AC Load Flow Analysis

July 27, 2018 | Author: Sorin Chirila | Category: Electrical Impedance, Ac Power, Electrical Engineering, Electricity, Electromagnetism
Share Embed Donate


Short Description

Download AC Load Flow Analysis...

Description

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

1.0

Scope of a Load Flow Analysis A Load Flow analysis is used to evaluate the running steady-state condition of a system, under different load, supply and configuration conditions.  The idea behind the load flow algorithm is to determine the following parameters, given that the load consumption at all busses is known: a. b. c. d.

Power flow in each branch (Lines & Transformers). Power consumption at each source of generation. Voltage magnitude and electrical angle at each bus. System Losses.

Once this data is known, corrective actions can be taken in order to ensure that every load is supplied with power that is within the acceptable limits of operation.  Such actions can include the calculation of: a. b. c. d.

Transformer tap settings. Reactive power compensation. Generator set points. Emergency power requirements.

A properly built load flow model of the system, lays a solid foundation for other important studies such as short circuit, motor starting, harmonic and transient stability.  The load flow model constitutes the basic network information and the initial steady-state condition which these studies rely upon.

2.0

Load Models Loads in general can be modeled in 4 different ways: a. b. c. d.

Constant Power Load (kVA) Constant Current (Amps) Constant Impedance (Ohms) Functional Load

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.1 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

2.1   Constant Power Load (kVA) This type of load is treated as constant demand of power.   The load flow algorithm will attempt convergence under the premise that these types of loads always draw the kVA specified by the user. Caution should be exercised when interpreting the convergence results in the presence constant kVA  loads. To illustrate this, let’s assume that a given load is rated 1.2kVA at 120 Volts; let’s further assume that the system experiences excessive losses (say 20% voltage drop on the load’s supply branch). Under these circumstances the only way in which the system can sustain the load at the prescribed kVA  is by supplying more current in order to compensate for the voltage drop.  More current means more voltage drop and this cycle will lead to a non-convergence situation.  The analysis is basically telling us that the system, as it has been designed, cannot supply 1.2 kVA to the load due to excessive losses.  At this point one can switch the definition of the load from constant load to constant impedance and determine exactly how much power can be transferred to the load.  This issue will be illustrated with an example in further sections of this manual.

2.2   Constant Current Load (Amps) The load (P+jQ) is treated as constant current load. The current is calculated by using the following equation:

I=

P Q V I

= = = =

P − jQ V∗

Load Active Power (kW) Load Reactive Power (kVAR) Load Rated Voltage Load equivalent constant current

How does this work?  When a load of rated “P” (kW), “Q” (kVAR) and “V” (Voltage) is entered, the program calculates the equivalent current “I” and defines the load as a constant draw of “I” (Amps).

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.2 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

2.1   Constant Power Load (kVA) This type of load is treated as constant demand of power.   The load flow algorithm will attempt convergence under the premise that these types of loads always draw the kVA specified by the user. Caution should be exercised when interpreting the convergence results in the presence constant kVA  loads. To illustrate this, let’s assume that a given load is rated 1.2kVA at 120 Volts; let’s further assume that the system experiences excessive losses (say 20% voltage drop on the load’s supply branch). Under these circumstances the only way in which the system can sustain the load at the prescribed kVA  is by supplying more current in order to compensate for the voltage drop.  More current means more voltage drop and this cycle will lead to a non-convergence situation.  The analysis is basically telling us that the system, as it has been designed, cannot supply 1.2 kVA to the load due to excessive losses.  At this point one can switch the definition of the load from constant load to constant impedance and determine exactly how much power can be transferred to the load.  This issue will be illustrated with an example in further sections of this manual.

2.2   Constant Current Load (Amps) The load (P+jQ) is treated as constant current load. The current is calculated by using the following equation:

I=

P Q V I

= = = =

P − jQ V∗

Load Active Power (kW) Load Reactive Power (kVAR) Load Rated Voltage Load equivalent constant current

How does this work?  When a load of rated “P” (kW), “Q” (kVAR) and “V” (Voltage) is entered, the program calculates the equivalent current “I” and defines the load as a constant draw of “I” (Amps).

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.2 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

2.3   Constant Impedance Load (Ohms) The load (P+jQ) is treated as constant impedance load. The impedance is calculated by using the following equation:

Z P Q V Z

= = = =

=

V2 P − jQ

Load Active Power (kW) Load Reactive Power (kVAR) Load Rated Voltage Load equivalent constant Impedance

How does this work?  When a load of a rated “P” (kW), “Q” (kVAR) and “V” (Voltage) is entered, the program calculates the equivalent impedance “Z” and defines the load as a constant shunt impedance of “Z” (Ohms).

