2nd Assignment - Furnace(1)
Short Description
assignment to enhance students' understanding on furnace mechanism...
Description
HAZOP STUDY PROCESS
Furnace/burner used to heat up using fuel oil + air Heating oil to 250 C to supply to Distillation re boiler
SECTION DATE
FURNACE
NODE NO
1
100 PARAMETER
PRESSURE
Guide Words
Deviation
MORE -
MORE - PRESSURE
posssible causes
possible consequences
Piping/tube thermal shock and craking lead to leakage of continously high flame the heating oil to the furnace and get contact with the to the furnace. flame and resulting to high temperature in furnace cause cracking and Explosion fuel gas valve malfuction - more fuel gas into the furnace
More fuel gas in the furnace, lead to high temperature in normal operation and may cause explosion during startup. Explosion at furnace stack or Fuel gas release to atmosphere in normal operation
Safe Guard/Prote Action required/Recommendation ction PIC 1, PT-1, PI- High Alarm, 4, PI-5 High-high Alarm, Fuel gas control valve - fail close PI 3, PI 6 & FI Interlock shut off valve 3 Pressure Safety Valve to flare Fuel gas control valve - fail close PI 3, PI 6, FI 3 Interlock shut off valve & AT-1 Pressure Safety Valve to flare
Flue gas control valve, High temperature of hot oil to reboiler, Distillation column PIC 1 malfaction - close experience high pressure that possible to crack and position explosion.
-
Air supply to the furnace high flow & pressure
2
PRESSURE
LESS -
LESS - PRESSURE
FT 2 & PI 2
TEMPERATURE
TEMPERATURE
COMPOSITION
MORE -
LESS -
NOT CORRECT -
MORE TEMPERATURE
LESS TEMPERATURE
NOT CORRECT COMPOSITION
Flow Recordable Control Alarm (FRCA) link to fuel control sytem
Less combustion The oil has not been heating up. The reboiler not reboil the (May caused by either PIC 1, PT-1, PIHC, the distillation flooding, liquid HC over flow to the Pressure Low Alarm less air pressure or less 4, PI-5 upper stream of distillation column. fuel gas) More fuel gas in the furnace, lead to explosion especially Less air pressure to during start-up or fuel gas release to atmosphere through FT 2 & PI 2 furnace for combustion stack due to low combustion
3
Pressure Safety Valve to flare
Additional one parallel air compressor by automatic cut in.
Less fuel gas to the furnace
The oil has not been heating up. The reboiler not reboil the FI 3, PI 3 & PI HC, the distillation flooding, liquid HC over flow to the 6 and bypass Flow Low alarm upper stream of distillation column. valve
High flame in the furnace (high fuel and air)
Piping/tube crack or burst due to overheating, mixture of oil burn and cause black smoke release
TI 8
Automatic shut down heater on low air flow and/or low air/fuel ratio.
High coke in furnace and piping, less heat transfer
TI 8
Maintenance (cleaning)
less hot oil flow to the tubing (less heat transfer )
Thermal craking to the furnace - fuel gas release can cause FT 1 a jet fire
BCPS link to FT 1 and Low flow alarm
No ignition and No flame in the furnace
High Fuel gas in the furnace - when it ignited it will exploded during start-up
pilot light
Temperature alarm low, additional one pilot light , automatic cut off the fuel and air supply
No heat transfer to Hot oil - No heating to reboiler of the distalltion column, if the Feed of the distillation is liquid, the distillation will flooding
pilot light
Temperature alarm low, additional one pilot light , automatic cut off the fuel and air supply
No air Flow
High Fuel gas in the furnace - when it ignited it will exploded
FT 2, PI 2
Air Flow Alarm Low and automatic shut down the fuel supply on low air flow and/or low air/fuel ratio.
No fuel flow
No heat transfer to Hot oil - No heating to reboiler of the distalltion column, if the Feed of the distillation is liquid, the distillation will flooding
FI 3
Fuel Flow Alarm Low and automatic shut down the air supply on low air flow and/or low air/fuel ratio.
