GM8806A-P6 USER’S MANUAL

GM8806A-P6130101 48010609221143 110606130002

©2011 , Shenzhen General Measure Technology Co., Ltd reserve all copyright. With Without out permi permiss ssio ion n from from Shen Shenzh zhen en Gener General al Measu Measure re Technology Co., Ltd , Any corporations or person must not copy, spread, record or translate into other language by any forms. Our compa mpany reserved the right to update user’s r’s manual without additional notice to make perfect for  customers. Thus please visit our website or contact with our  service person to get update information. Website:http://www.szgmt.com  Approved standard:GB/T 7724—2008

Table 1

General Information.............................................................1 1.1 Function 1.1  Function.......................................................................... 1 1.2 Description 1.2  Description..................................................................... 2 1.3 Rear 1.3  Rear illustration............................................................. 3 1.4 Specification 1.4  Specification...................................................................4 1.5 Dimension 1.5  Dimension...................................................................... 5 2   Wiring.....................................................................................6 2.1 Installation 2.1  Installation...................................................................... 6 2.2 Power 2.2  Power connection......................................................... 7 2.3 Load 2.3  Load cell connection.....................................................7 2.4 I/O 2.4  I/O terminals...................................................................9 2.5 Analog 2.5  Analog output connection..........................................10 2.6 Serial 2.6  Serial port connection................................................ 11 3   Calibration...........................................................................12 3.1 Instruction 3.1  Instruction.....................................................................12 3.2 Flow 3.2  Flow chart.....................................................................12 3.3 Millivolt 3.3  Millivolt display ............................................................ 15 3.4 Calibration 3.4  Calibration without weights....................................... 16 3.5 Fast 3.5  Fast zero/gain calibration.......................................... 18 3.6 Parameter 3.6  Parameter table.......................................................... 18 3.7 Parameter 3.7  Parameter record........................................................18 4 Parameter setting.............................................................. 19 4.1 Defination 4.1  Defination..................................................................... 19 4.2 Operation 4.2  Operation parameter table........................................ 21 5 Recipe Recipe setting setting.................................................................... 25 5.1 Recipe 5.1  Recipe number ............................................................ ............................................................25 5.2 Recipe 5.2  Recipe configuration.................................................. 25 5.3 Recipe 5.3  Recipe parameter table............................................. 26 6   Operation............................................................................ 39 6.1 Operating 6.1  Operating status..........................................................39 6.2 Batching 6.2  Batching times setting................................................39

7

8

9

6.3 Sort batching in turn................................................... 40 6.4 Check and clear accumulative total .........................41 6.5 Manual discharging.................................................... 42 6.6 Manual zeroing............................................................42 6.7 Save for power down................................................. 42 6.8 Compensation............................................................. 43 6.9 Free fall compensation.............................................. 43 6.10 Discharging monitor ................................................. 43 6.11 Batching monitor ....................................................... 43 6.12 I/O testing...................................................................44 6.13 I/O defination............................................................. 45 6.14 Display testing...........................................................48 6.15 Reset.......................................................................... 49 6.16 Backup....................................................................... 50 6.17 Restore backup.........................................................51 6.18 Analog calibration & self-definition........................ 51 6.18.1 Analog calibration.....................................51 6.18.2  Analog self-definition................................53 6.19 Password................................................................... 54 6.20 Password setting...................................................... 54 6.21  Operation mode..................................................55 6.22 Serial port upgrade.............................................56 Automatical batching........................................................ 57 7.1 Sketch map..................................................................57 7.2 Description................................................................... 57 Serial port communication............................................... 59 8.1 RS protocol.................................................................. 59 8.2 TOLEDO  protocol.................................................82 8.3 RE protocol.................................................................. 83 8.4 MODBUS protocol......................................................84 Error and alarm message...............................................111

GM8806A-P6 Batching controller 

1 General information GM8806A-P6 batching controller is a kind of weighing control instruments to control automatic batching machine at high accuracy and powerful function, which widely used in various batching systems for concrete, bitumen, fertilizer, feeding stuff and so on. 1.1 Function  Small

volume, unique design, easy operation; Suit to all of load cells at bridge-type resistance strain gauge;  14 I/O( 4 input / 10 output);  Full Digital Calibration;  Fast, moderate and slow feeding with “Jog feeding”;  Multi digital filter;  Automatical modify for free fall; Full serial ports function, to achieve all the functions of  the indicator by serial ports;  High precision 16bit DA analog output(optional);  Automatical compensation;  Digital calibration with or without weights;  Password for calibration, operation parameters etc.;  Automatic zeroing when power up;  Automatic zero tracking;  6 kinds of material batching at Maximum; Function of two-way isolation serial ports of RS232/RS485 which is convenient to communicate with computer, printer and/or a second display.

