LV AC CABLE SIZING CALCULATION
رباء
D ' T R E C D ' P P A D ' K E H C
رباء
Saudi Electricity Company A . H K
A . H K
INDEX SHEET NO. 9 0 . 2 1 . 7 0 D E T A D 3 4 3 0 3 0 4 9 2 0 5 9 0 # R E T T E L N I
N O I T P I R C S E D
L A V O R P P A R O F D E U S S I
Y B
S . A
S . A
E T A D
9 0 . 0 1 . 9 1
9 0 . 2 1 . 3 1
. O N
0
1
2 03 04-0 04-05 5 06-1 06-17 7
Attachment-1
S T N E M M O C C E S R E P S A D E S I V E R
DESIGNED
DATE:-
A.S
13.12.09 CHECKED
BY:-
A.R/KH.A
DATE:-
13.12.09
Index Reference Documents / De Design basis Sizi Sizing ng cal calcu cula lati tion on of of ACDB ACDB Inc Incom omer er cab cable less Sizi Sizing ng cal calcu cula lati tion on of of auxi auxili liar ary y AC cab cable less Attachments Attachments List
REVISIONS BY:-
CONTENT
OPRG. DEPT BY DATE:-
ENG'G. DEPT. BY:DATE:-
CERTIFIED. BY:-
AS BUILT
RIYADH Cable Co. Cataloug
D ' T R E C D ' P P A D ' K E H C
رباء
Saudi Electricity Company A . H K
A . H K
INDEX SHEET NO. 9 0 . 2 1 . 7 0 D E T A D 3 4 3 0 3 0 4 9 2 0 5 9 0 # R E T T E L N I
N O I T P I R C S E D
L A V O R P P A R O F D E U S S I
Y B
S . A
S . A
E T A D
9 0 . 0 1 . 9 1
9 0 . 2 1 . 3 1
. O N
0
1
2 03 04-0 04-05 5 06-1 06-17 7
Attachment-1
S T N E M M O C C E S R E P S A D E S I V E R
DESIGNED
DATE:-
A.S
13.12.09 CHECKED
BY:-
A.R/KH.A
DATE:-
13.12.09
Index Reference Documents / De Design basis Sizi Sizing ng cal calcu cula lati tion on of of ACDB ACDB Inc Incom omer er cab cable less Sizi Sizing ng cal calcu cula lati tion on of of auxi auxili liar ary y AC cab cable less Attachments Attachments List
REVISIONS BY:-
CONTENT
OPRG. DEPT BY DATE:-
ENG'G. DEPT. BY:DATE:-
CERTIFIED. BY:-
AS BUILT
RIYADH Cable Co. Cataloug
D ' T R E C D ' P P A D ' K E H C
N O I T P I R C S E D
Saudi Electricity Company A . H K
L A V O R P P A R O F D E U S S I
A . H K
Y B
S . A
S . A
E T A D
9 0 . 0 1 . 9 1
9 0 . 2 1 . 3 1
. O N
0
1
REVISIONS DESIGNED BY:DATE:-
A.S
13.12.09 CHECKED
BY:-
A.R/KH.A
DATE:-
13.12.09 OPRG. DEPT
BY DATE:-
ENG'G. DEPT. BY:DATE:-
CERTIFIED. BY:-
Reference Documents :
1 Transmission Engineering Engineering Standard Standard – TES-P-104.03: TES-P-104.03: Cable Sizing & Selection 2 Transmission Engineering Standard – TES-P-119.29: TES-P-119.29: LV Cable Cable Selection & Sizing(600 Sizing(600 3 Transmission Material Standard Standard Specification 11-TMSS-10: 11-TMSS-10: Power and/or AL. Conducto 4 Dwg. No. CA-113554 – One Line Diagram - 220/127V AC 5 Doc. No. CE-113342 – AC Load Schedule & Aux. TR. Sizing Calculation Calculation 6 Dwg. No. CA-113549– Substation Overall Overall layout -Plan 7 Scope of Work and Technical Specification - PTS # 08CN300 attachment-1) 8 RIYADH Cable Co. Catalouge ( attachment-1)
9 0 . 2 1 . 7 0 D E T A D 3 4 3 0 3 0 4 9 2 0 5 9 0 # R E T T E L N I
S T N E M M O C C E S R E P S A D E S I V E R
هرباء
Note :-
All 0.6/1kV Cable Data are referred from RIYADH Cable Co. Catalogues (for calculation purpose)
Design Basis:-
1
2
The follow following ing type type of of cabl cables es are consid consider ered: ed: a) Power cables – 0.6/1kV, Cu., XLPE insulated, LMDPE sheathed for 630Sqmm cable. b) Power cables – 0.6/1kV, Cu., XLPE insulated, PVC ST 2 sheathed for other cables The follow following ing are are the the limits limits of volta voltage ge drop drop consid considered ered for design: design: AC Circuits:-
a) Auxiliary Transformer to ACDB
0.8
b) ACDB to Indoor Lighting panel (ILP) Lighting Panel (ILP) to Indoor lighting circuits
1.6 2.6
c) ACDB to Outdoor Lighting Panel (LP-OD) Lighting panel (LP-OD) to Outdoor lighting
1.6 2.6
d) ACDB to SDB SDB to SDB various loads
1.6 2.6
e) ACDB to Battery charger, Oil filtration sockets, etc…
4.2
شرة سعودية لك
شرة سعودية لك
لك سعودية ةشر
& Below) ,600 /1000V rating
% % % % % % % %
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
ه ر ب ء
Saudi Electricity Company
س ع و د ي
طىو
Central Operating Area LV AC CABLE SIZING CALCULATION
Incomer cable sizing from Aux. Trafo to ACDB ( Q101, Q10
Cable From Cable To System Voltage (V) Connected Load (S) Current through the feeder
: : = = = =
ACDB 220 ### S/√3x 5249
Current considered for design (I)
=
5249
Cable size selected and
No. of runs (N) Underated current carrying capacity of the cable (I c)
2000KVA
6x 1C x 3x 1C x = 6 = 1117
Derating Factors
Type of Cable laying a) K 1 - Air Rating factor at 40˚C b) K 2 - Group rating factor
: = =
Trefoil touching in cable trench 0.91 (As Per Riyadh cable Co. catalouge t 0.87 (As per TES-P-119.29 Cl. 7.1.7.a.i)
Net derating Factor (K)
=
0.79
Derated current carrying capacity of the cable
= =
K x Ic x 5306
The derated current carrying capacity of the cable is higher than the m
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
Saudi Electricity Company
ه ر ب ء
س ع و د ي
طىو
Central Operating Area
Calculation of Voltage Drop
Unit AC resistance of the cable @ 90 oC (R) Unit reactance of the cable (X) Total route length of the cable (L) Net Resistance of the cable (R l = L x R / N x 1000) Net Reactance of the cable (X l = L x X / N x 1000) Load Power Factor - cos φ sin φ Total Voltage drop (V d) % Voltage drop
Permissible Voltage drop
= 0.04 = 0.09 = 13.5 = 0.0001 = 0.0002 = 0.85 = 0.53 = √3xIx = 1.71 = Vd x 100 =
0.78
=
0.8
The actual voltage drop is lesser than the permissible voltage drop -->
Check for Short circuit withstand capacity of the cable
The conductor size is checked for short circuit with the following formulae: Isc =143 x S / √ t , where t = Duration of Short circuit = 1 S = Cross sectional area of the cable = 630 Substituting in the above equation, we get Isc = 90090 = 90 Rated fault withstanding current at the Tranformer = 80.325 Short circuit current withstand capacity of the cable is higher than that
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
Saudi Electricity Company Central Operating Area
From 1,2 & 3 the design is safe.
ه ر ب ء
س ع و د ي
طىو
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
مانطقة أ ,Q103 )
AUX. TR
V VA A A
630 mm2 Cu./ Phase 630 mm2 Cu./ Neutral A
ble 10)
A ximum feeder current --
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
مانطقة أ
Ω / km Ω / km
m Ω Ω
31.79
Rl cos φ + Xl sin φ ] V /V % %
second mm2 A
KA, for one second KA at the Tranformer -->3
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
مانطقة أ
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
Saudi Electricity Company Central Operating Area
LV AC CABLE SIZING CALCULATION VOLTAGE DROP LIMIT ACDB TO VARIUOS LOADS ACDB TO OLP/ILP ACDB TO SDB SDB TO VARIOUS LOADS
S.No.
From
To
4.2 1.6 1.6 2.6
% % % %
KW
Phase
Derating Factors: k1 = Variation in air temperature -Indoor: 40 °C k1 = Variation in air temperature -Outdoor: 50 °C k2 = Group rating factor
%VD = (Voltage Drop / S VOLTAGE DROP (3Ph) VOLTAGE DROP (1Ph) I = Current in Amp. L = Route length in met
Cables are laid on racks System Voltage =
VOLT
Amp
No. of cables per ph.
I req. Amp
Type
Core
mm²
Amp
I
PF
220 / 127 VAC Selected Cable
DERATING FACTORS Over K1 K2 All
derated current Amp
C.B current Amp
PANEL : MAIN DISTRIBUTION BOARD BUS-A 220/127V AC 1
ACDB BUS-A INDOOR LIGHTING PANEL -1( LOC -CONTROL ROOM)
134.190
3
220
0.85
414.3
2
207.1
XLPE
4C
150
407
0.91
0.7
0.64
259.26
500
2
ACDB BUS-A INDOOR LIGHTING PANEL -2( LOC -AC/DC ROOM)
130.770
3
220
0.85
403.7
2
201.9
XLPE
4C
120
355
0.91
0.7
0.64
226.14
500
3
ACDB BUS-A OUTDOOR LIGHTING PANEL-2 (LOC -380KV GIS ROOM)
117.90
3
220
0.85
364.0
2
182.0
XLPE
1C
630
1117
0.91
0.7
0.64
711.53
500
4
ACDB BUS-A OUTDOOR LIGHTING PANEL -3( LOC -132KV GIS ROOM)
66.06
3
220
0.85
204.0
2
102.0
XLPE
4C
240
551
0.91
0.7
0.64
350.99
320
5
ACDB BUS-A 300A OIL FILTERATION SOCKET (REACTOR AREA-1)
77.74
3
220
0.85
240.0
1
240.0
XLPE
4C
185
469
0.91
0.7
0.64
298.75
320
6
ACDB BUS-A SDB-1A (LOC -380KV GIS BLD)
80.75
3
220
0.85
249.3
2
124.7
XLPE
4C
150
407
0.91
0.7
0.64
259.26
320
7
ACDB BUS-A SDB-2 (LOC -132KV GIS BLD)
56.087
3
220
0.85
173.2
2
86.6
XLPE
4C
240
551
0.91
0.7
0.64
350.99
320
8
ACDB BUS-A PORTABLE 125V DC BATTERY CHARGER (380KV DC SYSTEM BATTERY CHARGER)
62.50
3
220
0.85
193.0
1
193.0
XLPE
4C
120
355
0.91
0.7
0.64
226.14
250
9
ACDB BUS-A SDB-1B (LOC -380KV GIS BLD)
43.977
3
220
0.85
135.8
2
67.9
XLPE
4C
185
469
0.91
0.7
0.64
298.75
200
10
ACDB BUS-A INDOOR LIGHTING PANEL -5( LOC -132KV GIS ROOM)
50.360
3
220
0.85
155.5
2
77.7
XLPE
4C
185
469
0.91
0.7
0.64
298.75
200
11
ACDB BUS-A TELECOM ROOM ACDB
31.095
3
220
0.85
96.0
1
96.0
XLPE
4C
35
160
0.91
0.7
0.64
101.92
125
12
ACDB BUS-A PORTABLE 125V DC BATTERY CHARGER (132KV DC SYSTEM BATTERY CHARGER)
31.250
3
220
0.85
96.48
1
96.5
XLPE
4C
35
160
0.91
0.7
0.64
101.92
125
13
ACDB BUS-A SGT-1 FANS GROUP-1
17.879
3
220
0.85
55.2
1
55.2
XLPE
4C
25
130
0.82
0.7
0.57
74.62
100
14
ACDB BUS-A SGT-1 FANS GROUP-2
17.879
3
220
0.85
55.2
1
55.2
XLPE
4C
25
130
0.82
0.7
0.57
74.62
100
15
ACDB BUS-A SGT-3 FANS GROUP-1
17.879
3
220
0.85
55.2
1
55.2
XLPE
4C
25
130
0.82
0.7
0.57
74.62
100
CE-113347, REV.01
13 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
Saudi Electricity Company Central Operating Area
LV AC CABLE SIZING CALCULATION VOLTAGE DROP LIMIT ACDB TO VARIUOS LOADS ACDB TO OLP/ILP ACDB TO SDB SDB TO VARIOUS LOADS
S.No.
