Air Dist for Labs, Hospitals and Clean Rooms-ASHRAE1
April 19, 2017 | Author: khanh.vec | Category: N/A
Short Description
Download Air Dist for Labs, Hospitals and Clean Rooms-ASHRAE1...
Description
Air Distribution for Laboratories, Hospitals and Clean Rooms Dan Int-Hout Chief Engineer / Krueger Richardson Texas
3/22/2011
Today’s Standard Lab?
Purpose Recognize the importance of proper air distribution selection in laboratory designs
Agenda • Defining the Problem – Lab Types – Design Parameters
• Possible Solutions – Types of Air Outlets
• Proving the Case – Case Studies
Defining the Problem
Common Laboratory Types • Biological – contain biologically active materials or involve chemical manipulation • Chemical – organic and inorganic analysis and synthesis • Animal – manipulation, surgical modification and pharmacological observation • Physical – incorporate lasers, optics, nuclear material, high and low temp materials • Isolation – can be infectious or protective in nature
HVAC Design Parameters • • • • • • •
Define Air Change Rate requirements Suppress & Remove Airborne Contaminants Optimize Air Change Effectiveness Control and Direct Room Air Motion Provide Occupant Comfort Room Controls Aid in Fume Hood Containment
Air Change Rates • Air Change Rates per Hour-ACH frequently established by exhaust hood make up air requirement – Typical Labs requires 6 -10 ACH – Animal Housing requires 15 ACH
Example • Room Dims – 10’Wx20’Lx10’H = 2000 ft3 • @ 10ACH = 333 CFM or 1.6 CFM/ft2 ACH = CFM * 60 / Room Volume
Suppress & Remove Airborne Contaminants Factors to Consider: • System Effectiveness • Particulate Concentration & Dilution Rate Measurements: • Particulate Dispersion – Particle Count – Gas Concentration – Contaminant Migration
High Count
Low Count
Optimize Air Change Effectiveness • Efficiency of Dilution • Speed of Extraction • Decrease Age of Air • Improve Operational Efficiency
Environmental Dust Pollen Mold
Copiers Ammonia Benzaldehyde Benzene Isopropanol Combustion Products
Paints Acetates Alcohol Alkanes Benzenes
Computer Butanol Butanole Butoxyethanol Ozone Phosphoric Acid Tolune
Occupants CO2
Floor Coverings Formaldehyde Acetates Styrenes Xylenes
Room air motion is primarily determined by supply air delivery and heat load, not exhaust flows
Control and Direct Room Air Motion Controlled Flow to avoid: • Excessive Drafts • Recirculation • Hot and Cold Spots • Interference with Experiments • Compromise Fume Hood Safety • Temperature Swings Supply air outlets direct air into the space in different ways. Supply outlet type and location must be evaluated to assure satisfactory room air motion.
Laboratory Pressure Controls Energy Efficiency
First Cost
Future Flexibility
Constant Volume
Low
$
Low
2 Position
Med
$$
Low
Direct Pressure
High
$$$
High
Flow Tracking
High
$$
High
Flow Tracking with Pressure Feedback
High
$$$
High
Safety
VAV Systems
Provide Occupant Comfort • Noise – Operating Fume Hoods generate NC levels between an NC 40 to 45 • Temperature – Uniform Temperature – No Stratification • Eliminate Drafts • Ventilation • Humidity
Fume Hood Containment ASHRAE Standard 110: 4.11.2 Supply Air Distribution “Supply air distribution shall be provided to create air jet velocities {distributed towards the hoods}less than half (preferably less than one-third) of the capture or face velocity of the exhaust hoods.” Fume Hood Face Velocity = 100 fpm
Fume Hood Containment Fume Hood Locations • Avoid walkways – Prevent spillage due to walking wake
• Avoid fume hoods near exits – Spills or accidents may increase the danger
Possible Solutions
3 Most Common Types of Air Outlets • High-Induction/Entrainment Outlets • Laminar Flow Outlets • Radial/Forced Displacement
High Induction/Entrainment Diffusers RM
• • • •
Commercial Office Spaces High Velocity Jets Long Throw Designed to Mix in Zone
PLQ-R
1400
Prism
Prism
Animation of High Induction/Entrainment Diffusers
Why Not a High Induction Diffuser in the Laboratory? • High velocity ceiling pattern and colliding jets may enter occupied zone • Results in mixing & re-circulation of air • particles and gases drawn into supply air stream • air ages before it is exhausted
• Operational Efficiency is Sacrificed • Requires higher ACR to reduce particle counts
• Interference w/ Fume Hood • Occupant comfort • Uniform Temperatures Only
Laminar Flow Outlets
• Hospital Operating Suites when used in conjunction with air curtain • Hi-Tech Electronics - Bench Top Applications
Why not a Laminar Flow Device in the Laboratory? • Vertical Column of Air • Velocity 30-100 fpm depending on T
• • • •
Turbulence in space Fume Hood Face Velocity Disturbance No Occupant comfort Operational Efficiency is Sacrificed • Results in higher ACR to reduce particle counts • Non Uniform SpaceTemperature
Animation of High Laminar Flow Diffuser
Radial Forced Displacement Outlets
• • • •
Pharmaceutical & Chemistry Labs University Labs Isolation Wards Animal Holding Rooms
Why a Radial Displacement Diffuser in a Laboratory? • Creates a low velocity radial air flow pattern • Suppresses mixing & re-circulation of air • particles and gases pushed down and away from work area toward exhausts • minimal age of air (one-pass-then-out)
• Operational Efficiency • ACE vs. ACR improved
• Occupant comfort • Uniform Temperatures • Improved Acoustics
• Minimal Fume Hood interference
Animation of Radial Flow Diffuser
Proving the Case
Case Study: Integrated-circuit
crystal growth chamber • Test problem: Determine the efficiency in which particles could be removed from a space based on the type of air distribution device employed.
