex EPROM segment E000 hex EPROM segment F000 hex Activate operating system Init.test of oper. system Power failure Wrong SW version oper.sys Wrong SW version Wrong clock

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

C Address List (continued)

C 3 Events C 3.1 Event Counters Address Description x y

Change

Default Range of Values

Unit or Meaning

Increment

04 00 04 05

MAIN: No. general start. MAIN: No. trip cmds

on on

0 0

0 ... 0 ...

9999 9999

Reset: 2x E Key Reset: 2x E Key

1 1

04 10

FREC: No. system disturb.

-

0

0 ...

9999

Reset via 03 06

1

04 19

MON: No. of mon.signals

-

0

0 ...

30

Reset via 03 08

1

04 20

FREC: No. of faults

-

0

0 ...

9999

Reset via 03 06

1

09 09 09 09

GFDSS: GFDSS: GFDSS: GFDSS:

on on on on

0 0 0 0

0 0 0 0

9999 9999 9999 9999

Reset: Reset: Reset: Reset:

1 1 1 1

00 01 02 03

No. No. No. No.

GF GF GF of

forwd./LS backwd./BS steady-st. GFs (curr.)

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

... ... ... ...

2 2 2 2

x x x x

E E E E

key key key key

o) o)

o)

o) o) o) o)

191

C Address List (continued)

C 3.2 Measured Fault Data

Address Description x y

Change

Default Range of Values

Unit or Meaning

Increment

s

0.01

n)o)

0.1

n)o)

04 21

FMEAS: Operating time

-

0.00 ... 65.00

04 22

FLOC: Fault location

-

0.0 ... 500.0

04 23

FMEAS: Fault impedance

-

0.00 ... 9.990 10.00 ... 200.0 0.000 ... 1.998 2.00 ... 40.00

W W W W

04 24 04 25 04 26

FMEAS: Fault loop angle FMEAS: Fault current p.u. FMEAS: Fault voltage p.u.

-

-180 ... 180 0.00 ... 99.99 0.000 ... 2.000

° Inom Vnom

04 27

FLOC: Fault location %

-

0.0 ... 200.0

04 28

FMEAS: Fault reactance

-

0.00 ... 9.990 10.00 ... 200.0 0.000 ... 1.998 2.00 ... 40.00

W W W W

at at at at

Inom Inom Inom Inom

= = = =

1 1 5 5

A A A A

0.01 0.10 0.002 0.020

04 29

FMEAS: Fault react. prim.

-

0.00 ... 9.990 10.00 ... 490.0 0.000 ... 1.998 2.00 ... 98.00

W W W W

at at at at

Inom Inom Inom Inom

= = = =

1 1 5 5

A A A A

0.01 0.10 0.002 0.020

04 37

FMEAS: Load impedance

-

0.00 ... 9.990 10.00 ... 200.0 0.000 ... 1.998 2.00 ... 40.00

W W W W

at at at at

Inom Inom Inom Inom

= = = =

1 1 5 5

A A A A

0.01 0.10 0.002 0.020

04 38 04 39

FMEAS: Load angle FMEAS: Residual current

-

-180 ... 180 0.00 ... 99.99

° Inom

1 0.01

n)o) n)o)

04 48 04 49

FMEAS: GF angle FMEAS: Fault IN p.u.

-

-180 ... 180 0.00 ... 99.99

° Inom

1 0.01

n)o) n)o)

09 20

GMEAS: Voltage VN-G p.u.

-

0.000 ... 1.500

Vnom/Ö3

0.001

n)o)

09 21 09 22 09 23

GMEAS: Current IN p.u. GMEAS: Curr. IN,act p.u. GMEAS: Curr.IN,reac p.u.

-

0.000 ... 9.999 0.000 ... 9.999 0.000 ... 9.999

Inom Inom Inom

0.001 0.001 0.001

n)o) n)o) n)o)

09 24

GMEAS: GF durat.steady-st

-

0.0 ... 999.9

min

0.1

n)o)

09 25

GMEAS: IN filtered p.u.

