7UT61X Transformer Protection
Short Description
PROTECTION DETAILS FOR TRANSFORMER TESTING...
Description
Module 10B: Transformer Protection The year of Profitable Growth
Global network of innovation
Power Transmission and Distribution
Commissioning and operating aids (4 of 5) Power Automation Progress. It‘s that simple.
Generator transformer SITRAM+ Siemens Transformer Monitoring System for all voltage levels
Shunt reactor
HVDC
System interconnecting transformer
FACTS Converter transformer
Furnace transformer
System transformer
Oil-immersed distribution transformer
Voltage regulator
GEAFOL cast-resin transformer
TLM50+ Siemens Transformer Life Management Program
Traction transformer
Power Automation
2
Power Transmission and Distribution
575-MVA Phase Angle Regulator (PAR) Transformer Set in the 345 kV Station Power Automation Progress. It‘s that simple.
Power Automation
3
Power Transmission and Distribution
630-kVA Oil-Immersed Distribution Transformers, TUMETIC, TUNORMA Power Automation Progress. It‘s that simple.
Power Automation
4
Power Transmission and Distribution
Transformer Prices Power Automation Progress. It‘s that simple.
>40 MVA 10,-US$ pro kVA => 30MVA = 40.000 kVA *10 US$ = 300.000US$ >200 MVA 8,-US $ pro kVA => 200 MVA 200.000kVA *8 US$ = 1’600.000US$
>1000 MVA 5,-US$ pro kVA => 1000 MVA 1000.000kVA *5 = 5’000.000 US$ Power Automation
5
Power Transmission and Distribution
TLM50+ – Siemens Transformer Life Management Program Power Automation Progress. It‘s that simple.
SIDRY, SMART DRY, SIREC advanced life extension programs
SITRAD Condition assessment program
Traditional heat and vacuum treatment
On-site services and repair SITRAM+ transformer monitoring system Power Automation
6
Power Transmission and Distribution
Transformer Faults Power Automation Progress. It‘s that simple.
Power Automation
7
Power Transmission and Distribution
The 7UT6 Family Power Automation Progress. It‘s that simple.
SIPROTEC 4 7UT6 differential protection relay for transformers, generators, motors and busbars
7UT612: 7UT613: 7UT633: 7UT635:
for two end protection objects for three end protection objects for three end protection objects for five end protection objects
(1/3 x 19’’ housing 7XP20) (1/2 x 19’’ housing 7XP20) (1/1 x 19’’ housing 7XP20) (1/1 x 19’’ housing 7XP20) Power Automation
8
Power Transmission and Distribution
Hardware options Power Automation Progress. It‘s that simple.
*
Device
7UT612
7UT613
7UT633
7UT635
Current Inputs (normal) Current Inputs (sensitive) Voltage Inputs (Uph / UE) Binary Inputs Binary Outputs Life contact LC Display
7 (7)* 1 --3 4 1 4 lines
11 (6)* 1** 3/1 5 8 1 4 lines
11 (6)* 1** 3/1 21 24 1 Graphic
14 (12)* 2** --29 24 1 Graphic
1A, 5A, (1A, 5A, 0.1A) changeable (jumper position)
** changeable normal or sensitive (jumper position)
Power Automation
9
Power Transmission and Distribution
Scope of functions and Protection objects Power Automation Progress. It‘s that simple.
Function
ANSI No.
Protection Objects
Differential
87T/G/M/L
Three-phase transformer
Restricted Earth fault
87 N
Single-phase transformer
Overcurrent-time, phases
50/51
Auto-transformer
Overcurrent-time, 3I0
50N/51N
Generator / Motor
Overcurrent-time, earth
50G/51G
Busbar, 3-phase (Branch point)
Overcurrent-time, single phase
Busbar, 1-phase
Negative sequence
46
Overload IEC 60255-8
49
Overload IEC 60354 (hot spot)
49
Overexcitation V/Hz
24
Breaker failure
50BF
External temperature monitoring
38
Lockout
86
Measured value supervision Trip circuit supervision
74TC
Direct coupling Operational measured values
Power Automation
10
Power Transmission and Distribution
Cross reference - functions and protected objects Power Automation
Protection functions
ANSI No.
