Annexure 4 Set Files & PSL

Page 1 of 252

11KV UGC Funct 50, 51, 51N, 49

Page 2 of 252

MiCOM S1 Studio

Page: 1

Settings File Report File: A10 SET.set Model Number: P141216A6M0420J

Printed on: 12/05/2010 12:48:06

: SYSTEM DATA:

00.01: 00.02: 00.03: 00.04: 00.05: 00.06: 00.08: 00.09: 00.0A: 00.0B: 00.0C: 00.0D: 00.0E: 00.10: 00.11: 00.20: 00.21: 00.22: 00.30: 00.40: 00.50: 00.51: 00.52: 00.D0: 00.D1: 00.D2: 00.D3:

Language:English Password:**** Sys Fn Links:0 Description:50/51/51N/49 Plant Reference:DID/A10/505151N Model Number:P141216A6M0420J Serial Number:3254478 Frequency:50 Hz Comms Level:2 Relay Address:1 Plant Status:0000000000000000 Control Status:0000000000000000 Active Group:1 CB Trip/Close:No Operation Software Ref. 1:P141____6__420_B Opto I/P Status:10000000 Relay O/P Status:0000000 Alarm Status 1:00000000000000000000000000000000 Opto I/P Status:10000000 Relay O/P Status:0000000 Alarm Status 1:00000000000000000000000000000000 Alarm Status 2:00000000000000000000000000000000 Alarm Status 3:00000000000000000000000000000000 Access Level:2 Password Control:2 Password Level 1:**** Password Level 2:****

: CB CONTROL: : DATE AND TIME: : CONFIGURATION:

09.01: 09.02: 09.03: 09.04: 09.05: 09.06: 09.07: 09.08: 09.09: 09.0A: 09.0B: 09.10: 09.11: 09.12: 09.13: 09.14: 09.15: 09.16:

Restore Defaults:No Operation Setting Group:Select via Menu Active Settings:Group 1 Save Changes:No Operation Copy From:Group 1 Copy To:No Operation Setting Group 1:Enabled Setting Group 2:Disabled Setting Group 3:Disabled Setting Group 4:Disabled System Config:Invisible Overcurrent:Enabled Neg Sequence O/C:Disabled Broken Conductor:Disabled Earth Fault 1:Enabled Earth Fault 2:Disabled SEF/REF Prot'n:Disabled Residual O/V NVD:Disabled

- Settings File Report -

Page 3 of 252

MiCOM S1 Studio

Page: 2

Settings File Report File: A10 SET.set Model Number: P141216A6M0420J 09.17: 09.18: 09.19: 09.1A: 09.1B: 09.1D: 09.1E: 09.1F: 09.20: 09.21: 09.22: 09.25: 09.26: 09.28: 09.29: 09.2A: 09.2B: 09.2C: 09.2D: 09.2E: 09.2F: 09.35: 09.36: 09.39: 09.FF:

Printed on: 12/05/2010 12:48:06

Thermal Overload:Enabled Neg Sequence O/V:Disabled Cold Load Pickup:Disabled Selective Logic:Disabled Admit Protection:Disabled Volt Protection:Disabled Freq Protection:Disabled df/dt Protection:Disabled CB Fail:Disabled Supervision:Disabled Fault Locator:Disabled Input Labels:Visible Output Labels:Visible CT & VT Ratios:Visible Record Control:Invisible Disturb Recorder:Visible Measure't Setup:Visible Comms Settings:Invisible Commission Tests:Invisible Setting Values:Secondary Control Inputs:Invisible Ctrl I/P Config:Invisible Ctrl I/P Labels:Invisible Direct Access:Disabled LCD Contrast:9

: CT AND VT RATIOS:

0A.01: 0A.02: 0A.07: 0A.08: 0A.09: 0A.0A: 0A.0B: 0A.0C: : : : : : :

Main VT Primary:11.00 kV Main VT Sec'y:110.0 V Phase CT Primary:400.0 A Phase CT Sec'y:1.000 A E/F CT Primary:400.0 A E/F CT Secondary:1.000 A SEF CT Primary:400.0 A SEF CT Secondary:1.000 A

DISTURB RECORDER: MEASURE'T SETUP: CB MONITOR SETUP: OPTO CONFIG: IED CONFIGURATOR: Group 1:

: GROUP 1 35.23: 35.24: 35.27: 35.2A: 35.2D: 35.2F: 35.32: 35.33:

OVERCURRENT: I>1 Function:IEC S Inverse I>1 Direction:Non-Directional I>1 Current Set:1.000 A I>1 TMS:400.0e-3 I>1 DT Adder:0 s I>1 tRESET:0 s I>2 Function:DT I>2 Direction:Non-Directional

- Settings File Report -

Page 4 of 252

MiCOM S1 Studio

Page: 3

Settings File Report File: A10 SET.set Model Number: P141216A6M0420J 35.36: 35.38: 35.3E: 35.40: 35.41: 35.44: 35.45: 35.47: 35.4E: 35.4F: 35.51: 35.52:

Printed on: 12/05/2010 12:48:06

I>2 Current Set:1.300 A I>2 Time Delay:0 s I>2 tRESET:0 s I>3 Status:Enabled I>3 Direction:Non-Directional I>3 Current Set:4.000 A I>3 Time Delay:50.00 ms I>4 Status:Disabled I> Blocking:001010000 I> Char Angle:45.00 deg V CONTROLLED O/C: VCO Status:Disabled

: GROUP 1 EARTH FAULT 1: 38.01: IN1> Input:Measured 38.25: IN1>1 Function:IEC S Inverse 38.26: IN1>1 Direction:Non-Directional 38.29: IN1>1 Current:300.0 mA 38.2D: IN1>1 TMS:400.0e-3 38.31: IN1>1 DT Adder:0 s 38.33: IN1>1 tRESET:0 s 38.36: IN1>2 Function:DT 38.37: IN1>2 Direction:Non-Directional 38.3A: IN1>2 Current:100.0 mA 38.3D: IN1>2 Time Delay:0 s 38.44: IN1>2 tRESET:0 s 38.46: IN1>3 Status:Enabled 38.47: IN1>3 Direction:Non-Directional 38.4A: IN1>3 Current:300.0 mA 38.4B: IN1>3 Time Delay:50.00 ms 38.4D: IN1>4 Status:Disabled 38.54: IN1> Blocking:01010000 38.55: IN1> POL: 38.56: IN1> Char Angle:-45.00 deg 38.57: IN1> Pol:Zero Sequence 38.59: IN1> VNpol Set:5.000 V : GROUP 1 3C.01: 3C.02: 3C.03: 3C.04:

THERMAL OVERLOAD: Characteristic:Single Thermal Trip:1.000 A Thermal Alarm:90.00% Time Constant 1:120.0 min

: GROUP 1 CB FAIL & I1 Start DDB #295

1

O/C_E/F START Latching

LED 1 DDB #064

IN1>1 Start DDB #315

O/C TRIP I>1 Trip DDB #243

Latching

LED 2 DDB #065

E/F TRIP IN1>1 Trip DDB #261

Latching

LED 3 DDB #066

SOTF TRIP R7 SOTF TRIP DDB #006

Latching

LED 4 DDB #067

THERMAL ALARM Thermal Alarm DDB #329

Latching

LED 5 DDB #068

THERMAL ALARM STG.2 Thermal Trip THERMAL HIGH ALARM DDB #276

1

Latching

LED 6 DDB #069

SR User Alarm 3 DDB #169

LOAD SHED TRIP RECEIVED L7 LOAD SHED TRI DDB #038

Latching

LED 7 DDB #070

PBB BLOCK SEND R1 BB BLK HI SET DDB #000

Latching

LED 8 DDB #071

Page : 1

Page 6 of 252

11KV OUTGOING FEEDER - 50/51/51N/49 Output Relay Mappings 100 R4 ANY TRIP(86) DDB #003

Dwell 0

Trip Command Out DDB #537

1 100 R3 ANY TRP SPARE DDB #002

Dwell 0

I>3 Trip DDB #251

100

1

&

IN1>3 Trip DDB #263

L1 CB CLOSE DDB #032

0

500

0 R5 SOTF 500MS DDB #004

Straight 0

IN1>2 Trip DDB #262

R7 SOTF TRIP DDB #006

Dwell

Pulse

I>2 Trip DDB #247

O/C,E/F TRIP TO TRIP RELAY (RL4)

0

100

1

R1 BB BLK HI SET DDB #000

Dwell 0

O/C,E/F TRIP TO WIRED SPARE CONTACT(RL3) SOTF TRIP ON O/C OR E/F + CB CLOSE COMMAND (RL7) CB CLOSE PLUS HOLDING FOR SOTF PROCESS (RL5) HIGH SET TRIP TO BLOCK PARTIAL BUSBAR PROTECTION (RL1)

Fault Record Trigger Mapping

Any Start DDB #294 R7 SOTF TRIP DDB #006 Thermal Alarm DDB #329 I>1 Trip DDB #243 I>2 Trip DDB #247

1

Fault REC TRIG DDB #144

IN1>1 Trip DDB #261 IN1>2 Trip DDB #262 Thermal Trip DDB #276 L7 LOAD SHED TRI DDB #038

I>1 Trip DDB #243 IN1>1 Trip DDB #261

1

Trip Command In DDB #536

Page : 2

Page 7 of 252

11KV OUTGOING FEEDER - 50/51/51N/49 USER ALARM MAPING FOR SCS GENERAL ALRAM

I>1 Trip DDB #243

IN1>1 Trip DDB #261

1

1

SR User Alarm 1 DDB #167

SR User Alarm 2 DDB #168

O/CTRIP

E/F TRIP

Page : 3

Page 8 of 252

A12 Funct 51, 51N, 49

Page 9 of 252

MiCOM S1 Studio

Page: 1

Settings File Report File: 11KV BUS SECTION O_C&E_F.set Model Number: P141216A6M0420J

Printed on: 11/05/2010 17:00:05

: SYSTEM DATA:

00.01: 00.02: 00.03: 00.04: 00.05: 00.06: 00.08: 00.09: 00.0A: 00.0B: 00.0C: 00.0D: 00.0E: 00.10: 00.11: 00.20: 00.21: 00.22: 00.30: 00.40: 00.50: 00.51: 00.52: 00.D0: 00.D1: 00.D2: 00.D3:

Language:English Password:**** Sys Fn Links:0 Description:A12/51/51N/49 Plant Reference:DID/11KV/51_51N Model Number:P141216A6M0420J Serial Number:3254474 Frequency:50 Hz Comms Level:2 Relay Address:1 Plant Status:0000000000000000 Control Status:0000000000000000 Active Group:1 CB Trip/Close:No Operation Software Ref. 1:P141____6__420_B Opto I/P Status:10000000 Relay O/P Status:0000000 Alarm Status 1:00000000000000000000000000000000 Opto I/P Status:10000000 Relay O/P Status:0000000 Alarm Status 1:00000000000000000000000000000000 Alarm Status 2:00000000000000000000000000000000 Alarm Status 3:00000000000000000000000000000000 Access Level:2 Password Control:2 Password Level 1:**** Password Level 2:****

: CB CONTROL: : DATE AND TIME: : CONFIGURATION:

09.01: 09.02: 09.03: 09.04: 09.05: 09.06: 09.07: 09.08: 09.09: 09.0A: 09.0B: 09.10: 09.11: 09.12: 09.13: 09.14: 09.15: 09.16:

Restore Defaults:No Operation Setting Group:Select via Menu Active Settings:Group 1 Save Changes:No Operation Copy From:Group 1 Copy To:No Operation Setting Group 1:Enabled Setting Group 2:Disabled Setting Group 3:Disabled Setting Group 4:Disabled System Config:Invisible Overcurrent:Enabled Neg Sequence O/C:Disabled Broken Conductor:Disabled Earth Fault 1:Disabled Earth Fault 2:Disabled SEF/REF Prot'n:Disabled Residual O/V NVD:Disabled

- Settings File Report -

Page 10 of 252

MiCOM S1 Studio

Page: 2

Settings File Report File: 11KV BUS SECTION O_C&E_F.set Model Number: P141216A6M0420J 09.17: 09.18: 09.19: 09.1A: 09.1B: 09.1D: 09.1E: 09.1F: 09.20: 09.21: 09.22: 09.25: 09.26: 09.28: 09.29: 09.2A: 09.2B: 09.2C: 09.2D: 09.2E: 09.2F: 09.35: 09.36: 09.39: 09.FF:

Printed on: 11/05/2010 17:00:05

Thermal Overload:Enabled Neg Sequence O/V:Disabled Cold Load Pickup:Disabled Selective Logic:Disabled Admit Protection:Disabled Volt Protection:Disabled Freq Protection:Disabled df/dt Protection:Disabled CB Fail:Disabled Supervision:Disabled Fault Locator:Disabled Input Labels:Visible Output Labels:Visible CT & VT Ratios:Visible Record Control:Invisible Disturb Recorder:Visible Measure't Setup:Visible Comms Settings:Visible Commission Tests:Visible Setting Values:Secondary Control Inputs:Invisible Ctrl I/P Config:Invisible Ctrl I/P Labels:Invisible Direct Access:Enabled LCD Contrast:9

: CT AND VT RATIOS:

0A.01: 0A.02: 0A.07: 0A.08: 0A.09: 0A.0A: 0A.0B: 0A.0C: : : : : :

Main VT Primary:11.00 kV Main VT Sec'y:110.0 V Phase CT Primary:2500 A Phase CT Sec'y:1.000 A E/F CT Primary:2500 A E/F CT Secondary:1.000 A SEF CT Primary:2500 A SEF CT Secondary:1.000 A

DISTURB RECORDER: MEASURE'T SETUP: COMMISSION TESTS: CB MONITOR SETUP: OPTO CONFIG:

11.01: Global Nominal V:110/125V 11.50: Opto Filter Cntl:11111111 11.80: Characteristic:Standard 60%-80% : IED CONFIGURATOR: : Group 1:

: GROUP 1 35.23: 35.24: 35.27: 35.2A:

OVERCURRENT: I>1 Function:IEC S Inverse I>1 Direction:Non-Directional I>1 Current Set:900.0 mA I>1 TMS:300.0e-3

- Settings File Report -

Page 11 of 252

MiCOM S1 Studio

Page: 3

Settings File Report File: 11KV BUS SECTION O_C&E_F.set Model Number: P141216A6M0420J 35.2D: 35.2F: 35.32: 35.40: 35.47: 35.4E: 35.4F: 35.51: 35.52: : GROUP 1 3C.01: 3C.02: 3C.03: 3C.04:

Printed on: 11/05/2010 17:00:05

I>1 DT Adder:0 s I>1 tRESET:0 s I>2 Function:Disabled I>3 Status:Disabled I>4 Status:Disabled I> Blocking:000000000 I> Char Angle:45.00 deg V CONTROLLED O/C: VCO Status:Disabled THERMAL OVERLOAD: Characteristic:Single Thermal Trip:1.000 A Thermal Alarm:90.00% Time Constant 1:8.000 min

: GROUP 1 CB FAIL & I1 Trip DDB #243

1

Test Mode DDB #441

100

1

R4 ANY TRIP - 86 DDB #003

Dwell

ANY TRIP

0

Page : 1

Page 13 of 252

MiCOM P141 Programmable Scheme Logic

SIGNAL MAPPING FOR SCS

I>1 Trip DDB #243

1

SR User Alarm 1 DDB #167

Thermal Trip DDB #276

SR User Alarm 3 DDB #169

IN1>1 Trip DDB #261

1

SR User Alarm 2 DDB #168

TRIP COMMAND MAPPING

I>1 Trip DDB #243

1

Trip Command In DDB #536

Page : 2

Page 14 of 252

MiCOM P141 Programmable Scheme Logic Output Relay Mappings 100 Trip Command Out DDB #537

R3 ANY TRP-SPARE DDB #002

Dwell 0

LED Mappings

Any Start DDB #294

Latching

LED 1 DDB #064

I>1 Trip DDB #243

Latching

LED 2 DDB #065

IN1>1 Trip DDB #261

Latching

LED 3 DDB #066

Thermal Alarm DDB #329

Latching

LED 5 DDB #068

Thermal Trip DDB #276

Latching

LED 6 DDB #069

Page : 3

Page 15 of 252

A12 Funct PBB

Page 16 of 252

MiCOM S1 Studio

Page: 1

Settings File Report File: PBB-1.set Model Number: P141216A6M0420J

Printed on: 11/05/2010 17:05:41

: SYSTEM DATA:

00.01: 00.02: 00.03: 00.04: 00.05: 00.06: 00.08: 00.09: 00.0A: 00.0B: 00.0C: 00.0D: 00.0E: 00.10: 00.11: 00.20: 00.21: 00.22: 00.30: 00.40: 00.50: 00.51: 00.52: 00.D0: 00.D1: 00.D2: 00.D3:

Language:English Password:**** Sys Fn Links:0 Description:50/50N+62-B1 Plant Reference:DID/11KV/PBB-1 Model Number:P141216A6M0420J Serial Number:3251104 Frequency:50 Hz Comms Level:2 Relay Address:1 Plant Status:0000000000000000 Control Status:0000000000000000 Active Group:1 CB Trip/Close:No Operation Software Ref. 1:P141____6__420_B Opto I/P Status:10100000 Relay O/P Status:0000000 Alarm Status 1:00000000000000000000000000000000 Opto I/P Status:10100000 Relay O/P Status:0000000 Alarm Status 1:00000000000000000000000000000000 Alarm Status 2:00000000000000000000000000000000 Alarm Status 3:00000000000000000000000000000000 Access Level:2 Password Control:2 Password Level 1:**** Password Level 2:****

: CB CONTROL: : DATE AND TIME: : CONFIGURATION:

09.01: 09.02: 09.03: 09.04: 09.05: 09.06: 09.07: 09.08: 09.09: 09.0A: 09.0B: 09.10: 09.11: 09.12: 09.13: 09.14: 09.15: 09.16:

Restore Defaults:No Operation Setting Group:Select via Menu Active Settings:Group 1 Save Changes:No Operation Copy From:Group 1 Copy To:No Operation Setting Group 1:Enabled Setting Group 2:Disabled Setting Group 3:Disabled Setting Group 4:Disabled System Config:Invisible Overcurrent:Enabled Neg Sequence O/C:Disabled Broken Conductor:Disabled Earth Fault 1:Enabled Earth Fault 2:Disabled SEF/REF Prot'n:Disabled Residual O/V NVD:Disabled

- Settings File Report -

Page 17 of 252

MiCOM S1 Studio

Page: 2

Settings File Report File: PBB-1.set Model Number: P141216A6M0420J 09.17: 09.18: 09.19: 09.1A: 09.1B: 09.1D: 09.1E: 09.1F: 09.20: 09.21: 09.22: 09.25: 09.26: 09.28: 09.29: 09.2A: 09.2B: 09.2C: 09.2D: 09.2E: 09.2F: 09.35: 09.36: 09.39: 09.FF:

Printed on: 11/05/2010 17:05:41

Thermal Overload:Disabled Neg Sequence O/V:Disabled Cold Load Pickup:Disabled Selective Logic:Disabled Admit Protection:Disabled Volt Protection:Disabled Freq Protection:Disabled df/dt Protection:Disabled CB Fail:Disabled Supervision:Disabled Fault Locator:Disabled Input Labels:Visible Output Labels:Visible CT & VT Ratios:Visible Record Control:Invisible Disturb Recorder:Visible Measure't Setup:Visible Comms Settings:Visible Commission Tests:Visible Setting Values:Secondary Control Inputs:Invisible Ctrl I/P Config:Invisible Ctrl I/P Labels:Invisible Direct Access:Enabled LCD Contrast:9

: CT AND VT RATIOS:

0A.01: 0A.02: 0A.07: 0A.08: 0A.09: 0A.0A: 0A.0B: 0A.0C: : : : : :

Main VT Primary:11.00 kV Main VT Sec'y:110.0 V Phase CT Primary:2500 A Phase CT Sec'y:1.000 A E/F CT Primary:2500 A E/F CT Secondary:1.000 A SEF CT Primary:2500 A SEF CT Secondary:1.000 A

DISTURB RECORDER: MEASURE'T SETUP: COMMISSION TESTS: CB MONITOR SETUP: OPTO CONFIG:

11.01: Global Nominal V:110/125V 11.50: Opto Filter Cntl:11111111 11.80: Characteristic:Standard 60%-80% : IED CONFIGURATOR: : Group 1:

: GROUP 1 35.23: 35.24: 35.27: 35.2A:

OVERCURRENT: I>1 Function:IEC S Inverse I>1 Direction:Non-Directional I>1 Current Set:1.410 A I>1 TMS:320.0e-3

- Settings File Report -

Page 18 of 252

MiCOM S1 Studio

Page: 3

Settings File Report File: PBB-1.set Model Number: P141216A6M0420J 35.2D: 35.2F: 35.32: 35.33: 35.36: 35.38: 35.3E: 35.40: 35.47: 35.4E: 35.4F: 35.51: 35.52:

Printed on: 11/05/2010 17:05:41

I>1 DT Adder:0 s I>1 tRESET:0 s I>2 Function:DT I>2 Direction:Non-Directional I>2 Current Set:2.500 A I>2 Time Delay:200.0 ms I>2 tRESET:0 s I>3 Status:Disabled I>4 Status:Disabled I> Blocking:000000000 I> Char Angle:45.00 deg V CONTROLLED O/C: VCO Status:Disabled

: GROUP 1 EARTH FAULT 1: 38.01: IN1> Input:Measured 38.25: IN1>1 Function:IEC S Inverse 38.26: IN1>1 Direction:Non-Directional 38.29: IN1>1 Current:80.00 mA 38.2D: IN1>1 TMS:500.0e-3 38.31: IN1>1 DT Adder:0 s 38.33: IN1>1 tRESET:0 s 38.36: IN1>2 Function:DT 38.37: IN1>2 Direction:Non-Directional 38.3A: IN1>2 Current:200.0 mA 38.3D: IN1>2 Time Delay:500.0 ms 38.44: IN1>2 tRESET:0 s 38.46: IN1>3 Status:Disabled 38.4D: IN1>4 Status:Disabled 38.54: IN1> Blocking:00000000 38.55: IN1> POL: 38.56: IN1> Char Angle:-45.00 deg 38.57: IN1> Pol:Zero Sequence 38.59: IN1> VNpol Set:5.000 V : GROUP 1 CB FAIL & I2 Timer Block DDB #204

1

HIGH SET BLOCK FROM O/G FEEDERS

IN1>2 Timer Blk DDB #209

1

L7 PBB-PROT-OUT DDB #038

HIGH SET PROTECTION BLOCK FROM PBB IN/OUT SWITCH

&

LED Mappings PBB HISET BLOCK RECEIVED FROM FEEDERS

L1 PBB1-BLK -FDR DDB #032

Latching

LED 1 DDB #064

L6 PBB-PROT-IN DDB #037

Non Latching

LED 2 DDB #065

PBB IN SERVICE

L7 PBB-PROT-OUT DDB #038

Non Latching

LED 3 DDB #066

PBB OUT OF SERVICE

I>1 Trip DDB #243

Latching

LED 4 DDB #067

PBB O/C BACK UP TRIP (IDMT)

I>2 Trip DDB #247

Latching

LED 5 DDB #068

PBB O/C HISET TRIP (DT)

IN1>1 Trip DDB #261

Latching

LED 6 DDB #069

PBB E/F BACK UP TRIP (IDMT)

IN1>2 Trip DDB #262

Latching

LED 7 DDB #070

PBB E/F HISET TRIP (DT)

Any Start DDB #294

Latching

LED 8 DDB #071

PBB START

Page : 1 Page 20 of 252

11KV PARTIAL BB PROTECTION Output Relay Mappings

I>2 Trip DDB #247 IN1>2 Trip DDB #262

I>1 Trip DDB #243

100

1

R1 HISET-TRP-86B DDB #000

Dwell 0

100

1

R2 IDMT TRIP BS DDB #001

Dwell

IN1>1 Trip DDB #261

0 100 R6 IDMT TR HV-86 DDB #005

Dwell 0

100 R3 TRIP-HV INTR1 DDB #002

Dwell 0

I>1 Trip DDB #243 I>2 Trip DDB #247 IN1>1 Trip DDB #261

100

1

R4 ANYTRIP-SPARE DDB #003

Dwell 0

IN1>2 Trip DDB #262

100 R5 TRIP-HV INTR2 DDB #004

Dwell 0

O/C & E/F HISET TRIP 86B (11KV FEEDERS) O/C & E/F IDMT TRIP - 86 (11KV BUS SECTION) O/C & E/F IDMT TRIP - 86 HV TRIP

O/C & E/F TRIPHV INTER TRIP -1 O/C & E/F TRIPWIRED SPARE OUT PUT O/C & E/F TRIPHV INTER TRIP -2

100 R7 TRIP-415 CB DDB #006

Dwell 0

O/C & E/F TRIP 415V TRIP

Fault Record Trigger Mapping I>1 Trip DDB #243 I>2 Trip DDB #247 IN1>1 Trip DDB #261

20

1

Fault REC TRIG DDB #144

Dwell 0

IN1>2 Trip DDB #262

Trip Output Mapping

Any Start DDB #294

I>1 Trip DDB #243 I>2 Trip DDB #247 IN1>1 Trip DDB #261

1

Trip Command In DDB #536

IN1>2 Trip DDB #262

Page : 2

Page 21 of 252

81UF

Page 22 of 252

MiCOM S1 Studio

Page: 1

Settings File Report File: 000.set Model Number: P923xAxxxxx V10

Printed on: 11/05/2010 17:54:16

: OP PARAMETERS:

010A: Reference:81UF 0005: Software Version:10.I 0104: Frequency:50 Hz : CONFIGURATION:

: GENERAL: 0126: Connection:3 Vpn + Vr 0127: Protection:Protect P-N 0109: Default Display:RMS Va : VT RATIO: 0120: Main VT Primary:11000V 0122: Main VT Secundary:110V 0123: E/Gnd VT Primary:11000V 0125: E/Gnd VT Secundary:110V : : : : : : : : : :

LED 5: LED 6: LED 7: LED 8: GROUP SELECT: FREQ,df/dt,DU/DT: ALARMS: LOGIC INPUTS: DATE FORMAT: RL1 & 2 OUTPUT RLY:

: PROTECTION G1:

: : : : : :

[27] UNDERVOLTAGE: [59] OVERVOLTAGE: [59N] RESIDUAL O/V: [47] NEG SEQ O/V: [27D] POS SEQ U/V: [81] FREQUENCY: 02D0: Function f1:81< 02D1: f1:49.2Hz 02D2: tf1:0.1s 02D3: Function f2:81< 02D4: f2:49Hz 02D5: tf2:0.1s 02D6: Function f3:81< 02D7: f3:48.8Hz 02D8: tf3:0.1s 02D9: Function f4:81< 02DA: f4:48.6Hz 02DB: tf4:0.1s 02DC: Function f5:81< 02DD: f5:48.4Hz 02DE: tf5:0.1s 02DF: Function f6:No

: [81R] FREQ CHANGE OF RATE: : DELTA U / DELTA T:

- Settings File Report -

Page 23 of 252

MiCOM S1 Studio

Page: 2

Settings File Report File: 000.set Model Number: P923xAxxxxx V10

Printed on: 11/05/2010 17:54:16

: PROTECTION G2: : AUTOMAT. CTRL: : RECORDS:

- Settings File Report -

Page 24 of 252

A12,B12, B10, B20, 66kV Spare UGC Funct - 25, 27C

Page 25 of 252

MiCOM S1 Studio

Page: 1

Settings File Report File: 25_27C.x3v Model Number: 613

Printed on: 12/05/2010 12:51:50

: Parameters:

: Device ID: : Config. parameters: : Function parameters: : Global: : General functions: : MAIN: : ASC: 018.000: General enable USER:Yes 101.212: Transm.cycle,meas.v.:10 s : V: 023.030: General enable USER:No : Parameter subset 1: : MAIN: : ASC: 018.020: Enable PS1:Yes 037.131: CB assignment PS1:Not assigned 037.135: System integrat. PS1:Autom.synchron.check 018.001: Active for HSR PS1:No 018.002: Active for TDR PS1:No 018.003: Clos.rej.w.block PS1:No 018.010: Operative time PS1:6000.0 s 018.025: Operating mode PS1:Volt./sync.-checked 000.038: AR with tCB PS1:No 018.029: Op.mode volt.chk.PS1:Not V or not Vref 026.017: V> volt.check PS1:0.80 Vnom(/©3) 018.017: V< volt. check PS1:0.20 Vnom(/©3) 018.018: tmin volt. check PS1:0.10 s 031.060: Measurement loop PS1:Loop B-G 018.011: V> sync. check PS1:0.80 Vnom(/©3) 018.012: Delta Vmax PS1:0.06 Vnom 018.014: Delta f max PS1:0.10 Hz 018.013: Delta phi max PS1:10 ° 018.034: Phi offset PS1:0 ° 018.015: tmin sync. check PS1:0.10 s : V: 076.246: 076.001: 001.155: 001.162: 076.002: 076.003: 076.004: 076.005: 076.027: 076.006: 076.007: 076.008: 076.009:

Enable Operating mode I enable V< Op. mode V< mon. Evaluation VNG V> V>> tV> tV> 3-pole tV>> V< V> tVpos> tVpos>> Vpos< Vpos> tVneg> tVneg>> VNG> VNG>> tVNG> tVNG>> Vref> tTransient Vref>> Hyst. V meas. tVref> Hyst. V deduc. tVref>> Vref< Vref sync. check PS1:0.80 Vnom(/©3) 018.012: Delta Vmax PS1:0.06 Vnom 018.014: Delta f max PS1:0.10 Hz 018.013: Delta phi max PS1:10 ° 018.034: Phi offset PS1:0 ° 018.015: tmin sync. check PS1:0.10 s : V: 076.246: 076.001: 001.155: 001.162: 076.002: 076.003: 076.004: 076.005: 076.027: 076.006: 076.007: 076.008:

Enable Operating mode I enable V< Op. mode V< mon. Evaluation VNG V> V>> tV> tV> 3-pole tV>> V< V> tVpos> tVpos>> Vpos< Vpos> tVneg> tVneg>> VNG> VNG>> tVNG> tVNG>> Vref> tTransient Vref>> Hyst. V meas. tVref> Hyst. V deduc. tVref>> Vref< Vref1 Trip

- Settings File Report -

Page 33 of 252

MiCOM S1 Studio

Page: 3

Settings File Report File: A18 67_67N.set Model Number: P141216A6M0420J 0C.0F: 0C.10: 0C.11: 0C.12: 0C.13: 0C.14: 0C.15: 0C.16: 0C.18: 0C.1A: 0C.1C: 0C.1E: 0C.20: 0C.22: 0C.24: 0C.26: 0C.28: 0C.2A: 0C.2C: 0C.2E: 0C.30: 0C.32: 0C.34: 0C.36: 0C.38: 0C.3A: 0C.3C: 0C.3E: 0C.40: 0C.42: 0C.44: 0C.46: 0C.48: 0C.4A: : : : : : :

Input 2 Digital Input 3 Digital Input 4 Digital Input 5 Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital

Printed on: 11/05/2010 18:32:42

Trigger:Trigger L/H Input 3:VT Fail Alarm Trigger:Trigger L/H Input 4:Input L2 Trigger:Trigger L/H Input 5:Prot'n Disabled Trigger:Trigger L/H Input 6:Unused Input 7:Unused Input 8:Unused Input 9:Unused Input 10:Unused Input 11:Unused Input 12:Unused Input 13:Unused Input 14:Unused Input 15:Unused Input 16:Unused Input 17:Unused Input 18:Unused Input 19:Unused Input 20:Unused Input 21:Unused Input 22:Unused Input 23:Unused Input 24:Unused Input 25:Unused Input 26:Unused Input 27:Unused Input 28:Unused Input 29:Unused Input 30:Unused Input 31:Unused Input 32:Unused

MEASURE'T SETUP: COMMISSION TESTS: CB MONITOR SETUP: OPTO CONFIG: IED CONFIGURATOR: Group 1:

: GROUP 1 35.23: 35.24: 35.27: 35.2A: 35.2D: 35.2F: 35.32: 35.40:

OVERCURRENT: I>1 Function:IEC S Inverse I>1 Direction:Directional Fwd I>1 Current Set:420.0 mA I>1 TMS:100.0e-3 I>1 DT Adder:0 s I>1 tRESET:0 s I>2 Function:Disabled I>3 Status:Disabled

- Settings File Report -

Page 34 of 252

MiCOM S1 Studio

Page: 4

Settings File Report File: A18 67_67N.set Model Number: P141216A6M0420J 35.47: 35.4E: 35.4F: 35.51: 35.52:

Printed on: 11/05/2010 18:32:42

I>4 Status:Disabled I> Blocking:000000001 I> Char Angle:45.00 deg V CONTROLLED O/C: VCO Status:Disabled

: GROUP 1 CB FAIL & I Inhibit:10.00 A VTS I2> Inhibit:50.00 mA CT SUPERVISION: CTS Status:Disabled

: GROUP 1 INPUT LABELS: : GROUP 1 OUTPUT LABELS:

- Settings File Report -

Page 35 of 252

A18 67_67N DIRECTIONAL OVER CURRENT RELAY Opto Input Mappings

1

L7 NOT USED L7 MCB TRIP DDB #038

L8 TEST MODE DDB #039

MCB/VTS DDB #231

1

Test Mode DDB #441

LED Mappings I>1 Start DDB #295

Latching

LED 1 DDB #064

I>1 Trip DDB #243

Latching

LED 2 DDB #065

VT Fail Alarm DDB #148

Non Latching

LED 3 DDB #066

L2VT MCB OFF/TRP DDB #033

Non Latching

LED 4 DDB #067

Fault Record Trigger Mapping

Any Start DDB #294 I>1 Trip DDB #243

50

1

Fault REC TRIG DDB #144

Dwell 0

Page : 1

Page 36 of 252

A18 67_67N DIRECTIONAL OVER CURRENT RELAY Output Relay Mappings

100 R1 NOT USED DDB #000

R1 86 TRIP

Dwell 0 100

R2 TO FIRE PROT DDB #001

R2 LV TRIP

Dwell 0 100

HV REM INTS-2 R3R3INTER TRIP-1 DDB #002

Dwell 0

1

I>1 Trip DDB #243

100 R5 SPARE-1 R5 FIRE PROTN DDB #004

Dwell 0 100

R6 SPARE-2 R6 SPARE-1 DDB #005

Dwell 0 100

R7 TO TRIP 415V DDB #006

R7 SPARE-2

Dwell 0

I>1 Trip DDB #243

Trip Command In DDB #536

Page : 2

Page 37 of 252

B11, B21 87T_50TC_P633

Page 38 of 252

MiCOM S1 Studio

Page: 1

Settings File Report File: B11_87T_50TC_P633_FINAL SET.x3v Model Number: 621

Printed on: 02/08/2010 12:50:23

: Parameters:

: DeviceID: : Config.parameters: : LOC: : PC: : COMM2: : IEC: : GOOSE: : GSSE: : F_KEY: : INP: 010.220: Filter:0 153.087: Fct. assignm. U 2001:LOGIC Input 1 EXT 153.090: Fct. assignm. U 2002:Without function 153.093: Fct. assignm. U 2003:Without function 153.096: Fct. assignm. U 2004:MAIN Test mode EXT 153.088: Oper. mode U 2001:Active "high" 153.091: Oper. mode U 2002:Active "high" 153.094: Oper. mode U 2003:Active "high" 153.097: Oper. mode U 2004:Active "low" : OUTP: 151.201: 151.204: 151.207: 151.210: 151.213: 151.216: 151.219: 151.222: 151.202: 151.205: 151.208: 151.211: 151.214: 151.217: 151.220: 151.223:

Fct. assignm. K 2001:DIFF Trip signal Fct. assignm. K 2002:LOGIC Output 3 (t) Fct. assignm. K 2003:DIFF Trip signal Fct. assignm. K 2004:LOGIC Output 3 (t) Fct. assignm. K 2005:LOGIC Output 3 (t) Fct. assignm. K 2006:Without function Fct. assignm. K 2007:Without function Fct. assignm. K 2008:MAIN Blocked/faulty Oper. mode K 2001:ES updating Oper. mode K 2002:ES reset (fault) Oper. mode K 2003:ES updating Oper. mode K 2004:NE updating Oper. mode K 2005:ES updating Oper. mode K 2006:ES updating Oper. mode K 2007:ES updating Oper. mode K 2008:NE updating

: MEASO: : LED: 085.184: 085.001: 085.004: 085.007: 085.057: 085.010: 085.060: 085.013: 085.063: 085.016:

Fct.assig. Fct.assig. Fct.assig. Fct.assig. Fct.assig. Fct.assig. Fct.assig. Fct.assig. Fct.assig. Fct.assig.

