31504569-TP48300-A Power System Quick Installation Guide(V100R001_05)
April 6, 2017 | Author: ryl_fans_neh | Category: N/A
Short Description
Download 31504569-TP48300-A Power System Quick Installation Guide(V100R001_05)...
Description
Prepare the following tools before the installation:
1
Flat-head screwdriver (M3M4)
Phillips screwdriver (M3M4)
Adjustable wrench
Nylon tie
Percussion drill
Ф12 drill bit
Wire stripper
Ratchet crimp tool
Diagonal pliers
Paint brush
Key to cabinet
Multimeter
Insulating tape
Marking pen
Vacuum cleaner
Hydraulic pliers
Insulating handle
Electric knife
Socket wrench
Torque wrench
Heat gun
A-shaped ladder (2 m)
Installing the Cabinet
According to actual conditions, use one of the following modes to install the cabinet: installing the cabinet on the rack of storage batteries, installing the cabinet on the ground, installing the cabinet on the 19-inch open rack, installing the cabinet on the BTS cabinet. The cabinet must be installed at the place which no more than 3m distance from the DC load.
Installing the Cabinet on the Rack of Storage Batteries According to actual conditions, use one of the following modes to install the cabinet: installing the cabinet on the rack of storage batteries directly, installing the cabinet on the rack of storage batteries using conversion board.
Installing the Cabinet on the Rack of Storage Batteries Directly 1 Install the rack-mounting ears to the cabinet. 2 Move the cabinet to the installation position on the rack of storage batteries. 3 Align the expansion bolt holes on the base in the front of the cabinet with the
installation holes for the bolt holes on the rack of storage batteries.
1
Rack-mounting ears
Operation side
4 Fix the bolts into the holes and fasten the bolts.
Ф8×20 mm (4pcs)
NOTE The layout of installation holes on the rack of storage batteries varies with the rack model. Align the first bolt hole on the base with the bolt hole on the storage rack, and then install other bolts in the proper holes.
Installing the Cabinet on the Conversion Board 1 Install the rack-mounting ears to the cabinet. 2 Install the conversion board on the rack of storage batteries.
Ф10×25 mm (4pcs) 1
2
Rack-mounting ears
Operation side
3 Align the expansion bolt holes on the base in the front of the cabinet with the installation holes for the bolt holes on the
conversion board.
4 Fix the bolts into the holes and fasten the bolts.
Ф8×20 mm (4pcs)
Installing the Cabinet on the Ground 1 Determine the installation position of the cabinet, and then mark the positions of the holes to be drilled with a marking pen.
Unit: mm 确认机柜安装位置,用粉笔标出打孔位置。 单位:mm Cabinet outline
316 Installation hole 4- 10
450
2 Drill holes at the hole positions, feed expansion bolts into the holes, and then secure (hammer and then tighten) the
expansion bolts. 确认机柜安装位置,用粉笔标出打孔位置。 单位:mm
Nut Spring washer Flat washer
Unit:mm
Expansion tube
Ф8×60 mm (4pcs)
Expansion trough Cone-head bolt 12
52-60
3 Install the rack-mounting ears to the cabinet. Place the cabinet on the expansion bolts, and then tighten the bolts.
Installation hole
Rack-mounting ears
Installing the Cabinet on the 19-inch Open Rack (IMU) 1 Fix the rack-mounting ears into the bolt holes at both sides of the cabinet. Ensure that the base of the rack-mounting ears.
install direction faces the front of the cabinet
确认机柜安装位置,用粉笔标出打孔位置。 2 Determine the installation position of the cabinet on the 19-inch open rack, and then install the Ф6 floating nuts at the holes 单位:mm for bolts. The recommended installation height of the cabinet is 1.5 m. The actual installation height of the cabinet must be determined according to the stature of installation personnel and installation requirements.