Transf. 3-phase
Transf. 1-phase
Autotransf.
Gen. / Motor
Busbar 3-phase
Busbar 1-phase
Differential
87T/G/M/L
X
X
X
X
X
X
Restricted Earth Fault
87 N
X
X
---
X
---
---
Overcurrent-time, phases
50/51
X
X
X
X
X
---
Overcurrent-time, 3I0
50N/51N
X
---
X
X
X
---
Overcurrent-time, earth
50G/51G
X
X
X
X
X
X
X
X
X
X
X
X
Progress. It‘s that simple.
Overcurrent-time, single phase
Negative sequence
46
X
---
X
X
X
---
Overload IEC 60255-8
49
X
X
X
X
X
---
Overload IEC 60354
49
X
X
X
X
X
---
24
X
X
X
X
X
X
Breaker failure
50 BF
X
X
X
X
X
---
External temperature monitoring (thermo-box)
38
X
X
X
X
X
X
Lockout
86
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Direct coupling 1
X
X
X
X
X
X
Direct coupling 2
X
X
X
X
X
X
Operational measured values
X
X
X
X
X
X
Overexcitation V/Hz
*)
Measured value supervision Trip circuit supervision
X Function applicable ;
74TC
--- Function not applicable ;
*) only 7UT613 / 633 Power Automation
11
Power Transmission and Distribution
Communication features Power Automation
Flexibility due to plug in modules
Progress. It‘s that simple.
Compatibility to international standards
RS232/RS485 electrical module
Front interface DIGSI4
WEB Monitor
Service interface (s) Fibre-optic module
Optical double-ring module
DIGSI4 operation modem connection RTD box
System interface IEC60870-5-103 Profibus FMS Profibus DP DNP3.0 Modbus ASCII/RTU
Time synchronising IRIG-B (GPS) DCF77
Power Automation
12
Power Transmission and Distribution
Connection Example M3 L1
Power Automation Progress. It‘s that simple.
side 3
L2
direct connection to the main Ct’s
L3
L1
M2
side 2
side 1
M1 L1
L2
L2
L3
L3
no matching transformers / no matching connections numerical vector group adaptation without zero sequence current correction depending of the type of earthing of the winding. increased sensitivity by 33% by measuring of the zero sequence current (7UT6) for single-pole faults.
IL1M2
IX1
IX3
IL1M1
IL2M2
IL2M1
IL3M2
IL3M1
1A/5A main Ct’s adaptation in the relay
permissible ratio Ct nominal current to transformer nominal current up to 1 : 4
IL1M3
Surface mounting housing
IL2M3
Flush/ cubiclemounting housing
IL3M3
7UT613 Power Automation
13
Power Transmission and Distribution
Application: 3-winding transformer YNd5d11 (1 of 4) Power Automation
IL1M1/I1
Progress. It‘s that simple. M1
IL2M1/I2
M2 400/1A M1 400/1A
IL3M1/I3 IL1M2/I4
M3 400/1A M2
IL2M2/I5 IL3M2/I6 IL1M3/I7
M3
IL2M3/I8 IL3M3/I9
M5 3500/1A
Side 1 200/1A
IL1M4/I10 M4
IL2M4/I11
IL3M4/I12
Side 3
Side 2
IL1M5/Ix1
M5
IL2M5/Ix2
M4 8000/1A
IL3M5/Ix3 Ix4
7UT635 Power Automation
14
Power Transmission and Distribution
Application: 3-winding transformer YNd5d11 (2 of 4) -Device Configuration and Power System Data 1 Power Automation Progress. It‘s that simple.
7UT635
Power Automation
15
Power Transmission and Distribution
Application: 3-winding transformer YNd5d11 (3 of 4) -continue Power System Data 1 Power Automation Progress. It‘s that simple.