-

0.000 ... 9.999

Inom

0.001

n)o)

09 26

GMEAS: GF durat.curr.meas

-

0.0 ... 999.9

min

0.1

n)o)

192

Ref. unit line length at at at at

Inom Inom Inom Inom

= = = =

1 1 5 5

0.01 0.10 0.002 0.020

A A A A

% Refer.value / reactance

1 0.01 0.001

n)o) n)o) n)o)

0.1

n)o)

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

C Address List (continued)

C 3.3 Fault Signals Address Description x y

03 00

FREC: Signal memory

Change

Default Range of Values

on

Unit or Meaning

---L

Entry into memory

/ / / / /

end/start end/start end/start end/start end/start ms s hh:mm dd.mm

Increment

Possible Entries 03 03 03 03 03 03 03 03 03 03 04 04 04 04 04 04 04 04 04 04 04 04 04 04 04 04 09 09 09 09 15 15 21 21 35 35 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36

28 40 41 80 86 93 94 96 97 98 20 21 22 23 24 25 26 27 28 29 60 61 62 63 64 65 35 36 37 38 08 09 12 13 00 01 00 01 02 03 04 05 09 13 14 15 16 17 18 19 20 21 26 27 28 29 30 31 34 35 45 46 47

MAIN: Prot. ext.activated MAIN: Man. trip cmd. USER FREC: Triggering USER PC: Command enabling PC: Sig./meas. val.block. FREC: Time (milliseconds) FREC: Time (seconds) FREC: Time of day FREC: Date FREC: Year FREC: No. of faults FMEAS: Operating time FLOC: Fault location FMEAS: Fault impedance FMEAS: Fault loop angle FMEAS: Fault current p.u. FMEAS: Fault voltage p.u. FLOC: Fault location % FMEAS: Fault reactance FMEAS: Fault react. prim. MAIN: Protect. not ready MAIN: M.c.b. trip VLS EXT I>SIG: Overcurrent MAIN: Ground fault PSIG: Telecom. faulty EXT MAIN: Blocked/faulty GFDSS: Direct. forw./LS GFDSS: Direct. backw./BS GFDSS: tVN-G> elapsed GFDSS: GF curr. meas. PSIG: Enabled PSIG: Test telecom. USER MAIN: Trip cmd.block USER MAIN: Trip cmd. blocked FREC: Fault occurence FREC: Signal mem.overflow START: General starting START: Starting A START: Starting B START: Starting C START: Starting GF MAIN: General trip signal DIST: Trip signal BUOC: Starting BUOC: Trip signal START: VN-G>> triggered START: tVN-G>> elapsed CBF: CB failure DIST: Fault forward /LS DIST: Fault backward /BS PSIG: t1 revers.interlock START: Zero sequ. start. DIST: t1 elapsed DIST: t2 elapsed DIST: t3 elapsed DIST: t4 elapsed DIST: t5 elapsed DIST: t6 elapsed CBF: Input EXT PSIG: Send (signal) MAIN: Trip cmd. block EXT DIST: Zone extension EXT SOTF: Manual close EXT

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

-

0 0 0 0 0

1 1 1 1 1

-

-

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

/ / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / /

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

s Ref. unit line length W ° Inom Vnom % Refer.value / reactance W W end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start

p)

1 1 0.01 0.01 1 1 0.01 0.1

n)o) n)o)

1 0.01 0.001 0.1

n)o) n)o) n)o) n)o)

193

C Address List (continued)

Address Description x y

36 36 36 36 36 36 36 36 36 36 36 36 36 37 37 37 37 37 37 37 37 37 37 37 38 38 38 38 38 38 38 38 38 40 40 40

194

48 49 51 60 63 64 65 66 69 70 71 88 89 18 20 21 28 29 70 71 72 73 74 75 07 16 20 23 24 27 29 37 48 16 17 20