1

GM8806A-P6 Batching controller 

1.2 Description

P 1-1

Keypad : Display value when zeroing or exit present function. : Parameters are optional. : Set parameter mode. : Enter parameters or calibration or confirmation.

Status indication: : Light in batching. /

: Both SP1 and SP2 light in fast feeding; SP1 light

in moderate feeding; SP2 light in slow feeding. : Light in discharging. : Light for zero when weight is among 0±1/4d. : Light for stability when weight is in stable range. Display: Main display:6digits, display weight and parameters. Sub-display:6digits, display G.W. and parameters. Set point display:1 digit, display batching numbers. 2

GM8806A-P6 Batching controller 

1.3 Rear illustration

P 1-2

I/O input terminals 2 I/O output terminals 3 Load cell terminals 4 Serial port / analog terminals 5 Power connection 6 Fuse socket 1

3

GM8806A-P6 Batching controller 

1.4 Specification Common: Power supply:AC90V

260V 50Hz (or 60Hz) ± 2%

Filter :Inside Working temperature:-10

40

Max humidity:90%R.H without dew Power consumption:About 10W Analog: Load cell power :DC5V 300mA (Max) Input impedance:10MΩ Zero steady range:0.02

9mV

Input sensitivity:0.01uV/d Gain input range:0.2

10mV

Transfer mode:Sigma - Delta A/D conversion speed:120times/sec Non-linearity:0.01%F.S Gain drift:10PPM/ Display Precision:1/30000 Digital: Weight display:6digits red high-brightness LED Minus display:“-” Overload display:“OFL” Decimal point:5kinds (optional) Keypads: 4 beeping keypads 4

GM8806A-P6 Batching controller 

1.5 Dimension

5

GM8806A-P6 Batching controller 

2

Wiring

2.1 Installation 1.   Cut hole as left size

in the suitable place of  control box.

2.   Screw open in four 

corners, then dismantle mounting plates.

3. Install indicator in the front of control box.

4. Insert mounting plates on both sides and then screw tightly.

P 2-1

6

GM8806A-P6 Batching controller 

2.2 Power connection GM8806A-P6   batching controller connects power as follows:

P 2-2

1. AC power must connect with ground; 2. Please do not connect indicator’s earth line with other huge electronic equipment directly.

2.3 Load cell connection EX+: Excitation+ SN-: Sense-  

6 wires 4-wires

EX-: Excitation- SN+: Sense+ SIG+: Signal+   SIG-: Signal-

EX+

SN+

EX+

EX-

SN-

EX-

1) 6 wires connection:

P 2-3

7

SIG+

SIG-

Shield

SIG+

SIG-

Shield

GM8806A-P6 Batching controller 

2) 4 wires connection:

P 2-4

1. As load cell output sensitive analog signal, please use shield cable to separate with other  cables, especially AC power; 2. 4 wires connection is suitable for short distance and stable temperature or low precision field, otherwise use 6 wires connection. 3. For more load cells parallel connection, their  sensitivity (mV/V) should be same.

8

GM8806A-P6 Batching controller 

2.4 I/O terminals GM8806A-P6 Weighing indicators transfer data by optoelectronic isolation technology, thus need 24 V DC outside as power supply, which anode connect with indicator  24V+, and cathode with 24V- through the COM1 (DC+) and the CO M2 (DC -) . The inp ut sig na l is low level effective, and the output is transistor open-collector output, which driving current can reach 300mA. I/O definition as follows:

P 2-5

Indicator input terminal connection:

P 2-6

Indicator output terminal connection:

P 2-7 9

GM8806A-P6 Batching controller 

I/O tolerant definition as follows: Ou tpu t

In pu t

OUT1

M a t e r i a l n o .1

IN1

OUT2

Material no. 2

IN2

OUT3

Material no. 3

IN3

OUT4

Material no. 4

IN4

OUT5

Coarse feeding

OUT6

Moderate feeding

OUT7

Fine feeding

OUT8

 

 

Manual discharging Ru n

 

Pause  

Stop

Discharging

OUT9

O v e r t o l e r a nc e

OUT10

Ru n

2.5 Analog output connection  Analog output two kinds: voltage and electric current. For voltage output, 0-5V/0-10V/-5-5V/-10-10V is optional for  voltage output ; 4-20mA/0-20mA/0-24mA is optional for  electric current output. Define terminals as follows:

P 2-8

Note: Analog output is optional function, please declare if  need when place orders. 10

GM8806A-P6 Batching controller 

2.6 Serial port connection Serial port(RS485 or RS232) connection as follows:

P 2-9 RS232 connection:

P 2-10

RS485 connection:

P 2-11

11

GM8806A-P6 Batching controller 

3

Calibration

3.1 Instruction GM8806A-P6 batching controller need calibrate at beginning of operation or changing any parts on weighing system or non-suitable application for user. The calibration can define radix point, minimum scale division, maximum scale capacity, zero and gain, etc. User can press

to enter next or press

to

save setting to only change one parameter, and then press

to exit.