7UT635
Power Automation
16
Power Transmission and Distribution
Application: 3-winding transformer YNd5d11 (4 of 4) -continue Power System Data 1 Power Automation Progress. It‘s that simple.
7UT635
Power Automation
17
Power Transmission and Distribution
Application: Autotransformer with ∆ Winding (1 of 2) Power Automation Progress. It‘s that simple.
M1
Side 1
M2
Side 3
M3
Side 2
IL1M2
IL1M3
IL2M2
IL2M3
IL3M2
IL3M3
IL1M1
IL2M1
IL3M1
7UT613 Power Automation
18
Power Transmission and Distribution
Application: Autotransformer with ∆ Winding (2 of 2) - Power System Data 1 Power Automation Progress. It‘s that simple.
7UT613
Power Automation
19
Power Transmission and Distribution
Application: Autotransformer with ∆ Winding (2 of 2) - Power System Data 1 Power Automation Progress. It‘s that simple.
Power Automation
20
Power Transmission and Distribution
Application: Autotransformer (bank) with 3 Ct’s at the star point side available Power Automation Progress. It‘s that simple.
(1 of 2)
M3
M1
Only compensation winding, no external connection!
M2
Increased sensitivity for phase to phase- and phase to ground faults towards the star point!
7UT613 Power Automation
21
Power Transmission and Distribution
Application: Autotransformer (bank) with 3 Ct’s at the neutral side
(2 of 2)
Power Automation Progress. It‘s that simple.
7UT613
Power Automation
22
Power Transmission and Distribution
Application: Single-phase bus bar (1/2) - Phase selective configuration (1 7UT6 for 1 phase) Power Automation Progress. It‘s that simple.
7UT612: 7 currentinputs 7UT613/633: 9 currentinputs 7UT635: 12 currentinputs
7UT612
Power Automation
23
Power Transmission and Distribution
Application: Single-phase bus bar (2/2) - Phase selective configuration (1 7UT6 for 1 phase) Power Automation Progress. It‘s that simple.
7UT612
2 more Relays for Phase 2 and 3 are necessary
Power Automation
24
Power Transmission and Distribution
Application: Single-phase bus bar - configuration with Summation Ct’s
(1 of 2)
Power Automation Progress. It‘s that simple.
7UT612: 7 currentinputs 0.1A 7UT613/633: 6 currentinputs 0.1A
7UT635: 12 current inputs 0.1A
*) Summation CT 4AM5120-3DA00-0AN2: 1/0.1A 4AM5120-4DA00-0AN2: 5/0.1A
7UT612
Power Automation
25
Power Transmission and Distribution
Application: Single-phase bus bar - configuration with Summation Ct’s
(2 of 2)
Power Automation Progress. It‘s that simple.
7UT612
Not important in this case
Power Automation
26
Power Transmission and Distribution
General Applications of 2)
(1
Power Automation Progress. It‘s that simple.
Two winding transformer 1 or 3 phases
Three winding transformer 1 or 3 phases
1 ½ C.B. application with two winding transformer
7UT613 7UT633 7UT612 7UM62
Short lines (2 ends)
7UT613 7UT633
Short lines (3 ends)
1 ½ C.B. application on HV and LV side with two winding transformer
7UT635
7UT612
7UT613 7UT633
Power Automation
27
Power Transmission and Distribution
General Applications of 2)
(2
Power Automation
Generator/Motor longitudinal or transversal differential protection
High-impedance Restricted Earth Fault Protection
G/M 3~
7UT612 7UM62
7UT6xx
Unit Protection (Overall Differential)
IEE input of the unit
Y
Progress. It‘s that simple.