PSIG: Receive EXT PSIG: Blocking EXT MAIN: CB closed sig. EXT PSIG: Telecom. faulty SOTF: tManual-close runn. SOTF: Trip aft. man.close DIST: Zone extension CBF: tCBF running MON: Trip by Ineg MON: Warning MAIN: General trip cmd. FLOC: Trigger EXT FREC: Trigger EXT MAIN: Man. trip cmd. EXT MON: Measuring circ.mon. BUOC: Backup DTOC mode PSIG: Not ready PSIG: Receive & gen.start PC/ILSA: Test mode EXT PC/ILSA: Test mode ILSA: Command enable EXT ILSA: Command enable ILSA: Sig./meas.block EXT ILSA: Sig./meas.block PSIG: Trip signal MAIN: Starting trig. EXT GFDSS: GF evaluation EXT MON: Volt. meas. circuits MON: Peripheral fault GFDSS: GFD not ready GFDSS: GF not ready DIST: Fault in cable run MON: Meas.volt. ok PASS: Input 1 EXT PASS: Input 2 EXT PASS: Output 1 (t)

Change

-

Default Range of Values

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

/ / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / /

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Unit or Meaning

Increment

end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start end/start

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

D Set Value Record Sheets

Serial No.

6.

Order No.

89521-0-

Diagram No.

89521.

Nominal Device Data Inom

A AC

Vnom

V AC

VA,nom

V DC

fnom

Hz

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

195

D Set Value Record Sheets (continued)

D 1 Device Identification D 1.1 Ordering Information Address x y

Description

Range of values

Unit or Meaning

00 80

IDENT: Add. HW modules

00 00

IDENT: Device type

00 48

IDENT: Device password 1

00 49

IDENT: Device password 2

00 50

IDENT: Auxiliary voltage

V

00 51

IDENT: Nominal voltage

V

00 52

IDENT: Nominal current

A

00 53

IDENT: Nominal frequency

Hz

00 54

IDENT: Nominal current IN

A

521

PD 521

D 1.2 Design Version Address x y

Description

Range of values

Unit or Meaning

02 00

IDENT: Data model

100

Version number

02 20

IDENT: SW version

1.0x

Version number

02 60

IDENT: Auxiliary address

196

For internal use

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

D Set Value Record Sheets (continued)

D 2 Configuration Parameters D 2.1 Control Interfaces Address x y

Description

Range of values

Unit or Meaning

03 11

LOC: Access lock active

03 12

PC/ILSA: Test mode USER

03 13

LOC: Autom. return addr.

xxyy

03 14

LOC: Autom. return time

s

03 50

ILSA: Delta V

%Vnom

03 51

ILSA: Delta I

%Inom

03 52

ILSA: Delta f

%fnom

03 53

ILSA: Delta t

min

03 54

ILSA: Delta P

%Snom

03 55

PC: Delta V

%Vnom

03 56

PC: Delta I

%Inom

03 57

PC: Delta f

%fnom

03 58

PC: Delta t

min

03 59

PC: Delta P

%Snom

03 68

PC/ILSA: Device addr.(CU)

} must be set

03 69

PC/ILSA: Device addr.(PU)

} identical

03 70

ILSA: Command enable USER

03 71

ILSA: Baud rate

03 74

ILSA: Transm. cycl. data

03 76

ILSA: Sig./meas.blck.USER

03 77

ILSA: Contin.general scan

03 80

PC: Command enabling

03 81

PC: Baud rate

03 84

PC: Transm. cycl. data

03 86

PC: Sig./meas. val.block

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

Baud

s

Baud

197

D Set Value Record Sheets (continued)

D 2.2 Binary Inputs Address x y

Description

54 01

INP: Fct. assignm. U 1

54 04

INP: Fct. assignm. U 2

54 02

INP: Operating mode U 1

54 05

INP: Operating mode U 2

Range of values

Unit or Meaning

Range of values

Unit or Meaning

D 2.3 Binary Outputs Address x y

Description

51 01

OUTP: Fct. assignm. K 1

51 03

OUTP: Fct. assignm. K 2

51 05

OUTP: Fct. assignm. K 3

51 07

OUTP: Fct. assignm. K 4

51 09

OUTP: Fct. assignm. K 5

51 11

OUTP: Fct. assignm. K 6

51 13

OUTP: Fct. assignm. K 7

51 15

OUTP: Fct. assignm. K 8

198

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

D Set Value Record Sheets (continued)