Floating nut
3
Side of the cabinet
2
4 Move the cabinet to the installation position of the 19-inch open rack, and then install the cabinet on the open rack.
确认机柜安装位置,用粉笔标出打孔位置。 单位:mm
3
Ф6×12 mm (4pcs)
CAUTION A minimum of three persons are required for safe installation on the 19-inch open rack. Otherwise, the cabinet may fall and cause injury.
Installing the Cabinet on the BTS Cabinet 1 Install the rack-mounting ears to the cabinet. 2 Install the conversion board on BTS cabinet.
2
1
Rack-mounting ears
Ф10×25 mm (2pcs) Ф6×12 mm (4pcs) Operation side 3 Align the expansion bolt holes on the base in the front of the cabinet with the installation holes for the bolt holes on the
conversion board.
4 Fix the bolts into the holes and fasten the bolts.
Ф6×12 mm (4pcs)
2
Installing Sensor
1 Installing indoor temperature and humidity sensor.
M4 X 35 Expansion Bolt
60
Shelter
m
m
Indoor temperature and humidity sensor
Indoor temperature and humidity sensor
Main equipment
2 Installing battery temperature sensor.
Connect to battery Connect to TP48300A
3
Installing the PGND Cables
1 Unlock and open the cabinet door, and then remove the cover plate of the cable window on the top of the cabinet.
Cover plate
2 Lead the PGND cables into the cabinet through the cable window, and then route the cables along the panels of the cabinet. NOTE Please installing the cabinet according to actual conditions: load power-off tributary using fuse, load power-off tributary using MCB.
Load power-off tributary using fuse DC output positive wiring busbar Negative pole of the battery The protection MCB on the battery Load power-off fuse Transfer copper bar AC input MCB
Monitoring module Earthing busbar of the cabinet AC surge protector
Rectifier module
Load power-off tributary using MCB
DC output positive wiring busbar Negative pole of the battery The protection MCB on the battery Load power-off MCB Transfer copper bar AC input MCB
Monitoring module Earthing busbar of the cabinet AC surge protector
Rectifier module
3 Connect the PGND cables to the earthing busbar.
CAUTION The PGND cables, AC cables, DC cables, signal cables, and communication cables must be bound separately.
4 Bind the PGND cables.
Load power-off tributary using fuse
4
4
3
3
The earthing busbar Load power-off tributary using MCB
4
4
3
3
The earthing busbar 5
Load power-off tributary using fuse
Use an insulating handle to remove battery fuses and load power-off fuses.
Load power-off tributary using MCB
Use an insulating handle to remove battery fuses and set the load power-off MCB to
OFF .
10
4
Installing the Dry Contact Signal Cables and Communication Cables (Optional) NOTE 1. The use of the dry contact signal cables and communication cables is scenario-specific.According to actual requirements, determine the dry contact signal cables and communication cables to be installed before installation. 2. Functions of dry contact points.
Alarm Type
Default Function
Description
ALM1
AC power-off alarm
ALM2
DC input overvoltage and undervoltage DC input undervoltage alarm port (DC Low)
ALM3
Power supply system fault alarm
Rectifier module fault alarm port (PSU Fail)
ALM4
Surge protector failure alarm
Surge protector alarm port (SPD Fail)
ALM5
Fuse disconnection alarm
Fuse disconnection alarm port (Fuse Alarm)
ALM6
Battery protection
Battery low-voltage isolation disconnection alarm port (Batt.LVD)
ALM7
Standby dry contact output 1
Reserved dry contact 1 (Reserve 1)
Ctrl1
Control for the diesel generator 1
Port for starting and stopping the Generator 1
Ctrl2
Control for the diesel generator 2
Port for starting and stopping the Generator 2
Detection for the running status of the diesel generator Detection for the start/stop control signals of diesel generator 1 Detection for the start/stop control signals of diesel generator 2
Port for detecting the running status of the diesel generator
Status Status1 Status2
AC input power-cut alarm port (AC Fail)
Port for detecting the start.stop signals of diesel generator 1 Port for detecting the start.stop signals of diesel generator 2
J13, J14, J4-J10 are nine dry contact sockets on the monitoring back plane. Status, Status1, Status2 are three circuits for the input of the detection signals of the diesel generator. Ctrl1 and Ctrl2 are two circuits for the output of the control signals of the diesel generator. ALM1-ALM7 are seven circuits for the output of the alarm signals of the diesel generator. Each circle represents the corresponding wiring terminal. The black circles are the common terminals of the constant-enabled ports and constant-disabled ports on the relays.NC represents constant-disabled port and NO represents constant-enabled port.By default, the output of the dry contact is set to OFF.