From
To
4.2 1.6 1.6 2.6
% % % %
KW
Phase
Derating Factors: k1 = Variation in air temperature -Indoor: 40 °C k1 = Variation in air temperature -Outdoor: 50 °C k2 = Group rating factor
%VD = (Voltage Drop / S VOLTAGE DROP (3Ph) VOLTAGE DROP (1Ph) I = Current in Amp. L = Route length in met
Cables are laid on racks System Voltage =
VOLT
PF
220 / 127 VAC
Amp
No. of cables per ph.
I req. Amp
Type
Core
mm²
Amp
I
Selected Cable
DERATI NG FACTORS Over K1 K2 All
derated current Amp
C.B current Amp
16
ACDB BUS-A SGT-3 FANS GROUP-2
17.879
3
220
0.85
55.2
1
55.2
XLPE
4C
25
130
0.82
0.7
0.57
74.62
100
17
ACDB BUS-A SGT-5 FANS GROUP-1
17.879
3
220
0.85
55.2
1
55.2
XLPE
4C
50
195
0.82
0.7
0.57
111.93
100
18
ACDB BUS-A SGT-5 FANS GROUP-2
17.879
3
220
0.85
55.2
1
55.2
XLPE
4C
50
195
0.82
0.7
0.57
111.93
100
19
ACDB BUS-A 100A WELDING RECEPTACLE AT HVAC PACU-1
25.91
3
220
0.85
80.0
1
80.0
XLPE
4C
70
247
0.82
0.7
0.57
141.78
100
20
ACDB BUS-A 48V DC BATTERY CHARGER-1
8.50
3
220
0.85
26.2
1
26.2
XLPE
4C
10
73
0.91
0.45
0.41
29.89
63
21
ACDB BUS-A HVAC CONTROL PANEL
15.00
3
220
0.85
46.3
1
46.3
XLPE
4C
16
96
0.91
0.7
0.64
61.15
63
22
ACDB BUS-A LIGHTING & SOCKETS,ONLINE GAS ANALYSER REACTOR-1
0.425
3
220
0.85
1.3
1
1.3
XLPE
4C
10
73
0.82
0.45
0.37
26.94
32
23
ACDB BUS-A LIGHTING & SOCKETS,ONLINE GAS ANALYSER REACTOR-2
0.425
3
220
0.85
1.3
1
1.3
XLPE
4C
10
73
0.82
0.45
0.37
26.94
32
24
ACDB BUS-A SGT-1 MK ( Lamp , Heater , Thermostat , Moisture-In-Oil Monitor & Receptacle)
3.732
1
220
0.85
20.0
1
20.0
XLPE
4C
10
73
0.82
0.45
0.37
26.94
32
25
ACDB BUS-A SGT-1 PIT PUMP
2.983
3
220
0.85
9.2
1
9.2
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
26
ACDB BUS-A SGT-2 PIT PUMP
2.983
3
220
0.85
9.2
1
9.2
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
27
ACDB BUS-A SGT-5 PIT PUMP
2.983
3
220
0.85
9.2
1
9.2
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
28
ACDB BUS-A SUMP PUMP CONTROL BLD BASEMENT
1.800
3
220
0.85
5.6
1
5.6
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
29
SUMP PUMP TUNNEL-A1 ACDB BUS A (380KV CONTROL CABLES TUNNEL)
3 60
3
220
08
11 1
1
11 1
XLPE
4C
10
3
0 82
04
03
26 94
20
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
Saudi Electricity Company Central Operating Area
LV AC CABLE SIZING CALCULATION VOLTAGE DROP LIMIT ACDB TO VARIUOS LOADS ACDB TO OLP/ILP ACDB TO SDB SDB TO VARIOUS LOADS
S.No.
From
To
4.2 1.6 1.6 2.6
% % % %
KW
Phase
Derating Factors: k1 = Variation in air temperature -Indoor: 40 °C k1 = Variation in air temperature -Outdoor: 50 °C k2 = Group rating factor
%VD = (Voltage Drop / S VOLTAGE DROP (3Ph) VOLTAGE DROP (1Ph) I = Current in Amp. L = Route length in met
Cables are laid on racks System Voltage =
VOLT
220 / 127 VAC
Amp
No. of cables per ph.
I req. Amp
Type
Core
mm²
Amp
I
PF
Selected Cable
DERATI NG FACTORS Over K1 K2 All
derated current Amp
C.B current Amp
16
ACDB BUS-A SGT-3 FANS GROUP-2
17.879
3
220
0.85
55.2
1
55.2
XLPE
4C
25
130
0.82
0.7
0.57
74.62
100
17
ACDB BUS-A SGT-5 FANS GROUP-1
17.879
3
220
0.85
55.2
1
55.2
XLPE
4C
50
195
0.82
0.7
0.57
111.93
100
18
ACDB BUS-A SGT-5 FANS GROUP-2
17.879
3
220
0.85
55.2
1
55.2
XLPE
4C
50
195
0.82
0.7
0.57
111.93
100
19
ACDB BUS-A 100A WELDING RECEPTACLE AT HVAC PACU-1
25.91
3
220
0.85
80.0
1
80.0
XLPE
4C
70
247
0.82
0.7
0.57
141.78
100
20
ACDB BUS-A 48V DC BATTERY CHARGER-1
8.50
3
220
0.85
26.2
1
26.2
XLPE
4C
10
73
0.91
0.45
0.41
29.89
63
21
ACDB BUS-A HVAC CONTROL PANEL
15.00
3
220
0.85
46.3
1
46.3
XLPE
4C
16
96
0.91
0.7
0.64
61.15
63
22
ACDB BUS-A LIGHTING & SOCKETS,ONLINE GAS ANALYSER REACTOR-1
0.425
3
220
0.85
1.3
1
1.3
XLPE
4C
10
73
0.82
0.45
0.37
26.94
32
23
ACDB BUS-A LIGHTING & SOCKETS,ONLINE GAS ANALYSER REACTOR-2
0.425
3
220
0.85
1.3
1
1.3
XLPE
4C
10
73
0.82
0.45
0.37
26.94
32
24
ACDB BUS-A SGT-1 MK ( Lamp , Heater , Thermostat , Moisture-In-Oil Monitor & Receptacle)
3.732
1
220
0.85
20.0
1
20.0
XLPE
4C
10
73
0.82
0.45
0.37
26.94
32
25
ACDB BUS-A SGT-1 PIT PUMP
2.983
3
220
0.85
9.2
1
9.2
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
26
ACDB BUS-A SGT-2 PIT PUMP
2.983
3
220
0.85
9.2
1
9.2
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
27
ACDB BUS-A SGT-5 PIT PUMP
2.983
3
220
0.85
9.2
1
9.2
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
28
ACDB BUS-A SUMP PUMP CONTROL BLD BASEMENT
1.800
3
220
0.85
5.6
1
5.6
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
29
SUMP PUMP TUNNEL-A1 ACDB BUS-A (380KV CONTROL CABLES TUNNEL)
3.60
3
220
0.85
11.1
1
11.1
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
30
ACDB BUS-A REACTOR -1 PIT PUMP
2.98
3
220
0.85
9.2
1
9.2
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
31
ACDB BUS-A AUXILIARY SUPPLY FOR GT-1
2.914
3
220
0.85
9.0
1
9.0
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
PANEL : MAIN DISTRIBUTION BOARD BUS-B 220/127V AC CE-113347, REV.01
14 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
Saudi Electricity Company Central Operating Area
LV AC CABLE SIZING CALCULATION VOLTAGE DROP LIMIT ACDB TO VARIUOS LOADS ACDB TO OLP/ILP ACDB TO SDB SDB TO VARIOUS LOADS
S.No.
From
To
4.2 1.6 1.6 2.6
% % % %
KW
Phase
Derating Factors: k1 = Variation in air temperature -Indoor: 40°C k1 = Variation in air temperature -Outdoor: 50 °C k2 = Group rating factor
%VD = (Voltage Drop / S VOLTAGE DROP (3Ph) VOLTAGE DROP (1Ph) I = Current in Amp. L = Route length in met
Cables are laid on racks System Voltage =
VOLT
220 / 127 VAC
Amp
No. of cables per ph.