H H H H H H H H H H

1 2 3 4 4 5 5 6 6 7

green:MAIN Healthy yell.:MAIN Blocked/faulty yell.:SFMON Warning (LED) red:MAIN Gen. trip signal green:Without function red:DIFF Trip signal 1 green:Without function red:DIFF Trip signal 2 green:Without function red:DIFF Trip signal 3

- Settings File Report -

Page 39 of 252

MiCOM S1 Studio

Page: 2

Settings File Report File: B11_87T_50TC_P633_FINAL SET.x3v Model Number: 621 085.066: 085.019: 085.069: 085.022: 085.072: 085.025: 085.075: 085.028: 085.078: 085.031: 085.081: 085.034: 085.084: 085.037: 085.087: 085.040: 085.090: 085.043: 085.093: 085.185: 085.131: 085.161: 085.134: 085.164: 085.137: 085.167: 085.140: 085.170: 085.143: 085.173: 085.146: 085.177: 085.182: 085.002: 085.005: 085.008: 085.011: 085.014: 085.017: 085.020: 085.023: 085.026: 085.029: 085.032: 085.035: 085.038: 085.041: 085.044: 085.183:

Fct.assig. H 7 Fct.assig. H 8 Fct.assig. H 8 Fct.assig. H 9 Fct.assig. H 9 Fct.assig. H10 Fct.assig. H10 Fct.assig. H11 Fct.assig. H11 Fct.assig. H12 Fct.assig. H12 Fct.assig. H13 Fct.assig. H13 Fct.assig. H14 Fct.assig. H14 Fct.assig. H15 Fct.assig. H15 Fct.assig. H16 Fct.assig. H16 Fct.assig. H17 Fct.assig. H18 Fct.assig. H18 Fct.assig. H19 Fct.assig. H19 Fct.assig. H20 Fct.assig. H20 Fct.assig. H21 Fct.assig. H21 Fct.assig. H22 Fct.assig. H22 Fct.assig. H23 Fct.assig. H23 Operating mode Operating mode Operating mode Operating mode Operating mode Operating mode Operating mode Operating mode Operating mode Operating mode Operating mode Operating mode Operating mode Operating mode Operating mode Operating mode Operating mode

Printed on: 02/08/2010 12:50:23

green:Without function red:LOGIC Output 5 green:Without function red:LOGIC Output 6 green:Without function red:DIFF Id>> triggered green:Without function red:DIFF Id>>> triggered green:Without function rot:LOGIC Input 1 EXT green:Without function red:LOGIC Output 3 (t) green:Without function red:Without function green:Without function red:Without function green:Without function red:MAIN Test mode green:Without function red:LOC Edit mode red:Without function green:Without function red:Without function green:Without function red:Without function green:Without function red:Without function green:Without function red:Without function green:Without function red:Without function green:Without function H 1:ES updating H 2:ES updating H 3:ES updating H 4:ES reset (fault) H 5:ES reset (fault) H 6:ES reset (fault) H 7:ES reset (fault) H 8:ES reset (fault) H 9:ES reset (fault) H 10:ES reset (fault) H 11:ES reset (fault) H 12:ES reset (fault) H 13:ES reset (fault) H 14:ES reset (fault) H 15:ES reset (fault) H 16:ES updating H 17:ES updating

- Settings File Report -

Page 40 of 252

MiCOM S1 Studio

Page: 3

Settings File Report File: B11_87T_50TC_P633_FINAL SET.x3v Model Number: 621 085.132: 085.135: 085.138: 085.141: 085.144: 085.147:

Operating Operating Operating Operating Operating Operating

mode mode mode mode mode mode

H H H H H H

18:ES 19:ES 20:ES 21:ES 22:ES 23:ES

Printed on: 02/08/2010 12:50:23

updating updating updating updating updating updating

: MAIN: : FT_RC: : DIFF: 056.027: Function group DIFF:With : : : : :

REF_1: REF_2: REF_3: DTOC1: DTOC2: 056.032: Function group DTOC2:With

: : : : : : : : : : : : : : : : : : :

DTOC3: IDMT1: IDMT2: IDMT3: THRM1: THRM2: V: f: V/f: MCM_1: MCM_2: MCM_3: CBF_1: CBF_2: CBF_3: LIM_1: LIM_2: LIM_3: LOGIC: 056.017: Function group LOGIC:With

: Function parameters: : Global: : PC: : OUTP: : MAIN: 003.030: Device on-line:Yes (= on) 003.012: Test mode USER:No 010.030: Nominal frequ. fnom:50 Hz 010.049: Phase sequence:A - B - C 019.020: Inom C.T.prim.,end a:400 A 019.021: Inom C.T.prim.,end b:2500 A 019.022: Inom C.T.prim.,end c:1200 A 019.027: Inom C.T.Yprim,end a:1 A

- Settings File Report -

Page 41 of 252

MiCOM S1 Studio

Page: 4

Settings File Report File: B11_87T_50TC_P633_FINAL SET.x3v Model Number: 621 019.028: 019.029: 010.002: 010.024: 010.025: 010.029: 010.142: 010.143: 010.144: 010.009: 010.140: 010.150: 010.160: 010.141: 010.151: 010.161: 011.030: 011.048: 011.058: 011.031: 011.036: 011.032: 010.113: 005.248: 005.249: 021.021: 021.022: 021.048: 021.049: 021.012: 021.001: 021.002: 021.046: 021.047: 021.003: 021.004: 021.032: 021.033: 021.023: 021.024: 021.025: 021.026: 021.031: 021.017: 021.020: 021.060: 021.061: 021.062: 021.063:

Printed on: 02/08/2010 12:50:23

Inom C.T.Yprim,end b:1 A Inom C.T.Yprim,end c:1 A Vnom V.T. prim.:66.0 kV Inom device, end a:1.0 A Inom device, end b:1.0 A Inom device, end c:1.0 A IY,nom device, end a:1.0 A IY,nom device, end b:1.0 A IY,nom device, end c:1.0 A Vnom V.T. sec.:110 V Conn.meas.circ. IP,a:Standard Conn.meas.circ. IP,b:Standard Conn.meas.circ. IP,c:Standard Conn.meas.circ. IY,a:Standard Conn.meas.circ. IY,b:Standard Conn.meas.circ. IY,c:Standard Meas. value rel. IP:0.00 Inom Meas.value rel. Ineg:0.000 Inom Meas.value rel. Ipos:0.000 Inom Meas. value rel. IN:0.000 Inom Meas. value rel. IY:0.000 IN,nom Meas. value rel. V:0.00 Vnom Settl. t. IP,max,del:15.0 min Fct.assign. reset 1:MAIN General reset EXT Fct.assign. reset 2:Without function Fct.assign. block. 1:Without function Fct.assign. block. 2:Without function Fct.assign. block. 3:Without function Fct.assign. block. 4:Without function Trip cmd.block. USER:No Fct.assig.trip cmd.1:DIFF Trip signal Fct.assig.trip cmd.2:Without function Fct.assig.trip cmd.3:Without function Fct.assig.trip cmd.4:Without function Min.dur. trip cmd. 1:0.25 s Min.dur. trip cmd. 2:0.25 s Min.dur. trip cmd. 3:0.25 s Min.dur. trip cmd. 4:0.25 s Latching trip cmd. 1:No Latching trip cmd. 2:No Latching trip cmd. 3:No Latching trip cmd. 4:No Fct. assign. fault:Without function Sig. asg. CB1 open:Without function Sig. asg. CB1 closed:Without function Sig. asg. CB2 closed:Without function Sig. asg. CB2 open:Without function Sig. asg. CB3 closed:Without function Sig. asg. CB3 open:Without function

-->

- Settings File Report -

Page 42 of 252

MiCOM S1 Studio

Page: 5

Settings File Report File: B11_87T_50TC_P633_FINAL SET.x3v Model Number: 621

Printed on: 02/08/2010 12:50:23

: PSS: : SFMON: : FT_RC: : General functions: : MAIN: 016.096: Evaluation IN, end a:Calculated 016.097: Evaluation IN, end b:Calculated 016.098: Evaluation IN, end c:Calculated 019.099: Current summation:Without 018.009: Hold time dyn.param.:Blocked : DIFF: 019.080: 019.016: 019.023: 019.024: 019.025: 004.105: 004.106: 004.127: 011.037: 011.038:

General enable USER:Yes Reference power Sref:40.0 MVA Ref. curr. Iref,a:0.350 kA Ref. curr. Iref,b:2.099 kA Ref. curr. Iref,c:2.099 kA Matching fact. kam,a:1.143 Matching fact. kam,b:1.191 Matching fact. kam,c:0.572 Meas. value rel. Id:0.000 Iref Meas. value rel. IR:0.000 Iref

: DTOC2: 031.136: General enable USER:Yes 019.104: Select. meas. input:End b : LOGIC: 031.099: 034.030: 034.031: 034.032: 034.033: 034.034: 034.035: 034.036: 034.037: 030.000: 030.001: 030.002: 030.003: 044.000: 044.001: 030.004: 030.005: 030.006: 030.007: 044.002: 044.003: 030.008: 030.009: 030.010:

General enable USER:Yes Set 1 USER:No Set 2 USER:No Set 3 USER:No Set 4 USER:No Set 5 USER:No Set 6 USER:No Set 7 USER:No Set 8 USER:No Fct.assignm. outp. 1:DTOC2 Trip signal tI> Op. mode t output 1:Without timer stage Time t1 output 1:0.00 s Time t2 output 1:0.00 s Sig.assig. outp. 1:Without function Sig.assig.outp. 1(t):Without function Fct.assignm. outp. 2:DIFF Trip signal Op. mode t output 2:Without timer stage Time t1 output 2:0.00 s Time t2 output 2:0.00 s Sig.assig. outp. 2:Without function Sig.assig.outp. 2(t):Without function Fct.assignm. outp. 3:DTOC2 Trip signal tI> Op. mode t output 3:Oper./releas.delay Time t1 output 3:0.00 s

-->

-->

-->

- Settings File Report -

Page 43 of 252

MiCOM S1 Studio

Page: 6

Settings File Report File: B11_87T_50TC_P633_FINAL SET.x3v Model Number: 621 030.011: 044.004: 044.005: 030.012: 030.013: 030.014: 030.015: 044.006: 044.007: 030.016: 030.017: 030.018: 030.019: 044.008: 044.009: 030.020: 030.021: 030.022: 030.023: 044.010: 044.011: 030.024: 030.025: 030.026: 030.027: 044.012: 044.013: 030.028: 030.029: 030.030: 030.031: 044.014: 044.015: 030.032: 030.033: 030.034: 030.035: 044.016: 044.017: 030.036: 030.037: 030.038: 030.039: 044.018: 044.019: 030.040: 030.041: 030.042: 030.043:

Printed on: 02/08/2010 12:50:23

Time t2 output 3:0.00 s Sig.assig. outp. 3:Without function Sig.assig.outp. 3(t):Without function Fct.assignm. outp. 4:Without function Op. mode t output 4:Without timer stage Time t1 output 4:0.00 s Time t2 output 4:0.00 s Sig.assig. outp. 4:Without function Sig.assig.outp. 4(t):Without function Fct.assignm. outp. 5:DIFF Harm.block 1 trigg. --> Op. mode t output 5:Without timer stage Time t1 output 5:0.00 s Time t2 output 5:0.00 s Sig.assig. outp. 5:Without function Sig.assig.outp. 5(t):Without function Fct.assignm. outp. 6:DIFF Overflux.bl.1 trigg. --> Op. mode t output 6:Without timer stage Time t1 output 6:0.00 s Time t2 output 6:0.00 s Sig.assig. outp. 6:Without function Sig.assig.outp. 6(t):Without function Fct.assignm. outp. 7:Without function Op. mode t output 7:Without timer stage Time t1 output 7:0.00 s Time t2 output 7:0.00 s Sig.assig. outp. 7:Without function Sig.assig.outp. 7(t):Without function Fct.assignm. outp. 8:Without function Op. mode t output 8:Without timer stage Time t1 output 8:0.00 s Time t2 output 8:0.00 s Sig.assig. outp. 8:Without function Sig.assig.outp. 8(t):Without function Fct.assignm. outp. 9:Without function Op. mode t output 9:Without timer stage Time t1 output 9:0.00 s Time t2 output 9:0.00 s Sig.assig. outp. 9:Without function Sig.assig.outp. 9(t):Without function Fct.assignm. outp.10:Without function Op. mode t output 10:Without timer stage Time t1 output 10:0.00 s Time t2 output 10:0.00 s Sig.assig. outp. 10:Without function Sig.assig.outp.10(t):Without function Fct.assignm. outp.11:Without function Op. mode t output 11:Without timer stage Time t1 output 11:0.00 s Time t2 output 11:0.00 s

- Settings File Report -

Page 44 of 252

MiCOM S1 Studio

Page: 7

Settings File Report File: B11_87T_50TC_P633_FINAL SET.x3v Model Number: 621 044.020: 044.021: 030.044: 030.045: 030.046: 030.047: 044.022: 044.023: 030.048: 030.049: 030.050: 030.051: 044.024: 044.025: 030.052: 030.053: 030.054: 030.055: 044.026: 044.027: 030.056: 030.057: 030.058: 030.059: 044.028: 044.029: 030.060: 030.061: 030.062: 030.063: 044.030: 044.031: 030.064: 030.065: 030.066: 030.067: 044.032: 044.033: 030.068: 030.069: 030.070: 030.071: 044.034: 044.035: 030.072: 030.073: 030.074: 030.075: 044.036:

Printed on: 02/08/2010 12:50:23

Sig.assig. outp. 11:Without function Sig.assig.outp.11(t):Without function Fct.assignm. outp.12:Without function Op. mode t output 12:Without timer stage Time t1 output 12:0.00 s Time t2 output 12:0.00 s Sig.assig. outp. 12:Without function Sig.assig.outp.12(t):Without function Fct.assignm. outp.13:Without function Op. mode t output 13:Without timer stage Time t1 output 13:0.00 s Time t2 output 13:0.00 s Sig.assig. outp. 13:Without function Sig.assig.outp.13(t):Without function Fct.assignm. outp.14:Without function Op. mode t output 14:Without timer stage Time t1 output 14:0.00 s Time t2 output 14:0.00 s Sig.assig. outp. 14:Without function Sig.assig.outp.14(t):Without function Fct.assignm. outp.15:Without function Op. mode t output 15:Without timer stage Time t1 output 15:0.00 s Time t2 output 15:0.00 s Sig.assig. outp. 15:Without function Sig.assig.outp.15(t):Without function Fct.assignm. outp.16:Without function Op. mode t output 16:Without timer stage Time t1 output 16:0.00 s Time t2 output 16:0.00 s Sig.assig. outp. 16:Without function Sig.assig.outp.16(t):Without function Fct.assignm. outp.17:Without function Op. mode t output 17:Without timer stage Time t1 output 17:0.00 s Time t2 output 17:0.00 s Sig.assig. outp. 17:Without function Sig.assig.outp.17(t):Without function Fct.assignm. outp.18:Without function Op. mode t output 18:Without timer stage Time t1 output 18:0.00 s Time t2 output 18:0.00 s Sig.assig. outp. 18:Without function Sig.assig.outp.18(t):Without function Fct.assignm. outp.19:Without function Op. mode t output 19:Without timer stage Time t1 output 19:0.00 s Time t2 output 19:0.00 s Sig.assig. outp. 19:Without function

- Settings File Report -

Page 45 of 252

MiCOM S1 Studio

Page: 8

Settings File Report File: B11_87T_50TC_P633_FINAL SET.x3v Model Number: 621 044.037: 030.076: 030.077: 030.078: 030.079: 044.038: 044.039: 030.080: 030.081: 030.082: 030.083: 044.040: 044.041: 030.084: 030.085: 030.086: 030.087: 044.042: 044.043: 030.088: 030.089: 030.090: 030.091: 044.044: 044.045: 030.092: 030.093: 030.094: 030.095: 044.046: 044.047: 030.096: 030.097: 030.098: 030.099: 044.048: 044.049: 031.000: 031.001: 031.002: 031.003: 044.050: 044.051: 031.004: 031.005: 031.006: 031.007: 044.052: 044.053:

Printed on: 02/08/2010 12:50:23

Sig.assig.outp.19(t):Without function Fct.assignm. outp.20:Without function Op. mode t output 20:Without timer stage Time t1 output 20:0.00 s Time t2 output 20:0.00 s Sig.assig. outp. 20:Without function Sig.assig.outp.20(t):Without function Fct.assignm. outp.21:Without function Op. mode t output 21:Without timer stage Time t1 output 21:0.00 s Time t2 output 21:0.00 s Sig.assig. outp. 21:Without function Sig.assig.outp.21(t):Without function Fct.assignm. outp.22:Without function Op. mode t output 22:Without timer stage Time t1 output 22:0.00 s Time t2 output 22:0.00 s Sig.assig. outp. 22:Without function Sig.assig.outp.22(t):Without function Fct.assignm. outp.23:Without function Op. mode t output 23:Without timer stage Time t1 output 23:0.00 s Time t2 output 23:0.00 s Sig.assig. outp. 23:Without function Sig.assig.outp.23(t):Without function Fct.assignm. outp.24:Without function Op. mode t output 24:Without timer stage Time t1 output 24:0.00 s Time t2 output 24:0.00 s Sig.assig. outp. 24:Without function Sig.assig.outp.24(t):Without function Fct.assignm. outp.25:Without function Op. mode t output 25:Without timer stage Time t1 output 25:0.00 s Time t2 output 25:0.00 s Sig.assig. outp. 25:Without function Sig.assig.outp.25(t):Without function Fct.assignm. outp.26:Without function Op. mode t output 26:Without timer stage Time t1 output 26:0.00 s Time t2 output 26:0.00 s Sig.assig. outp. 26:Without function Sig.assig.outp.26(t):Without function Fct.assignm. outp.27:Without function Op. mode t output 27:Without timer stage Time t1 output 27:0.00 s Time t2 output 27:0.00 s Sig.assig. outp. 27:Without function Sig.assig.outp.27(t):Without function

- Settings File Report -

Page 46 of 252

MiCOM S1 Studio

Page: 9

Settings File Report File: B11_87T_50TC_P633_FINAL SET.x3v Model Number: 621 031.008: 031.009: 031.010: 031.011: 044.054: 044.055: 031.012: 031.013: 031.014: 031.015: 044.056: 044.057: 031.016: 031.017: 031.018: 031.019: 044.058: 044.059: 031.020: 031.021: 031.022: 031.023: 044.060: 044.061: 031.024: 031.025: 031.026: 031.027: 044.062: 044.063:

Printed on: 02/08/2010 12:50:23

Fct.assignm. outp.28:Without function Op. mode t output 28:Without timer stage Time t1 output 28:0.00 s Time t2 output 28:0.00 s Sig.assig. outp. 28:Without function Sig.assig.outp.28(t):Without function Fct.assignm. outp.29:Without function Op. mode t output 29:Without timer stage Time t1 output 29:0.00 s Time t2 output 29:0.00 s Sig.assig. outp. 29:Without function Sig.assig.outp.29(t):Without function Fct.assignm. outp.30:Without function Op. mode t output 30:Without timer stage Time t1 output 30:0.00 s Time t2 output 30:0.00 s Sig.assig. outp. 30:Without function Sig.assig.outp.30(t):Without function Fct.assignm. outp.31:Without function Op. mode t output 31:Without timer stage Time t1 output 31:0.00 s Time t2 output 31:0.00 s Sig.assig. outp. 31:Without function Sig.assig.outp.31(t):Without function Fct.assignm. outp.32:Without function Op. mode t output 32:Without timer stage Time t1 output 32:0.00 s Time t2 output 32:0.00 s Sig.assig. outp. 32:Without function Sig.assig.outp.32(t):Without function

: Parameter subset 1: : MAIN: : DIFF: 072.152: Enable PS1:Yes 019.010: Vec.gr. ends a-b PS1:1 019.011: Vec.gr. ends a-c PS1:1 072.142: Idiff> PS1:0.30 Iref 072.143: Idiff>> PS1:5.0 Iref 072.144: Idiff>>> PS1:9.1 Iref 080.000: Idiff>(CTS) PS1:0.30 Iref 072.145: m1 PS1:0.30 072.146: m2 PS1:0.70 072.147: IR,m2 PS1:4.0 Iref 072.148: Op.mode rush rst.PS1:Not phase-selective 072.159: RushI(2f0)/I(f0) PS1:10 % 072.155: 0-seq. filt.a en.PS1:Yes 072.156: 0-seq. filt.b en.PS1:Yes 072.157: 0-seq. filt.c en.PS1:Yes 072.158: Overflux.bl. en. PS1:Yes

- Settings File Report -

Page 47 of 252

MiCOM S1 Studio

Page: 10

Settings File Report File: B11_87T_50TC_P633_FINAL SET.x3v Model Number: 621

Printed on: 02/08/2010 12:50:23

072.160: Ov. I(5f0)/I(f0) PS1:25 % 010.162: Op.del.,trip sig.PS1:0.00 s 072.006: Hyst. effective PS1:Yes : DTOC2: 076.070: 076.087: 076.086: 076.085: 076.083: 076.071: 076.072: 076.163: 076.161: 076.162: 076.173: 076.077: 076.078: 076.169: 076.207: 076.208: 076.209: 076.210: 076.211: 076.212: 076.213: 076.214: 076.215: 076.164: 076.165: 076.166: 076.174: 076.175: 076.176: 076.170: 076.171: 076.172:

Enable PS1:Yes Block tim.st. IN PS1:Without Gen.starting modePS1:With start. IN/Ineg tGS PS1:0.00 s Rush restr.enabl PS1:No I> PS1:1.09 Inom I>> PS1:Blocked I>>> PS1:Blocked I> dynamic PS1:Blocked I>> dynamic PS1:Blocked I>>> dynamic PS1:Blocked tI> PS1:0.00 s tI>> PS1:Blocked tI>>> PS1:Blocked Ineg> PS1:Blocked Ineg>> PS1:Blocked Ineg>>> PS1:Blocked Ineg> dynamic PS1:Blocked Ineg>> dynamic PS1:Blocked Ineg>>> dynamic PS1:Blocked tIneg> PS1:Blocked tIneg>> PS1:Blocked tIneg>>> PS1:Blocked IN> PS1:Blocked IN>> PS1:Blocked IN>>> PS1:Blocked IN> dynamic PS1:Blocked IN>> dynamic PS1:Blocked IN>>> dynamic PS1:Blocked tIN> PS1:Blocked tIN>> PS1:Blocked tIN>>> PS1:Blocked

: Parameter subset 2: : Parameter subset 3: : Parameter subset 4: : Operation: : Events:

- Settings File Report -

Page 48 of 252

B11, B21 Funct 50, 51, 51N

Page 49 of 252

MiCOM S1 Studio

Page: 1

Settings File Report File: B11-50_51N.set Model Number: P141216A6M0420J

Printed on: 02/08/2010 12:53:03

: SYSTEM DATA:

00.01: 00.02: 00.03: 00.04: 00.05: 00.06: 00.08: 00.09: 00.0A: 00.0B: 00.0C: 00.0D: 00.0E: 00.10: 00.11: 00.20: 00.21: 00.22: 00.30: 00.40: 00.50: 00.51: 00.52: 00.D0: 00.D1: 00.D2: 00.D3:

Language:English Password:**** Sys Fn Links:0 Description:B11/ 50/51/51N Plant Reference:DID/66KV IBT Model Number:P141216A6M0420J Serial Number:3275575 Frequency:50 Hz Comms Level:2 Relay Address:1 Plant Status:0000000000000000 Control Status:0000000000000000 Active Group:1 CB Trip/Close:No Operation Software Ref. 1:P141____6__420_B Opto I/P Status:10000000 Relay O/P Status:0000000 Alarm Status 1:00000000000000000000000000000000 Opto I/P Status:10000000 Relay O/P Status:0000000 Alarm Status 1:00000000000000000000000000000000 Alarm Status 2:00000000000000000000000000000000 Alarm Status 3:00000000000000000000000000000000 Access Level:2 Password Control:2 Password Level 1:**** Password Level 2:****

: CB CONTROL: : DATE AND TIME: : CONFIGURATION:

09.01: 09.02: 09.03: 09.04: 09.05: 09.06: 09.07: 09.08: 09.09: 09.0A: 09.0B: 09.10: 09.11: 09.12: 09.13: 09.14: 09.15: 09.16:

Restore Defaults:No Operation Setting Group:Select via Menu Active Settings:Group 1 Save Changes:No Operation Copy From:Group 1 Copy To:No Operation Setting Group 1:Enabled Setting Group 2:Disabled Setting Group 3:Disabled Setting Group 4:Disabled System Config:Invisible Overcurrent:Enabled Neg Sequence O/C:Disabled Broken Conductor:Disabled Earth Fault 1:Disabled Earth Fault 2:Disabled SEF/REF Prot'n:Disabled Residual O/V NVD:Disabled

- Settings File Report -

Page 50 of 252

MiCOM S1 Studio

Page: 2

Settings File Report File: B11-50_51N.set Model Number: P141216A6M0420J 09.17: 09.18: 09.19: 09.1A: 09.1B: 09.1D: 09.1E: 09.1F: 09.20: 09.21: 09.22: 09.25: 09.26: 09.28: 09.29: 09.2A: 09.2B: 09.2C: 09.2D: 09.2E: 09.2F: 09.35: 09.36: 09.39: 09.FF:

Printed on: 02/08/2010 12:53:03

Thermal Overload:Disabled Neg Sequence O/V:Disabled Cold Load Pickup:Disabled Selective Logic:Disabled Admit Protection:Disabled Volt Protection:Disabled Freq Protection:Disabled df/dt Protection:Disabled CB Fail:Disabled Supervision:Disabled Fault Locator:Disabled Input Labels:Visible Output Labels:Visible CT & VT Ratios:Visible Record Control:Invisible Disturb Recorder:Visible Measure't Setup:Visible Comms Settings:Visible Commission Tests:Visible Setting Values:Secondary Control Inputs:Invisible Ctrl I/P Config:Invisible Ctrl I/P Labels:Invisible Direct Access:Enabled LCD Contrast:9

: CT AND VT RATIOS:

0A.01: 0A.02: 0A.07: 0A.08: 0A.09: 0A.0A: 0A.0B: 0A.0C:

Main VT Primary:66.00 kV Main VT Sec'y:110.0 V Phase CT Primary:400.0 A Phase CT Sec'y:1.000 A E/F CT Primary:400.0 A E/F CT Secondary:1.000 A SEF CT Primary:400.0 A SEF CT Secondary:1.000 A

: DISTURB RECORDER:

0C.01: 0C.02: 0C.03: 0C.04: 0C.05: 0C.06: 0C.07: 0C.08: 0C.09: 0C.0A: 0C.0B: 0C.0C: 0C.0D: 0C.0E:

Duration:2.000 s Trigger Position:33.30% Trigger Mode:Single Analog Channel 1:VA Analog Channel 2:VB Analog Channel 3:VC Analog Channel 4:IA Analog Channel 5:IB Analog Channel 6:IC Analog Channel 7:IN Analog Channel 8:IN Sensitive Digital Input 1:I>1 Trip Input 1 Trigger:Trigger L/H Digital Input 2:ISEF>1 Trip

- Settings File Report -

Page 51 of 252

MiCOM S1 Studio

Page: 3

Settings File Report File: B11-50_51N.set Model Number: P141216A6M0420J 0C.0F: 0C.10: 0C.11: 0C.12: 0C.13: 0C.14: 0C.15: 0C.16: 0C.18: 0C.1A: 0C.1C: 0C.1E: 0C.20: 0C.22: 0C.24: 0C.26: 0C.28: 0C.2A: 0C.2C: 0C.2E: 0C.30: 0C.32: 0C.34: 0C.36: 0C.38: 0C.3A: 0C.3C: 0C.3E: 0C.40: 0C.42: 0C.44: 0C.46: 0C.48: 0C.4A:

Input 2 Digital Input 3 Digital Input 4 Digital Input 5 Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital

Printed on: 02/08/2010 12:53:03

Trigger:Trigger L/H Input 3:I>3 Trip Trigger:Trigger L/H Input 4:ISEF>2 Trip Trigger:Trigger L/H Input 5:Prot'n Disabled Trigger:Trigger L/H Input 6:Unused Input 7:Unused Input 8:Unused Input 9:Unused Input 10:Unused Input 11:Unused Input 12:Unused Input 13:Unused Input 14:Unused Input 15:Unused Input 16:Unused Input 17:Unused Input 18:Unused Input 19:Unused Input 20:Unused Input 21:Unused Input 22:Unused Input 23:Unused Input 24:Unused Input 25:Unused Input 26:Unused Input 27:Unused Input 28:Unused Input 29:Unused Input 30:Unused Input 31:Unused Input 32:Unused

: MEASURE'T SETUP:

0D.01: 0D.02: 0D.03: 0D.04: 0D.05: 0D.06: 0D.07: 0D.08:

Default Display:3Ph + N Current Local Values:Primary Remote Values:Primary Measurement Ref:IA Measurement Mode:0 Fix Dem Period:30.00 min Roll Sub Period:30.00 min Num Sub Periods:1

: COMMISSION TESTS: : CB MONITOR SETUP: : OPTO CONFIG:

11.01: Global Nominal V:110/125V 11.50: Opto Filter Cntl:11111111 11.80: Characteristic:Standard 60%-80%

- Settings File Report -

Page 52 of 252

MiCOM S1 Studio

Page: 4

Settings File Report File: B11-50_51N.set Model Number: P141216A6M0420J

Printed on: 02/08/2010 12:53:03

: IED CONFIGURATOR: : Group 1:

: GROUP 1 35.23: 35.24: 35.27: 35.2A: 35.2D: 35.2F: 35.32: 35.33: 35.36: 35.38: 35.3E: 35.40: 35.41: 35.44: 35.45: 35.47: 35.4E: 35.4F: 35.51: 35.52:

OVERCURRENT: I>1 Function:IEC V Inverse I>1 Direction:Non-Directional I>1 Current Set:1.310 A I>1 TMS:420.0e-3 I>1 DT Adder:0 s I>1 tRESET:0 s I>2 Function:DT I>2 Direction:Non-Directional I>2 Current Set:960.0 mA I>2 Time Delay:0 s I>2 tRESET:0 s I>3 Status:Enabled I>3 Direction:Non-Directional I>3 Current Set:7.970 A I>3 Time Delay:100.0 ms I>4 Status:Disabled I> Blocking:000000000 I> Char Angle:45.00 deg V CONTROLLED O/C: VCO Status:Disabled

: GROUP 1 CB FAIL & Itrip coil 2 3:R3->LV side Trip 4:R4->TRIP 415V 5:R5-> Fire Prot. 6:R6 Spare 7:R7 NOT USED

- Settings File Report -

Page 53 of 252

MiCOM P141 Programmable Scheme Logic Opto Input Mappings L8 TEST MODE DDB #039

1

Test Mode DDB #441

LED Mappings

Any Start DDB #294

Latching

LED 1 DDB #064

Latching

LED 4 DDB #067

Non Latching

LED 8 DDB #071

I>1 Trip DDB #243

1 I>3 Trip DDB #251

L8 TEST MODE DDB #039

1

Fault Record Trigger Mapping I>1 Trip DDB #243

1 I>3 Trip DDB #251

Trip Command In DDB #536

Fault REC TRIG DDB #144

Page : 1 Page 54 of 252

MiCOM P141 Programmable Scheme Logic Output Relay Mappings

0 R1 51N TRIP BS DDB #000

Pick-Up 0 I>1 Trip DDB #243

0

1

R2 TO TRIP 415V DDB #001

Pick-Up

I>3 Trip DDB #251

0 0 R3 HV REM SEND-2 DDB #002

Pick-Up 0 0

R4 86 TRIP DDB #003

Pick-Up 0 0

R5 ANT TRIP SPAR DDB #004

Pick-Up 0 0

R6 NOT USED DDB #005

Pick-Up 0 0

R7 NOT USED DDB #006

Pick-Up 0

Transformer Overcurrent User Alarming 110% Full Load

I>2 Trip DDB #247

SR User Alarm 1 DDB #167

Page : 2

Page 55 of 252

A18_A28-50_51N_SBEF

Page 56 of 252

MiCOM S1 Studio

Page: 1

Settings File Report File: A18-50_51N_SBEF.set Model Number: P141216A6M0420J

Printed on: 02/08/2010 13:02:35

: SYSTEM DATA:

00.01: 00.02: 00.03: 00.04: 00.05: 00.06: 00.08: 00.09: 00.0A: 00.0B: 00.0C: 00.0D: 00.0E: 00.10: 00.11: 00.20: 00.21: 00.22: 00.30: 00.40: 00.50: 00.51: 00.52: 00.D0: 00.D1: 00.D2: 00.D3:

Language:English Password:**** Sys Fn Links:0 Description:A18/ 50/51/51N Plant Reference:DID/11KV IC/SBEF Model Number:P141216A6M0420J Serial Number:3275575 Frequency:50 Hz Comms Level:2 Relay Address:1 Plant Status:0000000000000000 Control Status:0000000000000000 Active Group:1 CB Trip/Close:No Operation Software Ref. 1:P141____6__420_B Opto I/P Status:10000000 Relay O/P Status:0000000 Alarm Status 1:00000000000000000000000000000000 Opto I/P Status:10000000 Relay O/P Status:0000000 Alarm Status 1:00000000000000000000000000000000 Alarm Status 2:00000000000000000000000000000000 Alarm Status 3:00000000000000000000000000000000 Access Level:2 Password Control:2 Password Level 1:**** Password Level 2:****

: CB CONTROL: : DATE AND TIME: : CONFIGURATION:

09.01: 09.02: 09.03: 09.04: 09.05: 09.06: 09.07: 09.08: 09.09: 09.0A: 09.0B: 09.10: 09.11: 09.12: 09.13: 09.14: 09.15: 09.16:

Restore Defaults:No Operation Setting Group:Select via Menu Active Settings:Group 1 Save Changes:No Operation Copy From:Group 1 Copy To:No Operation Setting Group 1:Enabled Setting Group 2:Disabled Setting Group 3:Disabled Setting Group 4:Disabled System Config:Invisible Overcurrent:Enabled Neg Sequence O/C:Disabled Broken Conductor:Disabled Earth Fault 1:Disabled Earth Fault 2:Disabled SEF/REF Prot'n:Enabled Residual O/V NVD:Disabled

- Settings File Report -

Page 57 of 252

MiCOM S1 Studio

Page: 2

Settings File Report File: A18-50_51N_SBEF.set Model Number: P141216A6M0420J 09.17: 09.18: 09.19: 09.1A: 09.1B: 09.1D: 09.1E: 09.1F: 09.20: 09.21: 09.22: 09.25: 09.26: 09.28: 09.29: 09.2A: 09.2B: 09.2C: 09.2D: 09.2E: 09.2F: 09.35: 09.36: 09.39: 09.FF:

Printed on: 02/08/2010 13:02:35

Thermal Overload:Disabled Neg Sequence O/V:Disabled Cold Load Pickup:Disabled Selective Logic:Disabled Admit Protection:Disabled Volt Protection:Disabled Freq Protection:Disabled df/dt Protection:Disabled CB Fail:Disabled Supervision:Disabled Fault Locator:Disabled Input Labels:Visible Output Labels:Visible CT & VT Ratios:Visible Record Control:Invisible Disturb Recorder:Visible Measure't Setup:Visible Comms Settings:Visible Commission Tests:Visible Setting Values:Secondary Control Inputs:Invisible Ctrl I/P Config:Invisible Ctrl I/P Labels:Invisible Direct Access:Enabled LCD Contrast:9

: CT AND VT RATIOS:

0A.01: 0A.02: 0A.07: 0A.08: 0A.09: 0A.0A: 0A.0B: 0A.0C:

Main VT Primary:11.00 kV Main VT Sec'y:110.0 V Phase CT Primary:29.00 A Phase CT Sec'y:1.000 A E/F CT Primary:750.0 A E/F CT Secondary:1.000 A SEF CT Primary:750.0 A SEF CT Secondary:1.000 A

: DISTURB RECORDER:

0C.01: 0C.02: 0C.03: 0C.04: 0C.05: 0C.06: 0C.07: 0C.08: 0C.09: 0C.0A: 0C.0B: 0C.0C: 0C.0D: 0C.0E:

Duration:2.000 s Trigger Position:33.30% Trigger Mode:Single Analog Channel 1:VA Analog Channel 2:VB Analog Channel 3:VC Analog Channel 4:IA Analog Channel 5:IB Analog Channel 6:IC Analog Channel 7:IN Analog Channel 8:IN Sensitive Digital Input 1:I>1 Trip Input 1 Trigger:Trigger L/H Digital Input 2:ISEF>1 Trip

- Settings File Report -

Page 58 of 252

MiCOM S1 Studio

Page: 3

Settings File Report File: A18-50_51N_SBEF.set Model Number: P141216A6M0420J 0C.0F: 0C.10: 0C.11: 0C.12: 0C.13: 0C.14: 0C.15: 0C.16: 0C.18: 0C.1A: 0C.1C: 0C.1E: 0C.20: 0C.22: 0C.24: 0C.26: 0C.28: 0C.2A: 0C.2C: 0C.2E: 0C.30: 0C.32: 0C.34: 0C.36: 0C.38: 0C.3A: 0C.3C: 0C.3E: 0C.40: 0C.42: 0C.44: 0C.46: 0C.48: 0C.4A:

Input 2 Digital Input 3 Digital Input 4 Digital Input 5 Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital

Printed on: 02/08/2010 13:02:35

Trigger:Trigger L/H Input 3:I>3 Trip Trigger:Trigger L/H Input 4:ISEF>2 Trip Trigger:Trigger L/H Input 5:Prot'n Disabled Trigger:Trigger L/H Input 6:Unused Input 7:Unused Input 8:Unused Input 9:Unused Input 10:Unused Input 11:Unused Input 12:Unused Input 13:Unused Input 14:Unused Input 15:Unused Input 16:Unused Input 17:Unused Input 18:Unused Input 19:Unused Input 20:Unused Input 21:Unused Input 22:Unused Input 23:Unused Input 24:Unused Input 25:Unused Input 26:Unused Input 27:Unused Input 28:Unused Input 29:Unused Input 30:Unused Input 31:Unused Input 32:Unused

: MEASURE'T SETUP:

0D.01: 0D.02: 0D.03: 0D.04: 0D.05: 0D.06: 0D.07: 0D.08:

Default Display:3Ph + N Current Local Values:Primary Remote Values:Primary Measurement Ref:IA Measurement Mode:0 Fix Dem Period:30.00 min Roll Sub Period:30.00 min Num Sub Periods:1

: COMMISSION TESTS: : CB MONITOR SETUP: : OPTO CONFIG:

11.01: Global Nominal V:110/125V 11.50: Opto Filter Cntl:11111111 11.80: Characteristic:Standard 60%-80%

- Settings File Report -

Page 59 of 252

MiCOM S1 Studio

Page: 4

Settings File Report File: A18-50_51N_SBEF.set Model Number: P141216A6M0420J

Printed on: 02/08/2010 13:02:35

: IED CONFIGURATOR: : Group 1:

: GROUP 1 35.23: 35.24: 35.27: 35.2A: 35.2D: 35.2F: 35.32: 35.40: 35.41: 35.44: 35.45: 35.47: 35.4E: 35.4F: 35.51: 35.52:

OVERCURRENT: I>1 Function:IEC V Inverse I>1 Direction:Non-Directional I>1 Current Set:1.360 A I>1 TMS:850.0e-3 I>1 DT Adder:0 s I>1 tRESET:0 s I>2 Function:Disabled I>3 Status:Enabled I>3 Direction:Non-Directional I>3 Current Set:15.00 A I>3 Time Delay:100.0 ms I>4 Status:Disabled I> Blocking:000000000 I> Char Angle:45.00 deg V CONTROLLED O/C: VCO Status:Disabled

: GROUP 1 SEF/REF PROT'N: 3A.01: SEF/REF Options:SEF 3A.2A: ISEF>1 Function:DT 3A.2B: ISEF>1 Direction:Non-Directional 3A.2E: ISEF>1 Current:100.0 mA 3A.31: ISEF>1 Delay:0 s 3A.37: ISEF>1 tRESET:0 s 3A.3A: ISEF>2 Function:Disabled 3A.49: ISEF>3 Status:Enabled 3A.4A: ISEF>3 Direction:Non-Directional 3A.4D: ISEF>3 Current:400.0 mA 3A.4E: ISEF>3 Delay:3.500 s 3A.50: ISEF>4 Status:Enabled 3A.51: ISEF>4 Direction:Non-Directional 3A.54: ISEF>4 Current:400.0 mA 3A.55: ISEF>4 Delay:4.500 s 3A.57: ISEF> Blocking:00000000 3A.58: ISEF POL: 3A.59: ISEF> Char Angle:45.00 deg 3A.5B: ISEF> VNpol Set:5.000 V : GROUP 1 CB FAIL & I1 Trip DDB #243

Latching

LED 2 DDB #065

I>3 Trip DDB #251

Latching

LED 3 DDB #066

ISEF>3 Trip DDB #271

Latching

LED 4 DDB #067

ISEF>4 Trip DDB #272

Latching

LED 5 DDB #068

Fault Record Trigger Mapping

Any Start DDB #294 I>1 Trip DDB #243 I>3 Trip DDB #251

1

1

50 Dwell 0

Fault REC TRIG DDB #144

ISEF>3 Trip DDB #271

ISEF>4 Trip DDB #272

Trip Command In DDB #536

Page 62 of 252

A18_ 50_51N_SBEF PROTECTION RELAY Output Relay Mappings

100 ISEF>3 Trip DDB #271

R1 51N TRIP BS DDB #000

Dwell 0 100

R2 TO TRIP 415V DDB #001

Dwell 0 100

I>1 Trip DDB #243

R3 HV REM SEND-2 DDB #002

Dwell I>3 Trip DDB #251

1

0 100 R5 ANY TRIP SPAR DDB #004

Dwell 0

ISEF>4 Trip DDB #272

100 R4 86 TRIP STG2 DDB #003

Dwell 0

ISEF>1 Trip DDB #269

SR User Alarm 1 DDB #167

Page : 2

Page 63 of 252

B12_51_51N_SET

Page 64 of 252

MiCOM S1 Studio

Page: 1

Settings File Report File: B12-51_51N.set Model Number: P141216A6M0420J

Printed on: 02/08/2010 13:05:31

: SYSTEM DATA:

00.01: 00.02: 00.03: 00.04: 00.05: 00.06: 00.08: 00.09: 00.0A: 00.0B: 00.0C: 00.0D: 00.0E: 00.10: 00.11: 00.20: 00.21: 00.22: 00.30: 00.40: 00.50: 00.51: 00.52: 00.D0: 00.D1: 00.D2: 00.D3:

Language:English Password:**** Sys Fn Links:0 Description:B12 51/51N Plant Reference:MUS/66KV BS Model Number:P141216A6M0420J Serial Number:3275575 Frequency:50 Hz Comms Level:2 Relay Address:1 Plant Status:0000000000000000 Control Status:0000000000000000 Active Group:1 CB Trip/Close:No Operation Software Ref. 1:P141____6__420_B Opto I/P Status:10000000 Relay O/P Status:0000000 Alarm Status 1:00000000000000000000000000000000 Opto I/P Status:10000000 Relay O/P Status:0000000 Alarm Status 1:00000000000000000000000000000000 Alarm Status 2:00000000000000000000000000000000 Alarm Status 3:00000000000000000000000000000000 Access Level:2 Password Control:2 Password Level 1:**** Password Level 2:****

: CB CONTROL: : DATE AND TIME: : CONFIGURATION:

09.01: 09.02: 09.03: 09.04: 09.05: 09.06: 09.07: 09.08: 09.09: 09.0A: 09.0B: 09.10: 09.11: 09.12: 09.13: 09.14: 09.15: 09.16:

Restore Defaults:No Operation Setting Group:Select via Menu Active Settings:Group 1 Save Changes:No Operation Copy From:Group 1 Copy To:No Operation Setting Group 1:Enabled Setting Group 2:Disabled Setting Group 3:Disabled Setting Group 4:Disabled System Config:Invisible Overcurrent:Enabled Neg Sequence O/C:Disabled Broken Conductor:Disabled Earth Fault 1:Disabled Earth Fault 2:Disabled SEF/REF Prot'n:Disabled Residual O/V NVD:Disabled

- Settings File Report -

Page 65 of 252

MiCOM S1 Studio

Page: 2

Settings File Report File: B12-51_51N.set Model Number: P141216A6M0420J 09.17: 09.18: 09.19: 09.1A: 09.1B: 09.1D: 09.1E: 09.1F: 09.20: 09.21: 09.22: 09.25: 09.26: 09.28: 09.29: 09.2A: 09.2B: 09.2C: 09.2D: 09.2E: 09.2F: 09.35: 09.36: 09.39: 09.FF:

Printed on: 02/08/2010 13:05:31

Thermal Overload:Disabled Neg Sequence O/V:Disabled Cold Load Pickup:Disabled Selective Logic:Disabled Admit Protection:Disabled Volt Protection:Disabled Freq Protection:Disabled df/dt Protection:Disabled CB Fail:Disabled Supervision:Disabled Fault Locator:Disabled Input Labels:Visible Output Labels:Visible CT & VT Ratios:Visible Record Control:Invisible Disturb Recorder:Visible Measure't Setup:Visible Comms Settings:Visible Commission Tests:Visible Setting Values:Secondary Control Inputs:Invisible Ctrl I/P Config:Invisible Ctrl I/P Labels:Invisible Direct Access:Enabled LCD Contrast:9

: CT AND VT RATIOS:

0A.01: 0A.02: 0A.07: 0A.08: 0A.09: 0A.0A: 0A.0B: 0A.0C:

Main VT Primary:66.00 kV Main VT Sec'y:110.0 V Phase CT Primary:2000 A Phase CT Sec'y:1.000 A E/F CT Primary:2000 A E/F CT Secondary:1.000 A SEF CT Primary:2000 A SEF CT Secondary:1.000 A

: DISTURB RECORDER:

0C.01: 0C.02: 0C.03: 0C.04: 0C.05: 0C.06: 0C.07: 0C.08: 0C.09: 0C.0A: 0C.0B: 0C.0C: 0C.0D: 0C.0E:

Duration:2.000 s Trigger Position:33.30% Trigger Mode:Single Analog Channel 1:VA Analog Channel 2:VB Analog Channel 3:VC Analog Channel 4:IA Analog Channel 5:IB Analog Channel 6:IC Analog Channel 7:IN Analog Channel 8:IN Sensitive Digital Input 1:I>1 Trip Input 1 Trigger:Trigger L/H Digital Input 2:ISEF>1 Trip

- Settings File Report -

Page 66 of 252

MiCOM S1 Studio

Page: 3

Settings File Report File: B12-51_51N.set Model Number: P141216A6M0420J 0C.0F: 0C.10: 0C.11: 0C.12: 0C.13: 0C.14: 0C.15: 0C.16: 0C.18: 0C.1A: 0C.1C: 0C.1E: 0C.20: 0C.22: 0C.24: 0C.26: 0C.28: 0C.2A: 0C.2C: 0C.2E: 0C.30: 0C.32: 0C.34: 0C.36: 0C.38: 0C.3A: 0C.3C: 0C.3E: 0C.40: 0C.42: 0C.44: 0C.46: 0C.48: 0C.4A:

Input 2 Digital Input 3 Digital Input 4 Digital Input 5 Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital

Printed on: 02/08/2010 13:05:31

Trigger:Trigger L/H Input 3:I>3 Trip Trigger:Trigger L/H Input 4:ISEF>2 Trip Trigger:Trigger L/H Input 5:Prot'n Disabled Trigger:Trigger L/H Input 6:Unused Input 7:Unused Input 8:Unused Input 9:Unused Input 10:Unused Input 11:Unused Input 12:Unused Input 13:Unused Input 14:Unused Input 15:Unused Input 16:Unused Input 17:Unused Input 18:Unused Input 19:Unused Input 20:Unused Input 21:Unused Input 22:Unused Input 23:Unused Input 24:Unused Input 25:Unused Input 26:Unused Input 27:Unused Input 28:Unused Input 29:Unused Input 30:Unused Input 31:Unused Input 32:Unused

: MEASURE'T SETUP:

0D.01: 0D.02: 0D.03: 0D.04: 0D.05: 0D.06: 0D.07: 0D.08:

Default Display:3Ph + N Current Local Values:Primary Remote Values:Primary Measurement Ref:IA Measurement Mode:0 Fix Dem Period:30.00 min Roll Sub Period:30.00 min Num Sub Periods:1

: COMMISSION TESTS: : CB MONITOR SETUP: : OPTO CONFIG:

11.01: Global Nominal V:110/125V 11.50: Opto Filter Cntl:11111111 11.80: Characteristic:Standard 60%-80%

- Settings File Report -

Page 67 of 252

MiCOM S1 Studio

Page: 4

Settings File Report File: B12-51_51N.set Model Number: P141216A6M0420J

Printed on: 02/08/2010 13:05:31

: IED CONFIGURATOR: : Group 1:

