VEGA T ELECTRONIC COUNTER
INSTALLATION MANUAL VAC VERSION CODE REVISION
Isoil Impianti S.p.A. - Italy Italy Sede ed e e stab tabil ilimento imento Head o ffice ffice and fa ctory 24061 Albano Alba no S.Aless .Alessandro (BG) (BG) 74, via Madonna delle Rose Tel. Tel. +39 035 035 4239 4239.0 .011 11 Fa Fax x +39 035 582078 E-ma E-mail il :
[email protected] [email protected] Web : www.is www.isoilmeter oilmeter.co .co m
Uffici Uffici C ommerciali Sales office 20092 C inisello Balsamo (MI) (MI) 27, via F.lli F.lli Grac c hi Tel. +39 02 6602 66027. 7.1 1 Fa Fax x +39 02 6123202 E-mail : sales@i sales@isoil-impia soil-impia nti.it nti.it
Sede legale Registered Regis tered offi o ffic ce 20124 Milano Milano 24, viale Vittorio Veneto C ap itale soc . int. Sottosc Sottoscri ritto tto 774.00 774.000 0 Euro C od ice Fisc . e part. p art. IVA 1306 1306690 690015 0153 3 C .C .I.A.A. .I.A.A . MI - Reg. Impr. 8 8644 6449/2000 9/2000 R.E.A. Mila no 16127 1612783 83
: MA/350/01/EN/11 : 01/2016
Information in this manua manuall is s ubject to change without pri or notic e. The manufa manufacturer cturer is not responsible for mist ake akes s in th is material or for inci denta dentall damage caused as as a direct or indirect result of the delivery, performance performance or use of t his material.
2.2.
INSTALLATION IN HAZARDOUS AREA Hazardous area/Zone Gas, mists or vapours Gas, mists or vapours Gas, mists or vapours
2.3.
AREA OF SAFE INSTALLATION INSTALLATION Category according to 94/9/CE directive
Allowed
1G 2G 3G
Only for the devices connected to the Ex-ia inputs YES YES
Zone 0 Zone 1 Zone 2
ATEX PLATE DESCRIPTION DESCRIPTION
fig.1 - ATEX PLATE
DESCRIPTION
LABEL
Symbol of the apparatus that can be installed in hazardous area II II 2 (1) G Ex d [ia Ga Ga]] ib IIB IIB Gb T6 T6 Tamb. -IP 25÷ °C 66+ 66 55 °C
Group II (surface) CATEGORY 2 APPARATUS. VEGA T can be installed in ZONE 1 CATEGORY 1 APPARATUS. The device connected to the Ex-ia inputs can be installed in ZONE 0. Explosive atmospheres caused by gas Type of protection, gas group Explosin protection level Temperature class Working temperature Degree ofenvironmental mechanical protection Symbol of conformity with European community norms
0080 0080
INERIS05 ATEX0034X
Number of Notified Body involved in ATEX/Q surveillance (INERIS)
Certificate number
COPYRIGHT: ISOIL IMPIANTI S.p.A. Reproduction of this document in any form is strictly prohibited by law
INSTALLATION MANUAL
Page n°3 of 30 Code MA-350/01/EN/11 dated 01/2016
3.
INSTRUCTIONS FOR MOUNTING Before to mount VEGA T the following recommendations have to be considered: 1. VEGA T mounting position has to be chosen to allow easy opening and wiring 2. The position must avoid damages caused from the passage of the trucks but also to assure good visibility of the indications 3. Avoid exposing the device to the rain and to the solar beams directly: a simple canopy of protection is to be forecast 4. Mounting has be done by using the 4 silent blocks located under the housing (see fig.2) 5. Before opening the device read the safety instructions at paragraph 2 6. The opening is done by removing the 14 screws that close the cover (see fig.2) – Take attention that the gasket remains in its own position.