• Displacement • Parameters: – 41x41x9 Room – 32 ACH – 20°F T
vs. Laminar (Qty=10) - Qty = 10
Case Study: Integrated-circuit
crystal growth chamber
Results: After 4 min. 207% ACE difference
Laminar, 800CFM/Diffuser – low efficiency
Displacement TAD, 600
CFM/Diffuser– High efficiency
TAD-800CFM/diffuser
Case Study: Animal Holding Room
Mock-Up • Test Problem: Determine the rate of decay in an animal holding room
• High Induction vs. • Parameters: – 20x14x9 Room – 15 ACH – 10°F T
Forced Radial Displacement
- (Qty=2)
Case Study: Animal Holding Room Mock-Up-High Induction Diffusers
17:40 min to reach Class 100,000
Case Study: Animal Holding Room MockUp-Forced Displacement Diffusers
13:45 min to reach Class 100,000 29%, ACE improvement
Case Study: Animal Holding Room
Mock-Up • Test Problem: Determine the most efficient room layout and exhaust location in a animal holding room mock up
• High Exhaust vs. Low Exhaust • Parameters: – – – –
Forced Radial Displacement (Qty=2) 20x14x9 Room 15 ACH 10°F T
Case Study: Animal Holding Room
Mock-Up with Ceiling Located Exhaust
Case Study: Animal Holding Room Mock-Up with Low Sidewall Exhaust
•Class 20,000 17%, ACE improvement over ceiling located exhaust
Effective Solutions
Effective Solutions Intrusive Radial flow
Flush Face Radial flow
Performance Matters • Notice Jets – Competition photo published in ASHRAE magazine
• Perforated Metal Physics – Air wants to travel Horizontal or Vertical to the face of the perforated metal – The larger the T the more difficult it is to throw at a 45° angle
Parallel SCC Unit in a Lab Application Parallel SCC Unit
Lab Pressure Control Valve Critical Environment Outlets
Hospital Air Curtain Systems
Down the road to bad assumptions Total particle counts reductions leads to reductions in infection rates
+ micro-filtered vertical laminar airflow of a specific velocity leads to total particle reductions
= micro-filtered vertical laminar airflow of a specific velocity is the only acceptable air distribution solution
“…what we observe is not nature in itself, but nature exposed to our method of questioning” Werner Heisenberg, physicist
Where Clean Counts • Other than the surgeon’s hands, nothing is more important than sterile in the hospital OR • Through bad choices, we can dirty an otherwise clean environment • Assumptions that hold true in the clean room may not apply in the OR
Fallacy: all vertical laminar is good laminar •
Laminar diffusers do not behave predictably outside a system that does not include these features: 1. Isothermal entry 2. Unbroken arrays 3. Controlled static (HEPA filter?) 4. Proper exhaust location 5. Precise balancing 6. Distributed heat load
OR’s are not clean rooms!
Fact: Vertical laminar can behave badly
May induce more than expected
Broken arrays may cause chaotic flow
Large arrays produce mass effect
Low velocity may not overpower mass heat source No proof that it works!
A Change of Heart What is needed is a “one pass – then out” system that was sensible, safe, efficient and economical
Enter the air curtain • Air distribution manufacturers realized several things: – Howorth systems did not play well with others – Laminar flow was unpredictable outside of the clean room – Designers needed a scalar design proven to reduce viable particle counts
Enter the air curtain • What an air curtain looks like:
Enter the air curtain • What an air curtain does:
Why air curtains work better
It doesn’t replace laminar; it helps laminar behave predictably Mechanically friendly
Catching and counting microbes
Classifications based on viable microbiologic particle counts Counts taken during periods of normal work activity (during surgery) Counts taken a locations where air approaches the site of actual work (incision, instrument tables, etc.)
