   VEGA T ELECTRONIC COUNTER 

 

INSTALLATION MANUAL  VAC VERSION CODE REVISION

Isoil Impianti S.p.A. - Italy Italy   Sede ed e e stab tabil ilimento imento Head o ffice ffice and fa ctory 24061 Albano Alba no S.Aless .Alessandro (BG) (BG)   74, via Madonna delle Rose  Tel.  Tel. +39 035 035 4239 4239.0 .011 11 Fa Fax x +39 035 582078 E-ma E-mail il : [email protected]  [email protected]  Web : www.is www.isoilmeter oilmeter.co .co m 

Uffici Uffici C ommerciali Sales office 20092 C inisello Balsamo (MI)  (MI)  27, via F.lli F.lli Grac c hi  Tel. +39 02 6602 66027. 7.1 1 Fa Fax x +39 02 6123202 E-mail : sales@i sales@isoil-impia soil-impia nti.it nti.it  

Sede legale Registered Regis tered offi o ffic ce 20124 Milano  Milano  24, viale Vittorio Veneto C ap itale soc . int. Sottosc Sottoscri ritto tto 774.00 774.000 0 Euro C od ice Fisc . e part. p art. IVA 1306 1306690 690015 0153 3 C .C .I.A.A. .I.A.A . MI - Reg. Impr. 8 8644 6449/2000 9/2000 R.E.A. Mila no 16127 1612783 83

: MA/350/01/EN/11 : 01/2016

 

Information in this manua manuall is s ubject to change without pri or notic e. The manufa manufacturer cturer is not responsible for mist ake akes s in th is material or for inci denta dentall damage caused as as a direct or indirect result of the delivery, performance performance or use of t his material. 

 

 

2.2. 

INSTALLATION IN HAZARDOUS AREA Hazardous area/Zone Gas, mists or vapours Gas, mists or vapours Gas, mists or vapours

2.3. 

 AREA OF SAFE INSTALLATION INSTALLATION  Category according to 94/9/CE directive

Allowed

1G 2G 3G

Only for the devices connected to the Ex-ia inputs YES YES

Zone 0 Zone 1 Zone 2

 ATEX PLATE DESCRIPTION DESCRIPTION

fig.1 - ATEX PLATE

DESCRIPTION

LABEL

Symbol of the apparatus that can be installed in hazardous area II  II  2  (1) G  Ex d [ia Ga Ga]] ib IIB IIB   Gb T6 T6   Tamb. -IP 25÷ °C   66+ 66    55 °C 

Group II (surface) CATEGORY 2 APPARATUS. VEGA T can be installed in ZONE 1 CATEGORY 1 APPARATUS. The device connected to the Ex-ia inputs can be installed in ZONE 0. Explosive atmospheres caused by gas Type of protection, gas group Explosin protection level Temperature class Working temperature Degree ofenvironmental mechanical protection Symbol of conformity with European community norms

0080   0080

INERIS05 ATEX0034X

Number of Notified Body involved in ATEX/Q surveillance (INERIS)

Certificate number

COPYRIGHT: ISOIL IMPIANTI S.p.A. Reproduction of this document in any form is strictly prohibited by law

INSTALLATION MANUAL

Page n°3 of 30 Code MA-350/01/EN/11 dated 01/2016

 

 

3. 

INSTRUCTIONS FOR MOUNTING Before to mount VEGA T the following recommendations have to be considered: 1.  VEGA T mounting position has to be chosen to allow easy opening and wiring 2.  The position must avoid damages caused from the passage of the trucks but also to assure good visibility of the indications 3.  Avoid exposing the device to the rain and to the solar beams directly: a simple canopy of protection is to be forecast 4.  Mounting has be done by using the 4 silent blocks located under the housing (see fig.2) 5.  Before opening the device read the safety instructions at paragraph 2 6.  The opening is done by removing the 14 screws that close the cover (see fig.2) – Take attention that the gasket remains in its own position.