3.2 Flow chart

Press to display CAL , and then press to

enter  

password. Input correct password, when display “CAL ON” one second, then enter to set radix point automatically.

12

GM8806A-P6 Batching controller 

1) Press set radix point (0~0.0000 5 kinds optional),

press to save and enter  mini division. 2) If not change radix point, press directly to enter   mini division. 1) Press division(1~50

to set mini 6kinds

optional) , press to save and enter max. capacity. 2) If not change mini division, press directly to enter   max. capacity. 1) Input max. capacity(≤mini division × 30000) , press to save and enter millivolt display. 2) If not change, press to enter millivolt display directly. 1) Select suitable sensitivity based on load cell, press to save and enter  millivolt display. Otherwise to press directly to enter   millivolt display.

13

GM8806A-P6 Batching controller 

1)

When load cell output

millivolt value, press to enter zero calibration directly. 2) The display value is similar  with millivolt from SIG+/SIGterminals. See Character 3.3 for details. 1) When scale platform is stable, press to take present weight as zero , and enter gain calibration. 2 ) Press to reserve original zero and enter gain calibration. 1) Gain calibration as the left chart. ▲When calibration with weights, please record zero millivolt, gain millivolt and weight value in list. If no weights, user will calibrate according to these data. 2) Press to enter   password directly, no gain calibration. 1) See Character 5.11 to set password, then press

to

exit calibration and return. 2)

If

press 14

not

set

password,

directly to return.

GM8806A-P6 Batching controller 

Normal working status.

3.3 Millivolt display This function is mainly used to test weighing system, four-corner position-error of force-transmitted equipment and load cell’s linearity. 1. Test weighing system (1) If the indicator display variational millivolt value according to add weight, thus indicate load cells are connected correctly and force-transmitted equipment is operated normally. (2) If the indicator display OFL (or –OFL), thus indicate the weight is too heavy (or too light), then need unload (or  add) the weight. But if always display OFL (or –OFL) after  changing weight, maybe the following reason cause: a. Please check force-transmitted equipment. b. Please check the load cell’s connection. c. Please check Load cells. 2. Test

four-corner

position-error

of

force-transmitted

equipment Please load same weight on scale’s every corner and record individual millivolt value. If the values are obviously different, please adjust force-transmitted equipment. 3. Test load cell’s linearity 15

GM8806A-P6 Batching controller 

Please load several same weight values within the weighing capacity and record relevant millivolt value after  zeroing every time; if the discrepancy is bigger among millivolt values, thus indicate that the load cell’s linearity is not

good,

need

change

new

load

cell

or

force-transmitted equipment.

3.4 Calibration without weights Calibration without weights is only for urgency. If  change new load cells or indicator, or adjust weighing system, calibration without weights is not correct.

16

adjust

GM8806A-P6 Batching controller 

17

GM8806A-P6 Batching controller 

3.5 Fast zero / gain calibration In weighing status, press for long time, when display password input, then input password correctly and enter zero calibration. See Character 6.19 for details.

3.6 Calibration parameter table Sign Point 1 d= CP St SE

Parameter  

Decimal point Mini division Max capacity   System millivolt Sensitivity

E SCAL

Z er o

 AddLd(d)

Gain Set password

PASS

Type  

5

 

Division 0,0.0,0.00,0.000, 0.0000 1,2,5,10,20,50

6

Initial value 0 1

≤min mini div divisio ision n×300 ×3000 00

100 10000

2,3

2(mV/V)

2

 

000000

3.7 Calibration parameter record Parameter

Valued

Date

Remark

Decimal point position Mini division Max capacity Load cell sensitivity Password setting

List(calibration with weights): Times

Zero millivolt (mV)

Gain millivolt (mV)

Weights   (Kg)

1 2 3

18

Da Date

Remark

GM8806A-P6 Batching controller 

4

Para Parame mete terr sett settiing

Note: Press

to switch among

parameters; press

to enter next

menu; press to return previous menu. See Chapter  4.1 for 4.1  for details.