2
1
1 Lead the dry contact signal cables and communication cables into the cabinet through the cable window, and then route the
cables along the panels of the cabinet.
2 According to the actual installation requirements, use a flat-head screwdriver to prop up the white contact plates to have
the metal dome sheets in the ports spring up. Insert the dry contact signal cable into the dry contact points, and pull out the screwdriver to fasten the signal cable.
Dry contact point 1
2
White contact plate
11
3 According to the actual installation requirements, insert the communication cables into the RJ45 ports on the monitoring
backplane.
2
1
Communication cable 4 According to the actual installation requirements, Insert the temperature and humidity sensor signal cable and battery
temperature sensor signal cable.
Indoor temperature and humidity sensor
Battery temperature sensor
5 Bind the dry contact signal cables and communication cables on the cable window separately, and then route all the
cables to the distribution frame.
5
Installing the DC Output Cables
DC output distribution can be customized.
Load power-off power-off tributary tributary using using fuse fuse Load 1 Insert the –48 V DC output cable into the output port on the battery protection MCB. 2 Loosen the bolt on the top of the load power-off fuse, connect the –48 V output cable to the bolt, use torque wrench to tighten
the bolt, force moment as 10 Nm.
3 Connect the 0 V output cable to the DC output positive wiring busbar. 4 Bind the DC output cables on the cable window. Ensure that the DC output cables are separated from other cables.
12
CAUTION 1. The force moment of tightening the bolt must less than 10 Nm. 2. The signal cables must be installed in the front of the –48 V cables.
1
2
3
Load power-off tributary tributary using using fuse MCB 机柜负载下电支路采用熔丝 Load power-off 1 Insert the –48 V DC output cable into the output port on the battery protection MCB. 2 Connect the 0 V output cable to the DC output positive wiring busbar. 3 Bind the DC output cables on the cable window. Ensure that the DC output cables are separated from other cables.
1
2
13
6
Installing the Power Cables of the Storage Battery Load power-off tributary tributary using using fuse fuse 机柜负载下电支路采用熔丝 Load power-off
1 Connect the of the storage battery to the DC output positive wiring busbar. 2 Loosen the bolt on the top of the base of the battery negative-pole access fuse, connect the –48 V input cables to the bolt,
and use torque wrench to tighten the bolt, force moment as 10 Nm.
3 Arrange the output cables, and then use a nylon bundling tape to bind the cables to the bundling tie at the rear of the cable
window.
CAUTION 1. Ensure that the signal cables are installed in the front of the battery negative-pole input cable and that the battery protection MCB is set to OFF. 2. When installing a fuse for the load storage batteries, ensure that the bare metal part of the screwdriver does not touch the positive bus and the fuse wiring terminal, otherwise a short circuit may be caused. 3. The force moment of tightening the bolt must less than 10 Nm. 4. If only one group of batteries is connected ,it should be connected to BF1.
Battery negative-pole 1
2
Battery positive-pole
BF1
BF2
BF1- BF2-
Load power-off tributary tributary using using fuse MCB 机柜负载下电支路采用熔丝 Load power-off 1 Connect the of the storage battery to the DC output positive wiring busbar. 2 Loosen the bolt on the top of the base of the battery negative-pole access fuse, connect the –48 V input cables to the bolt,
and use torque wrench to tighten the bolt, force moment as 10 Nm.