WARNING: VEGA T MUST BE PROTECTED FROM DIRECT SUNLIGHT  SUNLIGHT 

fig.2 – external dimensions Page n°4 of 30 Code MA/350/01/EN/11 dated 01/2016

INSTALLATION MANUAL

COPYRIGHT: ISOIL IMPIANTI S.p.A. Reproduction of this document in any form is strictly prohibited by law

 

 

4. 

TECHNICAL SPECIFICATIONS

4.1. 

 AMBIENT CONDITIONS CONDITIONS Operating temperature Storage temperature Humidity

-25 ÷+55°C (-13 ÷131°F) -40 ÷+65°C (-40÷149°F) 5÷95% without condensation

WARNING: VEGA WARNING:  VEGA T should be shaded from direct sunlight. For temperatures lower then –5°C VEGA T must be maintained switched on 4.2. 

4.3. 

HOUSING PROTECTION  ATEX

CE 0080 

Weatherproof MECHANICAL SPECIFICATIONS

IP66  IP66 

Housing material Dimensions Weight Fitting Cable entries keyboard 4.4. 

II 2 (1) G Ex d [ia Ga] ib IIB T6 Gb CE - Certificate INERIS 05 ATEX0034 

 Aluminium casting 248 x 248 x 76 mm 6 kg By four silent blocks (see fig.1) n° 7 holes ½” NPT or on request M20x1,5” 28 push-button membrane type

ELECTRICAL SPECIFICATIONS SPECIFICATIONS Power supply Count inputs Power supply for pulses emitters Ex-iadigital digitalinputs inputs Ex-d Ex-d Digital outputs Ex-d Digital power outputs

115÷230 Vac 15W n° 1 input, A and B channels phased of 90° ± 10°, f m max ax 5kHz. Open collector or Square wave: V(High) = 4 Vdcmin ÷ 24 Vdcmax;  V(Low) = 1 Vdc +5Vdc 100mA or 12 Vdc 100mA

max

Ex-ia Temperature probe imputs Ex-d Serial communication lines

N° 4 6,from: powered VEGA Torfrom: contacts (simple devices) or Exia NAMUR SENSORS N° Freeby contacts OpenFree Collector N°4 current sink/source (10÷30Vdc) Imax=0,2 A each. OUTPUT 5, 6, and 7 (MECHANICAL (MECHANICAL RELAY) RELAY) OUTPUT 1, 2,3 and 4 (SOLID STATE RELAY)   Maximum switching power: 750VA, 90W   Operating voltage range: 100260 Vac (5060Hz)   Maximum switching voltage: 270 Vac, 125 Vdc   Load Current Range: 1 Arms   Maximum swiching current: 2A   Max Off-State Leakage @ Rated Current: 2 mA rms   Max On-State Voltage Drop @ Rated Current: 1,5 Vpk  Min switching load: 1mA, 5V Pt100 (alpha 0.00385), 0.00385), Class A IEC751, DIN 43760. n° 2 RS 485 (2 wires) + n° 2 RS 232 (TX-RX-COM) + n° 1 RS 485/422 485/422 (4 wires)

Display

Graphic Liquid Crystal Display (LCD) 240x128 pixel; LED backlight.

COPYRIGHT: ISOIL IMPIANTI S.p.A. Reproduction of this document in any form is strictly prohibited by law

INSTALLATION MANUAL

Page n°5 of 30 Code MA-350/01/EN/11 dated 01/2016

 

 

WARNING 5. 

In order to prevent VEGAT buffer battery from being completely depleted, it is necessary to connect VEGAT to power network for 24 hours straight at least once per  month. Buffer battery is used to maintain in memory the delivery data and parameters par ameters customization. 

