Description Alarm call master panel 100 V Relay card 100 V / Signal Relay card Amplifier monitoring 100V Relay card / General Alarm Digital I/O card Telephone interface / external control input DAC Digital Announce Card 230V power supply / Battery switch Back-up microphone Back-up push button panel DAC Digital Announce Card for the back-up system Digital power amplifier 100V - 250 W / 500 W Digital power amplifier 100V - 250 W / 500 W
- PC connection for programming purpose - General alarm. There is a system error - Data bus active. Data transfer is taking place
DSP1
- Led is on when microphone panel 1 is connected and ready to use - Led blinks when microphone panel 1 is not connected or defective
DSP2
- Led is on when microphone panel 2 is connected and ready to use - Led blinks when microphone panel 2 is not connected or defective
DSP3
- Led is on when microphone panel 3 is connected and ready to use - Led blinks when microphone panel 3 is not connected or defective
DSP4
- Led is on when microphone panel 4 is connected and ready to use - Led blinks when microphone panel 4 is not connected or defective
DSP5
- Led is on when microphone panel 5 is connected and ready to use - Led blinks when microphone panel is not connected or defective
DSP6
- Led is on when microphone panel 6 is connected and ready to use - Led blinks when microphone panel 6 is not connected or defective
4
Module 1 – Alarm call signal control ( Programme - Music)
Input 1
- Led is on when music input 1 is active
Input 2
- Led is on when music input 2 is active
Input 3
- Led is on when music input 3 is active
IN1
- Volume / Level music input 1
IN2
- Volume / Level music input 2
IN3
- Volume / Level music input 3
Level
- Master volume of all music signals
LF
- Low frequency – increase / decrease 80Hz +/- 12 dB
HF
- High frequency – increase / decrease 8,000Hz +/- 12 dB
Level[dB]
- Sound level indicator
5
Module 1 - Alarm call signal control – (Call / Alarm)
Level
- Volume level adjustment of announcement This control has no purpose for alarm signals from the DAC (module 8) The volume of the alarm signal can be adjusted via the DAC (module 8)
LF
- Low frequency - increase / decrease 80Hz +/- 12 dB
HF
- High frequency - increase / decrease 8,000Hz +/- 12 dB
Level[dB]
- Sound level indicator
ACTIVE
- Led is on if one of the microphone panels is active or if there is an alarm
6
Module 2 and 3 – Relay card (Module 2 en 3)
Module 2 Rel. Rel. Rel. Rel. Rel. Rel.
active active active active active active
LED LED LED LED LED LED
1 2 3 4 5 6
-
LED LED LED LED LED LED
on: on: on: on: on: on:
Zone Zone Zone Zone Zone Zone
1 2 3 4 5 6
active active active active active active
LED LED LED LED LED LED
1 2 3 4 5 6
-
LED LED LED LED LED LED
on: on: on: on: on: on:
Zone 7 active Zone 8 active Alarm 1 active Alarm 2 active Alarm 3 active Alarm output active
Master System (Module 1) back-up System (Module 10&11) Master System (Module 1) back-up System (Module 10&11) Master System (Module 1) back-up System (Module 10&11) Master System (Module 1) back-up System (Module 10&11) Master System (Module 1) back-up System (Module 10&11) Master System (Module 1) back-up System (Module 10&11) Master System (Module 1) back-up System (Module 10&11) Master System (Module 1) back-up System (Module 10&11)
System Error active System in use
Input LED 1 on Error from back-up system active (Module 10&11) Input LED 2 on The back-up system (Module 10&11) is in use In-Output LED 16 blinking Digital I/O Card DIO16MS (Module 5) active – OK
9
Module 7 and 8 – Telephone interface / signal input (Module 7) - DAC (Module 8)
Module 7 Pwr.[data] Led Error Led C/A Preset Led Prg. Preset Level 1 Level 2 Level 3 Rs 232
Blinks during active data transmission and Power OK On: System failure On: External Call input on this module is active Not in use Volume adjustment of telephone announcements Not in use Not in use PC Interface / (Only for service)
Module 8 Power[data] Led Play Led Error Led
Blinks during active data transmission and Power OK On: message is playing Blinking: testing message On: SD card error / failure
Level Level Level Level Level Level
Volume Alarm 1 Volume Alarm 2 Volume Alarm 3 Volume pre-announcement tone Not in use Not in use
1 2 3 4 5 6
10
Module 9 and 10 – Power supply (Module 9) - back-up microphone (Module 10)
Module 9 P Led on E Led on S Led on
Power OK Power failure / No battery connected Standby (Not in use)
Module 10 Back-up microphone. This microphone has priority over the Master system. By pushing the call button an announcement can be made in all zones at once. This function will remain when the Master system fails.
11
Module 11 and 12 - Back-up push button field (Module 11) - Back-up DAC (Module 12)
The back-up system always has priority over the master system.
Module 12 Power[data] Led Play Led Error Led
On: Power OK On: Message is playing Blinking: Testing message On: Sd card failure
Level Level Level Level Level Level
Volume alarm 1 (back-up system level) Volume alarm 2 (back-up system level) Volume alarm 3 (back-up system level) Not in use Not in use Not in use
1 2 3 4 5 6
12
Module 13 and 14 - Amplifier
Module 13 + 14
PS OK Led Bat Error Led BAT active Led SPK CON Standby Led GND Fault Error
Power OK Battery failure Amplifier operating on battery Loudspeaker wiring OK Not in use Earth loop on loudspeaker output determined Amplifier failure / Overload