Cummins Speed Controller EFC 3044196 / EFC 3062322

Function: 3044196 Speed Controller is a fully electronic closed loop control design; it is used for fast transient load changes Fast and accurate response to control engine speed, when connected to the match the EFC series actuator and magnetic speed electronic transmission CUMMINS Sensor signals can be perfectly controlled CUMMINS engine. By design, it can be pre-installed simple adjustments, including adjustment of work rate and idle, to help for more than one machine or a special Special use of the input, and to prevent reverse battery voltage, instantaneous pulse voltage, short circuit actuator failures and the loss of speed.

Sensor signal or power supply in case of security protection. 3062322 is the power plus large, can drive the engine of 500KW or more)

Technical Specifications: Speed Stability: Better Than ± 0.25% Speed Range: 1 KHz ~ 6.5 KHz Thermal Stability: ± 0.7% maximum Regulation: 260 ± 20Hz IDLE 85% of Rated Speed DROOP Adjustment: Minimum Position for the 15Hz ± 6Hz / per Ampere of Load Current Changes

Maximum position: 400Hz ± 75Hz /Per Ampere of Load Current Changes External Speed Adjustment: ± 200Hz (external 1KΩ) AUX input sensitivity: 148Hz / 1V ± 10Hz. Impedance: 1MΩ

Environment: Operating temperature range: Operating humidity range: Storage temperature: Shock:

-40~85°C Max 95% RH -55~92°C 20~100Hz 500mm/Sec

Input Power: Supply voltage 12V and 24V DC battery systems, Ground Negative polarity, Power consumption 40mA Actuator continuous current minimum 1A; maximum 4.5A (3062322 maximum current up to 8A) Speed sensor signal: 2 ~120V RMS

Note: The performance parameters are measured at the working frequency of 3800Hz

Installation: Step 1 - 3044196 installation: 1. According to the following data in the appropriate position openings, it is proposed to install anti-slip self-locking screw four mounting holes: 135mm×102mm, 5.5mm Place center of a circle distance: 135mm × 102mm, 5.5mm diameter holes installed 2. In accordance with the following wiring connections can be one to one: 123-4 5-6 7-8-9 1011-

+ Positive Power supply - Negative Power Supply Output For Actuators Input From MPU (Speed Sensor) External Speed Tuning Idle Speed Switch Public Side

Step 2 - 3044196 debug: In the power off, generators do not run the case; adjust the trim to its original position: The IDLE SPEED (idle speed) adjustment to the midpoint (20 laps fine-tuning, the first counter-clockwise in the end, then clockwise Acupuncture can be rotate 10 laps) . Will RUN (running speed) adjustment to the midpoint (20 laps fine-tuning, the first counter-clockwise in the end, then clockwise Acupuncture can be rotate 10 laps). The GAIN (gain) adjusted to 20% to 50% (fine-tuning of a circle). Will DROOP (speed droop rate) adjusted to 0. DROOP operation: regulating DROOP to load to full load value between the dates required, to adjust clockwise DROOP will increase.

Start the engine: Adjust potentiometer to control the speed of the engine is operating at a predetermined rotating speed Clockwise to increase Engine speed. GAIN if the speed controls system instability that is slightly lower GAIN settings. GAIN: When the engine is a no-load, GAIN adjustment is as follows: The GAIN adjustment clockwise until the engine speed slowly began to swing. Then slowly rotate counter-clockwise to reduce the GAIN value until the speed of adjustment stable.

Synchronous operation (ISOCHRONOUS) should pay attention when: To use synchronized operation, they have to DROOP in the end turned the knob and then it started. Speed droop rate of operation is controlled by the DROOP button; clockwise rotation will increase its rate of speed droop; To set the speed droop rate value, must be made light of MPU and the throttle actuator frequency axis in No load to full load under the rotation. For example, when MPU access frequency of 4260Hz and the throttle actuator axis Rotation between the no-load to full load is about 30 degrees, it will DROOP button can be set in the 10 clock position Provide about 4% set by the air speed to full speed pulse droop rate; and lower electromagnetic pulse frequency or speed Smaller axis of rotation will make the system speed droop even lower.