WARNING: VEGA T MUST BE PROTECTED FROM DIRECT SUNLIGHT SUNLIGHT
fig.2 – external dimensions Page n°4 of 30 Code MA/350/01/EN/11 dated 01/2016
INSTALLATION MANUAL
COPYRIGHT: ISOIL IMPIANTI S.p.A. Reproduction of this document in any form is strictly prohibited by law
4.
TECHNICAL SPECIFICATIONS
4.1.
AMBIENT CONDITIONS CONDITIONS Operating temperature Storage temperature Humidity
-25 ÷+55°C (-13 ÷131°F) -40 ÷+65°C (-40÷149°F) 5÷95% without condensation
WARNING: VEGA WARNING: VEGA T should be shaded from direct sunlight. For temperatures lower then –5°C VEGA T must be maintained switched on 4.2.
4.3.
HOUSING PROTECTION ATEX
CE 0080
Weatherproof MECHANICAL SPECIFICATIONS
IP66 IP66
Housing material Dimensions Weight Fitting Cable entries keyboard 4.4.
II 2 (1) G Ex d [ia Ga] ib IIB T6 Gb CE - Certificate INERIS 05 ATEX0034
Aluminium casting 248 x 248 x 76 mm 6 kg By four silent blocks (see fig.1) n° 7 holes ½” NPT or on request M20x1,5” 28 push-button membrane type
ELECTRICAL SPECIFICATIONS SPECIFICATIONS Power supply Count inputs Power supply for pulses emitters Ex-iadigital digitalinputs inputs Ex-d Ex-d Digital outputs Ex-d Digital power outputs
115÷230 Vac 15W n° 1 input, A and B channels phased of 90° ± 10°, f m max ax 5kHz. Open collector or Square wave: V(High) = 4 Vdcmin ÷ 24 Vdcmax; V(Low) = 1 Vdc +5Vdc 100mA or 12 Vdc 100mA
max
Ex-ia Temperature probe imputs Ex-d Serial communication lines
N° 4 6,from: powered VEGA Torfrom: contacts (simple devices) or Exia NAMUR SENSORS N° Freeby contacts OpenFree Collector N°4 current sink/source (10÷30Vdc) Imax=0,2 A each. OUTPUT 5, 6, and 7 (MECHANICAL (MECHANICAL RELAY) RELAY) OUTPUT 1, 2,3 and 4 (SOLID STATE RELAY) Maximum switching power: 750VA, 90W Operating voltage range: 100260 Vac (5060Hz) Maximum switching voltage: 270 Vac, 125 Vdc Load Current Range: 1 Arms Maximum swiching current: 2A Max Off-State Leakage @ Rated Current: 2 mA rms Max On-State Voltage Drop @ Rated Current: 1,5 Vpk Min switching load: 1mA, 5V Pt100 (alpha 0.00385), 0.00385), Class A IEC751, DIN 43760. n° 2 RS 485 (2 wires) + n° 2 RS 232 (TX-RX-COM) + n° 1 RS 485/422 485/422 (4 wires)
Display
Graphic Liquid Crystal Display (LCD) 240x128 pixel; LED backlight.
COPYRIGHT: ISOIL IMPIANTI S.p.A. Reproduction of this document in any form is strictly prohibited by law
INSTALLATION MANUAL
Page n°5 of 30 Code MA-350/01/EN/11 dated 01/2016
WARNING 5.
In order to prevent VEGAT buffer battery from being completely depleted, it is necessary to connect VEGAT to power network for 24 hours straight at least once per month. Buffer battery is used to maintain in memory the delivery data and parameters par ameters customization.
