Download 367B. Testing of 7SA610 With F6150-DistPro...
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Testing of 7SA610 relay with F6150 Kamin Dave (Relay Application Engineer) DOBLE ENGINEERING PVT LTD
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Introduction Relay:
Zones limit The nominal shape of the 7SA610 characteristic curve is shown in the following image.
7SA610 characteristic curve It is a characteristic polygonal curve with the following features: Directional-1: - 45°; Directional-2: 135°; DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Settings are: -Æ Values X1, X2, X3,X1B or X1L; -Æ Values R1, R2, R3, R1B or R1L for multiphase faults -Æ Values R1E, R2E, R3E, R1BE, R1LE, for single phase faults. .Trip time 1ph: T1,T2, T3; for trip time with mono phase faults. .Trip time >1ph: T1,T2, T3; for trip time with multi phase faults. According to the setting, the dedicated subroutine: Calculates the equations of the lines that define the nominal curve; Calculates the intersections between these lines and the corresponding angles; Given a line, that passes through the axis origin and is inclined of a certain angle referred to the R axis, calculates the intersections with the characteristic curve in terms of resistance and reactance: these are the nominal values that the test subroutine must compute. Relay Settings: R1 = 1.363 Ohms R1E = 10.613 Ohms X1 = 0.569 Ohms R2 = 1.468 Ohms R2E = 10.72 Ohms X2 = 1.09088 Ohms R3 = 1.8 Ohms R3E = 11.05 Ohms X3 = 2.764 Ohms Line Angle = 78 degree Inclination Angle = 78 degree RE/RL = 0.77 XE/XL = 3.01
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
TEST CIRCUIT OF 7SA610 relay
I1
Ln1
VA
I2
VB
I3
VC
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Before the distance relay test start, output voltage and current are zero. When the program is started, three healthy voltages are applied for a second. After this, the program begins with the test of the general start (if requested); then the faults simulation begins to check the zone limits. Faults are generated as follows. Phase to ground fault: on the selected phase (AN, BN, CN) the voltage decreases while the current becomes the fault current; the voltages of the other two phases are modified. Two-phase fault on the pairs AB, BC, CA. With this selection: The amplitude and the angle of the voltages will be automatically modified to simulate a two-phase fault without ground. The two currents (IA & IB) are equal in module but opposite in phase. Three-phase fault: The three voltages have the same module, and also the three currents. After the relay tripping, the fault lasts for a programmable time (corresponding to the breaker opening delay) before returning to healthy conditions. Before starting with a new fault, healthy values are kept for a programmable time, to allow the reset of the relay under test.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
How to Export the relay settings for Test from DIGSI software?
Double click on “Setting Group A”
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Now, Open address “0013”
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
It shows the zone settings like Zone Z1/Z2/Z3/Z4/Z5.
Now, Zone Z1 settings are; 1301 = Forward 1302----Æ R1 = 1.363 Ohms 1303----Æ X1 = 0.569 Ohms 1304----Æ R1E = 10.619 Ohms 1305----Æ T1 = 0 seconds
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Zone Z2
Now, Zone Z2 settings are; 1311 = Forward 1312----Æ R2 = 1.468 Ohms 1313----Æ X2 = 1.099 Ohms 1314----Æ R2E = 10.720 Ohms 1315----Æ T2 for SLG = 0.3 seconds 1316----Æ T2 for LL & L-L-L = 0.3 seconds
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Now, Zone Z3 settings are; 1321 = Forward 1322----Æ R3 = 1.8 Ohms 1323----Æ X3 = 2.764 Ohms 1324----Æ R3E = 11.05 Ohms 1325----Æ T3 for SLG = 1.0 seconds
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Press on “Graph” button
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
It shows graph for zones
Z1, Z2, Z3 are for LL & L-L-L faults Z1E, Z2E & Z3E are for SLG fault
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Press on “Export” button to export RIO file
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Save file as a “RIO” file in “C” drive
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Now, open the F6TEST software
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Select database
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Create new relay (Ctrl + A) or double click on existing DB
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Click on “Relay parameters” Tab
Press “Import” button to import RIO file
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Open existing RIO file
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Rename file as “K_T_1”.
Press “Apply” button
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
How to open RIO file in F6TEST?
This is the “K_T_1” file & press “show” button
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
It shows zone settings
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Compensation settings are automatically imported
RE/RL & XE/XL
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Click on “TestPlan” Now, Open test plan
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Module type: Z-Char Open Z-char module for characteristic test
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Open “Test Elements” Tab Select setting file “K_T_1”
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Open “Test Configuration” Tab “Test method” Tab
Select “Test Method type” (Constant I, Constant V & Constant Z)
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Open “Test Timing & Trigger selection” Select “time option” (Cycles, Milliseconds, Seconds)
Select Trigger type: AB, BC & CA
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Click on “Test Lines” Tab
Select option: “Radial Lines”
Enter the boundary (say 0 – 20 degree insteps of 10 degrees)
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Click on “Test” Tab.
Select “AB” fault
Select fault type: AB, BC & CA
Phasor shows; magnitude & angle of fault voltage & current
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Results (BC-Fault):
Blue line shows “Expected boundary” & Green points shows actual operating boundary
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Results (CA-Fault):
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Now, select “Ph-N” fault in “Test Elements” Tab
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Test Method: Constant Current
Select “separate arc resistance” options
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Fault type: AN, BN, CN & TRIGGER: Open to Close
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Test Lines for Fault Type: Ph-N Test Lines Method: Radial Lines
Enter Angle Boundary & delta steps
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Click on “Test” Tab
Fault type: AN
Results
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Results: BN-Fault
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Results: CN-Fault
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Time Test: Module Type: Z-TIME Double click on “Time test”
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Fault type: “Ph-Ph” in “Test Elements” Tab
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Test Method: Constant Current
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Fault type: AB, BC, CA TRIGGER NAME TRIGGER CONDITION: Open to Close
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Click on “Add boundary Test Points” button
Z Angle %Zone
“Expected Time” for zone operation
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Results (AB-Fault): Graph shows in “R-X” Plane
%Zone = 94.9% to 105% It should be operated on 94.9% & not operated on 105%
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
Results (AB-Fault):
Graph shows in “Z-T” Plane
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com
India
Knowledge Is Power SM
DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD 305-SAKAR, OLD PADRA ROAD VADODARA-390 015, INDIA PH: +91 265 655 77 15 Cell: +91 94267 47545 Email:
[email protected] Website: www.doble.com
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA www.doble.com