Brian Kim N. Benoza BSEE-4th year In the design of electrical power systems, the ANSI standard device numbers (ANSI /IEEE Standard C37.2 Standard for Electrical Power System Device Function Numbers, Acronyms, and Contact Designations ) identifies the features of a protective device such as a relay or circuit breaker. These types of devices protect electrical systems and components from damage when an unwanted event occurs, such as an electrical fault. Device numbers are used to identify the functions of devices shown on a schematic diagram. Function descriptions are given in the standard. One physical device may correspond to one function number, for example "29 Isolating Switch", or a single physical device may have many function numbers associated with it, such as a numerical protective relay. Suffix and prefix letters may be added to further specify the purpose and function of a device. ANSI/IEEE C37.2-2008 is one of a continuing series of revisions of the standard, which originated in 1928. ANSI Device Numbers Apparatus
50G - Instantaneous Earth Over Current Relay (Neutral CT Method)
50N - Instantaneous Earth Over Current Relay (Residual Method)
50BF - Breaker failure
51 – AC Inverse Time Overcurrent Relay
51G- AC Inverse Time Earth Overcurrent Relay (Neutral CT Method)
51N- AC Inverse Time Earth Overcurrent Relay (Residual Method)
37 – Undercurrent or Underpower Relay
38 – Bearing Protective Device
39 – Mechanical Condition Monitor
40 – Field (over/under excitation) Relay
41 – Field Circuit Breaker
52a- AC Circuit Breaker Position (Contact Open when Breaker Open)
42 – Running Circuit Breaker
52b- AC Circuit Breaker Position (Contact Closed when Breaker Open)
43 – Manual Transfer or Selector Device
53 – Exciter or DC Generator Relay
44 – Unit Sequence Starting Relay
54 – Turning Gear Engaging Device
45 – Abnormal Atmospheric Condition Monitor
55 – Power Factor Relay
56 – Field Application Relay
52 – AC Circuit Breaker
57 – Short-Circuiting or Grounding Device
58 – Rectification Failure Relay
59 – Overvoltage Relay
60 – Voltage or Current Balance Relay
61 – Density Switch or Sensor
62 – Time-Delay Stopping or Opening Relay
77 – Telemetering Device
78 – Phase-Angle Measuring Relay or "Out-of-Step" Relay
79 – AC Reclosing Relay (Auto Reclosing)
80 – Flow Switch
81 – Frequency Relay
82 – DC Reclosing Relay
63 – Pressure Switch
64 – Ground Detector Relay
64R - Restricted earth fault
64S - Stator earth fault
65 – Governor
86 – Lockout Relay/Master Trip
66 – Notching or Jogging Device
87 – Differential Protective Relay
67 – AC Directional Overcurrent Relay
88 – Auxiliary Motor or Motor Generator
68 – Blocking Relay
89 – Line Switch
69 – Permissive Control Device
90 – Regulating Device
70 – Rheostat
91 – Voltage Directional Relay
71 – Liquid Level Switch
92 – Voltage and Power Directional Relay
72 – DC Circuit Breaker
93 – Field Changing Contactor
73 – Load-Resistor Contactor
94 – Tripping or Trip-Free Relay
74 – Alarm Relay
96 – Busbar Trip Lockout relay
75 – Position Changing Mechanism
150 – Earth Fault Indicator
76 – DC Overcurrent Relay
83 – Automatic Selective Control or Transfer Relay 84 – Operating Mechanism 85 – Communications,Carrier or PilotWire Relay
ANSI Devices used in 5 MVA Transformers Fuses and switchgear E-rated power fuses are typically used in fused switches serving transformers. The purpose of the fuse is to allow for full use of the transformer and to protect the transformer and cables from faults. To accomplish this, the fuse curve should be to the right of the transformer inrush point and to the left of the cable damage curve. Typically, the fuse will cross the transformer damage curve in the long time region (overcurrent region). The secondary main device provides overcurrent protection for the circuit. “E” fuse ratings should always be greater than the transformer full load amps (FLA). The cable damage curve must be above the maximum fault current at 0.01 s. For transformers 3 MVA and less, standard overcurrent protection schemes for MV switchgear breakers should include an instantaneous and overcurrent combination relay (device 50/51). For transformers greater than 5 MVA, protection schemes become more complex. IEEE device numbers from IEEE C37.2 are used to outline the protection scheme. Transformer MV breakers may include the following protective device numbers: In MV systems, current transformers (CTs) connect protective or metering devices. CTs interface the electronic device and the MV primary system. The MV primary system voltage and current levels are dangerously high and cannot be connected directly to a relay or meter. The CTs provide isolation from the cable’s high voltage and current levels and translate the primary current to a signal level that can be handled by delicate relays/meters. The rated secondary current is commonly 5 amp, though lower currents such as or 1 amp are not uncommon. Protective relay’s CTs are expected to deliver about 5 amps or less under healthy load conditions. The current will go to a high value when a fault occurs. Per ANSI C57.13, normal protective CT class secondary should withstand up to 20 times for a short period of times under fault conditions. As a consequence, protective class CTs are accurate enough to drive a set of indication instruments, but will not be good enough for revenue class summation energy metering.
Thank you for interesting in our services. We are a non-profit group that run this website to share documents. We need your help to maintenance this website.