3 Arrange the output cables, and then use a nylon bundling tape to bind the cables to the bundling tie at the rear of the cable
window.
CAUTION 1. Ensure that the signal cables are installed in the front of the battery negative-pole input cable and that the battery protection MCB is set to OFF. 2. When installing a fuse for the load storage batteries, ensure that the bare metal part of the screwdriver does not touch the positive bus and the fuse wiring terminal, otherwise a short circuit may be caused. 3.The force moment of tightening the bolt must less than 10 Nm 4. If only one group of batteries is connected ,it should be connected to BF1.
Battery negative-pole 2
1
Battery positive-pole
BF1- BF2-
14
7
Installing the AC Input Cables AC input MCB using 3-pole MCB 机柜负载下电支路采用熔丝
1 The cabinet supports the single-phase and three-phase AC input cables, which must be installed in different ways.
Mode 1: To install the single-phase AC input lines, perform the following steps: a) Connect the neutral line to the N-terminal.b) Install the copper bar on the AC input MCB. c) Connect live line to the copper bar. N-terminal a
c
b
Neutral line
Input copper bar
Live line
Mode 2: To install the three-phase AC input lines, perform the following steps: a) Connect the neutral line to the N-terminal. b) Connect the U-phase, V-phase, and W-phase lines to the AC input MCB. N-terminal a
b
Neutral line
AC input MCB using 4-pole MCB 机柜负载下电支路采用熔丝 To install the three-phase AC input lines, perform the following steps: Connect the N-phase, U-phase, V-phase, and W-phase lines to the AC input MCB.
U V W
N
15
2 Install the plastic protection plate. 3 Bind the AC input cable to the nearest bundling tie.
2
3
电池负极 1Plastic protection plate
8
2
电池正极
Checks After the Installation
1 Ensure that the cabinet and cables are secure. BF1-a multimeter BF22 According to the connecting diagram, ensure that the cables are installed properly by sight or with and that the BF1
BF2
live line, earth line, and neutral line are not short-circuited.Ensure that the 0 V cable and –48 V cable are not short-circuited.
3 Insert the removed fuses into the corresponding positions.
Scenario1: load power-off tributary using fuse.
电池负极 2
1
电池正极
BF1- BF2-
Scenario2: load power-off tributary using MCB.
4 Ensure that the AC input MCB and battery power-off MCB is set to ON.Check whether the MCBs and fuses are not dam-
aged with a multimeter and replace the damaged MCBs or fuses.
5 Cut the cover plate of the cable window on the top of the cabinet according to the cabling conditions, and then place the cover
plate back to its original position.
6 Ensure that the cabinet door is closed and locked. 7 Check whether paint on the surface of the cabinet is improper and repaint the surface of the cabinet where paint falls off.
16
9
Cabling guide The scenario with Cabling Rack 1 The power cable of the storage battery
NOTE The AC input cables and signal cables must be bound and routed separately.
2 DC output cable 3 PGND cable 4 AC input cable 5 Dry contact signal cable 6 Temperature and humidity sensor signal cable 7 Battery temperature sensor
1 4
-
2
3 6
5
7
2
6
4
5
+
3
-
+
+
-
+ +
1
+ c
7
a 1
b
Cutaway view: a
Cable Cable Rack
17
b
Cable Rack
c
Cable Rack
The scenario without Cabling Rack 6
2
1 The power cable of the storage battery
5 4
2 DC output cable
3
NOTE The AC input cables and signal cables must be bound and routed separately.