-
Automatic shut down the heater on low air flow and/or low air/fuel ratio.
not corret stoikometri for perfect combustion High black smoke release to Atmosphere. of fuel gas Less heat transfer to the hot oil tubing/piping, less separation in distillation column, can lead to tower flooding,
4
OTHERS VALVE
PILOT LIGHT
MAINTENANCE SHUT DOWN & START UP
fuel gas valve un-adequate malfuction - cause maintenance of valve leakage to and instrument furnace. no pilot light
un-adequate maintenance of valve and instrument
un adequate maintenance of Budget Control and unPiping and aware of the risk instrumentation Not follow Human Factor Procedure
explosion when fuel gas over filling in the furnace with out combustion, and operator tried to start up the plant.
explosion when main firing started. explosion when the enough pressure of fuel gas in the furnace Instrument malfunction - lead to false reading and indication and can lead to Explosion. Piping will crack Furnace will crack Explosion can happen if not following the SU and SD procedure.
Periodic Maintenance
HAZOP STUDY
Furnace/burner used to heat up using fuel oil + air Heating oil
PROCESS
Air line supply to the furnace
Section Date NODE
200
NO
PARAMETER
Guide Words
Deviation
MORE -
MORE - FLOW
LESS -
LESS - FLOW
NO -
NO - FLOW
VALVE
Valve malfuction
FLOW
OTHERS THAN
MAINTENANCE SHUT DOWN & START UP
Not follow Procedure
HAZOP STUDY
er used to heat up using fuel oil + air Heating oil to 250 C to supply to Distillation re boiler Air line supply to the furnace
posssible causes
possible consequences
the valve or control valve malfuction
air to fuel ratio not as per FT 2 stoikiometric, high presure in the furnace more gas rushing out to atm,
piping leaking
piping leaking pump/compressor failure Piping blockage/valve malfuction
un-edequate maintenance air supply to actuator block controller malfuction cost cutting
Human Factor
Safe Guard/Protection
PT 1, PI 4 & PI 5 PIC 1
air to fuel ratio not as per stoikiometric, more fuel coming out from the stack FT 2 & PI 2 can cause detonation/explosion more fuel gas in the furnace can cause explosion
more flow or no flow of air to furnace equipment malfuction and error can occurred may lead to explosion Explosion can happen if not following the SU and SD procedure.
FT 2 & PI 2
llation re boiler
action required/Recommendation
Air Flow Alarm Low and automatic shut down the fuel supply or heater on low air flow and/or low air/fuel ratio.
Periodic Piping inspection, Risk based inspection (RBI)
Air Flow Alarm Low and automatic shut down the fuel supply or heater on low air flow and/or low air/fuel ratio.
HAZOP STUDY
Furnace/burner used to heat up using fuel oil + air Heating
PROCESS
Fuel gas line supply to Furnace
section date study node
300
NO
PARAMETER
Guide Words
Deviation
1
PRESSURE
MORE -
MORE - PRESSURE
LESS -
LESS - PRESSURE
NO -
NO -PRESSURE
3
TEMPERATURE
MORE -
MORE - TEMPERATURE
4
FLOW
REVERSE -
REVERSE - FLOW
MORE -
MORE - FLOW
LESS NO -
LESS - FLOW NO - FLOW
VALVE
Valve malfuction
OTHERS THAN
MAINTENANCE SHUT DOWN & START UP
Not follow Procedure
HAZOP STUDY
sed to heat up using fuel oil + air Heating oil to 250 C to supply to Distillation re boiler Fuel gas line supply to Furnace
posssible causes
possible consequences
Fuel gas control valve malfunction
more fuel in the furnace, can cause explosion during start-up
piping leaking valve malfuction valve malfuction piping leaking external heating cause the gas expanded
more air in the furnace, no enough heat to heat up hot oil to desired temperature.
explosion when enter furnace.