4.1 Defination Press

to select parameters, then press

to set pa parameters, af after th that, pr press setting. 1) Optional parameter setting Set“parameter  5 ”(ON)for example:

19

and to save

GM8806A-P6 Batching controller 

1. Press sparkle “OFF “OFF”. ”.

, then sub-display

2. Press show“ON show“ON”. ”.

, then sub-display

3. Press need set re s s

to save setting. If not other parameters,

to return.

2) Numerical parameter setting Set “parameter  “parameter 7 7”(as 35)for example: 1. Press in the left.

, sub-display sparkle “5”

2. Press

till sub-displa splay y show “3”,

then press right one.

3. Press ress then press

20

,sparkle move to the

till sub-dis display play show“ ow“5”, to save and finish.

GM8806A-P6 Batching controller 

4.2 Operation parameter table No.

Para.

1 2

3

3.1

01

99

  1200~57   600

 

rS/rE/tt/ bUS

  Read/Co   nt

Initial 01

Scale no.

9600

Baud rate

rS

Cont

3.1.1

0~5

1

3.1

Rtu/Asc

Rtu

3.1.1

Hi Lo Lo Hi

Description

Hi Lo

Communication mode: Read/Cont are optional in item 3.1 for   rS/tt/rE mode; Rtu/Asc is optional in item 3.1 for Bus mode. Rs/Re mode: READ:command; CONT:continue Serial port data-sent speed for   CONT at rS/tt/rE mode: 1-5:means 10-50ms; 0:means one character time. MODBUS communication mode: Rtu or  Asc MODBUS dual-byte register  storage turn for Rtu at MODBUS: Hi Lo:High byte in the front, low byte at back; Lo Hi:Low byte in the front, high byte at back. 21

GM8806A-P6 Batching controller 

4

18N2 18E1 18O1 18N1 17N2 17E1 17O1

18E1

Data format: ; 18N2 (R / C / B_r   optional) ; 18E1 (R / C / B_r   optional) ; 18O1 (R / C / B_r   optional) ; 18N1 (R / C / B_r   optional) ; 17N2 (R / C optional) ; 17E1 (R / C optional) 17O1 (R / C optional).

5

ON/OFF

OFF

Automatic zeroing when power on

6

00

99

0

Zero tacking range(00~99d optional). If setting 0, not zero tracking.

7

01

99

50

Zeroing range(01%~99% of  full capacity).

8

01

99

03

Stability criterion range(01~ 99d optional).

5

Digital filter parameter  0:no filter ;9:strongest filter 

0

Stability filter: Second filter  based on first one: 0:no filter ;9:strongest filter 

9

10

11

0~9

0~9

b_zero /   b_zero b_tare

Zeroing/tare-off operation before batching: b_tare:tare off ; b_zero:zeroing. 22

GM8806A-P6 Batching controller 

11.1

12

13

14

15

ON / OFF

groSSd/ nEtd/ nonCEd

ON / OFF

1~6

  ON/OFF/ CONT

OFF

Switch for Zeroing/tare-off  operation before batching: ON:operate; OFF shut.

groSS d

 Analogue display mode options: groSSd:Gross weight mode output nEtd:Net weight mode output nonCEd:Current weight mode output

OFF

6

OFF

Switch to count manual discharging into accumulative total: ON:yes;OFF not. Material numbers. For  example, 1 means only to batch one kind of material. Save when power off : ON: Restore after restart again when power off; OFF: not restore. CONT: Restart after power  off and enter into option of  “resume or not resume to the saved status”.

23

GM8806A-P6 Batching controller 

16

4-20 / 0-20 / 0-24 / 0-5 / 0-10 / -5-5 / -10-10/ USEr 

17   ON/OFF

18   ON/OFF

4-20

 Analog output: 4-20 4-20mA 0-20 0-20 mA 0-24 0-24 mA 0-5 0-5V 0-10 0-10V -5-5 -5-5V -10-10 -10-10V USEr: User define mode

OFF

On: When batching finished, indicator will send current batching result automatically through the serial port(RS)

OFF

On: Negative gross weight zeroing in stop status, stable,negative gross weight and within zeroing range.

19   UPDATE   None 20

ON / OFF

20.1

******

OFF

Serial ports update Password protection switch for working parameters Password setting. See Character 6.20 for details.

24

GM8806A-P6 Batching controller 

5

Recipe setting

5.1 Recipe number  GM8806A-P6 can store 40pcs recipes related number  01~40, which can be configured by user.

5.2 Recipe configuring 1) Optional recipe parameters  Alternate between recipe parameters F1~F12 by

,

enter by and return by . 2) Configure recipe parameters In recipe selection interface, user can press enter to check or change the parameters. 25

to

GM8806A-P6 Batching controller 

5.3 Recipe parameter table No.

Pa ra .