3 PGND cable 4 AC input cable 5 Dry contact signal cable 6 Temperature and humidity sensor signal cable 7 Battery temperature sensor
-
1
7 6 2
4
5
+
3
-
+
+
-
+
-
+
+ 1
c
a
7 b
1
Cutaway view: a
Cable Cable Rack
18
b
Cable Rack
c
Cable Rack
10 a
Power-on Testing
Conducting a power-on test
Power on TP48300/A power system. CAUTION Do not power on the DC load before the storage batteries parameter is correctly set on the CPMU01 , otherwise, it will cause damage to storage batteries.
b
Setting the monitoring system
NOTE 1. The position of the CPMU01 monitoring module, operating keyboard, and status indicator are shown in the following figure. 2. When the TP48300/A power system is working properly and communicate with the main equipment, the ALM indicator on the CPMU01 does not light and the RUN flash slowly. When the TP48300/A power system is working properly and the TP48300/A power system does not communicate with the main equipment, the ALM indicator on the CPMU01 does not work and the RUN indicator is ON. When the TP48300/A power system has serious alarms, the ALM indicator on the CPMU01 is ON and the buzzer sounds. For details, see the TP48300/A power system Maintenance Guide. 3. When the system is in standby mode, press "↓" and "Enter" at the same time to reduce the contrast of the LCD or press "↑" and "Enter" at the same time to increase the contrast of the LCD. 4. Before setting the CPMU01 menu, press "↓" or "↑" to select options and configure values.Press "Enter" to enter the main menu when the system is standby. On the main menu, press "Enter" to view the submenu, and save the configuration by pressing "Enter" on the submenu.Press Cancel to undo the operation and return to the upper menu without saving the configuration. 5. The PMU does not generate any alarm. When the current interface is not the main menu, the LCD goes dark five minutes later if you do not press any button, and the main menu is displayed eight minutes later if you do not press any button. 6. -On the System Control interface, you can access the system with the user password, engineer password, or administrator password.3. On the Engineer Advanced Setting interface, you can access the system with the engineer password or administrator password.The user password and engineer password are 0# and 11# respectively and can be reset on the menu.The administrator password is provided by Huawei.
Set the parameters: 1 Group and capacity of batteries.
NOTE The number of the battery group can be set as 0, 1 or 2. Please set the number of the battery group and capacity according to actual configuration. If you face to the door, the fuse at the leftside is BF1- and the fuse at the rightside is BF2- . 1. If only one group of batteries is connected, please connect to BF1- , set the number of the battery group as 1, and set "battery capacity 1" according to actual configuration. 2. If two groups of batteries are connected, please separately connect to BF1- and BF2- , set the number of the battery group as 2, and set "battery capacity 1", "battery capacity 2" according to actual configuration. 3. If four groups of batteries are connected, two battery groups connect to BF1- and the other two battery groups connect to BF2- , set the number of the battery group as 2, and set "battery capacity 1", "battery capacity 2" according to total actual capacity of every two battery groups. 4. This guide take two groups of 300Ah batteries as an example.