ELECTRICAL CONNECTIONS  VEGAT is provided with 7 cable entries. The five left side entries are foreseen for power supply, pulses from encoder, output for valves, etc. The two right side si de cable entries can be used only for the intrinsically safe connections (PT100, digital inputs). Take care to choose accessories threaded ISO 7/1 (UNI 6125-74) .  VEGAT is delivered with gland en entries tries closed by plastic threaded screw-caps. These threaded screw-caps must be removed and the not utilized entries must be closed with metallic screws-plugs conforming to EN60079-1 norm.

fig. 3 – cable entries

Page n°6 of 30 Code MA/350/01/EN/11 dated 01/2016

INSTALLATION MANUAL

COPYRIGHT: ISOIL IMPIANTI S.p.A. Reproduction of this document in any form is strictly prohibited by law

 

 

fig. 4 – connectors position EX-d AREA X1 X2 X3 X4

= POWER SUPPLY (115/230 Vac) = N° 7 DIGITAL POWER OUTPUTS = N°4 DIGITAL POWER OUTPUTS = N° 2 EX-d DIGITAL INPUTS

Ex-ia AREA X10 X11 X12 X13

= N° 3 Ex-ia DIGITAL INPUTS = N° 3 Ex-ia DIGITAL INPUTS = 4 WIRES INPUTS FOR THERMAL SENSOR TYPE PT100 (*) = NOT USED

X5 = PULSE COUNTING INPUTS / POWER SUPPLY FOR PULSE EMITTERS X6 = N° 2 RS485 TWO WIRES SERIAL COMMUNICATION LINES X7 = N° 2 RS232 SERIAL COMMUNICATION LINES X8 = N° 2 EX-d DIGITAL INPUTS X9 = N° 1 RS485/422 FOUR WIRES SERIAL COMMUNICATION LINE X14 = N° 2 INPUTS 4÷20mA + 2° OUTPUTS 4÷20mA (OPTIONAL) (*) only for versions with temperature compensation COPYRIGHT: ISOIL IMPIANTI S.p.A. Reproduction of this document in any form is strictly prohibited by law

INSTALLATION MANUAL

Page n°7 of 30 Code MA-350/01/EN/11 dated 01/2016

Reproduction of this document in any form is strictly prohibited by law

Code MA 350/01/EN/11 dated 01/2016

 

 

5.1. 

Ex-d AREA - ELE ELECTRICAL CTRICAL CON CONNECTIONS NECTIONS

5.1.1. 

POWER SUPPLY CONNECTION

  fig.5 – power supply connections

fig. 6 – X1 and internal EARTH position

NOTE Put a 2 Ampere external fuse in series to the PHASE (see fig.5).   The X1 connector accepts wires having having section 0,5÷2,5mm²   

Page n°8 of 30

INSTALLATION MANUAL

COPYRIGHT: ISOIL IMPIANTI S.p.A.

Code MA/350/01/EN/11 dated 01/2016

Reproduction of this document in any form is strictly prohibited by law

 

 

5.1.2. 

DIGITAL INPUTS CONNECTIONS

 X4 connector  X4-1= + 5 Vdc 100mA max  X4-2=INPUT n° 9  X4-3=INPUT n° 10  X4-4=(-) GND  X4-5=+ 12 Vdc 100mA max  max  The inputs can be connected to: FREE CONTACTS (see fig.8)  fig.8)    OPEN COLLECTOR (see fig.9)  fig.9)    fig.7 –X4 and X8 connectors position

ig.8 – FREE CONTACTS f ig.8

COPYRIGHT: ISOIL IMPIANTI S.p.A.

X4 accepts wires having section 0,25÷1,5mm²

fig.9- OPEN COLLECTOR

INSTALLATION MANUAL

X8 connector   X8-1= INPUT n° 7  X8-3= INPUT n° 8

The inputs can be connected to FREE CONTACTS (see fig.10)  fig.10)  X8 accepts wires having section 0,25÷1,5mm²

fig.10- FREE CONTACTS

Page n°9 of 30

Reproduction of this document in any form is strictly prohibited by law

Code MA 350/01/EN/11 dated 01/2016

 

 

5.1.3. 