Reliability to be achieved through repetitive sampling
Minimum sampling 30 cubic feet of air
Record temperature, humidity, ACH, delta P
Class 1 Microbiologic Cleanliness: 1 particle per cubic foot
Catching and counting microbes
Real time tests –
13 tests
–
2 hospitals
–
8 surgeries
–
5 surgeries were total knee replacements
–
Meets all requirements of definition
–
Class 1 Microbiologic Cleanliness inside the curtain, Class 5 outside
There is only one air curtain systems on the market based on designs tested during actual surgery
What should you do?
Ask facility what level of microbiologic clean air they want Use laminar arrays when they count – –
Don’t apply blindly without recognizing the limitations Keep the big picture in mind
Use air curtain systems when they count – – – –
Large OR’s or high ACH Invasive or critical surgery Other mechanical equipment placement important Don’t apply blindly without recognizing limitations
“sensible, safe, efficient and economical design” Harold Laufman CORE Chairman 1972-1979
Summary • The path to clean OR air has not always been clear • Early pioneering efforts did not provide complete solutions • Assumptions not based on microbe counts have proven wrong • There is such a thing as a harmful approach • There are solutions based on counting microbes • Air distribution must be part of a complete approach • As surgery advances, we must advance with it • Not all manufacturers may be qualified
Cleanroom Product Overview
Cleanroom Overview Market Characteristics - Size: $200M Worldwide – NA $50M - A few companies competing for the larger jobs - Focus on traditional HEPA/ULPA products
Trends - Regulations: ISO, SEMI, IEST, UL, CE, FM - NanoTechnology will be the next driver in the US market. - New greenfield projects are down in US. Retrofit projects are more common.
North America Cleanroom Market Fan Filter Unit = $20 M
Other = $5 M
10% 40%
MiniEnv. = $5 M
10%
40%
Terminal Filter = $20 M
Technology Overview
HEPA Filters: How They Work Dirty Air
Pre-Filter
Straining
HEPA Filter
Clean Air
Impingement
Interception
Diffusion
Brownian Effect
Laminar Flow in Cleanrooms What is Laminar Flow? • Laminar Flow is usually HEPA filtered. Laminar flow removes particles and creates a clean zone. It does this by maintaining a minimum velocity.
Central Air System SUPPLY AIR AIR DUCTS TO EACH FILTER
RETURN AIR AHU TERMINAL FILTER RETURN AIR
CEILING GRID HEPA/ULPA FILTER CLEANROOM CLASSIFICATIONS ENGLISH SI 1 M1.5 10 M2.5 100 M3.5 1000 M4.5 M5.5 10,000
LAMINAR AIR FLOW
HOLLOW RETURN WALL PERFORATED RAISED FLOOR
Pressurized Plenum AHU
SUPPLY AIR
POSITIVE PRESSURE PLENUM (RELATIVE TO ROOM)
HEPA/ULPA PANEL FILTER RETURN AIR
CEILING GRID WALL CLEANROOM CLASSIFICATIONS ENGLISH SI 1 M1.5 10 M2.5 100 M3.5 1000 M4.5 10,000 M5.5
LAMINAR AIR FLOW PERFORATED RAISED FLOOR
Fan Filter Unit System SUPPLY AIR
NEGATIVE PRESSURE PLENUM (RELATIVE TO ROOM)
AHU
FAN FILTER UNIT (MAC 10) RETURN AIR
HEPA/ULPA FILTER CLEANROOM CLASSIFICATIONS ENGLISH SI 1 M1.5 10 M2.5 100 M3.5 1000 M4.5 10,000 M5.5
LAMINAR AIR FLOW
HOLLOW RETURN WALL PERFORATED RAISED FLOOR
Fan Filter Units Standard Features • Low sound, low watts, low profile • Solid State or Digital Speed Control • Snap-in prefilter; no tools required • Walkable plenum • UL Listed and CE marked • Various sizes and voltages available • Exceeds latest ISO 14644
Options • Room-Side Replaceable (ARS) • ULPA Filter • Airflow Indicator Light • A/C Collar (10 & 12 in dia.) • Painted or Stainless Steel Exterior • Power Cord • Challenge and Test Port • Knife Edge • Custom-Sizes Available
Data Comparison
PSC motor ECM motor
Unit Motor Average Watts @ DBA Size HP Airflow 90 FPM Sound 24x24 1/5 325 150 48 24x48 24x24
1/5 1/3
650 325
190 80
50 46
24x48
1/3
650
105
48
FFU System Summary • Fan Filter units offer the most cost effective method of supplying Clean Room Air quantities, with the lowest maintenance and energy costs. • These include moth PSC and ECM constant flow rate motor driven units. • Available Smart Control Systems provide both setpoint control and monitoring of system performance • Cost savings from optimized performance and reduced down-time offset the investment in upgraded control systems.
Specialty Air System Summary • Hospitals can provide a safer Operating Room environment with air curtain air delivery systems than with “laminar” systems. • Laboratories with Fume Hoods require special air delivery systems to ensure that supply air doesn’t cause outflow from the hood opening. • Fan Filter units offer the most cost effective method of supplying Clean Room Air quantities, with the lowest maintenance and energy costs.
View more...
Comments