I req. Amp
Type
Core
mm²
I
PF
Amp
DERATING FACTORS Over K1 K2 All
derated current Amp
C.B current Amp
Selected Cable
32
ACDB BUS-B HVAC PANEL-3(LOC -132KV GIS BLD)
210.17
3
220
0.85
648.9
4
162.2
XLPE
1C
630
1117
0.91
0.7
0.64
711.53
800
33
ACDB BUS-B INDOOR LIGHTING PANEL -1( LOC -CONTROL ROOM)
134.190
3
220
0.85
414.3
2
207.1
XLPE
4C
150
407
0.91
0.7
0.64
259.26
500
34
ACDB BUS-B INDOOR LIGHTING PANEL -2( LOC -AC/DC ROOM)
130.770
3
220
0.85
403.7
2
201.9
XLPE
4C
120
355
0.91
0.7
0.64
226.14
500
35
ACDB BUS-B OUTDOOR LIGHTING PANEL-2 (LOC -380KV GIS ROOM)
117.90
3
220
0.85
364.0
2
182.0
XLPE
1C
630
1117
0.91
0.7
0.64
711.53
500
36
ACDB BUS-B OUTDOOR LIGHTING PANEL -3( LOC -132KV GIS ROOM)
66.06
3
220
0.85
204.0
2
102.0
XLPE
4C
240
551
0.91
0.7
0.64
350.99
320
37
ACDB BUS-B SDB-1A (LOC -380KV GIS BLD)
67.77
3
220
0.85
143.0
2
71.5
XLPE
4C
95
305
0.91
0.7
0.64
194.29
320
38
ACDB BUS-B SDB-2 (LOC -132KV GIS BLD)
75.449
3
220
0.85
232.9
3
77.6
XLPE
4C
185
469
0.91
0.7
0.64
298.75
320
39
ACDB BUS-B OIL FILTERATION SOCKET FOR AUXILIARY TRANSFORMER
77.74
3
220
0.85
240.00
2
120.0
XLPE
4C
120
355
0.82
0.7
0.57
203.77
320
40
ACDB BUS-B 125V DC BATTERY CHARGER-2 (380KV DC SYSTEM BATTERY CHARGER)
62.50
3
220
0.85
193.0
1
193.0
XLPE
4C
120
355
0.91
0.7
0.64
226.14
250
41
ACDB BUS-B OUTDOOR LIGHTING PANEL-1 (LOC -AC/DC ROOM)
45.90
3
220
0.85
141.7
1
141.7
XLPE
4C
70
247
0.91
0.7
0.64
157.34
200
42
ACDB BUS-B SDB-1B (LOC -380KV GIS BLD)
43.937
3
220
0.85
135.6
2
67.8
XLPE
4C
185
469
0.91
0.7
0.64
298.75
200
43
ACDB BUS-B INDOOR LIGHTING PANEL -3( LOC -380KV GIS ROOM)
50.360
3
220
0.85
155.5
1
155.5
XLPE
4C
150
407
0.91
0.7
0.64
259.26
200
44
ACDB BUS-B INDOOR LIGHTING PANEL -4( LOC -380KV GIS ROOM)
50.360
3
220
0.85
155.5
2
77.7
XLPE
4C
150
407
0.91
0.7
0.64
259.26
200
4
ACDB BUS B INDOOR LIGHTING PANEL ( LOC 132KV GIS ROOM)
0 360
3
220
08
1
2
XLPE
4C
18
469
0 91
0
0 64
298
200
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
Saudi Electricity Company Central Operating Area
LV AC CABLE SIZING CALCULATION VOLTAGE DROP LIMIT ACDB TO VARIUOS LOADS ACDB TO OLP/ILP ACDB TO SDB SDB TO VARIOUS LOADS
S.No.
From
To
4.2 1.6 1.6 2.6
% % % %
KW
Phase
Derating Factors: k1 = Variation in air temperature -Indoor: 40°C k1 = Variation in air temperature -Outdoor: 50 °C k2 = Group rating factor
%VD = (Voltage Drop / S VOLTAGE DROP (3Ph) VOLTAGE DROP (1Ph) I = Current in Amp. L = Route length in met
Cables are laid on racks System Voltage =
VOLT
Amp
No. of cables per ph.
I req. Amp
Type
Core
mm²
I
PF
220 / 127 VAC
Amp
DERATING FACTORS Over K1 K2 All
derated current Amp
C.B current Amp
Selected Cable
32
ACDB BUS-B HVAC PANEL-3(LOC -132KV GIS BLD)
210.17
3
220
0.85
648.9
4
162.2
XLPE
1C
630
1117
0.91
0.7
0.64
711.53
800
33
ACDB BUS-B INDOOR LIGHTING PANEL -1( LOC -CONTROL ROOM)
134.190
3
220
0.85
414.3
2
207.1
XLPE
4C
150
407
0.91
0.7
0.64
259.26
500
34
ACDB BUS-B INDOOR LIGHTING PANEL -2( LOC -AC/DC ROOM)
130.770
3
220
0.85
403.7
2
201.9
XLPE
4C
120
355
0.91
0.7
0.64
226.14
500
35
ACDB BUS-B OUTDOOR LIGHTING PANEL-2 (LOC -380KV GIS ROOM)
117.90
3
220
0.85
364.0
2
182.0
XLPE
1C
630
1117
0.91
0.7
0.64
711.53
500
36
ACDB BUS-B OUTDOOR LIGHTING PANEL -3( LOC -132KV GIS ROOM)
66.06
3
220
0.85
204.0
2
102.0
XLPE
4C
240
551
0.91
0.7
0.64
350.99
320
37
ACDB BUS-B SDB-1A (LOC -380KV GIS BLD)
67.77
3
220
0.85
143.0
2
71.5
XLPE
4C
95
305
0.91
0.7
0.64
194.29
320
38
ACDB BUS-B SDB-2 (LOC -132KV GIS BLD)
75.449
3
220
0.85
232.9
3
77.6
XLPE
4C
185
469
0.91
0.7
0.64
298.75
320
39
ACDB BUS-B OIL FILTERATION SOCKET FOR AUXILIARY TRANSFORMER
77.74
3
220
0.85
240.00
2
120.0
XLPE
4C
120
355
0.82
0.7
0.57
203.77
320
40
ACDB BUS-B 125V DC BATTERY CHARGER-2 (380KV DC SYSTEM BATTERY CHARGER)
62.50
3
220
0.85
193.0
1
193.0
XLPE
4C
120
355
0.91
0.7
0.64
226.14
250
41
ACDB BUS-B OUTDOOR LIGHTING PANEL-1 (LOC -AC/DC ROOM)
45.90
3
220
0.85
141.7
1
141.7
XLPE
4C
70
247
0.91
0.7
0.64
157.34
200
42
ACDB BUS-B SDB-1B (LOC -380KV GIS BLD)
43.937
3
220
0.85
135.6
2
67.8
XLPE
4C
185
469
0.91
0.7
0.64
298.75
200
43
ACDB BUS-B INDOOR LIGHTING PANEL -3( LOC -380KV GIS ROOM)
50.360
3
220
0.85
155.5
1
155.5
XLPE
4C
150
407
0.91
0.7
0.64
259.26
200
44
ACDB BUS-B INDOOR LIGHTING PANEL -4( LOC -380KV GIS ROOM)
50.360
3
220
0.85
155.5
2
77.7
XLPE
4C
150
407
0.91
0.7
0.64
259.26
200
45
ACDB BUS-B INDOOR LIGHTING PANEL -5( LOC -132KV GIS ROOM)
50.360
3
220
0.85
155.5
2
77.7
XLPE
4C
185
469
0.91
0.7
0.64
298.75
200
46
125V DC BATTERY CHARGER ACDB BUS-B PORTABLE (132KV DC SYSTEM BATTERY CHARGER)
31.250
3
220
0.85
96.48
1
96.5
XLPE
4C
35
160
0.91
0.7
0.64
101.92
125
47
ACDB BUS-B 100A WELDING RECEPTACLE AT HVAC PACU-2
25.91
3
220
0.85
80.0
1
80.0
XLPE
4C
70
247
0.91
0.7
0.64
157.34
100
48
ACDB BUS-B 48V DC BATTERY CHARGER-2
8.50
3
220
0.85
26.2
1
26.2
XLPE
4C
10
73
0.91
0.45
0.41
29.89
63
CE-113347, REV.01
15 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
Saudi Electricity Company Central Operating Area
LV AC CABLE SIZING CALCULATION VOLTAGE DROP LIMIT ACDB TO VARIUOS LOADS ACDB TO OLP/ILP ACDB TO SDB SDB TO VARIOUS LOADS
S.No.
From
To
4.2 1.6 1.6 2.6
% % % %
KW
Phase
Derating Factors: k1 = Variation in air temperature -Indoor: 40 °C k1 = Variation in air temperature -Outdoor: 50 °C k2 = Group rating factor
%VD = (Voltage Drop / S VOLTAGE DROP (3Ph) VOLTAGE DROP (1Ph) I = Current in Amp. L = Route length in met
Cables are laid on racks System Voltage =
VOLT
PF
220 / 127 VAC
Amp
No. of cables per ph.
I req. Amp
Type
Core
mm²
Amp
I
Selected Cable
DERATING FACTORS Over K1 K2 All
derated current Amp
C.B current Amp
49
ACDB BUS-B SGT-2 MK ( Lamp , Heater , Thermostat , Moisture-In-Oil Monitor & Receptacle)
3.732
1
220
0.85
11.5
1
11.5
XLPE
4C
10
73
0.82
0.45
0.37
26.94
32
50
3.732
1
220
0.85
11.5
1
11.5
XLPE
4C
10
73
0.82
0.45
0.37
26.94
32
51
MK ( Lamp , Heater , Thermostat , Moisture-In-Oil ACDB BUS-B SGT-5 Monitor & Receptacle) SUMP PUMP TUNNEL-B1 ACDB BUS-B (132KV CONTROL CABLES TUNNEL)
3.600
3
220
0.85
11.1
1
11.1
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
52
ACDB BUS-B SGT-1 OLTC DRIVE MOTOR
2.890
3
220
0.85
8.9
1
8.9
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
53
ACDB BUS-B SGT-2 OLTC DRIVE MOTOR
2.890
3
220
0.85
8.9
1
8.9
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
54
ACDB BUS-B SGT-5 OLTC DRIVE MOTOR
2.890
3
220
0.85
8.9
1
8.9
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
55
ACDB BUS-B SGT-1 OLTC HEATER SUPPLY
0.170
3
220
0.85
0.5
1
0.5
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
56
ACDB BUS-B SGT-2 OLTC HEATER SUPPLY
0.170
3
220
0.85
0.5
1
0.5
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
57
ACDB BUS-B SGT-5 OLTC HEATER SUPPLY
0.170
3
220
0.85
0.5
1
0.5
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
58
ACDB BUS-B WATER TRANSFER PUMP
2.237
3
220
0.85
6.9
1
6.9
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
59
ACDB BUS-B LIGHTING SIGN BOARD
0.550
3
220
0.85
1.7
1
1.7
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
60
ACDB BUS-B GATE HOUSE LIGHTING
0.392
4
127
0.85
2.1
1
2.1
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
61
ACDB BUS-B AUXILIARY SUPPLY FOR GT-2
2.914
3
220
0.85
9.0
1
9.0
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
PANEL : MAIN DISTRIBUTION BOARD BUS-C 220/127V AC
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
Saudi Electricity Company Central Operating Area
LV AC CABLE SIZING CALCULATION VOLTAGE DROP LIMIT ACDB TO VARIUOS LOADS ACDB TO OLP/ILP ACDB TO SDB SDB TO VARIOUS LOADS
S.No.
From
To
4.2 1.6 1.6 2.6
% % % %
KW
Phase
Derating Factors: k1 = Variation in air temperature -Indoor: 40 °C k1 = Variation in air temperature -Outdoor: 50 °C k2 = Group rating factor
%VD = (Voltage Drop / S VOLTAGE DROP (3Ph) VOLTAGE DROP (1Ph) I = Current in Amp. L = Route length in met
Cables are laid on racks System Voltage =
VOLT
Amp
No. of cables per ph.