D 2.4 LED Indicators Address x y

Description

Range of values

Unit or Meaning

57 01

LED: Fct. assignm. H 1

36.70

MON: Warning

57 03

LED: Fct. assignm. H 2

03.31

MAIN: Operation

57 05

LED: Fct. assignm. H 3

04.65

MAIN: Blocked/faulty

57 07

LED: Fct. assignm. H 4

57 09

LED: Fct. assignm. H 5

57 11

LED: Fct. assignm. H 6

57 13

LED: Fct. assignm. H 7

57 15

LED: Fct. assignm. H 8

57 17

LED: Fct. assignm. H 9

57 19

LED: Fct. assignm. H 10

57 21

LED: Fct. assignm. H 11

57 23

LED: Fct. assignm. H 12

D 3 Function Parameters D 3.1 Global Address x y

Description

03 30

MAIN: Protection active

10 03

MAIN: Nominal current

10 04

MAIN: Connect. meas.curr.

10 30

MAIN: System Frequency

10 40

MAIN: Transfer for 1p

10 41

MAIN: Phase priority 2pN

10 48

MAIN: Neutral-point treat

10 49

MAIN: Rotary field

21 12

MAIN: Trip cmd.block USER

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

Range of values

Unit or Meaning

199

D Set Value Record Sheets (continued)

D 3.2 Main Functions Address x y

Description

Range of values

Unit or Meaning

Starting 10 36

START: tI>>

s

10 50

START: Xfw

W

10 51

START: Rfw P-G

W

10 52

START: Rfw P-P

W

10 53

START: Zbw/Zfw

10 54

START: I>>

Inom

10 55

START: IN>

Inom

10 56

START: VN-G>

Vnom/Ö3

10 57

START: tIN>

s

10 60

START: Trip tVN-G>>

10 61

START: tVN-G>>

s

10 62

START: VN-G>>

Vnom/Ö3

10 63

START: b

°

10 67

START: Operating mode

10 68

START: I> (Imin)

Inom

10 69

START: V<

Vnom or Vnom/Ö3

25 93

START: Z evaluation

Distance measurement 12 00

DIST: Zone 4

12 01

DIST: X1

(polygon)

W

12 02

DIST: X2

(polygon)

W

12 03

DIST: X3

(polygon)

W

12 04

DIST: X4

(polygon)

W

12 05

DIST: R1 P-G

(polygon)

W

12 06

DIST: R1 P-P

(polygon)

W

12 07

DIST: R2 P-G

(polygon)

W

12 08

DIST: R2 P-P

(polygon)

W

200

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

D Set Value Record Sheets (continued)

Address x y

Description

Range of values

Unit or Meaning

12 09

DIST: R3 P-G

(polygon)

W

12 10

DIST: R3 P-P

(polygon)

W

12 11

DIST: R4 P-G

(polygon)

W

12 12

DIST: R4 P-P

(polygon)

W

12 13

DIST: a (polygon)

12 23

DIST: Direction N1

12 24

DIST: Direction N2

12 25

DIST: Direction N3

12 26

DIST: Direction N4

12 27

DIST: Direction N5

12 28

DIST: t1

s

12 29

DIST: t2

s

12 30

DIST: t3

s

12 31

DIST: t4

s

12 32

DIST: t5

s

12 33

DIST: t6

s

12 34

DIST: kze P-G HSR

12 35

DIST: kze P-P HSR

12 36

DIST: kG angle

12 37

DIST: kG abs. value

12 38

DIST: Arc comp. (circle)

12 40

DIST: Characteristic

12 41

DIST: a

(circle)

°

12 42

DIST: Z1

(circle)

W

12 43

DIST: Z2

(circle)

W

12 44

DIST: Z3

(circle)

W

12 45

DIST: Z4

(circle)

W

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

°

201

D Set Value Record Sheets (continued)

D 3.3 Supplementary Functions Operating Value Measurement Address x y

Description

Range of values

Unit or Meaning

10 01

OMEAS: Inom,prim. C.T.

