TSR N: E-FD-7010.00-62 E-FD-7010.00-6240-800-A 40-800-AEV-003 EV-003

REV: A

AST N 31  3 127-I-HD-003

REV: A

Sh..: 1 Of: 15

CLIENT: TRANSIERRA S.A JOB: GASYRG ESTACION DE COMPRESION VILLAMONTES JOB N: 3127

DATA SHEET

CONTROL VALVES

 A 0 REV.

29-4-2003 14-1-2003 DATE

ISSUE FOR CONSTRUCTION ISSUE FOR APPROVAL DESCRIPTION

DP DP BY

OS OS CHKD.

GN GN APPROVAL

TSR N: E-FD-7010.00-6240-800-AEV-003

Rev.: A

Sh.: 2 Of: 15

AST N: 3127-I-HD-003

CLIENT: TRANSIERRA S.A. JOB: GASYRG ESTACION DE COMPRESION VILLAMONTES

CONTROL VALVE LIST N! TAG

SERVICE

LOCATION

P&ID

MANUFACTURER / MODEL

SHEET

LV

- 016

FT-0201 DRAIN

Skid 0201

3127-F-PI-009

Fisher / 357 (1")

3

LV

- 017

FT-0201 DRAIN

Skid 0201

3127-F-PI-009

Fisher / 357 (1")

4

LV

- 022

FT-0202 DRAIN

Skid 0202

3127-F-PI-009

Fisher / 357 (1")

5

LV

- 023

FT-0202 DRAIN

Skid 0202

3127-F-PI-009

Fisher / 357 (1")

6

TV

- 106A

Fuel gas heater

Skid 0205

3127-F-PI-013

Fisher / YD (3")

7

TV

- 106B

Fuel gas heater

Skid 0205

3127-F-PI-013

Fisher / YD (3")

8

PV

- 107A

Fuel gas to TC

Skid 0205

3127-F-PI-014

Fisher / ET (2")

9

PV

- 107B

Fuel gas to TC

Skid 0205

3127-F-PI-014

Fisher / ET (2")

10

PV

- 109

Start up gas to TC

Skid 0205

3127-F-PI-014

Fisher / ET (2")

11

TV

- 175A

Fuel gas to MG

Skid 0204

3127-F-PI-019

Fisher / YD (1")

12

TV

- 175B

Fuel gas to MG

Skid 0204

3127-F-PI-019

Fisher / YD (1")

13

PV

- 181A

Gas to MG fuel gas filter

Skid 0204

3127-F-PI-009

Fisher / 357 (2")

14

PV

- 181B

Gas to MG fuel gas filter

Skid 0204

3127-F-PI-009

Fisher / 357 (2")

15

 

References:

NOTES

New  A

1. P&IDs 3127-F-PI-009 a 022 Rev B  

Notes:

1) Not only the valve but also actuators shall be supplied with their TAGS engraved on a name plate. 2) Solenoide valve will be suitable for Zone 2 Gr IIA T3, IP55, provided with terminal block. Low power solenoids must be employed. The insulation class of solenoid valves coils must be selected in accordance with environmental temperature and the temperature raise in the solenoid itself (minimum class F). The use of Solenoid valves with manual return handle must be avoided.  Ambient temperatures: Minimum: 10,4 C Normal: 25,2 C Maximum:40 C 3) All tubing and fitting for connecting the additional equipment and actuator shall be integral part of valve vendor !s supply. Tubing and fitting shall be stainless steel (A ISI 316). Fitting shall be double ferrule type.

3127-I-HD-003-A.xls