: GROUP 1 35.23: 35.24: 35.27: 35.2A: 35.2D: 35.2F: 35.32: 35.40: 35.47: 35.4E: 35.4F: 35.51: 35.52:

OVERCURRENT: I>1 Function:IEC V Inverse I>1 Direction:Non-Directional I>1 Current Set:1.100 A I>1 TMS:150.0e-3 I>1 DT Adder:0 s I>1 tRESET:0 s I>2 Function:Disabled I>3 Status:Disabled I>4 Status:Disabled I> Blocking:000000000 I> Char Angle:45.00 deg V CONTROLLED O/C: VCO Status:Disabled

: GROUP 1 CB FAIL & Itrip coil 2 3:R3->LV side Trip 4:R4->TRIP 415V 5:R5-> Fire Prot. 6:R6 Spare 7:R7 NOT USED

- Settings File Report -

Page 68 of 252

MiCOM P141 Programmable Scheme Logic OPTO INPUT MAPPING L8 TEST MODE DDB #039

I>1 Trip DDB #243

1

Test Mode DDB #441

100

1

R4 ANY TRIP - 86 DDB #003

Dwell

ANY TRIP

0

Page 69 of 252

MiCOM P141 Programmable Scheme Logic

SIGNAL MAPPING FOR SCS

I>1 Trip DDB #243

1

SR User Alarm 1 DDB #167

TRIP COMMAND MAPPING

I>1 Trip DDB #243

1

Trip Command In DDB #536

Page 70 of 252

MiCOM P141 Programmable Scheme Logic Output Relay Mappings 100 Trip Command Out DDB #537

R3 ANY TRP-SPARE DDB #002

Dwell 0

LED Mappings

Any Start DDB #294

Latching

LED 1 DDB #064

I>1 Trip DDB #243

Latching

LED 2 DDB #065

Page 71 of 252

66kV Busbar Protection

Page 72 of 252

MiCOM S1 Studio

Page: 1

Settings File Report File: 66kV BS SET.set Model Number: P743211A1M0420K

Printed on: 04/03/2010 13:59:54

: SYSTEM DATA:

00.01: 00.02: 00.04: 00.05: 00.06: 00.08: 00.09: 00.0A: 00.0B: 00.0C: 00.0D: 00.0E: 00.10: 00.11: 00.20: 00.21: 00.22: 00.40: 00.50: 00.51: 00.52: 00.D0: 00.D1: 00.D2: 00.D3:

Language:English Password:**** Description:66kV BS No DZ Plant Reference: Model Number:P743211A1M0420K Serial Number:070707P Frequency:50 Hz Comms Level:2 Relay Address:7 Plant Status:0000000000000011 Control Status:0000000000000000 Active Group:1 CB Trip/Close:No Operation Software Ref. 1:D4.0beta4 Opto I/P Status:000000000000000000000000 Relay O/P Status:0000000010000000 Alarm Status 1:00000000010001110001000010000000 Relay O/P Status:0000000010000000 Alarm Status 1:00000000010001110001000010000000 Alarm Status 2:00000000000000000000000000000000 Alarm Status 3:00000000000000000000000000000000 Access Level:2 Password Control:2 Password Level 1:**** Password Level 2:****

: CB CONTROL: : DATE AND TIME: : CONFIGURATION:

09.01: 09.02: 09.03: 09.04: 09.05: 09.06: 09.07: 09.08: 09.09: 09.0A: 09.0F: 09.10: 09.12: 09.13: 09.14: 09.25: 09.26: 09.28: 09.29: 09.2A:

Restore Defaults:No Operation Setting Group:Select via Menu Active Settings:Group 1 Save Changes:No Operation Copy From:Group 1 Copy To:No Operation Setting Group 1:Enabled Setting Group 2:Disabled Setting Group 3:Disabled Setting Group 4:Disabled Dead Zone Prot:Disabled BB Trip Confirm:Disabled Overcurrent Prot:Disabled Earth Fault Prot:Disabled CB Fail & I Status:Disabled 45.06: GROUP 1 Internal Trip: 45.07: CB Fail Timer 1:70.00 ms 45.08: CB Fail Timer 2:180.0 ms 45.09: GROUP 1 External Trip: 45.0A: CB Fail Timer 3:70.00 ms 45.0B: CB Fail Timer 4:180.0 ms : GROUP 1 SUPERVISION: : GROUP 1 INPUT LABELS: : GROUP 1 OUTPUT LABELS:

- Settings File Report -

Page 74 of 252

INPUTS

P743

Reset all indications CU->PU Signal 01 DDB #192

Non Latching

1

FnKey LED 1 Red DDB #656 FnKey LED 1 Grn DDB #657

Function Key 1 DDB #676

Green: Reset indication

Reset Indication DDB #135

Reset Trip Relays (if latched is enabled)

CU->PU Signal 02 DDB #193

Non Latching

1

Function Key 2 DDB #677

FnKey LED 2 Red DDB #658 FnKey LED 2 Grn DDB #659

Green: Reset Trip Latch

Reset Trip latch DDB #131

Isolator 1 L5 G1704 CLS POS DDB #068

Q1 Aux. (89a) DDB #105

Closed position

L4 G1704 OPN POS DDB #067

Q1 Aux. (89b) DDB #104

Open position

L7 G1702 CLS POS DDB #070

Q2 Aux. (89a) DDB #107

Closed position

L6 G1702 OPN POS DDB #069

Q2 Aux. (89b) DDB #106

Open position

Isolator 2

Cicruit breaker L3 G1700 CLS POS DDB #066

CB Aux. 3ph(52a) DDB #123

Closed position

L2 G1700 OPN POS DDB #065

CB Aux. 3ph(52b) DDB #124

Open position

External CB Failure Protection Integrated CB Failure Protection Ext. 3 ph Trip DDB #116

L1 50BF 3PH INT DDB #064

&

External 3phase Trip order

PU Overhaul mode DDB #307

Commissioning modes

50BF Disabled DDB #308

Non Latching

PU Overhaul mode DDB #307

Non Latching

L16 PU TEST MODE DDB #079 L12 50BF Y INT DDB #075 L11 50BF R INT DDB #074

1 &

FnKey LED 4 Red DDB #662 FnKey LED 4 Grn DDB #663

FnKey LED 5 Red DDB #664 FnKey LED 5 Grn DDB #665

Overhaul Mode DDB #312

Mode 50BF Disabled: - Local trip disabled - 50BF disabled - No backtrip - 87BB in service on this PU

Mode Overhaul: - PU 87BB protection in Overhaul mode - Position of isolator and CB are forced - Mode used to test local protection - Local trip enabled - No backtrip

Page 75 of 252

1/4

P743

Isolator 1

Status Alarm

L5 G1704 CLS POS DDB #068 L4 G1704 OPN POS DDB #067

&

1

5000 0

L5 G1704 CLS POS DDB #068 L4 G1704 OPN POS DDB #067

Q1 Status Alarm DDB #321

Pick-Up

Red: Closed Yellow: Status Alarm Green: Open

1

Q1 Closed DDB #320

1

Q1 Closed DDB #320

Non Latching

LED 1 Red DDB #640 LED 1 Grn DDB #641

1

L7 G1702 CLS POS DDB #070 L6 G1702 OPN POS DDB #069

&

5000 Pick-Up 0

L7 G1702 CLS POS DDB #070 L6 G1702 OPN POS DDB #069

1

Q2 Status Alarm DDB #323

1

Red: Closed Yellow: Status Alarm Green: Open

1

Q2 Closed DDB #322

Non Latching

1

LED 2 Red DDB #642 LED 2 Grn DDB #643

Saturation ph A DDB #232 Saturation ph B DDB #233 Saturation ph C DDB #234 CT Fail IN DDB #255 All Prot Blocked DDB #270

1

PU->CU Signal 08 DDB #151

PU Overhaul mode DDB #307 50BF Disabled DDB #308 Q1 Status Forced DDB #336 Q2 Status Forced DDB #337 CB Status Forced DDB #342

Fault recorder 20 Fault_REC_TRIG DDB #468

Dwell Any Trip DDB #358

0

Page 76 of 252

2/4

LEFT-HAND LEDS

P743

CIRCUIT BREAKER CB Closed DDB #332

1

CB Status Alarm DDB #352

Non Latching

1

CB Closed DDB #332

LED 3 Red DDB #644 LED 3 Grn DDB #645

Red: Closed Yellow: Status Alarm Green: Open

Trip information

Red: Dead Zone Fault

Internal Trip DDB #256

&

Trip 87BB DDB #257

L1 50BF 3PH INT DDB #064

Internal Trip DDB #256 Trip 50BF (CU) DDB #259

Fibre Com Error DDB #252 Fibre Com Worn DDB #253 Fibre Com Error DDB #252 Fibre Com Worn DDB #253

Latching

Latching

&

1

Latching

Non Latching

LED 5 Red DDB #648 LED 5 Grn DDB #649

LED 6 Red DDB #650 LED 6 Grn DDB #651

LED 7 Red DDB #652 LED 7 Grn DDB #653

LED 8 Red DDB #654 LED 8 Grn DDB #655

Red: Trip on 87BB CU trip order

Red: Ext. 50BF Initation 3phase or 1phase

Red: Trip on 50BF CU backtrip order

Fibre com Red: Error Yellow: Change Green: Healthy

1

Page 77 of 252

3/4

OUTPUT RELAYS

P743

100 RL01 TRIP TRC1-R DDB #000

Dwell 0 Internal Trip DDB #256 Trip 87BB DDB #257 Internal Trip DDB #256

0

&

RL02 TRIP TRC1-Y DDB #001

Pick-Up 0

&

1

Trip 50BF (CU) DDB #259

100 RL03 TRIP TRC1-B DDB #002

Dwell 0

Int. Retrip 3 ph DDB #171

&

PU Overhaul mode DDB #307

0

1

RL12 TRIP 50BF 1 DDB #011

Pick-Up 0

0 RL11 TRIP 87BB DDB #010

Pick-Up 0 Internal Trip DDB #256

&

Trip 87BB DDB #257

0

1

RL04 87BB+50BF 2 DDB #003

Pick-Up 0 0

Internal Trip DDB #256

RL05 87BB+50BF 2 DDB #004

Pick-Up

&

0

Trip 50BF (CU) DDB #259

0 RL13 TRIP 50BF 2 DDB #012

Pick-Up 0 0

1

RL14 87BB+50BF 2 DDB #013

Pick-Up 0

Page 78 of 252

4/4

P741 Function Key 1 DDB #676 Circt Flt Alm Zx DDB #266 Circt Flt Alm CZ DDB #284

&

Circt Flt Lck Zx DDB #280

1

&

PU error

1

Function Key 2 DDB #677 PU Error Lck Zx DDB #282

Reset for Zones / Check Zone

Reset Circt Flt DDB #106

Function Key 2 DDB #677

PU Error Alm CZ DDB #286

FnKey LED 1 Grn DDB #657

Zones or Check Zone: Red = Blocking Yellow = Alarm only Green = No Alarm

&

Function Key 1 DDB #676

PU Error Alm Zx DDB #281

FnKey LED 1 Red DDB #656

Non Latching

1

Function Key 1 DDB #676 Circt Flt Alm Zx DDB #266

Circuitry fault

FnKey LED 2 Red DDB #658

Non Latching

FnKey LED 2 Grn DDB #659

&

Zones or Check Zone: Red = Blocking Yellow = Alarm only Green = No Alarm

1

PU Error Lck CZ DDB #287

Reset for Zones / Check Zone

Reset PU Error DDB #110

Function Key 2 DDB #677

Reset all indications FnKey LED 6 Red DDB #666

Non Latching

Function Key 6 DDB #681 Function Key 7 DDB #682

1

Green = Reset CU indications

FnKey LED 7 Red DDB #668

Green = Reset CU&PU indications

Reset Indication DDB #109

Non Latching

Function Key 7 DDB #682

FnKey LED 6 Grn DDB #667

FnKey LED 7 Grn DDB #669

Green = Reset PU Trip Latch

CU->PU Signal 01 DDB #112 CU->PU Signal 02 DDB #113

INPUTS Opto Label 01 DDB #064

& Opto Label 02 DDB #065

1

All Prot Blocked DDB #111

Opto Label 08 DDB #071

1/3 Page 79 of 252

P741

Fault Phase A DDB #262

Fault Phase B DDB #263

1

Trip 87BB Zone 1 DDB #191

Trip 50BF Zone 2 DDB #206

LED 2 Grn DDB #643

LED 3 Grn DDB #645

LED 4 Red DDB #646 LED 4 Grn DDB #647

LED 5 Red DDB #648

Latching

1

Lck Lev.1 Zone 1 DDB #247

LED 5 Grn DDB #649

Non Latching

&

Circt Flt Lck z1 DDB #167

87BB Fault phase B

87BB Fault phase C

Red: Trip zone 1

Red: Trip zone 2

Zone 1: Red: Zone blocking Yellow: Check Zone blocking Green: Protected

1

1

87BB Fault phase A

LED 3 Red DDB #644

Latching

1

Trip 87BB Zone 2 DDB #190

PU Error Lck z1 DDB #151

LED 2 Red DDB #642

Latching

Trip 50BF Zone 1 DDB #207

PU Error Lck CZ DDB #287

LED 1 Grn DDB #641

Latching

Fault Phase C DDB #264

Circt Flt Lck CZ DDB #285

LED 1 Red DDB #640

Latching

FnKey LED 4 Red DDB #662 FnKey LED 4 Grn DDB #663

Lck Lev.2 Zone 1 DDB #255

Circt Flt Lck CZ DDB #285 PU Error Lck CZ DDB #287

1

Zone 2: Red: Zone blocking Yellow: Check Zone blocking Green: Protected

1

Lck Lev.1 Zone 2 DDB #246 PU Error Lck z2 DDB #150

Non Latching

1

&

Circt Flt Lck z2 DDB #166

FnKey LED 5 Red DDB #664 FnKey LED 5 Grn DDB #665

Lck Lev.2 Zone 2 DDB #254

Fibre Com Error DDB #135

1

Fibre Com Worn DDB #272

Non Latching Fibre Com Error DDB #135

LED 8 Red DDB #654

Fibre communication Red: Error Yellow: Change Green: Healthy

LED 8 Grn DDB #655

1

Fibre Com Worn DDB #272

FAULT RECORDER Trip 87BB DDB #256 Trip 50BF DDB #259

20

1

Fault_REC_TRIG DDB #468

Dwell 0

2/3 Page 80 of 252

P741

Trip 87BB DDB #256

Latching

Trip 50BF DDB #259

Latching

Trip 87BB Zone 3 DDB #189

1

Trip 50BF Zone 3 DDB #205

Trip 87BB Zone 4 DDB #188

1

Trip 50BF Zone 4 DDB #204

Circt Flt Lck CZ DDB #285

Latching

1

PU Error Lck CZ DDB #287

Latching

Circt Flt Lck z3 DDB #165

FnKey LED 8 Red DDB #670 FnKey LED 8 Grn DDB #671

LED 6 Grn DDB #651

LED 7 Red DDB #652 LED 7 Grn DDB #653

Red: Trip Zone 4

FnKey LED 9 Red DDB #672 FnKey LED 9 Grn DDB #673

&

1

1 Non Latching

Lck Lev.1 Zone 4 DDB #244

Circt Flt Lck z4 DDB #164

Red: Trip Zone 3

Zone 4: Red: Zone blocking Yellow: Check Zone blocking Green: Protected

PU Error Lck CZ DDB #287

PU Error Lck z4 DDB #148

Red: 50BF Trip

LED 6 Red DDB #650

Lck Lev.2 Zone 3 DDB #253

Circt Flt Lck CZ DDB #285

Red: 87BB Trip

1 Non Latching

1

FnKey LED 3 Grn DDB #661

Zone 3: Red: Zone blocking Yellow: Check Zone blocking Green: Protected

Lck Lev.1 Zone 3 DDB #245 PU Error Lck z3 DDB #149

FnKey LED 3 Red DDB #660

1

FnKey LED 10 Red DDB #674 FnKey LED 10 Grn DDB #675

&

Lck Lev.2 Zone 4 DDB #252

3/3 Page 81 of 252

MiCOM S1 Studio

Page: 1

Settings File Report File: 66kV CU.set Model Number: P741276A6M0420K

Printed on: 04/03/2010 13:58:00

: SYSTEM DATA:

00.01: 00.02: 00.04: 00.05: 00.06: 00.08: 00.09: 00.0A: 00.0B: 00.0C: 00.0D: 00.0E: 00.11: 00.12: 00.20: 00.21: 00.22: 00.40: 00.50: 00.51: 00.52: 00.D0: 00.D1: 00.D2: 00.D3:

Language:English Password:**** Description:66kV BBP CU Plant Reference: Model Number:P741276A6M0420K Serial Number:060606C Frequency:50 Hz Comms Level:2 Relay Address:6 Plant Status:0000000000000000 Control Status:0000000000000000 Active Group:1 Software Ref. 1:D4.0beta4 Software Ref. 2:D4.0 Opto I/P Status:00000000 Relay O/P Status:00000000 Alarm Status 1:00000100000000100000000000000000 Relay O/P Status:00000000 Alarm Status 1:00000100000000100000000000000000 Alarm Status 2:00000000000000000000000000000000 Alarm Status 3:00000000000000000000000000000000 Access Level:2 Password Control:2 Password Level 1:**** Password Level 2:****

: PU CONF & STATUS: : DATE AND TIME: : CONFIGURATION:

09.01: 09.02: 09.03: 09.04: 09.05: 09.06: 09.07: 09.08: 09.09: 09.0A: 09.0F: 09.10: 09.25: 09.26: 09.29: 09.2A: 09.2B: 09.2C: 09.2D: 09.2E:

Restore Defaults:No Operation Setting Group:Select via Menu Active Settings:Group 1 Save Changes:No Operation Copy From:Group 1 Copy To:No Operation Setting Group 1:Enabled Setting Group 2:Disabled Setting Group 3:Disabled Setting Group 4:Disabled Busbar Option:Visible Diff Busbar Prot:Enabled Input Labels:Visible Output Labels:Visible Record Control:Visible Disturb Recorder:Visible Measure't Setup:Visible Comms Settings:Invisible Commission Tests:Visible Setting Values:Primary

- Settings File Report -

Page 82 of 252

MiCOM S1 Studio

Page: 2

Settings File Report File: 66kV CU.set Model Number: P741276A6M0420K 09.2F: 09.35: 09.36: 09.39: 09.50: 09.FB: 09.FD: : : : : :

Printed on: 04/03/2010 13:58:00

Control Inputs:Visible Ctrl I/P Config:Visible Ctrl I/P Labels:Visible Direct Access:Enabled Function Key:Visible RP1 Read Only:Disabled NIC Read Only:Disabled

RECORD CONTROL: DISTURB RECORDER: MEASURE'T SETUP: COMMISSION TESTS: OPTO CONFIG:

11.01: Global Nominal V:110/125V : : : : :

CTRL I/P CONFIG: FUNCTION KEYS: IED CONFIGURATOR: CTRL I/P LABELS: Group 1:

: GROUP 1 DIFF BUSBAR PROT: 30.01: GROUP 1 Diff Phase Fault: 30.02: GROUP 1 CZ Parameters: 30.04: Phase Slope kCZ:30.00% 30.05: IDCZ>2 Current:2400 A 30.06: GROUP 1 Zone Parameters: 30.08: Phase Slope k2:65.00% 30.09: ID>2 Current:2400 A 30.0A: GROUP 1 Common: 30.0B: ID>1 Current:200.0 A 30.0C: Phase Slope k1:10.00% 30.0D: ID>1 Alarm Timer:5.000 s 30.10: Diff Earth Fault:Disabled : GROUP 1 BUSBAR OPTION: 31.01: CZ Circ Flt Mode:AlarmSR&No Block 31.02: Zx Circ Flt Mode:Self-Reset 31.03: Circuitry tReset:60.00 s 31.04: Circ. Blok Mode:3phase Blocking 31.05: CZ PU Err.Mode:AlarmSR&No Block 31.06: Zx PU Err.Mode:Self-Reset 31.07: PU Error Timer:5.000 s 31.08: PU Error tReset:60.00 s 31.09: SEF Block Alarm:Enabled 31.0A: Reset PU Error:Without Comm Err : GROUP 1 INPUT LABELS: : GROUP 1 OUTPUT LABELS:

- Settings File Report -

Page 83 of 252

MiCOM S1 Studio

Page: 1

Settings File Report File: 66kV UGC - Trafo SET.set Model Number: P743211A1M0420K

Printed on: 04/03/2010 14:00:59

: SYSTEM DATA:

00.01: 00.02: 00.04: 00.05: 00.06: 00.08: 00.09: 00.0A: 00.0B: 00.0C: 00.0D: 00.0E: 00.10: 00.11: 00.20: 00.21: 00.22: 00.40: 00.50: 00.51: 00.52: 00.D0: 00.D1: 00.D2: 00.D3:

Language:English Password:**** Description:66kV PU_UGC w DZ Plant Reference: Model Number:P743211A1M0420K Serial Number:070707P Frequency:50 Hz Comms Level:2 Relay Address:7 Plant Status:0000000000000011 Control Status:0000000000000000 Active Group:1 CB Trip/Close:No Operation Software Ref. 1:D4.0beta4 Opto I/P Status:000000000000000000000000 Relay O/P Status:0000000010000000 Alarm Status 1:00000000010001110001000010000000 Relay O/P Status:0000000010000000 Alarm Status 1:00000000010001110001000010000000 Alarm Status 2:00000000000000000000000000000000 Alarm Status 3:00000000000000000000000000000000 Access Level:2 Password Control:2 Password Level 1:**** Password Level 2:****

: CB CONTROL: : DATE AND TIME: : CONFIGURATION:

09.01: 09.02: 09.03: 09.04: 09.05: 09.06: 09.07: 09.08: 09.09: 09.0A: 09.0F: 09.10: 09.12: 09.13: 09.14: 09.25: 09.26: 09.28: 09.29: 09.2A:

Restore Defaults:No Operation Setting Group:Select via Menu Active Settings:Group 1 Save Changes:No Operation Copy From:Group 1 Copy To:No Operation Setting Group 1:Enabled Setting Group 2:Disabled Setting Group 3:Disabled Setting Group 4:Disabled Dead Zone Prot:Enabled BB Trip Confirm:Disabled Overcurrent Prot:Disabled Earth Fault Prot:Disabled CB Fail & IDZ Current Set:1.200 A 31.02: I>DZ Time Delay:50.00 ms 31.03: Dead Zone Earth:Disabled : GROUP 1 CB FAIL: 45.01: Control By:I< 45.02: I< Current Set:100.0 mA 45.03: I> Status:Disabled 45.06: GROUP 1 Internal Trip: 45.07: CB Fail Timer 1:70.00 ms 45.08: CB Fail Timer 2:180.0 ms 45.09: GROUP 1 External Trip: 45.0A: CB Fail Timer 3:70.00 ms 45.0B: CB Fail Timer 4:180.0 ms : GROUP 1 SUPERVISION: : GROUP 1 INPUT LABELS: : GROUP 1 OUTPUT LABELS:

- Settings File Report -

Page 85 of 252

INPUTS

P743

Reset all indications CU->PU Signal 01 DDB #192

Non Latching

1

FnKey LED 1 Red DDB #656 FnKey LED 1 Grn DDB #657

Function Key 1 DDB #676

Green: Reset indication

Reset Indication DDB #135

Reset Trip Relays (if latched is enabled)

CU->PU Signal 02 DDB #193

Non Latching

1

Function Key 2 DDB #677

FnKey LED 2 Red DDB #658 FnKey LED 2 Grn DDB #659

Green: Reset Trip Latch

Reset Trip latch DDB #131

Isolator 1 L3 G1700 CLS POS DDB #066

Q1 Aux. (89a) DDB #105

Closed position

L2 G1700 OPN POS DDB #065

Q1 Aux. (89b) DDB #104

Open position

Cicruit breaker L7 G1702 CLS POS DDB #070

CB Aux. 3ph(52a) DDB #123

Closed position

L6 G1702 OPN POS DDB #069

CB Aux. 3ph(52b) DDB #124

Open position

External CB Failure Protection Integrated CB Failure Protection Ext. 3 ph Trip DDB #116

L1 50BF 3PH INT DDB #064

&

External 3phase Trip order

PU Overhaul mode DDB #307

Commissioning modes

50BF Disabled DDB #308

Non Latching

PU Overhaul mode DDB #307

Non Latching

L16 PU TEST MODE DDB #079 L12 50BF Y INT DDB #075 L11 50BF R INT DDB #074

1 &

FnKey LED 4 Red DDB #662 FnKey LED 4 Grn DDB #663

FnKey LED 5 Red DDB #664 FnKey LED 5 Grn DDB #665

Overhaul Mode DDB #312

Mode 50BF Disabled: - Local trip disabled - 50BF disabled - No backtrip - 87BB in service on this PU

Mode Overhaul: - PU 87BB protection in Overhaul mode - Position of isolator and CB are forced - Mode used to test local protection - Local trip enabled - No backtrip

Page 86 of 252

1/4

P743

Isolator 1 L3 G1700 CLS POS DDB #066

Status Alarm

&

L2 G1700 OPN POS DDB #065 L3 G1700 CLS POS DDB #066 L2 G1700 OPN POS DDB #065

5000

1

Q1 Status Alarm DDB #321

Pick-Up 0

1

Red: Closed Yellow: Status Alarm Green: Open

Q1 Closed DDB #320

1

Q1 Closed DDB #320

Non Latching

LED 1 Red DDB #640 LED 1 Grn DDB #641

1

Saturation ph A DDB #232 Saturation ph B DDB #233 Saturation ph C DDB #234 CT Fail IN DDB #255 All Prot Blocked DDB #270

1

PU->CU Signal 08 DDB #151

PU Overhaul mode DDB #307 50BF Disabled DDB #308 Q1 Status Forced DDB #336 Q2 Status Forced DDB #337 CB Status Forced DDB #342

Fault recorder Dead Zone Fault DDB #261 Any Trip DDB #358

20

1

Fault_REC_TRIG DDB #468

Dwell 0

Page 87 of 252

2/4

LEFT-HAND LEDS

P743

CIRCUIT BREAKER CB Closed DDB #332

1

CB Status Alarm DDB #352

Non Latching

1

CB Closed DDB #332

LED 3 Red DDB #644 LED 3 Grn DDB #645

Red: Closed Yellow: Status Alarm Green: Open

Trip information Dead Zone Fault DDB #261

Internal Trip DDB #256

Latching

&

Trip 87BB DDB #257

L1 50BF 3PH INT DDB #064

Internal Trip DDB #256 Trip 50BF (CU) DDB #259

Fibre Com Error DDB #252 Fibre Com Worn DDB #253 Fibre Com Error DDB #252 Fibre Com Worn DDB #253

Latching

Latching

&

1

Latching

Non Latching

LED 4 Red DDB #646

Red: Dead Zone Fault

LED 4 Grn DDB #647

LED 5 Red DDB #648 LED 5 Grn DDB #649

LED 6 Red DDB #650 LED 6 Grn DDB #651

LED 7 Red DDB #652 LED 7 Grn DDB #653

LED 8 Red DDB #654 LED 8 Grn DDB #655

Red: Trip on 87BB CU trip order

Red: Ext. 50BF Initation 3phase or 1phase

Red: Trip on 50BF CU backtrip order

Fibre com Red: Error Yellow: Change Green: Healthy

1

Page 88 of 252

3/4

OUTPUT RELAYS

P743

100 RL01 TRIP TRC1-R DDB #000

Dwell 0

Internal Trip DDB #256 Trip 87BB DDB #257 Internal Trip DDB #256

0

&

0 100

&

1

Trip 50BF (CU) DDB #259

Int. Retrip 3 ph DDB #171

RL02 TRIP TRC1-Y DDB #001

Pick-Up

RL03 TRIP TRC1-B DDB #002

Dwell 0

&

Dead Zone Fault DDB #261

&

PU Overhaul mode DDB #307

0

1

RL12 TRIP 50BF 1 DDB #011

Pick-Up 0

0 RL11 TRIP 87BB DDB #010

Pick-Up 0 Internal Trip DDB #256

&

Trip 87BB DDB #257

0

1

RL04 87BB+50BF 2 DDB #003

Pick-Up 0 0

Internal Trip DDB #256

RL05 87BB+50BF 2 DDB #004

Pick-Up

&

0

Trip 50BF (CU) DDB #259

0 RL13 TRIP 50BF 2 DDB #012

Pick-Up 0 0

1

RL14 87BB+50BF 2 DDB #013

Pick-Up 0

Page 89 of 252

4/4

B11, B21 Funct 87NH

Page 90 of 252

MiCOM S1 Studio

Page: 1

Settings File Report File: B11-87NH.set Model Number: P141216A6M0420J

Printed on: 11/05/2010 18:47:20

: SYSTEM DATA:

00.01: 00.02: 00.03: 00.04: 00.05: 00.06: 00.08: 00.09: 00.0A: 00.0B: 00.0C: 00.0D: 00.0E: 00.10: 00.11: 00.20: 00.21: 00.22: 00.30: 00.40: 00.50: 00.51: 00.52: 00.D0: 00.D1: 00.D2: 00.D3:

Language:English Password:**** Sys Fn Links:0 Description:DID/B11-87NH Plant Reference:DID S/S Model Number:P141216A6M0420J Serial Number:3277101 Frequency:50 Hz Comms Level:2 Relay Address:1 Plant Status:0000000000000000 Control Status:0000000000000000 Active Group:1 CB Trip/Close:No Operation Software Ref. 1:P141____6__420_B Opto I/P Status:10000000 Relay O/P Status:0000000 Alarm Status 1:00000000000000000000000000000000 Opto I/P Status:10000000 Relay O/P Status:0000000 Alarm Status 1:00000000000000000000000000000000 Alarm Status 2:00000000000000000000000000000000 Alarm Status 3:00000000000000000000000000000000 Access Level:2 Password Control:2 Password Level 1:**** Password Level 2:****

: CB CONTROL: : DATE AND TIME: : CONFIGURATION:

09.01: 09.02: 09.03: 09.04: 09.05: 09.06: 09.07: 09.08: 09.09: 09.0A: 09.0B: 09.10: 09.11: 09.12: 09.13: 09.14: 09.15: 09.16:

Restore Defaults:No Operation Setting Group:Select via Menu Active Settings:Group 1 Save Changes:No Operation Copy From:Group 1 Copy To:No Operation Setting Group 1:Enabled Setting Group 2:Disabled Setting Group 3:Disabled Setting Group 4:Disabled System Config:Invisible Overcurrent:Disabled Neg Sequence O/C:Disabled Broken Conductor:Disabled Earth Fault 1:Disabled Earth Fault 2:Disabled SEF/REF Prot'n:Enabled Residual O/V NVD:Disabled

- Settings File Report -

Page 91 of 252

MiCOM S1 Studio

Page: 2

Settings File Report File: B11-87NH.set Model Number: P141216A6M0420J 09.17: 09.18: 09.19: 09.1A: 09.1B: 09.1D: 09.1E: 09.1F: 09.20: 09.21: 09.22: 09.25: 09.26: 09.28: 09.29: 09.2A: 09.2B: 09.2C: 09.2D: 09.2E: 09.2F: 09.35: 09.36: 09.39: 09.FF:

Printed on: 11/05/2010 18:47:20

Thermal Overload:Disabled Neg Sequence O/V:Disabled Cold Load Pickup:Disabled Selective Logic:Disabled Admit Protection:Disabled Volt Protection:Disabled Freq Protection:Disabled df/dt Protection:Disabled CB Fail:Disabled Supervision:Disabled Fault Locator:Disabled Input Labels:Visible Output Labels:Visible CT & VT Ratios:Visible Record Control:Invisible Disturb Recorder:Visible Measure't Setup:Visible Comms Settings:Visible Commission Tests:Visible Setting Values:Secondary Control Inputs:Invisible Ctrl I/P Config:Invisible Ctrl I/P Labels:Invisible Direct Access:Enabled LCD Contrast:11

: CT AND VT RATIOS:

0A.01: 0A.02: 0A.07: 0A.08: 0A.09: 0A.0A: 0A.0B: 0A.0C: : : : : :

Main VT Primary:66.00 kV Main VT Sec'y:110.0 V Phase CT Primary:400.0 A Phase CT Sec'y:1.000 A E/F CT Primary:400.0 A E/F CT Secondary:1.000 A SEF CT Primary:400.0 A SEF CT Secondary:1.000 A

DISTURB RECORDER: MEASURE'T SETUP: COMMISSION TESTS: CB MONITOR SETUP: OPTO CONFIG:

11.01: Global Nominal V:110/125V 11.50: Opto Filter Cntl:11111111 11.80: Characteristic:Standard 60%-80% : IED CONFIGURATOR: : Group 1:

: GROUP 1 SEF/REF PROT'N: 3A.01: SEF/REF Options:Hi Z REF 3A.60: RESTRICTED E/F: 3A.65: IREF> Is:170.0 mA : GROUP 1 CB FAIL & I Trip DDB #273

LED 1 DDB #064

Latching

Output Relay Mappings

0 R1 REF TRIP -LV DDB #000

Straight 0 0

R2 REF TRIP SPAR DDB #001

Straight 0 IREF> Trip DDB #273

0 R4 REF TRIP INTS DDB #003

Straight 0 0

R6 REF TRIP-LVAC DDB #005

Straight 0 0

R7 REF TRIP-FIRE DDB #006

Straight 0 0

R5 REF TRIP SPAR DDB #004

Pick-Up 0

Page 94 of 252

50 IREF> Trip DDB #273

Fault REC TRIG DDB #144

Dwell 0

IREF> Trip DDB #273

Any Start DDB #294

Trip Command In DDB #536

0 R3 NOT USED DDB #002

Pick-Up 0

Page 95 of 252

A18, A28 Funct 87NL

Page 96 of 252

MiCOM S1 Studio

Page: 1

Settings File Report File: 87NL.set Model Number: P141216A6M0420J

Printed on: 11/05/2010 18:50:14

: SYSTEM DATA:

00.01: 00.02: 00.03: 00.04: 00.05: 00.06: 00.08: 00.09: 00.0A: 00.0B: 00.0C: 00.0D: 00.0E: 00.10: 00.11: 00.20: 00.21: 00.22: 00.30: 00.40: 00.50: 00.51: 00.52: 00.D0: 00.D1: 00.D2: 00.D3:

Language:English Password:**** Sys Fn Links:0 Description:A18-87NL Plant Reference:DID/A18/87NL Model Number:P141216A6M0420J Serial Number:3251112 Frequency:50 Hz Comms Level:2 Relay Address:1 Plant Status:0000000000000000 Control Status:0000000000000000 Active Group:1 CB Trip/Close:No Operation Software Ref. 1:P141____6__420_B Opto I/P Status:10000000 Relay O/P Status:0000000 Alarm Status 1:00000000000000000000000000000000 Opto I/P Status:10000000 Relay O/P Status:0000000 Alarm Status 1:00000000000000000000000000000000 Alarm Status 2:00000000000000000000000000000000 Alarm Status 3:00000000000000000000000000000000 Access Level:2 Password Control:2 Password Level 1:**** Password Level 2:****

: CB CONTROL: : DATE AND TIME: : CONFIGURATION:

09.01: 09.02: 09.03: 09.04: 09.05: 09.06: 09.07: 09.08: 09.09: 09.0A: 09.0B: 09.10: 09.11: 09.12: 09.13: 09.14: 09.15: 09.16:

Restore Defaults:No Operation Setting Group:Select via Menu Active Settings:Group 1 Save Changes:No Operation Copy From:Group 1 Copy To:No Operation Setting Group 1:Enabled Setting Group 2:Disabled Setting Group 3:Disabled Setting Group 4:Disabled System Config:Invisible Overcurrent:Disabled Neg Sequence O/C:Disabled Broken Conductor:Disabled Earth Fault 1:Disabled Earth Fault 2:Disabled SEF/REF Prot'n:Enabled Residual O/V NVD:Disabled

- Settings File Report -

Page 97 of 252

MiCOM S1 Studio

Page: 2

Settings File Report File: 87NL.set Model Number: P141216A6M0420J 09.17: 09.18: 09.19: 09.1A: 09.1B: 09.1D: 09.1E: 09.1F: 09.20: 09.21: 09.22: 09.25: 09.26: 09.28: 09.29: 09.2A: 09.2B: 09.2C: 09.2D: 09.2E: 09.2F: 09.35: 09.36: 09.39: 09.FF:

Printed on: 11/05/2010 18:50:14

Thermal Overload:Disabled Neg Sequence O/V:Disabled Cold Load Pickup:Disabled Selective Logic:Disabled Admit Protection:Disabled Volt Protection:Disabled Freq Protection:Disabled df/dt Protection:Disabled CB Fail:Disabled Supervision:Disabled Fault Locator:Disabled Input Labels:Visible Output Labels:Visible CT & VT Ratios:Visible Record Control:Invisible Disturb Recorder:Visible Measure't Setup:Visible Comms Settings:Invisible Commission Tests:Visible Setting Values:Secondary Control Inputs:Invisible Ctrl I/P Config:Invisible Ctrl I/P Labels:Invisible Direct Access:Enabled LCD Contrast:9

: CT AND VT RATIOS:

0A.01: 0A.02: 0A.07: 0A.08: 0A.09: 0A.0A: 0A.0B: 0A.0C: : : : : :

Main VT Primary:11.00 kV Main VT Sec'y:110.0 V Phase CT Primary:2500 A Phase CT Sec'y:1.000 A E/F CT Primary:2500 A E/F CT Secondary:1.000 A SEF CT Primary:2500 A SEF CT Secondary:1.000 A

DISTURB RECORDER: MEASURE'T SETUP: COMMISSION TESTS: CB MONITOR SETUP: OPTO CONFIG:

11.01: Global Nominal V:110/125V 11.50: Opto Filter Cntl:11111111 11.80: Characteristic:Standard 60%-80% : IED CONFIGURATOR: : Group 1:

: GROUP 1 SEF/REF PROT'N: 3A.01: SEF/REF Options:Hi Z REF 3A.60: RESTRICTED E/F: 3A.65: IREF> Is:80.00 mA : GROUP 1 CB FAIL & I Trip DDB #273

LED 1 DDB #064

Latching

SR User Alarm 1 DDB #167

1

IREF> Trip DDB #273

SR User Alarm 2 DDB #168

Output Relay Mappings 100 R2 HV REM INTS DDB #001

Dwell 0 100

R3 TO FIRE PROT DDB #002

Dwell 0 IREF> Trip DDB #273

1

100 R4 REF 86 TRIP DDB #003

Dwell 0 100

R7TRIP 415V LVAC DDB #006

Dwell 0 100

R5 SPARE DDB #004

Dwell 0 100

R6 SPARE DDB #005

Dwell 0

Fault Record Trigger Mapping 50 IREF> Trip DDB #273

Fault REC TRIG DDB #144

Dwell 0

Trip Output Mapping Note: DDB SignalsTrip Command In and Trip Command Out are joined together in the fixed scheme logic

IREF> Trip DDB #273

Trip Command In DDB #536

Page 100 of 252

A18, A28 Funct ET 87NHE

Page 101 of 252

MiCOM S1 Studio

Page: 1

Settings File Report File: 87NHE.set Model Number: P141216A6M0420J

Printed on: 11/05/2010 18:53:14

: SYSTEM DATA:

00.01: 00.02: 00.03: 00.04: 00.05: 00.06: 00.08: 00.09: 00.0A: 00.0B: 00.0C: 00.0D: 00.0E: 00.10: 00.11: 00.20: 00.21: 00.22: 00.30: 00.40: 00.50: 00.51: 00.52: 00.D0: 00.D1: 00.D2: 00.D3:

Language:English Password:**** Sys Fn Links:0 Description:P141-87NHE Plant Reference:DID/A18/87NHE Model Number:P141216A6M0420J Serial Number:3272476 Frequency:50 Hz Comms Level:2 Relay Address:1 Plant Status:0000000000000000 Control Status:0000000000000000 Active Group:1 CB Trip/Close:No Operation Software Ref. 1:P141____6__420_B Opto I/P Status:10000000 Relay O/P Status:0000000 Alarm Status 1:00000000000000000000000000000000 Opto I/P Status:10000000 Relay O/P Status:0000000 Alarm Status 1:00000000000000000000000000000000 Alarm Status 2:00000000000000000000000000000000 Alarm Status 3:00000000000000000000000000000000 Access Level:2 Password Control:2 Password Level 1:**** Password Level 2:****

: CB CONTROL: : DATE AND TIME: : CONFIGURATION:

09.01: 09.02: 09.03: 09.04: 09.05: 09.06: 09.07: 09.08: 09.09: 09.0A: 09.0B: 09.10: 09.11: 09.12: 09.13: 09.14: 09.15: 09.16:

Restore Defaults:No Operation Setting Group:Select via Menu Active Settings:Group 1 Save Changes:No Operation Copy From:Group 1 Copy To:No Operation Setting Group 1:Enabled Setting Group 2:Disabled Setting Group 3:Disabled Setting Group 4:Disabled System Config:Invisible Overcurrent:Disabled Neg Sequence O/C:Disabled Broken Conductor:Disabled Earth Fault 1:Disabled Earth Fault 2:Disabled SEF/REF Prot'n:Enabled Residual O/V NVD:Disabled

- Settings File Report -

Page 102 of 252

MiCOM S1 Studio

Page: 2

Settings File Report File: 87NHE.set Model Number: P141216A6M0420J 09.17: 09.18: 09.19: 09.1A: 09.1B: 09.1D: 09.1E: 09.1F: 09.20: 09.21: 09.22: 09.25: 09.26: 09.28: 09.29: 09.2A: 09.2B: 09.2C: 09.2D: 09.2E: 09.2F: 09.35: 09.36: 09.39: 09.FF:

Printed on: 11/05/2010 18:53:14

Thermal Overload:Disabled Neg Sequence O/V:Disabled Cold Load Pickup:Disabled Selective Logic:Disabled Admit Protection:Disabled Volt Protection:Disabled Freq Protection:Disabled df/dt Protection:Disabled CB Fail:Disabled Supervision:Disabled Fault Locator:Disabled Input Labels:Visible Output Labels:Visible CT & VT Ratios:Visible Record Control:Invisible Disturb Recorder:Visible Measure't Setup:Visible Comms Settings:Invisible Commission Tests:Visible Setting Values:Secondary Control Inputs:Invisible Ctrl I/P Config:Invisible Ctrl I/P Labels:Invisible Direct Access:Enabled LCD Contrast:9

: CT AND VT RATIOS:

0A.01: 0A.02: 0A.07: 0A.08: 0A.09: 0A.0A: 0A.0B: 0A.0C: : : : : :

Main VT Primary:11.00 kV Main VT Sec'y:110.0 V Phase CT Primary:50.00 A Phase CT Sec'y:1.000 A E/F CT Primary:50.00 A E/F CT Secondary:1.000 A SEF CT Primary:50.00 A SEF CT Secondary:1.000 A