DIGITAL POWER OUTPUTS CONNECTIONS

X2 accepts wires having section 0,5÷2,5mm²

fig. 12 – X2 connector position

fig.11 – electrical connection example

 

ELECTRICAL CHARACTERISTICS FOR OUT N. 1 4 – SOLID STATE RELAY Operating voltage range: 100260 Vac (5060Hz) Load Current Range: 1 Arms

   

Max Off-State Leakage @ Rated Current: 2 mA rms Max On-State Voltage Drop @ Rated Current: 1,5 Vpk

 

       

ELECTRICAL CHARACTERISTICS FOR OUT N. 5, 6 and 7 – MECHANICAL RELAY Maximum switching power: 750VA, 90W Maximum switching voltage: 270 Vac, 125 Vdc Maximum swiching current: 2A Min switching load: 1mA, 5V

Page n°10 of 30

INSTALLATION MANUAL

COPYRIGHT: ISOIL IMPIANTI S.p.A.

Code MA/350/01/EN/11 dated 01/2016

Reproduction of this document in any form is strictly prohibited by law

 

 

5.1.4. 

DIGITAL OUTPUTS CONNECTIONS

WARNING: J1=1-2 fig.13 – example n.1 (internal power supply)

WARNING: J1=2-3 fig.14 –example n.2 (external power supply)

NOTE:  Operating

Voltage Range: 5 30 Vdc - Max Load Current: 0,2 A – Vce 1,8 Vmax

  To

use internal voltage (+12Vdc) put the jumper on J1 to 1-2 position

  X3

accepts wires having a section 0,25÷1,5mm² 

fig.15 – X3 and J1 position COPYRIGHT: ISOIL IMPIANTI S.p.A.

INSTALLATION MANUAL

Page n°11 of 30

Reproduction of this document in any form is strictly prohibited by law

Code MA-350/01/EN/11 dated 01/2016

 

 

WARNING: J1=2-3 fig.16 – example n.3 (CURRENT SINK)

WARNING: J1=2-3 fig.17 – example n.4 (CURRENT SOURCE)

NOTE:  Operating

Voltage Range: 5 30 Vdc - Max Load Current: 0,2 A – Vce 1,8 Vmax

  To

use external voltage put the jum jumper per on J1 in 2-3 position

  X3

accepts wires having a section 0,25÷1,5mm² 

fig.18 – X3 and J1 position

Page n°12 of 30

INSTALLATION MANUAL

COPYRIGHT: ISOIL IMPIANTI S.p.A.

Code MA/350/01/EN/11 dated 01/2016

Reproduction of this document in any form is strictly prohibited by law

 

 

5.1.5. 

PULSES INPUTS COUNTING CONNECTIONS

fig.19 - OPEN COLLECTOR

fig.20 – ACTIVE PULSES

 X5 connector  connector   X5-1= +5 Vdc 100 mA max.  X5-2=CHANNEL “A”  X5-3=CHANNEL “B”  X5-4=(-) GND  X5-5= +12 Vdc 100mA max. The pulses inputs (CHANNEL A and B) accept signal from:   OPEN COLLECTOR (see fig.19)  fig.19)     ACTIVE PULSES V(High) = 4 Vdcmin ÷ 30 Vdcmax;  V(Low) = 1 Vdc  

max 8

(see fig.20)

The 5 Vdc (X5-1) and 12 Vdc (X5-5) can be used to supply external pulse emitters. X5 accepts wires having section secti on 0,25÷1,5mm²

COPYRIGHT: ISOIL IMPIANTI S.p.A.

fig.21 – X5 position  position 

INSTALLATION MANUAL

Page n°13 of 30

INSTALLATION MANUAL

Reproduction of this document in any form is strictly prohibited by law

Code MA-350/01/EN/11 dated 01/2016

 

 

5.1.6. 

4 20 mA INPUTS/OUTPUTS (OPTIONAL) INPUTS - TWO WIRES 420mA SENSORS

OUTPUTS - TWO WIRES CONNECTIONS

Fig.22

Fig.23

INPUTS – INPUTS  – THREE WIRES 420mA SENSORS

Fig.25 - X14 position NOTE: cable entry n° 5 (see fig.3).  These connectors are suitable for wires of AWG 28 14.  Use shielded cable.  Use

Fig.24

Page n°14 of 30

COPYRIGHT: ISOIL IMPIANTI S.p.A.

INSTALLATION MANUAL

Code MA/350/01/EN/11 dated 01/2016

Reproduction of this document in any form is strictly prohibited by law

 

 

5.1.7. 