I req. Amp
Type
Core
mm²
Amp
I
PF
220 / 127 VAC Selected Cable
DERATING FACTORS Over K1 K2 All
derated current Amp
C.B current Amp
49
ACDB BUS-B SGT-2 MK ( Lamp , Heater , Thermostat , Moisture-In-Oil Monitor & Receptacle)
3.732
1
220
0.85
11.5
1
11.5
XLPE
4C
10
73
0.82
0.45
0.37
26.94
32
50
3.732
1
220
0.85
11.5
1
11.5
XLPE
4C
10
73
0.82
0.45
0.37
26.94
32
51
MK ( Lamp , Heater , Thermostat , Moisture-In-Oil ACDB BUS-B SGT-5 Monitor & Receptacle) SUMP PUMP TUNNEL-B1 ACDB BUS-B (132KV CONTROL CABLES TUNNEL)
3.600
3
220
0.85
11.1
1
11.1
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
52
ACDB BUS-B SGT-1 OLTC DRIVE MOTOR
2.890
3
220
0.85
8.9
1
8.9
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
53
ACDB BUS-B SGT-2 OLTC DRIVE MOTOR
2.890
3
220
0.85
8.9
1
8.9
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
54
ACDB BUS-B SGT-5 OLTC DRIVE MOTOR
2.890
3
220
0.85
8.9
1
8.9
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
55
ACDB BUS-B SGT-1 OLTC HEATER SUPPLY
0.170
3
220
0.85
0.5
1
0.5
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
56
ACDB BUS-B SGT-2 OLTC HEATER SUPPLY
0.170
3
220
0.85
0.5
1
0.5
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
57
ACDB BUS-B SGT-5 OLTC HEATER SUPPLY
0.170
3
220
0.85
0.5
1
0.5
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
58
ACDB BUS-B WATER TRANSFER PUMP
2.237
3
220
0.85
6.9
1
6.9
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
59
ACDB BUS-B LIGHTING SIGN BOARD
0.550
3
220
0.85
1.7
1
1.7
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
60
ACDB BUS-B GATE HOUSE LIGHTING
0.392
4
127
0.85
2.1
1
2.1
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
61
ACDB BUS-B AUXILIARY SUPPLY FOR GT-2
2.914
3
220
0.85
9.0
1
9.0
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
PANEL : MAIN DISTRIBUTION BOARD BUS-C 220/127V AC 62
ACDB BUS-C HVAC PANEL-2(LOC -380KV GIS BLD)
309.22
3
220
0.85
954.7
5
190.9
XLPE
1C
630
1117
0.91
0.7
0.64
711.53
1250
63
ACDB BUS-C HVAC PANEL-1(LOC -CONTROL BLD)
195.72
3
220
0.85
604.2
2
302.1
XLPE
4C
240
551
0.91
0.7
0.64
350.99
800
64
ACDB BUS-C 300A OIL FILTERATION SOCKET (TRF AREA)
77.74
3
220
0.85
240.0
1
240.0
XLPE
4C
150
407
0.91
0.7
0.64
259.26
320
CE-113347, REV.01
16 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
Saudi Electricity Company Central Operating Area
LV AC CABLE SIZING CALCULATION VOLTAGE DROP LIMIT ACDB TO VARIUOS LOADS ACDB TO OLP/ILP ACDB TO SDB SDB TO VARIOUS LOADS
S.No.
From
To
4.2 1.6 1.6 2.6
% % % %
KW
Phase
Derating Factors: k1 = Variation in air temperature -Indoor: 40 °C k1 = Variation in air temperature -Outdoor: 50 °C k2 = Group rating factor
%VD = (Voltage Drop / S VOLTAGE DROP (3Ph) VOLTAGE DROP (1Ph) I = Current in Amp. L = Route length in met
Cables are laid on racks System Voltage =
VOLT
PF
220 / 127 VAC
Amp
No. of cables per ph.
I req. Amp
Type
Core
mm²
I
Amp
DERATING FACTORS Over K1 K2 All
derated current Amp
C.B current Amp
Selected Cable
65
ACDB BUS-C 125V DC BATTERY CHARGER-1 (380KV DC SYSTEM BATTERY CHARGER)
62.50
3
220
0.85
193.0
1
193.0
XLPE
4C
120
355
0.91
0.7
0.64
226.14
250
66
ACDB BUS-C OUTDOOR LIGHTING PANEL-1 (LOC -AC/DC ROOM)
45.90
3
220
0.85
141.7
1
141.7
XLPE
4C
70
247
0.91
0.7
0.64
157.34
200
67
ACDB BUS-C INDOOR LIGHTING PANEL -3( LOC -380KV GIS ROOM)
50.360
3
220
0.85
155.5
1
155.5
XLPE
4C
150
407
0.91
0.7
0.64
259.26
200
68
ACDB BUS-C INDOOR LIGHTING PANEL -4( LOC -380KV GIS ROOM)
50.360
3
220
0.85
155.5
2
77.7
XLPE
4C
150
407
0.91
0.7
0.64
259.26
200
69
125V DC BATTERY CHARGER ACDB BUS-C PORTABLE (132KV DC SYSTEM BATTERY CHARGER)
31.250
3
220
0.85
96.48
1
96.5
XLPE
4C
35
160
0.91
0.7
0.64
101.92
125
70
ACDB BUS-C 100A RECEPTACLE FOR TRF AREA
25.91
3
220
0.85
80.0
1
80.0
XLPE
4C
50
195
0.91
0.7
0.64
124.22
100
71
ACDB BUS-C 100A RECEPTACLE FOR REACTOR AREA
25.91
3
220
0.85
80.0
1
80.0
XLPE
4C
50
195
0.91
0.7
0.64
124.22
100
72
ACDB BUS-C SGT-2 FANS GROUP-1
17.879
3
220
0.85
55.2
1
55.2
XLPE
4C
25
130
0.82
0.7
0.57
74.62
100
73
ACDB BUS-C SGT-2 FANS GROUP-2
17.879
3
220
0.85
55.2
1
55.2
XLPE
4C
25
130
0.82
0.7
0.57
74.62
100
74
ACDB BUS-C SGT-4 FANS GROUP-1
17.879
3
220
0.85
55.2
1
55.2
XLPE
4C
35
160
0.82
0.7
0.57
91.84
100
75
ACDB BUS-C SGT-4 FANS GROUP-2
17.879
3
220
0.85
55.2
1
55.2
XLPE
4C
35
160
0.82
0.7
0.57
91.84
100
76
ACDB BUS-C SGT-3 MK ( Lamp , Heater , Thermostat , Moisture-In-Oil Monitor & Receptacle)
3.732
1
220
0.85
11.5
1
11.5
XLPE
4C
10
73
0.82
0.45
0.37
26.94
32
77
MK ( Lamp , Heater , Thermostat , Moisture-In-Oil ACDB BUS-C SGT-4 Monitor & Receptacle)
3.732
1
220
0.85
11.5
1
11.5
XLPE
4C
10
73
0.82
0.45
0.37
26.94
32
78
ACDB BUS C SGT 3 PIT PUMP
2 983
3
220
0 85
92
1
92
XLPE
4C
10
73
0 82
0 45
0 37
26 94
20
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
Saudi Electricity Company Central Operating Area
LV AC CABLE SIZING CALCULATION VOLTAGE DROP LIMIT ACDB TO VARIUOS LOADS ACDB TO OLP/ILP ACDB TO SDB SDB TO VARIOUS LOADS
S.No.
From
To
4.2 1.6 1.6 2.6
% % % %
KW
Phase
Derating Factors: k1 = Variation in air temperature -Indoor: 40 °C k1 = Variation in air temperature -Outdoor: 50 °C k2 = Group rating factor
%VD = (Voltage Drop / S VOLTAGE DROP (3Ph) VOLTAGE DROP (1Ph) I = Current in Amp. L = Route length in met
Cables are laid on racks System Voltage =
VOLT
Amp
No. of cables per ph.
I req. Amp
Type
Core
mm²
I
PF
220 / 127 VAC
Amp
DERATING FACTORS Over K1 K2 All
derated current Amp
C.B current Amp
Selected Cable
65
ACDB BUS-C 125V DC BATTERY CHARGER-1 (380KV DC SYSTEM BATTERY CHARGER)
62.50
3
220
0.85
193.0
1
193.0
XLPE
4C
120
355
0.91
0.7
0.64
226.14
250
66
ACDB BUS-C OUTDOOR LIGHTING PANEL-1 (LOC -AC/DC ROOM)
45.90
3
220
0.85
141.7
1
141.7
XLPE
4C
70
247
0.91
0.7
0.64
157.34
200
67
ACDB BUS-C INDOOR LIGHTING PANEL -3( LOC -380KV GIS ROOM)
50.360
3
220
0.85
155.5
1
155.5
XLPE
4C
150
407
0.91
0.7
0.64
259.26
200
68
ACDB BUS-C INDOOR LIGHTING PANEL -4( LOC -380KV GIS ROOM)
50.360
3
220
0.85
155.5
2
77.7
XLPE
4C
150
407
0.91
0.7
0.64
259.26
200
69
125V DC BATTERY CHARGER ACDB BUS-C PORTABLE (132KV DC SYSTEM BATTERY CHARGER)
31.250
3
220
0.85
96.48
1
96.5
XLPE
4C
35
160
0.91
0.7
0.64
101.92
125
70
ACDB BUS-C 100A RECEPTACLE FOR TRF AREA
25.91
3
220
0.85
80.0
1
80.0
XLPE
4C
50
195
0.91
0.7
0.64
124.22
100
71
ACDB BUS-C 100A RECEPTACLE FOR REACTOR AREA
25.91
3
220
0.85
80.0
1
80.0
XLPE
4C
50
195
0.91
0.7
0.64
124.22
100
72
ACDB BUS-C SGT-2 FANS GROUP-1
17.879
3
220
0.85
55.2
1
55.2
XLPE
4C
25
130
0.82
0.7
0.57
74.62
100
73
ACDB BUS-C SGT-2 FANS GROUP-2
17.879
3
220
0.85
55.2
1
55.2
XLPE
4C
25
130
0.82
0.7
0.57
74.62
100
74
ACDB BUS-C SGT-4 FANS GROUP-1
17.879
3
220
0.85
55.2
1
55.2
XLPE
4C
35
160
0.82
0.7
0.57
91.84
100
75
ACDB BUS-C SGT-4 FANS GROUP-2
17.879
3
220
0.85
55.2
1
55.2
XLPE
4C
35
160
0.82
0.7
0.57
91.84
100
76
ACDB BUS-C SGT-3 MK ( Lamp , Heater , Thermostat , Moisture-In-Oil Monitor & Receptacle)
3.732
1
220
0.85
11.5
1
11.5
XLPE
4C
10
73
0.82
0.45
0.37
26.94
32
77
MK ( Lamp , Heater , Thermostat , Moisture-In-Oil ACDB BUS-C SGT-4 Monitor & Receptacle)
3.732
1
220
0.85
11.5
1
11.5
XLPE
4C
10
73
0.82
0.45
0.37
26.94
32
78
ACDB BUS-C SGT-3 PIT PUMP
2.983
3
220
0.85
9.2
1
9.2
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
79
ACDB BUS-C SGT-4 PIT PUMP
2.983
3
220
0.85
9.2
1
9.2
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
80
ACDB BUS-C SGT-3 OLTC DRIVE MOTOR
2.890
3
220
0.85
8.9
1
8.9
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
81
ACDB BUS-C SGT-4 OLTC DRIVE MOTOR
2.890
3
220
0.85
8.9
1
8.9
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
CE-113347, REV.01
17 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
Saudi Electricity Company Central Operating Area
LV AC CABLE SIZING CALCULATION VOLTAGE DROP LIMIT ACDB TO VARIUOS LOADS ACDB TO OLP/ILP ACDB TO SDB SDB TO VARIOUS LOADS
S.No.
