SETTING CALCULATION FOR BUSBAR PROTECTION RELAYS 400KV BUSBAR PROTECTIONS CUSTOMER
:M/s HVPNL LTD
PROJECT
:400/220/66/33KV S/S AT FARIDABAD (NAWADA)
GRID
Page 1 of 6
400KV BUSBAR PROTECTION 1. SUBSTATION INFORMATION Settings and configuration of the P741 Numerical bus bar protection scheme is arrived based on the substation information provided by ALTOM SYSTEMS/HVPNL as detailed below. CTR - Primary of all feeders
2000
CTR - Secondary of all feeders
1
CT knee Point for all feeders
2000 V
CT resistance for all feeders
15 Ohms
Maximum Load level in a feeder
3000 A
Minimum load current in a feeder
245 A
Minimum Short circuit level (ASSUMED)
6 kA
Maximum Short circuit level
40 kA
Maximum loading of 1 bar (ASSUMED)
3000 A
Number of independent bars
Two Main System
Maximum breaking time of CB
100 m sec (assumed 40msec breaker op. time + arcing time)
2. SETTING CRIETERIA OF MiCOM P741 – CENTRAL UNIT
6 values have to be entered in MiCOM P741 central unit Note: All values in CU is for base current of 2000A. 1.ID>1 (from 0.01 to 0.5 A (secondary value)) During normal operation the differential current in the scheme should be zero or negligible. Any abnormality is detected via a given threshold ID>1. This element is using for CT supervision. Recommended setting should be more than 2 % of maximum CT ratio and less than “Minimum Loaded feeder Current”. Recommended setting is 40 A. (NOTE : IF THE SPILL CURRENT IS MORE THAN 90A SHALL BE ADJUSTED AT SITE ACCORDINGLY) 2. Slope k1 setting range is from 0% to 50%. Recommended setting is 0% , as the minimum loading current is very less and CTs are of same ratio & similar magnetising characteristics.
FOR M/S. HVPNL - NAWADA 400KV BUSBAR PROTECTION, Rev-0
Page 2 of 6
M/S. ALSTOM T&D INDIA LTD, 19/1, G.S.T.ROAD, PALLAVARAM, CHENNAI - 600043.
3. Slope k2 setting range is from 20% to 90%, and recommendation is 65% , as the CTs are of same ratio & similar magnetizing characteristics and to provide stability for through faults. A trip is only permitted if this differential current exceeds the set slope of the bias characteristic. Recommended value for normal application is 65%. 4. Slope KCZ setting range is from 0% to 90%, it should be less than Icc min (1 bar) / (((Independent bar - 1) x IloadMax (1 bar)) + Icc min (1 bar)). Recommended setting is 30%. 5.ID>2 (from 0.5 to 30 A (secondary value)) as low as possible The main differential current element of MiCOM P741 will only be able to operate if the differential current reaches a threshold ID>2. In general, this setting will be adjusted above highest normal full load current in order to avoid mal operation even max loaded feeder CT fails. Normally recommended setting is more than 110 -180% of max load level. We shall choose ID>2, more than max loading considering (high instantaneous loading) and less than 50% of minimum short circuit level. Recommended setting is 2000*1.2= 2400 A 6.ID>1 Alarm Timer (from 100ms to 600 s) shall be greater than the longest protection time (such as line, over current, etc…) Recommended time delay is 5 secs. GROUP 1 DIFF BUSBAR PROT GROUP 1 Diff Phase Fault GROUP 1 CZ Parameters Phase Slope kcz IDCZ>2 Current GROUP 1 Zone Parameters Phase Slope k2 ID>2 Current GROUP 1 Common
30.00% 2400 65.00% 2400
Phase Slope k1
0.00%
ID>1 Current
40.00 Amp
ID>1 Alarm Timer
5.00 sec
Diff Earth Fault
Disable
P741 Central unit blocking modes: GROUP1 Busbar Option: CZ circ flt mode Zx circ flt mode Circ flt reset time Circ flt block mode Cz PU error Zx PU error PU error timer PU error reset time
Alarms Latched Alarms Latched 60 secs Block / phase. Alarms Latched Alarms Latched 5 secs 60 secs
FOR M/S. HVPNL - NAWADA 400KV BUSBAR PROTECTION, Rev-0
Amp
Page 3 of 6
Amp
M/S. ALSTOM T&D INDIA LTD, 19/1, G.S.T.ROAD, PALLAVARAM, CHENNAI - 600043.
3.SETTING CRITERIA OF MICOM P743 – PERIPHERAL UNITS CT & VT RATIOS: For all feeders Phase CT Primary Phase CT Sec'y
2000 1 Amp
Amp
RBPh / RBN Power Parameters:For all feeders
--------(TO BE ENTERED AT SITE)
Standard Input
British Standard
Knee Voltage Vk
2000 V
RCT Sec'y
15 Ohms
Eff. Burden Ohm
----------(TO BE ENTERED AT SITE)
NOTE: RBPh/RBn, Vk, Rct & Effective Burden values are very important to detect /confirm the CT Saturation condition. 4. CB Fail Protection: 50 LBB CB Fail: For all feeders I< (under current)
Recommended setting is 20% of CTR. The setting is 400 A.