2.4   Functional Load A functional load is a load that is composed of any combination of constant load, constant current, and/or constant impedance.  For example, in a single phase system, the total load at 120 Volts may be (12 kW+j0 kVAR) broken down as follows: 30% as constant power load: 3.6 kW – 3.6 kW 60% as constant current:   7.2 kW – 60.0 Amps 10% as constant impedance:   1.2 kW – 12.0 ohms

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.3 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

3.0

Generator Models The Load Flow study algorithm, specifies each bus based on; Active/Reactive power consumption (Load or PQ Bus), Voltage magnitude (Generation or PV Bus), and Voltage reference (Swing Bus).   Supply busses that contain synchronous generators may also be specified as PQ busses depending on application, or re-designation from PV busses if the prescribed limits of reactive power generation are reached during the Load Flow Analysis. The Swing bus is the only bus at which the power is not specified.  Net power flows cannot be fixed in advance at every generating bus, since the network power losses are not known until the study has been completed.   The Swing bus is therefore defined based solely on voltage and angle, leaving the rest of the variables (kW & kVAR, including system losses) free to adjust (SWING) to the requirements of the network.   In other words, Active and Reactive Power are the unknown variables of the Swing bus. In light of the above, a Load Flow Analysis is not mathematically feasible (by computer, by hand, or otherwise) without the presence of a Swing bus or busses in the network.  The Swing bus designation is bestowed upon the stiffest busses in the network, traditionally Power Company or Utility busses. The table below summarizes the critical variables for each type of bus:

Bus Type Swing Load PQ Generator PV Generator

Know own n Variables V = 1.0 PU δ = 0 deg P&Q P&Q P&V

Unkno now wn Varia iab bles P&Q V &  δ V &  δ Q &  δ

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.4 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

4.0

Conducting a Balanced Load Flow Analysis (File: EDM7.axd)

Step 1. Proceed to open the file EDM7.axd” 

Step 2. Run a Load Flow Connectivity Error Check”, and correct any problems as required.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.5 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

Generator

Utility Supply

Switch Position Table BKR-1 BKR-2

1. Co-Gen. Closed Closed

Scenario Name 2. Normal Closed Open

3. Emergency Open Closed

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.6 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

Generator Model

Generator Full Rating in kVA.

Generator Type.

Generator Load Flow set-points.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.7 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

Utility Model

Calculated SC Impedance values.

Short Circuit Levels.

When X” is selected, the positive sequence SC impedance, is included in the Load Flow model for the Swing bus. This allows the program to calculate the voltage drop at th e “non-ideal” Swing-Bus.

The positive sequence impedance is passed onto the Load Flow model.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.8 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

4.1

Running the Load Flow & the Load Flow Options Screen

Step 1. Invoke the Load Flow program by selecting either of these commands. Step 2. Select the scenario to be analyzed. Step 3. Select the calculation method. Step 4. Verify the “Scenario” to be studied (Normal).

Refer to steps 6a & 6b in the next page.

Step 5. Select the rest of the options.

Step 6. Select “OK”. Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.9 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

Step 6a. Fine-tune the advanced options as needed.

Step 7. Here the program is letting the user know that there is a dead island caused by the “Normal” scenario configuration. This scenario calls for BKR-2 to be opened, which isolates the generator from the system.  Select “Yes” to initiate the analysis.

Step 6b. Select “OK”.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.10 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

4.2

Viewing the Load Flow Analysis Results Step 1. Verify that the analysis has converged.

Step 2. To view the results, select the desired output format from the “Results” menu. Select “TD LoadFlow Format 1” 

Step 3. Select the desired report sections and options to be displayed.

Step 4. Select “OK”.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.11 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

Partial view of the output results for scenario 2 “Normal Power”.

Exercise

Using the same procedure explained in this section, conduct load  flow analyses for the cases 1 & 3 (Co-Gen, and Emergency). Compare the results of the 3 scenarios. Do the results make sense? Why? 

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.12 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

4.3

Convergence & Constant kVA Loads (File EDM8.axd)

Step 1. Open the file named “EDM8.axd”.

Step 2. Model this load as a “Constant kVA” load.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.13 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

Step 3. Run the load flow analysis, and verify that in this case it does NOT converge.

Step 4. View the report.  The results, which in cases of nonconvergence ARE NOT TO BE RELIED UPON, seem to indicate that the losses are too great.  The system is not able to supply 750 kVA to the load.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.14 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

4.4

Convergence & Constant Impedance Loads (File EDM8.axd) Step 1. Open the file named “EDM8.axd”.