ELECTRICAL CONNECTIONS VEGAT is provided with 7 cable entries. The five left side entries are foreseen for power supply, pulses from encoder, output for valves, etc. The two right side si de cable entries can be used only for the intrinsically safe connections (PT100, digital inputs). Take care to choose accessories threaded ISO 7/1 (UNI 6125-74) . VEGAT is delivered with gland en entries tries closed by plastic threaded screw-caps. These threaded screw-caps must be removed and the not utilized entries must be closed with metallic screws-plugs conforming to EN60079-1 norm.
fig. 3 – cable entries
Page n°6 of 30 Code MA/350/01/EN/11 dated 01/2016
INSTALLATION MANUAL
COPYRIGHT: ISOIL IMPIANTI S.p.A. Reproduction of this document in any form is strictly prohibited by law
fig. 4 – connectors position EX-d AREA X1 X2 X3 X4
= POWER SUPPLY (115/230 Vac) = N° 7 DIGITAL POWER OUTPUTS = N°4 DIGITAL POWER OUTPUTS = N° 2 EX-d DIGITAL INPUTS
Ex-ia AREA X10 X11 X12 X13
= N° 3 Ex-ia DIGITAL INPUTS = N° 3 Ex-ia DIGITAL INPUTS = 4 WIRES INPUTS FOR THERMAL SENSOR TYPE PT100 (*) = NOT USED
X5 = PULSE COUNTING INPUTS / POWER SUPPLY FOR PULSE EMITTERS X6 = N° 2 RS485 TWO WIRES SERIAL COMMUNICATION LINES X7 = N° 2 RS232 SERIAL COMMUNICATION LINES X8 = N° 2 EX-d DIGITAL INPUTS X9 = N° 1 RS485/422 FOUR WIRES SERIAL COMMUNICATION LINE X14 = N° 2 INPUTS 4÷20mA + 2° OUTPUTS 4÷20mA (OPTIONAL) (*) only for versions with temperature compensation COPYRIGHT: ISOIL IMPIANTI S.p.A. Reproduction of this document in any form is strictly prohibited by law
INSTALLATION MANUAL
Page n°7 of 30 Code MA-350/01/EN/11 dated 01/2016
Reproduction of this document in any form is strictly prohibited by law
Code MA 350/01/EN/11 dated 01/2016
5.1.
Ex-d AREA - ELE ELECTRICAL CTRICAL CON CONNECTIONS NECTIONS
5.1.1.
POWER SUPPLY CONNECTION
fig.5 – power supply connections
fig. 6 – X1 and internal EARTH position
NOTE Put a 2 Ampere external fuse in series to the PHASE (see fig.5). The X1 connector accepts wires having having section 0,5÷2,5mm²
Page n°8 of 30
INSTALLATION MANUAL
COPYRIGHT: ISOIL IMPIANTI S.p.A.
Code MA/350/01/EN/11 dated 01/2016
Reproduction of this document in any form is strictly prohibited by law
5.1.2.
DIGITAL INPUTS CONNECTIONS
X4 connector X4-1= + 5 Vdc 100mA max X4-2=INPUT n° 9 X4-3=INPUT n° 10 X4-4=(-) GND X4-5=+ 12 Vdc 100mA max max The inputs can be connected to: FREE CONTACTS (see fig.8) fig.8) OPEN COLLECTOR (see fig.9) fig.9) fig.7 –X4 and X8 connectors position
ig.8 – FREE CONTACTS f ig.8
COPYRIGHT: ISOIL IMPIANTI S.p.A.
X4 accepts wires having section 0,25÷1,5mm²
fig.9- OPEN COLLECTOR
INSTALLATION MANUAL
X8 connector X8-1= INPUT n° 7 X8-3= INPUT n° 8
The inputs can be connected to FREE CONTACTS (see fig.10) fig.10) X8 accepts wires having section 0,25÷1,5mm²
fig.10- FREE CONTACTS
Page n°9 of 30
Reproduction of this document in any form is strictly prohibited by law
Code MA 350/01/EN/11 dated 01/2016
5.1.3.
DIGITAL POWER OUTPUTS CONNECTIONS
X2 accepts wires having section 0,5÷2,5mm²
fig. 12 – X2 connector position
fig.11 – electrical connection example
ELECTRICAL CHARACTERISTICS FOR OUT N. 1 4 – SOLID STATE RELAY Operating voltage range: 100260 Vac (5060Hz) Load Current Range: 1 Arms
Max Off-State Leakage @ Rated Current: 2 mA rms Max On-State Voltage Drop @ Rated Current: 1,5 Vpk
ELECTRICAL CHARACTERISTICS FOR OUT N. 5, 6 and 7 – MECHANICAL RELAY Maximum switching power: 750VA, 90W Maximum switching voltage: 270 Vac, 125 Vdc Maximum swiching current: 2A Min switching load: 1mA, 5V
Page n°10 of 30
INSTALLATION MANUAL
COPYRIGHT: ISOIL IMPIANTI S.p.A.