A

10 02

OMEAS: Vnom,prim. V.T.

kV

Pass-Through Functions Address x y

Description

17 21

PASS: tEM1

17 30

PASS: Op. mode tEM1

202

Range of values

Unit or Meaning s

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

D Set Value Record Sheets (continued)

Ground Fault Direction Determination Address x y

Description

Range of values

Unit or Meaning

16 60

GFDSS: Enabled

16 61

GFDSS: tVN-G>

s

16 62

GFDSS: VN-G>

Vnom

16 63

GFDSS: Operating mode

16 64

GFDSS: IN,act>/IN,reac

Inom

16 65

GFDSS: Sector angle LS

°

16 66

GFDSS: Operate delay LS

s

16 67

GFDSS: IN,act>/IN,reac

Inom

16 68

GFDSS: Sector angle

BS

°

16 69

GFDSS: Operate delay BS

s

16 70

GFDSS: Connect.meas.curr.

16 71

GFDSS: Common reset

16 72

GFDSS: Release delay LS

s

16 73

GFDSS: Release delay BS

s

16 90

GFDSS: Select GFD/GF

16 91

GFDSS: f0 (GFD)

Hz

16 92

GFDSS: f0 (GF)

Hz

16 93

GFDSS: IN>

Inom

16 94

GFDSS: Operate delay IN

s

16 95

GFDSS: Release delay IN

s

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

203

D Set Value Record Sheets (continued)

Fault Localization Address x y

Description

10 05

FLOC: Line length

10 11

FLOC: Start determination

10 12

FLOC: Line reactance

Range of values

Unit or Meaning

W

Overcurrent (I>) Signal Address x y

Description

Range of values

Unit or Meaning

14 04

I>SIG: Thresh. value DTOC

Inom

14 08

I>SIG: t

s

CB-Failure Protection Address x y 11 67

Description

Range of values

CBF: tCBF

Unit or Meaning s

Back-up Protection Address x y

Description

Range of values

Unit or Meaning

14 00

BUOC: Operating mode

17 00

BUOC: I>

Inom

17 03

BUOC: IN>

Inom

17 04

BUOC: tI>

s

17 08

BUOC: tIN>

s

204

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

D Set Value Record Sheets (continued)

Fault Recording Address x y

Description

Range of values

Unit or Meaning

03 78

FREC: Pre-fault time

ms

03 79

FREC: Post-fault time

ms

03 95

FREC: Time-switching

03 96

FREC: Time of day

hh:mm

03 97

FREC: Date

dd.mm

03 98

FREC: Year

Protective Signaling Address x y

Description

15 00

PSIG: Operating mode

15 02

PSIG: Reset time send

15 03

PSIG: Echo on receive

15 04

PSIG: Enabled USER

15 11

PSIG: Tripping time

15 12

PSIG: DC loop op. mode

Range of values

Unit or Meaning

s

s

Self-monitoring Address x y

Description

03 15

MON: Peripheral fault

14 01

MON: Meas.circuit mon.

14 02

MON: Threshold value Ineg

14 03

MON: Trip by Ineg

14 07

MON: Meas. volt. circuit

Range of values

Unit or Meaning

Range of values

Unit or Meaning

Switch on to Fault Protection Address x y

Description

11 60

SOTF: Manual close timer

11 61

SOTF: Operating mode

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

s

205

E Terminal Connection Diagrams

111 Terminal connection diagram for PD521 version -302 -401 -602, diagram 89521.401 part 1 of 2

206

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

E Terminal Connection Diagrams (continued)

112 Terminal connection diagram for PD521 version -302 -401 -602, diagram 89521.401 part 2 of 2

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

207

E Terminal Connection Diagrams

113 Terminal connection diagram for PD521 version -303 -402 -602, diagram 89521.402 part 1 of 2

208

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

E Terminal Connection Diagrams (continued)