2 Temp Alarm. 3 time and date.
19
English
English
English
English
中 文
中 文
中 文
中 文
▼
ENT
2008-08-06 53.6VDC 227VAC Load:0.2A Batt:0.0A
ENT
▼
MAIN MENU Status Maintenance Settings
ENT
▼
▼
2008-08-06 53.6VDC 227VAC Load:0.2A Batt:0.0A
ENT
ENT
Batt Settings Batt Selection LVD Setting Charge
▼
ENT
▼
ENT
▼
ENT Address:0 Text:English Comm Mode:Modem Band:9600
Batt Selection Batt String:1 Cap.1:400Ah Cap.2:0Ah
Temp Comp Basis: Batt 1 Temp Comp: 80mV/ ℃
ENT
▼ ENT
Batt Selection Batt String:2 Cap.1:400Ah Cap.2:0Ah
▼ ENT
Batt Selection Batt String:2 Cap.1:400Ah Cap.2:0Ah
▼ ▼or
▼ ▼or
▼ ▼or
Low Temp Alarm: 0℃ High Temp Alarm: 50℃
ENT
Batt Selection Batt String:2 Cap.1:300Ah Cap.2:0Ah
ENT
Batt Selection Batt String:2 Cap.1:300Ah Cap.2:0Ah
▼ ▼or
▼ ENT
ENT
Batt Selection Batt String:2 Cap.1:300Ah Cap.2:300Ah
20
▼ ▼or
ENT
▼ ▼or
ENT
Date: 2008-08-08 Time: 09:10
ENT
▼ ENT Date: 2008-08-08 Time: 09:10
Low Temp Alarm: 0℃ High Temp Alarm: 50℃
ENT
▼
Setting System Settings Alarm Settings AC Settings
Batt Settings Batt Test Temp coeff
▼ ENT ▼or
▼
MAIN MENU Status Maintenance Settings
ENT
▼
ENT
Settings DC Settings Batt Settings AMB. Settings
ENT
ENT
2008-08-06 53.6VDC 227VAC Load:0.2A Batt:0.0A
▼
ENT
▼
▼
MAIN MENU Status Maintenance Settings
Settings DC Settings Batt Settings AMB. Settings
Address:0 Text:English Comm Mode:Modem Band:9600
Load Shunt:Yes Pisp Contrast:3 System Type: TP48300/A
▼
ENT
ENT
ENT
ENT
2008-08-06 53.6VDC 227VAC Load:0.2A Batt:0.0A
ENT
Load Shunt:Yes Pisp Contrast:3 System Type: TP48300/A
▼
MAIN MENU Status Maintenance Settings
Setting System Settings Alarm Settings AC Settings
▼
ENT
ENT
c
Monitoring Menu Structure
Appendix 1 Main menu Parameter setting
System control
Running information
Address Automatic
Control Mode
Module ID
Floating charging
Output current Current limit Start
Status Alarm SN Alarm severity
Major alarm
Generation time
System parameter setting
Date Time
Quick test
Load current divider
Password modification
Display contrast
End test
Parameter initialize
System type
Equalized charging
Engineer advanced setting
On
Dormant permit Alarm type
Modules 1-6
Alarm severity Off
Alarm SN
Alarm parameter setting
Alarm control parameter
Alarm severity
Minor alarm
Alarm name
Relay relate
Generation time
Digital alarm
Alarm SN
AC parameter setting
Alarm severity History alarm
Baud rate
Standard test
Alarm name Current alarm
Communication on mode
Manual
Output voltage Module information
Language
DC parameter setting
Alarm name
Battery parameter setting
Generation time End time
Environment parameter setting
Severity Alarm sound Clearing of history alarms Alarm type Relate relay
Overvoltage Undervoltage Overvoltage Undervoltage Appendix 2 High limit Low limit High temperature Low temperature Generator enable
Battery test result
Output power DG parameter setting
DOD High-TEMP switch-off DG switch-on temperature
Version disply
DG switch-off temperature Air-conditioner parameter setting
21
Type Power
Appendix 2
Battery string Capacity
Battery parameter
Installation date Load power-off permit Power-off parameter
Battery power-off permit Battery power-off voltage Load power-off voltage Floating charging
Charging parameter
Equalized charging equalized charing period Charging current limit