Code MA/350/01/EN/11 dated 01/2016
Reproduction of this document in any form is strictly prohibited by law
5.1.4.
DIGITAL OUTPUTS CONNECTIONS
WARNING: J1=1-2 fig.13 – example n.1 (internal power supply)
WARNING: J1=2-3 fig.14 –example n.2 (external power supply)
NOTE: Operating
Voltage Range: 5 30 Vdc - Max Load Current: 0,2 A – Vce 1,8 Vmax
To
use internal voltage (+12Vdc) put the jumper on J1 to 1-2 position
X3
accepts wires having a section 0,25÷1,5mm²
fig.15 – X3 and J1 position COPYRIGHT: ISOIL IMPIANTI S.p.A.
INSTALLATION MANUAL
Page n°11 of 30
Reproduction of this document in any form is strictly prohibited by law
Code MA-350/01/EN/11 dated 01/2016
WARNING: J1=2-3 fig.16 – example n.3 (CURRENT SINK)
WARNING: J1=2-3 fig.17 – example n.4 (CURRENT SOURCE)
NOTE: Operating
Voltage Range: 5 30 Vdc - Max Load Current: 0,2 A – Vce 1,8 Vmax
To
use external voltage put the jum jumper per on J1 in 2-3 position
X3
accepts wires having a section 0,25÷1,5mm²
fig.18 – X3 and J1 position
Page n°12 of 30
INSTALLATION MANUAL
COPYRIGHT: ISOIL IMPIANTI S.p.A.
Code MA/350/01/EN/11 dated 01/2016
Reproduction of this document in any form is strictly prohibited by law
5.1.5.
PULSES INPUTS COUNTING CONNECTIONS
fig.19 - OPEN COLLECTOR
fig.20 – ACTIVE PULSES
X5 connector connector X5-1= +5 Vdc 100 mA max. X5-2=CHANNEL “A” X5-3=CHANNEL “B” X5-4=(-) GND X5-5= +12 Vdc 100mA max. The pulses inputs (CHANNEL A and B) accept signal from: OPEN COLLECTOR (see fig.19) fig.19) ACTIVE PULSES V(High) = 4 Vdcmin ÷ 30 Vdcmax; V(Low) = 1 Vdc
max 8
(see fig.20)
The 5 Vdc (X5-1) and 12 Vdc (X5-5) can be used to supply external pulse emitters. X5 accepts wires having section secti on 0,25÷1,5mm²
COPYRIGHT: ISOIL IMPIANTI S.p.A.
fig.21 – X5 position position
INSTALLATION MANUAL
Page n°13 of 30
INSTALLATION MANUAL
Reproduction of this document in any form is strictly prohibited by law
Code MA-350/01/EN/11 dated 01/2016
5.1.6.
4 20 mA INPUTS/OUTPUTS (OPTIONAL) INPUTS - TWO WIRES 420mA SENSORS
OUTPUTS - TWO WIRES CONNECTIONS
Fig.22
Fig.23
INPUTS – INPUTS – THREE WIRES 420mA SENSORS
Fig.25 - X14 position NOTE: cable entry n° 5 (see fig.3). These connectors are suitable for wires of AWG 28 14. Use shielded cable. Use
Fig.24
Page n°14 of 30
COPYRIGHT: ISOIL IMPIANTI S.p.A.
INSTALLATION MANUAL
Code MA/350/01/EN/11 dated 01/2016
Reproduction of this document in any form is strictly prohibited by law
5.1.7.