SERIAL COMMUNICATION LINES CONNECTIONS LINE 1 and LINE 2 (RS485)

LINE 3 and LINE 4 (RS232)

LINE 5 (RS422/485)

fig.26

fig.27

fig.28

X6 = N°2 RS485 (see fig.26) X7 = N°2 RS232 (see fig.27) fi g.27) X9 = N°1 RS422/485 (see fig.28)

X6, X7 and X9 accept wires having section 0,25÷1,5mm²

fig.29 – X6, X7 e X9 position

COPYRIGHT: ISOIL IMPIANTI S.p.A.

Page n°15 of 30

INSTALLATION MANUAL

Reproduction of this document in any form is strictly prohibited by law

Code MA-350/01/EN/11 dated 01/2016

 

 

CABLES for RS232 and RS485/422 TYPE: BELDEN 9842 (2 PAIRS), BELDEN 9843 (3 PAIRS), BELDEN 9844 (4 PAIRS) TYPE: BELDEN DESCRIPTION: 24 AWG (7 X 32) TINNED COPPER CNDRS., POLYETHYLENE INSULATED PAIRS, OVERALL BELDFOIL(R) AND TINNED COPPER 28 BRAID SHIELD WITH A 24 AWG STRANDED TINNED COPPER DRAIN WIRE, PVC JACKET. ELECTRICAL CHARACTERISTICS: NOM. CAPACITANCE CONDUCTOR TO SHIELD @ 1 KHZ*: 23.0 PF/FT.   NOM. IMPEDANCE: 120 OHMS     NOM. CONDUCTOR DC RESISTANCE @ 20 DEG. C: 24 OHMS/1000 FT   NOM. SHIELD DC RESISTANCE @ 20 DEG. C: 2.20 OHMS/1000 FT. NOM. VELOCITY OF PROPAGATION: 66%   PHYSICAL CHARACTERISTICS:   TEMPERATURE RATING: -30 TO +80 °C MIN. BEND RADIUS: 2.5"    LINE TYPE

RS 232

RS 485/422

BAUD RATE 19.200 9.600 4.800

METERS 15 50 75

CABLE TYPE BELDEN 9842, 9843, 9844 BELDEN 9842, 9843, 9844 BELDEN 9842, 9843, 9844

2.400 1.200 19.200 9.600 4.800 2.400 1.200

75 75 1200 1200 1200 1200 1200

BELDEN 9842, 9843, 9844 BELDEN 9842, 9843, 9844 BELDEN 9842, 9843, 9844 BELDEN 9842, 9843, 9844 BELDEN 9842, 9843, 9844 BELDEN 9842, 9843, 9844 BELDEN 9842, 9843, 9844

SUGGESTIONS: The cables can be different types but with the same characteristics   Suitable anti over-voltages protection devices must be considered aga against inst atmospheric (Suggested: ISOIL PL360/2) PL360/2)   The communication lines must be segregated from power leading cables. Ducts must be separated     For W&M reasons is preferable that communication lines for SPD and for other systems (PC, PLC, DCS…) are separated. Using the same multi-cable can occur    

problemsthe in case a sealing the path is required. Limiting number of theofdevices connected in multi-point; avoid for example to connect together all the VEGAII for the same product. Consider to use more SPD and printers. Choosing cables suitable as electrical characteristics and mechanical strength.

Page n°16 of 30

COPYRIGHT: ISOIL IMPIANTI S.p.A.

INSTALLATION MANUAL

Code MA/350/01/EN/11 dated 01/2016

Reproduction of this document in any form is strictly prohibited by law

 

 

5.2. 

Ex-ia AREA ELECTRICAL CONNECTIO CONNECTIONS NS

5.2.1. 

DIGITAL INPUTS CONNECTIONS FREE CONTACTS CONNECTIONS

WARNING PARAMETERS THAT MUST BE RESPECTED: Maximum external capacity: Co = 17,4 µF Maximum external inductance: Lo = 8,7 mH   In this case the parameters are relative to the cables used because the free contact sensors haven’t capacity or inductance.

fig.30

fig.31

Use only the entries n. 6 and 7 located on the right side of the VEGA T (see fig.3).