DISTURB RECORDER: MEASURE'T SETUP: COMMISSION TESTS: CB MONITOR SETUP: OPTO CONFIG:

11.01: Global Nominal V:110/125V 11.50: Opto Filter Cntl:11111111 11.80: Characteristic:Standard 60%-80% : IED CONFIGURATOR: : Group 1:

: GROUP 1 SEF/REF PROT'N: 3A.01: SEF/REF Options:Hi Z REF 3A.60: RESTRICTED E/F: 3A.65: IREF> Is:300.0 mA : GROUP 1 CB FAIL & I Trip DDB #273

LED 1 DDB #064

Latching

Output Relay Mappings

100 R2HV REM IT.SEND DDB #001

Dwell 0 100

R3 TO TRIP 415V DDB #002

Dwell 0 IREF> Trip DDB #273

1

100 R4 REF 86 TRIP DDB #003

Dwell 0 100

R5 REF TRIP SPAR DDB #004

Dwell 0 100

R6 REF TRIP SPAR DDB #005

Dwell 0

Fault Record Trigger Mapping 50 IREF> Trip DDB #273

Fault REC TRIG DDB #144

Dwell 0

Trip Output Mapping

Note: DDB SignalsTrip Command In and Trip Command Out are joined together in the fixed scheme logic

IREF> Trip DDB #273

Trip Command In DDB #536

Page 105 of 252

A18, A28 Funct ET 87NLE

Page 106 of 252

MiCOM S1 Studio

Page: 1

Settings File Report File: 87NLE.set Model Number: P141216A6M0420J

Printed on: 11/05/2010 18:55:35

: SYSTEM DATA:

00.01: 00.02: 00.03: 00.04: 00.05: 00.06: 00.08: 00.09: 00.0A: 00.0B: 00.0C: 00.0D: 00.0E: 00.10: 00.11: 00.20: 00.21: 00.22: 00.30: 00.40: 00.50: 00.51: 00.52: 00.D0: 00.D1: 00.D2: 00.D3:

Language:English Password:**** Sys Fn Links:0 Description:A18/87NLE Plant Reference:DID/A18/87NLE Model Number:P141216A6M0420J Serial Number:3288750 Frequency:50 Hz Comms Level:2 Relay Address:1 Plant Status:0000000000000000 Control Status:0000000000000000 Active Group:1 CB Trip/Close:No Operation Software Ref. 1:P141____6__420_B Opto I/P Status:10000000 Relay O/P Status:0000000 Alarm Status 1:00000000000000000000000000000000 Opto I/P Status:10000000 Relay O/P Status:0000000 Alarm Status 1:00000000000000000000000000000000 Alarm Status 2:00000000000000000000000000000000 Alarm Status 3:00000000000000000000000000000000 Access Level:2 Password Control:2 Password Level 1:**** Password Level 2:****

: CB CONTROL: : DATE AND TIME: : CONFIGURATION:

09.01: 09.02: 09.03: 09.04: 09.05: 09.06: 09.07: 09.08: 09.09: 09.0A: 09.0B: 09.10: 09.11: 09.12: 09.13: 09.14: 09.15: 09.16:

Restore Defaults:No Operation Setting Group:Select via Menu Active Settings:Group 1 Save Changes:No Operation Copy From:Group 1 Copy To:No Operation Setting Group 1:Enabled Setting Group 2:Disabled Setting Group 3:Disabled Setting Group 4:Disabled System Config:Invisible Overcurrent:Disabled Neg Sequence O/C:Disabled Broken Conductor:Disabled Earth Fault 1:Disabled Earth Fault 2:Disabled SEF/REF Prot'n:Enabled Residual O/V NVD:Disabled

- Settings File Report -

Page 107 of 252

MiCOM S1 Studio

Page: 2

Settings File Report File: 87NLE.set Model Number: P141216A6M0420J 09.17: 09.18: 09.19: 09.1A: 09.1B: 09.1D: 09.1E: 09.1F: 09.20: 09.21: 09.22: 09.25: 09.26: 09.28: 09.29: 09.2A: 09.2B: 09.2C: 09.2D: 09.2E: 09.2F: 09.35: 09.36: 09.39: 09.FF:

Printed on: 11/05/2010 18:55:35

Thermal Overload:Disabled Neg Sequence O/V:Disabled Cold Load Pickup:Disabled Selective Logic:Disabled Admit Protection:Disabled Volt Protection:Disabled Freq Protection:Disabled df/dt Protection:Disabled CB Fail:Disabled Supervision:Disabled Fault Locator:Disabled Input Labels:Visible Output Labels:Visible CT & VT Ratios:Visible Record Control:Invisible Disturb Recorder:Visible Measure't Setup:Visible Comms Settings:Visible Commission Tests:Visible Setting Values:Secondary Control Inputs:Invisible Ctrl I/P Config:Invisible Ctrl I/P Labels:Invisible Direct Access:Enabled LCD Contrast:9

: CT AND VT RATIOS:

0A.01: 0A.02: 0A.07: 0A.08: 0A.09: 0A.0A: 0A.0B: 0A.0C: : : : : :

Main VT Primary:11.00 kV Main VT Sec'y:110.0 V Phase CT Primary:750.0 A Phase CT Sec'y:1.000 A E/F CT Primary:750.0 A E/F CT Secondary:1.000 A SEF CT Primary:750.0 A SEF CT Secondary:1.000 A

DISTURB RECORDER: MEASURE'T SETUP: COMMISSION TESTS: CB MONITOR SETUP: OPTO CONFIG:

11.01: Global Nominal V:110/125V 11.50: Opto Filter Cntl:11111111 11.80: Characteristic:Standard 60%-80% : IED CONFIGURATOR: : Group 1:

: GROUP 1 SEF/REF PROT'N: 3A.01: SEF/REF Options:Hi Z REF 3A.60: RESTRICTED E/F: 3A.65: IREF> Is:320.0 mA : GROUP 1 CB FAIL & I Trip DDB #273

LED 1 DDB #064

Latching

L1 SPARE-1 DDB #032

Reset Relays/LED DDB #235

Output Relay Mappings 0 R2 TRIP TO 415V DDB #001

Pick-Up 0 0

R3HV REM.IT.SEND DDB #002

Pick-Up 0 IREF> Trip DDB #273

0

1

R4 REF 86 TRIP DDB #003

Pick-Up 0 0

R5 REF TRIP SPAR DDB #004

Pick-Up 0 0

R6 REF TRIP SPAR DDB #005

Pick-Up 0

Fault Record Trigger Mapping 50

IREF> Trip DDB #273

1

Fault REC TRIG DDB #144

Dwell 0

Trip Output Mapping

Note: DDB SignalsTrip Command In and Trip Command Out are joined together in the fixed scheme logic

IREF> Trip DDB #273

Trip Command In DDB #536

Page 110 of 252

A

B10, B20 Funct 87, 21, 49

Page 111 of 252

MiCOM S1 Studio

Page: 1

Settings File Report File: =B10 Funct 87C, 21C,51C,49C.set Model Number: P545216C6M0540K

Printed on: 02/08/2010 15:22:03

: SYSTEM DATA:

00.01: 00.02: 00.03: 00.04: 00.05: 00.06: 00.08: 00.09: 00.0A: 00.0B: 00.0C: 00.0D: 00.0E: 00.10: 00.11: 00.20: 00.21: 00.22: 00.50: 00.51: 00.52: 00.D0: 00.D1: 00.D2: 00.D3:

Language:English Password:**** Sys Fn Links:0 Description:B10_87_21_49 Plant Reference:DID Model Number:P545216C6M0540K Serial Number:12345 Frequency:50 Hz Comms Level:2 Relay Address:1 Plant Status:0000000000000010 Control Status:0000000000000000 Active Group:1 CB Trip/Close:No Operation Software Ref. 1:P545____4__540_A Opto I/P Status:000000000000000000000000 Relay O/P Status:00000000000000000000000000001010 Alarm Status 1:00000010100000000000000000000000 Alarm Status 1:00000010100000000000000000000000 Alarm Status 2:00000000000000000000000000000000 Alarm Status 3:00000000000000000000000000000000 Access Level:2 Password Control:2 Password Level 1:**** Password Level 2:****

: CB CONTROL: : DATE AND TIME: : CONFIGURATION:

09.01: 09.02: 09.03: 09.04: 09.05: 09.06: 09.07: 09.08: 09.09: 09.0A: 09.0B: 09.0C: 09.0F: 09.10: 09.11: 09.12: 09.13: 09.15: 09.16: 09.17:

Restore Defaults:No Operation Setting Group:Select via Menu Active Settings:Group 1 Save Changes:No Operation Copy From:Group 1 Copy To:No Operation Setting Group 1:Enabled Setting Group 2:Disabled Setting Group 3:Disabled Setting Group 4:Disabled Distance:Enabled Directional E/F:Disabled Phase Diff:Enabled Overcurrent:Enabled Neg Sequence O/C:Disabled Broken Conductor:Disabled Earth Fault:Disabled Sensitive E/F:Disabled Residual O/V NVD:Disabled Thermal Overload:Enabled

- Settings File Report -

Page 112 of 252

MiCOM S1 Studio

Page: 2

Settings File Report File: =B10 Funct 87C, 21C,51C,49C.set Model Number: P545216C6M0540K 09.18: 09.1D: 09.1E: 09.1F: 09.20: 09.21: 09.23: 09.24: 09.25: 09.26: 09.28: 09.29: 09.2A: 09.2B: 09.2C: 09.2D: 09.2E: 09.2F: 09.35: 09.36: 09.39: 09.50: 09.FF:

Printed on: 02/08/2010 15:22:03

PowerSwing Block:Enabled Volt Protection:Disabled Freq Protection:Disabled df/dt Protection:Disabled CB Fail:Disabled Supervision:Enabled System Checks:Disabled Auto-Reclose:Disabled Input Labels:Visible Output Labels:Visible CT & VT Ratios:Visible Record Control:Visible Disturb Recorder:Visible Measure't Setup:Visible Comms Settings:Visible Commission Tests:Visible Setting Values:Secondary Control Inputs:Visible Ctrl I/P Config:Visible Ctrl I/P Labels:Visible Direct Access:Enabled Function Key:Visible LCD Contrast:11

: CT AND VT RATIOS:

0A.01: 0A.02: 0A.03: 0A.04: 0A.07: 0A.08: 0A.0B: 0A.0C: 0A.0D: 0A.0E: 0A.0F: 0A.10: 0A.11: 0A.13: 0A.14: 0A.18:

Main VT Primary:66.00 kV Main VT Sec'y:110.0 V C/S VT Primary:66.00 kV C/S VT Secondary:110.0 V Phase CT Primary:800.0 A Phase CT Sec'y:1.000 A SEF CT Primary:800.0 A SEF CT Secondary:1.000 A MComp CT Primary:800.0 A MComp CT Sec'y:1.000 A C/S Input:A-N Main VT Location:Line CT Polarity:Standard SEF CT Polarity:Standard M CT Polarity:Standard VT Connected:Yes

: RECORD CONTROL: : DISTURB RECORDER:

0C.01: 0C.02: 0C.03: 0C.04: 0C.05: 0C.06: 0C.07:

Duration:2.000 s Trigger Position:33.30% Trigger Mode:Single Analog Channel 1:VA Analog Channel 2:VB Analog Channel 3:VC Analog Channel 4:IA

- Settings File Report -

Page 113 of 252

MiCOM S1 Studio

Page: 3

Settings File Report File: =B10 Funct 87C, 21C,51C,49C.set Model Number: P545216C6M0540K 0C.08: 0C.09: 0C.0A: 0C.0B: 0C.0C: 0C.0D: 0C.0E: 0C.0F: 0C.10: 0C.11: 0C.12: 0C.13: 0C.14: 0C.15: 0C.16: 0C.17: 0C.18: 0C.19: 0C.1A: 0C.1B: 0C.1C: 0C.1D: 0C.1E: 0C.1F: 0C.20: 0C.21: 0C.22: 0C.23: 0C.24: 0C.25: 0C.26: 0C.27: 0C.28: 0C.29: 0C.2A: 0C.2B: 0C.2C: 0C.2D: 0C.2E: 0C.2F: 0C.30: 0C.31: 0C.32: 0C.33: 0C.34: 0C.35: 0C.36: 0C.37: 0C.38:

Printed on: 02/08/2010 15:22:03

Analog Channel 5:IB Analog Channel 6:IC Analog Channel 7:IN Analog Channel 8:IN Sensitive Digital Input 1:Diff Trip Input 1 Trigger:No Trigger Digital Input 2:I>1 Trip Input 2 Trigger:No Trigger Digital Input 3:Relay 3 Input 3 Trigger:Trigger L/H Digital Input 4:Zone 1 Trip Input 4 Trigger:No Trigger Digital Input 5:Zone 2 Trip Input 5 Trigger:No Trigger Digital Input 6:Zone 3 Trip Input 6 Trigger:No Trigger Digital Input 7:Trip Output A Input 7 Trigger:No Trigger Digital Input 8:Trip Output B Input 8 Trigger:No Trigger Digital Input 9:Trip Output C Input 9 Trigger:No Trigger Digital Input 10:Thermal Trip Input 10 Trigger:No Trigger Digital Input 11:Thermal Alarm Input 11 Trigger:No Trigger Digital Input 12:Relay 12 Input 12 Trigger:No Trigger Digital Input 13:Relay 13 Input 13 Trigger:No Trigger Digital Input 14:Relay 14 Input 14 Trigger:No Trigger Digital Input 15:Relay 15 Input 15 Trigger:No Trigger Digital Input 16:Relay 16 Input 16 Trigger:No Trigger Digital Input 17:Opto 1 Input 17 Trigger:No Trigger Digital Input 18:Opto 2 Input 18 Trigger:No Trigger Digital Input 19:Opto 3 Input 19 Trigger:No Trigger Digital Input 20:Opto 4 Input 20 Trigger:No Trigger Digital Input 21:Opto 5 Input 21 Trigger:No Trigger Digital Input 22:Opto 6 Input 22 Trigger:No Trigger Digital Input 23:Opto 7

- Settings File Report -

Page 114 of 252

MiCOM S1 Studio

Page: 4

Settings File Report File: =B10 Funct 87C, 21C,51C,49C.set Model Number: P545216C6M0540K 0C.39: 0C.3A: 0C.3B: 0C.3C: 0C.3D: 0C.3E: 0C.3F: 0C.40: 0C.41: 0C.42: 0C.43: 0C.44: 0C.45: 0C.46: 0C.47: 0C.48: 0C.49: 0C.4A: 0C.4B: 0C.50: 0C.51: 0C.52: 0C.53:

Printed on: 02/08/2010 15:22:03

Input 23 Trigger:No Trigger Digital Input 24:Opto 8 Input 24 Trigger:No Trigger Digital Input 25:Opto 9 Input 25 Trigger:No Trigger Digital Input 26:Opto 10 Input 26 Trigger:No Trigger Digital Input 27:Opto 11 Input 27 Trigger:No Trigger Digital Input 28:Opto 12 Input 28 Trigger:No Trigger Digital Input 29:Opto 13 Input 29 Trigger:No Trigger Digital Input 30:Opto 14 Input 30 Trigger:No Trigger Digital Input 31:Opto 15 Input 31 Trigger:No Trigger Digital Input 32:Opto 16 Input 32 Trigger:No Trigger Analog Channel 9:V Checksync Analog Channel10:IM Analog Channel11:IN Analog Channel12:IN

: MEASURE'T SETUP:

0D.01: 0D.02: 0D.03: 0D.04: 0D.05: 0D.06: 0D.07: 0D.08: 0D.09: 0D.0A:

Default Display:3Ph + N Current Local Values:Primary Remote Values:Primary Measurement Ref:VA Measurement Mode:0 Fix Dem Period:30.00 min Roll Sub Period:30.00 min Num Sub Periods:1 Distance Unit:Kilometres Fault Location:Distance

: COMMISSION TESTS: : CB MONITOR SETUP: : OPTO CONFIG:

11.01: Global Nominal V:110/125V 11.60: Opto Filter Cntl:111111111011011111111011 11.80: Characteristic:Standard 60%-80% : : : :

CONTROL INPUTS: CTRL I/P CONFIG: FUNCTION KEYS: PROT COMMS/ IM64:

20.01: 20.03: 20.10: 20.11: 20.12:

Scheme Setup:Dual Redundant Address:1-B Comms Mode:Standard Baud Rate Ch1:64kbits/s Baud Rate Ch2:64kbits/s

- Settings File Report -

Page 115 of 252

MiCOM S1 Studio

Page: 5

Settings File Report File: =B10 Funct 87C, 21C,51C,49C.set Model Number: P545216C6M0540K 20.13: 20.14: 20.17: 20.18: 20.19: 20.1A: 20.1B: 20.1F: 20.20: 20.21: 20.22: 20.30: 20.31: 20.32: 20.34: 20.35: 20.36: 20.38: 20.39: 20.3A: 20.3C: 20.3D: 20.3E: 20.40: 20.41: 20.42: 20.44: 20.45: 20.46: 20.48: 20.49: 20.4A: 20.4C: 20.4D: 20.4E:

Printed on: 02/08/2010 15:22:03

Clock Source Ch1:Internal Clock Source Ch2:Internal Comm Delay Tol:350.0 us Comm Fail Timer:10.00 s Comm Fail Mode:Ch 1 and 2 Fail GPS Sync:Disabled Char Mod Time:500.0 ms Alarm Level:25.00% Prop Delay Stats:Enabled MaxCh1 PropDelay:15.00 ms MaxCh2 PropDelay:15.00 ms IM1 Cmd Type:Permissive IM1 Fallbck Mode:Default IM1 Default Val:0 IM2 Cmd Type:Permissive IM2 Fallbck Mode:Default IM2 Default Val:0 IM3 Cmd Type:Permissive IM3 Fallbck Mode:Default IM3 Default Val:0 IM4 Cmd Type:Permissive IM4 Fallbck Mode:Default IM4 Default Val:0 IM5 Cmd Type:Permissive IM5 Fallbck Mode:Default IM5 Default Val:0 IM6 Cmd Type:Permissive IM6 Fallbck Mode:Default IM6 Default Val:0 IM7 Cmd Type:Permissive IM7 Fallbck Mode:Default IM7 Default Val:0 IM8 Cmd Type:Permissive IM8 Fallbck Mode:Default IM8 Default Val:0

: CTRL I/P LABELS: : Group 1:

: GROUP 1 LINE PARAMETERS: 30.01: Line Length:8250 8450 m 30.03: Line Impedance:1.200 1.700 Ohm 30.04: Line Angle:81.00 85.00 deg 260.0 30.05: kZN Res Comp:160.0e-3 -144.0 30.06: kZN Res Angle:-170.0 deg 30.07: Mutual Comp:Disabled 30.0B: Phase Sequence:Standard ABC 30.0C: Tripping Mode:3 Pole 30.10: Line Charging Y:100.0 uS : GROUP 1 DISTANCE SETUP: 31.0C: Setting Mode:Advanced

- Settings File Report -

Page 116 of 252

MiCOM S1 Studio

Page: 6

Settings File Report File: =B10 Funct 87C, 21C,51C,49C.set Model Number: P545216C6M0540K 31.10: 31.11: 31.20: 31.30: 31.40: 31.42: 31.50: 31.60: 31.70: 31.71: 31.80: 31.90: 31.A0: 31.A2: 31.B0: 31.C0: 31.D0: 31.D1: 31.D3: 31.D7: 31.E0: 31.E1: 31.E2: 31.E3:

Printed on: 02/08/2010 15:22:03

PHASE DISTANCE: Phase Chars.:Quad Zone 1 Ph Status:Enabled Ch Fail Zone 2 Ph Status:Enabled Zone 3 Ph Status:Enabled Zone 3 Ph Offset:Disabled Zone P Ph Status:Disabled Zone 4 Ph Status:Disabled GROUND DISTANCE: Ground Chars.:Quad Zone 1 Gnd Stat.:Enabled Ch Fail Zone 2 Gnd Stat.:Enabled Zone 3 Gnd Stat.:Enabled Zone3 Gnd Offset:Disabled Zone P Gnd Stat.:Disabled Zone 4 Gnd Stat.:Disabled Digital Filter:Standard CVT Filters:Disabled Load Blinders:Disabled Dist. Polarizing:1.000 DELTADIRECTIONAL: Dir. Status:Enabled AidedDeltaStatus:Disabled Dir. Char Angle:45.00 deg

: GROUP 1 DIST. ELEMENTS: 32.01: PHASE DISTANCE: 1.58 32.02: Z1 Ph. Reach:840.0 mOhm 32.03: Z1 Ph. Angle:81.00 85.00 deg 4.75 32.07: R1 Ph. Resistive:2.530 Ohm 32.08: Z1 Tilt Top Line:-3.000 deg 32.09: Z1 Sensit. Iph>1:75.00 mA 32.10: Z2 Ph. Reach:1.810 Ohm 2.94 32.11: Z2 Ph. Angle:81.00 85.00 deg 8.82 32.15: R2 Ph. Resistive:5.420 Ohm 32.16: Z2 Tilt Top Line:-3.000 deg 32.17: Z2 Sensit. Iph>2:75.00 mA 32.20: Z3 Ph. Reach:2.910 Ohm 4.52 85.00 deg 32.21: Z3 Ph. Angle:81.00 13.57 Ohm 32.25: R3 Ph. Res. Fwd.:8.730 32.27: Z3 Tilt Top Line:-3.000 deg 32.28: Z3 Sensit. Iph>3:50.00 mA 32.50: GROUND DISTANCE: 1.58 32.51: Z1 Gnd. Reach:840.0 mOhm 85.00 deg 32.52: Z1 Gnd. Angle:81.00 32.53: Z1 Dynamic Tilt:Enabled 32.54: Z1 Tilt Top Line:-3.000 deg 32.55: kZN1 Res. Comp.:160.0e-3 260.0 -144.0 deg 32.56: kZN1 Res. Angle:-170.0 7.12 32.59: R1 Gnd Resistive:3.790 Ohm

- Settings File Report -

Page 117 of 252

MiCOM S1 Studio

Page: 7

Settings File Report File: =B10 Funct 87C, 21C,51C,49C.set Model Number: P545216C6M0540K 32.5B: 32.60: 32.61: 32.63: 32.64: 32.65: 32.66: 32.69: 32.6B: 32.70: 32.71: 32.73: 32.74: 32.75: 32.76: 32.79: 32.7C:

Printed on: 02/08/2010 15:22:03

Z1 Sensit Ignd>1:75.00 mA Z2 Gnd. Reach:1.810 Ohm 2.94 Z2 Gnd. Angle:81.00 85.00 deg Z2 Dynamic Tilt:Enabled Z2 Tilt Top Line:-3.000 deg kZN2 Res. Comp.:160.0e-3 260.0 -144.0 deg kZN2 Res. Angle:-170.0 13.23 Ohm R2 Gnd Resistive:8.120 Z2 Sensit Ignd>2:75.00 mA Z3 Gnd. Reach:2.910 Ohm 4.52 Z3 Gnd. Angle:81.00 85.00 deg Z3 Dynamic Tilt:Enabled Z3 Tilt Top Line:-3.000 deg kZN3 Res. Comp.:160.0e-3 260.0 -144.0 deg kZN3 Res. Angle:-170.0 20.35 Ohm R3 Gnd. Res. Fwd:13.10 Z3 Sensit Ignd>3:50.00 mA

: GROUP 1 PHASE DIFF: 33.01: Phase Diff:Enabled 33.06: Phase Is1:200.0 mA 33.07: Phase Is2:2.000 A 33.08: Phase k1:30.00% 33.09: Phase k2:150.0% 33.0A: Phase Char:DT 33.0B: Phase Time Delay:0 s 33.0E: PIT Time:0 s 33.0F: Ph CT Corr'tion:1.000 33.10: Compensation:None 33.17: PIT I selection:Local : GROUP 1 SCHEME LOGIC: 34.01: BASIC SCHEME: 34.08: Zone1 Tripping:Phase And Ground 34.09: tZ1 Ph. Delay:0 s 34.0A: tZ1 Gnd. Delay:0 s 34.10: Zone2 Tripping:Phase And Ground 34.11: tZ2 Ph. Delay:400.0 ms 34.12: tZ2 Gnd. Delay:400.0 ms 34.18: Zone3 Tripping:Phase And Ground 34.19: tZ3 Ph. Delay:5.000 s 34.1A: tZ3 Gnd. Delay:5.000 s 34.20: ZoneP Tripping:Disabled 34.28: Zone4 Tripping:Disabled 34.40: AIDED SCHEME 1: 34.41: Aid. 1 Selection:Disabled 34.60: AIDED SCHEME 2: 34.61: Aid. 2 Selection:Disabled 34.80: Trip On Close: 34.81: SOTF Status:Enabled ExtPulse 34.83: SOTF Tripping:000011

- Settings File Report -

Page 118 of 252

MiCOM S1 Studio

Page: 8

Settings File Report File: =B10 Funct 87C, 21C,51C,49C.set Model Number: P545216C6M0540K 34.84: 34.86: 34.87: 34.88: 34.B0: 34.B1: 34.C0: 34.C1:

Printed on: 02/08/2010 15:22:03

TOR Status:Disabled TOC Reset Delay:500.0 ms SOTF Pulse:500.0 ms TOC Delay:200.0 ms Z1 Extension: Z1 Ext Scheme:Disabled Loss Of Load: LOL Scheme:Disabled

: GROUP 1 35.01: 35.02: 35.03: 35.04: 35.06: 35.09: 35.0A: 35.13: 35.18: 35.1C: 35.1D:

OVERCURRENT: I>1 Status:Enabled I>1 Function:IEC S Inverse I>1 Directional:Non-Directional I>1 Current Set:960.0 mA I>1 TMS:1.000 I>1 tRESET:0 s I>2 Status:Disabled I>3 Status:Disabled I>4 Status:Disabled I> Char Angle:30.00 deg I> Blocking:001111

: GROUP 1 3C.01: 3C.02: 3C.03: 3C.04:

THERMAL OVERLOAD: Characteristic:Single Thermal Trip:1.000 A Thermal Alarm:90.00% Time Constant 1:25.00 min

: GROUP 1 POWER SWING BLK.: 3D.01: PSB Status:Blocking 3D.03: Zone 1 Ph. PSB:Blocking 3D.05: Zone 2 Ph. PSB:Blocking 3D.07: Zone 3 Ph. PSB:Blocking 3D.09: Zone P Ph. PSB:Blocking 3D.0B: Zone 4 Ph. PSB:Blocking 3D.0D: Zone 1 Gnd. PSB:Blocking 3D.0F: Zone 2 Gnd. PSB:Blocking 3D.11: Zone 3 Gnd. PSB:Blocking 3D.13: Zone P Gnd. PSB:Blocking 3D.15: Zone 4 Gnd. PSB:Blocking 3D.20: PSB Unblocking:Disabled 3D.22: PSB Reset Delay:500.0 ms 3D.23: OST Mode:OST Disabled 3D.24: Z5:30.01 Ohm 3D.26: Z5':-29.97 Ohm 3D.28: R5:20.00 Ohm 3D.2A: R5':-20.00 Ohm 3D.2C: Blinder Angle:80.00 deg : GROUP 1 CB FAIL & P.DEAD: : GROUP 1 SUPERVISION: 46.01: VTS Mode:Measured + MCB 46.02: VTS Status:Blocking

- Settings File Report -

Page 119 of 252

MiCOM S1 Studio

Page: 9

Settings File Report File: =B10 Funct 87C, 21C,51C,49C.set Model Number: P545216C6M0540K 46.03: 46.04: 46.05: 46.06: 46.0E: 46.0F: 46.10: 46.11: 46.30: 46.31:

Printed on: 02/08/2010 15:22:03

VTS Reset Mode:Auto VTS Time Delay:5.000 s VTS I> Inhibit:27.06 19.70 A VTS I2> Inhibit:50.00 mA INRUSH DETECTION: I>2nd Harmonic:20.00% WEAK INFEED BLK: WI Inhibit:Disabled CT SUPERVISION: CTS Mode:Disabled

: GROUP 1 INPUT 4A.01: Opto 4A.02: Opto 4A.03: Opto 4A.04: Opto 4A.05: Opto 4A.06: Opto 4A.07: Opto 4A.08: Opto 4A.09: Opto 4A.0A: Opto 4A.0B: Opto 4A.0C: Opto 4A.0D: Opto 4A.0E: Opto 4A.0F: Opto 4A.10: Opto 4A.11: Opto 4A.12: Opto 4A.13: Opto 4A.14: Opto 4A.15: Opto 4A.16: Opto 4A.17: Opto 4A.18: Opto

LABELS: Input 1:Un used Input 2:CB Close Pulse Input 3:Un used Input 4:Un used Input 5:Dist Carrrier Rx Input 6:DEF Carrier Rx Input 7:Un used Input 8:Un used Input 9:ES G901 Open Input 10:ES G901 Close Input 11:CB G900 Open Input 12:CB G900 Close Input 13:Un used Input 14:Un used Input 15:Test Mode Input 16:Un used Input 17:Un used Input 18:Un used Input 19:Un used Input 20:Un used Input 21:LVT MCB Open Input 22:Un used Input 23:Un used Input 24:Un used

: GROUP 1 OUTPUT 4B.01: Relay 4B.02: Relay 4B.03: Relay 4B.04: Relay 4B.05: Relay 4B.06: Relay 4B.07: Relay 4B.08: Relay 4B.09: Relay 4B.0A: Relay 4B.0B: Relay 4B.0C: Relay 4B.0D: Relay

LABELS: 1:TO TRIP 86-1 2:INT TRIP RECEIVD 3:A-PH TRIP 4:VT FAIL 5:B-PH TRIP 6:C-PH TRIP 7:UN USED 8:UN USED 9:SPARE 10:SPARE 11:UN USED 12:INT TRIP SEND 13:UN USED

- Settings File Report -

Page 120 of 252

MiCOM S1 Studio

Page: 10

Settings File Report File: =B10 Funct 87C, 21C,51C,49C.set Model Number: P545216C6M0540K 4B.0E: 4B.0F: 4B.10: 4B.11: 4B.12: 4B.13: 4B.14: 4B.15: 4B.16: 4B.17: 4B.18: 4B.19: 4B.1A: 4B.1B: 4B.1C: 4B.1D: 4B.1E: 4B.1F: 4B.20:

Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay

Printed on: 02/08/2010 15:22:03

14:UN USED 15:UN USED 16:UN USED 17:A-PH TRIP 94-1R 18:B-PH TIRP 94-IY 19:C-PH TRIP 94-1B 20:UN USED 21:UN USED 22:UN USED 23:UN USED 24:UN USED 25:UN USED 26:UN USED 27:DIST OPTD 28:DEF OPTD 29:UN USED 30:UN USED 31:UN USED 32:UN USED

- Settings File Report -

Page 121 of 252

MiCOM P545 Programmable Logic Opto Input Mappings

IM64 Ch1 Output1 DDB #112

1

Input L1 DDB #032

IM64 Ch2 Output1 DDB #120 Set SOTF DDB #488

Input L2 DDB #033

1

Input L9 DDB #040

IM64 Ch1 Output2 DDB #113 IM64 Ch2 Output2 DDB #121

1

Input L10 DDB #041

IM64 Ch1 Output3 DDB #114 IM64 Ch2 Output3 DDB #122

1

Input L11 DDB #042

IM64 Ch1 Output4 DDB #115 IM64 Ch2 Output4 DDB #123 IM64 Ch1 Output5 DDB #116

1

Input L12 DDB #043

MCB/VTS DDB #438

Input L21 DDB #052

Input L24 DDB #055

IM64 Ch2 Output5 DDB #124

&

Test Mode DDB #459

Non Latching

Opto L5 & L16 can be found on other pages

FnKey LED1 Red DDB #1040 FnKey LED1 Grn DDB #1041

Page 1 Page 122 of 252

MiCOM P545 Programmable Logic Output Contacts Diff InterTrip DDB #586

0

Zone 1 Trip DDB #608

Output R1 DDB #000

Straight 0

Zone 2 Trip DDB #613

0

Zone 3 Trip DDB #618

Output R9 DDB #008

Straight

1

SOTF Trip Zone 1 DDB #709

0 0

SOTF Trip Zone 2 DDB #710

Output R10 DDB #009

Straight 0

SOTF Trip Zone 3 DDB #711

I>1 Trip DDB #655 Diff Trip DDB #582

0 IM64 Ch1 Input 1 DDB #096 IM64 Ch2 Input 1 DDB #104

Output R2 DDB #001

Straight 0

1

0 Output R11 DDB #010

Straight

Diff Trip A DDB #583

0

Diff InterTrip A DDB #587 Zone 1 A Trip DDB #609

0

1

I>1 Trip DDB #655

Output R3 DDB #002

Straight 0

SOTF Trip Zone 1 DDB #709 SOTF Trip Zone 2 DDB #710 SOTF Trip Zone 3 DDB #711

0

VTS Blk Distance DDB #1404

Output R4 DDB #003

Straight 0

Diff Trip B DDB #584 Diff InterTrip B DDB #588 Zone 1 B Trip DDB #610 IN>1 Trip DDB #671 IN>2 Trip DDB #672

0 Output R5 DDB #004

Straight

1

0

SOTF Trip Zone 1 DDB #709 SOTF Trip Zone 2 DDB #710 SOTF Trip Zone 3 DDB #711 Diff Trip C DDB #585 Diff InterTrip C DDB #589 Zone 1 C Trip DDB #611

0

I>1 Trip DDB #655

1

Output R6 DDB #005

Straight 0

SOTF Trip Zone 1 DDB #709 SOTF Trip Zone 2 DDB #710 SOTF Trip Zone 3 DDB #711

Page Page 123 of 252

2

MiCOM P545 Programmable Logic Output Contacts SG-opto Invalid DDB #288 Prot'n Disabled DDB #289 Static Test Mode DDB #290 Test Loopback DDB #291 Test IM64 DDB #292 VT Fail Alarm DDB #293 CT Fail Alarm DDB #294 Remote CT Alarm DDB #296 Power Swing DDB #297 CB Fail Alarm DDB #298 CB Monitor Alarm DDB #299 CB Lockout Alarm DDB #300 CB Status Alarm DDB #301 CB Trip Fail DDB #302 CB Close Fail DDB #303 Man CB Unhealthy DDB #304 No C/S Man Close DDB #305 A/R Lockout DDB #306 A/R CB Unhealthy DDB #307 A/R No Checksync DDB #308

1 General Alarm

System Split DDB #309 GPS Alarm DDB #310 Signalling Fail DDB #311

GENERAL ALARM IS NOT REQUIRED

Comm Delay Alarm DDB #312 C Diff Failure DDB #313 IM64 SchemeFail DDB #314 IEEE C37.94 Fail DDB #315 Aid 1 Chan Fail DDB #317 Aid 2 Chan Fail DDB #318 F out of Range DDB #319 Incompatible Rly DDB #332 InValid Mesg Fmt DDB #333 Main Prot. Fail DDB #334 Config Error DDB #335 Re-Config Error DDB #336 Comms Changed DDB #337 Battery Fail DDB #352 Field Volts Fail DDB #353 Max Prop. Alarm DDB #338

Page 3 Page 124 of 252

MiCOM P545 Programmable Logic Output Contacts

0 Input L1 DDB #032

Output R12 DDB #011

Straight 0

Any Trip DDB #522

Fault REC TRIG DDB #702

Page 4 Page 125 of 252

MiCOM P545 Programmable Logic

LEDs

Diff Trip DDB #582 Diff InterTrip DDB #586

1

Zone 1 Trip DDB #608

Latching

Latching

Zone 2 Trip DDB #613

Latching

Zone 3 Trip DDB #618

Latching

SOTF Trip Zone 1 DDB #709 SOTF Trip Zone 2 DDB #710

1

Latching

SOTF Trip Zone 3 DDB #711

I>1 Trip DDB #655

Non Latching

LED1 Red DDB #1024 LED1 Grn DDB #1025 LED2 Red DDB #1026 LED2 Grn DDB #1027 LED3 Red DDB #1028 LED3 Grn DDB #1029 LED4 Red DDB #1030 LED4 Grn DDB #1031 LED6 Red DDB #1034 LED6 Grn DDB #1035

LED7 Red DDB #1036 LED7 Grn DDB #1037

Page 5 Page 126 of 252

Diff Start A DDB #738

MiCOM P545 Programmable Logic

Zone 1 A Start DDB #741

Start Phase Mappings. Used in Fault Record & on LCD Display

Zone 2 A Start DDB #745 Zone 3 A Start DDB #749 Zone P A Start DDB #753

1

Started Phase A DDB #956

Zone 4 A Start DDB #757 I>1 Start A DDB #762

Caution: Do Not remove "Started Phase" DDB signals

I>2 Start A DDB #766 I>3 Start A DDB #770 I>4 Start A DDB #774 Diff Start B DDB #739 Zone 1 B Start DDB #742

Any Phase Start >>page 7

1

Zone 2 B Start DDB #746 Zone 3 B Start DDB #750 Zone P B Start DDB #754

1

Started Phase B DDB #957

Zone 4 B Start DDB #758 I>1 Start B DDB #763 I>2 Start B DDB #767 I>3 Start B DDB #771 I>4 Start B DDB #775 Diff Start C DDB #740 Zone 1 C Start DDB #743 Zone 2 C Start DDB #747 Zone 3 C Start DDB #751 Zone P C Start DDB #755

1

Started Phase C DDB #958

Zone 4 C Start DDB #759 I>1 Start C DDB #764 I>2 Start C DDB #768 I>3 Start C DDB #772 I>4 Start C DDB #776

Page 6 Page 127 of 252

Zone 1 N Start DDB #744

MiCOM P545 Programmable Logic

Zone 2 N Start DDB #748

Any Ground Start >> page8

Zone 3 N Start DDB #752 Zone P N Start DDB #756 Zone 4 N Start DDB #760 IN>1 Start DDB #777 IN>2 Start DDB #778 IN>3 Start DDB #779

1

Started Phase N DDB #959

IN>4 Start DDB #780 ISEF>1 Start DDB #781 ISEF>2 Start DDB #782 ISEF>3 Start DDB #783 ISEF>4 Start DDB #784

Phase Select N DDB #1013

&

Any Trip DDB #522

>>page6 Any Phase Start

Any Phase Start >>page8

Phase Select N DDB #1013

& 10

Any Trip DDB #522

Pulse 0

This logic ensures correct N indications for faults involving ground. The pulse prevents pole scatter affecting the N indication.

N Phase Start >> page8 then page 9 then page 10

A/R Status 3P DDB #856

& 1

A/R Status 1P DDB #857

Reset Relays/LED DDB #444

This reset controls: Reset latched relays, Reset latched LEDs, Reset A/R Lockout. This logic clears all latched indications at the start of Any Trip Page 7

Page 128 of 252

MiCOM P545 Programmable Logic

>> page7 Any Ground Start

>> page7 Any Phase Start Non Latching

Any Trip DDB #522

LED5 Red DDB #1032 LED5 Grn DDB #1033

I2>1 Start DDB #567 I2>2 Start DDB #568 I2>3 Start DDB #569 Any Start DDB #736

I2>4 Start DDB #570 V2 Start DDB #800 VN>1 Start DDB #804

1

Caution: Do Not remove "Any Start" DDB signal

VN>2 Start DDB #805 F2 Cmp Start DDB #924

>> page 7 N Phase Start

N Phase Start >>page 9 then page 10 Page 8

Page 129 of 252

MiCOM P545 Programmable Logic

Diff Trip A DDB #583 Diff InterTrip A DDB #587 Zone 1 A Trip DDB #609 Zone 2 A Trip DDB #614 Zone 3 A Trip DDB #619 Zone P A Trip DDB #624 Zone 4 A Trip DDB #629 Aided 1 Trip A DDB #633 Aid 1 WI Trip A DDB #637

1

Faulted Phase A DDB #952

Aided 2 Trip A DDB #643 Aid 2 WI Trip A DDB #647 I>1 Trip A DDB #656 I>2 Trip A DDB #660 I>3 Trip A DDB #664 I>4 Trip A DDB #668 AR Trip Test A DDB #577

Faulted Phase Flag, Used in Fault record and on LCD display. Caution: Do Not remove "Faulted Phase" DDB signals

Diff Trip B DDB #584 Diff InterTrip B DDB #588 Zone 1 B Trip DDB #610 Zone 2 B Trip DDB #615 Zone 3 B Trip DDB #620 Zone P B Trip DDB #625 Zone 4 B Trip DDB #630 Aided 1 Trip B DDB #634 Aid 1 WI Trip B DDB #638

1

Faulted Phase B DDB #953

Aided 2 Trip B DDB #644 Aid 2 WI Trip B DDB #648 I>1 Trip B DDB #657 I>2 Trip B DDB #661 I>3 Trip B DDB #665 I>4 Trip B DDB #669 AR Trip Test B DDB #578

>> page 7 then page 8 N Phase Start

N Phase Start >> page 10 Page 9

Page 130 of 252

MiCOM P545 Programmable Logic

Diff Trip C DDB #585 Diff InterTrip C DDB #589 Zone 1 C Trip DDB #611 Zone 2 C Trip DDB #616 Zone 3 C Trip DDB #621 Zone P C Trip DDB #626 Zone 4 C Trip DDB #631 Aided 1 Trip C DDB #635

1

Faulted Phase C DDB #954

Aid 1 WI Trip C DDB #639 Aided 2 Trip C DDB #645 Aid 2 WI Trip C DDB #649 I>1 Trip C DDB #658 I>2 Trip C DDB #662 I>3 Trip C DDB #666 I>4 Trip C DDB #670 AR Trip Test C DDB #579

Faulted Phase Flag, Used in Fault record and on LCD display.

Zone 1 N Trip DDB #612

Caution: Do Not remove "Faulted Phase" DDB signals

Zone 2 N Trip DDB #617 Zone 3 N Trip DDB #622 Zone P N Trip DDB #627 Zone 4 N Trip DDB #632 Aided 1 Trip N DDB #636 Aided 2 Trip N DDB #646 IN>1 Trip DDB #671 IN>2 Trip DDB #672

1

Faulted Phase N DDB #955

IN>3 Trip DDB #673 IN>4 Trip DDB #674 VN>1 Trip DDB #700 VN>2 Trip DDB #701 ISEF>1 Trip DDB #675 ISEF>2 Trip DDB #676 ISEF>3 Trip DDB #677 ISEF>4 Trip DDB #678

>> page 7 then page 8 the page 9 N Phase Start Page 10

Page 131 of 252

MiCOM P545 Programmable Logic Diff Trip A DDB #583

Inputs to Trip Conversion Logic:These Raw trip signals are then processed in relay fixed logic, to obtain the correct single, or three pole trip response.