7UT635
∆
G 3~
Power Automation
28
Power Transmission and Distribution
Differential functions IDiff> and IDiff>> Power Automation
measured value pre-processing ( vector gr. ,Ct’s )
Progress. It‘s that simple. i1L
Instantaneous values iRest = │i1│ + │i2│
side 1
i2L
iDiff = i1 + i2
side 2
rectified mean value: IRest = iRest fundamental wave: IDiff = rms(iDiff)50Hz
Tripping characteristic, saturation detection IDiff IDiff>
IRest
&
Trip IDiff>
≥1
Trip IDiff>>
Motor start DC off set analysing of harmonics: -block by 2. & 3. or 5.har -cross block iDiff
iRest IRest
IDiff
IDiff I / InO
I / InO
IDiff>>
ms
iDiff 2·IDiff>> ms
IDiff> restrained (biased) differential function, IDiff> = f(IRest) - Ct-saturation detector (add on stabilization) for external faults. IDiff>> fast unrestrained high current differential function, it’s setting therefore should be higher then the maximum possible through flowing current! Example Transformer: IDiff>> > (1/uk)·InO This function will be not blocked by harmonics due to an inrush or Ct-saturation! The IDiff>> stage evaluates the fundamental wave of the currents as well as the instantaneous values. - Fundamental wave processing: fast tripping at the set threshold. - Instantaneous value processing: ensures fast tripping even in case the fundamental wave of the current is strongly reduced by Ct-saturation. Because of the possible DC offset after fault inception, the instantaneous value stage operates only above twice the set threshold. Power Automation
29
Power Transmission and Distribution
Tripping Characteristic Reasons for this shape of characteristic Power Automation Progress. It‘s that simple.
x
I Diff InO 3.0
2.5 Trip
Slope 2 Total
2.0
Block 1.5
CTerror
1.0
Slope 1
Tapchanger
0.5 IDiff> 0
Magnet. current 0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
I Rest InO
Example: Transformer with Tap changer
Power Automation
30
Power Transmission and Distribution
Tripping Characteristic of 2) Power Automation Progress. It‘s that simple.
Tripping Characteristic 7UT6
I Diff InO 1231 IDiff>>
(1
7 1243A SLOPE 2
6 45°
5
Block
Trip 4
*) 3 2
Add-on Stabilization
1241A SLOPE 1
1 1221 IDiff>
0
0
2
4
6
1242A 1256A BASE POINT 1 I-ADD ON STAB 1244A BASE POINT 2
8
10
12
14
16
*) Slope for Add-on Stabilization: 7UT6 Slope 1 ; 7UT5 ½ Slope 1
I Rest InO
flexible adaptation to various transformers, e.g. with tap changer or different Ct’s high stability against external faults with Ct saturation IDiff>>: fast tripping for solid short-circuits within one period Power Automation
31
Power Automation
Tripping Characteristic of 2) - Parameters
Power Transmission and Distribution
(2
Progress. It‘s that simple.
7UT6: settable 7UT5: 0 (fixed) 7UT6 only min. setting: 7UT6: 3 ; 7UT5: 5 7UT613 / 63x
Power Automation
32
Power Transmission and Distribution
Tripping Characteristic - Pickup of differential function Power Automation Progress. It‘s that simple.
For triggering of internal tasks, events and fault records the differential protection function needs a pickup information. This pickup becomes active, if the differential current or the restraint current is over an internal threshold (dotted line). Each external large current leads to a pickup. Pickup doesn‘t always mean internal failure! Power Automation
33
Power Transmission and Distribution
Tripping Characteristic - Add on stabilization during external fault Power Automation Progress. It‘s that simple.
During an external fault which produces a high through-flowing current, causing Ct saturation, a considerable differentialcurrent can be simulated, especially when the degree of saturation is different at the two sides. If the quantities IDiff/IRest result in an operating point which lays in the trip area of the operating characteristic, a trip signal would be the consequence, if there were no special measures
Tripping Characteristic 7UT6
I Diff InO IDiff>>
(1 of 2)
7
Trip 6 45°
Block
5 D C
4 3
Add-on Stabilization
2
1 Saturation inception
B
IDiff>
0 0 A
2
4
6
8
10
12
14
16
I Rest InO
Immediately after fault inception (A) the fault currents increase severely thus producing a high restraint quantity. At the instant of Ct saturation (B) a differential quantity is produced and the restraint quantity is reduced. In consequence, the operating point IDiff/IRest may move into the tripping area (C). In contrast, the operating point moves immediately along the fault characteristic (D) when an internal fault occurs.