From
To
4.2 1.6 1.6 2.6
% % % %
KW
Phase
Derating Factors: k1 = Variation in air temperature -Indoor: 40 °C k1 = Variation in air temperature -Outdoor: 50 °C k2 = Group rating factor
%VD = (Voltage Drop / S VOLTAGE DROP (3Ph) VOLTAGE DROP (1Ph) I = Current in Amp. L = Route length in met
Cables are laid on racks System Voltage =
VOLT
PF
220 / 127 VAC
Amp
No. of cables per ph.
I req. Amp
Type
Core
mm²
Amp
I
Selected Cable
DERATING FACTORS Over K1 K2 All
derated current Amp
C.B current Amp
82
ACDB BUS-C SGT-3 OLTC HEATER SUPPLY
0.170
3
220
0.85
0.5
1
0.5
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
83
ACDB BUS-C SGT-4 OLTC HEATER SUPPLY
0.170
3
220
0.85
0.5
1
0.5
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
84
ACDB BUS-C BOASTER PUMP
2.237
3
220
0.85
6.9
1
6.9
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
85
ACDB BUS-C AUXILIARY SUPPLY FOR GT-3
2.914
3
220
0.85
9.0
1
9.0
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
86
ACDB BUS-C AUXILIARY SUPPLY FOR GT-4
2.914
3
220
0.85
9.0
1
9.0
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
SUB-DISTRIBUTION BOARD-1A (BUS-A) 87
SDB-1A ( BUS-A)
100A,HIGH VOLTAGE TEST SOCKET-1
25.912
3
220
0.85
80.00
1
80.00
XLPE
4C
25
130
0.91
0.7
0.64
82.81
100
88
SDB-1A ( BUS-A)
100A,RECEPTACLE AT HVAC PACU-3
25.91
3
220
0.85
80.00
1
80.00
XLPE
4C
35
160
0.82
0.7
0.57
91.84
100
89
SDB-1A ( BUS-A)
63A,GAS FILLING RECEPTACLE-1
16.325
3
220
0.85
50.40
1
50.40
XLPE
4C
16
96
0.91
0.7
0.64
61.15
63
90
SDB-1A ( BUS-A)
SUMP PUMP TUNNEL-A1 (380KV CONTROL CABLES TUNNEL)
1.80
3
220
0.85
5.56
1
5.56
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
91
SDB-1A ( BUS-A)
SUMP PUMP TUNNEL-A2 (380KV CONTROL CABLES TUNNEL)
1.80
3
220
0.85
5.56
1
5.56
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
92
SDB-1A ( BUS-A)
380KV LCC (C02-A) CB MOTOR SUPPLY
1.00
3
220
0.85
3.09
1
3.09
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
93
SDB-1A
380
1 00
3
220
08
3 09
1
3 09
C
10
3
0 91
0
0 1
29 89
20
CC (C02 ) C
O O S
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
Saudi Electricity Company Central Operating Area
LV AC CABLE SIZING CALCULATION VOLTAGE DROP LIMIT ACDB TO VARIUOS LOADS ACDB TO OLP/ILP ACDB TO SDB SDB TO VARIOUS LOADS
S.No.
From
To
4.2 1.6 1.6 2.6
% % % %
KW
Phase
Derating Factors: k1 = Variation in air temperature -Indoor: 40 °C k1 = Variation in air temperature -Outdoor: 50 °C k2 = Group rating factor
%VD = (Voltage Drop / S VOLTAGE DROP (3Ph) VOLTAGE DROP (1Ph) I = Current in Amp. L = Route length in met
Cables are laid on racks System Voltage =
VOLT
Amp
No. of cables per ph.
I req. Amp
Type
Core
mm²
Amp
I
PF
220 / 127 VAC Selected Cable
DERATING FACTORS Over K1 K2 All
derated current Amp
C.B current Amp
82
ACDB BUS-C SGT-3 OLTC HEATER SUPPLY
0.170
3
220
0.85
0.5
1
0.5
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
83
ACDB BUS-C SGT-4 OLTC HEATER SUPPLY
0.170
3
220
0.85
0.5
1
0.5
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
84
ACDB BUS-C BOASTER PUMP
2.237
3
220
0.85
6.9
1
6.9
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
85
ACDB BUS-C AUXILIARY SUPPLY FOR GT-3
2.914
3
220
0.85
9.0
1
9.0
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
86
ACDB BUS-C AUXILIARY SUPPLY FOR GT-4
2.914
3
220
0.85
9.0
1
9.0
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
SUB-DISTRIBUTION BOARD-1A (BUS-A) 87
SDB-1A ( BUS-A)
100A,HIGH VOLTAGE TEST SOCKET-1
25.912
3
220
0.85
80.00
1
80.00
XLPE
4C
25
130
0.91
0.7
0.64
82.81
100
88
SDB-1A ( BUS-A)
100A,RECEPTACLE AT HVAC PACU-3
25.91
3
220
0.85
80.00
1
80.00
XLPE
4C
35
160
0.82
0.7
0.57
91.84
100
89
SDB-1A ( BUS-A)
63A,GAS FILLING RECEPTACLE-1
16.325
3
220
0.85
50.40
1
50.40
XLPE
4C
16
96
0.91
0.7
0.64
61.15
63
90
SDB-1A ( BUS-A)
SUMP PUMP TUNNEL-A1 (380KV CONTROL CABLES TUNNEL)
1.80
3
220
0.85
5.56
1
5.56
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
91
SDB-1A ( BUS-A)
SUMP PUMP TUNNEL-A2 (380KV CONTROL CABLES TUNNEL)
1.80
3
220
0.85
5.56
1
5.56
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
92
SDB-1A ( BUS-A)
380KV LCC (C02-A) CB MOTOR SUPPLY
1.00
3
220
0.85
3.09
1
3.09
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
93
SDB-1A ( BUS-A)
380KV LCC (C02-B) CB MOTOR SUPPLY
1.00
3
220
0.85
3.09
1
3.09
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
94
SDB-1A ( BUS-A)
380KV LCC (C02-C) CB MOTOR SUPPLY
1.00
3
220
0.85
3.09
1
3.09
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
95
SDB-1A ( BUS-A)
380KV LCC (C03-A) CB MOTOR SUPPLY
1.00
3
220
0.85
3.09
1
3.09
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
CE-113347, REV.01
18 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
Saudi Electricity Company Central Operating Area
LV AC CABLE SIZING CALCULATION VOLTAGE DROP LIMIT ACDB TO VARIUOS LOADS ACDB TO OLP/ILP ACDB TO SDB SDB TO VARIOUS LOADS
S.No.
From
To
4.2 1.6 1.6 2.6
% % % %
KW
Phase
Derating Factors: k1 = Variation in air temperature -Indoor: 40 °C k1 = Variation in air temperature -Outdoor: 50 °C k2 = Group rating factor
%VD = (Voltage Drop / S VOLTAGE DROP (3Ph) VOLTAGE DROP (1Ph) I = Current in Amp. L = Route length in met
Cables are laid on racks System Voltage =
VOLT
PF
220 / 127 VAC
Amp
No. of cables per ph.
I req. Amp
Type
Core
mm²
Amp
I
Selected Cable
DERATING FACTORS Over K1 K2 All
derated current Amp
C.B current Amp
96
SDB-1A ( BUS-A)
380KV LCC (C03-B) CB MOTOR SUPPLY
1.00
3
220
0.85
3.09
1
3.09
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
97
SDB-1A ( BUS-A)
380KV LCC (C03-C) CB MOTOR SUPPLY
1.00
3
220
0.85
3.09
1
3.09
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
98
SDB-1A ( BUS-A)
380KV LCC (C04-A) CB MOTOR SUPPLY
1.00
3
220
0.85
3.09
1
3.09
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
99
SDB-1A ( BUS-A)
380KV LCC (C04-B) CB MOTOR SUPPLY
1.00
3
220
0.85
3.09
1
3.09
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
100
SDB-1A ( BUS-A)
380KV LCC (C04-C) CB MOTOR SUPPLY
1.00
3
220
0.85
3.09
1
3.09
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
SUB-DISTRIBUTION BOARD-1A (BUS-B) 101
SDB-1A ( BUS-B)
100A,HIGH VOLTAGE TEST SOCKET-2
25.912
3
220
0.85
80.00
1
80.00
XLPE
4C
70
247
0.91
0.7
0.64
157.34
100
102
SDB-1A ( BUS-B)
HVAC CONTROL PANEL-2(380KV GIS BLD)
20.000
3
220
0.85
61.75
1
61.75
XLPE
4C
25
130
0.91
0.7
0.64
82.81
100
103
SDB-1A ( BUS-B)
EOT CRANE
6.750
3
220
0.85
20.84
1
20.84
XLPE
4C
10
73
0.91
0.45
0.41
29.89
63
104
SDB-1A ( BUS-B)
SUMP PUMP TUNNEL-A3 (380KV O/G CABLES TUNNEL)
1.80
3
220
0.85
5.56
1
5.56
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
105
SDB-1A ( BUS-B)
ROLLING SHUTTER MOTOR-1
1.70
3
220
0.85
5.25
1
5.25
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
106
SDB-1A ( BUS-B)
380KV OUTDOOR CT'S MISCELLANEOUS HEATERS
2.610
3
220
0.85
8.06
1
8.06
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
Saudi Electricity Company Central Operating Area
LV AC CABLE SIZING CALCULATION VOLTAGE DROP LIMIT ACDB TO VARIUOS LOADS ACDB TO OLP/ILP ACDB TO SDB SDB TO VARIOUS LOADS
S.No.
From
To
4.2 1.6 1.6 2.6
% % % %
KW
Phase
Derating Factors: k1 = Variation in air temperature -Indoor: 40 °C k1 = Variation in air temperature -Outdoor: 50 °C k2 = Group rating factor
%VD = (Voltage Drop / S VOLTAGE DROP (3Ph) VOLTAGE DROP (1Ph) I = Current in Amp. L = Route length in met
Cables are laid on racks System Voltage =
VOLT
Amp
No. of cables per ph.