Diff InterTrip A DDB #587 Zone 1 A Trip DDB #609 Aided 1 Trip A DDB #633

I>1 Trip A DDB #656

1

Trip Inputs A DDB #530

Aid 1 WI Trip A DDB #637 Aided 2 Trip A DDB #643 Aid 2 WI Trip A DDB #647 AR Trip Test A DDB #577

Caution: Do Not remove "Trip Inputs" DDB signals

Diff Trip B DDB #584 Diff InterTrip B DDB #588 Zone 1 B Trip DDB #610 Aided 1 Trip B DDB #634

I>1 Trip B DDB #657

1

Trip Inputs B DDB #531

1

Trip Inputs C DDB #532

Aid 1 WI Trip B DDB #638 Aided 2 Trip B DDB #644 Aid 2 WI Trip B DDB #648 AR Trip Test B DDB #578

Diff Trip C DDB #585 Diff InterTrip C DDB #589 Zone 1 C Trip DDB #611

I>1 Trip C DDB #658 Aided 1 Trip C DDB #635 Aid 1 WI Trip C DDB #639 Aided 2 Trip C DDB #645 Aid 2 WI Trip C DDB #649 AR Trip Test C DDB #579

Page 11 Page 132 of 252

MiCOM P545 Programmable Logic

AR Trip Test DDB #576 Perm InterTrip DDB #590 Broken Wire Trip DDB #679 Thermal Trip DDB #680

Trip Inputs 3Ph >> page 13

1 V2 Trip DDB #695

Caution: Do Not remove "Trip Inputs" DDB signals

VN>1 Trip DDB #700 VN>2 Trip DDB #701 F2 Cmp Trip DDB #926

Page 12 Page 133 of 252

MiCOM P545 Programmable Logic page 12 >> Trip Inputs 3Ph

Pred. OST DDB #551 OST DDB #553 Stub Bus Trip DDB #591 Zone 2 Trip DDB #613 Zone 3 Trip DDB #618 Zone P Trip DDB #623 Zone 4 Trip DDB #628 I>1 Trip DDB #655 I>2 Trip DDB #659 I>3 Trip DDB #663 I>4 Trip DDB #667 IN>1 Trip DDB #671 IN>2 Trip DDB #672 IN>3 Trip DDB #673 IN>4 Trip DDB #674 Aid1 DEF Trip3Ph DDB #641

1

Trip Inputs 3Ph DDB #529

Aid1 WI Trip 3Ph DDB #642 Aid2 DEF Trip3Ph DDB #651 Aid2 WI Trip 3Ph DDB #652 Loss ofLoad Trip DDB #654

Caution: Do Not remove "Trip Inputs" DDB signals

Pole Discrepancy DDB #699 TOR Trip Zone 1 DDB #704 TOR Trip Zone 2 DDB #705 TOR Trip Zone 3 DDB #706 TOR Trip Zone P DDB #708 TOR Trip Zone 4 DDB #707 TOR Trip CNV DDB #557 SOTF Trip CNV DDB #558 SOTF Trip Zone 1 DDB #709 SOTF Trip Zone 2 DDB #710 SOTF Trip Zone 3 DDB #711 SOTF Trip Zone P DDB #713 SOTF Trip Zone 4 DDB #712

Page 13 Page 134 of 252

MiCOM P545 Programmable Logic

This logic enables Check Synchro to function only for Live Line / Live Bus conditions.

CS1 Enabled DDB #881 Live Bus DDB #886

&

CS2 Enabled DDB #882 SysSplit Enabled DDB #885

Dead Line DDB #889

Dead Bus DDB #887

& &

Live Line DDB #888

1

Ctl Check Sync DDB #898

Safety Interlock. Logic must be satisfied before any manual CB closures can proceed.

Check Sync 1 OK DDB #883 Check Sync 2 OK DDB #884

SysChks Inactive DDB #880

AR Sys Checks OK DDB #899

Force 3 pole DDB #858 Aid 1 Chan Fail DDB #317

1

Force 3Pole Trip DDB #533

1

BAR DDB #448

Aid 2 Chan Fail DDB #318 Signalling Fail DDB #311

Input L16 DDB #047

Default PSL blocks autoreclose if any aided scheme channel fails.

Power Swing DDB #297

Inhibit WI DDB #458

Page 14 Page 135 of 252

A

B50, B60 Spare Funct 87, 21, 49

Page 136 of 252

MiCOM S1 Studio

Page: 1

Settings File Report File: =B Spare Funct 87, 21, 49.set Model Number: P545216C6M0540K

Printed on: 02/08/2010 16:22:28

: SYSTEM DATA:

00.01: 00.02: 00.03: 00.04: 00.05: 00.06: 00.08: 00.09: 00.0A: 00.0B: 00.0C: 00.0D: 00.0E: 00.10: 00.11: 00.20: 00.21: 00.22: 00.50: 00.51: 00.52: 00.D0: 00.D1: 00.D2: 00.D3:

Language:English Password:**** Sys Fn Links:0 Description:B50_87_21_49 Plant Reference:DID Model Number:P545216C6M0540K Serial Number:12345 Frequency:50 Hz Comms Level:2 Relay Address:1 Plant Status:0000000000000010 Control Status:0000000000000000 Active Group:1 CB Trip/Close:No Operation Software Ref. 1:P545____4__540_A Opto I/P Status:000000000000000000000000 Relay O/P Status:00000000000000000000000000001010 Alarm Status 1:00000010100000000000000000000000 Alarm Status 1:00000010100000000000000000000000 Alarm Status 2:00000000000000000000000000000000 Alarm Status 3:00000000000000000000000000000000 Access Level:2 Password Control:2 Password Level 1:**** Password Level 2:****

: CB CONTROL: : DATE AND TIME: : CONFIGURATION:

09.01: 09.02: 09.03: 09.04: 09.05: 09.06: 09.07: 09.08: 09.09: 09.0A: 09.0B: 09.0C: 09.0F: 09.10: 09.11: 09.12: 09.13: 09.15: 09.16: 09.17:

Restore Defaults:No Operation Setting Group:Select via Menu Active Settings:Group 1 Save Changes:No Operation Copy From:Group 1 Copy To:No Operation Setting Group 1:Enabled Setting Group 2:Disabled Setting Group 3:Disabled Setting Group 4:Disabled Distance:Enabled Directional E/F:Disabled Phase Diff:Enabled Overcurrent:Enabled Neg Sequence O/C:Disabled Broken Conductor:Disabled Earth Fault:Disabled Sensitive E/F:Disabled Residual O/V NVD:Disabled Thermal Overload:Enabled

- Settings File Report -

Page 137 of 252

MiCOM S1 Studio

Page: 2

Settings File Report File: =B Spare Funct 87, 21, 49.set Model Number: P545216C6M0540K 09.18: 09.1D: 09.1E: 09.1F: 09.20: 09.21: 09.23: 09.24: 09.25: 09.26: 09.28: 09.29: 09.2A: 09.2B: 09.2C: 09.2D: 09.2E: 09.2F: 09.35: 09.36: 09.39: 09.50: 09.FF:

Printed on: 02/08/2010 16:22:28

PowerSwing Block:Enabled Volt Protection:Disabled Freq Protection:Disabled df/dt Protection:Disabled CB Fail:Disabled Supervision:Enabled System Checks:Disabled Auto-Reclose:Disabled Input Labels:Visible Output Labels:Visible CT & VT Ratios:Visible Record Control:Visible Disturb Recorder:Visible Measure't Setup:Visible Comms Settings:Visible Commission Tests:Visible Setting Values:Secondary Control Inputs:Visible Ctrl I/P Config:Visible Ctrl I/P Labels:Visible Direct Access:Enabled Function Key:Visible LCD Contrast:11

: CT AND VT RATIOS:

0A.01: 0A.02: 0A.03: 0A.04: 0A.07: 0A.08: 0A.0B: 0A.0C: 0A.0D: 0A.0E: 0A.0F: 0A.10: 0A.11: 0A.13: 0A.14: 0A.18:

Main VT Primary:66.00 kV Main VT Sec'y:110.0 V C/S VT Primary:66.00 kV C/S VT Secondary:110.0 V Phase CT Primary:800.0 1200.0 A Phase CT Sec'y:1.000 A SEF CT Primary:800.0 1200.0 A SEF CT Secondary:1.000 A MComp CT Primary:800.0 1200.0 A MComp CT Sec'y:1.000 A C/S Input:A-N Main VT Location:Line CT Polarity:Standard SEF CT Polarity:Standard M CT Polarity:Standard VT Connected:Yes

: RECORD CONTROL: : DISTURB RECORDER:

0C.01: 0C.02: 0C.03: 0C.04: 0C.05: 0C.06: 0C.07:

Duration:2.000 s Trigger Position:33.30% Trigger Mode:Single Analog Channel 1:VA Analog Channel 2:VB Analog Channel 3:VC Analog Channel 4:IA

- Settings File Report -

Page 138 of 252

MiCOM S1 Studio

Page: 3

Settings File Report File: =B Spare Funct 87, 21, 49.set Model Number: P545216C6M0540K 0C.08: 0C.09: 0C.0A: 0C.0B: 0C.0C: 0C.0D: 0C.0E: 0C.0F: 0C.10: 0C.11: 0C.12: 0C.13: 0C.14: 0C.15: 0C.16: 0C.17: 0C.18: 0C.19: 0C.1A: 0C.1B: 0C.1C: 0C.1D: 0C.1E: 0C.1F: 0C.20: 0C.21: 0C.22: 0C.23: 0C.24: 0C.25: 0C.26: 0C.27: 0C.28: 0C.29: 0C.2A: 0C.2B: 0C.2C: 0C.2D: 0C.2E: 0C.2F: 0C.30: 0C.31: 0C.32: 0C.33: 0C.34: 0C.35: 0C.36: 0C.37: 0C.38:

Printed on: 02/08/2010 16:22:28

Analog Channel 5:IB Analog Channel 6:IC Analog Channel 7:IN Analog Channel 8:IN Sensitive Digital Input 1:Diff Trip Input 1 Trigger:No Trigger Digital Input 2:Zone 1 Trip Input 2 Trigger:No Trigger Digital Input 3:Relay 3 Input 3 Trigger:Trigger L/H Digital Input 4:Zone 2 Trip Input 4 Trigger:No Trigger Digital Input 5:Zone 3 Trip Input 5 Trigger:No Trigger Digital Input 6:Thermal Trip Input 6 Trigger:No Trigger Digital Input 7:Thermal Alarm Input 7 Trigger:No Trigger Digital Input 8:I>1 Trip Input 8 Trigger:No Trigger Digital Input 9:Relay 9 Input 9 Trigger:No Trigger Digital Input 10:Relay 10 Input 10 Trigger:No Trigger Digital Input 11:Relay 11 Input 11 Trigger:No Trigger Digital Input 12:Relay 12 Input 12 Trigger:No Trigger Digital Input 13:Relay 13 Input 13 Trigger:No Trigger Digital Input 14:Relay 14 Input 14 Trigger:No Trigger Digital Input 15:Relay 15 Input 15 Trigger:No Trigger Digital Input 16:Relay 16 Input 16 Trigger:No Trigger Digital Input 17:Opto 1 Input 17 Trigger:No Trigger Digital Input 18:Opto 2 Input 18 Trigger:No Trigger Digital Input 19:Opto 3 Input 19 Trigger:No Trigger Digital Input 20:Opto 4 Input 20 Trigger:No Trigger Digital Input 21:Opto 5 Input 21 Trigger:No Trigger Digital Input 22:Opto 6 Input 22 Trigger:No Trigger Digital Input 23:Opto 7

- Settings File Report -

Page 139 of 252

MiCOM S1 Studio

Page: 4

Settings File Report File: =B Spare Funct 87, 21, 49.set Model Number: P545216C6M0540K 0C.39: 0C.3A: 0C.3B: 0C.3C: 0C.3D: 0C.3E: 0C.3F: 0C.40: 0C.41: 0C.42: 0C.43: 0C.44: 0C.45: 0C.46: 0C.47: 0C.48: 0C.49: 0C.4A: 0C.4B: 0C.50: 0C.51: 0C.52: 0C.53:

Printed on: 02/08/2010 16:22:28

Input 23 Trigger:No Trigger Digital Input 24:Opto 8 Input 24 Trigger:No Trigger Digital Input 25:Opto 9 Input 25 Trigger:No Trigger Digital Input 26:Opto 10 Input 26 Trigger:No Trigger Digital Input 27:Opto 11 Input 27 Trigger:No Trigger Digital Input 28:Opto 12 Input 28 Trigger:No Trigger Digital Input 29:Opto 13 Input 29 Trigger:No Trigger Digital Input 30:Opto 14 Input 30 Trigger:No Trigger Digital Input 31:Opto 15 Input 31 Trigger:No Trigger Digital Input 32:Opto 16 Input 32 Trigger:No Trigger Analog Channel 9:V Checksync Analog Channel10:IM Analog Channel11:IN Analog Channel12:IN

: MEASURE'T SETUP:

0D.01: 0D.02: 0D.03: 0D.04: 0D.05: 0D.06: 0D.07: 0D.08: 0D.09: 0D.0A:

Default Display:3Ph + N Current Local Values:Primary Remote Values:Primary Measurement Ref:VA Measurement Mode:0 Fix Dem Period:30.00 min Roll Sub Period:30.00 min Num Sub Periods:1 Distance Unit:Kilometres Fault Location:Distance

: COMMISSION TESTS: : CB MONITOR SETUP: : OPTO CONFIG:

11.01: Global Nominal V:110/125V 11.60: Opto Filter Cntl:111111111011011111111011 11.80: Characteristic:Standard 60%-80% : : : :

CONTROL INPUTS: CTRL I/P CONFIG: FUNCTION KEYS: PROT COMMS/ IM64:

20.01: 20.03: 20.10: 20.11: 20.12:

Scheme Setup:Dual Redundant Address:2-A Comms Mode:Standard Baud Rate Ch1:64kbits/s Baud Rate Ch2:64kbits/s

- Settings File Report -

Page 140 of 252

MiCOM S1 Studio

Page: 5

Settings File Report File: =B Spare Funct 87, 21, 49.set Model Number: P545216C6M0540K 20.13: 20.14: 20.17: 20.18: 20.19: 20.1A: 20.1B: 20.1F: 20.20: 20.21: 20.22: 20.30: 20.31: 20.32: 20.34: 20.35: 20.36: 20.38: 20.39: 20.3A: 20.3C: 20.3D: 20.3E: 20.40: 20.41: 20.42: 20.44: 20.45: 20.46: 20.48: 20.49: 20.4A: 20.4C: 20.4D: 20.4E:

Printed on: 02/08/2010 16:22:28

Clock Source Ch1:Internal Clock Source Ch2:Internal Comm Delay Tol:350.0 us Comm Fail Timer:10.00 s Comm Fail Mode:Ch 1 and 2 Fail GPS Sync:Disabled Char Mod Time:500.0 ms Alarm Level:25.00% Prop Delay Stats:Enabled MaxCh1 PropDelay:15.00 ms MaxCh2 PropDelay:15.00 ms IM1 Cmd Type:Permissive IM1 Fallbck Mode:Default IM1 Default Val:0 IM2 Cmd Type:Permissive IM2 Fallbck Mode:Default IM2 Default Val:0 IM3 Cmd Type:Permissive IM3 Fallbck Mode:Default IM3 Default Val:0 IM4 Cmd Type:Permissive IM4 Fallbck Mode:Default IM4 Default Val:0 IM5 Cmd Type:Permissive IM5 Fallbck Mode:Default IM5 Default Val:0 IM6 Cmd Type:Permissive IM6 Fallbck Mode:Default IM6 Default Val:0 IM7 Cmd Type:Permissive IM7 Fallbck Mode:Default IM7 Default Val:0 IM8 Cmd Type:Permissive IM8 Fallbck Mode:Default IM8 Default Val:0

: CTRL I/P LABELS: : Group 1:

: GROUP 1 LINE PARAMETERS: 30.01: Line Length:2000 m 30.03: Line Impedance:290.0 mOhm 438.0 30.04: Line Angle:81.00 deg 30.05: kZN Res Comp:160.0e-3 30.06: kZN Res Angle:-170.0 deg 30.07: Mutual Comp:Disabled 30.0B: Phase Sequence:Standard ABC 30.0C: Tripping Mode:3 Pole 30.10: Line Charging Y:100.0 uS : GROUP 1 DISTANCE SETUP: 31.0C: Setting Mode:Advanced

- Settings File Report -

Page 141 of 252

MiCOM S1 Studio

Page: 6

Settings File Report File: =B Spare Funct 87, 21, 49.set Model Number: P545216C6M0540K 31.10: 31.11: 31.20: 31.30: 31.40: 31.42: 31.50: 31.60: 31.70: 31.71: 31.80: 31.90: 31.A0: 31.A2: 31.B0: 31.C0: 31.D0: 31.D1: 31.D3: 31.D7: 31.E0: 31.E1: 31.E2: 31.E3:

Printed on: 02/08/2010 16:22:28

PHASE DISTANCE: Phase Chars.:Quad Zone 1 Ph Status:Enabled Ch Fail Zone 2 Ph Status:Enabled Zone 3 Ph Status:Enabled Zone 3 Ph Offset:Disabled Zone P Ph Status:Disabled Zone 4 Ph Status:Disabled GROUND DISTANCE: Ground Chars.:Quad Zone 1 Gnd Stat.:Enabled Ch Fail Zone 2 Gnd Stat.:Enabled Zone 3 Gnd Stat.:Enabled Zone3 Gnd Offset:Disabled Zone P Gnd Stat.:Disabled Zone 4 Gnd Stat.:Disabled Digital Filter:Standard CVT Filters:Disabled Load Blinders:Disabled Dist. Polarizing:1.000 DELTADIRECTIONAL: Dir. Status:Enabled AidedDeltaStatus:Disabled Dir. Char Angle:45.00 deg

: GROUP 1 DIST. ELEMENTS: 32.01: PHASE DISTANCE: 32.02: Z1 Ph. Reach:200.0 mOhm 310.0 32.03: Z1 Ph. Angle:81.00 deg 0.92 32.07: R1 Ph. Resistive:2.660 Ohm 32.08: Z1 Tilt Top Line:-3.000 deg 32.09: Z1 Sensit. Iph>1:75.00 mA 570.0 32.10: Z2 Ph. Reach:380.0 mOhm 32.11: Z2 Ph. Angle:81.00 deg 1.71 32.15: R2 Ph. Resistive:2.660 Ohm 32.16: Z2 Tilt Top Line:-3.000 deg 32.17: Z2 Sensit. Iph>2:75.00 mA 880.0 32.20: Z3 Ph. Reach:580.0 mOhm 32.21: Z3 Ph. Angle:81.00 deg 2.63 32.25: R3 Ph. Res. Fwd.:2.660 Ohm 32.27: Z3 Tilt Top Line:-3.000 deg 32.28: Z3 Sensit. Iph>3:50.00 mA 32.50: GROUND DISTANCE: 310.0 32.51: Z1 Gnd. Reach:200.0 mOhm 32.52: Z1 Gnd. Angle:81.00 deg 32.53: Z1 Dynamic Tilt:Enabled 32.54: Z1 Tilt Top Line:-3.000 deg 32.55: kZN1 Res. Comp.:160.0e-3 32.56: kZN1 Res. Angle:-170.0 deg 32.59: R1 Gnd Resistive:4.000 Ohm 1.38

- Settings File Report -

Page 142 of 252

MiCOM S1 Studio

Page: 7

Settings File Report File: =B Spare Funct 87, 21, 49.set Model Number: P545216C6M0540K 32.5B: 32.60: 32.61: 32.63: 32.64: 32.65: 32.66: 32.69: 32.6B: 32.70: 32.71: 32.73: 32.74: 32.75: 32.76: 32.79: 32.7C:

Printed on: 02/08/2010 16:22:28

Z1 Sensit Ignd>1:75.00 mA 570.0 Z2 Gnd. Reach:380.0 mOhm Z2 Gnd. Angle:81.00 deg Z2 Dynamic Tilt:Enabled Z2 Tilt Top Line:-3.000 deg kZN2 Res. Comp.:160.0e-3 kZN2 Res. Angle:-170.0 deg R2 Gnd Resistive:4.000 Ohm 2.56 Z2 Sensit Ignd>2:75.00 mA 880.0 Z3 Gnd. Reach:580.0 mOhm Z3 Gnd. Angle:81.00 deg Z3 Dynamic Tilt:Enabled Z3 Tilt Top Line:-3.000 deg kZN3 Res. Comp.:160.0e-3 kZN3 Res. Angle:-170.0 deg 3.94 R3 Gnd. Res. Fwd:4.000 Ohm Z3 Sensit Ignd>3:50.00 mA

: GROUP 1 PHASE DIFF: 33.01: Phase Diff:Enabled 33.06: Phase Is1:200.0 mA 33.07: Phase Is2:2.000 A 33.08: Phase k1:30.00% 33.09: Phase k2:150.0% 33.0A: Phase Char:DT 33.0B: Phase Time Delay:0 s 33.0E: PIT Time:0 s 33.0F: Ph CT Corr'tion:1.000 33.10: Compensation:None 33.17: PIT I selection:Local : GROUP 1 SCHEME LOGIC: 34.01: BASIC SCHEME: 34.08: Zone1 Tripping:Phase And Ground 34.09: tZ1 Ph. Delay:0 s 34.0A: tZ1 Gnd. Delay:0 s 34.10: Zone2 Tripping:Phase And Ground 34.11: tZ2 Ph. Delay:400.0 ms 34.12: tZ2 Gnd. Delay:400.0 ms 34.18: Zone3 Tripping:Phase And Ground 34.19: tZ3 Ph. Delay:5.000 s 34.1A: tZ3 Gnd. Delay:5.000 s 34.20: ZoneP Tripping:Disabled 34.28: Zone4 Tripping:Disabled 34.40: AIDED SCHEME 1: 34.41: Aid. 1 Selection:Disabled 34.60: AIDED SCHEME 2: 34.61: Aid. 2 Selection:Disabled 34.80: Trip On Close: 34.81: SOTF Status:Enabled ExtPulse 34.83: SOTF Tripping:000011

- Settings File Report -

Page 143 of 252

MiCOM S1 Studio

Page: 8

Settings File Report File: =B Spare Funct 87, 21, 49.set Model Number: P545216C6M0540K 34.84: 34.86: 34.87: 34.88: 34.B0: 34.B1: 34.C0: 34.C1:

Printed on: 02/08/2010 16:22:28

TOR Status:Disabled TOC Reset Delay:500.0 ms SOTF Pulse:500.0 ms TOC Delay:200.0 ms Z1 Extension: Z1 Ext Scheme:Disabled Loss Of Load: LOL Scheme:Disabled

: GROUP 1 35.01: 35.02: 35.03: 35.04: 35.06: 35.09: 35.0A: 35.13: 35.18: 35.1C: 35.1D:

OVERCURRENT: I>1 Status:Enabled I>1 Function:IEC S Inverse I>1 Directional:Non-Directional I>1 Current Set:960.0 mA 640.0 I>1 TMS:1.000 I>1 tRESET:0 s I>2 Status:Disabled I>3 Status:Disabled I>4 Status:Disabled I> Char Angle:30.00 deg I> Blocking:001111

: GROUP 1 3C.01: 3C.02: 3C.03: 3C.04:

THERMAL OVERLOAD: Characteristic:Single Thermal Trip:1.000 A 700.0 mA Thermal Alarm:90.00% Time Constant 1:25.00 min

: GROUP 1 POWER SWING BLK.: 3D.01: PSB Status:Blocking 3D.03: Zone 1 Ph. PSB:Blocking 3D.05: Zone 2 Ph. PSB:Blocking 3D.07: Zone 3 Ph. PSB:Blocking 3D.09: Zone P Ph. PSB:Blocking 3D.0B: Zone 4 Ph. PSB:Blocking 3D.0D: Zone 1 Gnd. PSB:Blocking 3D.0F: Zone 2 Gnd. PSB:Blocking 3D.11: Zone 3 Gnd. PSB:Blocking 3D.13: Zone P Gnd. PSB:Blocking 3D.15: Zone 4 Gnd. PSB:Blocking 3D.20: PSB Unblocking:Disabled 3D.22: PSB Reset Delay:500.0 ms 3D.23: OST Mode:OST Disabled 3D.24: Z5:30.01 Ohm 3D.26: Z5':-29.97 Ohm 3D.28: R5:20.00 Ohm 3D.2A: R5':-20.00 Ohm 3D.2C: Blinder Angle:80.00 deg : GROUP 1 CB FAIL & P.DEAD: : GROUP 1 SUPERVISION: 46.01: VTS Mode:Measured + MCB 46.02: VTS Status:Blocking

- Settings File Report -

Page 144 of 252

MiCOM S1 Studio

Page: 9

Settings File Report File: =B Spare Funct 87, 21, 49.set Model Number: P545216C6M0540K 46.03: 46.04: 46.05: 46.06: 46.0E: 46.0F: 46.10: 46.11: 46.30: 46.31:

Printed on: 02/08/2010 16:22:28

VTS Reset Mode:Auto VTS Time Delay:5.000 s VTS I> Inhibit:32.00 A 26.70 VTS I2> Inhibit:50.00 mA INRUSH DETECTION: I>2nd Harmonic:20.00% WEAK INFEED BLK: WI Inhibit:Disabled CT SUPERVISION: CTS Mode:Disabled

: GROUP 1 INPUT 4A.01: Opto 4A.02: Opto 4A.03: Opto 4A.04: Opto 4A.05: Opto 4A.06: Opto 4A.07: Opto 4A.08: Opto 4A.09: Opto 4A.0A: Opto 4A.0B: Opto 4A.0C: Opto 4A.0D: Opto 4A.0E: Opto 4A.0F: Opto 4A.10: Opto 4A.11: Opto 4A.12: Opto 4A.13: Opto 4A.14: Opto 4A.15: Opto 4A.16: Opto 4A.17: Opto 4A.18: Opto

LABELS: Input 1:Un used Input 2:CB Close Pulse Input 3:Un used Input 4:Un used Input 5:Dist Carrrier Rx Input 6:DEF Carrier Rx Input 7:Un used Input 8:Un used Input 9:ES G901 Open Input 10:ES G901 Close Input 11:CB G900 Open Input 12:CB G900 Close Input 13:Un used Input 14:Un used Input 15:Test Mode Input 16:Un used Input 17:Un used Input 18:Un used Input 19:Un used Input 20:Un used Input 21:LVT MCB Open Input 22:Un used Input 23:Un used Input 24:Un used

: GROUP 1 OUTPUT 4B.01: Relay 4B.02: Relay 4B.03: Relay 4B.04: Relay 4B.05: Relay 4B.06: Relay 4B.07: Relay 4B.08: Relay 4B.09: Relay 4B.0A: Relay 4B.0B: Relay 4B.0C: Relay 4B.0D: Relay

LABELS: 1:TO TRIP 86-1 2:INT TRIP RECEIVD 3:A-PH TRIP 4:VT FAIL 5:B-PH TRIP 6:C-PH TRIP 7:UN USED 8:UN USED 9:SPARE 10:SPARE 11:UN USED 12:INT TRIP SEND 13:UN USED

- Settings File Report -

Page 145 of 252

MiCOM S1 Studio

Page: 10

Settings File Report File: =B Spare Funct 87, 21, 49.set Model Number: P545216C6M0540K 4B.0E: 4B.0F: 4B.10: 4B.11: 4B.12: 4B.13: 4B.14: 4B.15: 4B.16: 4B.17: 4B.18: 4B.19: 4B.1A: 4B.1B: 4B.1C: 4B.1D: 4B.1E: 4B.1F: 4B.20:

Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay

Printed on: 02/08/2010 16:22:28

14:UN USED 15:UN USED 16:UN USED 17:A-PH TRIP 94-1R 18:B-PH TIRP 94-IY 19:C-PH TRIP 94-1B 20:UN USED 21:UN USED 22:UN USED 23:UN USED 24:UN USED 25:UN USED 26:UN USED 27:DIST OPTD 28:DEF OPTD 29:UN USED 30:UN USED 31:UN USED 32:UN USED

- Settings File Report -

Page 146 of 252

MiCOM P545 Programmable Logic Opto Input Mappings

IM64 Ch1 Output1 DDB #112

1

Input L1 DDB #032

IM64 Ch2 Output1 DDB #120 Set SOTF DDB #488

Input L2 DDB #033

1

Input L9 DDB #040

IM64 Ch1 Output2 DDB #113 IM64 Ch2 Output2 DDB #121

1

Input L10 DDB #041

IM64 Ch1 Output3 DDB #114 IM64 Ch2 Output3 DDB #122

1

Input L11 DDB #042

IM64 Ch1 Output4 DDB #115 IM64 Ch2 Output4 DDB #123 IM64 Ch1 Output5 DDB #116

1

Input L12 DDB #043

MCB/VTS DDB #438

Input L21 DDB #052

Input L24 DDB #055

IM64 Ch2 Output5 DDB #124

&

Test Mode DDB #459

Non Latching

Opto L5 & L16 can be found on other pages

FnKey LED1 Red DDB #1040 FnKey LED1 Grn DDB #1041

Page 1 Page 147 of 252

MiCOM P545 Programmable Logic Output Contacts Diff InterTrip DDB #586

0

Zone 1 Trip DDB #608

Output R1 DDB #000

Straight 0

Zone 2 Trip DDB #613

0

Zone 3 Trip DDB #618

Output R9 DDB #008

Straight

1

SOTF Trip Zone 1 DDB #709

0 0

SOTF Trip Zone 2 DDB #710

Output R10 DDB #009

Straight 0

SOTF Trip Zone 3 DDB #711

I>1 Trip DDB #655 Diff Trip DDB #582

0 IM64 Ch1 Input 1 DDB #096 IM64 Ch2 Input 1 DDB #104

Output R2 DDB #001

Straight 0

1

0 Output R11 DDB #010

Straight

Diff Trip A DDB #583

0

Diff InterTrip A DDB #587 Zone 1 A Trip DDB #609

0

1

I>1 Trip DDB #655

Output R3 DDB #002

Straight 0

SOTF Trip Zone 1 DDB #709 SOTF Trip Zone 2 DDB #710 SOTF Trip Zone 3 DDB #711

0

VTS Blk Distance DDB #1404

Output R4 DDB #003

Straight 0

Diff Trip B DDB #584 Diff InterTrip B DDB #588 Zone 1 B Trip DDB #610 IN>1 Trip DDB #671 IN>2 Trip DDB #672

0 Output R5 DDB #004

Straight

1

0

SOTF Trip Zone 1 DDB #709 SOTF Trip Zone 2 DDB #710 SOTF Trip Zone 3 DDB #711 Diff Trip C DDB #585 Diff InterTrip C DDB #589 Zone 1 C Trip DDB #611

0

I>1 Trip DDB #655

1

Output R6 DDB #005

Straight 0

SOTF Trip Zone 1 DDB #709 SOTF Trip Zone 2 DDB #710 SOTF Trip Zone 3 DDB #711

Page Page 148 of 252

2

MiCOM P545 Programmable Logic Output Contacts SG-opto Invalid DDB #288 Prot'n Disabled DDB #289 Static Test Mode DDB #290 Test Loopback DDB #291 Test IM64 DDB #292 VT Fail Alarm DDB #293 CT Fail Alarm DDB #294 Remote CT Alarm DDB #296 Power Swing DDB #297 CB Fail Alarm DDB #298 CB Monitor Alarm DDB #299 CB Lockout Alarm DDB #300 CB Status Alarm DDB #301 CB Trip Fail DDB #302 CB Close Fail DDB #303 Man CB Unhealthy DDB #304 No C/S Man Close DDB #305 A/R Lockout DDB #306 A/R CB Unhealthy DDB #307 A/R No Checksync DDB #308

1 General Alarm

System Split DDB #309 GPS Alarm DDB #310 Signalling Fail DDB #311

GENERAL ALARM IS NOT REQUIRED

Comm Delay Alarm DDB #312 C Diff Failure DDB #313 IM64 SchemeFail DDB #314 IEEE C37.94 Fail DDB #315 Aid 1 Chan Fail DDB #317 Aid 2 Chan Fail DDB #318 F out of Range DDB #319 Incompatible Rly DDB #332 InValid Mesg Fmt DDB #333 Main Prot. Fail DDB #334 Config Error DDB #335 Re-Config Error DDB #336 Comms Changed DDB #337 Battery Fail DDB #352 Field Volts Fail DDB #353 Max Prop. Alarm DDB #338

Page 3 Page 149 of 252

MiCOM P545 Programmable Logic Output Contacts

0 Input L1 DDB #032

Output R12 DDB #011

Straight 0

Any Trip DDB #522

Fault REC TRIG DDB #702

Page 4 Page 150 of 252

MiCOM P545 Programmable Logic

LEDs

Diff Trip DDB #582 Diff InterTrip DDB #586

1

Zone 1 Trip DDB #608

Latching

Latching

Zone 2 Trip DDB #613

Latching

Zone 3 Trip DDB #618

Latching

SOTF Trip Zone 1 DDB #709 SOTF Trip Zone 2 DDB #710

1

Latching

SOTF Trip Zone 3 DDB #711

I>1 Trip DDB #655

Non Latching

LED1 Red DDB #1024 LED1 Grn DDB #1025 LED2 Red DDB #1026 LED2 Grn DDB #1027 LED3 Red DDB #1028 LED3 Grn DDB #1029 LED4 Red DDB #1030 LED4 Grn DDB #1031 LED6 Red DDB #1034 LED6 Grn DDB #1035

LED7 Red DDB #1036 LED7 Grn DDB #1037

Page 5 Page 151 of 252

Diff Start A DDB #738

MiCOM P545 Programmable Logic

Zone 1 A Start DDB #741

Start Phase Mappings. Used in Fault Record & on LCD Display

Zone 2 A Start DDB #745 Zone 3 A Start DDB #749 Zone P A Start DDB #753

1

Started Phase A DDB #956

Zone 4 A Start DDB #757 I>1 Start A DDB #762

Caution: Do Not remove "Started Phase" DDB signals

I>2 Start A DDB #766 I>3 Start A DDB #770 I>4 Start A DDB #774 Diff Start B DDB #739 Zone 1 B Start DDB #742

Any Phase Start >>page 7

1

Zone 2 B Start DDB #746 Zone 3 B Start DDB #750 Zone P B Start DDB #754

1

Started Phase B DDB #957

Zone 4 B Start DDB #758 I>1 Start B DDB #763 I>2 Start B DDB #767 I>3 Start B DDB #771 I>4 Start B DDB #775 Diff Start C DDB #740 Zone 1 C Start DDB #743 Zone 2 C Start DDB #747 Zone 3 C Start DDB #751 Zone P C Start DDB #755

1

Started Phase C DDB #958

Zone 4 C Start DDB #759 I>1 Start C DDB #764 I>2 Start C DDB #768 I>3 Start C DDB #772 I>4 Start C DDB #776

Page 6 Page 152 of 252

Zone 1 N Start DDB #744

MiCOM P545 Programmable Logic

Zone 2 N Start DDB #748

Any Ground Start >> page8

Zone 3 N Start DDB #752 Zone P N Start DDB #756 Zone 4 N Start DDB #760 IN>1 Start DDB #777 IN>2 Start DDB #778 IN>3 Start DDB #779

1

Started Phase N DDB #959

IN>4 Start DDB #780 ISEF>1 Start DDB #781 ISEF>2 Start DDB #782 ISEF>3 Start DDB #783 ISEF>4 Start DDB #784

Phase Select N DDB #1013

&

Any Trip DDB #522

>>page6 Any Phase Start

Any Phase Start >>page8

Phase Select N DDB #1013

& 10

Any Trip DDB #522

Pulse 0

This logic ensures correct N indications for faults involving ground. The pulse prevents pole scatter affecting the N indication.

N Phase Start >> page8 then page 9 then page 10

A/R Status 3P DDB #856

& 1

A/R Status 1P DDB #857

Reset Relays/LED DDB #444

This reset controls: Reset latched relays, Reset latched LEDs, Reset A/R Lockout. This logic clears all latched indications at the start of Any Trip Page 7

Page 153 of 252

MiCOM P545 Programmable Logic

>> page7 Any Ground Start

>> page7 Any Phase Start Non Latching

Any Trip DDB #522

LED5 Red DDB #1032 LED5 Grn DDB #1033

I2>1 Start DDB #567 I2>2 Start DDB #568 I2>3 Start DDB #569 Any Start DDB #736

I2>4 Start DDB #570 V2 Start DDB #800 VN>1 Start DDB #804

1

Caution: Do Not remove "Any Start" DDB signal

VN>2 Start DDB #805 F2 Cmp Start DDB #924

>> page 7 N Phase Start

N Phase Start >>page 9 then page 10 Page 8

Page 154 of 252

MiCOM P545 Programmable Logic

Diff Trip A DDB #583 Diff InterTrip A DDB #587 Zone 1 A Trip DDB #609 Zone 2 A Trip DDB #614 Zone 3 A Trip DDB #619 Zone P A Trip DDB #624 Zone 4 A Trip DDB #629 Aided 1 Trip A DDB #633 Aid 1 WI Trip A DDB #637

1

Faulted Phase A DDB #952

Aided 2 Trip A DDB #643 Aid 2 WI Trip A DDB #647 I>1 Trip A DDB #656 I>2 Trip A DDB #660 I>3 Trip A DDB #664 I>4 Trip A DDB #668 AR Trip Test A DDB #577

Faulted Phase Flag, Used in Fault record and on LCD display. Caution: Do Not remove "Faulted Phase" DDB signals

Diff Trip B DDB #584 Diff InterTrip B DDB #588 Zone 1 B Trip DDB #610 Zone 2 B Trip DDB #615 Zone 3 B Trip DDB #620 Zone P B Trip DDB #625 Zone 4 B Trip DDB #630 Aided 1 Trip B DDB #634 Aid 1 WI Trip B DDB #638

1

Faulted Phase B DDB #953

Aided 2 Trip B DDB #644 Aid 2 WI Trip B DDB #648 I>1 Trip B DDB #657 I>2 Trip B DDB #661 I>3 Trip B DDB #665 I>4 Trip B DDB #669 AR Trip Test B DDB #578

>> page 7 then page 8 N Phase Start

N Phase Start >> page 10 Page 9

Page 155 of 252

MiCOM P545 Programmable Logic

Diff Trip C DDB #585 Diff InterTrip C DDB #589 Zone 1 C Trip DDB #611 Zone 2 C Trip DDB #616 Zone 3 C Trip DDB #621 Zone P C Trip DDB #626 Zone 4 C Trip DDB #631 Aided 1 Trip C DDB #635

1

Faulted Phase C DDB #954

Aid 1 WI Trip C DDB #639 Aided 2 Trip C DDB #645 Aid 2 WI Trip C DDB #649 I>1 Trip C DDB #658 I>2 Trip C DDB #662 I>3 Trip C DDB #666 I>4 Trip C DDB #670 AR Trip Test C DDB #579

Faulted Phase Flag, Used in Fault record and on LCD display.

Zone 1 N Trip DDB #612

Caution: Do Not remove "Faulted Phase" DDB signals

Zone 2 N Trip DDB #617 Zone 3 N Trip DDB #622 Zone P N Trip DDB #627 Zone 4 N Trip DDB #632 Aided 1 Trip N DDB #636 Aided 2 Trip N DDB #646 IN>1 Trip DDB #671 IN>2 Trip DDB #672

1

Faulted Phase N DDB #955

IN>3 Trip DDB #673 IN>4 Trip DDB #674 VN>1 Trip DDB #700 VN>2 Trip DDB #701 ISEF>1 Trip DDB #675 ISEF>2 Trip DDB #676 ISEF>3 Trip DDB #677 ISEF>4 Trip DDB #678

>> page 7 then page 8 the page 9 N Phase Start Page 10

Page 156 of 252

MiCOM P545 Programmable Logic Diff Trip A DDB #583

Inputs to Trip Conversion Logic:These Raw trip signals are then processed in relay fixed logic, to obtain the correct single, or three pole trip response.

Diff InterTrip A DDB #587 Zone 1 A Trip DDB #609 Aided 1 Trip A DDB #633

I>1 Trip A DDB #656

1

Trip Inputs A DDB #530

Aid 1 WI Trip A DDB #637 Aided 2 Trip A DDB #643 Aid 2 WI Trip A DDB #647 AR Trip Test A DDB #577

Caution: Do Not remove "Trip Inputs" DDB signals

Diff Trip B DDB #584 Diff InterTrip B DDB #588 Zone 1 B Trip DDB #610 Aided 1 Trip B DDB #634

I>1 Trip B DDB #657

1

Trip Inputs B DDB #531

1

Trip Inputs C DDB #532

Aid 1 WI Trip B DDB #638 Aided 2 Trip B DDB #644 Aid 2 WI Trip B DDB #648 AR Trip Test B DDB #578

Diff Trip C DDB #585 Diff InterTrip C DDB #589 Zone 1 C Trip DDB #611

I>1 Trip C DDB #658 Aided 1 Trip C DDB #635 Aid 1 WI Trip C DDB #639 Aided 2 Trip C DDB #645 Aid 2 WI Trip C DDB #649 AR Trip Test C DDB #579

Page 11 Page 157 of 252

MiCOM P545 Programmable Logic

AR Trip Test DDB #576 Perm InterTrip DDB #590 Broken Wire Trip DDB #679 Thermal Trip DDB #680

Trip Inputs 3Ph >> page 13

1 V2 Trip DDB #695

Caution: Do Not remove "Trip Inputs" DDB signals

VN>1 Trip DDB #700 VN>2 Trip DDB #701 F2 Cmp Trip DDB #926

Page 12 Page 158 of 252

MiCOM P545 Programmable Logic page 12 >> Trip Inputs 3Ph

Pred. OST DDB #551 OST DDB #553 Stub Bus Trip DDB #591 Zone 2 Trip DDB #613 Zone 3 Trip DDB #618 Zone P Trip DDB #623 Zone 4 Trip DDB #628 I>1 Trip DDB #655 I>2 Trip DDB #659 I>3 Trip DDB #663 I>4 Trip DDB #667 IN>1 Trip DDB #671 IN>2 Trip DDB #672 IN>3 Trip DDB #673 IN>4 Trip DDB #674 Aid1 DEF Trip3Ph DDB #641

1

Trip Inputs 3Ph DDB #529

Aid1 WI Trip 3Ph DDB #642 Aid2 DEF Trip3Ph DDB #651 Aid2 WI Trip 3Ph DDB #652 Loss ofLoad Trip DDB #654

Caution: Do Not remove "Trip Inputs" DDB signals

Pole Discrepancy DDB #699 TOR Trip Zone 1 DDB #704 TOR Trip Zone 2 DDB #705 TOR Trip Zone 3 DDB #706 TOR Trip Zone P DDB #708 TOR Trip Zone 4 DDB #707 TOR Trip CNV DDB #557 SOTF Trip CNV DDB #558 SOTF Trip Zone 1 DDB #709 SOTF Trip Zone 2 DDB #710 SOTF Trip Zone 3 DDB #711 SOTF Trip Zone P DDB #713 SOTF Trip Zone 4 DDB #712

Page 13 Page 159 of 252

MiCOM P545 Programmable Logic

This logic enables Check Synchro to function only for Live Line / Live Bus conditions.