When an external fault is detected, the differential stage for this phase is blocked by an adjustable no. of periods. (for 7UT613/63x now also cross block is possible) Power Automation
34
Power Transmission and Distribution
Power Automation
Tripping Characteristic of 2) - Demonstration of add-on stabilization
(2
Progress. It‘s that simple.
Block
45 °
Trip
add-on stabilisati on
Power Automation
35
Power Transmission and Distribution
Tripping Characteristic - Motor Start Power Automation Progress. It‘s that simple.
Typical for motor start is the starting current and the superimposed dc component with a large time constant. The two Ct-sets may transform this dc component differently. The result is a differential current and the risk of an over-function is given. Detection of motor starting: Increases the pick-up values for a settable time Tripping Characteristic 7UT6 for Motor start
I Diff InO 1231 Idiff>>
Criterion: Supervision of restraint current
7 Start-up characteristic 6 5
IRest > I-Restr. Startup (until 2 I/InO)
4
than the Start-Factor (max. 2) is active for the time:
T Start Max (Duration of dynamical increasing of pickup)
Steady-state characteristic
Trip
45°
Increase of pickup
3 2 Block 1 1221 Idiff>
0
0
2
4
6
8
10
12
14
16
Power Automation
I Rest InO 36
Power Transmission and Distribution
Tripping Characteristic DC offset: Increasing of the Characteristic Power Automation Progress. It‘s that simple. increased characteristic (factor 2)
0.24
0.36 Steady state characteristic
0.12 0.18 Minimum setting Add-on stabilization
Setting Add-on stabilization: 5
7UT613/63x only Power Automation
37
Power Transmission and Distribution
Inrush, cross block, over excitation [V/Hz] 2)
(1 of
filter window 1 cycle
Power Automation Progress. It‘s that simple. iRUSH = iDiff
Cross-block = No (phase separate blocking)
Inrush current in one phase
1P
I 2har I Diff
2P
IDiff, L1 > trip blocking
L2-block
IDiff, L2 > trip blocking
L3-block
IDiff, L3 > trip blocking
3P t
Cross-block = Yes (blocking of all phases)
block Setting value
15 %
L1-block
L1-block L2-block
OR ≥1
IDiff > trip blocking for an adjustable time
L3-block
no block 0
0
t
recognise inrush condition by evaluating the ratio 2nd harmonic I2har to basic wave IDiff.
Time limit for cross-block. Reliable reaction to the inrush condition with cross-block. Trip of a short circuit after the set time delay. recognise over excitation [V/Hz] by evaluating the ratio 3rd or 5th harmonic to basic wave Power Automation
38
Power Transmission and Distribution
Inrush, cross block, over excitation [V/Hz] (2 of 2) Demo: Inrush followed by an internal Fault L1-E Power Automation Progress. It‘s that simple.
Internal fault
IDiff>>
Inrush
IDiff>
Add-on stabilizati on
3 cycles
Power Automation
39
Power Transmission and Distribution
Low impedance Restricted Earth Fault (REF) 2)
(1 of
Power Automation Progress. It‘s that simple.
The REF measures the Neutral current of the object ( ISP = 3I0’ ) and, depending on the angle (∆φ) between 3I0’ and the also measured sum of the phase currents ( 3I0’’ = IL1 + IL2 + IL3 ), decides for internal or external fault. The sensitivity of the REF is almost independent from the load of the object. (The sensitivity of the “Differential Function” especially for high ohm faults will be reduced by the load due to the slope of its “Tripping Characteristic” ).
The REF can be stetted to 0.1 I/INO (min. 0.05) and is therefore more sensitive as the “Differential Protection” (even without load).