In i ti al

F1

U_ L Set

No ne

1.A1

xx xx x x

00 0 00 0

Target value of material no.1.

00 00 0 0

Leading quantity of fast feeding for material no.1;In fixing value,if weight ≥ target value - leading quantity of fast feeding,then fast feeding stop.

00 00 0 0

Leading quantity of  moderate feeding for  material no.1;In fixing value,if weight ≥ target value - leading quantity of  fast feeding,then moderate feeding stop.

1.A2

1.A3

xx xx x x

xx xx x x

De s cri p ti o n None

1.A4

xx xx x x

00 00 0 0

Free fall value of material no.1;In fixing value,if  weight ≥ target value – free fall value,then slow feeding stop.

1.b1

xx xx x x

00 00 0 0

Target value of material no.2.

00 00 0 0

Leading quantity of fast feeding for material no.2;In fixing value,if weight ≥ target value - leading quantity of fast feeding,then fast feeding stop.

1.b2

xx xx x x

26

GM8806A-P6 Batching controller 

1.b3

xx xx x x

00 00 0 0

Leading quantity of  moderate feeding for  material no.2;In fixing value,if weight ≥ target value - leading quantity of  fast feeding,then moderate feeding stop.

1.b4

xx xx x x

00 00 0 0

Free fall value of material no.2;In fixing value,if  weight ≥ target value – free fall value,then slow feeding stop.

1.C1

xx xx x x

00 00 0 0

Target value of material no.3.

00 00 0 0

Leading quantity of fast feeding for material no.3;In fixing value,if weight ≥ target value - leading quantity of fast feeding,then fast feeding stop.

00 00 0 0

Leading quantity of  moderate feeding for  material no.3;In fixing value,if weight ≥ target value - leading quantity of  fast feeding,then moderate feeding stop.

1.C2

1.C3

xx xx x x

xx xx x x

1.C4

xx xx x x

00 00 0 0

Free fall value of material no.3; In fixing value,if  weight ≥ target value – free fall value,fine feeding stop.

1.d1

xx xx x x

00 00 0 0

Target value of material no.4.

27

GM8806A-P6 Batching controller 

1.d2

1.d3

xx xx x x

xx xx x x

00 00 0 0

Leading quantity of fast feeding for material no.4;In fixing value,if weight ≥ target value - leading quantity of fast feeding,then fast feeding stop.

00 00 0 0

Leading quantity of  moderate feeding for  material no.4;In fixing value,if weight ≥ target value - leading quantity of  fast feeding,then moderate feeding stop.

1.d4

xx xx x x

00 00 0 0

Free fall value of material no.4;In fixing value,if  weight ≥ target value – free fall value,then slow feeding stop.

1.E1

xx xx x x

00 00 0 0

Target value of material no.5.

00 00 0 0

Leading quantity of fast feeding for material no.5;In fixing value,if weight ≥ target value - leading quantity of fast feeding,then fast feeding stop.

00 00 0 0

Leading quantity of  moderate feeding for  material no.5;In fixing value,if weight ≥ target value - leading quantity of  fast feeding,then moderate feeding stop.

1.E2

1.E3

xx xx x x

xx xx x x

28

GM8806A-P6 Batching controller 

1.E4

xx xx x x

00 00 0 0

Free fall value of material no.5;In fixing value,if  weight ≥ target value – free fall value,then slow feeding stop.

1.F1

xx xx x x

00 00 0 0

Target value of material no.6.

00 00 0 0

Leading quantity of fast feeding for material no.6;In fixing value,if weight ≥ target value - leading quantity of fast feeding,then fast feeding stop.

00 00 0 0

Leading quantity of  moderate feeding for  material no.6;In fixing value,if weight ≥ target value - leading quantity of  fast feeding,then moderate feeding stop.

00 00 0 0

Free fall value of material no.6;In fixing value,if  weight ≥ target value – free fall value,then slow feeding stop.

00 00 0 0

Zero value;In fixing value process,if weight ≤ zero value, then start discharging delay timers,shut discharging output after  time t7 is up.

1.F2

1.F3

1.F4

1.G0

xx xx x x

xx xx x x

xx xx x x

xx xx x x

29

GM8806A-P6 Batching controller 

Time setting: press F2

Ti

se t   None

  00.0 99. 9 F2.1   seconds

F2.2

F2.3

F2.4

  00.0 99. 9   seconds

  00.0 99. 9   seconds

  00.0 99. 9   seconds

enter, or press item F3.

to into

00.5

Feeding after time t1: Feeding after time t1 at the beginning of baching.

00.5

No contrast time t2 in fast feeding: When fast feeding within time t2, the batching controller don’t contrast present weight with the value (target value leading quantity of fast feeding).