SERIAL COMMUNICATION LINES CONNECTIONS LINE 1 and LINE 2 (RS485)
LINE 3 and LINE 4 (RS232)
LINE 5 (RS422/485)
fig.26
fig.27
fig.28
X6 = N°2 RS485 (see fig.26) X7 = N°2 RS232 (see fig.27) fi g.27) X9 = N°1 RS422/485 (see fig.28)
X6, X7 and X9 accept wires having section 0,25÷1,5mm²
fig.29 – X6, X7 e X9 position
COPYRIGHT: ISOIL IMPIANTI S.p.A.
Page n°15 of 30
INSTALLATION MANUAL
Reproduction of this document in any form is strictly prohibited by law
Code MA-350/01/EN/11 dated 01/2016
CABLES for RS232 and RS485/422 TYPE: BELDEN 9842 (2 PAIRS), BELDEN 9843 (3 PAIRS), BELDEN 9844 (4 PAIRS) TYPE: BELDEN DESCRIPTION: 24 AWG (7 X 32) TINNED COPPER CNDRS., POLYETHYLENE INSULATED PAIRS, OVERALL BELDFOIL(R) AND TINNED COPPER 28 BRAID SHIELD WITH A 24 AWG STRANDED TINNED COPPER DRAIN WIRE, PVC JACKET. ELECTRICAL CHARACTERISTICS: NOM. CAPACITANCE CONDUCTOR TO SHIELD @ 1 KHZ*: 23.0 PF/FT. NOM. IMPEDANCE: 120 OHMS NOM. CONDUCTOR DC RESISTANCE @ 20 DEG. C: 24 OHMS/1000 FT NOM. SHIELD DC RESISTANCE @ 20 DEG. C: 2.20 OHMS/1000 FT. NOM. VELOCITY OF PROPAGATION: 66% PHYSICAL CHARACTERISTICS: TEMPERATURE RATING: -30 TO +80 °C MIN. BEND RADIUS: 2.5" LINE TYPE
RS 232
RS 485/422
BAUD RATE 19.200 9.600 4.800
METERS 15 50 75
CABLE TYPE BELDEN 9842, 9843, 9844 BELDEN 9842, 9843, 9844 BELDEN 9842, 9843, 9844
2.400 1.200 19.200 9.600 4.800 2.400 1.200
75 75 1200 1200 1200 1200 1200
BELDEN 9842, 9843, 9844 BELDEN 9842, 9843, 9844 BELDEN 9842, 9843, 9844 BELDEN 9842, 9843, 9844 BELDEN 9842, 9843, 9844 BELDEN 9842, 9843, 9844 BELDEN 9842, 9843, 9844
SUGGESTIONS: The cables can be different types but with the same characteristics Suitable anti over-voltages protection devices must be considered aga against inst atmospheric (Suggested: ISOIL PL360/2) PL360/2) The communication lines must be segregated from power leading cables. Ducts must be separated For W&M reasons is preferable that communication lines for SPD and for other systems (PC, PLC, DCS…) are separated. Using the same multi-cable can occur
problemsthe in case a sealing the path is required. Limiting number of theofdevices connected in multi-point; avoid for example to connect together all the VEGAII for the same product. Consider to use more SPD and printers. Choosing cables suitable as electrical characteristics and mechanical strength.
Page n°16 of 30
COPYRIGHT: ISOIL IMPIANTI S.p.A.
INSTALLATION MANUAL
Code MA/350/01/EN/11 dated 01/2016
Reproduction of this document in any form is strictly prohibited by law
5.2.
Ex-ia AREA ELECTRICAL CONNECTIO CONNECTIONS NS
5.2.1.
DIGITAL INPUTS CONNECTIONS FREE CONTACTS CONNECTIONS
WARNING PARAMETERS THAT MUST BE RESPECTED: Maximum external capacity: Co = 17,4 µF Maximum external inductance: Lo = 8,7 mH In this case the parameters are relative to the cables used because the free contact sensors haven’t capacity or inductance.
fig.30
fig.31
Use only the entries n. 6 and 7 located on the right side of the VEGA T (see fig.3).