NAMUR SENSORS CONNECTIONS

WARNING PARAMETERS THAT MUST BE RESPECTED: Values for every single sensor: Maximum voltage: Maximum current: Maximum power: Maximum external capacity: Maximum external inductance:

fig.32

fig.33

Uo=10,4 Vdc Io = 134 mA Po = 0,35 W Co=17,4 µF Lo = 8,7 mH  

Use only the entries n. 6 and 7 located on the right side of the VEGA T (see fig.3).

 X10 and X11 accept wires having section from from 0,25 to 1,5mm² COPYRIGHT: ISOIL IMPIANTI S.p.A.

Page n°17 of 30

INSTALLATION MANUAL

Reproduction of this document in any form is strictly prohibited by law

Code MA-350/01/EN/11 dated 01/2016

 

 

5.2.2. 

THERMAL SENSOR Pt100 CONNECTIO CONNECTIONS NS THERMAL SENSOR “PT100 “ CONNECTIONS

fig.34- four wires connections

fig.35- X12 connector position NOTE The cable used to connect VEGA T with PT100 must respect the following parameters: Co=17,4 µF   Maximum capacity:   Maximum inductance: Lo = 8,7 mH    Use only cable entries n.6 or n. 7 (see fig.3). X12 accepts wires having section from 0,25 to 1,5mm² Use only thermal sensors type PT100 class A IEC751, DIN 43760 

((0,00385  /°C)).  /°C)).   Pt100 can be not ATEX certified  certified because is a simple apparatus. WARNING: The cable used to connect VEGA T with PT100 PT100 must be 4 wires. Connect the fourth wire with the third on the connector of the PT100.   fig.36- three wires connections 

Page n°18 of 30

COPYRIGHT: ISOIL IMPIANTI S.p.A.

Code MA/350/01/EN/11 dated 01/2016

INSTALLATION MANUAL

Reproduction of this document in any form is strictly prohibited by law

 

 

5.3. 

EXAMPLES OF CONNECTIONS CONNECTIONS 

5.3.1. 

EXAMPLE OF CONNECTIONS WITH DTE (DATA TERMINAL EQUIPMENT)

fig.37 Notes:   MULTIPRO 6 = Sourge protection device for serial communication lines type RS422/RS485 RS422/RS485 COPYRIGHT: ISOIL IMPIANTI S.p.A.

Page n°19 of 30

INSTALLATION MANUAL

Reproduction of this document in any form is strictly prohibited by law  

 

5.3.2. 

EXAMPLE OF CONNECTIONS WITH PRINTER “ST500-A” (maximum distance 50m)

fig.38 Notes:   ST500-A = Needles printer with 80 columns and RS232 communication line   PL360/1 = Sourge protection device for serial communication lines type RS232

Code MA-350/01/EN/11 dated 01/2016

Page n 20 of 30 Code MA/350/01/EN/11 dated 01/2016

COPYRIGHT: ISOIL IMPIANTI S.p.A. Reproduction of this document in any form is strictly prohibited by law

INSTALLATION MANUAL

 

 

5.3.3. 

EXAMPLE OF CONNECTIONS WITH PRINTER “ST500-B” (maximum distance 1000m)

fig.39 Notes:   ST500-B = Needles printer with 80 columns and RS422/RS485 (4 wires) communication line   PL360/2 = Sourge protection device for serial communication lines type RS422/RS485

COPYRIGHT: ISOIL IMPIANTI S.p.A. Reproduction of this document in any form is strictly prohibited by law

INSTALLATION MANUAL

Page n 21 of 30 Code MA-350/01/EN/11 dated 01/2016

 

 

5.3.4. 

EXAMPLE OF MULTIDROP CONNECTIONS WITH PRINTER “ST500-M” (maximum distance 1000m)

fig.40 Notes:   ST500-M = Needles printer with 80 columns columns and RS422/RS485 (4 wires) communication line. It gives the possibility to use the same printer to print the data coming from many VEGA T (max n.16)    MULTIPRO 6 = Sourge protection device for serial communication lines type RS422/RS485

Page n 22 of 30 Code MA/350/01/EN/11 dated 01/2016

COPYRIGHT: ISOIL IMPIANTI S.p.A. Reproduction of this document in any form is strictly prohibited by law

INSTALLATION MANUAL

 

 

5.3.5. 