I req. Amp
Type
Core
mm²
Amp
I
PF
220 / 127 VAC Selected Cable
DERATING FACTORS Over K1 K2 All
derated current Amp
C.B current Amp
96
SDB-1A ( BUS-A)
380KV LCC (C03-B) CB MOTOR SUPPLY
1.00
3
220
0.85
3.09
1
3.09
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
97
SDB-1A ( BUS-A)
380KV LCC (C03-C) CB MOTOR SUPPLY
1.00
3
220
0.85
3.09
1
3.09
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
98
SDB-1A ( BUS-A)
380KV LCC (C04-A) CB MOTOR SUPPLY
1.00
3
220
0.85
3.09
1
3.09
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
99
SDB-1A ( BUS-A)
380KV LCC (C04-B) CB MOTOR SUPPLY
1.00
3
220
0.85
3.09
1
3.09
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
100
SDB-1A ( BUS-A)
380KV LCC (C04-C) CB MOTOR SUPPLY
1.00
3
220
0.85
3.09
1
3.09
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
SUB-DISTRIBUTION BOARD-1A (BUS-B) 101
SDB-1A ( BUS-B)
100A,HIGH VOLTAGE TEST SOCKET-2
25.912
3
220
0.85
80.00
1
80.00
XLPE
4C
70
247
0.91
0.7
0.64
157.34
100
102
SDB-1A ( BUS-B)
HVAC CONTROL PANEL-2(380KV GIS BLD)
20.000
3
220
0.85
61.75
1
61.75
XLPE
4C
25
130
0.91
0.7
0.64
82.81
100
103
SDB-1A ( BUS-B)
EOT CRANE
6.750
3
220
0.85
20.84
1
20.84
XLPE
4C
10
73
0.91
0.45
0.41
29.89
63
104
SDB-1A ( BUS-B)
SUMP PUMP TUNNEL-A3 (380KV O/G CABLES TUNNEL)
1.80
3
220
0.85
5.56
1
5.56
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
105
SDB-1A ( BUS-B)
ROLLING SHUTTER MOTOR-1
1.70
3
220
0.85
5.25
1
5.25
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
106
SDB-1A ( BUS-B)
380KV OUTDOOR CT'S MISCELLANEOUS HEATERS
2.610
3
220
0.85
8.06
1
8.06
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
107
SDB-1A ( BUS-B)
380KV LCC (C05-A) CB MOTOR SUPPLY
1.00
3
220
0.85
3.09
1
3.09
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
108
SDB-1A ( BUS-B)
380KV LCC (C05-B) CB MOTOR SUPPLY
1.00
3
220
0.85
3.09
1
3.09
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
109
SDB-1A ( BUS-B)
380KV LCC (C05-C) CB MOTOR SUPPLY
1.00
3
220
0.85
3.09
1
3.09
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
CE-113347, REV.01
19 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
Saudi Electricity Company Central Operating Area
LV AC CABLE SIZING CALCULATION VOLTAGE DROP LIMIT ACDB TO VARIUOS LOADS ACDB TO OLP/ILP ACDB TO SDB SDB TO VARIOUS LOADS
S.No.
From
To
4.2 1.6 1.6 2.6
% % % %
KW
Phase
Derating Factors: k1 = Variation in air temperature -Indoor: 40 °C k1 = Variation in air temperature -Outdoor: 50 °C k2 = Group rating factor
%VD = (Voltage Drop / S VOLTAGE DROP (3Ph) VOLTAGE DROP (1Ph) I = Current in Amp. L = Route length in met
Cables are laid on racks System Voltage =
VOLT
PF
220 / 127 VAC
Amp
No. of cables per ph.
I req. Amp
Type
Core
mm²
Amp
I
Selected Cable
DERATING FACTORS Over K1 K2 All
derated current Amp
C.B current Amp
110
SDB-1A ( BUS-B)
380KV LCC (C06-A) CB MOTOR SUPPLY
1.00
3
220
0.85
3.09
1
3.09
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
111
SDB-1A ( BUS-B)
380KV LCC (C06-B) CB MOTOR SUPPLY
1.00
3
220
0.85
3.09
1
3.09
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
112
SDB-1A ( BUS-B)
380KV LCC (C06-C) CB MOTOR SUPPLY
1.00
3
220
0.85
3.09
1
3.09
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
113
SDB-1A ( BUS-B)
380KV LCC (C07-A) CB MOTOR SUPPLY
1.00
3
220
0.85
3.09
1
3.09
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
114
SDB-1A ( BUS-B)
380KV LCC (C07-B) CB MOTOR SUPPLY
1.00
3
220
0.85
3.09
1
3.09
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
115
SDB-1A ( BUS-B)
380KV LCC (C07-C) CB MOTOR SUPPLY
1.00
3
220
0.85
3.09
1
3.09
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
SUB-DISTRIBUTION BOARD-1B (BUS-A) 116
SDB-1B ( BUS-A)
100A,RECEPTACLE AT HVAC PACU-2
25.912
3
220
0.85
80.00
1
80.00
XLPE
4C
35
160
0.82
0.7
0.57
91.84
100
117
SDB-1B ( BUS-A)
63A,GAS FILLING RECEPTACLE-2
16.325
3
220
0.85
50.40
1
50.40
XLPE
4C
16
96
0.91
0.7
0.64
61.15
63
118
SDB-1B ( BUS-A)
380KV OUTDOOR CT'S MISCELLANEOUS HEATERS
1.740
3
220
0.85
5.37
1
5.37
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
25.91
3
220
0.85
80.00
1
80.00
XLPE
4C
50
195
0.82
0.7
0.57
111.93
100
SUB-DISTRIBUTION BOARD-1B (BUS-B) 119
SDB-1B ( BUS-B)
100A,RECEPTACLE AT HVAC PACU-1
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
Saudi Electricity Company Central Operating Area
LV AC CABLE SIZING CALCULATION VOLTAGE DROP LIMIT ACDB TO VARIUOS LOADS ACDB TO OLP/ILP ACDB TO SDB SDB TO VARIOUS LOADS
S.No.
From
To
4.2 1.6 1.6 2.6
% % % %
KW
Phase
Derating Factors: k1 = Variation in air temperature -Indoor: 40 °C k1 = Variation in air temperature -Outdoor: 50 °C k2 = Group rating factor
%VD = (Voltage Drop / S VOLTAGE DROP (3Ph) VOLTAGE DROP (1Ph) I = Current in Amp. L = Route length in met
Cables are laid on racks System Voltage =
VOLT
Amp
No. of cables per ph.
I req. Amp
Type
Core
mm²
Amp
I
PF
220 / 127 VAC Selected Cable
DERATING FACTORS Over K1 K2 All
derated current Amp
C.B current Amp
110
SDB-1A ( BUS-B)
380KV LCC (C06-A) CB MOTOR SUPPLY
1.00
3
220
0.85
3.09
1
3.09
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
111
SDB-1A ( BUS-B)
380KV LCC (C06-B) CB MOTOR SUPPLY
1.00
3
220
0.85
3.09
1
3.09
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
112
SDB-1A ( BUS-B)
380KV LCC (C06-C) CB MOTOR SUPPLY
1.00
3
220
0.85
3.09
1
3.09
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
113
SDB-1A ( BUS-B)
380KV LCC (C07-A) CB MOTOR SUPPLY
1.00
3
220
0.85
3.09
1
3.09
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
114
SDB-1A ( BUS-B)
380KV LCC (C07-B) CB MOTOR SUPPLY
1.00
3
220
0.85
3.09
1
3.09
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
115
SDB-1A ( BUS-B)
380KV LCC (C07-C) CB MOTOR SUPPLY
1.00
3
220
0.85
3.09
1
3.09
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
SUB-DISTRIBUTION BOARD-1B (BUS-A) 116
SDB-1B ( BUS-A)
100A,RECEPTACLE AT HVAC PACU-2
25.912
3
220
0.85
80.00
1
80.00
XLPE
4C
35
160
0.82
0.7
0.57
91.84
100
117
SDB-1B ( BUS-A)
63A,GAS FILLING RECEPTACLE-2
16.325
3
220
0.85
50.40
1
50.40
XLPE
4C
16
96
0.91
0.7
0.64
61.15
63
118
SDB-1B ( BUS-A)
380KV OUTDOOR CT'S MISCELLANEOUS HEATERS
1.740
3
220
0.85
5.37
1
5.37
XLPE
4C
10
73
0.82
0.45
0.37
26.94
20
SUB-DISTRIBUTION BOARD-1B (BUS-B) 119
SDB-1B ( BUS-B)
100A,RECEPTACLE AT HVAC PACU-1
25.91
3
220
0.85
80.00
1
80.00
XLPE
4C
50
195
0.82
0.7
0.57
111.93
100
120
SDB-1B ( BUS-B)
63A,GAS FILLING RECEPTACLE-3
16.325
3
220
0.85
50.40
1
50.40
XLPE
4C
16
96
0.91
0.7
0.64
61.15
63
121
SDB-1B ( BUS-B)
ROLLING SHUTTER MOTOR-2
1.70
3
220
0.85
5.25
1
5.25
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
SUB-DISTRIBUTION BOARD-2 (BUS-A) CE-113347, REV.01
20 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
Saudi Electricity Company Central Operating Area
LV AC CABLE SIZING CALCULATION VOLTAGE DROP LIMIT ACDB TO VARIUOS LOADS ACDB TO OLP/ILP ACDB TO SDB SDB TO VARIOUS LOADS
S.No.
From
To
4.2 1.6 1.6 2.6
% % % %
KW
Phase
Derating Factors: k1 = Variation in air temperature -Indoor: 40 °C k1 = Variation in air temperature -Outdoor: 50 °C k2 = Group rating factor
%VD = (Voltage Drop / S VOLTAGE DROP (3Ph) VOLTAGE DROP (1Ph) I = Current in Amp. L = Route length in met
Cables are laid on racks System Voltage =
VOLT
PF
220 / 127 VAC
Amp
No. of cables per ph.
I req. Amp
Type
Core
mm²
Amp
I
Selected Cable
DERATI NG FACTORS Over K1 K2 All
derated current Amp
C.B current Amp
122
SDB-2 ( BUS-A)
100A,RECEPTACLE AT HVAC UNITS -1
25.912
3
220
0.85
80.00
1
80.00
XLPE
4C
35
160
0.82
0.7
0.57
91.84
100
123
SDB-2 ( BUS-A)
63A,GAS FILLING RECEPTACLES # 1,2,3
16.325
3
220
0.85
50.40
1
50.40
XLPE
4C
25
130
0.91
0.7
0.64
82.81
63
124
SDB-2 ( BUS-A)
EOT CRANE
6.750
3
220
0.85
20.84
1
20.84
XLPE
4C
16
96
0.91
0.7
0.64
61.15
63
125
SDB-2 ( BUS-A)
ROLLING SHUTTER MOTOR DOOR-1
1.70
3
220
0.85
5.25
1
5.25
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
126
SDB-2 ( BUS-A)
SUMP PUMP-1&2 132KV GIS BASEMENT
3.60
3
220
0.85
11.11
1
11.11
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
127
SDB-1A ( BUS-B)
SUMP PUMP TUNNEL-B2 (132KV O/G CABLES TUNNEL)
1.80
3
220
0.85
5.56
1
5.56
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
SUB-DISTRIBUTION BOARD-2 (BUS-B) 128
SDB-2 ( BUS-B)
100A,RECEPTACLE AT HVAC UNITS -2
25.912
3
220
0.85
80.00
1
80.00
XLPE
4C
70
247
0.82
0.45
0.37
91.14
100
129
SDB-2 ( BUS-B)
100A,RECEPTACLE AT HVAC UNITS -3
25.912
3
220
0.85
80.00
1
80.00
XLPE
4C
70
247
0.82
0.45
0.37
91.14
100
130
SDB-2 ( BUS-B)
63A,GAS FILLING RECEPTACLES # 4,5,6
16.325
3
220
0.85
50.40
1
50.40
XLPE
4C
16
96
0.91
0.7
0.64
61.15
63
131
SDB-2 ( BUS-B)
HVAC CONTROL PANEL-2(132KV GIS BLD)
2.00
3
220
0.85
6.17
1
6.17
XLPE
4C
10
73
0.91
0.45
0.41
29.89
63
132
SDB-2 ( BUS-B)
SUMP PUMP-3 132KV GIS BASEMENT
1.80
3
220
0.85
5.56
1
5.56
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
Saudi Electricity Company Central Operating Area
LV AC CABLE SIZING CALCULATION VOLTAGE DROP LIMIT ACDB TO VARIUOS LOADS ACDB TO OLP/ILP ACDB TO SDB SDB TO VARIOUS LOADS
S.No.