Step 2. Model this load as a “Constant Impedance”  load.

Step 3. Run the load flow analysis, and verify that in this case it DOES converge.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.15 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

Step 4. View the report.  The results confirm that due to the high losses in the transformer and the line, the system is only able to supply 484.5 kVA to the load.

Voltage available at the load: 385.85 Volts

Voltage drop at the load: 19.62%.

kVA =

2

2

412 + 255 = 484.5 kVA

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.16 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

4.5

Voltage Control Techniques (File EDM7.axd) The EDSA Object Oriented Load Flow analysis program can assist in correcting voltage levels by means of the any of the following techniques: -

Transformer tap settings. Static reactive power adjustment (Capacitors & Inductors). PV Generator reactive power adjustment (Exciter Control). A combination of any the above techniques.

The first step is to prepare the network as follows: -

Select the transformer(s) with adjustable taps that will be used as voltage control transformers. Select the bus or busses at which static reactive compensation is to be considered. Select the voltage control generators by defining them as PV units.  PQ generators cannot regulate voltage. Step 1. Open the file named “EDM7.axd”.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.17 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

Step 2. Define the settings for all the potential voltage control means desired.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.18 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

Step 3. Following the guidelines explained in previous sections of this manual, run a Load Flow Analysis using scenario No.1 (Co-Generation).

Step 4. Produce a report that includes the “Bus Voltage” results and a voltage violation summary for all busses outside a ±10% voltage tolerance. The screen-capture shown here is a partial view of the report showing the voltage violation report

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.19 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

4.5.1 Voltage Control / Transformer Taps

Step 1. Select “Voltage Control”.

Step 2. Complete the “Voltage Control Limits” section as indicated here.

Step 3. Select “Transformer Tap Adjustments” as a means of  control.  Press “OK”.

Step 4. Select “OK”.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.20 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

Step 5. Review the results and select “Done” to exit.

Step 6. Select “No’ for now.  This option will be explained later.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.21 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

4.5.2 Voltage Control / Capacitors-Inductors

Step 1. Select “Voltage Control”.

Step 2. Complete the “Voltage Control Limits” section as indicated here.

Step 3. Select “Capacitor/Inductor...”  as a means of control.  Press “OK” 

Step 4. Select “OK”.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.22 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

Required amount of reactive compensation, in per unit of base kVA.  To obtain actual kVA, multiply by the base kVA (10,000 kVA). Step 5. Review the results and select “Done” to exit.

Step 6. Select “No’ for now.  This option will be explained later.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.23 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

4.5.3 Voltage Control / Transformer Taps & Generator Settings

Step 1. Select “Voltage Control”.

Step 2. Complete the “Voltage Control Limits” section as indicated here.

Step 3. Select “Transformer…” and “Generator…”  as combined means of control.  Press “OK” 

Step 4. Select “OK”.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.24 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

Required amount of additional generator reactive compensation, in per unit of base kVA.  To obtain actual kVA, multiply by the base kVA (10,000 kVA). Step 5. Review the results and select “Done” to exit.

Step 6. Select “Yes’ to test the results. Step 7. Select OK to acknowledge.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.25 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

Step 8. Select “Yes” and verify convergence.

Step 9. The solution proves to be effective as indicated here.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.26 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

Step 10. Select “Exit”.

Step 11. Select “Yes”.

Step 12. Save the file under a different name, if you wish to avoid overwriting the original one.  Press “Save”.

Exercise

Conduct a volt  age control analysis for case 1 ( Co-Generation), using ONLY Generator Reactive Power control as means of  correcting the voltage drops in the network.  Use ±7% as the  acceptable tolerance.  Is the calculation successful? Why? 

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.27 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

4.6

Load Flow Transformer Sizing (File EDM7.axd) Step 1. Run a Load Flow analysis on the subject file.

Step 2. Select “Xfr Sizing”.

Step 3. Enter the “Design Margin” in %, and select “OK”.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.28 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

4.7

Back Annotation of Load Flow Results (File EDM7.axd)

Step 2. Select “ON”. Step 1. Click here to select the “Back Annotation” tool.

Step 3. Select the desired components from the “AC Load Flow” section.

Step 4. Select “OK”.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.29 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

Load Flow back  annotation.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.30 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

5.0

Unbalanced Load Flow Analysis (File EDM9.axd)

Step 1. Proceed to open the file “EDM9.axd” 

Note: These three static loads will be entered as unbalanced loads.

Step 2. Run a Load Flow Connectivity Error Check”, and correct any problems as required.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.31 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

5.1

Preparing the Master File Editor

Step 1. Click here to invoke the “Master File Editor”.