EXAMPLE OF MULTIDROP CONNECTIONS CONNECTIONS WITH PRINTING SYSTEM “SPD-02” + PRINTER “ST501” (maximum distance 1000m)

Fig.41 Notes:  

   

ST501 = Printer with 80 columns, 24 needles and parallel CE CENTRONICS NTRONICS port SPD-02 = Shared Printing Device with sourge protection included.  MULTIPRO 6 = Sourge protection device for serial communication lines type RS422/RS485  

COPYRIGHT: ISOIL IMPIANTI S.p.A. Reproduction of this document in any form is strictly prohibited by law

INSTALLATION MANUAL

Page n°23 of 30 Code MA-350/01/EN/11 dated 01/2016

 

 

6. 

 ASSOCIABLE ISOIL DEVICES DEVICES

6.1. 

ISOIL PULSE EMITTER “EM6422”

Pulse emitter “Encoder EM6422”, developed by ISOIL IMPIANTI, converts the rotary motion of a Positive Displacement Meter into electric pulses representing the delivered volume. It allows the pdmeter to interface with an electronic control device (electronic register, flow computer). The pulse emitter can be factory installed directly on to the front cover af any new Isoil pdmeter. By the use of suitable flanges it can be retrofitted onto any existing ISOIL pdmeter, in place of the mechanical register or other pulse emitters. Installation on most other manufacturer’s pdmeter is possible as well by means of specialutilizes adaptors. Unlike most similar devices, which use optical sensors, the EM6422 a state-of–the-art method, that detects the rotary motion of the pdmeter’s shaft through a thin separating wall. The electronic circuit is placed in a sealed housing completely insulated from the process fluid in the pdmeter. The housing is closed by a cover with o-ring seal and there is a threaded female inlet for cable glands or counduit entrance. In the following tables are included the nominal number of pulses for litre emitted by EM6422 when is mounted directly on the relative ISOIL METER. The “number of pulses” must be programmed inside the parameter K-FACTOR of the VEGAT. 

fig.42 – EM6422

Table ISOIL PDMETER  EM6422 (64 pulses/revolution) ISOIL METER

Pulses/liter

ISOIL METER

Pulses/liter

ISOIL METER

Pulses/liter

SBM 32 SBM 75 SBM 150 S 9000

133,056 102,4 28,073 13,0

BM 200 BM 400 BM 600 P 4000

28,131 14,065 9,377 13,0

LBM 1000 LBM 3000

4,33 2,166

ISOIL METER

Pulses/liter

ISOIL METER

Pulses/liter

ISOIL METER

Pulses/liter

SBM 32 SBM 75 SBM 150 S 9000

532,244 409,6 112,292 52

BM 200 BM 400 BM 600 P 4000

112,524 56,26 37,508 52

LBM 1000 LBM 3000

17,053 8,664

Table ISOIL PDMETER  EM6422 (256 pulses/revolution)

Page n°24 of 30 Code MA/350/01/EN/11 dated 01/2016

COPYRIGHT: ISOIL IMPIANTI S.p.A. Reproduction of this document in any form is strictly prohibited by law

INSTALLATION MANUAL

 

  1.111

TU

6.1.1. 

CONNECTIONS WITH EM6422 PULSES TRANSMISSION VERSION

fig. 43

6.1.2. 

CONNECTION WITH EM6422 CanBus TRANSMISSION VERSION

EM6422  Address: 21(Hex) see switch SW2

fig. 44

COPYRIGHT: ISOIL IMPIANTI S.p.A. Reproduction of this document in any form is strictly prohibited by law

Page n°25 of 30 Code MA-350/01/EN/11 dated 01/2016

INSTALLATION MANUAL

 

 

6.2. 

ISOIL THERMAL PROBE Pt100

6.2.1. 