00.5

No contrast time t3 in moderate feeding: When moderate feeding within time t3, the batching controller don’t contrast present weight with the value (target value - leading quantity of moderate feeding).

00.5

No contrast time t4 in slow feeding: When slow feeding within time t4, the bataching controller don’t contrast present weight with the value (target value - free fall value). 30

GM8806A-P6 Batching controller 

  00.0 99. 9 F2.5   seconds

  00.0 99. 9 F2.6   seconds   00.0 99. 9 F2.7   seconds

F2.8

F2.9

000 999 seconds

000 999 seconds

00.5

Over tolerance checking time t5: Check over  tolerance in stability after  time t5.

00.5

Fixed value time t6   after  time t5 is over, then begin to discharge.

00.5

Shut off discharging after  time t7   when weight is less than zero value.

000

Discharging monitor time t8: shut discharging if  discharging signal is still effective after time t8.

000

Batching monitor time t9 (Fast and slow feeding effective time): alarm output when system haven’t finished batching within time t9. Feeding mode: ON:Fast, moderate and slow feeding individually.

F3

ON/ OF F

Press

OF F

to enter   F3.1;

press to enter  F4. OFF:Fast, moderate and slow feeding together. Press

31

or

to F4.

GM8806A-P6 Batching controller 

F3.1

F3.2

  00.0 99. 9   seconds

  00.0 99. 9   seconds

00.0

Pause time t10 between t10 between fast feeding and moderate feeding: when fast feeding finished, moderate feeding start after time t10. time  t10.

00.0

Pause time t11 t11  between moderate feeding and slow feeding: when moderate feeding finished, slow feeding start after time t11. time  t11. Over/under tolerance alarm: ON

F4

ON/OFF

OFF

press

F4.1;press directly;

to enter   to enter F5

OFF: press or enter F5 directly.

F4.1

F4.2

0.0

0.0

9. 9

9. 9

to

0. 5

Over tolerance percent: When fixed value,if weight ≥ target value + target value × over tolerance percent,so it is over tolerance.

0. 5

Under tolerance percent: When fixed value,if weight ≤ target value - target value x under tolerance percent, so it is under tolerance.

32

GM8806A-P6 Batching controller 

F4.3

F4.4

ON/OFF

  00.0~99.9   seconds

OFF

Pause switch for  Over/under tolerance: ON When over or under  tolerance, pause to wait for  user. Batching controller  display present net weight, so user can press or  input “clear alarm” effective signal, then go on; Also can input “stop” effective signal to return stop state. OFF When over or under  tolerance, batching controller only output alarm message, but not stop.

00.5

Over/under tolerance alarm time t: When t:  When Over/under  tolerance pause is off , batching controller will output alarm within time t. Free fall compensation:

F5

ON/OFF

OFF

ON:Press

to enter  

F5.1;Press directly.

to enter F6 r F6

OFF:Press or enter F6 enter  F6 directly.  directly.

F5.1

00

99

Free fall compensation times: The indicator will make this average as compensation value.

01

33

to

GM8806A-P6 Batching controller 

F5.2

F5.3

00

1

99

3

02

Free fall compensation percent of target value: If  free fall value is more than the percent of target value, the value will not be accounted to average.

2

Free fall compensation range: 1 for 100%;2 for  50%;3 for 25%. Discharging-controlled switch: ON:Press

F6

ON/OFF

to enter  

F6.1;Press

OFF

to enter F7 r F7

directly. OFF:Press

or

to

enter F7 enter  F7 directly  directly,Initial as F6.1=F6.2= OFF.

F6.1

F6.2

ON/OFF

ON/OFF

OFF

Discharging mode switch: ON Discharge directly after  batching one kind of  material. OFF Discharge when all of  material material batching batching finished. finished.

OFF

Discharging-permited switch: ON Discharge till received discharging signal. OFF Discharge directly when finish batching. 34

GM8806A-P6 Batching controller 

Supplement switch: ON:Press F7

ON/OFF

F7.1;Press directly.

OFF

to enter   to enter F8

OFF:Press or enter F8 directly.

F7.1

00

99

to

Jog-feeding supplement times for under tolerance. If  the weight is still under  tolerance, then stop directly.

03

F7.2

  00.0 99. 9   seconds

00.5

Jog-feeding supplement effective time.

F7.3

  00.0 99. 9   seconds

00.5

Jog-feeding supplement alternation time. Jog-feeding output switch: ON:Press

F8

ON/OFF

F8.1;Press directly.

OFF

to enter   to enter F9

OFF:Press or enter F9 directly.