NAMUR SENSORS CONNECTIONS
WARNING PARAMETERS THAT MUST BE RESPECTED: Values for every single sensor: Maximum voltage: Maximum current: Maximum power: Maximum external capacity: Maximum external inductance:
fig.32
fig.33
Uo=10,4 Vdc Io = 134 mA Po = 0,35 W Co=17,4 µF Lo = 8,7 mH
Use only the entries n. 6 and 7 located on the right side of the VEGA T (see fig.3).
X10 and X11 accept wires having section from from 0,25 to 1,5mm² COPYRIGHT: ISOIL IMPIANTI S.p.A.
Page n°17 of 30
INSTALLATION MANUAL
Reproduction of this document in any form is strictly prohibited by law
Code MA-350/01/EN/11 dated 01/2016
5.2.2.
THERMAL SENSOR Pt100 CONNECTIO CONNECTIONS NS THERMAL SENSOR “PT100 “ CONNECTIONS
fig.34- four wires connections
fig.35- X12 connector position NOTE The cable used to connect VEGA T with PT100 must respect the following parameters: Co=17,4 µF Maximum capacity: Maximum inductance: Lo = 8,7 mH Use only cable entries n.6 or n. 7 (see fig.3). X12 accepts wires having section from 0,25 to 1,5mm² Use only thermal sensors type PT100 class A IEC751, DIN 43760
((0,00385 /°C)). /°C)). Pt100 can be not ATEX certified certified because is a simple apparatus. WARNING: The cable used to connect VEGA T with PT100 PT100 must be 4 wires. Connect the fourth wire with the third on the connector of the PT100. fig.36- three wires connections
Page n°18 of 30
COPYRIGHT: ISOIL IMPIANTI S.p.A.
Code MA/350/01/EN/11 dated 01/2016
INSTALLATION MANUAL
Reproduction of this document in any form is strictly prohibited by law
5.3.
EXAMPLES OF CONNECTIONS CONNECTIONS
5.3.1.
EXAMPLE OF CONNECTIONS WITH DTE (DATA TERMINAL EQUIPMENT)
fig.37 Notes: MULTIPRO 6 = Sourge protection device for serial communication lines type RS422/RS485 RS422/RS485 COPYRIGHT: ISOIL IMPIANTI S.p.A.
Page n°19 of 30
INSTALLATION MANUAL
Reproduction of this document in any form is strictly prohibited by law
5.3.2.
EXAMPLE OF CONNECTIONS WITH PRINTER “ST500-A” (maximum distance 50m)
fig.38 Notes: ST500-A = Needles printer with 80 columns and RS232 communication line PL360/1 = Sourge protection device for serial communication lines type RS232
Code MA-350/01/EN/11 dated 01/2016
Page n 20 of 30 Code MA/350/01/EN/11 dated 01/2016
COPYRIGHT: ISOIL IMPIANTI S.p.A. Reproduction of this document in any form is strictly prohibited by law
INSTALLATION MANUAL
5.3.3.
EXAMPLE OF CONNECTIONS WITH PRINTER “ST500-B” (maximum distance 1000m)
fig.39 Notes: ST500-B = Needles printer with 80 columns and RS422/RS485 (4 wires) communication line PL360/2 = Sourge protection device for serial communication lines type RS422/RS485
COPYRIGHT: ISOIL IMPIANTI S.p.A. Reproduction of this document in any form is strictly prohibited by law
INSTALLATION MANUAL
Page n 21 of 30 Code MA-350/01/EN/11 dated 01/2016
5.3.4.
EXAMPLE OF MULTIDROP CONNECTIONS WITH PRINTER “ST500-M” (maximum distance 1000m)
fig.40 Notes: ST500-M = Needles printer with 80 columns columns and RS422/RS485 (4 wires) communication line. It gives the possibility to use the same printer to print the data coming from many VEGA T (max n.16) MULTIPRO 6 = Sourge protection device for serial communication lines type RS422/RS485
Page n 22 of 30 Code MA/350/01/EN/11 dated 01/2016
COPYRIGHT: ISOIL IMPIANTI S.p.A. Reproduction of this document in any form is strictly prohibited by law
INSTALLATION MANUAL
5.3.5.