Pt100 NOT Ex-d  72

 

EXAGON 26mm

20

20

32

 1/2" NPT

Ø8

1

 

Ø6

ISO IS O  IL

14,6

FONTANA

 

18,6

Brembilla

1/2" NPT  70

fig.45 – Pt100 dimensions fig.46 –GRIT TECHNICAL SPECIFICATIONS Mechanical specifications Mounting/enclosure: Installation with integral thread 1/2" NPT Operating temperature of connecting line: - 30 ... + 60 °C Dimensions: see fig.45 Installation position: any Weight approx. = 0.6 kg  Ambient conditions Operating temperature of connecting head: - 40 ... + 60 °C Operating temperature of connecting line: - 30 ... + 60 °C Degree of protection: IP 65 in accordance with EN 60529 Electrical specifications

fig.47 – electrical drawing connection

Cable connection: 5 m lenght, four-wired, armoured, with open ends to the connection. Device-specific data Measuring element: Pt 100 in accordance with DIN IEC 751, class A Measuring range: - 50 ... + 200 °C Response time: t90 < 15 s, Calibration points: at 0 °C and 50 °C NOTE: The sensor Pt100 must be installed near the meter.

Page n°26 of 30 Code MA/350/01/EN/11 dated 01/2016

COPYRIGHT: ISOIL IMPIANTI S.p.A. Reproduction of this document in any form is strictly prohibited by law

INSTALLATION MANUAL

 

 

6.2.2. 

Pt100 Ex-d

Brembilla

ISO IS O  IL

FONTANA

FONTANA

   

Brembilla

1/2" NPT

IS ISOIL OIL IM PIANTI S S.p.A. .p.A.

COPYRIGHT: ISOIL IMPIANTI S.p.A. Reproduction of this document in any form is strictly prohibited by law

INSTALLATION MANUAL

 

 

7. 

 VERSIONS 

VERSIONS OF FLOW COMPUTER “ VEGA T”  

X

TOTALI TALIZER ZER + PRESET TOTALIZER+ PRESET+ TEMPERA EMPERAT TURE C OMPENSAT MPENSATION IO N

3 4

ONE METER POWERSUPPLY 115/230 115/ 230 Vac Vac POWER SUPPLY 24 Vdc Vdc FIXED FIELD FIXED FIELD WITHOUTANALOG ANALOG I/ O 4÷20 mA WITH TWO INPUT INPUTS AND TWO OUTPUTS 4÷20 mA FIXED FIELD

2

9

X

-

1

N

X

3

9 5 8 1 N 0 1 3

Page n°27 of 30 Code MA-350/01/EN/11 dated 01/2016

Page n°28 of 30 Code MA/350/01/EN/11 dated 01/2016

INSTALLATION MANUAL

COPYRIGHT: ISOIL IMPIANTI S.p.A. Reproduction of this document in any form is strictly prohibited by law

 

 

8. 

SPARE PARTS OF VEGA T 

N.

DESCRIPTION

1

KIT WITH ALL NECESSARY SCREWS TO CLOSE THE COVER

2

KIT KEYBOARD

3 4

MAIN ELECTRONIC BOARD (VDC VERSION) KIT KEYBOARD CONNECTION

5

DISPLAY BOARD

6

MEMORY BOARD WITH SOFTWARE INSTALLED

8

WEIGHT AND MEASURE SWITCH

9

FUSE 3.15 AL 250V “5x20mm”

10

I/O 4-20mA BOARD

11

KIT WITH ALL THE CLAMPS

12

PT100 BOARD

13

KIT WITH N.4 SILENT BLOCKS

14

COVER

15

O-RING FOR COVER

 ATTENTION To ask for some SPARE PARTS you have to give the number of SPARE PART and the SERIAL NUMBER of the VEGA T. You can find the serial number on the external ATEX plate.

Fig.48 – SPARE PARTS 

COPYRIGHT: ISOIL IMPIANTI S.p.A. Reproduction of this document in any form is strictly prohibited by law  

 

INSTALLATION MANUAL

Page n°29 of 30 Code MA-350/01/EN/11 dated 01/2016