Power Automation
40
Power Transmission and Distribution
Low impedance Restricted Earth Fault (REF) Power Automation Progress. It‘s that simple.
Tripping Characteristic REF
IREF> = Setting value (Trip Threshold) IRest = Restraint current IREF = │3I0’│
I REF I REF
Char. for ∆φ= 180°
4
1) for basic Trip-Area (0° ≤ ∆φ ≤ 90°): IREF = │3I0’│ and must be ≥ IREF>
Tripping 3
Characteristic_1): IREF / IREF> = 1 (no restraining current IRest effective)
2
2) for extended Trip-Area (90° ≤ ∆φ ≤ 180°):
1
Blocking
Characteristic_2): IREF = IREF> + k·IRest where IRest = (│3I0’-3I0’’│-│3I0’+3I0’’│) IRest includes the direction
(2 of 2)
-0.3
-0.2
-0.1
0.0
180° ≥ ∆φ > 90° extended Trip-Area
+0.1
+0.2
+0.3
3I '0' 3I '0
90° ≥ ∆φ ≥ 0° basic Trip-Area
calculation of the basic wave and the complex vectors of I0' and I0" evaluation of the modulus and angle between I0' and I0" sensitive fault detection starting with 5% transformer nominal current Power Automation
41
Power Transmission and Distribution
CT Requirements Power Automation Progress. It‘s that simple.
(1 of 3)
Request: k ALF
k ALF_N
R ct R ct
Rb R 'b
4
k ALF
k ALF_N
R ct R ct
Rb R 'b
5
IP I NCtPrim IP I NCtPrim
for : TP 100ms for : TP
where: kALF_N = rated Accuracy Limiting Factor Rct = secondary winding resistance Rb = rated resistive burden IP = max. primary symmetrical short circuit current Example: (TP ≤ 100ms)
100ms
kALF = actual Accuracy Limiting Factor R’b = actual resistive burden TP = Primary (Net-) Time constant
Explanation: 5P20: kALF_N = 20
110 kV 7UT6 200/1A 5P20,15VA Rct = 1Ω
80m , 2.5 mm2
Wind.1 0.1 Ω
38.1 MVA 110/11 kV uk = 10% 2000/1A 10P10, 10VA Rct = 2Ω
11 kV
50m , 4 mm2
Wind.2 0.1 Ω
Power Automation
42
Power Transmission and Distribution
CT Requirements of 3) Power Automation
(2 Side 2 (LV):
Side 1 (HV):
Progress. It‘s that simple.
Nominal transformer current:
SN 3 U N1
InO1
38100kVA 3 110kV
Nominal transformer current:
Maximum through flowing current:
c InO1 100% uk
I P_1
R 'b
k ALF
Sb I
2 NCtS
2 l ρ q
20
15VA 1A 2
1.1 200A 100% 10%
2200A
15Ω
160m 0.0175 2.5mm
Ωmm 2 m 2
0.1Ω 1.22Ω
1Ω 15Ω 144 1Ω 1.22Ω
k ALF 144
4
IP I NCT prim
4
2200A 200A
c InO 2 100% uk
I P_2
2000A
R 'b
Sb I
2 NCtS
2 l ρ q
k ALF 10 44
OK!
1.1 2000A 100% 10%
22000A
where: c = factor for max. possible over voltage
Rb
R Relay
38100kVA 3 11kV
Maximum through flowing current:
where: c = factor for max. possible over voltage
Rb
SN 3 U N2
InO 2
200A
k ALF
10VA 1A 2
10Ω 100m 0.0175
R Relay
2Ω 10Ω 2Ω 0.54Ω
47.2 4
IP I NCT prim
Ωmm 2 m
4mm 2
0.1Ω
0.54Ω
47.2 4
22000A 2000A
44
OK!
Power Automation
43
Power Transmission and Distribution
CT Requirements of 3) Power Automation Progress. It‘s that simple.