Retrip timer TBF1/tBF3: A re-trip can be applied after a time tBF1/tBF3. Here we are issuing the retrip command after 50ms of main trip. CBF timer TBF2/tBF4: When both the local trip & retrip have failed, the countdown continues with a second timer adjusted to have a value of tBF2/tBF4. Recommended setting is “maximum breaking time of CB” + 100 msec. Recommended tBF2 & 4 setting is 200msec. GROUP 1 CB FAIL Control By I< Current Set for all feeders I> Status GROUP 1 Internal Trip CB Fail Timer 1 CB Fail Timer 2 GROUP 1 External Trip CB Fail Timer 3 CB Fail Timer 4 5. Dead Zone Protection: Dead Zone setting for all feeders:
I< 400 Disabled 50ms 200.0ms 50ms 200.0ms
Dead zone tripping is provided to sense the fault in-between CT and breaker when breaker is open. Dead zone setting shall be more than maximum loading & less than 80 % of the minimum fault current. Time delay of 50 m secs shall be given to avoid mal operation during arcing period, CB scattering during fault, where CB Open has been realised by PU. I>DZ Current setting I> DZ time delay
FOR M/S. HVPNL - NAWADA 400KV BUSBAR PROTECTION, Rev-0
2400 50 m sec
Page 4 of 6
Amp
M/S. ALSTOM T&D INDIA LTD, 19/1, G.S.T.ROAD, PALLAVARAM, CHENNAI - 600043.
Group 1 Io supervision : Internal CT / AD converter of PU can be monitored by comparing the measured 3Io and derived neutral (IN =IR + IY + IB). Error co efficient shall be kept at 40% in order to detect internal CT (PU) failure. 40% Error factor KCE 5 secs Alarm delay 6A. SETTING SUMMARY FOR CENTRAL UNIT – P741 Group1 DIFF BUSBAR PROT Range/Options available Description Minimum Maximum Phase slope KCZ 0% 90%
Adopted Settings 30%
Remarks Check zone slope
IDCZ>2 current
50A
30.0kA
2400
Check zone threshold
Phase slope K2
20%
90%
65%
Main zone slope
ID>2 current
50A
30.0kA
2400
Main zone threshold
ID>1 current
10A
500A
90A
Circuitry fault pickup
Phase slope K1
0%
50%
0%
Circuitry fault slope
100ms
600 s
5 secs
Maximum
Adopted Settings
ID>1 Alarm timer
Circuitry fault alarm delay
Group1 Busbar Option Range/Options available
Description
Minimum
Remarks
CZ circ flt mode
Blocking latched, Alarms latched, self reset, Alarms Resetting mode Alarms latched & no block, Alarms SR & no block circuitry fault
Zx circ flt mode
Blocking latched, Alarms latched, self reset, Alarms Resetting mode of main Alarms latched & no block, Alarms SR & no block zones circuitry fault 600 s
of
CZ
Circuitry t reset
5s
Circ block mode
Blocking/ phase , 3 phase block
CZ PU Error mode
Blocking latched, Alarms latched, self reset, Alarms Resetting mode Alarms latched & no block, Alarms SR & no block during CZ error
of
PU
Zx PU Error mode
Blocking latched, Alarms latched, self reset, Alarms Resetting mode of Alarms latched & no block, Alarms SR & no block during main zone error
PU
60 s Blocking / phase
Circuitry fault reset time Blocking modes on circuitry fault
PU Error timer
2s
600 s
5secs
Alarm delay of PU error
PU Error reset
5s
600 s
60secs
Reset time of PU error
6B. SETTING SUMMARY FOR PHERIPHAL UNIT – P743 Range/Options available Description Minimum Maximum
Adopted Settings
Remarks
CT, VT Ratios: Phase CT Primary
FOR M/S. HVPNL - NAWADA 400KV BUSBAR PROTECTION, Rev-0
1A
30.0 kA
Page 5 of 6
2000 A for all CT Primary Rating feeders
M/S. ALSTOM T&D INDIA LTD, 19/1, G.S.T.ROAD, PALLAVARAM, CHENNAI - 600043.
Phase CT Secondary
1A
5A
1A
CT Secondary Rating
RBph/RBN
0.5
10
**
Ratio of Phase & neutral CT leads resistance
Standard Input
British Standard / IEC
British Standard
CT Standard
2000 V for all CT Knee point Voltage feeders
Knee Voltage Vk
20 V
5000 V
RCT Sec
0.1 Ω
50 Ω
Effective Burden ohm
0.1 Ω
200 Ω
**
Minimum
Maximum
Adopted Settings
I> DZ Current Set
60 A
4800 A
2400
I> DZ Time Delay
0 sec
100 sec
50 msec
15 Ohms forall CT sec resistance feeders Effective burden of lead
Group1 Dead Zone Protection: Description
Range/Options available
Enable/Disable
Disable
Range/Options available
Adopted Settings
IN> DZ Current Set
Remarks
Group1 CB Fail: Description
Minimum
Maximum
I