F8.1

  00.0 99. 9   seconds

  00.0 99. 9 F8.2   seconds

to

00.5

Jog-feeding output time: Slow feeding effective time ta every time.

00.5

Jog-feedingoutput time: Slow feeding ineffective time tb every time.

35

GM8806A-P6 Batching controller 

F9

F10

dSP-rE/ dSP-dA/ rdP-S1/ rdP-S3/ dSP-G/ dSP-n/ dSP-P

rdp_fi rdp_s1 rdp_s2 rdP-S3/ dSP-G/ dSP-n/ dSP-P

dsp_re

In stop status,sub-display: dsp_re Recipe no.; dsp_DA  Analog; rdp_s1  Accumulative total for present material; rdp_s3 Total feedling value. dSP-G:Display gross weight; dSP-n:Display Net weight; dSP-P:Display tare weight.

rdp_fi

In run status, sub-display: rdp_fi Target value for  present material; rdp_s1  Accumulative total for present material; rdp_s2 Target value – feeding value for present material; rdp_s3 Total feeding ; dSP-G:Show gross weight; dSP-n:Show Net weight; dSP-P:Show tare weight. Batching compositor  switch: ON:Press

F11

ON/OFF

OFF

F11.1;Press F12 directly.

to enter   to enter 

OFF:Press or enter F12 directly. 36

to

GM8806A-P6 Batching controller 

F11.1

XXXXXX

XXXX sort in turn as 1 2 3 4 5 6  from high to low in turn. For example, if input 65 4231,sort batching in turn from 6# 5# 4# 2# 3# 1#,and XXXX every digits are not same.

123456

Tare weight upper/lower  limitation switch: F12

F12.1

ON/OFF

Tare upper  limitation

OFF

ON:Press

to enter  

F12.1; Press F13;

to enter 则

OFF:Press enter F13

and

to

Tare weight detecting upper  limitation. When F12 is ON, after indicator enter into working status, first to check if the current weight is between tare weight lower  limitation and tare weight upper limitation. If yes, then start charging material, if no, then back to stop status.

000000

37

GM8806A-P6 Batching controller 

F12.2

Tare lower  limitation

000000

F13

ON/OFF

OFF

F13.1

XXXXXX

F14

ON/OFF

F14.1

******

Tare weight detecting lower  limitation. When F12 is ON,after indicator enter into working status,first to check if the current weight is between tare weight lower  limitation and tare weight upper limitation. If yes, then start charging material, if no, then go back to stop status. Pause function switch between materials. Pause function switch between materials, to represent materials 1#、2#、 3#、4#、5#、6# and to define if execute pause when material finished charging. 0:NO Pause 1:Pause

000000

Password for recipe parameters.

OFF

Please refer Character   6.20 for details to set password.

38

GM8806A-P6 Batching controller 

6 Operation 6.1 Operation status Working parameter 15(power down save switch )set to different value, the status o controller will be different afte power up. When controller is power up, first to execute self-check,buzzer hoots, main and sub-display flash “8” ,and status indicator lights also sparkle. When pass the self-check,main display show the selected working mode, and sub-display show version no. under this mode.

6.2 Batching times setting Batching times range is from   0~9999.   When finished, batching controller display “ERROR5” alarm and pause. When user press or input “clear alarm” effective signal, batching controller return stop status. For example, set batching times “3” as follows: 1. In stop status, press main display show bAt.

(4times) till

2. Press to enter and sub-display show“0000”and sparkle in hight digit. 3. Press

to move sparkling digit to

the left, then press change to“3”. 4. Press press

till sparkling digit

to save and finish, then to return stop status. 39

GM8806A-P6 Batching controller 

1. If batching times are zero, then enter stop status directly after discharging. 2. If batching several kinds of material individually, only when total batching finished, batching controller  check if batching times are up.

6.3 Sort batching in turn 1) Operating parameter 14 to decide current material kinds and the setting range of recipe parameter   F11.1. For example, if operation parameter 14 set 5, which means to batch 5 kinds of material, and recipe parameter  F11.1 can set the front 5 digits, the sixth digit is 0. 2) Recipe parameter   F11.1 to decide batching sequence(F11 is ON). If setting value is illogical, then output “ERROR” alarm message. For example: operation parameter   14=3 and material no. is 1 3 4,  so set F11.1 to “431000” to sort 4-3-1 in turn.

40

GM8806A-P6 Batching controller 

6.4 Check and clear accumulative total 1. In stop status, press

(5times) till

main display show total. Press to enter material no. 1 accumulative total. 2. ID   no.1 means accumulative total for  material no. 1. Accumulative total display 9digits at most, which main display show 3digits and sub-display show 6digits. For  example, main display show high 3digits and the sub-display show low 6digits, the accumulative total for material no. 1 is 123456789 as left chart. 3. Press to check accumulative total of material no. 2-6.