Step 2. Select the “Visibility” tab.

The steps described in this section, will enable the “Unbalanced Load Flow” tab at every load in the single line diagram.  The user can enter, as required, the percentile distribution of the load across the phases. These % figures are based on the full load condition entered in the “Load Flow” tab. The initial default assumed by the program is a balanced state as indicated here.

Step 4. Select “OK”.

Step 3. Check the “View Unbalanced Load Flow Fields” option.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.32 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

5.2

Preparing the Unbalanced Loads Step 1. Double click on each of the static loads fed from bus J#1066, and edit the Unbalanced Load Flow conditions as indicated in steps 2 & 3.

Step 2. Select the “Unbalanced Load Flow” tab.

Step 3. Enter a per-phase distribution as indicated here. Assume the same percentile values for all three static loads.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.33 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

5.3

The Unbalanced Load Flow Analysis Interface Step 2. Select “Run”.

Step 1. Select “AC 3-Phase Unbalanced”.

Step 3. Select “Continue”.

Step 4. Select the desired options and press “OK”. Step 5. Allow the program to adjust the tolerance by selecting “Yes”.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.34 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

Step 6. Verify that the calculation has converged and select “View Results”.

Partial view of the final report.  To exit select “Done” 

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.35 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

6.0

Load Flow Analysis Voltage / Profile Method (File EDM10.axd)

Step 1. Proceed to open the file “EDM10.axd” 

Note: These four loads will be entered as cycling loads.

Step 2. Run a Load Flow Connectivity Error Check”, and correct any problems as required.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.36 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

6.1

Preparing the Master File Editor Step 1. Click here to invoke the “Master File Editor”.

Step 2. Select the “Visibility” tab. Step 3. Check the “View Voltage Profile Fields” option.

Step 4. Select the “Time Periods” tab.

Step 5. Define the “Load-Cycling”  time periods.  Select “OK”.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.37 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

6.2

Preparing the Cycling Loads Step 1. Double click on each of the loads fed from bus J#1066, and edit the cycling conditions as indicated in this page.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.38 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

6.3

The Voltage Profile Load Flow Interface Step 2. Select “Run”.

Step 3. Define the “Load Flow Options”, and select “OK”.

Step 1. Select “AC Voltage Profile”.

Step 4. Verify convergence for all periods, and select “Done”.

Step 5. To view the results, select “Results”.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.39 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

6.4

Graphical View of the Results

Step 3. Select “OK”  to return.

Step 1. Select the bus to view, by clicking on it once.

Step 2. View and edit the graphs. When done press “Exit”.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.40 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

7.0

Single Phase Load Flow Analysis / Building the Job-File Step 2. Select Electrical One Line Single-Phase.axd”, and press “OK”.

Step 1. Click here to create a new job-file.

Step 3. Name the file, and select “Open”.

Step 4. De-select the password requirement, and press “OK”.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.41 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

Single-Phase Element catalog. This catalog contains both, singlephase busses and branches.

Master Job-File Editor settings.

Step 5. Following the same guidelines outlined in the “Main User Interface” section of this manual, proceed to build the required single-phase network.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.42 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

7.1

Conducting a Single-Phase Load Flow Analysis (File: EDM6.axd)

Step 2. Run a load-flow connectivity error check.

Step 3. Invoke the AC Load-Flow Analysis program.

Step 1. Proceed to open the single-phase file named “EDM6.axd”.

Exercise

Step 3. The AC Load Flow Analysis program is designed to analyze both single and three-phase systems.  To continue, simply repeat the same steps explained in section 4.0 of this manual.

Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.43 ©2002 EDSA Micro Corp. / PQ Logic Corp.

EDSA T2K Design Master AC Load Flow Analysis

`~å~Ç~=

8.0

Practical Exercise (File: EDM7X.axd) Power Factor Correction Capacitor Bank.

Using the File “EDM7X.axd”, shown in the  above picture, complete the following questionnaire: 1.

Total Power in kVA demanded from the utility supply:

2.

Power Factor at the Utility Bus:

3.

Total System Losses on kW:

4.

Voltage Drop at 480 V Bus J#1066:

5.

List the transformers loaded beyond 100% of their capacity:    

   

     

   

   

 

 

           

 

 

 

 

 

   

 

   

 

______________kVA   

   

_______________%  

 

______________kW _______________%

F:______               T:_____   

F:______          T:______  Notes: …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. …………………………………………………………………………………………………………………………………………………………………. Page LF.44 ©2002 EDSA Micro Corp. / PQ Logic Corp.

View more...

Comments

Copyright ©2017 KUPDF Inc.
SUPPORT KUPDF