CS1 Enabled DDB #881 Live Bus DDB #886

&

CS2 Enabled DDB #882 SysSplit Enabled DDB #885

Dead Line DDB #889

Dead Bus DDB #887

& &

Live Line DDB #888

1

Ctl Check Sync DDB #898

Safety Interlock. Logic must be satisfied before any manual CB closures can proceed.

Check Sync 1 OK DDB #883 Check Sync 2 OK DDB #884

SysChks Inactive DDB #880

AR Sys Checks OK DDB #899

Force 3 pole DDB #858 Aid 1 Chan Fail DDB #317

1

Force 3Pole Trip DDB #533

1

BAR DDB #448

Aid 2 Chan Fail DDB #318 Signalling Fail DDB #311

Input L16 DDB #047

Default PSL blocks autoreclose if any aided scheme channel fails.

Power Swing DDB #297

Inhibit WI DDB #458

Page 14 Page 160 of 252

A

B30 Funct 87, 49

Page 161 of 252

MiCOM S1 Studio

Page: 1

Settings File Report File: 87C_49.set Model Number: P545216C6M0540K

Printed on: 02/08/2010 15:27:18

: SYSTEM DATA:

00.01: 00.02: 00.03: 00.04: 00.05: 00.06: 00.08: 00.09: 00.0A: 00.0B: 00.0C: 00.0D: 00.0E: 00.10: 00.11: 00.20: 00.21: 00.22: 00.50: 00.51: 00.52: 00.D0: 00.D1: 00.D2: 00.D3:

Language:English Password:**** Sys Fn Links:0 Description:87C/49C-1 Plant Reference:66kV Cab. Tr.B30 Model Number:P545216C6M0540K Serial Number:336820P Frequency:50 Hz Comms Level:2 Relay Address:1 Plant Status:0000000000000010 Control Status:0000000000000000 Active Group:1 CB Trip/Close:No Operation Software Ref. 1:P545____6__540_F Opto I/P Status:000000000000000000000000 Relay O/P Status:00000000000000000000000000000000 Alarm Status 1:00000000000000000000000000000000 Alarm Status 1:00000000000000000000000000000000 Alarm Status 2:00000000000000000000000000000000 Alarm Status 3:00000000000000000000000000000000 Access Level:2 Password Control:2 Password Level 1:**** Password Level 2:****

: CB CONTROL: : DATE AND TIME: : CONFIGURATION:

09.01: 09.02: 09.03: 09.04: 09.05: 09.06: 09.07: 09.08: 09.09: 09.0A: 09.0B: 09.0C: 09.0F: 09.10: 09.11: 09.12: 09.13: 09.15: 09.16: 09.17:

Restore Defaults:No Operation Setting Group:Select via Menu Active Settings:Group 1 Save Changes:No Operation Copy From:Group 1 Copy To:No Operation Setting Group 1:Enabled Setting Group 2:Disabled Setting Group 3:Disabled Setting Group 4:Disabled Distance:Disabled Directional E/F:Disabled Phase Diff:Enabled Overcurrent:Disabled Neg Sequence O/C:Disabled Broken Conductor:Disabled Earth Fault:Disabled Sensitive E/F:Disabled Residual O/V NVD:Disabled Thermal Overload:Enabled

- Settings File Report -

Page 162 of 252

MiCOM S1 Studio

Page: 2

Settings File Report File: 87C_49.set Model Number: P545216C6M0540K 09.18: 09.1D: 09.1E: 09.1F: 09.20: 09.21: 09.23: 09.24: 09.25: 09.26: 09.28: 09.29: 09.2A: 09.2B: 09.2C: 09.2D: 09.2E: 09.2F: 09.35: 09.36: 09.39: 09.50: 09.FF:

Printed on: 02/08/2010 15:27:18

PowerSwing Block:Disabled Volt Protection:Disabled Freq Protection:Disabled df/dt Protection:Disabled CB Fail:Disabled Supervision:Disabled System Checks:Disabled Auto-Reclose:Disabled Input Labels:Visible Output Labels:Visible CT & VT Ratios:Visible Record Control:Visible Disturb Recorder:Visible Measure't Setup:Visible Comms Settings:Visible Commission Tests:Visible Setting Values:Secondary Control Inputs:Visible Ctrl I/P Config:Visible Ctrl I/P Labels:Visible Direct Access:Enabled Function Key:Visible LCD Contrast:10

: CT AND VT RATIOS:

0A.01: 0A.02: 0A.03: 0A.04: 0A.07: 0A.08: 0A.0B: 0A.0C: 0A.0D: 0A.0E: 0A.0F: 0A.10: 0A.11: 0A.13: 0A.14: 0A.18:

Main VT Primary:66.00 kV Main VT Sec'y:110.0 V C/S VT Primary:66.00 kV C/S VT Secondary:110.0 V Phase CT Primary:400.0 A Phase CT Sec'y:1.000 A SEF CT Primary:400.0 A SEF CT Secondary:1.000 A MComp CT Primary:400.0 A MComp CT Sec'y:1.000 A C/S Input:A-N Main VT Location:Line CT Polarity:Standard SEF CT Polarity:Standard M CT Polarity:Standard VT Connected:No

: RECORD CONTROL: : DISTURB RECORDER:

0C.01: 0C.02: 0C.03: 0C.04: 0C.05: 0C.06: 0C.07:

Duration:2.000 s Trigger Position:33.30% Trigger Mode:Single Analog Channel 1:VA Analog Channel 2:VB Analog Channel 3:VC Analog Channel 4:IA

- Settings File Report -

Page 163 of 252

MiCOM S1 Studio

Page: 3

Settings File Report File: 87C_49.set Model Number: P545216C6M0540K 0C.08: 0C.09: 0C.0A: 0C.0B: 0C.0C: 0C.0D: 0C.0E: 0C.0F: 0C.10: 0C.11: 0C.12: 0C.13: 0C.14: 0C.15: 0C.16: 0C.17: 0C.18: 0C.19: 0C.1A: 0C.1B: 0C.1C: 0C.1D: 0C.1E: 0C.1F: 0C.20: 0C.21: 0C.22: 0C.23: 0C.24: 0C.25: 0C.26: 0C.27: 0C.28: 0C.29: 0C.2A: 0C.2B: 0C.2C: 0C.2D: 0C.2E: 0C.2F: 0C.30: 0C.31: 0C.32: 0C.33: 0C.34: 0C.35: 0C.36: 0C.37: 0C.38:

Printed on: 02/08/2010 15:27:18

Analog Channel 5:IB Analog Channel 6:IC Analog Channel 7:IN Analog Channel 8:IN Sensitive Digital Input 1:Diff Trip Input 1 Trigger:No Trigger Digital Input 2:Thermal Trip Input 2 Trigger:No Trigger Digital Input 3:Relay 3 Input 3 Trigger:Trigger L/H Digital Input 4:Thermal Alarm Input 4 Trigger:No Trigger Digital Input 5:Trip Output A Input 5 Trigger:No Trigger Digital Input 6:Trip Output B Input 6 Trigger:No Trigger Digital Input 7:Trip Output C Input 7 Trigger:No Trigger Digital Input 8:Relay 8 Input 8 Trigger:No Trigger Digital Input 9:Relay 9 Input 9 Trigger:No Trigger Digital Input 10:Relay 10 Input 10 Trigger:No Trigger Digital Input 11:Relay 11 Input 11 Trigger:No Trigger Digital Input 12:Relay 12 Input 12 Trigger:No Trigger Digital Input 13:Relay 13 Input 13 Trigger:No Trigger Digital Input 14:Relay 14 Input 14 Trigger:No Trigger Digital Input 15:Relay 15 Input 15 Trigger:No Trigger Digital Input 16:Relay 16 Input 16 Trigger:No Trigger Digital Input 17:Opto 1 Input 17 Trigger:No Trigger Digital Input 18:Opto 2 Input 18 Trigger:No Trigger Digital Input 19:Opto 3 Input 19 Trigger:No Trigger Digital Input 20:Opto 4 Input 20 Trigger:No Trigger Digital Input 21:Opto 5 Input 21 Trigger:No Trigger Digital Input 22:Opto 6 Input 22 Trigger:No Trigger Digital Input 23:Opto 7

- Settings File Report -

Page 164 of 252

MiCOM S1 Studio

Page: 4

Settings File Report File: 87C_49.set Model Number: P545216C6M0540K 0C.39: 0C.3A: 0C.3B: 0C.3C: 0C.3D: 0C.3E: 0C.3F: 0C.40: 0C.41: 0C.42: 0C.43: 0C.44: 0C.45: 0C.46: 0C.47: 0C.48: 0C.49: 0C.4A: 0C.4B: 0C.50: 0C.51: 0C.52: 0C.53:

Printed on: 02/08/2010 15:27:18

Input 23 Trigger:No Trigger Digital Input 24:Opto 8 Input 24 Trigger:No Trigger Digital Input 25:Opto 9 Input 25 Trigger:No Trigger Digital Input 26:Opto 10 Input 26 Trigger:No Trigger Digital Input 27:Opto 11 Input 27 Trigger:No Trigger Digital Input 28:Opto 12 Input 28 Trigger:No Trigger Digital Input 29:Opto 13 Input 29 Trigger:No Trigger Digital Input 30:Opto 14 Input 30 Trigger:No Trigger Digital Input 31:Opto 15 Input 31 Trigger:No Trigger Digital Input 32:Opto 16 Input 32 Trigger:No Trigger Analog Channel 9:V Checksync Analog Channel10:IM Analog Channel11:IN Analog Channel12:IN

: MEASURE'T SETUP:

0D.01: 0D.02: 0D.03: 0D.04: 0D.05: 0D.06: 0D.07: 0D.08: 0D.09: 0D.0A:

Default Display:3Ph + N Current Local Values:Primary Remote Values:Primary Measurement Ref:VA Measurement Mode:0 Fix Dem Period:30.00 min Roll Sub Period:30.00 min Num Sub Periods:1 Distance Unit:Kilometres Fault Location:Distance

: COMMISSION TESTS: : CB MONITOR SETUP: : OPTO CONFIG:

11.01: Global Nominal V:110/125V 11.60: Opto Filter Cntl:111111111011011111111011 11.80: Characteristic:Standard 60%-80% : : : :

CONTROL INPUTS: CTRL I/P CONFIG: FUNCTION KEYS: PROT COMMS/ IM64:

20.01: 20.03: 20.10: 20.11: 20.12:

Scheme Setup:Dual Redundant Address:1-B Comms Mode:Standard Baud Rate Ch1:64kbits/s Baud Rate Ch2:64kbits/s

- Settings File Report -

Page 165 of 252

MiCOM S1 Studio

Page: 5

Settings File Report File: 87C_49.set Model Number: P545216C6M0540K 20.13: 20.14: 20.17: 20.18: 20.19: 20.1A: 20.1B: 20.1F: 20.20: 20.21: 20.22: 20.30: 20.31: 20.32: 20.34: 20.35: 20.36: 20.38: 20.39: 20.3A: 20.3C: 20.3D: 20.3E: 20.40: 20.41: 20.42: 20.44: 20.45: 20.46: 20.48: 20.49: 20.4A: 20.4C: 20.4D: 20.4E:

Printed on: 02/08/2010 15:27:18

Clock Source Ch1:Internal Clock Source Ch2:Internal Comm Delay Tol:350.0 us Comm Fail Timer:10.00 s Comm Fail Mode:Ch 1 and 2 Fail GPS Sync:Disabled Char Mod Time:500.0 ms Alarm Level:25.00% Prop Delay Stats:Enabled MaxCh1 PropDelay:15.00 ms MaxCh2 PropDelay:15.00 ms IM1 Cmd Type:Permissive IM1 Fallbck Mode:Default IM1 Default Val:0 IM2 Cmd Type:Permissive IM2 Fallbck Mode:Default IM2 Default Val:0 IM3 Cmd Type:Permissive IM3 Fallbck Mode:Default IM3 Default Val:0 IM4 Cmd Type:Permissive IM4 Fallbck Mode:Default IM4 Default Val:0 IM5 Cmd Type:Permissive IM5 Fallbck Mode:Default IM5 Default Val:0 IM6 Cmd Type:Permissive IM6 Fallbck Mode:Default IM6 Default Val:0 IM7 Cmd Type:Permissive IM7 Fallbck Mode:Default IM7 Default Val:0 IM8 Cmd Type:Permissive IM8 Fallbck Mode:Default IM8 Default Val:0

: CTRL I/P LABELS: : Group 1:

: GROUP 1 LINE PARAMETERS: : GROUP 1 PHASE DIFF: 33.01: Phase Diff:Enabled 33.06: Phase Is1:200.0 mA 33.07: Phase Is2:2.000 A 33.08: Phase k1:30.00% 33.09: Phase k2:150.0% 33.0A: Phase Char:DT 33.0B: Phase Time Delay:0 s 33.0E: PIT Time:0 s 33.0F: Ph CT Corr'tion:1.000 33.10: Compensation:None

- Settings File Report -

Page 166 of 252

MiCOM S1 Studio

Page: 6

Settings File Report File: 87C_49.set Model Number: P545216C6M0540K

Printed on: 02/08/2010 15:27:18

33.17: PIT I selection:Remote : GROUP 1 SCHEME LOGIC: : GROUP 1 THERMAL OVERLOAD: 3C.01: Characteristic:Single 3C.02: Thermal Trip:960.0 mA 3C.03: Thermal Alarm:90.00% 3C.04: Time Constant 1:1.000 min : GROUP 1 CB FAIL & P.DEAD: : GROUP 1 INPUT LABELS: 4A.01: Opto Input 1:L1IT SEND,BB,LBB 4A.02: Opto Input 2:L2 CB CLOSE ORDE 4A.03: Opto Input 3:L3 SPARE-1 4A.04: Opto Input 4:L4 SPARE-2 4A.05: Opto Input 5:L5 NOT USED 4A.06: Opto Input 6:L6 NOT USED 4A.07: Opto Input 7:L7 NOT USED 4A.08: Opto Input 8:L8 NOT USED 4A.09: Opto Input 9:L9 ES OPEN STS 4A.0A: Opto Input 10:L10 ES CLOSE STS 4A.0B: Opto Input 11:L11 CB OPEN STS 4A.0C: Opto Input 12:L12 CB CLOSE STS 4A.0D: Opto Input 13:L13 NOT USED 4A.0E: Opto Input 14:L14 SPARE-3 4A.0F: Opto Input 15:L15 SPARE-4 4A.10: Opto Input 16:L16 NOT USED 4A.11: Opto Input 17:L17 SPARE-5 4A.12: Opto Input 18:L18 SPARE-6 4A.13: Opto Input 19:L19 NOT USED 4A.14: Opto Input 20:L20 NOT USED 4A.15: Opto Input 21:L21 NOT USED 4A.16: Opto Input 22:L22 NOT USED 4A.17: Opto Input 23:L23 NOT USED 4A.18: Opto Input 24:L24 TEST MODE : GROUP 1 OUTPUT 4B.01: Relay 4B.02: Relay 4B.03: Relay 4B.04: Relay 4B.05: Relay 4B.06: Relay 4B.07: Relay 4B.08: Relay 4B.09: Relay 4B.0A: Relay 4B.0B: Relay 4B.0C: Relay 4B.0D: Relay 4B.0E: Relay 4B.0F: Relay

LABELS: 1:R1 TO 86 TRIP 2:R2 IT RECEIVE-1 3:R3TRIP TC-1 4:R4 N0T USED 5:R5 N0T USED 6:R6 N0T USED 7:R7 N0T USED 8:R8 N0T USED 9:R9 ANY TRIP SPAR 10:R10ANY TRIP SPAR 11:R11 IT RECEIVE-1 12:R12 IT SEND-1 13:R13 NOT USED 14:R14 NOT USED 15:R15 NOT USED

- Settings File Report -

Page 167 of 252

MiCOM S1 Studio

Page: 7

Settings File Report File: 87C_49.set Model Number: P545216C6M0540K 4B.10: 4B.11: 4B.12: 4B.13: 4B.14: 4B.15: 4B.16: 4B.17: 4B.18: 4B.19: 4B.1A: 4B.1B: 4B.1C: 4B.1D: 4B.1E: 4B.1F: 4B.20:

Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay

16:R16 17:R17 18:R18 19:R19 20:R20 21:R21 22:R22 23:R23 24:R24 25:R25 26:R26 27:R27 28:R28 29:R29 30:R30 31:R31 32:R32

NOT NOT NOT NOT NOT NOT NOT NOT NOT NOT NOT NOT NOT NOT NOT NOT NOT

Printed on: 02/08/2010 15:27:18

USED USED USED USED USED USED USED USED USED USED USED USED USED USED USED USED USED

- Settings File Report -

Page 168 of 252

MiCOM P545 Programmable Logic

Opto Input Mappings

L9 ES GXX1 OPEN DDB #040

IM64 Ch1 Output1 DDB #112

1

L10ES GXX1 CLOSE DDB #041

IM64 Ch2 Output1 DDB #120

IM64 Ch1 Output2 DDB #113

1

IM64 Ch2 Output2 DDB #121

L11 CB GXX0 OPEN DDB #042

IM64 Ch1 Output3 DDB #114

1

IM64 Ch2 Output3 DDB #122 L12CB GXX0 CLOSE DDB #043

IM64 Ch1 Output4 DDB #115

1

IM64 Ch2 Output4 DDB #123

1

L21LI/VT MCB TR DDB #052

L24 TEST MODE DDB #055

MCB/VTS DDB #438

1

Test Mode DDB #459

Aided1 Scheme Rx DDB #493 L5 NOT USED DDB #036

L6 NOT USED DDB #037

C Diff Failure DDB #313

Aided2 Scheme Rx DDB #507

Non Latching

FnKey LED5 Red DDB #1048 FnKey LED5 Grn DDB #1049

Page 1

Page 169 of 252

MiCOM P545 Programmable Logic Output Contacts

Trip 3ph DDB #526

100

Diff Trip DDB #582

.

1

R1 86-1 TRIP DDB #000

Dwell 0

Thermal Trip DDB #680

0

Aided 2 Receive DDB #508

R2 IT REC-1 TR DDB #001

Pick-Up

Aided 1 Receive DDB #494

0

1 0

Trip Output A DDB #523

R3 TRIP TC1 R-PH DDB #002

Pick-Up 0

0 Trip Output B DDB #524

R5 TRIP TC1 Y-PH DDB #004

Pick-Up 0 0

Trip Output C DDB #525

R6 TRIP TC1 B-PH DDB #005

Pick-Up 0 0

Any Trip DDB #522

R9ANY TRIP SPARE DDB #008

Pick-Up

1

0 0 R10ANY TRIP SPAR DDB #009

Pick-Up 0 Aided 1 Send DDB #498 Aided 2 Send DDB #514

0

1

R12 IT SEND-1 DDB #011

Pick-Up 0

0 Trip Output A DDB #523

R17 NOT USED DDB #016

Pick-Up 0 0

Trip Output B DDB #524

R18 NOT USED DDB #017

Pick-Up 0 0

Trip Output C DDB #525

R19 NOT USED DDB #018

Pick-Up 0 0

Aided 2 Send DDB #514

R27 NOT USED DDB #026

Pick-Up 0 0

Aided 1 Send DDB #498

R28 NOT USED DDB #027

Pick-Up 0

Page 2

Page 170 of 252

MiCOM P545 Programmable Logic Diff Trip DDB #582

LED1 Red DDB #1024

Latching

Diff Trip A DDB #583

LED1 Grn DDB #1025 LED2 Red DDB #1026

Latching

Diff Trip B DDB #584

LED2 Grn DDB #1027 LED3 Red DDB #1028

Latching

Diff Trip C DDB #585

LED3 Grn DDB #1029 LED4 Red DDB #1030

Latching

LED4 Grn DDB #1031

IM64 Ch1 Input 1 DDB #096

1

IM64 Ch2 Input 1 DDB #104

FnKey LED1 Red DDB #1040

Non Latching

IM64 Ch1 Input 2 DDB #097

FnKey LED1 Grn DDB #1041

1

IM64 Ch2 Input 2 DDB #105

IM64 Ch1 Input 3 DDB #098 IM64 Ch2 Input 3 DDB #106

FnKey LED2 Red DDB #1042

Non Latching

1

FnKey LED2 Grn DDB #1043

IM64 Ch1 Input 4 DDB #099 IM64 Ch2 Input 4 DDB #107

1 Signalling Fail DDB #311

1

Test Loopback DDB #291

FnKey LED10 Red DDB #1058

Non Latching

Signalling Fail DDB #311

FnKey LED10 Grn DDB #1059

1 .

Diff Trip DDB #582

20 Thermal Trip DDB #680

SOTF Trip Zone 2 DDB #710

Fault REC TRIG DDB #702

Dwell

.

0

1

SOTF Trip Zone 3 DDB #711

SOTF Trip Zone 4 DDB #712

Page 171 of 252

MiCOM P545 Programmable Logic Output Contacts

SignalFail Ch1Rx DDB #1120 SignalFail Ch1Tx DDB #1121

1

SR User Alarm 1 DDB #344

SignalFail Ch2Rx DDB #1130 SignalFail Ch2Tx DDB #1131

Page 4

Page 172 of 252

Start Phase Mappings. Used in Fault Record & on LCD Display

MiCOM P545 Programmable Logic

Diff Start A DDB #738

1

Started Phase A DDB #956

Caution: Do Not remove "Started Phase" DDB signals Diff Start B DDB #739

1

Started Phase B DDB #957

1

Diff Start C DDB #740

1

Any Start DDB #736

Started Phase C DDB #958

Any Phase Start >>page 7

This logic ensures correct N indications for faults involving ground. The pulse prevents pole scatter affecting the N indication.

Page 173 of 252

Diff Trip A DDB #583 Diff InterTrip A DDB #587

1

Faulted Phase A DDB #952

Aided 1 Trip A DDB #633 Aid 1 WI Trip A DDB #637 Aided 2 Trip A DDB #643 Aid 2 WI Trip A DDB #647

Diff Trip B DDB #584 Diff InterTrip B DDB #588

Aided 1 Trip B DDB #634

1

Faulted Phase B DDB #953

Aid 1 WI Trip B DDB #638 Aided 2 Trip B DDB #644 Aid 2 WI Trip B DDB #648 Diff Trip C DDB #585 Diff InterTrip C DDB #589

1

Faulted Phase C DDB #954

Aided 1 Trip C DDB #635 Aid 1 WI Trip C DDB #639 Aided 2 Trip C DDB #645 Aid 2 WI Trip C DDB #649

1

Faulted Phase N DDB #955

Aided 1 Trip N DDB #636 Aided 2 Trip N DDB #646 IN>1 Trip DDB #671

Page 174 of 252

A

B40 Funct 87, 49

Page 175 of 252

MiCOM S1 Studio

Page: 1

Settings File Report File: 87C_49.set Model Number: P545216C6M0540K

Printed on: 02/08/2010 15:30:56

: SYSTEM DATA:

00.01: 00.02: 00.03: 00.04: 00.05: 00.06: 00.08: 00.09: 00.0A: 00.0B: 00.0C: 00.0D: 00.0E: 00.10: 00.11: 00.20: 00.21: 00.22: 00.50: 00.51: 00.52: 00.D0: 00.D1: 00.D2: 00.D3:

Language:English Password:**** Sys Fn Links:0 Description:87C/49C-1 Plant Reference:66kV Cab. Tr.B40 Model Number:P545216C6M0540K Serial Number:336820P Frequency:50 Hz Comms Level:2 Relay Address:1 Plant Status:0000000000000010 Control Status:0000000000000000 Active Group:1 CB Trip/Close:No Operation Software Ref. 1:P545____6__540_F Opto I/P Status:000000000000000000000000 Relay O/P Status:00000000000000000000000000000000 Alarm Status 1:00000000000000000000000000000000 Alarm Status 1:00000000000000000000000000000000 Alarm Status 2:00000000000000000000000000000000 Alarm Status 3:00000000000000000000000000000000 Access Level:2 Password Control:2 Password Level 1:**** Password Level 2:****

: CB CONTROL: : DATE AND TIME: : CONFIGURATION:

09.01: 09.02: 09.03: 09.04: 09.05: 09.06: 09.07: 09.08: 09.09: 09.0A: 09.0B: 09.0C: 09.0F: 09.10: 09.11: 09.12: 09.13: 09.15: 09.16: 09.17:

Restore Defaults:No Operation Setting Group:Select via Menu Active Settings:Group 1 Save Changes:No Operation Copy From:Group 1 Copy To:No Operation Setting Group 1:Enabled Setting Group 2:Disabled Setting Group 3:Disabled Setting Group 4:Disabled Distance:Disabled Directional E/F:Disabled Phase Diff:Enabled Overcurrent:Disabled Neg Sequence O/C:Disabled Broken Conductor:Disabled Earth Fault:Disabled Sensitive E/F:Disabled Residual O/V NVD:Disabled Thermal Overload:Enabled

- Settings File Report -

Page 176 of 252

MiCOM S1 Studio

Page: 2

Settings File Report File: 87C_49.set Model Number: P545216C6M0540K 09.18: 09.1D: 09.1E: 09.1F: 09.20: 09.21: 09.23: 09.24: 09.25: 09.26: 09.28: 09.29: 09.2A: 09.2B: 09.2C: 09.2D: 09.2E: 09.2F: 09.35: 09.36: 09.39: 09.50: 09.FF:

Printed on: 02/08/2010 15:30:56

PowerSwing Block:Disabled Volt Protection:Disabled Freq Protection:Disabled df/dt Protection:Disabled CB Fail:Disabled Supervision:Disabled System Checks:Disabled Auto-Reclose:Disabled Input Labels:Visible Output Labels:Visible CT & VT Ratios:Visible Record Control:Visible Disturb Recorder:Visible Measure't Setup:Visible Comms Settings:Visible Commission Tests:Visible Setting Values:Secondary Control Inputs:Visible Ctrl I/P Config:Visible Ctrl I/P Labels:Visible Direct Access:Enabled Function Key:Visible LCD Contrast:10

: CT AND VT RATIOS:

0A.01: 0A.02: 0A.03: 0A.04: 0A.07: 0A.08: 0A.0B: 0A.0C: 0A.0D: 0A.0E: 0A.0F: 0A.10: 0A.11: 0A.13: 0A.14: 0A.18:

Main VT Primary:66.00 kV Main VT Sec'y:110.0 V C/S VT Primary:66.00 kV C/S VT Secondary:110.0 V Phase CT Primary:400.0 A Phase CT Sec'y:1.000 A SEF CT Primary:400.0 A SEF CT Secondary:1.000 A MComp CT Primary:400.0 A MComp CT Sec'y:1.000 A C/S Input:A-N Main VT Location:Line CT Polarity:Standard SEF CT Polarity:Standard M CT Polarity:Standard VT Connected:No

: RECORD CONTROL: : DISTURB RECORDER:

0C.01: 0C.02: 0C.03: 0C.04: 0C.05: 0C.06: 0C.07:

Duration:2.000 s Trigger Position:33.30% Trigger Mode:Single Analog Channel 1:VA Analog Channel 2:VB Analog Channel 3:VC Analog Channel 4:IA

- Settings File Report -

Page 177 of 252

MiCOM S1 Studio

Page: 3

Settings File Report File: 87C_49.set Model Number: P545216C6M0540K 0C.08: 0C.09: 0C.0A: 0C.0B: 0C.0C: 0C.0D: 0C.0E: 0C.0F: 0C.10: 0C.11: 0C.12: 0C.13: 0C.14: 0C.15: 0C.16: 0C.17: 0C.18: 0C.19: 0C.1A: 0C.1B: 0C.1C: 0C.1D: 0C.1E: 0C.1F: 0C.20: 0C.21: 0C.22: 0C.23: 0C.24: 0C.25: 0C.26: 0C.27: 0C.28: 0C.29: 0C.2A: 0C.2B: 0C.2C: 0C.2D: 0C.2E: 0C.2F: 0C.30: 0C.31: 0C.32: 0C.33: 0C.34: 0C.35: 0C.36: 0C.37: 0C.38:

Printed on: 02/08/2010 15:30:56

Analog Channel 5:IB Analog Channel 6:IC Analog Channel 7:IN Analog Channel 8:IN Sensitive Digital Input 1:Diff Trip Input 1 Trigger:No Trigger Digital Input 2:Thermal Trip Input 2 Trigger:No Trigger Digital Input 3:Relay 3 Input 3 Trigger:Trigger L/H Digital Input 4:Thermal Alarm Input 4 Trigger:No Trigger Digital Input 5:Trip Output A Input 5 Trigger:No Trigger Digital Input 6:Trip Output B Input 6 Trigger:No Trigger Digital Input 7:Trip Output C Input 7 Trigger:No Trigger Digital Input 8:Relay 8 Input 8 Trigger:No Trigger Digital Input 9:Relay 9 Input 9 Trigger:No Trigger Digital Input 10:Relay 10 Input 10 Trigger:No Trigger Digital Input 11:Relay 11 Input 11 Trigger:No Trigger Digital Input 12:Relay 12 Input 12 Trigger:No Trigger Digital Input 13:Relay 13 Input 13 Trigger:No Trigger Digital Input 14:Relay 14 Input 14 Trigger:No Trigger Digital Input 15:Relay 15 Input 15 Trigger:No Trigger Digital Input 16:Relay 16 Input 16 Trigger:No Trigger Digital Input 17:Opto 1 Input 17 Trigger:No Trigger Digital Input 18:Opto 2 Input 18 Trigger:No Trigger Digital Input 19:Opto 3 Input 19 Trigger:No Trigger Digital Input 20:Opto 4 Input 20 Trigger:No Trigger Digital Input 21:Opto 5 Input 21 Trigger:No Trigger Digital Input 22:Opto 6 Input 22 Trigger:No Trigger Digital Input 23:Opto 7

- Settings File Report -

Page 178 of 252

MiCOM S1 Studio

Page: 4

Settings File Report File: 87C_49.set Model Number: P545216C6M0540K 0C.39: 0C.3A: 0C.3B: 0C.3C: 0C.3D: 0C.3E: 0C.3F: 0C.40: 0C.41: 0C.42: 0C.43: 0C.44: 0C.45: 0C.46: 0C.47: 0C.48: 0C.49: 0C.4A: 0C.4B: 0C.50: 0C.51: 0C.52: 0C.53:

Printed on: 02/08/2010 15:30:56

Input 23 Trigger:No Trigger Digital Input 24:Opto 8 Input 24 Trigger:No Trigger Digital Input 25:Opto 9 Input 25 Trigger:No Trigger Digital Input 26:Opto 10 Input 26 Trigger:No Trigger Digital Input 27:Opto 11 Input 27 Trigger:No Trigger Digital Input 28:Opto 12 Input 28 Trigger:No Trigger Digital Input 29:Opto 13 Input 29 Trigger:No Trigger Digital Input 30:Opto 14 Input 30 Trigger:No Trigger Digital Input 31:Opto 15 Input 31 Trigger:No Trigger Digital Input 32:Opto 16 Input 32 Trigger:No Trigger Analog Channel 9:V Checksync Analog Channel10:IM Analog Channel11:IN Analog Channel12:IN

: MEASURE'T SETUP:

0D.01: 0D.02: 0D.03: 0D.04: 0D.05: 0D.06: 0D.07: 0D.08: 0D.09: 0D.0A:

Default Display:3Ph + N Current Local Values:Primary Remote Values:Primary Measurement Ref:VA Measurement Mode:0 Fix Dem Period:30.00 min Roll Sub Period:30.00 min Num Sub Periods:1 Distance Unit:Kilometres Fault Location:Distance

: COMMISSION TESTS: : CB MONITOR SETUP: : OPTO CONFIG:

11.01: Global Nominal V:110/125V 11.60: Opto Filter Cntl:111111111011011111111011 11.80: Characteristic:Standard 60%-80% : : : :

CONTROL INPUTS: CTRL I/P CONFIG: FUNCTION KEYS: PROT COMMS/ IM64:

20.01: 20.03: 20.10: 20.11: 20.12:

Scheme Setup:Dual Redundant Address:1-A Comms Mode:Standard Baud Rate Ch1:64kbits/s Baud Rate Ch2:64kbits/s

- Settings File Report -

Page 179 of 252

MiCOM S1 Studio

Page: 5

Settings File Report File: 87C_49.set Model Number: P545216C6M0540K 20.13: 20.14: 20.17: 20.18: 20.19: 20.1A: 20.1B: 20.1F: 20.20: 20.21: 20.22: 20.30: 20.31: 20.32: 20.34: 20.35: 20.36: 20.38: 20.39: 20.3A: 20.3C: 20.3D: 20.3E: 20.40: 20.41: 20.42: 20.44: 20.45: 20.46: 20.48: 20.49: 20.4A: 20.4C: 20.4D: 20.4E:

Printed on: 02/08/2010 15:30:56

Clock Source Ch1:Internal Clock Source Ch2:Internal Comm Delay Tol:350.0 us Comm Fail Timer:10.00 s Comm Fail Mode:Ch 1 and 2 Fail GPS Sync:Disabled Char Mod Time:500.0 ms Alarm Level:25.00% Prop Delay Stats:Enabled MaxCh1 PropDelay:15.00 ms MaxCh2 PropDelay:15.00 ms IM1 Cmd Type:Permissive IM1 Fallbck Mode:Default IM1 Default Val:0 IM2 Cmd Type:Permissive IM2 Fallbck Mode:Default IM2 Default Val:0 IM3 Cmd Type:Permissive IM3 Fallbck Mode:Default IM3 Default Val:0 IM4 Cmd Type:Permissive IM4 Fallbck Mode:Default IM4 Default Val:0 IM5 Cmd Type:Permissive IM5 Fallbck Mode:Default IM5 Default Val:0 IM6 Cmd Type:Permissive IM6 Fallbck Mode:Default IM6 Default Val:0 IM7 Cmd Type:Permissive IM7 Fallbck Mode:Default IM7 Default Val:0 IM8 Cmd Type:Permissive IM8 Fallbck Mode:Default IM8 Default Val:0

: CTRL I/P LABELS: : Group 1:

: : : :

GROUP 1 LINE PARAMETERS: GROUP 1 PHASE DIFF: GROUP 1 SCHEME LOGIC: GROUP 1 THERMAL OVERLOAD: 3C.01: Characteristic:Single 3C.02: Thermal Trip:960.0 mA 3C.03: Thermal Alarm:90.00% 3C.04: Time Constant 1:1.000 min

: GROUP 1 CB FAIL & P.DEAD: : GROUP 1 INPUT LABELS: 4A.01: Opto Input 1:L1IT SEND,BB,LBB 4A.02: Opto Input 2:L2 CB CLOSE ORDE

- Settings File Report -

Page 180 of 252

MiCOM S1 Studio

Page: 6

Settings File Report File: 87C_49.set Model Number: P545216C6M0540K 4A.03: 4A.04: 4A.05: 4A.06: 4A.07: 4A.08: 4A.09: 4A.0A: 4A.0B: 4A.0C: 4A.0D: 4A.0E: 4A.0F: 4A.10: 4A.11: 4A.12: 4A.13: 4A.14: 4A.15: 4A.16: 4A.17: 4A.18:

Opto Opto Opto Opto Opto Opto Opto Opto Opto Opto Opto Opto Opto Opto Opto Opto Opto Opto Opto Opto Opto Opto

Input Input Input Input Input Input Input Input Input Input Input Input Input Input Input Input Input Input Input Input Input Input

: GROUP 1 OUTPUT 4B.01: Relay 4B.02: Relay 4B.03: Relay 4B.04: Relay 4B.05: Relay 4B.06: Relay 4B.07: Relay 4B.08: Relay 4B.09: Relay 4B.0A: Relay 4B.0B: Relay 4B.0C: Relay 4B.0D: Relay 4B.0E: Relay 4B.0F: Relay 4B.10: Relay 4B.11: Relay 4B.12: Relay 4B.13: Relay 4B.14: Relay 4B.15: Relay 4B.16: Relay 4B.17: Relay 4B.18: Relay 4B.19: Relay 4B.1A: Relay

Printed on: 02/08/2010 15:30:56

3:L3 SPARE-1 4:L4 SPARE-2 5:L5 NOT USED 6:L6 NOT USED 7:L7 NOT USED 8:L8 NOT USED 9:L9 ES OPEN STS 10:L10 ES CLOSE STS 11:L11 CB OPEN STS 12:L12 CB CLOSE STS 13:L13 NOT USED 14:L14 SPARE-3 15:L15 SPARE-4 16:L16 NOT USED 17:L17 SPARE-5 18:L18 SPARE-6 19:L19 NOT USED 20:L20 NOT USED 21:L21 NOT USED 22:L22 NOT USED 23:L23 NOT USED 24:L24 TEST MODE

LABELS: 1:R1 TO 86 TRIP 2:R2 IT RECEIVE-1 3:R3TRIP TC-1 4:R4 N0T USED 5:R5 N0T USED 6:R6 N0T USED 7:R7 N0T USED 8:R8 N0T USED 9:R9 ANY TRIP SPAR 10:R10ANY TRIP SPAR 11:R11 IT RECEIVE-1 12:R12 IT SEND-1 13:R13 NOT USED 14:R14 NOT USED 15:R15 NOT USED 16:R16 NOT USED 17:R17 NOT USED 18:R18 NOT USED 19:R19 NOT USED 20:R20 NOT USED 21:R21 NOT USED 22:R22 NOT USED 23:R23 NOT USED 24:R24 NOT USED 25:R25 NOT USED 26:R26 NOT USED

- Settings File Report -

Page 181 of 252

MiCOM S1 Studio

Page: 7

Settings File Report File: 87C_49.set Model Number: P545216C6M0540K 4B.1B: 4B.1C: 4B.1D: 4B.1E: 4B.1F: 4B.20:

Relay Relay Relay Relay Relay Relay

27:R27 28:R28 29:R29 30:R30 31:R31 32:R32

NOT NOT NOT NOT NOT NOT

Printed on: 02/08/2010 15:30:56

USED USED USED USED USED USED

- Settings File Report -

Page 182 of 252

MiCOM P545 Programmable Logic

Opto Input Mappings

L9 ES GXX1 OPEN DDB #040

IM64 Ch1 Output1 DDB #112

1

L10ES GXX1 CLOSE DDB #041

IM64 Ch2 Output1 DDB #120

IM64 Ch1 Output2 DDB #113

1

IM64 Ch2 Output2 DDB #121

L11 CB GXX0 OPEN DDB #042

IM64 Ch1 Output3 DDB #114

1

IM64 Ch2 Output3 DDB #122 L12CB GXX0 CLOSE DDB #043

IM64 Ch1 Output4 DDB #115

1

IM64 Ch2 Output4 DDB #123

1

L21LI/VT MCB TR DDB #052

L24 TEST MODE DDB #055

MCB/VTS DDB #438

1

Test Mode DDB #459

Aided1 Scheme Rx DDB #493 L5 NOT USED DDB #036

L6 NOT USED DDB #037

C Diff Failure DDB #313

Aided2 Scheme Rx DDB #507

Non Latching

FnKey LED5 Red DDB #1048 FnKey LED5 Grn DDB #1049

Page 1

Page 183 of 252

MiCOM P545 Programmable Logic Output Contacts

Trip 3ph DDB #526

100

Diff Trip DDB #582

.

1

R1 86-1 TRIP DDB #000

Dwell 0

Thermal Trip DDB #680

0

Aided 2 Receive DDB #508

R2 IT REC-1 TR DDB #001

Pick-Up

Aided 1 Receive DDB #494

0

1 0

Trip Output A DDB #523

R3 TRIP TC1 R-PH DDB #002

Pick-Up 0

0 Trip Output B DDB #524

R5 TRIP TC1 Y-PH DDB #004

Pick-Up 0 0

Trip Output C DDB #525

R6 TRIP TC1 B-PH DDB #005

Pick-Up 0 0

Any Trip DDB #522

R9ANY TRIP SPARE DDB #008

Pick-Up

1

0 0 R10ANY TRIP SPAR DDB #009

Pick-Up 0 Aided 1 Send DDB #498 Aided 2 Send DDB #514

0

1

R12 IT SEND-1 DDB #011

Pick-Up 0

0 Trip Output A DDB #523

R17 NOT USED DDB #016

Pick-Up 0 0

Trip Output B DDB #524

R18 NOT USED DDB #017

Pick-Up 0 0

Trip Output C DDB #525

R19 NOT USED DDB #018

Pick-Up 0 0

Aided 2 Send DDB #514

R27 NOT USED DDB #026

Pick-Up 0 0

Aided 1 Send DDB #498

R28 NOT USED DDB #027

Pick-Up 0

Page 2

Page 184 of 252

MiCOM P545 Programmable Logic Diff Trip DDB #582

LED1 Red DDB #1024

Latching

Diff Trip A DDB #583

LED1 Grn DDB #1025 LED2 Red DDB #1026

Latching

Diff Trip B DDB #584

LED2 Grn DDB #1027 LED3 Red DDB #1028

Latching

Diff Trip C DDB #585

LED3 Grn DDB #1029 LED4 Red DDB #1030

Latching

LED4 Grn DDB #1031

IM64 Ch1 Input 1 DDB #096

1

IM64 Ch2 Input 1 DDB #104

FnKey LED1 Red DDB #1040

Non Latching

IM64 Ch1 Input 2 DDB #097

FnKey LED1 Grn DDB #1041

1

IM64 Ch2 Input 2 DDB #105

IM64 Ch1 Input 3 DDB #098 IM64 Ch2 Input 3 DDB #106

FnKey LED2 Red DDB #1042

Non Latching

1

FnKey LED2 Grn DDB #1043

IM64 Ch1 Input 4 DDB #099 IM64 Ch2 Input 4 DDB #107

1 Signalling Fail DDB #311

1

Test Loopback DDB #291

FnKey LED10 Red DDB #1058

Non Latching

Signalling Fail DDB #311

FnKey LED10 Grn DDB #1059

1 .

Diff Trip DDB #582

20 Thermal Trip DDB #680

SOTF Trip Zone 2 DDB #710

Fault REC TRIG DDB #702

Dwell

.

0

1

SOTF Trip Zone 3 DDB #711

SOTF Trip Zone 4 DDB #712

Page 185 of 252

MiCOM P545 Programmable Logic Output Contacts

SignalFail Ch1Rx DDB #1120 SignalFail Ch1Tx DDB #1121

1

SR User Alarm 1 DDB #344

SignalFail Ch2Rx DDB #1130 SignalFail Ch2Tx DDB #1131

Page 4

Page 186 of 252

Start Phase Mappings. Used in Fault Record & on LCD Display

MiCOM P545 Programmable Logic

Diff Start A DDB #738

1

Started Phase A DDB #956

Caution: Do Not remove "Started Phase" DDB signals Diff Start B DDB #739

1

Started Phase B DDB #957

1

Diff Start C DDB #740

1

Any Start DDB #736

Started Phase C DDB #958

Any Phase Start >>page 7

This logic ensures correct N indications for faults involving ground. The pulse prevents pole scatter affecting the N indication.