From
To
4.2 1.6 1.6 2.6
% % % %
KW
Phase
Derating Factors: k1 = Variation in air temperature -Indoor: 40 °C k1 = Variation in air temperature -Outdoor: 50 °C k2 = Group rating factor
%VD = (Voltage Drop / S VOLTAGE DROP (3Ph) VOLTAGE DROP (1Ph) I = Current in Amp. L = Route length in met
Cables are laid on racks System Voltage =
VOLT
Amp
No. of cables per ph.
I req. Amp
Type
Core
mm²
Amp
I
PF
220 / 127 VAC Selected Cable
DERATI NG FACTORS Over K1 K2 All
derated current Amp
C.B current Amp
122
SDB-2 ( BUS-A)
100A,RECEPTACLE AT HVAC UNITS -1
25.912
3
220
0.85
80.00
1
80.00
XLPE
4C
35
160
0.82
0.7
0.57
91.84
100
123
SDB-2 ( BUS-A)
63A,GAS FILLING RECEPTACLES # 1,2,3
16.325
3
220
0.85
50.40
1
50.40
XLPE
4C
25
130
0.91
0.7
0.64
82.81
63
124
SDB-2 ( BUS-A)
EOT CRANE
6.750
3
220
0.85
20.84
1
20.84
XLPE
4C
16
96
0.91
0.7
0.64
61.15
63
125
SDB-2 ( BUS-A)
ROLLING SHUTTER MOTOR DOOR-1
1.70
3
220
0.85
5.25
1
5.25
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
126
SDB-2 ( BUS-A)
SUMP PUMP-1&2 132KV GIS BASEMENT
3.60
3
220
0.85
11.11
1
11.11
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
127
SDB-1A ( BUS-B)
SUMP PUMP TUNNEL-B2 (132KV O/G CABLES TUNNEL)
1.80
3
220
0.85
5.56
1
5.56
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
SUB-DISTRIBUTION BOARD-2 (BUS-B) 128
SDB-2 ( BUS-B)
100A,RECEPTACLE AT HVAC UNITS -2
25.912
3
220
0.85
80.00
1
80.00
XLPE
4C
70
247
0.82
0.45
0.37
91.14
100
129
SDB-2 ( BUS-B)
100A,RECEPTACLE AT HVAC UNITS -3
25.912
3
220
0.85
80.00
1
80.00
XLPE
4C
70
247
0.82
0.45
0.37
91.14
100
130
SDB-2 ( BUS-B)
63A,GAS FILLING RECEPTACLES # 4,5,6
16.325
3
220
0.85
50.40
1
50.40
XLPE
4C
16
96
0.91
0.7
0.64
61.15
63
131
SDB-2 ( BUS-B)
HVAC CONTROL PANEL-2(132KV GIS BLD)
2.00
3
220
0.85
6.17
1
6.17
XLPE
4C
10
73
0.91
0.45
0.41
29.89
63
132
SDB-2 ( BUS-B)
SUMP PUMP-3 132KV GIS BASEMENT
1.80
3
220
0.85
5.56
1
5.56
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
133
SDB-2 ( BUS-B)
ROLLING SHUTTER MOTOR DOOR-2
1.70
3
220
0.85
5.25
1
5.25
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
134
SDB-1A ( BUS-B)
SUMP PUMP TUNNEL-B3 (132KV O/G CABLES TUNNEL)
1.80
3
220
0.85
5.56
1
5.56
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
HVAC PANEL-1 CE-113347, REV.01
21 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
Saudi Electricity Company Central Operating Area
LV AC CABLE SIZING CALCULATION VOLTAGE DROP LIMIT ACDB TO VARIUOS LOADS ACDB TO OLP/ILP ACDB TO SDB SDB TO VARIOUS LOADS
S.No.
From
To
4.2 1.6 1.6 2.6
% % % %
KW
Phase
Derating Factors: k1 = Variation in air temperature -Indoor: 40 °C k1 = Variation in air temperature -Outdoor: 50 °C k2 = Group rating factor
%VD = (Voltage Drop / S VOLTAGE DROP (3Ph) VOLTAGE DROP (1Ph) I = Current in Amp. L = Route length in met
Cables are laid on racks System Voltage =
VOLT
PF
220 / 127 VAC
Amp
No. of cables per ph.
I req. Amp
Type
Core
mm²
Amp
I
Selected Cable
DERATING FACTORS Over K1 K2 All
derated current Amp
C.B current Amp
135
HVAC-1
PACU-1A (DUTY)
68.300
3
220
0.85
210.87
1
210.87
XLPE
4C
150
407
0.82
0.7
0.57
233.62
320
136
HVAC-1
PACU-2A (DUTY)
73.470
3
220
0.85
226.83
1
226.83
XLPE
4C
185
469
0.82
0.7
0.57
269.21
320
137
HVAC-1
PACU-1B (STANDBY)
68.300
3
220
0.85
210.87
1
210.87
XLPE
4C
150
407
0.82
0.7
0.57
233.62
320
138
HVAC-1
PACU-2B (STANDBY)
73.470
3
220
0.85
226.83
1
226.83
XLPE
4C
185
469
0.82
0.7
0.57
269.21
320
139
HVAC-1
ELECTRIC DUCT HEATER (AC/DC ROOM)
45.000
3
220
0.85
138.93
1
138.93
XLPE
4C
70
247
0.91
0.7
0.64
157.34
200
140
HVAC-1
SUPPLY FAN- TUNNEL A1 (380KV CONTROL CABELS TUNNEL)
2.237
3
220
0.85
6.91
1
6.91
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
141
HVAC-1
EXHAUST FAN- TUNNEL A1 (380KV CONTROL CABELS TUNNEL)
2.237
3
220
0.85
6.91
1
6.91
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
142
HVAC-1
SUPPLY FAN- TUNNEL B1 (132KV CONTROL CABELS TUNNEL)
2.237
3
220
0.85
6.91
1
6.91
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
143
HVAC-1
EXHAUST FAN- TUNNEL B1 (132KV CONTROL CABELS TUNNEL)
2.237
3
220
0.85
6.91
1
6.91
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
HVAC PANEL-2 144
HVAC-2
PACU-1A (DUTY)
100.090
3
220
0.85
309.01
1
309.01
XLPE
4C
240
551
0.82
0.7
0.57
316.27
400
145
HVAC-2
PACU-2A (DUTY)
100.090
3
220
0.85
309.01
2
154.51
XLPE
4C
185
469
0.82
0.7
0.57
269.21
400
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
Saudi Electricity Company Central Operating Area
LV AC CABLE SIZING CALCULATION VOLTAGE DROP LIMIT ACDB TO VARIUOS LOADS ACDB TO OLP/ILP ACDB TO SDB SDB TO VARIOUS LOADS
S.No.
From
To
4.2 1.6 1.6 2.6
% % % %
KW
Phase
Derating Factors: k1 = Variation in air temperature -Indoor: 40 °C k1 = Variation in air temperature -Outdoor: 50 °C k2 = Group rating factor
%VD = (Voltage Drop / S VOLTAGE DROP (3Ph) VOLTAGE DROP (1Ph) I = Current in Amp. L = Route length in met
Cables are laid on racks System Voltage =
VOLT
Amp
No. of cables per ph.
I req. Amp
Type
Core
mm²
Amp
I
PF
220 / 127 VAC Selected Cable
DERATING FACTORS Over K1 K2 All
derated current Amp
C.B current Amp
135
HVAC-1
PACU-1A (DUTY)
68.300
3
220
0.85
210.87
1
210.87
XLPE
4C
150
407
0.82
0.7
0.57
233.62
320
136
HVAC-1
PACU-2A (DUTY)
73.470
3
220
0.85
226.83
1
226.83
XLPE
4C
185
469
0.82
0.7
0.57
269.21
320
137
HVAC-1
PACU-1B (STANDBY)
68.300
3
220
0.85
210.87
1
210.87
XLPE
4C
150
407
0.82
0.7
0.57
233.62
320
138
HVAC-1
PACU-2B (STANDBY)
73.470
3
220
0.85
226.83
1
226.83
XLPE
4C
185
469
0.82
0.7
0.57
269.21
320
139
HVAC-1
ELECTRIC DUCT HEATER (AC/DC ROOM)
45.000
3
220
0.85
138.93
1
138.93
XLPE
4C
70
247
0.91
0.7
0.64
157.34
200
140
HVAC-1
SUPPLY FAN- TUNNEL A1 (380KV CONTROL CABELS TUNNEL)
2.237
3
220
0.85
6.91
1
6.91
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
141
HVAC-1
EXHAUST FAN- TUNNEL A1 (380KV CONTROL CABELS TUNNEL)
2.237
3
220
0.85
6.91
1
6.91
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
142
HVAC-1
SUPPLY FAN- TUNNEL B1 (132KV CONTROL CABELS TUNNEL)
2.237
3
220
0.85
6.91
1
6.91
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
143
HVAC-1
EXHAUST FAN- TUNNEL B1 (132KV CONTROL CABELS TUNNEL)
2.237
3
220
0.85
6.91
1
6.91
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
HVAC PANEL-2 144
HVAC-2
PACU-1A (DUTY)
100.090
3
220
0.85
309.01
1
309.01
XLPE
4C
240
551
0.82
0.7
0.57
316.27
400
145
HVAC-2
PACU-2A (DUTY)
100.090
3
220
0.85
309.01
2
154.51
XLPE
4C
185
469
0.82
0.7
0.57
269.21
400
146
HVAC-2
PACU-3A (DUTY)
100.090
3
220
0.85
309.01
1
309.01
XLPE
4C
240
551
0.82
0.7
0.57
316.27
400
147
HVAC-2
PACU-1B (STANDBY)
100.090
3
220
0.85
309.01
1
309.01
XLPE
4C
240
551
0.82
0.7
0.57
316.27
400
148
HVAC-2
PACU-2B (STANDBY)
100.090
3
220
0.85
309.01
2
154.51
XLPE
4C
185
469
0.82
0.7
0.57
269.21
400
CE-113347, REV.01
22 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
Saudi Electricity Company Central Operating Area
LV AC CABLE SIZING CALCULATION VOLTAGE DROP LIMIT ACDB TO VARIUOS LOADS ACDB TO OLP/ILP ACDB TO SDB SDB TO VARIOUS LOADS
S.No.
