3 Winding Transformer Impedance Calculation in IEC Short Circuit Study

July 3, 2019 | Author: drboud | Category: N/A
Share Embed Donate


Short Description

Transformer Impedance Calculations...

Description

ETAP Knowledge Base

3-Winding Transformer Impedance in IEC Short Circuit Study Description: Calculation of 3-Winding Transformer Impedance in IEC Short Circuit Study Category:

3-Winding Transformer Impedance

Type:

Information

Keywords:

3-Winding Transformer, Impedance

3-Winding Transformer Impedance in IEC Short Circuit Study While calculating transformer impedance in IEC short circuit study impedance correction factor (KT) is used as per IEC 60909.

Where, KT - Impedance Correction Factor Cmax - Voltage factor related to the terminal voltage of the network connected to the low-voltage Side of the network transformer xT - Relative Reactance of the transformer ZTK = ZT X KT So for a 3-Winding Transformer Transformer

This document is confidential and proprietary to Operation Technology, Inc. and may not be reproduced, published or disclosed to others without the written authorization authorization of Operation Technology, Inc., Inc., 17 Goodyear, Suite 100, Irvine, CA 92618, USA. © 2011 by Operation Technology, Inc. Inc. All Rights Reserved. Reserved.

© Operation Technology, Inc.

Page 1 of 4

ETAPKB

ETAP Knowledge Base

3-Winding Transformer Impedance in IEC Short Circuit Study Calculations performed for an example

Input data

This document is confidential and proprietary to Operation Technology, Inc. and may not be reproduced, published or disclosed to others without the written authorization of Operation Technology, Inc., 17 Goodyear, Suite 100, Irvine, CA 92618, USA. © 2011 by Operation Technology, Inc. All Rights Reserved.

© Operation Technology, Inc.

Page 2 of 4

ETAPKB

ETAP Knowledge Base

3-Winding Transformer Impedance in IEC Short Circuit Study Calculations

This document is confidential and proprietary to Operation Technology, Inc. and may not be reproduced, published or disclosed to others without the written authorization of Operation Technology, Inc., 17 Goodyear, Suite 100, Irvine, CA 92618, USA. © 2011 by Operation Technology, Inc. All Rights Reserved.

© Operation Technology, Inc.

Page 3 of 4

ETAPKB

ETAP Knowledge Base

3-Winding Transformer Impedance in IEC Short Circuit Study

‘Branch Connections’ output report of a IEC short circuit study The results displayed on the output report and results calculated are identical.

This document is confidential and proprietary to Operation Technology, Inc. and may not be reproduced, published or disclosed to others without the written authorization of Operation Technology, Inc., 17 Goodyear, Suite 100, Irvine, CA 92618, USA. © 2011 by Operation Technology, Inc. All Rights Reserved.

© Operation Technology, Inc.

Page 4 of 4

ETAPKB