Page 187 of 252

Diff Trip A DDB #583 Diff InterTrip A DDB #587

1

Faulted Phase A DDB #952

Aided 1 Trip A DDB #633 Aid 1 WI Trip A DDB #637 Aided 2 Trip A DDB #643 Aid 2 WI Trip A DDB #647

Diff Trip B DDB #584 Diff InterTrip B DDB #588

Aided 1 Trip B DDB #634

1

Faulted Phase B DDB #953

Aid 1 WI Trip B DDB #638 Aided 2 Trip B DDB #644 Aid 2 WI Trip B DDB #648 Diff Trip C DDB #585 Diff InterTrip C DDB #589

1

Faulted Phase C DDB #954

Aided 1 Trip C DDB #635 Aid 1 WI Trip C DDB #639 Aided 2 Trip C DDB #645 Aid 2 WI Trip C DDB #649

1

Faulted Phase N DDB #955

Aided 1 Trip N DDB #636 Aided 2 Trip N DDB #646 IN>1 Trip DDB #671

Page 188 of 252

A

B30_B40_ 50_51_51N

Page 189 of 252

MiCOM S1 Studio

Page: 1

Settings File Report File: 50_51_51N.set Model Number: P141216A6M0420J

Printed on: 02/08/2010 15:35:34

: SYSTEM DATA:

00.01: 00.02: 00.03: 00.04: 00.05: 00.06: 00.08: 00.09: 00.0A: 00.0B: 00.0C: 00.0D: 00.0E: 00.10: 00.11: 00.20: 00.21: 00.22: 00.30: 00.40: 00.50: 00.51: 00.52: 00.D0: 00.D1: 00.D2: 00.D3:

Language:English Password:**** Sys Fn Links:0 Description:50_51_51N Plant Reference:66kV Cab Tr.B30 Model Number:P141216A6M0420J Serial Number:123456A Frequency:50 Hz Comms Level:2 Relay Address:1 Plant Status:0000000000000000 Control Status:0000000000000000 Active Group:1 CB Trip/Close:No Operation Software Ref. 1:P141____4__420_A Opto I/P Status:01000000 Relay O/P Status:0000000 Alarm Status 1:00000000000000000000000000000000 Opto I/P Status:01000000 Relay O/P Status:0000000 Alarm Status 1:00000000000000000000000000000000 Alarm Status 2:00000000000000000000000000000000 Alarm Status 3:00000000000000000000000000000100 Access Level:2 Password Control:2 Password Level 1:**** Password Level 2:****

: CB CONTROL: : DATE AND TIME: : CONFIGURATION:

09.01: 09.02: 09.03: 09.04: 09.05: 09.06: 09.07: 09.08: 09.09: 09.0A: 09.0B: 09.10: 09.11: 09.12: 09.13: 09.14: 09.15: 09.16:

Restore Defaults:No Operation Setting Group:Select via Menu Active Settings:Group 1 Save Changes:No Operation Copy From:Group 1 Copy To:No Operation Setting Group 1:Enabled Setting Group 2:Disabled Setting Group 3:Disabled Setting Group 4:Disabled System Config:Invisible Overcurrent:Enabled Neg Sequence O/C:Disabled Broken Conductor:Disabled Earth Fault 1:Disabled Earth Fault 2:Disabled SEF/REF Prot'n:Disabled Residual O/V NVD:Disabled

- Settings File Report -

Page 190 of 252

MiCOM S1 Studio

Page: 2

Settings File Report File: 50_51_51N.set Model Number: P141216A6M0420J 09.17: 09.18: 09.19: 09.1A: 09.1B: 09.1D: 09.1E: 09.1F: 09.20: 09.21: 09.22: 09.25: 09.26: 09.28: 09.29: 09.2A: 09.2B: 09.2C: 09.2D: 09.2E: 09.2F: 09.35: 09.36: 09.39: 09.FF:

Printed on: 02/08/2010 15:35:34

Thermal Overload:Disabled Neg Sequence O/V:Disabled Cold Load Pickup:Disabled Selective Logic:Disabled Admit Protection:Disabled Volt Protection:Disabled Freq Protection:Disabled df/dt Protection:Disabled CB Fail:Disabled Supervision:Disabled Fault Locator:Disabled Input Labels:Visible Output Labels:Visible CT & VT Ratios:Visible Record Control:Invisible Disturb Recorder:Invisible Measure't Setup:Invisible Comms Settings:Visible Commission Tests:Visible Setting Values:Secondary Control Inputs:Visible Ctrl I/P Config:Visible Ctrl I/P Labels:Visible Direct Access:Enabled LCD Contrast:11

: CT AND VT RATIOS:

0A.01: 0A.02: 0A.07: 0A.08: 0A.09: 0A.0A: 0A.0B: 0A.0C:

Main VT Primary:66.00 kV Main VT Sec'y:110.0 V Phase CT Primary:400.0 A Phase CT Sec'y:1.000 A E/F CT Primary:400.0 A E/F CT Secondary:1.000 A SEF CT Primary:1.000 A SEF CT Secondary:1.000 A

: COMMISSION TESTS: : CB MONITOR SETUP: : OPTO CONFIG:

11.01: Global Nominal V:110/125V 11.50: Opto Filter Cntl:11111111 11.80: Characteristic:Standard 60%-80% : : : : :

CONTROL INPUTS: CTRL I/P CONFIG: IED CONFIGURATOR: CTRL I/P LABELS: Group 1:

: GROUP 1 35.23: 35.24: 35.27:

OVERCURRENT: I>1 Function:IEC V Inverse I>1 Direction:Non-Directional I>1 Current Set:1.310 A

- Settings File Report -

Page 191 of 252

MiCOM S1 Studio

Page: 3

Settings File Report File: 50_51_51N.set Model Number: P141216A6M0420J 35.2A: 35.2D: 35.2F: 35.32: 35.40: 35.41: 35.44: 35.45: 35.47: 35.4E: 35.4F: 35.51: 35.52:

Printed on: 02/08/2010 15:35:34

I>1 TMS:420.0e-3 I>1 DT Adder:0 s I>1 tRESET:0 s I>2 Function:Disabled I>3 Status:Enabled I>3 Direction:Non-Directional I>3 Current Set:7.970 A I>3 Time Delay:100.0 ms I>4 Status:Disabled I> Blocking:000001111 I> Char Angle:45.00 deg V CONTROLLED O/C: VCO Status:Disabled

: GROUP 1 CB FAIL & I1 Trip DDB #243

1 I>3 Trip DDB #251

L8 TEST MODE DDB #039

1

Fault Record Trigger Mapping I>1 Trip DDB #243

Trip Command In DDB #536

1 I>3 Trip DDB #251

Fault REC TRIG DDB #144

Page : 1

Page 193 of 252

MiCOM P141 Programmable Scheme Logic Output Relay Mappings

0 R1 51N TRIP BS DDB #000

Pick-Up 0 I>1 Trip DDB #243

0

1

R2 TO TRIP 415V DDB #001

Pick-Up

I>3 Trip DDB #251

0 0 R3 HV REM SEND-2 DDB #002

Pick-Up 0 0

R4 86 TRIP DDB #003

Pick-Up 0 0

R5 ANT TRIP SPAR DDB #004

Pick-Up 0 0

R6 NOT USED DDB #005

Pick-Up 0 0

R7 NOT USED DDB #006

Pick-Up 0

Page : 2

Page 194 of 252

A

B40 RED670_87C+T SET

Page 195 of 252

8/2/2010

KHARAMAA_latest/Region/DID/66KV/B40_TYP/B40_RED_670C_T Parameter Name

IED Value

PC Value

Unit

Min

Max

B40_RED_670C_T Settings Activate setting group ActiveSetGrp

SettingGroup1

[+] Time General settings Power system Identifiers StationName

DID

StationNumber

0

ObjectName

B40

ObjectNumber

0

UnitName

RED670_C+T

UnitNumber

0

18 charact 0

99999 18 charact

0

99999 18 charact

0

99999

50.0

60.0

Primary values Frequency

50.0

Hz

[+] Communication Analog modules AnalogInputs6Iand6U 1 NAMECH1

I PH.R

RatedTrans1

1.0

CTStarPoint1

ToObject

CTsec1

13 charact A

0.1

300.0

1

A

1

10

CTprim1

400

A

1

99999

NAMECH2

I PH.Y

RatedTrans2

1.0

CTStarPoint2

ToObject

CTsec2

13 charact A

0.1

300.0

1

A

1

10

CTprim2

400

A

1

99999

NAMECH3

I PH.B

RatedTrans3

1.0

CTStarPoint3

ToObject

CTsec3

13 charact A

0.1

300.0

1

A

1

10

CTprim3

400

A

1

99999

NAMECH4

TRM40-CH4

13 charact

1 Page 196 of 252

8/2/2010

KHARAMAA_latest/Region/DID/66KV/B40_TYP/B40_RED_670C_T Parameter Name

IED Value

PC Value

Unit

Min

Max

RatedTrans4

1.0

A

0.1

300.0

CTStarPoint4

ToObject

CTsec4

1

A

1

10

CTprim4

400

A

1

99999

NAMECH5

TRM40-CH5

RatedTrans5

1.0

CTStarPoint5

ToObject

CTsec5

13 charact A

0.1

300.0

1

A

1

10

CTprim5

99999

A

1

99999

NAMECH6

TRM40-CH6

RatedTrans6

1.0

CTStarPoint6

ToObject

CTsec6

13 charact A

0.1

300.0

1

A

1

10

CTprim6

99999

A

1

99999

NAMECH7

U PH.R

RatedTrans7

110.0

V

0.1

300.0

VTsec7

110.000

V

0.001

999.999

VTprim7

1.00

kV

0.05

2000.00

NAMECH8

U PH.Y

RatedTrans8

110.0

V

0.1

300.0

VTsec8

110.000

V

0.001

999.999

VTprim8

1.00

kV

0.05

2000.00

NAMECH9

U PH.B

RatedTrans9

110.0

V

0.1

300.0

VTsec9

110.000

V

0.001

999.999

VTprim9

1.00

kV

0.05

2000.00

NAMECH10

TRM40-CH10

RatedTrans10

110.0

V

0.1

300.0

VTsec10

110.000

V

0.001

999.999

VTprim10

1.00

kV

0.05

2000.00

NAMECH11

TRM40-CH11

RatedTrans11

110.0

V

0.1

300.0

VTsec11

110.000

V

0.001

999.999

VTprim11

1.00

kV

0.05

2000.00

NAMECH12

TRM40-CH12

13 charact

13 charact

13 charact

13 charact

13 charact

13 charact

2 Page 197 of 252

8/2/2010

KHARAMAA_latest/Region/DID/66KV/B40_TYP/B40_RED_670C_T Parameter Name

IED Value

PC Value

Unit

Min

Max

RatedTrans12

110.0

V

0.1

300.0

VTsec12

110.000

V

0.001

999.999

VTprim12

1.00

kV

0.05

2000.00

LDCM312 NAMECH1

REM I PH.R

13 charact

NAMECH2

REM I PH.Y

13 charact

NAMECH3

REM I PH.B

13 charact

NAMECH4

LDCM312-CH4

13 charact

[+] Reference channel service values [+] 3PhaseAnalogGroup [+] I/O modules [+] HMI Differential protection LineTrfDiff3Terminal(PDIF,87L) LT3D NoOfTerminals

2

Chan2IsLocal

No

IBase

400.0

ZerSeqCurSubtr

On

TraAOnInpCh

2

RatVoltW1TraA

A

50.0

9999.9

66.0

kV

1.0

9999.9

RatVoltW2TraA

11.0

kV

1.0

9999.9

ClockNumTransA

1 [30 deg lag]

ZerSeqPassTraA

No

TraBOnInpCh

No Transf B

RatVoltW1TraB

1.0

kV

1.0

9999.9

RatVoltW2TraB

1.0

kV

1.0

9999.9

ClockNumTransB

0 [0 deg]

ZerSeqPassTraB

No

LineDiffLogic LDL Operation

On

Current protection PhaseOverCurrent4Step(PTOC,51/67) TOC1

3 Page 198 of 252

8/2/2010

KHARAMAA_latest/Region/DID/66KV/B40_TYP/B40_RED_670C_T Parameter Name

IED Value

MeasType

PC Value

Unit

Min

Max

DFT

[+] Voltage protection [+] Control Monitoring DisturbanceReport DisturbanceReport(RDRE) Operation

On

PreFaultRecT

0.30

s

0.05

1.00

PostFaultRecT

0.5

s

0.1

10.0

TimeLimit

2.0

s

0.5

10.0

PostRetrig

Off

ZeroAngleRef

1

Ch

1

30

OpModeTest

Off

[+] BinarySignals(RBDR) [+] AnalogSignals(RADR) [+] FaultLocator(RFLO) [+] IEC60870-5-103 Setting group N1 Differential protection LineTrfDiff3Terminal(PDIF,87L) LT3D Operation

On

IdMin

0.30

IB

0.20

2.00

EndSection1

1.09 1.1

IB

0.20

1.50

EndSection2

2.6 2.62

IB

1.00

10.00

SlopeSection2

40.0

%

10.0

50.0

SlopeSection3

80.0

%

30.0

100.0

IdMinHigh

2.00

IB

0.20

10.00

tIdMinHigh

5.000

s

0.000

60.000

IdUnre

7.4 7.36

IB

1.00

50.00

NegSeqDiffEn

On

NegSeqROA

60.0

Deg

30.0

120.0

IMinNegSeq

0.04

IB

0.01

0.20

CrossBlockEn

Yes

I2/I1Ratio

10.0

%

5.0

100.0

4 Page 199 of 252

8/2/2010

KHARAMAA_latest/Region/DID/66KV/B40_TYP/B40_RED_670C_T Parameter Name

IED Value

PC Value

Unit

Min

Max

I5/I1Ratio

25.0

%

5.0

100.0

ChargCurEnable

Off

AddDelay

Off

IMaxAddDelay

1.00

IB

0.20

5.00

tDefTime

0.000

s

0.000

6.000

tMinInv

0.010

s

0.001

6.000

CurveType

IEC Def. Time

k

1.00

0.05

1.10

p

0.02

0.01

1000.00

a

0.14

0.01

1000.00

b

1.00

0.01

1000.00

c

1.00

0.01

1000.00

IdiffAlarm

0.15

IB

0.05

1.00

tAlarmdelay

10.000

s

0.000

60.000

OpenCTEnable

Off

tOCTAlarmDelay

1.000

s

0.100

10.000

tOCTResetDelay

0.250

s

0.100

10.000

[+] Impedance Protection Current protection [+] BrokenCondCheck(PTOC,46) [+] InstPhaseOverCurrent(PIOC,50) [+] PhaseOverCurrent4Step(PTOC,51/67) [+] ResidualOverCurr4Step(PTOC,51N/67N) ThermalOverload1TimeConst(PTTR,26) THL1 Operation

On

IBase

400

A

0

99999

TRef

90

Deg

0

600

IRef

96

%IB

0

400

IMult

1

1

5

Tau

1

Min

0

1000

AlarmTemp

85

Deg

0

200

TripTemp

95

Deg

0

600

ReclTemp

75

Deg

0

600

tPulse

0.10

s

0.05

0.30

5 Page 200 of 252

8/2/2010

KHARAMAA_latest/Region/DID/66KV/B40_TYP/B40_RED_670C_T Parameter Name

IED Value

PC Value

Unit

Min

Max

AmbiSens

Off

DefaultAmbTemp

20

Deg

-50

250

DefaultTemp

50

Deg

-50

600

s

0.000

60.000

[+] Voltage protection [+] Scheme communication [+] Secondary system supervision [+] Monitoring Logic TripLogic(PTRC,94) TRP1 Operation

On

Program

1ph/3ph

TripLockout

Off

AutoLock

Off

tTripMin

0.150

[+] TripMatrix(GGIO) [+] LogicGate

6 Page 201 of 252

A

66kV UGC_7SD532_B10&B20

Page 202 of 252

SIMATIC

DID / 66_11kV / 7SD532_B10&B20/7SD532

02.08.10 17:16:31

DID / 66_11kV / 7SD532_B10&B20 MLFB: 7SD53215PB999HL6 Parameter set version: V04.62.03 Device path: \\10.178.2.32\SAS Qatar\SAS - LIVE PROJECTS\A12_Qatar Phase 8 - Kahramaa - Qatar\PH8GTC144A-AREVA\2_TECHNICAL\05_CT CALC & RElAY SETTINGS\02_RELAY SETTINGS\01_MAIN SUBSTATION\7_DOHA INDUSTRIAL-D\Rev.0\Base files\DIGSI\Did\P7DI\GV\SD\00000001 Author: Creation date: 12.05.10 14:03:42 Last modified: 02.08.10 17:08:23 Operating mode: Offline Comment: Setting values in: Secondary value description

PRINT - CONTENTS 1 Device Configuration 2 Configuration - short (column-oriented) 2.1 Binary inputs 2.2 Binary outputs 2.3 LEDs 3 General Device Settings 3.1 Group Device 4 Power System Data 1 4.1 Group Power System Data 1; Group Transformers 4.2 Group Power System Data 1; Group Power System 4.3 Group Power System Data 1; Group Breaker 4.4 Group Power System Data 1; Group CT Data 5 Oscillographic Fault Records 5.1 Group Oscillographic Fault Records 6 Settings groups 6.1 Group Power System Data 2; Group Local Line End 6.2 Group Power System Data 2; Group Line Status 6.3 Group Differential Protection; Group General 6.4 Group Differential Protection; Group Diff Protection 6.5 Group Differential Protection; Group Inrush 6.6 Group Intertrip 6.7 Group Distance protection, general settings; Group General 6.8 Group Distance protection, general settings; Group Earth faults

3 4 4 4 4 6 6 7 7 7 7 7 8 8 9 9 9 9 9 10 10 10 10 Page 1 of 17

Page 203 of 252

SIMATIC

DID / 66_11kV / 7SD532_B10&B20/7SD532

02.08.10 17:16:31

6.9 Group Distance protection, general settings; Group Time Delays 6.10 Group Distance zones (quadrilateral); Group Zone Z1 6.11 Group Distance zones (quadrilateral); Group Zone Z1B-exten. 6.12 Group Distance zones (quadrilateral); Group Zone Z2 6.13 Group Distance zones (quadrilateral); Group Zone Z3 6.14 Group Distance zones (quadrilateral); Group Zone Z4 6.15 Group Distance zones (quadrilateral); Group Zone Z5 6.16 Group Power Swing 6.17 Group Backup overcurrent; Group General 6.18 Group Backup overcurrent; Group I>> 6.19 Group Backup overcurrent; Group I> 6.20 Group Backup overcurrent; Group Inverse 6.21 Group Backup overcurrent; Group I - STUB 6.22 Group Demand Measurement Setup; Group Measurement 6.23 Group Min/Max Measurement Setup; Group Measurement 6.24 Group Measurement Supervision; Group Symmetry 6.25 Group Measurement Supervision; Group Fuse Fail. Mon. 6.26 Group Measurement Supervision; Group I/U-Monitoring 6.27 Group Measurement Supervision; Group VT mcb 6.28 Group Measurement Supervision; Group Load Angle 6.29 Group Fault Locator; Group Fault Locator 6.30 Group Thermal Overload 6.31 Group Protection Interface (Port D+E); Group General 6.32 Group Protection Interface (Port D+E); Group Interface 1 6.33 Group Protection Interface (Port D+E); Group Interface 2 6.34 Group Differential Topology

11 11 11 12 12 12 12 13 13 13 13 13 14 14 14 14 15 15 15 15 15 16 16 16 16 16

Page 2 of 17

Page 204 of 252

SIMATIC

DID / 66_11kV / 7SD532_B10&B20/7SD532

02.08.10 17:16:31

1 Device Configuration No.

Function

Scope

0103 Setting Group Change Option

Disabled

0112 Differential protection

Enabled

0115 Phase Distance

Quadrilateral

0116 Earth Distance

Quadrilateral

0120 Power Swing detection

Enabled

0121 Teleprotection for Distance prot.

Disabled

0122 DTT Direct Transfer Trip

Disabled

0124 Instantaneous HighSpeed/SOTF Overcurrent

Disabled

0125 Weak Infeed (Trip and/or Echo)

Disabled

0126 Backup overcurrent

Time Overcurrent Curve IEC

0131 Earth fault overcurrent

Disabled

0132 Teleprotection for Earth fault overcurr.

Disabled

0138 Fault Locator

Enabled

0139 Breaker Failure Protection

Disabled

0140 Trip Circuit Supervision

Disabled

0142 Thermal Overload Protection

Enabled

0144 Voltage transformers

connected

0145 Protection Interface 1 (Port D)

Enabled

0146 Protection Interface 2 (Port E)

Enabled

0149 charging current compensation

Disabled

0160 Line sections for fault locator

1 Line Section

Page 3 of 17

Page 205 of 252

SIMATIC

DID / 66_11kV / 7SD532_B10&B20/7SD532

02.08.10 17:16:31

2 Configuration - short (column-oriented) 2.1 Binary inputs No.

Binary inputs

Group

Information

1

03541 Remote Signals

>Remote Trip 1 signal input

2

00356 P.System Data 2 >Manual close signal

Type Configuration SP

H

SP

H

5

Remote Signals

BXX64 VT Disconnector Open

SP

H

6

Remote Signals

BXX64 VT Disconnector Close

SP

H

9

Remote Signals

BXX1 Earth Switch Open

SP

H

10

Remote Signals

BXX1 Earth Switch Close

SP

H

11

Remote Signals

BXX3 Disconnector Open

SP

H

12

Remote Signals

BXX3 Disconnector Close

SP

H

13

Remote Signals

BXX0 Circuit Breaker Open

SP

H

14

Remote Signals

BXX0 Circuit Breaker Close

SP

H

15

Remote Signals

BXX4 Disconnector Open

SP

H

16

Remote Signals

BXX4 Disconnector Close

SP

H

19

Remote Signals

BXXM1 Earth Switch Open

SP

H

20

Remote Signals

BXXM1 Earth Switch Close

SP

H

21

Remote Signals

BXXM2 Earth Switch Open

SP

H

22

Remote Signals

BXXM2 Earth Switch Close

SP

H

23

00361 P.System Data 2 >Failure: Feeder VT (MCB tripped)

SP

H

24

00015 Device

>Test mode

SP

L

24

03525 Diff. Prot

>Differential protection blocking signal

SP

L

2.2 Binary outputs BO

No.

Group

Information

Type Configuration

4

00511 P.System Data 2

Relay GENERAL TRIP command

OUT U

5

03545 Remote Signals

Remote Trip 1 received

OUT U

6

00511 P.System Data 2

Relay GENERAL TRIP command

OUT U

7

00169 Measurem.Superv VT Fuse Failure (alarm >10s)

OUT U

7

00170 Measurem.Superv VT Fuse Failure (alarm instantaneous)

OUT U

13 03545 Remote Signals

Remote Trip 1 received

OUT U

14 03541 Remote Signals

>Remote Trip 1 signal input

SP

U

Page 4 of 17

Page 206 of 252

SIMATIC

DID / 66_11kV / 7SD532_B10&B20/7SD532

02.08.10 17:16:31

2.3 LEDs LEDs

No.

Group

Information

Type Configuration

1

00511 P.System Data 2

Relay GENERAL TRIP command

OUT L

2

00503 P.System Data 2

Relay PICKUP Phase L1

OUT L

3

00504 P.System Data 2

Relay PICKUP Phase L2

OUT L

4

00505 P.System Data 2

Relay PICKUP Phase L3

OUT L

5

03141 Diff. Prot

Diff: General TRIP

OUT L

6

03541 Remote Signals

>Remote Trip 1 signal input

SP

6

03545 Remote Signals

Remote Trip 1 received

OUT L

7

03823 Dis. General

DisTRIP 3phase in Z1 with single-ph Flt.

OUT L

7

03824 Dis. General

DisTRIP 3phase in Z1 with multi-ph Flt.

OUT L

8

03817 Dis. General

Distance TRIP 3phase in Z2

OUT L

9

03818 Dis. General

Distance TRIP 3phase in Z3

OUT L

SOTF TRIP WITH ZONE-1B

SP

10

P.System Data 2

L

L

11

04164 Power Swing

Power Swing detected

OUT L

11

07211 Back-Up O/C

Backup O/C General TRIP command

OUT L

12

00169 Measurem.Superv VT Fuse Failure (alarm >10s)

OUT U

12

00170 Measurem.Superv VT Fuse Failure (alarm instantaneous)

OUT U

13

03148 Diff. Prot

Diff: Differential protection is blocked

OUT L

14

03230 Prot. Interface

Prot Int 1: Total receiption failure

OUT L

14

03232 Prot. Interface

Prot Int 2: Total receiption failure

OUT L

Page 5 of 17

Page 207 of 252

SIMATIC

DID / 66_11kV / 7SD532_B10&B20/7SD532

02.08.10 17:16:31

3 General Device Settings 3.1 Group Device No.

Settings

Value

Group

0610

Fault Display on LED / LCD

Display Targets on every Pickup

All

0615

Spontaneous display of flt.annunciations

YES

All

0625A Minimum hold time of lachted LEDs

0 min

All

0640

image 1

All

Start image Default Display

Page 6 of 17

Page 208 of 252

SIMATIC

DID / 66_11kV / 7SD532_B10&B20/7SD532

02.08.10 17:16:31

4 Power System Data 1 4.1 Group Power System Data 1; Group Transformers No.

Settings

Value

Group

0201 CT Starpoint

towards Line

All

0203 Rated Primary Voltage

66.0 kV

All

0204 Rated Secondary Voltage (Ph-Ph)

110 V

All

0205 CT Rated Primary Current

800 A

All

0206 CT Rated Secondary Current

1A

All

0210 U4 voltage transformer is

not connected

All

0211 Matching ratio Phase-VT To Open-Delta-VT

1.73

All

0220 I4 current transformer is

Neutral Current (of the protected line)

All

0221 Matching ratio I4/Iph for CT's

1.000

All

4.2 Group Power System Data 1; Group Power System No.

Settings

Value

Group

Solid Earthed

All

0208A 1-1/2 Circuit breaker arrangement

NO

All

0230

Rated Frequency

50 Hz

All

0236

Distance measurement unit

km

All

0237

Setting format for zero seq.comp. format

Zero seq. comp. factors RE/RL and XE/XL

All

0207

System Starpoint is

4.3 Group Power System Data 1; Group Breaker No.

Settings

Value

Group

0240A Minimum TRIP Command Duration

0.10 sec All

0241A Maximum Close Command Duration

1.00 sec All

0242

0.10 sec All

Dead Time for CB test-autoreclosure

4.4 Group Power System Data 1; Group CT Data No.

Settings

Value Group

0251 k_alf/k_alf nominal

1.50

All

0253 CT Error in % at k_alf/k_alf nominal

3.0 %

All

0254 CT Error in % at k_alf nominal

10.0 % All

Page 7 of 17

Page 209 of 252

SIMATIC

DID / 66_11kV / 7SD532_B10&B20/7SD532

02.08.10 17:16:31

5 Oscillographic Fault Records 5.1 Group Oscillographic Fault Records No.

Settings

Value

Group

0402A Waveform Capture

Save with TRIP All

0403A Scope of Waveform Data

Fault event

All

0410

Max. length of a Waveform Capture Record

2.00 sec

All

0411

Captured Waveform Prior to Trigger

0.30 sec

All

0412

Captured Waveform after Event

0.50 sec

All

0415

Capture Time via Binary Input

0.50 sec

All

Page 8 of 17

Page 210 of 252

SIMATIC

DID / 66_11kV / 7SD532_B10&B20/7SD532

02.08.10 17:16:31

6 Settings groups 6.1 Group Power System Data 2; Group Local Line End No.

Settings

Value

Group

1103 Measurement: Full Scale Voltage (100%)

66.0 kV

A

1104 Measurement: Full Scale Current (100%)

800 A 85 81 °

A

1105 Line Angle 1511 Angle of inclination, distance charact.

A

81 ° A 85 not reversed A 0.2670 0.1440 Ohm / km A

1107 P,Q operational measured values sign 1111 x' - Line Reactance per length unit 1112 c' - capacit. per unit line len. µF/km

A

1116 Zero seq. comp. factor RE/RL for Z1

0.263 µF/km 0.195 8.5 8.2 km 1.58 0.01

1117 Zero seq. comp. factor XE/XL for Z1

-0.22 -0.17

A

1118 Zero seq. comp.factor RE/RL for Z1B...Z5

A

1119 Zero seq. comp.factor XE/XL for Z1B...Z5

0.40 1.58 -0.22 -0.19

1124 center phase of feeder

Phase 2

A

1113 Line Length

A A

A

6.2 Group Power System Data 2; Group Line Status No.

Settings

Value

Group

1130A Pole Open Current Threshold

0.10 A

A

1131A Pole Open Voltage Threshold

13 V

A

1132A Seal-in Time after ALL closures

0.10 sec

A

1133A minimal time for line open before SOTF

30.00 sec

A

1134

Recognition of Line Closures with

Manual Close BI only

A

1135

RESET of Trip Command

with Pole Open Current Threshold only

A

1136

open pole detector

with measurement (U/I,trip,pickup,CBaux)

A

1140A CT Saturation Threshold

50.0 A

A

1150A Seal-in Time after MANUAL closures

0.30 sec

A

1151

Manual CLOSE COMMAND generation

NO

A

1152

MANUAL Closure Impulse after CONTROL



All

6.3 Group Differential Protection; Group General No.

Settings

1201 State of differential protection

Value Group ON

A

Page 9 of 17

Page 211 of 252

SIMATIC

DID / 66_11kV / 7SD532_B10&B20/7SD532

02.08.10 17:16:31

6.4 Group Differential Protection; Group Diff Protection No.

Settings

Value

Group

1210

I-DIFF>: Pickup value

0.20 A

A

1213

I-DIFF>: Value under switch on condition

0.30 A

A

1217A I-DIFF>: Trip time delay

0.00 sec A

1219A Min. local current to release DIFF-Trip

0.00 A

A

1233

I-DIFF>>: Pickup value

1.7 A

A

1235

I-DIFF>>: Value under switch on cond.

2.6 A

A

6.5 Group Differential Protection; Group Inrush No.

Settings

Value

Group

2301 Inrush Restraint

OFF

A

2302 2nd. harmonic in % of fundamental

10 %

A

2303 Cross Block

NO

A

2305 Maximum inrush-peak value

10.0 A

A

2310 Time for Crossblock with 2nd harmonic

0.10 sec A

6.6 Group Intertrip No.

Settings

Value

Group

1301 State of transmit. the intertrip command

NO

A

1302 Reaction if intertrip command is receiv.

Trip

A

1303 Delay for intertrip via binary input

0.02 sec A

1304 Prolongation for intertrip via bin.input

0.00 sec A

6.7 Group Distance protection, general settings; Group General No.

Settings

Value

Group

1501 Distance protection

ON

A

1502 Phase Current threshold for dist. meas.

0.10 A

A

1511 Angle of inclination, distance charact.

81 ° 85 NO

A

1508 Series compensated line 1532 Instantaneous trip after SwitchOnToFault

with Zone Z1B A

1533 Zone Z1 blocked by diff. active

YES

A

1541 R load, minimum Load Impedance (ph-e)

47.040 Ohm

A

1542 PHI load, maximum Load Angle (ph-e)

42 °

A

1543 R load, minimum Load Impedance (ph-ph)

41.820 Ohm

A

1544 PHI load, maximum Load Angle (ph-ph)

42 °

A

1657 Z1B enabled before 1st AR (int. or ext.)

NO

A

A

Page 10 of 17

Page 212 of 252

SIMATIC

DID / 66_11kV / 7SD532_B10&B20/7SD532

02.08.10 17:16:31

6.8 Group Distance protection, general settings; Group Earth faults No.

Settings

Value

Group

1503

3I0 threshold for neutral current pickup

0.10 A

A

1504

3U0 threshold zero seq. voltage pickup

5V

A

1507A 3I0>-pickup-stabilisation (3I0> /Iphmax)

0.10

A

1509A criterion of earth fault recognition

3I0> AND 3U0>

A

1521A Loop selection with 2Ph-E faults

block leading ph-e loop A

6.9 Group Distance protection, general settings; Group Time Delays No.

Settings

Value

Group

1510 Condition for zone timer start

with distance pickup A

1605 T1-1phase, delay for single phase faults

0.00 sec

A

1606 T1multi-ph, delay for multi phase faults

0.00 sec

A

1615 T2-1phase, delay for single phase faults

0.40 sec

A

1616 T2multi-ph, delay for multi phase faults

0.40 sec

A

1625 T3 delay

5.00 sec

A

1635 T4 delay

oo sec

A

1645 T5 delay

oo sec

A

1655 T1B-1phase, delay for single ph. faults

0.00 sec

A

1656 T1B-multi-ph, delay for multi ph. faults

0.00 sec

A

6.10 Group Distance zones (quadrilateral); Group Zone Z1 No.

Settings

Value

Group

1601 Operating mode Z1

Forward

1602 R(Z1), Resistance for ph-ph-faults

1.247 Ohm A 2.37 1.58 0.832 Ohm A

1603 X(Z1), Reactance 1604 RE(Z1), Resistance for ph-e faults

A

1605 T1-1phase, delay for single phase faults

3.714 Ohm A 2.75 0.00 sec A

1606 T1multi-ph, delay for multi phase faults

0.00 sec

A

1607 Zone Reduction Angle (load compensation)



A

Page 11 of 17

Page 213 of 252

SIMATIC

DID / 66_11kV / 7SD532_B10&B20/7SD532

02.08.10 17:16:31

6.11 Group Distance zones (quadrilateral); Group Zone Z1B-exten. No.

Settings

Value

Group

1651 Operating mode Z1B (overrreach zone)

Forward

A

1652 R(Z1B), Resistance for ph-ph-faults

2.673 Ohm A 4.41

1653 X(Z1B), Reactance 1654 RE(Z1B), Resistance for ph-e faults

1.782 Ohm A 2.93 5.710 Ohm A 5.12

1655 T1B-1phase, delay for single ph. faults

0.00 sec

A

1656 T1B-multi-ph, delay for multi ph. faults

0.00 sec

A

1657 Z1B enabled before 1st AR (int. or ext.)

NO

A

6.12 Group Distance zones (quadrilateral); Group Zone Z2 No.

Settings

Value

Group

1611 Operating mode Z2

Forward

1612 R(Z2), Resistance for ph-ph-faults

4.41 2.673 Ohm A

A

1613 X(Z2), Reactance 1614 RE(Z2), Resistance for ph-e faults

1.782 Ohm A 2.93 5.710 Ohm A 5.12

1615 T2-1phase, delay for single phase faults

0.40 sec

A

1616 T2multi-ph, delay for multi phase faults

0.40 sec

A

6.13 Group Distance zones (quadrilateral); Group Zone Z3 No.

Settings

Value

Group

1621 Operating mode Z3

Forward

A

1622 R(Z3), Resistance for ph-ph-faults

6.78 4.337 Ohm A

1623 X(Z3), Reactance

2.890 Ohm A 4.51

1624 RE(Z3), Resistance for ph-e faults 7.87 9.265 Ohm A 1625 T3 delay

5.00 sec

A

6.14 Group Distance zones (quadrilateral); Group Zone Z4 No.

Settings

Value

Group A

1631 Operating mode Z4

Inactive

1632 R(Z4), Resistance for ph-ph-faults

12.000 Ohm A

1633 X(Z4), Reactance

12.000 Ohm A

1634 RE(Z4), Resistance for ph-e faults

12.000 Ohm A

1635 T4 delay

oo sec

A

Page 12 of 17

Page 214 of 252

SIMATIC

DID / 66_11kV / 7SD532_B10&B20/7SD532

02.08.10 17:16:31

6.15 Group Distance zones (quadrilateral); Group Zone Z5 No.

Settings

Value

Group

1641 Operating mode Z5

Inactive

A

1642 R(Z5), Resistance for ph-ph-faults

12.000 Ohm A

1643 X(Z5)+, Reactance for Forward direction

12.000 Ohm A

1644 RE(Z5), Resistance for ph-e faults

12.000 Ohm A

1645 T5 delay

oo sec

A

1646 X(Z5)-, Reactance for Reverse direction

4.000 Ohm

A

6.16 Group Power Swing No.

Settings

Value

Group

2002 Power Swing Operating mode

all zones blocked A

2006 Power swing trip

NO

A

2007 Trip delay after Power Swing Blocking

0.50 sec

A

6.17 Group Backup overcurrent; Group General No.

Settings

2601 Operating mode

Value ON

Group A

2602 Trip time delay after SOTF 0.00 sec A

6.18 Group Backup overcurrent; Group I>> No.

Settings

Value Group A

2610 Iph>> Pickup

oo A

2611 T Iph>> Time delay

oo sec A

2612 3I0>> Pickup

oo A

2613 T 3I0>> Time delay

oo sec A

2614 Instantaneous trip via Teleprot./BI

NO

A

2615 Instantaneous trip after SwitchOnToFault

NO

A

A

6.19 Group Backup overcurrent; Group I> No.

Settings

Value Group A

2620 Iph> Pickup

oo A

2621 T Iph> Time delay

oo sec A

2622 3I0> Pickup

oo A

2623 T 3I0> Time delay

oo sec A

2624 Instantaneous trip via Teleprot./BI

NO

A

2625 Instantaneous trip after SwitchOnToFault

NO

A

A

Page 13 of 17

Page 215 of 252

SIMATIC

DID / 66_11kV / 7SD532_B10&B20/7SD532

02.08.10 17:16:31

6.20 Group Backup overcurrent; Group Inverse No.

Settings

Value

Group

2640 Ip> Pickup

0.96 A

A

2642 T Ip Time Dial

1.00 sec

A

2646 T Ip Additional Time Delay

0.00 sec

A

2650 3I0p Pickup

oo A

A

2652 T 3I0p Time Dial

oo sec

A

2656 T 3I0p Additional Time Delay

0.00 sec

A

2660 IEC Curve

Normal Inverse A

2670 Instantaneous trip via Teleprot./BI

NO

A

2671 Instantaneous trip after SwitchOnToFault

NO

A

6.21 Group Backup overcurrent; Group I - STUB No.

Settings

Value Group

2630 Iph> STUB Pickup

oo A

A

2631 T Iph STUB Time delay

oo sec A

2632 3I0> STUB Pickup

oo A

2633 T 3I0 STUB Time delay

oo sec A

2634 Instantaneous trip via Teleprot./BI

NO

A

2635 Instantaneous trip after SwitchOnToFault

NO

A

A

6.22 Group Demand Measurement Setup; Group Measurement No.

Settings

Value

Group

2801 Demand Calculation Intervals

60 Min per., 1 Sub. A

2802 Demand Synchronization Time

On the Hour

A

6.23 Group Min/Max Measurement Setup; Group Measurement No.

Settings

Value

Group

2811 Automatic Cyclic Reset Function

YES

A

2812 MinMax Reset Timer

0 min

A

2813 MinMax Reset Cycle Period

7 day(s) A

2814 MinMax Start Reset Cycle in

1 Days

A

Page 14 of 17

Page 216 of 252

SIMATIC

DID / 66_11kV / 7SD532_B10&B20/7SD532

02.08.10 17:16:31

6.24 Group Measurement Supervision; Group Symmetry No. 2901

Settings

Value Group

Measurement Supervision

ON

A

2902A Voltage Threshold for Balance Monitoring

50 V

A

2903A Balance Factor for Voltage Monitor

0.75

A

2904A Current Balance Monitor

0.50 A A

2905A Balance Factor for Current Monitor

0.50

A

2908A T Balance Factor for Voltage Monitor

5 sec

A

2909A T Current Balance Monitor

5 sec

A

6.25 Group Measurement Supervision; Group Fuse Fail. Mon. No. 2910

Settings

Value

Fuse Failure Monitor

Group

ON

A

2911A Minimum Voltage Threshold U>

30 V

A

2912A Maximum Current Threshold I<

0.10 A

A

2913A Maximum Voltage Threshold U< (3phase)

5V

A

2914A Delta Current Threshold (3phase)

0.10 A

A

2915

with current supervision A

Voltage Failure Supervision

2916A Delay Voltage Failure Supervision

3.00 sec

A

6.26 Group Measurement Supervision; Group I/U-Monitoring No.

Settings

Value Group

2931

Fast broken current-wire supervision

OFF

A

2933

State of fast current summation supervis

ON

A

2906A Summated Current Monitoring Threshold

0.25 A A

2907A Summated Current Monitoring Factor

0.50

A

6.27 Group Measurement Supervision; Group VT mcb No.

Settings

Value Group

2921 VT mcb operating time 0 ms

A

6.28 Group Measurement Supervision; Group Load Angle No.

Settings

Value Group

2941 Limit setting PhiA

200 °

A

2942 Limit setting PhiB

340 °

A

2943 Minimum value I1>

0.05 A A

2944 Minimum value U1> 20 V

A

Page 15 of 17

Page 217 of 252

SIMATIC

DID / 66_11kV / 7SD532_B10&B20/7SD532

02.08.10 17:16:31

6.29 Group Fault Locator; Group Fault Locator No.

Settings

Value Group

3802 Start fault locator with

TRIP A

3806 Load Compensation

NO

3807 two ended fault location OFF

A A

6.30 Group Thermal Overload No.

Settings

Value

Group

4201 Thermal overload protection

Alarm Only A

4202 K-Factor

1.00

A

4203 Time Constant

25.0 min

A

4204 Thermal Alarm Stage

90 %

A

4205 Current Overload Alarm Setpoint

0.91 A

A

4206 Method of Acquiring Temperature

Theta Max A

6.31 Group Protection Interface (Port D+E); Group General No.

Settings

Value

Group

4509 Time delay for data disturbance alarm

0.10 sec A

4510 Time del for transmission failure alarm

6.0 sec

4512 Remote signal RESET DELAY for comm.fail

0.00 sec A

A

6.32 Group Protection Interface (Port D+E); Group Interface 1 No.

Settings

Value

Group

4501

State of protection interface 1

ON

A

4502

Connection 1 over

Direct connection with fibre optic cable

A

4505A Prot 1: Maximal permissible delay time

30.0 ms

A

4506A Prot 1: Diff. in send and receive time

0.100 ms

A

4513A Prot 1: Maximal permissible error rate

1.0 %

A

4515A Prot.1: Block. due to unsym. delay time

YES

A

6.33 Group Protection Interface (Port D+E); Group Interface 2 No.

Settings

Value

Group

4601

State of protection interface 2

ON

A

4602

Connection 2 over

Direct connection with fibre optic cable

A

4605A Prot 2: Maximal permissible delay time

30.0 ms

A

4606A Prot 2: Diff. in send and receive time

0.100 ms

A

4613A Prot 1: Maximal permissible error rate

1.0 %

A

4615A Prot.2: Block. due to unsym. delay time

YES

A

Page 16 of 17

Page 218 of 252

SIMATIC

DID / 66_11kV / 7SD532_B10&B20/7SD532

02.08.10 17:16:31

6.34 Group Differential Topology No.

Settings

Value Group

4701 Identification number of relay 1

1

A

4702 Identification number of relay 2

2

A

4710 Local relay is

relay 1 A

Page 17 of 17

Page 219 of 252

A

66kV UGC_7SD532_B50&B60

Page 220 of 252

SIMATIC

DID / 66_11kV / 7SD532_B50&B60/7SD532

02.08.10 18:14:15

DID / 66_11kV / 7SD532_B50&B60 MLFB: 7SD53215PB999HL6 Parameter set version: V04.62.03 Device path: \\10.178.2.32\SAS Qatar\SAS - LIVE PROJECTS\A12_Qatar Phase 8 - Kahramaa - Qatar\PH8GTC144A-AREVA\2_TECHNICAL\05_CT CALC & RElAY SETTINGS\02_RELAY SETTINGS\01_MAIN SUBSTATION\7_DOHA INDUSTRIAL-D\Rev.0\Base files\DIGSI\Did\P7DI\GV\SD\00000002 Author: Creation date: 12.05.10 15:12:18 Last modified: 02.08.10 17:18:03 Operating mode: Offline Comment: Setting values in: Secondary value description