(3
5P20, 200/1A, 15VA, Rct = 1Ω, R’b = 1.22Ω, 11·I/INCT ; TP = 100ms
10P10, 2000/1A, 10VA, Rct = 2Ω, R’b = 0.54Ω, 11·I/INCT ; TP = 100ms
Power Automation
44
Power Transmission and Distribution
Power Automation Progress. It‘s that simple.
Commissioning and operating aids 4) WEB-Technology
(1 of
Access to the relay with a WEB Monitor Help system in INTRANET / INTERNET http://www.siprotec.com
1. Serial connection Direct or via modem with a standard DIAL-UP Network
The homepage of the relay is:http://141.141.255.160 IP-address is set with DIGSI 4 on front- or rear service port
WEB server in the relays firmware Server sends it’s HTML-pages and JAVA-code to the WEB Monitor after a DIAL-UP connection
2. HTML page view in a WEB Monitor with the IP-address of the relay http://141.141.255.160 Power Automation
45
Power Transmission and Distribution
Commissioning and operating aids 4)
(2 of
Power Automation Progress. It‘s that simple.
Transformer YNd11d11, 110/11/11kV, 38.1MVA, IL2S2 wrong polarity Power Automation
46
Power Transmission and Distribution
Commissioning and operating aids 4)
(3 of
Power Automation Progress. It‘s that simple.
Transformer YNd11d11, 110/11/11kV, 38.1MVA, IL2S2 wrong polarity Power Automation
47
Power Transmission and Distribution
Commissioning and operating aids 4)
(4 of
Power Automation Progress. It‘s that simple.
Power Automation
48
Power Transmission and Distribution
Benefits for the Customer Power Automation Progress. It‘s that simple.
Protection relay with flexible adaptation to the transformer/generator/motor or short line. Programming of the device data in the relay. Reduced amount of wiring by direct connection to the main Ct’s. No matching transformers and therefore no wiring errors. Zero sequence current can be measured (in the 7UT6). Sensitivity for single-pole faults in the transformer increased by 33% .
Flexible adaptation of the tripping characteristic to various main Ct’s, tapped transformers. Exact discrimination between the short circuit condition and the inrush condition by on-line analysis of the harmonics. Fast tripping for high-current faults. Ct saturation detector for external faults. Thermal monitoring of one transformer winding (including RTD meas.)
Back-up DMTL/IDMTL with reverse blocking for one winding. Sensitive short circuit protection for faults winding against earth. External Trip functions Various commissioning aids. Common DIGSI 4 software Power Automation
49
Power Transmission and Distribution
Comparison of functions/settings between 7UT51- and 7UT6 relays 7UT51
7UT612
7UT613
7UT633
7UT635
Tripping Characteristic: Base point for slope 1 settable
---
X
X
X
X
Tripping Characteristic: Increasing of characteristic at start
---
X
X
X
X
Tripping Characteristic: minimum setting for add-on stabilization I/InO
5
3
3
3
3
Tripping Characteristic: cross block for add-on stabilization
---
---
X
X
X
Tripping Characteristic: slope of add-on stabilization / slope 1
½
1
1
1
1
Tripping Characteristic: Increasing of characteristic due to DC offset in IDiff
---
---
X
X
X
Transformer inrush: Default setting for cross block 2. harmonic [cycles]
0
3
3
3
3
Transformer inrush: Default setting for 5. harmonic [%]
80
30
30
30
30
Negative sequence current protection
---
X
X
X
X
Over excitation protection [V/Hz]
---
---
X
X
---
Overload protection IEC 60354 (hot spot)
---
X
X
X
X
Single phase busbar differential
---
X
X
X
X
High impedance Restricted Earth Fault
---
X
X
X
X
Voltage measurements
---
---
X
X
---
Temperature monitoring (via Thermo-box / RS 485)
---
X
X
X
X
All functions can be enabled at the same time
---
X
X
X
X
WEB Toll (commissioning aid)
---
X
X
X
X
Power Automation Progress. It‘s that simple.
Power Automation
50
View more...
Comments