Battery parameter setting
Auto test permit Start test period Test end voltage
Auto test
Test time Battery test
Test delay Test time
Short test
Test end voltage
TEMP compensate basis TEMP compensate factor High-TEMP power-off permit Battery temperature factor
High-TEMP power TEMP TEMP alarm lower limit TEMP alarm upper limit Upper limit Lower limit
d
CPMU01 Menu Reference Main Menu
Setting
Second-Level Menu
third-Level Menu
Fourth-Level Menu
System Setting
Eng Setting
22
Paremeter
Value
Address
0
Text
English
Comm Mode
Modem
Band
9600
Date
2001-01-01
Time
00:00
Load Shunt
Yes
Disp Contrast
3
System Type
TP48300/A
Modify PWD
None
Init Para
No
Rect Sleep
No
Main Menu
Second-Level Menu
third-Level Menu
Fourth-Level Menu
Setting
Paremeter
AC ON/OFF
Serious
AC Volt Low/High
Common
DC Volt Low/High
Serious
Load Off Alarm
Serious
Batt Off Alarm
Serious
Batt Fuse Alarm
Serious
Temp1 Alarm
Alarm Level Alarm Setting
Digital Alarm
Digital 1
Alarm Control Relay Relate AC Setting DC Setting
Batt Setting Batt Setting LVD Setting
Charge
23
Value
Common
Humidity Alarm
No Alarm
Batt Temp Alarm
Common
Door Alarm
Common
Water Alarm
Serious
Smoke Alarm
Serious
Rect Fail
Serious
Rect Protect
Common
Rect Comm Fail
Common
Charge Curr High
Common
Switch 1
Common
Switch 2
Common
DC SPD Alarm
Common
AC SPD Alarm
Common
Switch 5
Common
Switch 6
Common
Switch 7
Common
Wire Alarm
Serious
Generator Fail
Serious
Load Fuse Alarm
Serious
Alarm Type
High
Set Alarm Name
Switch 1
Audible Alarm Clr Hist Alarm
Yes No
Alarm Relate Relay Over Volt
AC OFF 1 280V
Under Volt
180V
Over Volt
58.0V
Under Volt
45.0V
Batt String
1
Cap 1 Cap 2
400Ah 0Ah
Install Date LLVD Enable BLVD Enable
Yes Yes
LLVD
44.0V
BLVD Float Boost
43.0V 53.5V 56.5V
Cyc BC Duration
60 days
Curr Limit
0.10C10
2001-01-01
Main Menu
Second-Level Menu
third-Level Menu
Batt Setting
Fourth-Level Menu
Auto Test Batt Test
Short Test Setting
Temp Coeff
AMB Setting
Generator
Air-condition
Paremeter
Value
Auto Test Enable
Disch Test
Cycle
120 days
Test End Volt
1.9V
Duration Test Dlay Test End Volt
10 hours — 45.0V
Duration
60 min
Temp Comp Basis
Batt 1
Temp Comp
80mV/℃
BHTD Enable
No
BHTD Temp
53℃
Low Temp Alarm
0℃
High Temp Alarm
50℃
Upper Limit
80℃
Lower Limit
-20℃
Upper Limit
80℃
Lower Limit
-20℃
High Alarm
50℃
Low Alarm
0℃
Generator Enable
No
Output Power
12.5kW
Discharge Depth
30%
High Temp OFF
Yes
Start Temp
45℃
OFF Temp Type
29℃ Single-Phase
Power
1.0kW
Rectifiers Status
Active Alarm
Major Alarm * Common Alarm *
History Alarm Batt Test Result
No Record
Version Disply
V100R001C01******** Auto
Mgmt Mode
Manual FC Std Test
Start
Quick Test End Test BC
Maintance
Rect1 Rect2 Rect3
Rect1
Rect4 Rect5 Rect6
24
ON
Appendix 3
TP48300/A Mini Power System Parameter List CAUTION Please set the number of the battery group, battery capacity, battery temperature and environment temperature according to actual configuration.
Item
Setting Bound
Factory Setting
Battery String
0~2
1
Battery Cap 1
30~1000
400Ah
Battery Cap 2
30~1000
0Ah
LLVD
BLVD~DC Under volt
44.0V
BLVD
35V~LLVD
43.0V
Battery Float
43.2V~57.6V
53.5V
Battery Boost
43.2V~57.6V
56.5V
Rect Sleep
YES/NO
NO
LLVD Enable
YES/NO
YES
BLVD Enable
YES/NO
YES
Current Limit Coefficient
0.05~0.25
0.1
Battery High Temp -50℃~100℃ Alarm Environment High -50℃~100℃ Alarm
50℃ 50℃
25
1st Rev Date
Sign 2st Rev
Date
Sign
View more...
Comments