PRINT - CONTENTS 1 Device Configuration 2 Configuration - short (column-oriented) 2.1 Binary inputs 2.2 Binary outputs 2.3 LEDs 3 General Device Settings 3.1 Group Device 4 Power System Data 1 4.1 Group Power System Data 1; Group Transformers 4.2 Group Power System Data 1; Group Power System 4.3 Group Power System Data 1; Group Breaker 4.4 Group Power System Data 1; Group CT Data 5 Oscillographic Fault Records 5.1 Group Oscillographic Fault Records 6 Settings groups 6.1 Group Power System Data 2; Group Local Line End 6.2 Group Power System Data 2; Group Line Status 6.3 Group Differential Protection; Group General 6.4 Group Differential Protection; Group Diff Protection 6.5 Group Differential Protection; Group Inrush 6.6 Group Intertrip 6.7 Group Distance protection, general settings; Group General 6.8 Group Distance protection, general settings; Group Earth faults

3 4 4 4 4 6 6 7 7 7 7 7 8 8 9 9 9 9 9 10 10 10 10 Page 1 of 17

Page 221 of 252

SIMATIC

DID / 66_11kV / 7SD532_B50&B60/7SD532

02.08.10 18:14:15

6.9 Group Distance protection, general settings; Group Time Delays 6.10 Group Distance zones (quadrilateral); Group Zone Z1 6.11 Group Distance zones (quadrilateral); Group Zone Z1B-exten. 6.12 Group Distance zones (quadrilateral); Group Zone Z2 6.13 Group Distance zones (quadrilateral); Group Zone Z3 6.14 Group Distance zones (quadrilateral); Group Zone Z4 6.15 Group Distance zones (quadrilateral); Group Zone Z5 6.16 Group Power Swing 6.17 Group Backup overcurrent; Group General 6.18 Group Backup overcurrent; Group I>> 6.19 Group Backup overcurrent; Group I> 6.20 Group Backup overcurrent; Group Inverse 6.21 Group Backup overcurrent; Group I - STUB 6.22 Group Demand Measurement Setup; Group Measurement 6.23 Group Min/Max Measurement Setup; Group Measurement 6.24 Group Measurement Supervision; Group Symmetry 6.25 Group Measurement Supervision; Group Fuse Fail. Mon. 6.26 Group Measurement Supervision; Group I/U-Monitoring 6.27 Group Measurement Supervision; Group VT mcb 6.28 Group Measurement Supervision; Group Load Angle 6.29 Group Fault Locator; Group Fault Locator 6.30 Group Thermal Overload 6.31 Group Protection Interface (Port D+E); Group General 6.32 Group Protection Interface (Port D+E); Group Interface 1 6.33 Group Protection Interface (Port D+E); Group Interface 2 6.34 Group Differential Topology

11 11 11 12 12 12 12 13 13 13 13 13 14 14 14 14 15 15 15 15 15 16 16 16 16 16

Page 2 of 17

Page 222 of 252

SIMATIC

DID / 66_11kV / 7SD532_B50&B60/7SD532

02.08.10 18:14:15

1 Device Configuration No.

Function

Scope

0103 Setting Group Change Option

Disabled

0112 Differential protection

Enabled

0115 Phase Distance

Quadrilateral

0116 Earth Distance

Quadrilateral

0120 Power Swing detection

Enabled

0121 Teleprotection for Distance prot.

Disabled

0122 DTT Direct Transfer Trip

Disabled

0124 Instantaneous HighSpeed/SOTF Overcurrent

Disabled

0125 Weak Infeed (Trip and/or Echo)

Disabled

0126 Backup overcurrent

Time Overcurrent Curve IEC

0131 Earth fault overcurrent

Disabled

0132 Teleprotection for Earth fault overcurr.

Disabled

0138 Fault Locator

Enabled

0139 Breaker Failure Protection

Disabled

0140 Trip Circuit Supervision

Disabled

0142 Thermal Overload Protection

Enabled

0144 Voltage transformers

connected

0145 Protection Interface 1 (Port D)

Enabled

0146 Protection Interface 2 (Port E)

Enabled

0149 charging current compensation

Disabled

0160 Line sections for fault locator

1 Line Section

Page 3 of 17

Page 223 of 252

SIMATIC

DID / 66_11kV / 7SD532_B50&B60/7SD532

02.08.10 18:14:15

2 Configuration - short (column-oriented) 2.1 Binary inputs No.

Binary inputs

Group

Information

1

03541 Remote Signals

>Remote Trip 1 signal input

2

00356 P.System Data 2 >Manual close signal

Type Configuration SP

H

SP

H

5

Remote Signals

BXX64 VT Disconnector Open

SP

H

6

Remote Signals

BXX64 VT Disconnector Close

SP

H

9

Remote Signals

BXX1 Earth Switch Open

SP

H

10

Remote Signals

BXX1 Earth Switch Close

SP

H

11

Remote Signals

BXX3 Disconnector Open

SP

H

12

Remote Signals

BXX3 Disconnector Close

SP

H

13

Remote Signals

BXX0 Circuit Breaker Open

SP

H

14

Remote Signals

BXX0 Circuit Breaker Close

SP

H

15

Remote Signals

BXX4 Disconnector Open

SP

H

16

Remote Signals

BXX4 Disconnector Close

SP

H

19

Remote Signals

BXXM1 Earth Switch Open

SP

H

20

Remote Signals

BXXM1 Earth Switch Close

SP

H

21

Remote Signals

BXXM2 Earth Switch Open

SP

H

22

Remote Signals

BXXM2 Earth Switch Close

SP

H

23

00361 P.System Data 2 >Failure: Feeder VT (MCB tripped)

SP

H

24

00015 Device

>Test mode

SP

L

24

03525 Diff. Prot

>Differential protection blocking signal

SP

L

2.2 Binary outputs BO

No.

Group

Information

Type Configuration

4

00511 P.System Data 2

Relay GENERAL TRIP command

OUT U

5

03545 Remote Signals

Remote Trip 1 received

OUT U

6

00511 P.System Data 2

Relay GENERAL TRIP command

OUT U

7

00169 Measurem.Superv VT Fuse Failure (alarm >10s)

OUT U

7

00170 Measurem.Superv VT Fuse Failure (alarm instantaneous)

OUT U

13 03545 Remote Signals

Remote Trip 1 received

OUT U

14 03541 Remote Signals

>Remote Trip 1 signal input

SP

U

Page 4 of 17

Page 224 of 252

SIMATIC

DID / 66_11kV / 7SD532_B50&B60/7SD532

02.08.10 18:14:15

2.3 LEDs LEDs

No.

Group

Information

Type Configuration

1

00511 P.System Data 2

Relay GENERAL TRIP command

OUT L

2

00503 P.System Data 2

Relay PICKUP Phase L1

OUT L

3

00504 P.System Data 2

Relay PICKUP Phase L2

OUT L

4

00505 P.System Data 2

Relay PICKUP Phase L3

OUT L

5

03141 Diff. Prot

Diff: General TRIP

OUT L

6

03541 Remote Signals

>Remote Trip 1 signal input

SP

6

03545 Remote Signals

Remote Trip 1 received

OUT L

7

03823 Dis. General

DisTRIP 3phase in Z1 with single-ph Flt.

OUT L

7

03824 Dis. General

DisTRIP 3phase in Z1 with multi-ph Flt.

OUT L

8

03817 Dis. General

Distance TRIP 3phase in Z2

OUT L

9

03818 Dis. General

Distance TRIP 3phase in Z3

OUT L

SOTF TRIP WITH ZONE-1B

SP

10

P.System Data 2

L

L

11

04164 Power Swing

Power Swing detected

OUT L

11

07211 Back-Up O/C

Backup O/C General TRIP command

OUT L

12

00169 Measurem.Superv VT Fuse Failure (alarm >10s)

OUT U

12

00170 Measurem.Superv VT Fuse Failure (alarm instantaneous)

OUT U

13

03148 Diff. Prot

Diff: Differential protection is blocked

OUT L

14

03230 Prot. Interface

Prot Int 1: Total receiption failure

OUT L

14

03232 Prot. Interface

Prot Int 2: Total receiption failure

OUT L

Page 5 of 17

Page 225 of 252

SIMATIC

DID / 66_11kV / 7SD532_B50&B60/7SD532

02.08.10 18:14:15

3 General Device Settings 3.1 Group Device No.

Settings

Value

Group

0610

Fault Display on LED / LCD

Display Targets on every Pickup

All

0615

Spontaneous display of flt.annunciations

YES

All

0625A Minimum hold time of lachted LEDs

0 min

All

0640

image 1

All

Start image Default Display

Page 6 of 17

Page 226 of 252

SIMATIC

DID / 66_11kV / 7SD532_B50&B60/7SD532

02.08.10 18:14:15

4 Power System Data 1 4.1 Group Power System Data 1; Group Transformers No.

Settings

Value

Group

0201 CT Starpoint

towards Line

All

0203 Rated Primary Voltage

66.0 kV

All

0204 Rated Secondary Voltage (Ph-Ph)

110 V

All

0205 CT Rated Primary Current

All

0206 CT Rated Secondary Current

800 AA 1200 1A

0210 U4 voltage transformer is

not connected

All

0211 Matching ratio Phase-VT To Open-Delta-VT

1.73

All

0220 I4 current transformer is

Neutral Current (of the protected line)

All

0221 Matching ratio I4/Iph for CT's

1.000

All

All

4.2 Group Power System Data 1; Group Power System No.

Settings

Value

Group

Solid Earthed

All

0208A 1-1/2 Circuit breaker arrangement

NO

All

0230

Rated Frequency

50 Hz

All

0236

Distance measurement unit

km

All

0237

Setting format for zero seq.comp. format

Zero seq. comp. factors RE/RL and XE/XL

All

0207

System Starpoint is

4.3 Group Power System Data 1; Group Breaker No.

Settings

Value

Group

0240A Minimum TRIP Command Duration

0.10 sec All

0241A Maximum Close Command Duration

1.00 sec All

0242

0.10 sec All

Dead Time for CB test-autoreclosure

4.4 Group Power System Data 1; Group CT Data No.

Settings

Value Group

0251 k_alf/k_alf nominal

1.50

All

0253 CT Error in % at k_alf/k_alf nominal

3.0 %

All

0254 CT Error in % at k_alf nominal

10.0 % All

Page 7 of 17

Page 227 of 252

SIMATIC

DID / 66_11kV / 7SD532_B50&B60/7SD532

02.08.10 18:14:15

5 Oscillographic Fault Records 5.1 Group Oscillographic Fault Records No.

Settings

Value

Group

0402A Waveform Capture

Save with TRIP All

0403A Scope of Waveform Data

Fault event

All

0410

Max. length of a Waveform Capture Record

2.00 sec

All

0411

Captured Waveform Prior to Trigger

0.30 sec

All

0412

Captured Waveform after Event

0.50 sec

All

0415

Capture Time via Binary Input

0.50 sec

All

Page 8 of 17

Page 228 of 252

SIMATIC

DID / 66_11kV / 7SD532_B50&B60/7SD532

02.08.10 18:14:15

6 Settings groups 6.1 Group Power System Data 2; Group Local Line End No.

Settings

Value

Group

1103 Measurement: Full Scale Voltage (100%)

66.0 kV

A

1104 Measurement: Full Scale Current (100%)

A

1105 Line Angle

800 AA 1200 81 °

1511 Angle of inclination, distance charact.

81 °

A

1107 P,Q operational measured values sign

not reversed A 0.2160 0.1440 Ohm / km A

1111 x' - Line Reactance per length unit

A

A

1113 Line Length

0.263 µF/km 0.176 2.0 km

1116 Zero seq. comp. factor RE/RL for Z1

0.01

A

1117 Zero seq. comp. factor XE/XL for Z1

-0.17

A

1118 Zero seq. comp.factor RE/RL for Z1B...Z5

0.01

A

1119 Zero seq. comp.factor XE/XL for Z1B...Z5

-0.17

A

1124 center phase of feeder

Phase 2

A

1112 c' - capacit. per unit line len. µF/km

A

6.2 Group Power System Data 2; Group Line Status No.

Settings

Value

Group

1130A Pole Open Current Threshold

0.10 A

A

1131A Pole Open Voltage Threshold

13 V

A

1132A Seal-in Time after ALL closures

0.10 sec

A

1133A minimal time for line open before SOTF

30.00 sec

A

1134

Recognition of Line Closures with

Manual Close BI only

A

1135

RESET of Trip Command

with Pole Open Current Threshold only

A

1136

open pole detector

with measurement (U/I,trip,pickup,CBaux)

A

1140A CT Saturation Threshold

50.0 A

A

1150A Seal-in Time after MANUAL closures

0.30 sec

A

1151

Manual CLOSE COMMAND generation

NO

A

1152

MANUAL Closure Impulse after CONTROL



All

6.3 Group Differential Protection; Group General No.

Settings

1201 State of differential protection

Value Group ON

A

Page 9 of 17

Page 229 of 252

SIMATIC

DID / 66_11kV / 7SD532_B50&B60/7SD532

02.08.10 18:14:15

6.4 Group Differential Protection; Group Diff Protection No.

Settings

Value

Group

1210

I-DIFF>: Pickup value

0.20 A

A

1213

I-DIFF>: Value under switch on condition

0.30 A

A

1217A I-DIFF>: Trip time delay

0.00 sec A

1219A Min. local current to release DIFF-Trip

0.00 A

A

1233

I-DIFF>>: Pickup value

1.2 1.7 A

A

1235

I-DIFF>>: Value under switch on cond.

1.8 2.6 A

A

6.5 Group Differential Protection; Group Inrush No.

Settings

Value

Group

2301 Inrush Restraint

OFF

A

2302 2nd. harmonic in % of fundamental

10 %

A

2303 Cross Block

NO

A

2305 Maximum inrush-peak value

10.0 A

A

2310 Time for Crossblock with 2nd harmonic

0.10 sec A

6.6 Group Intertrip No.

Settings

Value

Group

1301 State of transmit. the intertrip command

NO

A

1302 Reaction if intertrip command is receiv.

Trip

A

1303 Delay for intertrip via binary input

0.02 sec A

1304 Prolongation for intertrip via bin.input

0.00 sec A

6.7 Group Distance protection, general settings; Group General No.

Settings

Value

Group

1501 Distance protection

ON

A

1502 Phase Current threshold for dist. meas.

0.10 A

A

1511 Angle of inclination, distance charact.

81 °

A

1508 Series compensated line

NO

A

1532 Instantaneous trip after SwitchOnToFault

with Zone Z1B A

1533 Zone Z1 blocked by diff. active

YES

A

1541 R load, minimum Load Impedance (ph-e)

A

1543 R load, minimum Load Impedance (ph-ph)

47.040 Ohm 70.570 42 ° 62.730 41.820 Ohm

1544 PHI load, maximum Load Angle (ph-ph)

42 °

A

1657 Z1B enabled before 1st AR (int. or ext.)

NO

A

1542 PHI load, maximum Load Angle (ph-e)

A A

Page 10 of 17

Page 230 of 252

SIMATIC

DID / 66_11kV / 7SD532_B50&B60/7SD532

02.08.10 18:14:15

6.8 Group Distance protection, general settings; Group Earth faults No.

Settings

Value

Group

1503

3I0 threshold for neutral current pickup

0.10 A

A

1504

3U0 threshold zero seq. voltage pickup

5V

A

1507A 3I0>-pickup-stabilisation (3I0> /Iphmax)

0.10

A

1509A criterion of earth fault recognition

3I0> AND 3U0>

A

1521A Loop selection with 2Ph-E faults

block leading ph-e loop A

6.9 Group Distance protection, general settings; Group Time Delays No.

Settings

Value

Group

1510 Condition for zone timer start

with distance pickup A

1605 T1-1phase, delay for single phase faults

0.00 sec

A

1606 T1multi-ph, delay for multi phase faults

0.00 sec

A

1615 T2-1phase, delay for single phase faults

0.40 sec

A

1616 T2multi-ph, delay for multi phase faults

0.40 sec

A

1625 T3 delay

5.00 sec

A

1635 T4 delay

oo sec

A

1645 T5 delay

oo sec

A

1655 T1B-1phase, delay for single ph. faults

0.00 sec

A

1656 T1B-multi-ph, delay for multi ph. faults

0.00 sec

A

6.10 Group Distance zones (quadrilateral); Group Zone Z1 No.

Settings

Value

Group

1601 Operating mode Z1

Forward

1602 R(Z1), Resistance for ph-ph-faults 1604 RE(Z1), Resistance for ph-e faults

1.330 Ohm A 0.450 0.300 0.200 Ohm A 1.350 3.970 Ohm A

1605 T1-1phase, delay for single phase faults

0.00 sec

A

1606 T1multi-ph, delay for multi phase faults

0.00 sec

A

1607 Zone Reduction Angle (load compensation)



A

1603 X(Z1), Reactance

A

Page 11 of 17

Page 231 of 252

SIMATIC

DID / 66_11kV / 7SD532_B50&B60/7SD532

02.08.10 18:14:15

6.11 Group Distance zones (quadrilateral); Group Zone Z1B-exten. No.

Settings

Value

Group

1651 Operating mode Z1B (overrreach zone)

Forward

1652 R(Z1B), Resistance for ph-ph-faults 1654 RE(Z1B), Resistance for ph-e faults

1.330 Ohm A 0.840 0.560 0.370 Ohm A 2.510 3.970 Ohm A

1655 T1B-1phase, delay for single ph. faults

0.00 sec

A

1656 T1B-multi-ph, delay for multi ph. faults

0.00 sec

A

1657 Z1B enabled before 1st AR (int. or ext.)

NO

A

1653 X(Z1B), Reactance

A

6.12 Group Distance zones (quadrilateral); Group Zone Z2 No.

Settings

Value

1611 Operating mode Z2

Group

1614 RE(Z2), Resistance for ph-e faults

Forward A 0.840 1.330 Ohm A 0.560 0.370 Ohm A 2.510 3.970 Ohm A

1615 T2-1phase, delay for single phase faults

0.40 sec

A

1616 T2multi-ph, delay for multi phase faults

0.40 sec

A

1612 R(Z2), Resistance for ph-ph-faults 1613 X(Z2), Reactance

6.13 Group Distance zones (quadrilateral); Group Zone Z3 No.

Settings

Value

Group

1621 Operating mode Z3

Forward A 1622 R(Z3), Resistance for ph-ph-faults 1.300 1.330 Ohm A 1623 X(Z3), Reactance

0.580 Ohm A 0.860

1624 RE(Z3), Resistance for ph-e faults 3.860 3.970 Ohm A 1625 T3 delay

5.00 sec

A

6.14 Group Distance zones (quadrilateral); Group Zone Z4 No.

Settings

Value

Group A

1631 Operating mode Z4

Inactive

1632 R(Z4), Resistance for ph-ph-faults

12.000 Ohm A

1633 X(Z4), Reactance

12.000 Ohm A

1634 RE(Z4), Resistance for ph-e faults

12.000 Ohm A

1635 T4 delay

oo sec

A

Page 12 of 17

Page 232 of 252

SIMATIC

DID / 66_11kV / 7SD532_B50&B60/7SD532

02.08.10 18:14:15

6.15 Group Distance zones (quadrilateral); Group Zone Z5 No.

Settings

Value

Group

1641 Operating mode Z5

Inactive

A

1642 R(Z5), Resistance for ph-ph-faults

12.000 Ohm A

1643 X(Z5)+, Reactance for Forward direction

12.000 Ohm A

1644 RE(Z5), Resistance for ph-e faults

12.000 Ohm A

1645 T5 delay

oo sec

A

1646 X(Z5)-, Reactance for Reverse direction

4.000 Ohm

A

6.16 Group Power Swing No.

Settings

Value

Group

2002 Power Swing Operating mode

all zones blocked A

2006 Power swing trip

NO

A

2007 Trip delay after Power Swing Blocking

0.50 sec

A

6.17 Group Backup overcurrent; Group General No.

Settings

2601 Operating mode

Value ON

Group A

2602 Trip time delay after SOTF 0.00 sec A

6.18 Group Backup overcurrent; Group I>> No.

Settings

Value Group A

2610 Iph>> Pickup

oo A

2611 T Iph>> Time delay

oo sec A

2612 3I0>> Pickup

oo A

2613 T 3I0>> Time delay

oo sec A

2614 Instantaneous trip via Teleprot./BI

NO

A

2615 Instantaneous trip after SwitchOnToFault

NO

A

A

6.19 Group Backup overcurrent; Group I> No.

Settings

Value Group A

2620 Iph> Pickup

oo A

2621 T Iph> Time delay

oo sec A

2622 3I0> Pickup

oo A

2623 T 3I0> Time delay

oo sec A

2624 Instantaneous trip via Teleprot./BI

NO

A

2625 Instantaneous trip after SwitchOnToFault

NO

A

A

Page 13 of 17

Page 233 of 252

SIMATIC

DID / 66_11kV / 7SD532_B50&B60/7SD532

02.08.10 18:14:15

6.20 Group Backup overcurrent; Group Inverse No.

Settings

Value

Group

2640 Ip> Pickup

0.64 0.96 A

A

2642 T Ip Time Dial

1.00 sec

A

2646 T Ip Additional Time Delay

0.00 sec

A

2650 3I0p Pickup

oo A

A

2652 T 3I0p Time Dial

oo sec

A

2656 T 3I0p Additional Time Delay

0.00 sec

A

2660 IEC Curve

Normal Inverse A

2670 Instantaneous trip via Teleprot./BI

NO

A

2671 Instantaneous trip after SwitchOnToFault

NO

A

6.21 Group Backup overcurrent; Group I - STUB No.

Settings

Value Group

2630 Iph> STUB Pickup

oo A

A

2631 T Iph STUB Time delay

oo sec A

2632 3I0> STUB Pickup

oo A

2633 T 3I0 STUB Time delay

oo sec A

2634 Instantaneous trip via Teleprot./BI

NO

A

2635 Instantaneous trip after SwitchOnToFault

NO

A

A

6.22 Group Demand Measurement Setup; Group Measurement No.

Settings

Value

Group

2801 Demand Calculation Intervals

60 Min per., 1 Sub. A

2802 Demand Synchronization Time

On the Hour

A

6.23 Group Min/Max Measurement Setup; Group Measurement No.

Settings

Value

Group

2811 Automatic Cyclic Reset Function

YES

A

2812 MinMax Reset Timer

0 min

A

2813 MinMax Reset Cycle Period

7 day(s) A

2814 MinMax Start Reset Cycle in

1 Days

A

Page 14 of 17

Page 234 of 252

SIMATIC

DID / 66_11kV / 7SD532_B50&B60/7SD532

02.08.10 18:14:15

6.24 Group Measurement Supervision; Group Symmetry No. 2901

Settings

Value Group

Measurement Supervision

ON

A

2902A Voltage Threshold for Balance Monitoring

50 V

A

2903A Balance Factor for Voltage Monitor

0.75

A

2904A Current Balance Monitor

0.50 A A

2905A Balance Factor for Current Monitor

0.50

A

2908A T Balance Factor for Voltage Monitor

5 sec

A

2909A T Current Balance Monitor

5 sec

A

6.25 Group Measurement Supervision; Group Fuse Fail. Mon. No. 2910

Settings

Value

Fuse Failure Monitor

Group

ON

A

2911A Minimum Voltage Threshold U>

30 V

A

2912A Maximum Current Threshold I<

0.10 A

A

2913A Maximum Voltage Threshold U< (3phase)

5V

A

2914A Delta Current Threshold (3phase)

0.10 A

A

2915

with current supervision A

Voltage Failure Supervision

2916A Delay Voltage Failure Supervision

3.00 sec

A

6.26 Group Measurement Supervision; Group I/U-Monitoring No.

Settings

Value Group

2931

Fast broken current-wire supervision

OFF

A

2933

State of fast current summation supervis

ON

A

2906A Summated Current Monitoring Threshold

0.25 A A

2907A Summated Current Monitoring Factor

0.50

A

6.27 Group Measurement Supervision; Group VT mcb No.

Settings

Value Group

2921 VT mcb operating time 0 ms

A

6.28 Group Measurement Supervision; Group Load Angle No.

Settings

Value Group

2941 Limit setting PhiA

200 °

A

2942 Limit setting PhiB

340 °

A

2943 Minimum value I1>

0.05 A A

2944 Minimum value U1> 20 V

A

Page 15 of 17

Page 235 of 252

SIMATIC

DID / 66_11kV / 7SD532_B50&B60/7SD532

02.08.10 18:14:15

6.29 Group Fault Locator; Group Fault Locator No.

Settings

Value Group

3802 Start fault locator with

TRIP A

3806 Load Compensation

NO

3807 two ended fault location OFF

A A

6.30 Group Thermal Overload No.

Settings

Value

Group

4201 Thermal overload protection

Alarm Only A

4202 K-Factor

0.70 1.00

A

4203 Time Constant

25.0 min

A

4204 Thermal Alarm Stage

A

4205 Current Overload Alarm Setpoint

90 % 0.61 0.91 A

4206 Method of Acquiring Temperature

Theta Max A

A

6.31 Group Protection Interface (Port D+E); Group General No.

Settings

Value

Group

4509 Time delay for data disturbance alarm

0.10 sec A

4510 Time del for transmission failure alarm

6.0 sec

4512 Remote signal RESET DELAY for comm.fail

0.00 sec A

A

6.32 Group Protection Interface (Port D+E); Group Interface 1 No.

Settings

Value

Group

4501

State of protection interface 1

ON

A

4502

Connection 1 over

Direct connection with fibre optic cable

A

4505A Prot 1: Maximal permissible delay time

30.0 ms

A

4506A Prot 1: Diff. in send and receive time

0.100 ms

A

4513A Prot 1: Maximal permissible error rate

1.0 %

A

4515A Prot.1: Block. due to unsym. delay time

YES

A

6.33 Group Protection Interface (Port D+E); Group Interface 2 No.

Settings

Value

Group

4601

State of protection interface 2

ON

A

4602

Connection 2 over

Direct connection with fibre optic cable

A

4605A Prot 2: Maximal permissible delay time

30.0 ms

A

4606A Prot 2: Diff. in send and receive time

0.100 ms

A

4613A Prot 1: Maximal permissible error rate

1.0 %

A

4615A Prot.2: Block. due to unsym. delay time

YES

A

Page 16 of 17

Page 236 of 252

SIMATIC

DID / 66_11kV / 7SD532_B50&B60/7SD532

02.08.10 18:14:15

6.34 Group Differential Topology No.

Settings

Value Group

4701 Identification number of relay 1

1

A

4702 Identification number of relay 2

2

A

4710 Local relay is

relay 1 A

Page 17 of 17

Page 237 of 252

A

Non Areva Make Tapcon

Page 238 of 252

Serial [19200 bauds]

07.11.2010 06.01.2010 12:53:19

Description

Communication:

Changed

Desired value 1 Desired value 2 Desired value 3 Bandwidth T1 delay time T1 Control mode T2 activation T2 delay time

Parameter

Normset activation Desired value 1 Primary voltage Secondary voltage

Normset

Parameter

1/6/2010 12:56:20 PM Page: 03.03.2010

MR Reinhausen Germany

1 / 7

UAA +A18.AQ01 +A18.AQ01 DID DID UAA +A18.AQ01 +A18.AQ01

Location:

-

DID A18 AQ01#1 UAA A18 AQ01#1

Parameter file:

TAPCON©: 0854 - DID+A18.AQ01#1 UAA +A18.AQ01#1 Type: TAPCON©260 DID Group: UAA 66/11kV 66-11KV

Page 239 of 252

110,0 110,0 110,0 1,25 90 T1 linear T2 on 8,0 8,0

Off 110,0 11 110,0

Value

V V V % s -

V kV V

Unit

s

49 49 49 0,5 0 -

49 0 57

Minimum

1

Page 1 of 14

140 140 140 9 600 10

Regulation param.

140 9999 110

Normset parameter

Maximum

U des. regulator 2 U< regulator 2 U< regulator 2 U> regulator 2 U> regulator 2 Alarm P.T. sec. voltage reg. 2 P.T. prim. voltage reg. 2

Parameter

03.03.2010 1/6/2010 12:56:20 PM Page:

MR Reinhausen Germany

2 / 7

Ur-Line Drop Compensation Ux-Line Drop Compensation Z - Compensation Z - Comp.Limit

Parameter

Absolute limit values U< Undervoltage (%) U< Undervoltage (V) U> Overvoltage (%) U> Overvoltage (V) I> Overcurrent Funct. Monitoring U< delay time U< Blocking U< under 30V Tap min. Tap max.

Parameter

Page 240 of 252

110,0 80 88,0 110 121,0 10 110,0 11

0,0 0,0 0,0 0,0

On 80 88,0 110 121,0 2850,00 Off 10,0 On Off 1 17

V % V % V s V kV

V V % %

% V % V A s -

49 60 34 100 34 0 57 0

-25 -25 0 0

60 34 100 34 1250,00 0 -128 -128

Page 2 of 14

140 100 160 140 160 10 110 9999

Cross checking

25 25 15 15

Compensation

100 160 140 160 5250,00 20 128 128

Limit values

Parallel operation method Par. contr. SKB CAN Address Stability Blocking Alarm Tapping direction, turned

Configuration

Language Controller identification Setting the baudrate Display kV / V Display % / A pulse time IO1-X1:33 IO1-X1:31 IO1-X1:25/26 IO1-X1:23/24 Display off Motor runtime IP network mask IP address Time server IP address Gateway IED name

Configuration

Primary voltage Secondary voltage Primary current C.T. terminal Instr.transformer circuit

Configuration

03.03.2010 1/6/2010 12:56:20 PM Page:

MR Reinhausen Germany

Page 241 of 252

3 / 7

Master Off 1 0,0 20,0 10 Standard

English 0854 19.2 kBaud V On 1,5 Local/Rem. Master/Foll. Master/Foll. Off On 0,0 255.255.0.0 172.16.70.45 172.16.104.203 172.16.0.111 XXXX

11 110,0 2500 1A 0 1PH

% % s -

s s -

kV V A -

0 0 0,5 1 -

0 0 0.0.0.0 0.0.0.0 0.0.0.0 0.0.0.0 -

0 57 0 -

Page 3 of 14

16 100 20 99 -

Parallel control

10 30 255.255.255.255 255.255.255.255 255.255.255.255 255.255.255.255 -

General

9999 110 10000 -

Data of meas.Trf.

Output 1 meas. value Output 1 bottom Output 1 top Output 1 lower value Output 1 upper value Output 2 meas. value Output 2 bottom Output 2 top Output 2 lower value Output 2 upper value

Configuration

MR Reinhausen Germany

03.03.2010 1/6/2010 12:56:20 PM Page:

4 / 7

Off +4mA 20mA 0 0 Off +4mA 20mA 0 0

-

-

-9999 -9999 -9999 -9999

-

100 100 999,9 999,9 100 100 999,9 999,9 100 100 999,9 999,9

Page 4 of 14

9999 9999 9999 9999

Transducer 1/2

-

Overcurr. Off Overvolt. Master Follower

0 0 -999,9 -999,9 0 0 -999,9 -999,9 0 0 -999,9 -999,9

LED1 LED2 LED3 LED4 red LED4 green

% % % % % % -

LED selection

0,0 100,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0

Analogue inputs

Configuration

Input 1 Lower limit Input 1 Upper limit Input 1 Lower value Input 1 Upper value Input 2 Lower limit Input 2 Upper limit Input 2 Lower value Input 2 Upper value Input 3 Lower limit Input 3 Upper limit Input 3 Lower value Input 3 Upper value

Configuration

Page 242 of 252

U< threshold U< memory U> threshold U> memory Mean value interval Event memory

Configuration

Output 3 meas. value Output 3 bottom Output 3 top Output 3 lower value Output 3 upper value Output 4 meas. value Output 4 bottom Output 4 top Output 4 lower value Output 4 upper value

Configuration

1/6/2010 12:56:20 PM Page: 03.03.2010

MR Reinhausen Germany

Page 243 of 252

5 / 7

60 35,0 110 110,0 10s 1024k

Off +4mA 20mA 0 0 Off +4mA 20mA 0 0

% V % V -

-

60 34 100 34 -

-9999 -9999 -9999 -9999

Page 5 of 14

100 160 140 160 -

Memory

9999 9999 9999 9999

Transducer 3/4

03.03.2010 1/6/2010 12:56:20 PM Page:

MR Reinhausen Germany

6 / 7

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Page 6 of 14

999 999 999 999 999 999 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80

-

Transformer ID 1 Transformer ID 2 Transformer ID 3 Transformer ID 4 Transformer ID 5 Transformer ID 6 switch1 node a switch1 node b switch2 node a switch2 node b switch3 node a switch3 node b switch4 node a switch4 node b switch5 node a switch5 node b switch6 node a switch6 node b switch7 node a switch7 node b switch8 node a switch8 node b switch9 node a switch9 node b switch10 node a switch10 node b switch11 node a switch11 node b switch12 node a switch12 node b switch13 node a switch13 node b switch14 node a switch14 node b switch15 node a

1 2 0 0 0 0 1 17 2 18 17 18 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Topology

Configuration

Page 244 of 252

1/6/2010 12:56:20 PM Page: 03.03.2010

MR Reinhausen Germany

7 / 7

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 -

Page 7 of 14

80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 -

-

switch15 node b switch16 node a switch16 node b switch17 node a switch17 node b switch18 node a switch18 node b switch19 node a switch19 node b switch20 node a switch20 node b switch21 node a switch21 node b switch22 node a switch22 node b switch23 node a switch23 node b switch24 node a switch24 node b Topology prim/sec.

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 secondary

Topology

Configuration

Page 245 of 252

A

B30 RED670_87C+T SET

Page 246 of 252

8/2/2010

KHARAMAA_latest/Region/DID/66KV/B30_TYP/DID_B30_RED_670C_T Parameter Name

IED Value

PC Value

Unit

Min

Max

DID_B30_RED_670C_T Settings Activate setting group ActiveSetGrp

SettingGroup1

[+] Time General settings Power system Identifiers StationName

DID

StationNumber

0

ObjectName

B30

ObjectNumber

0

UnitName

RED670_C+T

UnitNumber

0

18 charact 0

99999 18 charact

0

99999 18 charact

0

99999

50.0

60.0

Primary values Frequency

50.0

Hz

[+] Communication Analog modules AnalogInputs6Iand6U 1 NAMECH1

I PH.R

RatedTrans1

1.0

CTStarPoint1

ToObject

CTsec1

13 charact A

0.1

300.0

1

A

1

10

CTprim1

400

A

1

99999

NAMECH2

I PH.Y

RatedTrans2

1.0

CTStarPoint2

ToObject

CTsec2

13 charact A

0.1

300.0

1

A

1

10

CTprim2

400

A

1

99999

NAMECH3

I PH.B

RatedTrans3

1.0

CTStarPoint3

ToObject

CTsec3

13 charact A

0.1

300.0

1

A

1

10

CTprim3

400

A

1

99999

NAMECH4

TRM40-CH4

13 charact

1 Page 247 of 252

8/2/2010

KHARAMAA_latest/Region/DID/66KV/B30_TYP/DID_B30_RED_670C_T Parameter Name

IED Value

PC Value

Unit

Min

Max

RatedTrans4

1.0

A

0.1

300.0

CTStarPoint4

ToObject

CTsec4

1

A

1

10

CTprim4

400

A

1

99999

NAMECH5

TRM40-CH5

RatedTrans5

1.0

CTStarPoint5

ToObject

CTsec5

13 charact A

0.1

300.0

1

A

1

10

CTprim5

99999

A

1

99999

NAMECH6

TRM40-CH6

RatedTrans6

1.0

CTStarPoint6

ToObject

CTsec6

13 charact A

0.1

300.0

1

A

1

10

CTprim6

99999

A

1

99999

NAMECH7

U PH.R

RatedTrans7

110.0

V

0.1

300.0

VTsec7

110.000

V

0.001

999.999

VTprim7

1.00

kV

0.05

2000.00

NAMECH8

U PH.Y

RatedTrans8

110.0

V

0.1

300.0

VTsec8

110.000

V

0.001

999.999

VTprim8

1.00

kV

0.05

2000.00

NAMECH9

U PH.B

RatedTrans9

110.0

V

0.1

300.0

VTsec9

110.000

V

0.001

999.999

VTprim9

1.00

kV

0.05

2000.00

NAMECH10

TRM40-CH10

RatedTrans10

110.0

V

0.1

300.0

VTsec10

110.000

V

0.001

999.999

VTprim10

1.00

kV

0.05

2000.00

NAMECH11

TRM40-CH11

RatedTrans11

110.0

V

0.1

300.0

VTsec11

110.000

V

0.001

999.999

VTprim11

1.00

kV

0.05

2000.00

NAMECH12

TRM40-CH12

13 charact

13 charact

13 charact

13 charact

13 charact

13 charact

2 Page 248 of 252

8/2/2010

KHARAMAA_latest/Region/DID/66KV/B30_TYP/DID_B30_RED_670C_T Parameter Name

IED Value

PC Value

Unit

Min

Max

RatedTrans12

110.0

V

0.1

300.0

VTsec12

110.000

V

0.001

999.999

VTprim12

1.00

kV

0.05

2000.00

A

50.0

9999.9

[+] LDCM312 [+] Reference channel service values [+] 3PhaseAnalogGroup [+] I/O modules [+] HMI Differential protection LineTrfDiff3Terminal(PDIF,87L) LT3D NoOfTerminals

2

Chan2IsLocal

No

IBase

400.0

ZerSeqCurSubtr

On

TraAOnInpCh

2

RatVoltW1TraA

66.0

kV

1.0

9999.9

RatVoltW2TraA

11.0

kV

1.0

9999.9

ClockNumTransA

1 [30 deg lag]

ZerSeqPassTraA

No

TraBOnInpCh

No Transf B

RatVoltW1TraB

1.0

kV

1.0

9999.9

RatVoltW2TraB

1.0

kV

1.0

9999.9

ClockNumTransB

0 [0 deg]

ZerSeqPassTraB

No

LineDiffLogic LDL Operation

On

Current protection PhaseOverCurrent4Step(PTOC,51/67) TOC1 MeasType

DFT

[+] Voltage protection [+] Control Monitoring

3 Page 249 of 252

8/2/2010

KHARAMAA_latest/Region/DID/66KV/B30_TYP/DID_B30_RED_670C_T Parameter Name

IED Value

PC Value

Unit

Min

Max

DisturbanceReport DisturbanceReport(RDRE) Operation

On

PreFaultRecT

0.30

s

0.05

1.00

PostFaultRecT

0.5

s

0.1

10.0

TimeLimit

2.0

s

0.5

10.0

PostRetrig

Off

ZeroAngleRef

1

Ch

1

30

OpModeTest

Off

[+] BinarySignals(RBDR) [+] AnalogSignals(RADR) [+] FaultLocator(RFLO) [+] IEC60870-5-103 Setting group N1 Differential protection LineTrfDiff3Terminal(PDIF,87L) LT3D Operation

On

IdMin

0.30

IB

0.20

2.00

EndSection1

1.1 1.09

IB

0.20

1.50

EndSection2

2.6 2.62

IB

1.00

10.00

SlopeSection2

40.0

%

10.0

50.0

SlopeSection3

80.0

%

30.0

100.0

IdMinHigh

2.00

IB

0.20

10.00

tIdMinHigh

5.000

s

0.000

60.000

IdUnre

7.40 7.36

IB

1.00

50.00

NegSeqDiffEn

On

NegSeqROA

60.0

Deg

30.0

120.0

IMinNegSeq

0.04

IB

0.01

0.20

CrossBlockEn

Yes

I2/I1Ratio

10.0

%

5.0

100.0

I5/I1Ratio

25.0

%

5.0

100.0

ChargCurEnable

Off

AddDelay

Off

IMaxAddDelay

1.00

IB

0.20

5.00

4 Page 250 of 252

8/2/2010

KHARAMAA_latest/Region/DID/66KV/B30_TYP/DID_B30_RED_670C_T Parameter Name

IED Value

PC Value

Unit

Min

Max

tDefTime

0.000

s

0.000

6.000

tMinInv

0.010

s

0.001

6.000

CurveType

IEC Def. Time

k

1.00

0.05

1.10

p

0.02

0.01

1000.00

a

0.14

0.01

1000.00

b

1.00

0.01

1000.00

c

1.00

0.01

1000.00

IdiffAlarm

0.15

IB

0.05

1.00

tAlarmdelay

10.000

s

0.000

60.000

OpenCTEnable

Off

tOCTAlarmDelay

1.000

s

0.100

10.000

tOCTResetDelay

0.250

s

0.100

10.000

[+] Impedance Protection Current protection [+] BrokenCondCheck(PTOC,46) [+] InstPhaseOverCurrent(PIOC,50) [+] PhaseOverCurrent4Step(PTOC,51/67) [+] ResidualOverCurr4Step(PTOC,51N/67N) ThermalOverload1TimeConst(PTTR,26) THL1 Operation

On

IBase

400

A

0

99999

TRef

90

Deg

0

600

IRef

96

%IB

0

400

IMult

1

1

5

Tau

1

Min

0

1000

AlarmTemp

85

Deg

0

200

TripTemp

95

Deg

0

600

ReclTemp

75

Deg

0

600

tPulse

0.10

s

0.05

0.30

AmbiSens

Off

DefaultAmbTemp

20

Deg

-50

250

DefaultTemp

50

Deg

-50

600

[+] Voltage protection

5 Page 251 of 252

8/2/2010

KHARAMAA_latest/Region/DID/66KV/B30_TYP/DID_B30_RED_670C_T Parameter Name

IED Value

PC Value

Unit

Min

Max

s

0.000

60.000

[+] Scheme communication [+] Secondary system supervision [+] Monitoring Logic TripLogic(PTRC,94) TRP1 Operation

On

Program

1ph/3ph

TripLockout

Off

AutoLock

Off

tTripMin

0.150

[+] TripMatrix(GGIO) [+] LogicGate