114 Terminal connection diagram for PD521 version -303 -402 -602, diagram 89521.402 part 2 of 2

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

209

210

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

ALSTOM Energietechnik GmbH Bereich Schutz- und Schaltanlagenleittechnik System Protection P. O. Box 71 01 07 D - 60491 Frankfurt

This operating manual is drafted according to our experience and is composed conscientiously. If nevertheless you still find any mistakes in it, please tell us by this enclosed form. We are also grateful for your further hints and improvement proposals.

Operating Manual "PD 521 Distance Protection Device" Publication ID No. "89521-302/-303-401/-402-602 / AFSV.12.06470 EN" Hints:

Sender Address:

Phone: Fax:

89521-302/-303-401/-402-602 / AFSV.12.06470 EN

211

Protection systems for power generation, transmission and distribution

Supervision equipment for the monitoring of ground faults, insulation, currents, voltages, asymmetry, frequency and reverse power

ALSTOM Sales Offices with System Protection Specialists Argentina

ALSTOM T&D S. A. Lavalle 3568 1603 Villa Martelli P. de Buenos Aires Phone +541730-1800 Fax +541730-1529

Australia

ALSTOM T &D 25 Princes Rd. POB 22 Regents Park NSW 2143 Phone +61296450735 Fax +61297438488 ALSTOM T&D MASA SA Protection & Control Av. Interlagos, 42111 04661-300 Sao Paulo Phone +55115241044 Fax +55115483429 ALSTOM Sales Network Inc. 5112 Timberlea Blvdl. Mississauga Ontario L4W-2S5 Phone +1905-6248300 Fax +1905-6248855 ALSTOM T&D Protection & Control Limited St Leonard Works Stafford ST174LX Phone +441785-223251 Fax +441785-212232

Brazil

Canada

Substation control and protection systems England

France

ALSTOM T&D Protection & Contrôle Avenue de Figuières, B.P. 75 34975 Lattes Cedex Phone +3346720-5526 Fax +3346720-5584

Hong Kong ALSTOM T&D Protection & Control Rm. 2006-7CC Wu Building 302-308 Hennessy Road Wanchai, GPO Box 15 Hong Kong Phone +85228336265 Fax +85228345279 India ALSTOM India Ltd. Pallavaram works 19/1, GST Road Pallavaram Madras-600043 Phone +91442368621 Fax +91442367276 Poland ALSTOM T&D REFA S.A. Strzegomska 23/27 58-160 Swiebodzice Phone +4874548410 Fax +4874541632 South Africa ALSTOM 35-37 Eleventh Road Kew, Johannesburg, 2090 Phone +27118853240 Fax +27118851100

Spain

USA

ALSTOM Sales Network,S.A. Paseo de la Castellana, 257 28046 Madrid Phone +341334.59.50 Fax +341334.59.51 ALSTOM T&D 4 Skyline Drive Hawthorne New York 10532-2160 California 90034 Phone +1-914347-5166 Fax +1-914347-5508

08.99 a Addresses of more sales offices and countries on request

ALSTOM Energietechnik GmbH Bereich Schutz- und Schaltanlagenleittechnik Lyoner Straße 44-48 D-60528 Frankfurt Postfach 71 01 07 D-60491 Frankfurt Phone +49 69 66 32-15 21 Fax +49 69 66 32-25 48 http://www.tde.alstom.com

AFSV.12.06470/0500EN

Printed in Germany

Contents subject to change

 ALSTOM Energietechnik GmbH · Energy Automation & Information Lyoner Straße 44-48 · 60528 Frankfurt · Postfach 71 01 07 · 60491 Frankfurt Telefon (0 69) 66 32 - 33 33 · Telefax (0 69) 66 32 - 25 48 www.tde.alstom.com [email protected]

View more...

Comments

Copyright ©2017 KUPDF Inc.
SUPPORT KUPDF