4. When state show“t”, it displays total value of 6 kinds of materials.

5. When state shows“n”, it display accumulative total times, which can display 6digits at most in main display. 1. When accumulative total disply, press

for 

sparkle value, then press to clear accumulative total value, and return stop status. 2. Not clear accumulative total value when runnin .

41

GM8806A-P6 Batching controller 

6.5 Manual discharging In stop status, input“manual discharging”signal, batching controller output effective discharging signal; input “manual discharging”signal again, then batching controller output ineffective discharging signal. In running status, after fixed value, when received “discharging permit” effective signal, batching controller  output“discharging”effective signal to discharge.

6.6 Manual zeroing In stop, press or input “zeroing” signal to clear G.W. Note: Operation must be in stable status or gross weight is in the zeroing range. Otherwise the indicator will display ERROR3 or ERROR2.

6.7 Save for power down When operation parameter  15 is ON, if power break, batching controller can restore previous working status. 1) Power cut out suddenly when operation parameter  15=OFF or   F15=ON   but in stop status, display working mode and version no. for 3 seconds, then enter into current weighing display status. 2) Power break suddenly when operation parameter   15=ON and in working status, re-up power and display working mode and version no. for 3 seconds, continue working and finish the batching process before the power cut out. 3) Power break suddenly when operation parameter   15=CONT and in working status, power re-up and display working mode and version no. for 3 seconds, main display is Gross weight, sub-display is “Conti?”. See right chart, 3# material is in batching process when power down. If press , go on to finish the batching process before the power down and start the next batching process. If press , enter into current weighing display status directly and other buttons invalid. 42

GM8806A-P6 Batching controller 

6.8 Compensation When recipe parameter F4 is ON and present weight is under tolerance, so batching controller begin compensation if receipe parameter  F7 is ON. After that, if present weight still is under tolerance, then output “ERROR9” alarm message for one second and continue the batching process. Batching controller begins compensation as following mode. 1) Present weight<target value – leading quantity of fast feeding, restart fast, moderate and slow feeding. Stop fast feeding when fast feeding go to (target value-leading quantity of fast feeding)/2, and enter into moderate feeding. 2) Target value - leading quantity of fast feeding ≤ present weight≤ target value – leading quantity of moderate feeding, restart moderate and slow feeding again. 3) Target value – leading quantity of moderate feeding ≤ present weight ≤ target value – leading quantity of slow feeding, restart jog feeding.

6.9 Free fall compensation When recipe parameter F5 is ON, batching controller  compensate free fall value automatically. User need press value in stop status.

long time to save the compensation

6.10 Discharging monitor   After“discharging signal”is effective, then discharge within discharging monitor time t8.   After time t8 is over, discharging signal is still effective, then output“ERROR6” alarm message within one second and return stop status. If  time t8 is“0”, shut off discharging monitor function.

6.11 Batching monitor  In batching proceed, if the system hasn’t finish within batching monitor time t9, then output“ERROR7”alarm message for one second and return stop status. If time t9 is“0”, shut off batching monitor function. 43

GM8806A-P6 Batching controller 

6.12 I/O testing Press to switch among OUT1~OUT10 and press to return to stop status.

Press

8 times till main-display show“tStio”. Sub-display indicate F means IN1~IN4 from left to right, when input effectively, F change to O.

, Press main-display show“inPUt”

For example, F change to O indicates IN1 input effectively and connect correctly.

Press to enter I/O input testing.

OUTPUT means testing. Main-display show output number, sub-display show status.

, Press main-display show“oUtPUt”

Press ,sub-display OFF change to ON indicates OUT1 output effectively and connect correctly.

Press to enter I/O output testing.

Press to switch output numbers, such as from OUT1 to OUT2. 44

GM8806A-P6 Batching controller 

6.13 I/O definition When stop, user can define I/O ports by

and

to return. The flow chart is to define OUT3 as O5(SP5) for example: When stop, press dis la show“iodEF”. Press

7times, main

to input correct calibration

password, the press to define. See Character 6.19 for details. Main display shows output port and sub-display show code, press main display show OUT3. Press

till

till sub-display show 05,

then press

to finish.

If not need define others, press to return. W h e n s l o w f e e d i n g e f f e c t ,   OUT3 ouput effectively. Output code table: Output Co d e

De fi n i ti on

O0

No ne

O1

Run

Effective in running status

O2

Stop

Effective in stop status

O3

Fast feeding

Des c ri pt i on No de f ini t i on

Begin fast feeding when weight
View more...