EXAMPLE OF MULTIDROP CONNECTIONS CONNECTIONS WITH PRINTING SYSTEM “SPD-02” + PRINTER “ST501” (maximum distance 1000m)
Fig.41 Notes:
ST501 = Printer with 80 columns, 24 needles and parallel CE CENTRONICS NTRONICS port SPD-02 = Shared Printing Device with sourge protection included. MULTIPRO 6 = Sourge protection device for serial communication lines type RS422/RS485
COPYRIGHT: ISOIL IMPIANTI S.p.A. Reproduction of this document in any form is strictly prohibited by law
INSTALLATION MANUAL
Page n°23 of 30 Code MA-350/01/EN/11 dated 01/2016
6.
ASSOCIABLE ISOIL DEVICES DEVICES
6.1.
ISOIL PULSE EMITTER “EM6422”
Pulse emitter “Encoder EM6422”, developed by ISOIL IMPIANTI, converts the rotary motion of a Positive Displacement Meter into electric pulses representing the delivered volume. It allows the pdmeter to interface with an electronic control device (electronic register, flow computer). The pulse emitter can be factory installed directly on to the front cover af any new Isoil pdmeter. By the use of suitable flanges it can be retrofitted onto any existing ISOIL pdmeter, in place of the mechanical register or other pulse emitters. Installation on most other manufacturer’s pdmeter is possible as well by means of specialutilizes adaptors. Unlike most similar devices, which use optical sensors, the EM6422 a state-of–the-art method, that detects the rotary motion of the pdmeter’s shaft through a thin separating wall. The electronic circuit is placed in a sealed housing completely insulated from the process fluid in the pdmeter. The housing is closed by a cover with o-ring seal and there is a threaded female inlet for cable glands or counduit entrance. In the following tables are included the nominal number of pulses for litre emitted by EM6422 when is mounted directly on the relative ISOIL METER. The “number of pulses” must be programmed inside the parameter K-FACTOR of the VEGAT.
fig.42 – EM6422
Table ISOIL PDMETER EM6422 (64 pulses/revolution) ISOIL METER
Pulses/liter
ISOIL METER
Pulses/liter
ISOIL METER
Pulses/liter
SBM 32 SBM 75 SBM 150 S 9000
133,056 102,4 28,073 13,0
BM 200 BM 400 BM 600 P 4000
28,131 14,065 9,377 13,0
LBM 1000 LBM 3000
4,33 2,166
ISOIL METER
Pulses/liter
ISOIL METER
Pulses/liter
ISOIL METER
Pulses/liter
SBM 32 SBM 75 SBM 150 S 9000
532,244 409,6 112,292 52
BM 200 BM 400 BM 600 P 4000
112,524 56,26 37,508 52
LBM 1000 LBM 3000
17,053 8,664
Table ISOIL PDMETER EM6422 (256 pulses/revolution)
Page n°24 of 30 Code MA/350/01/EN/11 dated 01/2016
COPYRIGHT: ISOIL IMPIANTI S.p.A. Reproduction of this document in any form is strictly prohibited by law
INSTALLATION MANUAL
1.111
TU
6.1.1.
CONNECTIONS WITH EM6422 PULSES TRANSMISSION VERSION
fig. 43
6.1.2.
CONNECTION WITH EM6422 CanBus TRANSMISSION VERSION
EM6422 Address: 21(Hex) see switch SW2
fig. 44
COPYRIGHT: ISOIL IMPIANTI S.p.A. Reproduction of this document in any form is strictly prohibited by law
Page n°25 of 30 Code MA-350/01/EN/11 dated 01/2016
INSTALLATION MANUAL
6.2.
ISOIL THERMAL PROBE Pt100
6.2.1.