Safe Guard/Protectio n PI 3 & PI 6
PI 3 & PI 6
TI 11
FI 3 Fuel gas control valve malfunction - fully open
piping leaking valve malfuction
more fuel in the furnace, can cause explosion more air in the furnace, no enough heat to heat up hot oil to desired temperature.
un-edequate maintenance air supply to actuator block
more flow or no flow to furnace
controller malfuction cost cutting Human Factor
equipment malfuction and error can occurred may lead to explosion Explosion can happen if not following the SU and SD procedure.
FI 3
tillation re boiler
Action required/Recommendation Fuel Pressure Alarm High and automatic shut down the fuel supply or heater on low air low air/fuel ratio or high fuel supply
Fuel Perssure Alarm Low and automatic shut down heater if Alarm Low Low triggered.
Automatic shut down fuel gas supply and heater
Fuel control valve - Fail close Fuel Flow Alarm High and automatic shut down the fuel supply or heater on low air low air/fuel ratio or high fuel supply
Fuel Flow Alarm Low
HAZOP STUDY
Furnace/burner used to heat up using fuel oil + air Heati
PROCESS
Heating oil piping/tubing going to fur
section date
400
study node
NO
PARAMETER PRESSURE
Guide Words
Deviation
MORE -
MORE - PRESSURE
LESS -
LESS - PRESSURE
NO -
NO -PRESSURE
MORE -
MORE - TEMPERATURE
LESS -
LESS - TEMPERATURE
1
TEMPERATURE
2
3
UN-EVEN TEMP
4 COMPOSITION 5
OTHERS THEN -
OTHERS THEN - COMPOSITION
FLOW
LESS -
LESS - FLOW
NO -
NO - FLOW
VALVE
Valve malfuction
OTHERS THAN
MAINTENANCE
SHUT DOWN & START UP
Not follow Procedure
HAZOP STUDY
p using fuel oil + air Heating oil to 250 C to supply to Distillation re boiler
oil piping/tubing going to furnace and out from furnace
posssible causes
possible consequences
HC from reboiler leaking into heating oil tube
Possible fie inside the tube and lead to explosion of tube and burst
piping leaking - in the furnace
Safe Guard/Protection
heating oil burn in furnace - black smoke , less heating oil to reboiler - column flooding with HC
high combustion in furnace - distillation column high pressure and TI 1 ~ TI 10 (exclude TI 8) more fuel and air can cause explosion.
Low combustion in furnace column flooding with liquid HC
TI 1 ~ TI 10 (exclude TI 8)
coking in the tubing
piping craking and less flow to reboiler
TI 1 ~ TI 10 (exclude TI 8)
HC leaking to the heating oil, Reboiler crack, or tube cracking
Possible fire inside the tube and lead to explosion of tube and burst
High moisture content
tube hammmering
piping leaking to furnace
heating oil burn in furnace - black smoke ,
coking in tubing
column flooding with liquid HC
piping leaking
pump failure
-
FT 1
column flooding with liquid HC
Piping blockage/valve malfuction
un-edequate maintenance air supply to actuator block
-
more flow or no flow of to furnace, no heating reboiler
controller malfuction cost cutting
equipment malfuction and error can occurred may lead to explosion
Human Factor
Explosion can happen if not following the SU and SD procedure.
Action required/Recom mendation Indication of pressure at tube Indication of pressure at tube Indication of pressure at tube
Temperature High Alarm and automatic shut down the heater if Temperature Alarm High High Temperature Alarm Low and automatic shut down the heater if Temperature Alarm Low Low Temperature Alarm Low and automatic shut down the heater if Temperature Alarm Low Low Indication of composition at tube
Vaporiser instalation at heating oil prior to inlet to furnace Indication of flow at exit stream of furnace Online decoking peridically Indication of flow at exit stream of furnace Standby pump, automatically cut in if another fail to function Online decoking peridically
View more...
Comments