From
To
149
HVAC-2
PACU-3B (STANDBY)
150
HVAC-2
151
4.2 1.6 1.6 2.6
% % % %
KW
Phase
Derating Factors: k1 = Variation in air temperature -Indoor: 40 °C k1 = Variation in air temperature -Outdoor: 50 °C k2 = Group rating factor
%VD = (Voltage Drop / S VOLTAGE DROP (3Ph) VOLTAGE DROP (1Ph) I = Current in Amp. L = Route length in met
Cables are laid on racks System Voltage =
VOLT
PF
220 / 127 VAC
Amp
No. of cables per ph.
I req. Amp
Type
Core
mm²
Amp
I
Selected Cable
DERATING FACTORS Over K1 K2 All
derated current Amp
C.B current Amp
100.090
3
220
0.85
309.01
1
309.01
XLPE
4C
240
551
0.82
0.7
0.57
316.27
400
SUPPLY FAN- TUNNEL A2 (380KV CONTROL CABELS TUNNEL)
2.237
3
220
0.85
6.91
1
6.91
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
HVAC-2
EXHAUST FAN- TUNNEL A2 (380KV CONTROL CABELS TUNNEL)
2.237
3
220
0.85
6.91
1
6.91
XLPE
4C
16
96
0.91
0.45
0.41
39.31
20
152
HVAC-2
SUPPLY FAN- TUNNEL A3 (380KV O/G CABLES TUNNEL)
2.237
3
220
0.85
6.91
1
6.91
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
153
HVAC-2
EXHAUST FAN- TUNNEL A3 (380KV O/G CABLES TUNNEL)
2.237
3
220
0.85
6.91
1
6.91
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
HVAC PANEL-3 154
HVAC-3
PACU-1A (DUTY) 132KV GIS HALL
65.170
3
220
0.85
201.20
1
201.20
XLPE
4C
120
355
0.82
0.7
0.57
203.77
320
155
HVAC-3
PACU-2A (DUTY) 132KV GIS HALL
65.170
3
220
0.85
201.20
1
201.20
XLPE
4C
120
355
0.82
0.7
0.57
203.77
320
156
HVAC-3
PACU-3A (DUTY) 132KV GIS BASEMENT
70.880
3
220
0.85
218.83
1
218.83
XLPE
4C
150
407
0.82
0.7
0.57
233.62
320
157
HVAC-3
PACU-1B (STANDBY) 132KV GIS HALL
65.170
3
220
0.85
201.20
1
201.20
XLPE
4C
120
355
0.82
0.7
0.57
203.77
320
158
HVAC-3
PACU-2B (STANDBY) 132KV GIS HALL
65.170
3
220
0.85
201.20
1
201.20
XLPE
4C
120
355
0.82
0.7
0.57
203.77
320
159
HVAC-3
PACU-3B (STANDBY) 132KV GIS BASEMENT
70.880
3
220
0.85
218.83
1
218.83
XLPE
4C
150
407
0.82
0.7
0.57
233.62
320
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
Saudi Electricity Company Central Operating Area
LV AC CABLE SIZING CALCULATION VOLTAGE DROP LIMIT ACDB TO VARIUOS LOADS ACDB TO OLP/ILP ACDB TO SDB SDB TO VARIOUS LOADS
S.No.
From
To
149
HVAC-2
PACU-3B (STANDBY)
150
HVAC-2
151
4.2 1.6 1.6 2.6
% % % %
KW
Phase
Derating Factors: k1 = Variation in air temperature -Indoor: 40 °C k1 = Variation in air temperature -Outdoor: 50 °C k2 = Group rating factor
%VD = (Voltage Drop / S VOLTAGE DROP (3Ph) VOLTAGE DROP (1Ph) I = Current in Amp. L = Route length in met
Cables are laid on racks System Voltage =
VOLT
Amp
No. of cables per ph.
I req. Amp
Type
Core
mm²
Amp
I
PF
220 / 127 VAC Selected Cable
DERATING FACTORS Over K1 K2 All
derated current Amp
C.B current Amp
100.090
3
220
0.85
309.01
1
309.01
XLPE
4C
240
551
0.82
0.7
0.57
316.27
400
SUPPLY FAN- TUNNEL A2 (380KV CONTROL CABELS TUNNEL)
2.237
3
220
0.85
6.91
1
6.91
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
HVAC-2
EXHAUST FAN- TUNNEL A2 (380KV CONTROL CABELS TUNNEL)
2.237
3
220
0.85
6.91
1
6.91
XLPE
4C
16
96
0.91
0.45
0.41
39.31
20
152
HVAC-2
SUPPLY FAN- TUNNEL A3 (380KV O/G CABLES TUNNEL)
2.237
3
220
0.85
6.91
1
6.91
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
153
HVAC-2
EXHAUST FAN- TUNNEL A3 (380KV O/G CABLES TUNNEL)
2.237
3
220
0.85
6.91
1
6.91
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
HVAC PANEL-3 154
HVAC-3
PACU-1A (DUTY) 132KV GIS HALL
65.170
3
220
0.85
201.20
1
201.20
XLPE
4C
120
355
0.82
0.7
0.57
203.77
320
155
HVAC-3
PACU-2A (DUTY) 132KV GIS HALL
65.170
3
220
0.85
201.20
1
201.20
XLPE
4C
120
355
0.82
0.7
0.57
203.77
320
156
HVAC-3
PACU-3A (DUTY) 132KV GIS BASEMENT
70.880
3
220
0.85
218.83
1
218.83
XLPE
4C
150
407
0.82
0.7
0.57
233.62
320
157
HVAC-3
PACU-1B (STANDBY) 132KV GIS HALL
65.170
3
220
0.85
201.20
1
201.20
XLPE
4C
120
355
0.82
0.7
0.57
203.77
320
158
HVAC-3
PACU-2B (STANDBY) 132KV GIS HALL
65.170
3
220
0.85
201.20
1
201.20
XLPE
4C
120
355
0.82
0.7
0.57
203.77
320
159
HVAC-3
PACU-3B (STANDBY) 132KV GIS BASEMENT
70.880
3
220
0.85
218.83
1
218.83
XLPE
4C
150
407
0.82
0.7
0.57
233.62
320
160
HVAC-3
SUPPLY FAN- TUNNEL B2 (132KV O/G CABLES TUNNEL)
2.237
3
220
0.85
6.91
1
6.91
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
161
HVAC-3
EXHAUST FAN- TUNNEL B2 (132KV O/G CABLES TUNNEL)
2.237
3
220
0.85
6.91
1
6.91
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
162
HVAC-3
SUPPLY FAN- TUNNEL B3 (132KV O/G CABLES TUNNEL)
2.237
3
220
0.85
6.91
1
6.91
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
CE-113347, REV.01
23 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
Saudi Electricity Company Central Operating Area
LV AC CABLE SIZING CALCULATION VOLTAGE DROP LIMIT ACDB TO VARIUOS LOADS ACDB TO OLP/ILP ACDB TO SDB SDB TO VARIOUS LOADS
S.No.
163
From
HVAC-3
To
EXHAUST FAN- TUNNEL B3 (132KV O/G CABLES TUNNEL)
4.2 1.6 1.6 2.6
% % % %
KW
Phase
Derating Factors: k1 = Variation in air temperature -Indoor: 40°C k1 = Variation in air temperature -Outdoor: 50°C k2 = Group rating factor
%VD = (Voltage Drop / S VOLTAGE DROP (3Ph) VOLTAGE DROP (1Ph) I = Current in Amp. L = Route length in met
Cables are laid on racks System Voltage =
VOLT
PF
220 / 127 VAC
Amp
No. of cables per ph.
I req. Amp
Type
Core
mm²
Amp
I
Selected Cable
DERATIN G FACTORS Over K1 K2 All
der ated current Amp
C.B current Amp
2.237
3
220
0.85
6.91
1
6.91
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
TELECOM ROOM ACDB 164
TELECOM ACDB
SMK PANELS LIGHT & HEATER
10.36
3
220
0.85
32.00
1
32.00
XLPE
4C
16
96
0.91
0.7
0.64
61.15
40
165
TELECOM ACDB
FMK PANELS LIGHT & HEATER
10.36
3
220
0.85
32.00
1
32.00
XLPE
4C
16
96
0.91
0.7
0.64
61.15
40
166
TELECOM ACDB
RTU PANELS LIGHT & HEATER
10.36
3
220
0.85
32.00
1
32.00
XLPE
4C
16
96
0.91
0.7
0.64
61.15
40
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
Saudi Electricity Company Central Operating Area
LV AC CABLE SIZING CALCULATION VOLTAGE DROP LIMIT ACDB TO VARIUOS LOADS ACDB TO OLP/ILP ACDB TO SDB SDB TO VARIOUS LOADS
S.No.
163
From
HVAC-3
To
EXHAUST FAN- TUNNEL B3 (132KV O/G CABLES TUNNEL)
4.2 1.6 1.6 2.6
% % % %
KW
Phase
Derating Factors: k1 = Variation in air temperature -Indoor: 40°C k1 = Variation in air temperature -Outdoor: 50°C k2 = Group rating factor
%VD = (Voltage Drop / S VOLTAGE DROP (3Ph) VOLTAGE DROP (1Ph) I = Current in Amp. L = Route length in met
Cables are laid on racks System Voltage =
VOLT
Amp
No. of cables per ph.
I req. Amp
Type
Core
mm²
Amp
I
PF
220 / 127 VAC Selected Cable
DERATIN G FACTORS Over K1 K2 All
der ated current Amp
C.B current Amp
2.237
3
220
0.85
6.91
1
6.91
XLPE
4C
10
73
0.91
0.45
0.41
29.89
20
TELECOM ROOM ACDB 164
TELECOM ACDB
SMK PANELS LIGHT & HEATER
10.36
3
220
0.85
32.00
1
32.00
XLPE
4C
16
96
0.91
0.7
0.64
61.15
40
165
TELECOM ACDB
FMK PANELS LIGHT & HEATER
10.36
3
220
0.85
32.00
1
32.00
XLPE
4C
16
96
0.91
0.7
0.64
61.15
40
166
TELECOM ACDB
RTU PANELS LIGHT & HEATER
10.36
3
220
0.85
32.00
1
32.00
XLPE
4C
16
96
0.91
0.7
0.64
61.15
40
CE-113347, REV.01
24 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
لكهرباء سعودية ةشر طىو مانطقة أ upply Voltage) x 100 = √3 x I x L ( R COS Φ + X SIN Φ ) = 2 x I x L ( R COS Φ + X SIN Φ ) er.
Length m
R
X
Ohm/kM
Ohm/kM
52
0.16
16
%VD
Remarks
0.09
1.56
FL Current