Pt100 NOT Ex-d 72
EXAGON 26mm
20
20
32
1/2" NPT
Ø8
1
Ø6
ISO IS O IL
14,6
FONTANA
18,6
Brembilla
1/2" NPT 70
fig.45 – Pt100 dimensions fig.46 –GRIT TECHNICAL SPECIFICATIONS Mechanical specifications Mounting/enclosure: Installation with integral thread 1/2" NPT Operating temperature of connecting line: - 30 ... + 60 °C Dimensions: see fig.45 Installation position: any Weight approx. = 0.6 kg Ambient conditions Operating temperature of connecting head: - 40 ... + 60 °C Operating temperature of connecting line: - 30 ... + 60 °C Degree of protection: IP 65 in accordance with EN 60529 Electrical specifications
fig.47 – electrical drawing connection
Cable connection: 5 m lenght, four-wired, armoured, with open ends to the connection. Device-specific data Measuring element: Pt 100 in accordance with DIN IEC 751, class A Measuring range: - 50 ... + 200 °C Response time: t90 < 15 s, Calibration points: at 0 °C and 50 °C NOTE: The sensor Pt100 must be installed near the meter.
Page n°26 of 30 Code MA/350/01/EN/11 dated 01/2016
COPYRIGHT: ISOIL IMPIANTI S.p.A. Reproduction of this document in any form is strictly prohibited by law
INSTALLATION MANUAL
6.2.2.
Pt100 Ex-d
Brembilla
ISO IS O IL
FONTANA
FONTANA
Brembilla
1/2" NPT
IS ISOIL OIL IM PIANTI S S.p.A. .p.A.
COPYRIGHT: ISOIL IMPIANTI S.p.A. Reproduction of this document in any form is strictly prohibited by law
INSTALLATION MANUAL
7.
VERSIONS
VERSIONS OF FLOW COMPUTER “ VEGA T”
X
TOTALI TALIZER ZER + PRESET TOTALIZER+ PRESET+ TEMPERA EMPERAT TURE C OMPENSAT MPENSATION IO N
3 4
ONE METER POWERSUPPLY 115/230 115/ 230 Vac Vac POWER SUPPLY 24 Vdc Vdc FIXED FIELD FIXED FIELD WITHOUTANALOG ANALOG I/ O 4÷20 mA WITH TWO INPUT INPUTS AND TWO OUTPUTS 4÷20 mA FIXED FIELD
2
9
X
-
1
N
X
3
9 5 8 1 N 0 1 3
Page n°27 of 30 Code MA-350/01/EN/11 dated 01/2016
Page n°28 of 30 Code MA/350/01/EN/11 dated 01/2016
INSTALLATION MANUAL
COPYRIGHT: ISOIL IMPIANTI S.p.A. Reproduction of this document in any form is strictly prohibited by law
8.
SPARE PARTS OF VEGA T
N.
DESCRIPTION
1
KIT WITH ALL NECESSARY SCREWS TO CLOSE THE COVER
2
KIT KEYBOARD
3 4
MAIN ELECTRONIC BOARD (VDC VERSION) KIT KEYBOARD CONNECTION
5
DISPLAY BOARD
6
MEMORY BOARD WITH SOFTWARE INSTALLED
8
WEIGHT AND MEASURE SWITCH
9
FUSE 3.15 AL 250V “5x20mm”
10
I/O 4-20mA BOARD
11
KIT WITH ALL THE CLAMPS
12
PT100 BOARD
13
KIT WITH N.4 SILENT BLOCKS
14
COVER
15
O-RING FOR COVER
ATTENTION To ask for some SPARE PARTS you have to give the number of SPARE PART and the SERIAL NUMBER of the VEGA T. You can find the serial number on the external ATEX plate.
Fig.48 – SPARE PARTS
COPYRIGHT: ISOIL IMPIANTI S.p.A. Reproduction of this document in any form is strictly prohibited by law
INSTALLATION MANUAL
Page n°29 of 30 Code MA-350/01/EN/11 dated 01/2016